FSSS (Furnace Safeguard Supervisory System)


A fully digital control system which governs mandatory requirements related to safe startup and safe shutdown of the bo
Includes main boiler permissive and protections.
Includes heavy oil and light oil firing interlocks.
Includes permissive & protections related to mills and feeders.

FSSS LOGIC SYSTEM

Furnace Safeguard Supervisory System (also named Burner Management System; BMS).
Satisfactory Boiler start up.
Startup of individual oil system AB/CD/EF.
Operation of fuel firing subject to certain conditions A/B/C/D/F.
Protection and interlock of oil /Coal System.

BOILER START- UP SEQUENCE

The boiler can be placed in service, initially or after a “Master Fuel Trip,” in the following sequence through FSSS.

Furnace Purge:- Before any fuel firing can takes place, initially or following a boiler trip, a satisfactory “Purge Cycle” must b
Initially, the Heavy Oil must be recirculated and heated to obtain the proper temperature and viscosity for efficient comb
is accomplished, the Heavy Oil Trip Valve (HOTV) can be closed and then the ‘furnace purge cycle’ can be started.
After the furnace purge cycle is completed, the heavy oil elevation (AB, CD, EF, & GH) can be taken into service. An oil ele
be “In Service,” when at least three out of four heavy oil nozzle valves are open and the flame is sensed by the scanners.
After the heavy oil elevation is ‘in service’, either of the adjacent coal elevation can be taken into service because “Ignitio
available for starting the pulverizer.
A Coal elevation is said to be “In Service” after the Pulverizer is ON, its Hot Air Gate (HAG) is open and the associated
(i.e., feeder ON for more than 50 seconds). A “fireball” signal is established when the associated fireball flame scanner s
“ELEVATION FLAME” indicator is illuminated on the FSSS console in control room.

UNIT START UP SEQUENCE

1. Boiler purge operation   


2. Startup of oil firing(AB,CD,FH & GH)
3. Adequate Ignition permit
POWER PLANT GYAN
4. Firing of coal elevation(A,B,C,D,E,F,G & H)
5. Flame sensingThis platform is created for sharing knowledge about power plant.
by scanners.

FSSS LOGIC

Privacy
FSSS logics can be broadly divided into 3 sections.
About
1. UnitUSLogic.
Contact
Privacy
2. OilPolicy
Elevation Logic.
3. Coal Elevation Logic
© 2024: POWER PLANT GYAN
UNIT LOGIC

1. Boiler purge logic


2. Master fuel trip logic
3. Oil trip valve operation logic
4. PA Fans logic
5. Scanner air Fans logic
6. Seal air Fan logic

FURNACE PURGE

Purpose: – Complete Removal of unburnt fuel/residues from entire furnace. Before every start or say restart, a furnace pur
be performed.

Furnace purging refers to the clearing of the entire flue gas path for any combustibles that are leftover in the furnace.
This clearing function is accomplished by ambient air.
This is a mandatory safety requirement before ignition of fuel and is an interlock in boiler startup.
When the boiler trips, the last bit of fuel that made entry in the furnace remains inside.
There is a gaseous mixture left in the furnace. When an attempt is made to re-ignite the furnace, there is a reaction
gases, which could possibly result in furnace explosion.
It applies during startup of the boiler, when there are sometimes multiple attempts required to start.
Purging is a requirement as warranted by the NFPA (National fire protection agency) norms.
The time required for purging is determined by the volume of the furnace and requires 5-7 cycles to displace the combus
boiler.

Procedure:-

Ensure that all fuel to furnace is cut off and all flame is out.
Provide adequate airflow through furnace (30 to 40%).
Initiate a MANDATORY purge time cycle (5, 8, or 10 minutes).
A 5 or 8 or 10 minutes mandatory cycles in which at least one set of FD fan & ID fan are running with 30 to 40 % air flow w
to the furnace, to ensure the removal of the un-burnt fuel left over in the furnace area after the last master fuel trip.

Consequence:-

Master Fuel Trip Relays are reset.


Firing of fuel into the furnace is allowed.

