Summary
Presentation 04
Benefits 05
Operation System 07
Main Applications 08
Construction Characteristics 09
General Characteristics 10
Coding 12
Accessories 14
Dimensions 35
Installation Recommendations 49
Curves 50
Wiring Diagram 52
www.weg.net
Weg line of air circuit breakers is used to protect electrical circuits against overloads and short
circuits, with microprocessed electronic protection. Developed for the industry, it integrates
technology and quality to improve the performance and safety of your applications. The circuit breaker has
a "stored-energy" operating mechanism with pre-charged springs. Those springs are manually charged
with the front lever or electrically charged with a motor, supplied as an accessory.
Offering a variety of accessories assembled at the factory, WEG air circuit breakers are the ideal solution
for different applications, including critical industries such as mining, oil and gas.
Benefits
Microprocessed electronic
protection unit
ABW800/ABW1600 ABW4000/ABW5000
In 800~1,600 A In 4,000~5,000 A
Icu = 65 kA @ 380 V Icu = 100 kA @ 380 V
Ics = 100% Icu Ics = 100% Icu
ABWC800/ABWC1600
In 800~1,600 A
Icu = 50 kA @ 380 V
Ics = 100% Icu
ABW2000/ABW2500/
ABW3200 ABW6300
In 2,000~3,200 A In 6,300 A
Icu = 85 kA @ 380 V Icu = 120 kA @ 380 V
Ics = 100% Icu Ics = 100% Icu
Ics = Icu @ 220 / 380 / 415 V Ics = Icu @ 440 / 480 / 500 V Ics = Icu @ 600 / 690 V
ABWC800/ABWC1600 50 kA ABWC800/ABWC1600 42 kA ABWC800/ABWC1600 42 kA
ABW800/ABW1600 65 kA ABW800/ABW1600 65 kA ABW800/ABW1600 50 kA
ABW2000/ABW2500/ABW3200 85 kA ABW2000/ABW2500/ABW3200 85 kA ABW2000/ABW2500/ABW3200 85 kA
ABW4000/ABW5000 100 kA ABW4000/ABW5000 100 kA ABW4000/ABW5000 85 kA
ABW6300 120 kA ABW6300 120 kA ABW6300 100 kA
Fixed Withdrawable
Operation System
The circuit breakers operate by means of a spring system, Remote operation is also possible by means of the closing
which can be manually charged with a front lever or and opening coils installed inside the circuit breaker. The
electrically charged with a motor (supplied as an accessory). closing coil has anti-pumping circuit, which prevents multiple
breaker closures.
When the springs are charged (situation in which the charge
indicator displays CHARGED), the circuit breaker is able to be There is also a front indicator of the circuit breaker state: ON
locally operated with the ON and OFF buttons. or OFF.
OFF Button
Spring Charge
ON/OFF Indicator Indicator
Regarding the installation, the circuit breakers can be supplied as fixed-mounted or withdrawable; the second version is
recommended for applications in which the occasional replacement or maintenance should be done as quickly as possible.
These circuit breakers can be positioned at three distinct points in the withdrawable rack:
Inserted: in this position both the power and control circuits are connected.
The position indicator shows CONNECTED.
Test: position in which only the control circuits are connected. The indicator
shows TEST.
Position
indicator Withdrawn: both circuits are disconnected. The indicator shows
DISCONNECTED.
Main Applications
Automotive Water
Construction Characteristics
Suspension Slots
OFF Button
ON Button
Operation Withdrawable
Counter Rack
General Characteristics
Circuit breaker ABWC08 ABWC16 ABW08 ABW16 ABW20 ABW25 ABW32 ABW40 ABW50 ABW63
Standard IEC 60947-2
Maximum rated current (40 °C) - In max. (A) 800 1,600 800 1,600 2,000 2,500 3,200 4,000 5,000 6,300
Current setting (0.4 ~1.0) x In max
Rated operational voltage - Ue (V) 690
Rated insulation voltage - Ui (V) 1,000
Impulse voltage - Uimp (kV) 12
Frequency (Hz) 50 / 60
Number of poles 3
Versions Fixed - withdrawable
Protection units LSIG Electronics
220 / 380 / 415 V 50 50 65 85 100 120
Rated ultimate short-circuit
440 / 480 / 500 V 42 42 65 85 100 120
breaking capacity - Icu (kA)
600 / 690 V 42 42 50 85 85 100
220 / 380 / 415 V 50 50 65 85 100 120
Rated service short-circuit
440 / 480 / 500 V 42 42 65 85 100 120
breaking capacity - Ics (kA)
600 / 690 V 42 42 50 85 85 100
1s 42 50 85 85 100
Rated short-time withstand current -
2s - 42 75 75 90
Icw (kA)
3s 25 36 65 65 85
220 / 380 / 415 V 143 187 220 264
Rated making capacity - Icm
440 / 480 / 500 V 88.2 143 187 220 264
(kA peak)
600 / 690 V 105 187 187 220
Utilization categories B
Opening (max.) 40
Operating time (ms)
Closing (max.) 80
Mechanical lifespan (number of Without maintenance 20,000 15,000 10,000 10,000
12,500
operations) With maintenance1) 30,000 20,000 15,000 15,000
Electrical lifespan (number of Without maintenance 5,000 5,000 2,000 2,000
6,000
operations) With maintenance1) 10,000 10,000 5,000 5,000
Altitude (m) ≤2,0002)
