AIR CIRCUIT BREAKERS

Safety and protection


in all applications

Motors | Automation | Energy | Transmission & Distribution | Coatings


Air Circuit Breakers

Summary
Presentation 04

Benefits 05

Overview of the Line 06

Operation System 07

Main Applications 08

Construction Characteristics 09

General Characteristics 10

Coding 12

Accessories 14

Dimensions 35

Installation Recommendations 49

Curves 50

Wiring Diagram 52
www.weg.net

SAFETY AND PROTECTION


IN ALL APPLICATIONS

Weg line of air circuit breakers is used to protect electrical circuits against overloads and short
circuits, with microprocessed electronic protection. Developed for the industry, it integrates
technology and quality to improve the performance and safety of your applications. The circuit breaker has
a "stored-energy" operating mechanism with pre-charged springs. Those springs are manually charged
with the front lever or electrically charged with a motor, supplied as an accessory.

Offering a variety of accessories assembled at the factory, WEG air circuit breakers are the ideal solution
for different applications, including critical industries such as mining, oil and gas.

4 Air Circuit Breakers


www.weg.net

Benefits
Microprocessed electronic
protection unit

Complete accessory line Standard LSIG protection

Earth leakage protection


(optional)

Network communication Suitable for different applications

Accessories assembled at the


Wide range of current setting
factory

Air Circuit Breakers 5


www.weg.net

Overview of the Line


Designed to protect low voltage electrical circuits, the circuit breakers are available in 5 frames and currents from 800 A to
6,300 A.

ABW800/ABW1600 ABW4000/ABW5000
In 800~1,600 A In 4,000~5,000 A
Icu = 65 kA @ 380 V Icu = 100 kA @ 380 V
Ics = 100% Icu Ics = 100% Icu

ABWC800/ABWC1600
In 800~1,600 A
Icu = 50 kA @ 380 V
Ics = 100% Icu

ABW2000/ABW2500/
ABW3200 ABW6300
In 2,000~3,200 A In 6,300 A
Icu = 85 kA @ 380 V Icu = 120 kA @ 380 V
Ics = 100% Icu Ics = 100% Icu

g Ics = 100% Icu in the whole line

Ics = Icu @ 220 / 380 / 415 V Ics = Icu @ 440 / 480 / 500 V Ics = Icu @ 600 / 690 V
ABWC800/ABWC1600 50 kA ABWC800/ABWC1600 42 kA ABWC800/ABWC1600 42 kA
ABW800/ABW1600 65 kA ABW800/ABW1600 65 kA ABW800/ABW1600 50 kA
ABW2000/ABW2500/ABW3200 85 kA ABW2000/ABW2500/ABW3200 85 kA ABW2000/ABW2500/ABW3200 85 kA
ABW4000/ABW5000 100 kA ABW4000/ABW5000 100 kA ABW4000/ABW5000 85 kA
ABW6300 120 kA ABW6300 120 kA ABW6300 100 kA

g Available in two mounting versions

Fixed Withdrawable

6 Air Circuit Breakers


www.weg.net

Operation System
The circuit breakers operate by means of a spring system, Remote operation is also possible by means of the closing
which can be manually charged with a front lever or and opening coils installed inside the circuit breaker. The
electrically charged with a motor (supplied as an accessory). closing coil has anti-pumping circuit, which prevents multiple
breaker closures.
When the springs are charged (situation in which the charge
indicator displays CHARGED), the circuit breaker is able to be There is also a front indicator of the circuit breaker state: ON
locally operated with the ON and OFF buttons. or OFF.

OFF Button

ON Button Charging lever

Spring Charge
ON/OFF Indicator Indicator

Regarding the installation, the circuit breakers can be supplied as fixed-mounted or withdrawable; the second version is
recommended for applications in which the occasional replacement or maintenance should be done as quickly as possible.
These circuit breakers can be positioned at three distinct points in the withdrawable rack:

Inserted: in this position both the power and control circuits are connected.
The position indicator shows CONNECTED.

Test: position in which only the control circuits are connected. The indicator
shows TEST.
Position
indicator Withdrawn: both circuits are disconnected. The indicator shows
DISCONNECTED.

Air Circuit Breakers 7


www.weg.net

Main Applications

Mining Chemical and Oil

Steel and Metallurgy Pulp and Paper

Food & Beverage Plastic

Automotive Water

Textil Sugar & Ethanol

8 Air Circuit Breakers


www.weg.net

Construction Characteristics

Spring Loading Lever

Protection Unit Arc Extinction Chambers

Suspension Slots

OFF Button

ON Button

Operation Withdrawable
Counter Rack

Withdrawable Rail (withdrawable)


Status Indicator
ON / OFF

Position indicator – Inserted / Test /


Withdrawn (withdrawable)
Spring Charge Indicator -
Charged / Not Charged

Position Locked by Padlock


Technical Data (withdrawable)

Air Circuit Breakers 9


www.weg.net

General Characteristics
Circuit breaker ABWC08 ABWC16 ABW08 ABW16 ABW20 ABW25 ABW32 ABW40 ABW50 ABW63
Standard IEC 60947-2
Maximum rated current (40 °C) - In max. (A) 800 1,600 800 1,600 2,000 2,500 3,200 4,000 5,000 6,300
Current setting (0.4 ~1.0) x In max
Rated operational voltage - Ue (V) 690
Rated insulation voltage - Ui (V) 1,000
Impulse voltage - Uimp (kV) 12
Frequency (Hz) 50 / 60
Number of poles 3
Versions Fixed - withdrawable
Protection units LSIG Electronics
220 / 380 / 415 V 50 50 65 85 100 120
Rated ultimate short-circuit
440 / 480 / 500 V 42 42 65 85 100 120
breaking capacity - Icu (kA)
600 / 690 V 42 42 50 85 85 100
220 / 380 / 415 V 50 50 65 85 100 120
Rated service short-circuit
440 / 480 / 500 V 42 42 65 85 100 120
breaking capacity - Ics (kA)
600 / 690 V 42 42 50 85 85 100
1s 42 50 85 85 100
Rated short-time withstand current -
2s - 42 75 75 90
Icw (kA)
3s 25 36 65 65 85
220 / 380 / 415 V 143 187 220 264
Rated making capacity - Icm
440 / 480 / 500 V 88.2 143 187 220 264
(kA peak)
600 / 690 V 105 187 187 220
Utilization categories B
Opening (max.) 40
Operating time (ms)
Closing (max.) 80
Mechanical lifespan (number of Without maintenance 20,000 15,000 10,000 10,000
12,500
operations) With maintenance1) 30,000 20,000 15,000 15,000
Electrical lifespan (number of Without maintenance 5,000 5,000 2,000 2,000
6,000
operations) With maintenance1) 10,000 10,000 5,000 5,000
Altitude (m) ≤2,0002)
Operation -5...40 °C3)
Ambient temperature
Storage -20...60 °C
Withdrawable 38 61 85 143 184
Weight (kg)4)
Fixed 16 32 42 74 101
Connection terminals - Horizontal Standard Standard Standard Standard Standard
withdrawable/fixed Vertical Optional Optional Optional Optional Optional
Withdrawable 364 x 272 x 269 430 x 334 x 375 430 x 412 x 375 430 x 629 x 375 430 x 785 x 375
External dimensions H x W x D (mm)
Fixed 322 x 272 x 198 300 x 300 x 295 300 x 378 x 295 300 x 597 x 295 300 x 751 x 295

Notes: 1) According to the maintenance routines indicated in the manual.


2) For installation above 2,000 m from sea level, please consider the voltage and current derating factors, as shown in the chart below.
3) For ambient temperature above 40 °C, check maximum rated current values in the chart below.
4) It may vary according to the configuration of optional accessories.

10 Air Circuit Breakers


www.weg.net

General Characteristics
Tightening torque
Screw Torque (kgf.cm) Tolerance Torque (N.m) Tolerance
Tightening torque of the
busbars at the rear M8 135 ±16 13.3 ±1.6
terminals for all M10 270 ±32 26.5 ±3.2
circuit breaker models
M12 480 ±57 46.6 ±5.6

Ratio-Corrector Factor
Altitude - h Rated operational voltage (V) Insulation voltage (V) Rated current reduction factor
h ≤2,000 m 690 1,000 1.00
2,000 < h ≤3,000 m 590 900 0.99
3,000 < h ≤4,000 m 520 700 0.96
4,000 < h ≤5,000 m 460 600 0.94

Horizontal position terminal - Temperature (°C) x Current (A)


Ambient temperature ABWC08 ABWC16 ABW08 ABW16 ABW20 ABW25 ABW32 ABW40 ABW50 ABW63
40 °C 800 1,600 800 1,600 2,000 2,500 3,200 4,000 5,000 6,300
45 °C 800 1,600 800 1,600 2,000 2,500 3,200 4,000 5,000 6,300
50 °C 800 1,600 800 1,520 2,000 2,500 3,100 3,920 4,900 6,170
55 °C 800 1,550 800 1,480 2,000 2,400 3,000 3,860 4,800 6,040
60 °C 800 1,500 800 1,420 2,000 2,300 2,900 3,800 4,700 5,900
65 °C 800 1,450 800 1,240 1,900 2,220 2,600 3,650 4,000 5,020
70 °C 800 1,390 800 1,180 1,800 2,140 2,460 3,500 3,800 4,780

Vertical position terminal - Temperature (°C) x Current (A)