UNIT LOGIC
Boiler purge logic, which ensures a five minutes purge cycle is completed before any fuel firing can take place.
A “Purge Ready” signal at control room will be available when all the following conditions are satisfied:

Boiler Purge Logic


  
No MFT condition present / No boiler trip.
HOTV closed (HFO trip valve is closed)
LOTV closed POWER PLANT GYAN
This platform
All HFO Nozzle Valves is created
are closed forclosed)
(all HONV sharing knowledge about power plant.
All LO Nozzle Valves are closed (All LONV closed)
All Pulverizers are off
Privacy
All feeders are off
About
All scanners sensing no flame.
Contact US
BothPolicy
Privacy PA fans off
All HAGs closed
© 2024: POWER PLANT GYAN
Air flow more than 30% and less than 40%
All auxiliary air dampers modulating
Wind box to furnace DP is adequate.
MFT DPUS unfreeze

PURGE PERMISSIVE

MASTER FUEL TRIP (MFT)

MFT or Boiler Trip means:


Complete isolation of all fuel to furnace under certain conditions.

Automatic Procedure:
All oil valves are given closing command.
All mills and feeders are given trip command.
All Primary Air (PA) Fans are given trip command.
All Hot Air Gates (to mills) are given closing command.

Further Consequences:
Turbine protection is initiated (to trip turbine).
All SH and RH spray valves are given closing command.
All elevation SADC are given full open command.
Furnace pressure & Airflow controls are set to manual.

MASTER FUEL TRIP LOGIC

This ensures a safe shut down of the boiler in case of any abnormal conditions in boiler/ furnace.
If some abnormal condition occurs, Master Fuel Trip Relay acts and ensures the closure of Heavy Oil Trip valve (HOTV) a
  
Valves (ONV), thus cutting off total oil supply.
It also ensures the stopping of all pulverizer systems and Primary Air (PA) fans, cutting off total coal supply to boiler.
POWER PLANT GYAN
The various abnormal operating conditions under which Master Fuel Trip occurs are as follows:-
1. Both FD fans OFF
This platform is created for sharing knowledge about power plant.
2. Both ID fans OFF.
3. Inadequate water wall circulation for more than 5 seconds.
Privacy
4. Loss of Reheat Protection for greater than 10 seconds.
5.
About All BFPs tripped.
Contact US
6. Drum level very high for more than 10 seconds (2/3 logic)
Privacy Policy
7. Drum level very low for more than 10 seconds (2/3 logic)
8. Furnace pressure very high (2/3 logic)
© 2024: POWER PLANT GYAN
9. Furnace pressure very low (2/3 logic)
10. Loss of all fuel.
11. All feeders OFF and loss of AC Supply to the elevation in service.
12. Unit flame failure.
13. Loss of Unit Critical Power for more than 2 seconds
14. Both Secondary APHs OFF.
15. Loss of 220 V DC Supply for more than 2 seconds.
16. Air flow less than 30% and boiler load not greater than 30%.
17. Manual Emergency trip.

Unit Logic MFT consequences

Trips all mills.


Trips all feeders.
Trips PA fans.
Closes HFO trip valve.
Closes all elevation nozzle valves.
Close all HAGs.

OIL TRIP VALVE OPERATION LOGIC

This logic ensures that oil trip valve can be opened after the purge cycle is completed and no MFT condition is present
conditions are also satisfied.
All nozzle valves are closed.
HFO supply pressure is satisfactory.
HFO header temperature is satisfactory.
Similarly, this logic ensures the closure of oil trip valve in case of MFT.

SCANNER AIR FANS LOGIC

It monitors the scanner air duct to furnace DP and ensures starting of scanner air fan – A or in case it fails to start, sca
This logic gives an open command to scanner fan outlet damper after starting the fan.
Also, in case of both FD fans not running, it ensures the scanner air emergency damper is open.

SEAL AIR FANS LOGIC

Monitors seal air header to cold air duct DP and ensures the starting of seal air fan – A or B (in case A does not start),
one PA fan is running.
Gives an open command to seal air fan discharge damper once fan starts.

OIL ELEVATION LOGIC


Start of oil elevations AB, CD, EF and GH


Sequential operation with start command.  
Corner-1,corner-3,corner-2 and corner-4.
Gun advance, igniter advance.
POWER PLANT GYAN
Spark, atomizing valve open, oil valve open.
This platform
Sensing of discriminatory is created for sharing knowledge about power plant.
flame.
Retract of igniter.

