Professional Documents
Culture Documents
CW_MAXIGARD_DIESEL_LIQUIDEWT_LS
CW_MAXIGARD_DIESEL_LIQUIDEWT_LS
CW_MAXIGARD_DIESEL_LIQUIDEWT_LS
ENGINE TYPE: MAIN: ________________ AUX:_______________ WATER SOURCE: DISTILLED: _______________ OTHER: ______________________
SYSTEMS/
WATER CAPACITY
ppm Month/Date
Product CWT Titret1
48,000 4.0
42,000 3.5
36,000 3.0
MAXIGARD 30,000 2.5
treatment
Satisfactory 24,000 2.0
22,000 1.8
19,000 1.6
18,000 1.5
17,000 1.4
16,000 1.3
22,000 2.5
17,000 2.0
15,000 1.8
14,000 1.6
LIQUIDEWT 13,000 1.5
treatment
Satisfactory 12,000 1.4
11,000 1.3
10,000 1.2
9,000 1.1
8,000 1.0
Chemical
Dosage
Makeup Water
Hardness
(makeup water) ppm
Chloride
(system water) ppm
Comments:
*If readings are below 12,000 (scale unit 1.0), use 10.0 ltr/ton and retest. If *If readings are below 8,000 (scale unit 1.0), use 5.0 ltr/ton and retest. If system
system has been partially drained and refilled, use initial dosage. has been partially drained and refilled, use initial dosage.
The use of high quality distilled makeup water is recommended as the best means of
controlling scale formation.
Parameter Limit
*If any parameter is higher than the maximum, use better quality water.
Procedure
1. Add one scoop (0.5 gm) Sample Pretreatment to approximately 70 ml cooling water and
stir well.
2. Let stand for two (2) minutes to allow precipitate to settle.
3. Filter the sample and proceed with the chloride determination using the Chloride LMP
Test Kit.
MAXIGARD_DIESEL_LIQUIDEWT_LS