Ambient temperature ABWC08 ABWC16 ABW08 ABW16 ABW20 ABW25 ABW32 ABW40 ABW50 ABW63
40 °C 800 1,600 800 1,600 2,000 2,500 3,200 4,000 5,000 6,300
45 °C 800 1,600 800 1,600 2,000 2,500 3,200 4,000 5,000 6,300
50 °C 800 1,600 800 1,580 2,000 2,500 3,120 3,960 4,950 6,220
55 °C 800 1,600 800 1,550 2,000 2,500 3,050 3,900 4,900 6,160
60 °C 800 1,600 800 1,500 2,000 2,400 2,950 3,880 4,850 6,100
65 °C 800 1,550 800 1,320 2,000 2,320 2,650 3,750 4,150 5,220
70 °C 800 1,500 800 1,260 2,000 2,240 2,530 3,620 3,950 4,980

Internal Resistance and Dissipated Power1)


Fixed version Withdrawable version
Circuit Rated Internal Dissipated Internal Dissipated
breaker current (A) resistance power resistance power
(mΩ) (W/3 fases) (mΩ) (W/3 fases)
ABWC08 800 0.02 38 0.035 67
ABWC16 1,600 0.02 154 0.035 269
ABW08 800 0.02 38 0.04 77
ABW16 1,600 0.02 154 0.04 307
ABW20 2,000 0.013 156 0.027 324
ABW32 3,200 0.01 307 0.02 614
ABW40 4,000 0.008 384 0.011 528
ABW50 5,000 0.008 600 0.011 825
ABW63 6,300 0.005 595 0.007 833

Note: 1) Power factor 1.

Air Circuit Breakers 11


www.weg.net

Coding

ABW 16 DN 3 - 16 AZ1 F - A 0 2 2 0
Maximum current Accessories
08 800 A No accessories
16 1,600 A B ON/OFF button lock
20 2,000 A K Key lock
25 2,500 A Phase sequence K2 Key interlock
32 3,200 A Mechanical interlock for 2 circuit
DN p/ 1,600 A - RST (N) M breakers1)
40 4,000 A ES p/ 2,000~3,200 A - RST (N) Mechanical interlock for 3 circuit
M3
50 5,000 A FS p/ 4,000~5,000 A - RST (N) breakers1)
63 6,300 A GS p/ 6,300 A - RST (N) D Door interlock
BK B+K
Number of poles B2 B+K2
Rated current 3 3P BM B+M
08 800 A BD B+D
16 1,600 A KM K+M
20 2,000 A KD K+D
25 2,500 A CP Profibus communication
Version Standard auxiliary contacts
32 3,200 A CM Modbus communication
F Fixed A 5NO+5NC
40 4,000 A
E Withdrawable Optional (withdrawable version)
50 5,000 A Undervoltage release
B Position auxiliary contact
63 6,300 A Standard
0 No release
Protection unit Optional
Standard unit 1 100~130 V ac/dc
LSIG + current - electronics power supply 100~250 V ac/dc and measurement frequency 2 200~250 V ac/dc
AZ1
60 Hz 3 24~30 V dc
Optional units 4 48~60 V ac/dc
000 No protection unit 5 380~480 V ac
LSIG + current - electronics power supply 100~250 V ac/dc and measurement frequency 6 200~250 V ac/dc with delay
AZ6
50 Hz 7 100~130 V ac/dc with delay
LSIG + current - electronics power supply 24~60 V dc and measurement frequency 8 48~60 V ac/dc with delay
AZ2
60 Hz LSI 9 380~480 V ac with delay
AZ7 LSIG + current - electronics power supply 24~60 V dc and measurement frequency 50 Hz
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and Standard opening coil
AF1
measurement frequency 60 Hz 2 200~250 V ac/dc
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and Optional
AF6
measurement frequency 50 Hz 0 No release
LSI + earth leakage + current - electronics power supply 24~60 V dc and measurement 1 100~130 V ac/dc
AF2
frequency 60 Hz 3 24~30 V dc
LSI + earth leakage + current - electronics power supply 24~60 V dc and measurement 4 48~60 V ac/dc
AF7 Motorized operator
frequency 50 Hz
Standard 5 380~480 V ac
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and
AC1 0 No motor operator
measurement frequency 60 Hz Standard closing coil
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and Optional
AC6 2 200~250 V ac/dc
measurement frequency 50 Hz 1 100~130 V ac/dc Optional
LSIG + current + communication2) - electronics power supply 24~60 V dc and 2 200~250 V ac/dc
AC2 0 No release
measurement frequency 60 Hz
3 24~30 V dc 1 100~130 V ac/dc
LSIG + current + communication2) - electronics power supply 24~60 V dc and
AC7 4 48~60 V ac/dc 3 24~30 V dc
measurement frequency 50 Hz
5 380 V ac 4 48~60 V ac/dc
LSIG + voltage + current + communication2) - electronics power supply
PC1 6 480 V ac 5 380~480 V dc
100~250 V ac/dc and measurement frequency 60 Hz
LSIG + voltage + current + communication2) - electronics power supply
PC6 Accessories supplied as standard for the entire range
100~250 V ac/dc and measurement frequency 50 Hz
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc and Auxiliary contacts (5NO+5NC)
PC2
measurement frequency 60 Hz
Alarm contacts
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc and
PC7 Opening coil 200~250 V ac/dc
measurement frequency 50 Hz
Closing coil 200~250 V ac/dc
Accessories supplied as optional items Operation counter
Motorized operator Door frame Position locking with padlock (padlock not included) - withdrawable version
Undervoltage release Transparent cover Position indicator (Inserted /Test/ Withdrawn) - withdrawable version
Condenser trip device Mechanical interlock
Key lock Door interlock
Key interlock Position auxiliary contact

Notes: 1) 2 circuit breakers are already considered for mechanical interlock M.


3 circuit breakers are already considered for mechanical interlock M3.
2) For communication via Profibus network, it is necessary to use the ABW-CP accessory.
For communication via Modbus network, see the Communication section of this catalog.

12 Air Circuit Breakers


www.weg.net

Coding

ABWC 16 DN 3 - 16 AZ1 F - C 0 2 2 0
Accessories
No accessories
Maximum current B ON/OFF button lock
08 800 A Phase sequence K Key lock
16 1,600 A DN p/ 1,600 A - RST (N) K2 Key interlock
Mechanical interlock for 2 circuit
M breakers1)
Rated current
Number of poles Mechanical interlock for 3 circuit
08 800 A M3 breakers1)
3 3P
16 1,600 A D Door interlock
BK B+K
B2 B+K2
BM B+M
Version BD B+D
F Fixed Standard auxiliary contacts KM K+M
E Withdrawable C 4NO+4NC KD K+D
FF Fixed - Front Optional (withdrawable version) CP Profibus communication
D 4C position auxiliary contact CM Modbus communication
E 8C position auxiliary contact
Undervoltage release
Standard
Protection unit
0 No release
Standard unit
Optional
LSIG + current - electronics power supply 100~250 V ac/dc and measurement
AZ1 1 100~130 V ac/dc
frequency 60 Hz
2 200~250 V ac/dc
Optional units
3 24~30 V dc
000 No protection unit
4 48~60 V ac/dc
LSIG + current - electronics power supply 100~250 V ac/dc and measurement
AZ6 5 380~480 V ac
frequency 50 Hz
6 200~250 V ac/dc with delay
LSIG + current - electronics power supply 24~60 V dc and measurement frequency
AZ2 7 100~130 V ac/dc with delay
60 Hz
8 48~60 V ac/dc with delay
LSIG + current - electronics power supply 24~60 V dc and measurement frequency
AZ7 9 380~480 V ac with delay
50 Hz
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and
AF1 Standard opening coil
measurement frequency 60 Hz
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and 2 200~250 V ac/dc
AF6 Optional
measurement frequency 50 Hz
LSI + earth leakage + current - electronics power supply 24~60 V dc and 0 No release
AF2
measurement frequency 60 Hz 1 100~130 V ac/dc
LSI + earth leakage + current - electronics power supply 24~60 V dc and 3 24~30 V dc
AF7
measurement frequency 50 Hz 4 48~60 V ac/dc
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and 5 380~480 V ac
AC1
measurement frequency 60 Hz
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and Standard closing coil
AC6 Motorized operator
measurement frequency 50 Hz 2 200~250 V ac/dc
LSIG + current + communication2) - electronics power supply 24~60 V dc and Standard Optional
AC2
measurement frequency 60 Hz 0 No motor operator 0 No release
LSIG + current + communication2) - electronics power supply 24~60 V dc and Optional 1 100~130 V ac/dc
AC7
measurement frequency 50 Hz 1 100~130 V ac/dc 3 24~30 V dc
LSIG + voltage + current + communication2) - electronics power supply 2 200~250 V ac/dc 4 48~60 V ac/dc
PC1
100~250 V ac/dc and measurement frequency 60 Hz
3 24~30 V dc 5 380~480 V dc
LSIG + voltage + current + communication2) - electronics power supply
PC6
100~250 V ac/dc and measurement frequency 50 Hz
Accessories supplied as standard for the entire range
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc
PC2
and measurement frequency 60 Hz Auxiliary contacts (4NO+4NC)
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc Alarm contacts
PC7
and measurement frequency 50 Hz
Opening coil 200~250 V ac/dc

Accessories supplied as optional items Closing coil 200~250 V ac/dc


Motorized operator Door frame Operation counter
Undervoltage release Transparent cover Position locking with padlock (padlock not included) - withdrawable version
Condenser trip device Mechanical interlock Position indicator (Inserted /Test/ Withdrawn) - withdrawable version
Key lock Door interlock
Key interlock Position auxiliary contact

Notes: 1) 2 circuit breakers are already considered for mechanical interlock M.


