Nebula WTP
Nebula WTP
BASIC ENGINEERING
Document Number
P90-UL73-01-001
Sources:
DM Water:
Considering regeneration, future load we need 4 m3/h capacity of DM plant but for auto
regeneration may have 3m3/h and 5m3/h model hence we are going for higher size while selection
of DM plant 5 m3/h.
Quantity Frequency
Product Tag Operation
(Lit/day) per day
Boiler 71B1.G Feed water for steam generation 48,000 Once a day
Note: Considering 40% condensate recovery we need to add 60% fresh water and future load we
have selected 3 m3/h softener plant.
2.0 PHILOSOPHY
Raw water:
MIDC water is collected in UG storage tank and then passed through sand filter (20 m3/h)
and transferred in overhead terrace RCC (20 KL) storage tank.
This raw water is further treated in WTP to generate Soft Water and DM water
User Points:
• Fire Hydrant and Sprinkler
• Safety Shower
• Eye washer
• Wash Basin
RO Water
RO water is collected in 100 KL UG RCC storage tank in ETP area from this will be
transferred in 20 KL overhead RCC tank at plant building.
Specific user points are connected from this RO tank
Pump will be installed at underground RCC RO permeate tank which will work on the level
of 20 KL RCC overhead storage tank
User points:
Cooling Tower
Boiler
HCL Scrubber
Chiller
ETP
Toilets
Floor Washing
Gardening
Soft water:
Boiler
DM water:
Process
Reactor washing
Soft Water:
Soft water produced by treatment of raw water through softener plant.
Treated water from softener is transferred to boiler feed water tank.
Total hardness for soft water at battery limit of system will be less than 5 PPM.
MGF and ACF will be backwashed once in day.
Regeneration of softener will be done after 80m3 water treatment with NaCl solution.
Effluent generated after regeneration will be sent to effluent treatment plant.
NaCl solution will be prepared in 225 litres P.V.C. tank for regeneration.
Condensate polishing softener will be installed for polishing of condensate return from
plant.
Condensate from plant will be stored in SS304 tank then passed through MS softener for
polishing before adding to boiler feed water tank
DM Water:
Refer attached P&ID.
Soft water:
Mechanical:
Construction:
Multigrade sand filter:
FRP Vessel with Multi grade sand Filtering Media and internal Distribution System.
This is considered for removal of suspended solids and turbidity in the water. This is to
safeguard the downstream equipment’s such as micron filters, other polishing systems
and UV. Chlorinated water helps sand filter less prone for microbial growth. Sand filter
will remove macro level particles.
Degasser Tower:
FRP tower with HDPE tank and blower.
Feed water from Cation column to Degasser tower to remove the Carbon Dioxide. Water
containing Bicarbonates when passed through the Cation Exchanger is converted to
Carbonic Acid. The Carbonic Acid easily breaks into Water and Carbon Dioxide.
Degasser helps remove the Carbon Dioxide from the water which otherwise gets into the
Anion exchanger and loads the exchanger. The Carbon Dioxide is considerable and the
quantity of the resins increases and hence the capital cost and also the recurring cost of
the Alkali for regeneration.
Mix Bed:
Polisher unit bed, FRP vessel, internals, and pipe work.
Mixed bed resins use SAC and SBA resins combined together
Mix bed unit, which polishes the water further for obtaining water of desired quality and
for pH correction. The treated water is collected in a DM water tank.
Softener bed:
FRP Vessel Charge of INDION 225 Na resin Filtering Media and internal Distribution
System.
Polishing Softener:
Raw Water has Salts of Calcium (Ca++) and Magnesium (Mg++). It imparts hardness to
water eventually leads to formation of scales. These compounds forms deposit and scale
on applied area and reduces process efficiency at great extent. Softener converts
Hardness imparting salts into Sodium salts and removes raw water hardness thus
improves water potential and its usability. The softener comprises of strongly acidic
cation exchanger resin in Sodium form (Na+). It exchanges the sodium ions for the
Piping:
DM Water:
All interconnecting piping of DM unit is of PVC piping.
