Frame structure: Extruded profile Al. anodized with thermal break. Panels: Double skin panels 48 mm thick +- 2 puff.
Inner skin: 20G GI plain and Outer skin: 24G GI pre-coated Skid: GI epoxy coated
Drain pan: 1.2 mm thick SS304 with 25mm Nitrile rubber sandwiched. Provide 40 mm SS threaded drain nipple. Dampers: Al.
anodized low leakage aerofoil.Shaft to accept motorized actuators.
Filter section: With MERV-13 filters, Prefilter ,access doors filters in extruded al. box type frames with gasket arrangements
around filter frames. This should include one set of commissioning filters.
Coil Section: Cu coils with hydrophilic coated al. fins,8 Row coil
Fan section: Plug Fans with access doors on both sides, inspection windows, limit switch to shut off fan on door opening.
Flexible connectors: Non flammable, weather and fungus proof
Vibration Isolators: For fans and mounting arrangements - Rust resistant spring
Drive: EFF-1 motor with Starter Panel & cabling, wireless remote, Non Polarised NO-NC contacts for tripping on signal from Fire
Dampers/Fire Alarm Panel with all required accessories should also be included in the quoted Price.
The maximum face velocity shall be 2.5 m/s. The port for manometers shall also be provided to monitor the pressure drop
individually across the pre-filter for each TFAU. The filter section shall be so arranged that they can be easily removed for
cleaning. Heavy duct flexible double layer canvas connection shall be provided at the outlet of TFAU Fan. The minimum external
fan static shall be as per technical specifications.
TFAU's should be suitable for Fan velocity not exceeding 1800 FPM, coil Face Velocity not exceeding 500 FPM and Fan RPM not
exceeding 1000 RPM. TFAUs with suitable VFD & bypass facility with separate starter panel. Fan efficiency > 70% &
complete as per specifications & drawings. TFAU's should be suitable for Multikit
connection with VRF Units.
1.8.1 3750 CFM/25 TR - 55mm wg Total static pressure ( GF ) Nos 1 INR 1,47,212.64 INR 8,832.76 INR 1,56,045.40
1.8.3 3750 CFM/25 TR - 55mm wg Total static pressure ( FF ) Nos 1 INR 1,47,212.64 INR 8,832.76 INR 1,56,045.40
Supply, installing, testing, commissioning & handing over of INLINE FRESH / EXHAUST Air Fan in accordance with and meeting
the intents & specifications & drawings complete with Fan with Drive Motors, Mild Steel Mounting Frame, Vibration Isolators,
Gravity louvers. (NOTE : SUBJECT TO ACTUAL STATIC PRESSURE
CALCULATION. ON SHOP DRAWINGS BY CONTRACTOR AND APPROVAL OF CONSULTANT)
1.9.1 1050 CFM / 20MM ESP - Exhaust Air Fan Nos 2 INR 12,517.10 INR 751.03 INR 26,536.25
1.9.2 750 CFM / 20MM ESP - Fresh Air Fan Nos 2 INR 11,985.37 INR 719.12 INR 25,408.98
1.9.3 650 CFM / 20MM ESP - Exhaust Air Fan Nos 2 INR 11,020.53 INR 661.23 INR 23,363.52
1.9.4 500 CFM / 20MM ESP - Fresh Air Fan Nos 2 INR 10,698.92 INR 641.94 INR 22,681.70
Copper Refrigerant Joint
2.0 Supply Of OEM make refrigerant joints Nos 52 INR 5,793.26 INR 347.60 INR 3,19,324.33
(Make : Mitsubishi Heavy / O General / Mitsubishi Electric)
2.7 Lifting, Shifting, Positioning, Installtion, Testing & Commissioning of VRF Outdoor. Also it should include first oil
& gas charge & commissioning etc. complete
2.7.4 16 HP Nos 1 INR 7,718.64 INR 463.12 INR 8,181.76
2.7.6 24 HP Nos 12 INR 7,718.64 INR 463.12 INR 98,181.14
Lifting, Shifting, Positioning, Installtion, Testing & Commissioning of Regular Cassette Units Indoor with accessaries like
2.8 required Cassette panel, support plate, , Threaded rods of 10mm Thk, Anchor fastner, nut bolts,
Washer & screws etc. ( Ground Floor )
2.8.1 2.0 TR Nos 5 INR 3,211.78 INR 192.71 INR 17,022.44
2.8.2 2.5 TR Nos 1 INR 3,211.78 INR 192.71 INR 3,404.49
2.8.3 3.2 TR Nos 5 INR 3,211.78 INR 192.71 INR 17,022.44
2.8.4 4.0 TR Nos 4 INR 3,211.78 INR 192.71 INR 13,617.96
Lifting, Shifting, Positioning, Installtion, Testing & Commissioning of Regular Cassette Units Indoor with accessaries like
2.9 required Cassette panel, support plate, , Threaded rods of 10mm Thk, Anchor fastner, nut bolts,
Washer & screws etc. ( First Floor )
2.9.1 1.6 TR Nos 3 INR 3,211.78 INR 192.71 INR 10,213.47
2.9.2 2.0 TR Nos 3 INR 3,211.78 INR 192.71 INR 10,213.47
2.9.3 2.5 TR Nos 1 INR 3,211.78 INR 192.71 INR 3,404.49
2.9.4 3.2 TR Nos 4 INR 3,211.78 INR 192.71 INR 13,617.96
2.9.5 4.0 TR Nos 8 INR 3,211.78 INR 192.71 INR 27,235.91
Lifting, Shifting, Positioning, Installtion, Testing & Commissioning of High Static Duct Type Units Indoor with accessaries like
3.2 required support plate,Threaded rods of 10mm Thk, Anchor fastner, nut bolts, Washer & screws
etc.