3 circuit breakers are already considered for mechanical interlock M3.
2) For communication via Profibus network, it is necessary to use the ABW-CP accessory.
For communication via Modbus network, see the Communication section of this catalog.

Air Circuit Breakers 13


www.weg.net

Accessories
Auxiliary Contacts
They indicate the circuit breaker status, ON or OFF. For ABW there are 5 Axa contacts (NO) and 5 Axb contacts (NC) and for
ABWC there are 4 Axc contacts (NOC).
Configuration Resistive load Inductive load
125 V ac 10 6
250 V ac 10 6
460 V ac 5 6
Switching capacity (A)
30 V dc 10 6
125 V dc 0.6 0.6
250 V dc 0.3 0.3

Auxiliary contact

Alarm Contacts
These contacts are incorporated in the protection units and indicate the occurrence of a trip by any of the protection functions.
The contacts are Alarm 1, Alarm 2 and Contacts 524, 534 and 544.
Configuration 2NO (generic) + 4NO (individual)
250 V ac 5
380 V ac 3
Switching capacity (A)
30 V dc 5
125 V dc 1
Minimum application levels 5 V dc / 10 mA

14 Air Circuit Breakers


www.weg.net

Accessories
Closing Coil
This coil allows closing the circuit breaker by means of electrical control. This remote control is valid only if the springs of the
operating mechanism are charged. This accessory is supplied as standard at voltage 250 V ac/V dc. The closing coils are
interchangeable with the ABWC line.
Characteristics Specification
Reference ABW-BF C34 ABW-BF E27 ABW-BF E10 ABW-BF E12 ABW-BF D85
Code 11193568 11193767 11193789 11193790 11193795
Power supply 24~28 V dc 48~60 V ac/dc 100~130 V ac/dc 200~250 V ac/dc 380~480 V ac
Operation voltage 0.75...1.1 x Un
Energization 200
Consumption (VA)
Steady-state 5
Closing time (ms) ≤80
Anti-pumping characteristic Yes, through electronic circuit
Minimum supply time for operation (ms) 200

Standard
Power supply Reference
200...250 V ac/dc ABW-BF E12

Closing coil

Air Circuit Breakers 15


www.weg.net

Accessories
Opening Coil
This coil allows opening the circuit breaker by means of Standard
electric control. This accessory is supplied as standard Power supply Reference
at voltage 250 V ac/V dc. The opening coils are 200...250 V ac/dc ABW-BA E12
interchangeable with the ABWC line.
Characteristics Specification
Reference ABW-BA C34 ABW-BA E27 ABW-BA E10 ABW-BA E12 ABW-BA D85
Code 11193796 11193875 11193879 11193880 11193881
Power supply 24~28 V dc 48~60 V ac/dc 110~130 V dc 200~250 V dc 380~480 V ac
Operation voltage 0.75...1.1 x Un
Energization 200
Consumption (VA)
Steady-state 5
Opening time (ms) ≤40
Anti-pumping characteristic Yes, through electronic circuit
Minimum supply time for operation (ms) 200

Opening coil

Motor Operator
The motorized drive is used for the automatic charging of the springs of the circuit breaker operating mechanism. The operation
begins immediately after the circuit breaker opens and, at the end of this process, an auxiliary contact indicates that the springs
are charged. Even if the motorized drive is installed, it is also possible to charge the springs manually through the front lever.
The standard circuit breaker allows charging the spring in the ON position.
Characteristics Specification
Reference ABW-AM E10 ABWC-AM E10 ABW-AM E12 ABWC-AM E12 ABW-AM C34 ABWC-AM C34 ABW-AM E27 ABW-AM D33 ABW-AM D74
Code 11193480 14794817 11193484 14794848 11193457 14794850 11193478 11193486 11193487
Power supply 100~130 V dc/ac 100~130 V dc/ac 200~250 V ac/dc 200~250 V ac/dc 24~28 V dc 24~28 V dc 48~60 V ac/dc 380 V ac 440 V dc
Rated current (A) 1 1 0.5 0.5 5 5 3 0.3 0.3
Starting current (A) 5 x rated current
Motor speed (rpm) 1,500~1,900 rpm
Charge time
≤5
(for spring charging) (s)

Motorized operator

16 Air Circuit Breakers


www.weg.net

Accessories
Charged Spring Auxiliary Contact
It is supplied incorporated to the motorized drive. This auxiliary contact sends a signal when the motor is charged. It has two
open contacts: 1 used for communication in general, and the other used for springs charged indication.

Undervoltage Release
It automatically disconnects the circuit breaker in cases of undervoltage or phase loss. Interchangeable with the ABWC line.
Characteristics Specification
Reference ABW-UVT E10 ABW-UVT E12 ABW-UVT E55 ABW-UVT C34 ABW-UVT E27
Code 11193884 11193888 11193854 11193882 11193883
Power supply 100~130 V ac/dc 200~250 V ac/dc 380~480 V ac 24~28 V dc 48~60 V ac/dc
Operation voltage range 0.65...0.85 x Un
Drop-out voltage range 0.4...0.6 x Un
Trip time (instantaneous) ≤50ms
Energization 200
Consumption (VA or W)
Steady-state 5

Undervoltage release

Undervoltage Time Delay Module Wiring Diagram


It delays the opening of the circuit breaker after the 14 16
command from the undervoltage release.
UVT Delay trip
Interchangeable with the ABWC line. 18 19 20
command

a c b
0.5 1
Signal for
Signal for
Characteristics Specification tripping
tripping
1.5
5 7
3
Reference ABW-UDC E10 ABW-UDC E12 ABW-UDC E55 ABW-UDC E27 DC48~60 V
AC48 [seg]
Code 11193451 11193452 11193453 11193406
ABW UDC
Power supply 100~130 V ac/dc 200~250 V ac/dc 380~480 V ac 48~60 V ac/dc 5 7
Time
Timedelay
delayfor
forUVT
UVT
Operation voltage range 0.65...0.85 x Un
14 16
Drop-out voltage range 0.4...0.6 x Un
Time delay (s) 0.5 - 1 - 1.5 - 3
Energization 200 Instantaneous
Consumption (VA) trip command
Steady-state 5

D1

D2
ABW UVT

Note: 18 = Common
19 = Normally Closed
20 = Normally Open.

Air Circuit Breakers 17


www.weg.net

Accessories
ABW Position Auxiliary Contact
It is a contact that indicates the current position of the ABW (CONNECTED, TEST, DISCONNECTED)
( � Common use for all models)

Operating Characteristics
Disconnected Connected
ABW position
Disconnected Test Connected
CL1, CL2 ON

Contact operation
OFF
(Connected)
CL3 ON
OFF
(TEST)
CL4 ON
(Disconnected) OFF

Voltage (V) Resistive load Inductive load

460 5 2.5

Contact capacity
AC 250
10 10
125

250 3 1.5

DC 125 10 6

30 10 10

com. com. com. com.


com. com. com. com.
381 371 361 351
341 331 321 311

CL4 CL3 CL2 CL1 CL4 CL3 CL2 CL1

342 344 332 334 322 324 312 314 382 384 372 374 362 364 352 354
NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO

Installation Method
Install the position auxiliary contact on the right plate, as
shown in the figure, since it is interlocked with the main
shaft in the truck.

18 Air Circuit Breakers


www.weg.net

Accessories
ABWC Position Auxiliary Contact

ABWC
position
auxiliary
contact

� It
 is a contact that indicates

the curren position of the


ABWC (CONNECTED, TEST,
DISCONNECTED)

Operating Characteristics
Disconnected Connected
ABWC position
Disconnected Test Connected
CL1, CL2 ON
(Connected) OFF
CL3 ON
Contact operation OFF
(TEST)
CL4 ON
(Disconnected) OFF

Voltage (V) Resistive load Inductive load

460 5 2.5

AC 250
10 10
Contact capacity 125

250 3 1.5

DC 125 10 10

30 10

com. com. com. com.


com. com. com. com.
381 371 361 351
341 331 321 311

CL4 CL3 CL2 CL1 CL4 CL3 CL2 CL1

342 344 332 334 322 324 312 314


382 384 372 374 362 364 352 354
NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO

Air Circuit Breakers 19


www.weg.net

Accessories
Key Lock

It locks the circuit breaker in the OFF position.

Circuit breakers Reference Code


ABW 08...63 ABW-BK1 11194682
ABWC 08...16 ABWC-BK1 14795246

Key Interlock

It allows the interlock of three circuit


breakers in the configuration below:

Circuit breakers Reference Code


ABW 08...63 ABW-IK2 11194685
ABWC 08...16 ABWC-IK2 14802482

Circuit breaker Circuit breaker Circuit breaker Status


(1) (2) (3) Load 1 Load 2
g Release/ g g g
OFF OFF
circuit breaker ON
g g g
ON ON
Circuit
g g g
ON ON breaker Circuit
1 breaker
M
g g g
ON ON 2

g Lock/ g g g
OFF OFF
circuit breaker OFF g g g
OFF ON Circuit
breaker
3
g g g
ON OFF

Notes: 1) W
 hen the key releases the circuit breaker, it is not possible to remove it from the interlock. Only in this
position is it possible to close the circuit breaker.
2) It is not possible to actuate the air circuit breaker locally or remotely (by closing coil) with the key interlock
actuated. The key is able to be removed only when the interlock in actuated.