Privacy
Stop of oil elevation
About
Closure of oil valve, opening of scavenge valve.
Contact US
Igniter
Privacy advance
Policy and sparking.
Closure of atomizing valve and scavenge valve.
© 2024: POWER PLANT GYAN
Retract of igniter and gun.

Oil Elevation Logic

There are four heavy oil elevations AB, CD, EF & GH.
For all these elevations, logics are same.
Oil elevation can be placed in service auto/manual.
For a particular elevation, only one command is given for all the four corners together. (E.g. One common start comma
AB-1, 2, 3 and 4 guns).
However, start command goes to corners 1 to 4 sequentially. First command goes to corner 1; after 15 seconds start co
corner 3; again after a lapse of 15 seconds start commend goes to corner 2; and again after a gap of 15 seconds start co
corner 4.
A particular corner takes the start command only if the following conditions are satisfied:-
The particular corner oil gun engaged feedback is available.
The steam scavenge valve is closed for the particular corner.

Sequence of operation

The sequence of operation taking place for a particular oil gun once the command is given is as follows:-

First, the oil gun is advanced.


Once gun advanced feedback is available the HEA igniter is advanced.
Then atomizing steam valve is opened for the particular corner.
Then HFO nozzle valve gets open command.
‘Spark’ command is given to igniter transformer, thus producing a spark at the spark tip.
Then for this particular corner ‘HFO flow satisfactory’ feedback comes from the flow switch in the oil line.
The corner oil gun proves when the DISCR FLAME SCANNER senses FLAME.
When 25 seconds elapses after oil valve open, igniter spark signal is removed and spark rod is retracted.
If the corner oil gun did not prove FLAME by this time, ‘Oil nozzle valve’ and atomizing steam valve closes. Gun and igniter

OIL FIRING PERMISSIVE-

Purge complete/MFT Reset and NO FIRST UP FAULT.


HFO Pr. Ok >25 ksc.
HFO Temp ok >95c
Ignitor air pr. >200 mmwg.
Ignitor oil pr. >10 ksc.
No light up in progress.
No burner start inhibit.
Permissive to fire oil.

OIL BURNER START LOGIC


  
Oil burner start push button (no other oil burner start in progress).

OIL BURNER START SEQUENCE


POWER PLANT GYAN
Oil burner sec. Air damper
This opened.
platform is created for sharing knowledge about power plant.
Open igniter oil master trip valve.
No flame sensed in last 5 sec.
Privacy
Energies igniter transformer.
Open
About igniter oil solenoid v/v.
Contact US
Detect ignition oil flame.
Privacy Policy
4 way v/v to firing position.
Oil flame detected. © 2024: POWER PLANT GYAN
Close IOTV/SOL V/V

COAL ELEVATION LOGIC


PULVERIZER START LOGIC

Availability of PA permit
Availability of ignition permit
Seal air /bowl differential pressure
No MFT
Lube oil pressure adequate
Pulverizer stop logic

FEEDER START LOGIC

Pulverizer on
Outlet temperature adequate
Speed demand minimum
No MFT
Feeder stop logic
Had/cad logic

PULVERISER LOGIC

This logic takes the count of total number of pulverisers in service at any point of time, the number of FD Fans & PA fans i
With PA Fan ‘ON’ and PA Header Pressure adequate (>560 mmwcl), it gives “PA permit” to start the Pulverizer.
In case of PA Header Pressure going low-low or PA/ FD fans trips, it ensures the shut down of Pulverizers from top elev
elevation in a timed sequence.
Each mill can be taken in to service manually or automatically.
Auto manual selection push button is available on FSSS console for each mill.
Initially, “Pulverizer Ignition Permit” signal must be established for the mill to start.
Other condition required to be established for starting the mill are as follows:-

MILL PERMISSIVE

Mill lub oil pressure adequate.


Start permit from FSSS.
Mill Discharge valve open.   
Mill outlet temp. > 93O(200OF)
Cold Air Gate (CAG) open.
POWER PLANT GYAN
Tramp iron vale (Top Reject Gate) open.
This platform is created for sharing knowledge about power plant.
Feeder inlet gate open.
Seal air DP adequate (200 mmwcl).
Feeder local switch in remote.
Privacy
About the mill is ON, associated HAG can be opened and feeder can be placed in service.
Once
Contact US
Privacy
OIL Policy
BURNER FIRING ON MILL BEING BROUGHT INTO SERVICE

For Any Mills (A,B,C,D,E,F,G,H) © 2024: POWER PLANT GYAN


1. At least three oil burners firing in selected elevation.
2. Boiler load > 30% BMCR & upper or lower adjacent coal burner in operation.