3.2.1 5.5 TR Nos 2 INR 3,211.78 INR 192.71 INR 6,808.98
3.2.2 8.1 TR Nos 1 INR 3,211.78 INR 192.71 INR 3,404.49
Lifting, Shifting, Assembling, Positioning, Installtion, Testing & Commissioning of Treated Fresh Air Type Units Indoor with
3.3 accessaries like required support plate,Threaded rods of 10mm Thk, Anchor fastner, nut bolts,
Washer & screws etc.
3.3.1 3750 CFM/25 TR - 55mm wg Total static pressure ( GF ) Nos 1 INR 917.61 INR 55.06 INR 972.67
3.3.2 3750 CFM/25 TR - 55mm wg Total static pressure ( FF ) Nos 1 INR 917.61 INR 55.06 INR 972.67
Lifting, Shifting, Assembling, Positioning, Installtion, Testing & Commissioning of Vetilation Fans with accessaries
3.4
like required support plate,Threaded rods of 10mm Thk, Anchor fastner, nut bolts, Washer & screws etc.
3.4.1 1050 CFM / 20MM ESP - Exhaust Air Fan Nos 2 INR 917.61 INR 55.06 INR 1,945.34
3.4.2 750 CFM / 20MM ESP - Fresh Air Fan Nos 2 INR 917.61 INR 55.06 INR 1,945.34
3.4.3 650 CFM / 20MM ESP - Exhaust Air Fan Nos 2 INR 917.61 INR 55.06 INR 1,945.34
3.4.4 500 CFM / 20MM ESP - Fresh Air Fan Nos 2 INR 917.61 INR 55.06 INR 1,945.34
Lifting, Shifting,Positioning, Installtion, Testing & Commissioning of Copper refrigerant joints with accessaries
3.5 Nos. 52 INR 91.71 INR 5.50 INR 5,055.24
like required support plate,Threaded rods of 10mm Thk, Anchor fastner, nut bolts, Washer & screws etc.
Lifting, Shifting,Positioning, Installtion, Testing & Commissioning of TFA Connection Kit with accessaries like required
3.6 support plate,Threaded rods of 10mm Thk, Anchor fastner, nut bolts, Washer & screws, cable Nos. 2 INR 917.61 INR 55.06 INR 1,945.34
termination with lugs, copper connection to kit etc.
3.7 Lifting, Shifting,Positioning, Installtion, Testing & Commissioning of Cordless Remote with baseplate, nut bolts, Nos. 34 INR 42.83 INR 2.57 INR 1,543.53
Washer & screws etc.
3.8 Lifting, Shifting,Positioning, Installtion, Testing & Commissioning of Corded Remote with cable termination with Nos. 3 INR 42.83 INR 2.57 INR 136.19
lugs, baseplate, nut bolts, Washer & screws etc.
3.9 Lifting, Shifting,Positioning, Installtion, Testing & Commissioning of Central Remote with cable termination with Nos. 1 INR 1,376.45 INR 82.59 INR 1,459.03
lugs, baseplate, nut bolts, Washer & screws etc.
4.0 Lifting, Shifting,Positioning, Installtion, Testing & Commissioning of TFA Starter Pane with cable termination with Nos. 2 INR 458.78 INR 27.53 INR 972.61
lugs,nut bolts, Washer & screws etc.
4.8 SITC of Fire retardant canvass connection Nos 2.00 INR 1,146.60 INR 68.80 INR 2,430.80