20 Air Circuit Breakers


www.weg.net

Accessories
Position Locked by Padlock

It allows locking the access to the


circuit breaker ON and OFF buttons.

ON/OFF
button lock

Circuit breakers Reference Code


ABW08...63 ABW-BB 11194681
ABWC08...16 ABWC-BB 14795244

Rear Terminals
ABW and ABWC circuit breakers can be supplied with the terminals in the Horizontal (Standard) or Vertical (Optional) position.
To change the terminals from horizontal to vertical on models ABWC and ABW up to 3,200 A, the terminal is simply rotated
and tightened according to the tightening torque table on page 10.
For models ABW40, ABW50 and ABW63, the terminals need to be replaced with different models to allow their rotation.
Below are the codes for the vertical terminal models.

Circuit breakers Reference Code


ABW40...50 ABW4000/5000 3P 11965750
ABW63 ABW6300 3P 11965751

Condenser Trip Device

This device electrically trips the circuit breaker within a preset time when the
control power is OFF. It discharges a capacitor by directly operating the
opening coil. It includes a lamp to indicate whether the capacitor is charged
and a discharge button. Installation on panel door.

Characteristics Specification
Reference ABW-CTD D58 ABW-CTD D64
Power supply (V ac) 100...110 200...220
Operation voltage 0.85...1.1 x Un
Frequency (Hz) 50/60
Charging time (s) Up to 5 seconds
Possible trip time (m) Up to 3 minutes Up to 2 minutes
Code 11193370 11193376

Air Circuit Breakers 21


www.weg.net

Accessories
Wiring Diagram

Circuit
Condenser trip device OFF breaker
button
Opening
C1 D1 R1 C6 S+
coil

SW1 R3
AC Discharge DC
TNR C button
(Input) (Output)

R2 Lamp

C3 S5 S-

124
117
75 15

15,3
66,5
75

Door Frame

Door frame. Supplied in the fixed and


withdrawable versions.

Circuit breakers Model References Code


ABW08...63 Fixed ABW-DFF 11321382
ABW08...63 Withdrawable ABW-DFE 11195048
ABWC08...16 Fixed ABWC-DFF 14795247
ABWC08...16 Withdrawable ABWC-DFE 14795328
Degree of protection IP3x

Panel
Rubber Frame

Door
frame

Circuit breaker

22 Air Circuit Breakers


www.weg.net

Accessories
Door Frame
Installation Method

Insert the door frame into the panel door cut-out and secure it with 10 M5 screws.

Transparent Cover

Panel door

Dust cover Door frame

It allows viewing the circuit breaker without opening the panel door. It can be opened or
closed with the circuit breaker in all positions: withdrawn, in test or in operation. Also used
for the fixed version.

Circuit breakers References Code


ABW08...63 ABW-DC 11195053
ABWC08...16 ABWC-DC 14802564
Degree of protection IP5x1)2)

Notes: 1) Protection only against dust, which is the agent that causes faults in this type of product and installation.
2) The Transparent Cover can be closed even if the withdrawable circuit breaker is in the test position.

Air Circuit Breakers 23


www.weg.net

Accessories
Mechanical Interlock

It enables two or three circuit breakers to be mechanically interlocked


with cables, controlling the closing and trip operations mutually.

Circuit breakers Quantity of circuit breakers Reference Code


ABW08/16/40/50 2 ABW-IM1 2D/F 11194710
ABW20/25/32/63 2 ABW-IM2 2E/G 11194711
ABW08/16/40/50 3 ABW-IM1 3D/F 11194713
ABW20/25/32/63 3 ABW-IM2 3E/G 11194717
ABWC08/16 2 ABWC-IM1 2D/F 14802487
ABWC08/16 3 ABWC-IM1 3D/F 14802509

For mechanical interlock between two circuit breakers, consider the following interlock options:

0: circuit breaker OFF


1 2 3
circuit circuit I: circuit breaker ON
breakerABW 2 breaker O O O It allows the configuration of a circuit breaker ON and a circuit
1 2
I O O breaker OFF and vice versa.
O I O The mechanical interlock cables length are 1.6 m.
O O I
O I I
I I O
I O I

24 Air Circuit Breakers


www.weg.net

Accessories
Mechanical Interlock

For mechanical interlock between three circuit breakers, consider the following interlock options:

1 2 3
0: circuit breaker OFF
O O O
circuit I: circuit breaker ON
breaker circuit I O O It allows the status of two circuit breakers ON and a circuit
1 circuit breaker
breaker 2 3 I I O
O breaker OFF.
I I
O O The mechanical interlock cables length between circuit breaker
O O
I I 1 and 2 is 1.3m and between circuit breaker 2 and 3 is 1.3 m.
I O I
I O
I O I

Door Interlock

It prevents the panel door from being


opened while the circuit breaker is ON.

Circuit breaker Reference Code


ABW08...63 ABW-DI 11195050
ABWC08/16 ABWC-DI 14805726
Cable length (m) 1.6

Install on the panel door

Install on the side plate of


the ABC truck

Air Circuit Breakers 25


www.weg.net

Accessories
Communication Module

The communication module is an optional item that has an I/O unit, enabling the
circuit breaker remote operation. All ABW and ABWC circuit breakers, with
protection units A and P, are able to communicate via network, allowing the user
to verify the status of the circuit breaker and operate it through a Modbus or
Profibus-DP network.
The communication module can be installed either on the circuit breaker
withdrawable rack (withdrawable version) or on a DIN rail.
1. Modbus/RS485 communication: two types of Modbus communication are
available:
� Reading: for an only-reading communication, the circuit breaker must be

installed as slave, and another device as master; it is not necessary to


purchase the ABW-CM accessory (supplied as an optional item).
� Control/writing: for a control Modbus communication, it is necessary to

install the ABW-CM accessory (supplied as optional item).


2. Profibus-DP communication: for a Profibus network communication (reading
or writing), it is necessary to install the ABW-CP accessory (supplied as an
optional item), which allows the user to check the circuit breaker status and
operate it.

Classification Range Note


Contact switching capacity 230 V ac 16 A / 30 V dc 16 A -
Circuit breaker control
Max. switching power 3,680 VA / 480 W -
Contact switching capacity 230 V ac 6 A / 25 V dc 6 A Load introduction
Alarm
Max. switching power 1,880 VA / 150 W (cosØ = 0.4, L/R = 7ms)

Wiring diagram with the ABW-CP and ABW-CM modules: Circuit breakers Reference Code
ABW08...63
ABW-CP 11193400
ABWC08...16
CN4-1
CN4-1
ABW08...63
ABW-CM 11193398
ABW-CM
ADW-CM 485+
485+ terminal
terminal ABWC08...16
ou
or
ABW-CP CN4-3
CN4-3
485- terminal
485- terminal

Control power AC/DC Relay 0


1 24 V circuit-breaker 13
110/220V Circuit breaker ON (+)
24 V GND closed
2 Power 5V 14
Circuit breaker ON (-)
5 V GND Relay 1 circuit
3 15
Circuit breaker ON breaker open Circuit breaker OFF (+)
4 16
Circuit breaker OFF Circuit breaker OFF (-)
5
General DI 1
6
Remote I/O unit General DI 2

DI_COM 7

9 RS485(-) 19

RS485(+) 20 *
10

11
Modbus
RS485 Profibus-DP
12

Note: if using Profibus-DP communication, it must communicate with the circuit breaker trip relay.

26 Air Circuit Breakers


www.weg.net

Accessories
Communication Module

J  he remote I/O unit has the I/O contact that can remotely trip
T
or close the ACB via communication.
J For the general DO, the output of DI1 or DI2 is selectable.
J The remote I/O unit communicates basically via Modbus/
RS485; Profibus-DP has to be purchased separately.
J It supports the SBO (Select Before Operation) function and
ensures control reliability.
J The remote I/O unit can be installed on the ACB truck or
inside the panel.

LED Status
1 DI1 Indicates the condition of digital input 1
2 DI2 Indicates the condition of digital input 2
- Baud rate settings 3 DO ON Indicates that the temperature alarm output is ON
- Communication 4 DO OFF Indicates that the temperature alarm output is OFF
address settings 5 Circuit breaker ON Indicates the closed circuit breaker condition
- Temperature settings 6 Circuit breaker OFF Indicates the open circuit breaker condition
7 Operation LED Indicates the operating condition of the unit
Circuit breaker Indicates a disconnection/circuit breaker terminal control error
8
ERROR condition

Insulation Barrier (IB)


The insulation barrier is an accessory that increases the insulation characteristics between the phases.
J 
In fixed circuit breakers, the insulation barrier must be installed in direction A, as shown in the figure below.
J In withdrawable circuit breakers, the insulation barrier must be installed in direction C, as shown in the figure below.

Circuit breakers Reference Code


ABW08-63 ABW-IB 11194726
ABWC08...16 ABWC-IB-E 11194726
ABWC08...16 ABWC-IB-F 14825646
ABWC08...16 ABWC-IB-FF 14825645

Fixed Circuit Breaker Withdrawable Circuit Breaker

Air Circuit Breakers 27


www.weg.net

Accessories Zero Arc


Space
(ZAS)

Zero Arc Space (ZAS)


The zero arc space is an accessory used to increase the application safety. It
extinguishes the electric arc generated to the external environment.
Circuit breaker Reference Code
ABW16 CAMARA EXTINCAO ZERO ARCO ABW-ZAS 16 13443038
ABW32 CAMARA EXTINCAO ZERO ARCO ABW-ZAS 32 13443039
ABW50 CAMARA EXTINCAO ZERO ARCO ABW-ZAS 50 13443040
ABW63 CAMARA EXTINCAO ZERO ARCO ABW-ZAS 63 13443042

Note: accessory only applicable to withdrawable circuit breakers.