EXAMPLE:

For MILL-A START PERMISSIVE:

Elevation AB-3/4 oil burner firing.

OR

MILL-B firing.

AND

BOILER LOAD >30% BCMR.

FOR B, D, F MILLS

At least 3 OIL BURNERS firing in the burner group above

AND

Adjacent COAL BURNER above in operation

AND

This elevation is highest in the burner group

EXAMPLE

For MILL-B START PERMISSIVE

Elevation AB-3/4 OIL burner are in service

OR

MILL-A firing OR Mill-C Firing

AND

BOILER LOAD > 30% of BCMR

OR

MILL-C firing

AND

ELEVATION CD-3/4 oil burner are in service


  

POWER PLANT GYAN


Note that B-ELEVATION is highest in the burner group AB.

PARTIAL FLAME FAILURE


This platform is created for sharing knowledge about power plant.
It will never occur for the following condition-

Privacy
If three or more mills firing then partial flame failure will never exists.
If less
About than three mills are firing then partial flame failure does not exists if mill, which is firing, have the mill permissive for
Contact US
It will occur
Privacy Policy when this logic satisfy-

© 2024: POWER PLANT GYAN


VOTING OF ELEVATION

Voting in AB elevation will be available

Case-1

Mill A feeder OR mill B feeder is in service.

AND

Elevation AB 2 / 4 flames in.

Interlocked with (all burner in AB elevation satisfactory S/D or 3 / 4 oil burner in that elevation are is in service

Case-2

Voting in BC elevation will be available.

Mill B feeder or mill-C feeder is in service.

AND

Elevation B 2 / 4 flames in.

VOTING WIL NOT BE AVAILABLE –


(1) Both feeders on burner elevation are not is in service.
OR
(2) 2/4 flame are not sensed interlocked with 3 / 4 oil burner are not firing.
OR
(3) oil gun in that elevation not satisfactorily shutdown interlocked with 3 / 4 oil burner in that elevation not firing.

FEEDER START LOGIC


  
Feeder start command is given from FSSS Elevation Logic only. This command is continuously required to keep the fe
Feeder speed demand minimum, Pulverizer ON, pulverizer outlet temp > 130OF, HAG open and no MFT are the impo

POWER PLANT GYAN


required to give the feeder start command from FSSS.

This
In case of pulveriser platform
power high,isbowl
created for sharing
DP High knowledge
or feeder about feeder
OFF command, power speed
plant. demand is driven to minimum.

Privacy
About
Contact US
Privacy Policy

© 2024: POWER PLANT GYAN


Release feeder to Auto Signal is also coming from FSSS. All of the above conditions are present and feeder is not ON f
seconds, release signal for auto is available.

 POWER PLANT GYAN  November 24, 2023  BOE exam, boiler, burner management system, Central BOE, FSSS, fuel firing system

 BOE, BOILER, BOILER OPERATION ENGINEERING EXAM, Uncategorized  Comments Off

 
 How Flue Gas Exit Temperature Impacts Coal Mill Performance :Newer
 Older: MAHARASHTRA STATE BOILER OPERATION ENGINEER

POWER PLANTRelated
GYAN Posts
This platform is created for sharing knowledge about power plant.
Analysis of the statement on mill outlet How Flue Gas Exit Temperature Impacts MAHARASHTRA STA
temperature: Coal Mill Performance OPERATION ENGINEERIN
Points in favor of higher mill outlet temperature (up to The efficiency of a coal-fired power plant hinges on Maharashtra state boiler operatio
Privacy 100 – VM): Risks and optimal heat transfer throughout the system. 2013 objective question with sol
Paper-1 contain
About
Contact US
Privacy Policy
COMMENTS ARE CLOSED
© 2024: POWER PLANT GYAN
  

POWER PLANT GYAN


This platform is created for sharing knowledge about power plant.

Privacy
About
Contact US
Privacy Policy

© 2024: POWER PLANT GYAN

You might also like