Pump suction and discharge pipes and pipe fittings will be SS316 for process water from
storage tank to plant.
Pipe sizes will be sized from detail engineering.
Feed water piping is of SS304 for DM plant from overhead raw water RCC storage tank.
Soft water:
Two Y strainer CS body with 40 mesh, SS304 filtering element will be used in the suction
of the feed pumps to filter any contaminants. One filter will be in line while the other will
be a standby filter.
Set of UPVC frontal Pipe work with side mounted Multi-port valves
All interconnecting piping of UPVC.
All piping apart from softener plant will be of MS.
Valve:
DM Water:
DM unit is operated by hydro pneumatic valves made of engineering thermoplastics
along with PVC piping.
Manually operated Ball valves with SS316 body and neoprene seat will be used for
process water.
The above valves are either DOPC (Diaphragm operated pressure to close) or DOPO
(Diaphragm operated pressure to open) depending on the stages of operation and
application.
Three-way solenoid valves are used for operating the pipe line valves in the sequence
required during the regeneration cycle.
Soft water:
All valves of MGF, ACF and softener will be of multiport UPVC.
CS Ball valve will be used after softener plant and feed water line.
Gaskets:
All gaskets used in process water plant line will be PTFE.
All gasket used in DM plant interconnecting piping will be of rubber.
All gasket should be of rubber for all interconnecting piping and for treated water is of
non-asbestos (Champion) for soft water.
Utility:
MIDC water for DM & Softener Plant and steam condensate for polishing softener.
RO permeate water for polishing softener
Civil:
It will be discussed in separate concept notes
NPT/SOP/PBE/005/F01 Rev No. 00 Effective date: 15/11/2017 Page 7 of 11
Project NEBULA
Electrical:
The system will be considered under non-flameproof area.
The motors used will be of IE3 class for all the running equipment.
It will have proper lighting arrangement for proper illumination in night.
All running equipment’s will have local emergency stop button with protection.
All the equipment and structure will have double earthing.
Further more details will be included in concept notes of electrical.
Instrumentation:
DM Water:
Overhead RCC tank will have level switches interlocked with Auto DM feed pump.
Conductivity sensor will be installed at the outlet of the anion unit.
Programmable Logic Controller is designed to operate a bank of solenoid valves in the
regeneration sequence, which in turn operates the piping valves
Pressure transmitter installed at outlet of DM Plant having interlock with feed water
pump.
Additionally, the instrument panel has Resistivity meter, which can be set to the desired
valves. Flow meter/totalizer, Push button for manual initiation
unit is provided with a Flow meter / Flow totalizer at outlet of DM plant.
Interlocks are provided in the panel of level switch of various tanks viz. feed water tank,
DM tank, Acid/ Alkali tanks.
Pressure gauge will be installed at discharge of pump and inlet piping of each column
Pressure gauge will be installed at candle filter (5 micron).
Level transmitter will be installed at storage tank having interlock with feed water pump
Soft Water:
Pressure gauge will be installed at discharge of pump and inlet piping of each column
Level transmitter will be installed at boiler feed water tank having interlock with feed
water pump
Pressure gauge to monitor the pressure drop across each column.
Polishing softener:
Pressure gauge will be installed at discharge of pump and inlet piping of column
Level switch (Normal float type) will be installed at condensate collection tank having
interlock with polishing softener feed water pump
Safety:
DM Water:
System will have following safety interlock
Feed tank will have level switches interlocked with Auto DM feed pump.
Pressure transmitter installed at outlet of DM Plant having interlock with feed water
pump.
Audible alarm with panel reading low level for Low level in feed tank, DM tank, Acid /
Alkali tanks.
audible alarm and also display NO AIR SUPPLY in case pneumatic air supplies to the
auto valves are not adequate or air supply has stopped
Soft Water:
The feed tank will have level switches interlocked with feed water pump.
3.0 SIZING
DM Plant:
Softener Plant:
4.0 LAYOUT
DM plant: -
Softener plant: -