Current Transformer (Toroid)

The leakage current can be set from 0.5 A to 30 A according to


the table below; the fault protection must be disabled.

Earth leakage (optional)


Current setting (A) I∆n 0.5 1 2 3 5 10 20 30 OFF
Time delay (ms) Alarm time 140 230 350 800 950 - - - -
∆t
Accuracy ± 15% Trip time 140 230 350 800 - - - - -

Reference Current Code


ABW-ZCT-120 1,000 A 11195018
ABW-ZCT-200 2,000 A 11195019

Dimensions
WEG CT (Ratio 30/5 A)

A
C

F G

Available in two models:


Model A B C D E F G H
ZCT-120 120 45 225 180 210 20 55 35
ZCT-200 200 53 310 260 286 20 70 35

28 Air Circuit Breakers


www.weg.net

Accessories
Protection Units
On the ABW and ABWC air circuit breakers, the ABW-OCR microprocessed electronic protection units perform the protections.
The AZ1 unit is supplied as standard for all circuit breakers and offers protection against overload (L), timed short circuit
(S), instantaneous short circuit (I) and ground fault (G)—functions which are set on the front dials. Other models are
supplied as optional accessories, allowing network communication, voltage measurement, earth leakage protection (external
CT required - supplied as optional accessory) and other protections.
Circuit breaker model Code Reference Protection unit supply voltage Protection unit measurement frequency
ABWC-AZ1 100~250 V ac/dc 60 Hz 60 Hz
14794814
ABWC-AZ6 100~250 V ac/dc 50 Hz 50 Hz
LSIG protection + current reading
ABWC-AZ2 24~60 V dc 60 Hz
15019080
ABWC-AZ7 24~60 V dc 50 Hz
ABWC-AC1 100~250 V ac/dc 60 Hz 60 Hz
14794811
ABWC-AC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + current reading
ABWC-AC2 24~60 V dc 60 Hz + communication
ABWC 15019085
ABWC-AC7 24~60 V dc 50 Hz
ABWC-AF1 100~250 V ac/dc 60 Hz 60 Hz LSIG protection + ground fault +
14794810
ABWC-AF6 100~250 V ac/dc 50 Hz 50 Hz current reading
ABWC-PC1 100~250 V ac/dc 60 Hz 60 Hz
14794812
ABWC-PC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + voltage and
ABWC-PC2 24~60 V dc 60 Hz current reading + communication
15019083
ABWC-PC7 24~60 V dc 50 Hz
ABW-AZ1 100~250 V ac/dc 60 Hz 60 Hz
11321384
ABW-AZ6 100~250 V ac/dc 50 Hz 50 Hz
LSIG protection + current reading
ABW-AZ2 24~60 V dc 60 Hz
11912860
ABW-AZ7 24~60 V dc 50 Hz
ABW-AC1 100~250 V ac/dc 60 Hz 60 Hz
11321408
ABW-AC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + current reading
ABW-AC2 24~60 V dc 60 Hz + communication
11912797
ABW-AC7 24~60 V dc 50 Hz
ABW
ABW-AF1 100~250 V ac/dc 60 Hz 60 Hz
11321386
ABW-AF6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + ground fault +
ABW-AF2 24~60 V dc 60 Hz current reading
12670394
ABW-AF7 24~60 V dc 50 Hz
ABW-PC1 100~250 V ac/dc 60 Hz 60 Hz
11321410
ABW-PC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + voltage and
ABW-PC2 24~60 V dc 60 Hz current reading + communication
11912858
ABW-PC7 24~60 V dc 50 Hz

Air Circuit Breakers 29


www.weg.net

Accessories

AZ1
Reading Communication Power supply
A Current Z No communication Code OCR Line reading frequency
P Current and voltage C With communication 1 100~250 V ac/dc 60 Hz
F Earth leakage 2 24~60 V dc 60 Hz
6 100~250 V ac/dc 50 Hz
7 24~60 V dc 50 Hz

AZ AC AF PC
110...250 V ac/dc 110...250 V ac/dc 110...250 V ac/dc 110...250 V ac/dc
Power supply
24...60 V dc 24...60 V dc 24...60 V dc 24...60 V dc
Consumption 5 VA 5 VA 5 VA 5 VA
1/2 60 Hz 60 Hz 60 Hz 60 Hz
Line frequency
6/7 50 Hz 50 Hz 50 Hz 50 Hz
L - Overload 3 3 3 3
S - Short circuit (timed) 3 3 3 3
Standard
I - Short circuit (instantaneous) 3 3 3 3
G - Ground fault 3 3 7 3
Earth leakage (external CT required - option) 7 7 3 7
Protection
ZSI (protective coordination) 3 3 3 3
functions
Under and overcurrent 7 7 7 3
Optional Frequency out of range 7 7 7 3
Unbalance (current/voltage) 7 7 7 3
Pre-trip alarm 7 7 7 3
Discrimination / trip type indication 3 (LEDs / aux. cont.) 3 (LEDs / aux. cont.) 3 (LEDs / aux. cont.) 3 (LEDs / aux. cont.)
Current (R / S / N / T) 3 3 3 3
Current / Voltage RMS 7 7 7 3
Measurements
Power (P, Q, S), FP (3 phases) 7 7 7 3
Frequency 7 7 7 3
Fault recording 3 3 3 3
Number of records 10 10 10 256
Event sequence 3 3 3 3
Broken current value 3 3 3 3
Total breaking time 3 3 3 3
Event recording 7 7 7 256
Digital outputs 3 fixed 3 fixed 3 fixed 3 programmable
Front adjustment knobs 3 3 3 3
Parameterization Display + navigation keys 3 3 3 3
Parameterization password 3 3 3 3
Door 7 RS485 7 RS485
Network communication Protocol 7 Modbus / Profibus1) 7 Modbus / Profibus1)
9,600 bps, 19,200 bps, 9,600 bps, 19,200 bps,
Baud rate 7 7
38,400 bps 38,400 bps
Note: 1) In order to use network communication, see the Communication Module topic in this catalog.

30 Air Circuit Breakers


www.weg.net

Accessories
Type A

Technical Data
The ABW-OCRAZ1 protection unit has
characteristics that meet the requirements of most
systems and applications. It is supplied as standard
for ABW08...63 circuit breakers.
g Overload protection (L)
g Long timing

g Short circuit protection

g Short timing (S)

g Instantaneous (I)

g I2 t ON/OFF optional (short timing)

g Ground fault protection (G)

g I2 t ON/OFF optional

g Earth leakage protection

g External CT required (accessory)

g It cancels the Ground fault function (G)

g Fault event sequence

g Up to 10 faults

g 3 fixed digital outputs to indicate protection alarm

g Network communication option

g Modbus/RS485

g Profibus-DP

Display
The home screen indicates the instantaneous current
values per phase. It is also possible to check other
information, available in different menus.

Indication LEDs

LED Function Indication


Indicates the possibility of overload (lights up at 90% of the set
1 Alarm
current and flashes above 105%)
2 Battery/Self-diagnosis Protection unit and battery charge self-diagnosis
3 Ir Indicates overload trip
4 Isd/Ii Indicates short-circuit trip
5 Ig/Δn Indicates ground fault trip
6 Communication Indicates network communication

Navigation Keys Setting of the Protection

Used for navigation through the available menus.


Key Function Parameter Function / Setting range

Iu Overload current setting (0.5-0.6-0.7-0.8-0.9-1.0) x In


Menu
Overload current setting (protection function L)
Ir
(0.8-0.83-0.85-0.88-0.89-0.9-0.93-0.95-0.98-1.0) x Iu

Moves the cursor or setting right / left Overload tripping delay


tr
(0.5-1-2-4-8-12-16-20-OFF) s @ 6xIr
Timed short-circuit tripping current (protection function S)
Is
Moves the cursor up or increases a setting value (1.5-2-3-4-5-6-7-8-9-10-OFF) x Ir
Is current delay I2t OFF (0.05-0.1-0.2-0.3-0.4) x Ir
tsd
I2t ON (0.1-0.2-0.3-0.4) x Ir
Moves the cursor down or decreases a setting
value Instantaneous short circuit tripping current
Ii (protection function I)
(2-3-4-6-8-10-12-15-OFF) x In
Enter
Ground fault detection current (protection function G)
Ig
(0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-OFF) x In

Fault reset / ESC from menu I2t OFF (0.05-0.1-0.2-0.3-0.4)


tg
I2t ON (0.1-0.2-0.3-0.4)

Air Circuit Breakers 31


www.weg.net

Accessories
Type A
Protection

t Long time
Iu = In×... 0.5 0.6 0.7 0.8 0.9 1.0 -
Ir Current setting (A)
Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1.0
t tr@ (1.5×lr) 12.5 25 50 100 200 300 400 500 OFF
Time delay (s)
Precision ±15% tr@ (6.0×lr) 0.5 1 2 4 8 12 16 20 OFF
t Ir 100ms
tr tr@ (7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 OFF
Ir Short time
lsd Current setting (A)
Precision ±10%
Isd = Ir×... 1.5 2 3 4 5 6 8 10 OFF
tr
tsd tsd
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
tr lsd Time delay (s) I2t ON 0.1 0.2 0.3 0.4 -
Ii @ 10×Ir Minimum 20 80 160 260 360 -
(I2t OFF) opening
lsd tsd time 80 140 240 340 440 -
I
tsd Ii Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 OFF
Ii I Opening time Below 50ms

I
t

t
t
Ig
Ground fault
Operating current (A)
Precision: ±10% (Ig>0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 OFF
Ig ±20% (Ig≤0.4In)
tg
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
Ig tg
I2t ON 0.1 0.2 0.3 0.4 -
tg Time delay (s)
Minimum
opening 20 80 160 260 360 -
I @ 1×In time
tg (I2t OFF)
Maximum
opening 80 140 240 340 440 -
I time

t Earth leakage (optional)


Current setting (A) I∆n 0.5 1 2 3 5 10 20 30 OFF
t Alarm time
I n Time delay (ms) (ms)
140 230 350 800 950 -
∆t
Precision: ±15% Opening time
140 230 350 800 -
(ms)
I n
t Note: earth leakage function available with external CT.
I n
t
I
t

I
I

32 Air Circuit Breakers


www.weg.net

Accessories
Type P

Technical Data
This unit was developed for applications with high technical
requirements. Available for the entire ABW line.
g Overload protection (L)
g Long timing

g Short circuit protection

g Short timing (S)

g Instantaneous (I)

g I2 t ON/OFF optional (short timing)

g Ground fault protection (G)

g I2 t ON/OFF optional

g  Protection against under and overcurrent, under and overvoltage,


current unbalance, voltage unbalance, frequency out of range and
reverse power
g Fault event sequence up to 256 faults

g  Event sequence up to 256 events the user chooses


g Protection coordinated by the ZSI (Zone Selective Interlocking)

g Fine tuning with knob and key


g Measurements of current / phase angle / voltage / power /

frequency / power factor / others


g 3 programmable digital outputs for alarm, trip and general purpose

g Network communication

g Modbus/RS485

g Profibus-DP

Display
The home screen indicates the instantaneous current values per phase.
It is also possible to check other information, available in different
menus.

Indication LEDs

LED Function
Alarm Overload alarm (L)
SP Indicates self-protection and battery test
IR Indicates timed short circuit tripping (S)
Isd/Ii Indicates instantaneous short circuit tripping (I) Setting of the Protection Functions
Ig Indicates ground fault (G)
Comm Indicates communication status (optional)

Navigation Keys

Used for navigation through the available menus.


Key Function Parameter Function / Setting range
Overload current setting (protection function L)
Ir
Menu (0.4-0.5-0.6-0.7-0.8-0.9-1.0) x In
Overload tripping delay
tr
(0.5-1-2-4-8-12-16-20-OFF) s @ 6xIr
Timed short circuit tripping current
Moves the cursor or setting right / left
Is (protection function S)
(1.5-2-3-4-5-6-7-8-9-10-OFF) x Ir
Is current delay
Moves the cursor up or increases a setting value tsd I2t OFF (0.05-0.1-0.2-0.3-0.4) x Ir
I2t ON (0.1-0.2-0.3-0.4) x Ir
Instantaneous short circuit tripping current
Moves the cursor down or decreases a setting Ii (protection function I)
value (2-3-4-6-8-10-12-15-OFF) x In
Ground fault detection current (protection function G)
Ig
(0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-OFF) x In
Enter
I2t OFF (0.05-0.1-0.2-0.3-0.4)
tg
I2t ON (0.1-0.2-0.3-0.4)
Fault reset / ESC from menu I2t OFF (0.05-0.1-0.2-0.3-0.4)
tg
I2t ON (0.1-0.2-0.3-0.4)

Air Circuit Breakers 33


www.weg.net

Accessories
Type P
Protection
Long time
Current setting (A) Ir = In×... 0.4 0.5 0.6 0.7 0.8 0.9 1.0 -
t tr@ (1.5×lr) 12.5 25 50 100 200 300 400 500 OFF
Time delay (s)
t Ir Precision: ±15% tr@ (6.0×lr) 0.5 1 2 4 8 12 16 20 OFF
100ms
tr@ (7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 OFF
Ir Short time
Current setting (A)
Isd = Ir×... 1.5 2 3 4 5 6 8 10 OFF
tr Precision: ±10%
tr tsd
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
lsd I2t ON - 0.1 0.2 0.3 0.4 -
lsd tsd Time delay (s)
Minimum
opening 20 80 160 260 360 -
@ 10×Ir time
tsd Ii (I2t OFF)
Maximum
opening 80 140 240 340 440 -
Ii time
I
Instantaneous
I Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 OFF
Opening time Below 50ms

t
t Ground fault
Operating current (A)
Precision: ±10% (Ig>0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 OFF
±20% (Ig≤0.4In)
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
tg
Ig I2t ON - 0.1 0.2 0.3 0.4 -
Ig Time delay (s)
Minimum
opening 20 80 160 260 360 -
@ 1×In time
(I2t OFF)
tg Maximum
opening 80 140 240 340 440 -
tg time

I
I

Earth leakage (optional)


t
Current setting (A) I∆n 0.5 1 2 3 5 10 20 30 OFF
t Alarm time
140 230 350 800 950 -
Time delay (ms) (ms)
∆t
Precision: ±15% Opening time
140 230 350 800 -
(ms)
Pre-trip alarm
I n
Current setting (A) Ip = Ir x … 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1
I n Time delay (ms)
tp@ (1.2×Ip) 1 5 10 15 20 25 30 35 OFF
Precision: ±15%
t
Note: earth leakage function available with external CT.
t

I
I
Operation Time delay (s)
Other protections
Setting range Measurement Precision Setting range Measurement Precision
Undervoltage 80 V ~ 0 V_Operation 1V ±5%
Overvoltage UV_Operation ~ 980 V 1V ±5% 1.2 ~ 40s
Unbalance voltage 6% ~ 99% 1% ±2.5% ou (*±10%)
Reverse power 10~500 kW 1 kW ±10%
0.2 ~ 40s
Overpower 500~5,000 kW 1 kW ±10%
0.1s ±0.1s
Unbalance current 6% ~ 99% 1% ±2.5% ou (*±10%)
60 Hz UF_Operation ~ 65 1 Hz ±0.1 Hz
Over-frequency
50 Hz UF_Operation ~ 55 1 Hz ±0.1 Hz 1.2 ~ 40s
60 Hz 55 Hz ~ OF_Operation 1 Hz ±0.1 Hz
Under-frequency
50 Hz 45 Hz ~ OF_Operation 1 Hz ±0.1 Hz

34 Air Circuit Breakers


www.weg.net

Dimensions
ABWC08...16DN3F_H - Fixed Version

Front View Horizontal Rear Terminal - Side Vertical Rear Terminal - Side
View View

272.4 198.5 198.5


246.4 188 188
104.5 104.5 47,6 109.5 47.6 109.5

Ø9 33
15

15

50
322
283

261.1
150
125
248

150
2-Ø11

25
15

49.5
62

32
13 37.5
37.5
87.1 92.5 51.5
87.1 92.5 51.5

Horizontal Rear Terminal - Top Vertical Rear Terminal - Side


View View
9 A

72.5 72.5
13

15 10
13

15 10 2-Ø11
15
50
322

70
70

70
70
15
72,5

25

15
.5
.5

R4
R4

Type H (horizontal type) Type V (vertical type)


272,4

Rear Terminal Dimensions

50
50

25
15
15

25
Ø1111

Air Circuit Breakers 35


www.weg.net

Dimensions

ABWC08...16 - Withdrawable Version

Front View Horizontal Rear Terminal - Side Vertical Rear Terminal - Side
View View
272.2

93.8
111.3
15

50
364.3

150
150

25
Ø8,5
Ø8,5

70.5
88
56
56
256

Horizontal Rear Terminal - Top Vertical Rear Terminal - Side


View View

75 170.5 75 170.5
2-Ø11
57.7

15
57.7
50
70

4-Ø8.5
70
140

140
70

70

4-Ø8.5
25

2,205 15 56
56
3,461
87,91

Type H (horizontal type) Type V (vertical type)

Rear Terminal Dimensions

50

0,984
25
15 15

25

2x0,433
Ø11
2x 11

36 Air Circuit Breakers


www.weg.net

Dimensions
ABWC08...16 - Fixed Version - Front Terminal

Front View Bottom View

9 99

15
1155
72,5
2,5
772.5
9 353,37

353,37
353.37
125
125

125
15

15
15

15
72,5

Ø99 9
353,37

272,4272,4
272.4

246,4
246.4 246,4

272,4
46,4
Side View

190,5190,5

190,5
190.5

Air Circuit Breakers 37


www.weg.net

Dimensions
ABW08...16 - Fixed Version
Front View Horizontal Rear Terminal - Side View
90
300
280 Insulation
barrier
150

15
Operating panel
center

15
270

118
133
300

270
320

59.5 15
67
35
65 20 165 45
35
20

295 32.5
12 165 165 12
354

Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
90 85 85
(Insulation
(Insulation 50
barrier)
barrier)
15
15

45
25
50
270

165
133
83
83
42 50

20
67
35
35

4 - Ø14 Assembly
hole
65 20 165
165 45
45
20 295 32.5 330
354

Vertical Rear Terminal - Top View Rear Terminal Dimensions


85
85 85 30

15
15
15
45
45
25

25

50
165
165

2 - Ø13
20

4- Ø14
4- 14
Mountinghole
Assembly hole
330
330

354
354

3P
3P

38 Air Circuit Breakers


www.weg.net

Dimensions
ABW08...16 - Withdrawable Version
Front View Horizontal Rear Terminal - Side View
20 394 20 Disconnected & Test Zero arc space
50 Connected
167
Insulation
15 55
barrier
90

2-M12 Tap
CMB-U/F

15
430
405

270

350
133
41 18

97
60 200 115
6
260 375
10 38.5
334
4 - Ø13 Mounting hole

Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected
Disconnected & Test& Test 85 85
50
50 Connected
Connected 50
15
15 55
55 Arc chutesurface
ARC Chute surface
90
90
(Insulation
(Insulation
barrier)
barrier)
115
50
50
270
270

200
133
350
350
133
41 18
18

97
97
41

60
60 200
200 115
115
66

10
10 375
375 38.5
38.5 260
6- 6
13-Mounting
Ø13 Mounting
hole hole 334

Vertical Rear Terminal - Top View Rear Terminal Dimensions


ype 15
15
85
85 85
85 35

15
115
115

50
25

2 - Ø13
200
200

260
260
334
334
33PP

Air Circuit Breakers 39


www.weg.net

Dimensions
ABW20...32 - Fixed Version
Front View Horizontal Rear Terminal - Side View
378 90
189 189
Insulation
280 barrier

15
Operating panel
center

20
270
300

270

113

133
320

20
67
57
35
35
20

204 204 65 20 165 45


12 12
295 32.5
432

Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
90
90 115 115
(Insulation
(Insulation 75
barrier)
barrier)
15

45
25
75

165
270

133
133
58
58

20
75
75

4 - Ø14
Mounting hole
67
67
35
35

408
432
65
65 20 165 45
45
29.5
29.5

295 32.5
32.5

Vertical Rear Terminal - Top View Rear Terminal Dimensions


115
115 115
115 30
20
20 15
45
45
25
25

25
75
165

25

3 - Ø13
20
20

4- 14
4 - Ø14
Mounting hole
Mounting hole
408
408
432
432

33PP

40 Air Circuit Breakers


90
(Insulation
www.weg.net

Dimensions
ABW20...32 - Withdrawable Version
Front View Horizontal Rear Terminal - Side View
20 472 20 Disconnected & Test
206 50 Connected Zero arc space
15 55

Insulation
barrier
90
2-M12 Tap
CMB-U/F

20
430
405

270

350
133
41 18

97
260 6 60 200 115
412 10 375 38.5
6 - Ø13 Mounting hole

Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected & Test
Disconnected & Test 115 115
50
50 Connected
Connected 75
15
15 55
55
ARCchute
Arc Chute surface
surface
90
90
(Insulation
barrier)
barrier)
115
75
75
270
270

200
350
350
133
133
41 18
18

97
97
41

60
60 200
200 115
115 260
6

10
10 375
375 38.5
38.5 412
6- 13 Mounting hole
6 - Ø13 Mounting hole

Vertical Rear Terminal - Top View Vertical Terminal Dimensions


type 115
115 115
115 34
20
20 15
115
115

25

75
25
200
200

3 - Ø13

260
260
412
412
3P
3P

Air Circuit Breakers 41


Disconnected & Test
50 Connected
www.weg.net

Dimensions
ABW40...50 - Fixed Version
Front View Horizontal Rear Terminal - Side View
90
595
280 Insulation
150 barrier

15
Operating panel
center

20
70
20
270
270
300

193
83
380

70 20
60 35
95
80

42 20
97
95

18
12 460 165 12
649
65 20 165 45
295 67.5

Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
90 190 190
(Insulation
(Insulation 125
barrier)
15

45
125
125
270
270

165
183
183
58

20
125

4 - Ø14
Mounting hole
625
102
102
95
95

649
39.5
20.5

39.5
20.5

65
65 20 165
165 45
45
295
295 67.5
67.5

Vertical Rear Terminal - Side View Rear Terminal Dimensions


190
190 190
190 34

20 70 20 15
20 70 20
25
45

25
125
25
165
165

25
20
20

5 - Ø13
4- 14
4 - Ø14
Mounting hole
625
625 Mounting hole

649
649

3P
3P

42 Air Circuit Breakers


90
(Insulation
barrier)
www.weg.net

Dimensions
ABW40...50 - Withdrawable Version
Front View Horizontal Rear Terminal - Side View
Disconnected & Test Zero arc space
20 689 20
50 Connected
147.5 Operating panel
center 15 55
90
Insulation
barrier
2-M12 Tap
CMB-U/F

20
460

110
70
435

20
270

193
380
83
110
295 260

36 41 18
629

97
42
200 115
10 375 63.5

6 - Ø13 Mounting hole

Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected &&Test
Disconnected Test 190 190
50 Connected
Connected
125
15
15 55
55 Arc chute surface
Arc surface

90
(Insulation
barrier)
barrier)
115
125
125

A
270
270

200
183
380
58

380
58
125
18
4118
36 41

120
102

295 260
39.5
39.5
36

200
200 115
115
10
10 375
375 53 .5
53.5
6-- 13
6 Ø13Mounting
Mountinghole
hole

Vertical Rear Terminal - Top View Rear Terminal Dimensions


190
190 190
190
34
al 20
20 70
70 20
20
15
25
115
115

25
125
25
200
200

25

5 - Ø13

295
295 260
260

33PP

Air Circuit Breakers 43

Disconnected & Test


Connected
www.weg.net

Dimensions
ABW63 - Fixed Version

Front View Horizontal Rear Terminal - Side View


751 90
562 189
Insulation
280 barrier
Operating panel

15
center

20
70
300

270

20
270
380

193
83
20
60 35
95
80

70
12 577 204 12

18

42 20
805

97
95

65 20 165 45
295 67.5

0 A ~5 0 0Vertical
0 A Rear Terminal - Side View Horizontal Rear Terminal - Top View
90
244 244
(Insulation
(Insulation 150
barrier)
barrier)
15

45
125

165
270
270

183
58

20
4 - Ø14
125

Mounting
781 hole
805
102
102
95
95

39.5
39.5
20.5
20.5

65 20 165
165 45
295 67.5

Vertical Rear Terminal - Top View Rear Terminal Dimensions


244
244 2244
44 34
20
20 70 20
70 20 15
25
45
45

25
165
165

150
25
25
20
20

44-- 14
25

Ø14
Mounting
781
781 Mounting
hole
hole
805
805
6 - Ø13
3P
4 0 0 0 A ~5 0 0 0 A
90
(Insulation
barrier)
15

44 Air Circuit Breakers


125
www.weg.net

Dimensions

ABW63 - Withdrawable Version

Front View Horizontal Rear Terminal - Side View


20 845 20 Disconnected & Test Zero arc space
186.5 50 Connected
Operating panel center
15 55
90
Insulation
2-M12 Tap barrier
CMB-U/F

70 20
460
435

110
20
270

193
380
83
260 113 260

110
36 41 18
785

97
42
200 115
10 375 63.5
6 - Ø13 Mounting hole

3P
4 0 0 0 A ~Vertical
5 0 0 0 A Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected & Test 244 244
Disconnected & Test
50
50 Connected
Connected 150
Arc chute
Arc chutesurface
surface
15
15 55
55
90
90
(Insulation
(Insulation
barrier)
barrier)
115
125
125

A
270
270

183
380
58
183
380
58

200
125
125
36 4118
41 18

102
102
39,5
39.5
36

200
200 115
115 260 113 260
10
10 375
375 53.5
53.5
6- 13 Mounting hole
102 6 - Ø13 Mounting hole

Vertical type
Vertical Rear Terminal - Top View Rear Terminal Dimensions
244
244 244
244 34
20
20 70
70 20
20 15
25
115
115

25
150
25
25
200
200

25

6 - Ø13

260
260 113
113 260
260

3P
3P
4 0 0 0 A ~5 0 0 0 A
Disconnected & Test
50 Connected
15 55 Arc chute surface
90 Air Circuit Breakers 45
(Insulation
barrier)
www.weg.net

Dimensions
Panel Cutout - Fixed Version

ABW08...32

10 - Ø9
315 (Panel cutout)
100

293 (Panel cutout)


108
170

100

165 165

Lower part of the withdrawable rack

ABW40...63

10 - Ø9
315 (Panel cutout)
100

293 (Panel cutout)


108
100
230

165 165

Lower part of the withdrawable rack

46 Air Circuit Breakers


www.weg.net

Dimensions
Panel Cutout - Withdrawable Version

ABW08...16
Door frame
10 - Ø5
315 (Panel cutout)
330
120

353 (Panel cutout)


128

304
170
120

109
Lower part of the withdrawable rack

11.5
165 165
Lower part of the withdrawable rack

ABW20...32
Door frame
10 - Ø5
315 (Panel cutout)
408
120

353 (Panel cutout)


128

304
170
120

109
Lower part of the withdrawable rack

11.5
165 165
Lower part of the withdrawable rack

ABW40...50
Door frame
10 - Ø5 315 (Panel cutout)
625
120

353 (Rasgo painel)


128

334
200
120

165 165 109


11.5

Lower part of the withdrawable rack


Lower part of the withdrawable rack

ABW63
10 - Ø5 Door frame
315 (Panel cutout)
781
120

353 (Panel cutout)


128

334
200
120

165 165 109


11.5

Lower part of the withdrawable rack


Lower part of the withdrawable rack

Air Circuit Breakers 47


www.weg.net

Dimensions
Minimum Distances

150
50 50

Minimum Insulation Distance


Follow the minimum insulation distance between poles below.

Insulation voltage (Ui) Min. insulation distance (X min)


600 V 8 mm
1,000 V 14 mm

ABW - UDC - Delay Module for Undervoltage Release


87

106

Condenser Trip Device ABW - CTD

131

118 7.5

15
75

75

108

48 Air Circuit Breakers


www.weg.net

Installation Recommendations
Busbar Connections Cable

Connections
Make sure there are no excessive mechanical forces applied to the circuit breaker back terminals.

Input Busbar - Connection to the General Busbar


The connector bars between the circuit breaker and the general busbar must be supported by insulators, avoiding the transfer
of its own weight to the circuit breaker terminals. In the fixation of these busbars to the circuit breaker terminals, tighten the
M12 screw with 50 Nm torque.

Maximum Safe Distance A


The forces resulting from short circuits must not be absorbed by the circuit breaker terminals. Position insulators with
maximum clearance "A" between the terminals and the anchoring point. See table below:

Short circuit capacity (kA) 30 50 65 80 100 150


Length A (mm) 350 300 250 150 150 150

Air Circuit Breakers 49


www.weg.net

Curves
IDMTL Instantaneous - Ground Fault
10,000 100

5,000 50
40
30
2,000
20

1,000
10

500
5
4
200 3

2
100
t(s) t(s) 1
50

0.4
20
0.3

0.2
10

5 0.1

0.05
2

1 0.02

0.05
0.01
7

10

20
0.5

0.7

3
4
5
7
10

2
3
0.05
0.07
0.1

0.2

0.3
0.4
0.5
0.7
1

X Ir
X In

Pre Trip Alarm


500

200

100

50
40
30
20

10

5
4
3
t(s)
2

0.4
0.3
0.2

0.1

0.05

0.02

0.01
5

10

20
0.5

0.7

30
7

X Ip

50 Air Circuit Breakers


www.weg.net

Curves
Long Delay

5,000
2,000

1,000

500

200

100

50
40
30
20

10

t(s) 5
4
3
2

0.4
0.3
0.2

0.1

0.05

0.02

0.01
10

20
1

4
5

7
0.5

0.7

X Ir

Short Delay
5,000
2,000

1,000

500

200

100

50
40
30
20
10

t(s) 5
4
3
2

0.4
0.3
0.2

0.1

0.05

0.02

0.01
0.5

0.7

10

20

X Ir

Air Circuit Breakers 51


www.weg.net

RTC Wiring Diagram - Ready to Close


Function
Electrical signaling to indicate when the circuit breaker is ready to receive the close command after the following conditions:
circuit breaker open, spring loaded, no open command or alarm.

ABW ABWC
Internal Wiring Diagram for RTC Contact Internal Wiring Diagram for RTC Contact

xx
xx 32 34
21

Auxiliary switch

Axb
Auxiliary switch
Axb

31
22
U3 U1
83 413

Alarm TRIP 1 Springs Loaded

Axb
Springs Loaded 81

84 414
Alarm TRIP 1
KT KT

YY
82 U2

KT KT
KT = CWCA auxiliary contactor (not included in circuit breaker supply)
External terminals XX-YY=0 (command not enabled) YY
External terminals XX-YY=1 (command enabled)

Installation of the External Current Transformer


The external current transformer must be connected to the circuit breaker power supply conductors.
Both output signal conductors of the external current transformer secondary must be connected to terminals E1 and E2 of
the circuit breaker command connector.

The current transformer has a secondary of 5 A, and a conductor must be provided to connect the CT signal to the circuit
breaker for such current.

Legend of the CT Terminals


S T

ZCT

J Primary CT terminals: K, L
J Secondary CT terminals: K, L

52 Air Circuit Breakers


www.weg.net

ABW Wiring Diagram


This diagram considers the ABW in the inserted position, in the open position (OFF) and motor loaded.
In the withdrawable version (with truck), the truck release latch must be in the regular (released) position.

1)
354
351
CL1 (Connected)

352
361

364

Cell switch
14
CL2 (Connected)
13

Axa
NO

362
23

24
Axa

374
371
CL3 (Test)

34
33

372
Axa

384
381
44
43

Axa CL4 (Disconnected)

382
53

Axa 54
21

12

314
311
Axb CL1 (Connected)
OFF

312
21

22

Axb

Cell switch 4C
324
321
32
31

Axb CL2 (Connected)

322
41

42

Axb

331

334
CL3 (Test)
51

52

Axb

332
344
341
61

Axb CL4 (Disconnected)

342
414
413

Charged

Accessory code description:


U1

U2
M

Axb
Axa, Axb Auxiliary switch

L Long time delay trip indicator


CC

A2
A1

SI Short time delay/instantaneous


UVT SHT2 SHT1

C2
C1

Axa
G Ground fault trip indicator
C11

C12
or

CL1~CL4 Cell switch


D1

D2

M Motor
183

184

CC Closing coil
83

84
251

252

SHT1 Shunt tripping device 1


Power supply

R1

SHT2 Shunt tripping device 2


R2

UVT UVT coil


513

534 524

Common L
485+ R11 R22

SI Z1 Z2 ZSI input

Z3 Z4 ZSI output
485- 544

Reset G

E1 E2 ZCT

VN ~ V3 Voltage module
Z1

Z2

ZSI Input
311 ~ 314 Position switch
Z3

Z4

ZSI Output
Trip relay
ZCT
E1

E2

Terminal code description:


16
Voltage module

VN

13 14 63 64 Auxiliary switch “NO”


15

V3

11 12 61 62 Auxiliary switch “NC”


14

V2

413 414 Charged signal


13

V1

U1 U2 Motor charging
1
3
5
7

A1 A2 Closing coil

C1 C2 Shunt trip
Main circuit

C11 C12 2nd Shunt trip

D1 D2 Voltage input terminal of UVT

83 84 Alarm trip 1

183 184 Alarm trip 2


Ready to close, the circuit breaker is
251 252
turned off and the spring is loaded
ABW

R1 R2 Control power

513 ~ 544 Alarm contact LSIG

R11 R22 Alarm reset

Note: 1) Available on request. 485+ 485- RS485 Communication

Air Circuit Breakers 53


www.weg.net

ABWC Wiring Diagram


This diagram considers the ABWC in the inserted position, in the open position (OFF) and motor loaded.
In the withdrawable version (with truck), the truck release latch must be in the regular (released) position.

1)
351

382 384 372 374 362 364 352 354


CL1 (Connected)

11
14

Axc
ON

361
12

Cell switch
CL2 (Connected)

21
24

Axc

371
CL3 (Test)
22
34

31

381
Axc CL1 (Connected)
32
44

41

Axc

311

342 344 332 334 322 324 312 314


CL1 (Connected)
42

OFF

321

Cell switch
CL2 (Connected)

331
CL3 (Test)

341
CL4 (Disconnected)
U2
U1

Auxiliary position contacts, optional item for


M

the withdrawable circuit-breaker:


U3

Charged

311 ~ 344 Cell switch

Accessory code description:


UVT SHT2 SHT1 CC

A2
A1
D1 C11 C1

C12 C2

Axc Auxiliary switch

L Long time delay trip indicator


or

D2

SI Short time delay/instantaneous


/RES(+)

/RES(-)
181

182

G Ground fault trip indicator


82
81

CL1~CL4 Cell switch


252
251

M Motor
Power supply

R1

CC Closing coil
R2

SHT1 Shunt tripping device 1


R11 R22 513

544 534 524

Common L

SI SHT2 Shunt tripping device 2


Reset G UVT UVT coil
485+

485-

Z1 Z2 ZSI input
Z1

Z2

ZSI Input
Z3 Z4 ZSI output
Z3

Z4

ZSI Output
Trip relay
ZCT

E1 E2 External CT
E1

E2

VN ~ V3 Voltage module
VN
module
Voltage

485+ ~ 485- RS485 Communication


V3
V2

311 ~ 314 Auxiliary position switch


V1

Terminal code description:


11 12 ~ 41 42 Auxiliary switch “b” contact

11 14 ~ 41 44 Auxiliary switch “a” contact

U3 U2 Spring loaded

U1 U2 Motor of spring charging

A1 A2 Closing coil
Main circuit

C1 C2 Shunt trip

C11 C12 2nd shunt trip

D1 D2 Voltage input terminal of UVT

81 82 Alarm trip 1

181 182 Alarm trip 2


Ready to close, the circuit breaker is
251 252
turned off and the spring is loaded
ABWC

R1 R2 Control power

513 ~ 544 Alarm contact

Note: 1) Available on request. R11 R22 Alarm reset

54 Air Circuit Breakers


www.weg.net

Global presence is essential,


as much as understanding your needs.

Global Presence
With more than 30,000 employees worldwide, WEG is one of the largest electric motors, electronic equipments and systems
manufacturers. We are constantly expanding our portfolio of products and services with expertise and market knowledge. We
create integrated and customized solutions ranging from innovative products to complete after-sales service.

WEG’s know-how guarantees our Air Circuit Breakers are the right choice for your application and business, assuring safety,
efficiency and reliability.

Availability is to have a global support network

Partnership is to create solutions that suit your needs

Competitive edge is to unite technology and innovation

Know More
High performance and reliable
products to improve your
production process.

Excellence is to provide a whole solution in


industrial automation that improves
our customers productivity.

Visit: www.weg.net youtube.com/wegvideos

Air Circuit Breakers 55