Operation -5...40 °C3)
Ambient temperature
Storage -20...60 °C
Withdrawable 38 61 85 143 184
Weight (kg)4)
Fixed 16 32 42 74 101
Connection terminals - Horizontal Standard Standard Standard Standard Standard
withdrawable/fixed Vertical Optional Optional Optional Optional Optional
Withdrawable 364 x 272 x 269 430 x 334 x 375 430 x 412 x 375 430 x 629 x 375 430 x 785 x 375
External dimensions H x W x D (mm)
Fixed 322 x 272 x 198 300 x 300 x 295 300 x 378 x 295 300 x 597 x 295 300 x 751 x 295
General Characteristics
Tightening torque
Screw Torque (kgf.cm) Tolerance Torque (N.m) Tolerance
Tightening torque of the
busbars at the rear M8 135 ±16 13.3 ±1.6
terminals for all M10 270 ±32 26.5 ±3.2
circuit breaker models
M12 480 ±57 46.6 ±5.6
Ratio-Corrector Factor
Altitude - h Rated operational voltage (V) Insulation voltage (V) Rated current reduction factor
h ≤2,000 m 690 1,000 1.00
2,000 < h ≤3,000 m 590 900 0.99
3,000 < h ≤4,000 m 520 700 0.96
4,000 < h ≤5,000 m 460 600 0.94
Coding
ABW 16 DN 3 - 16 AZ1 F - A 0 2 2 0
Maximum current Accessories
08 800 A No accessories
16 1,600 A B ON/OFF button lock
20 2,000 A K Key lock
25 2,500 A Phase sequence K2 Key interlock
32 3,200 A Mechanical interlock for 2 circuit
DN p/ 1,600 A - RST (N) M breakers1)
40 4,000 A ES p/ 2,000~3,200 A - RST (N) Mechanical interlock for 3 circuit
M3
50 5,000 A FS p/ 4,000~5,000 A - RST (N) breakers1)
63 6,300 A GS p/ 6,300 A - RST (N) D Door interlock
BK B+K
Number of poles B2 B+K2
Rated current 3 3P BM B+M
08 800 A BD B+D
16 1,600 A KM K+M
20 2,000 A KD K+D
25 2,500 A CP Profibus communication
Version Standard auxiliary contacts
32 3,200 A CM Modbus communication
F Fixed A 5NO+5NC
40 4,000 A
E Withdrawable Optional (withdrawable version)
50 5,000 A Undervoltage release
B Position auxiliary contact
63 6,300 A Standard
0 No release
Protection unit Optional
Standard unit 1 100~130 V ac/dc
LSIG + current - electronics power supply 100~250 V ac/dc and measurement frequency 2 200~250 V ac/dc
AZ1
60 Hz 3 24~30 V dc
Optional units 4 48~60 V ac/dc
000 No protection unit 5 380~480 V ac
LSIG + current - electronics power supply 100~250 V ac/dc and measurement frequency 6 200~250 V ac/dc with delay
AZ6
50 Hz 7 100~130 V ac/dc with delay
LSIG + current - electronics power supply 24~60 V dc and measurement frequency 8 48~60 V ac/dc with delay
AZ2
60 Hz LSI 9 380~480 V ac with delay
AZ7 LSIG + current - electronics power supply 24~60 V dc and measurement frequency 50 Hz
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and Standard opening coil
AF1
measurement frequency 60 Hz 2 200~250 V ac/dc
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and Optional
AF6
measurement frequency 50 Hz 0 No release
LSI + earth leakage + current - electronics power supply 24~60 V dc and measurement 1 100~130 V ac/dc
AF2
frequency 60 Hz 3 24~30 V dc
LSI + earth leakage + current - electronics power supply 24~60 V dc and measurement 4 48~60 V ac/dc
AF7 Motorized operator
frequency 50 Hz
Standard 5 380~480 V ac
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and
AC1 0 No motor operator
measurement frequency 60 Hz Standard closing coil
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and Optional
AC6 2 200~250 V ac/dc
measurement frequency 50 Hz 1 100~130 V ac/dc Optional
LSIG + current + communication2) - electronics power supply 24~60 V dc and 2 200~250 V ac/dc
AC2 0 No release
measurement frequency 60 Hz
3 24~30 V dc 1 100~130 V ac/dc
LSIG + current + communication2) - electronics power supply 24~60 V dc and
AC7 4 48~60 V ac/dc 3 24~30 V dc
measurement frequency 50 Hz
5 380 V ac 4 48~60 V ac/dc
LSIG + voltage + current + communication2) - electronics power supply
PC1 6 480 V ac 5 380~480 V dc
100~250 V ac/dc and measurement frequency 60 Hz
LSIG + voltage + current + communication2) - electronics power supply
PC6 Accessories supplied as standard for the entire range
100~250 V ac/dc and measurement frequency 50 Hz
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc and Auxiliary contacts (5NO+5NC)
PC2
measurement frequency 60 Hz
Alarm contacts
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc and
PC7 Opening coil 200~250 V ac/dc
measurement frequency 50 Hz
Closing coil 200~250 V ac/dc
Accessories supplied as optional items Operation counter
Motorized operator Door frame Position locking with padlock (padlock not included) - withdrawable version
Undervoltage release Transparent cover Position indicator (Inserted /Test/ Withdrawn) - withdrawable version
Condenser trip device Mechanical interlock
Key lock Door interlock
Key interlock Position auxiliary contact
Coding
ABWC 16 DN 3 - 16 AZ1 F - C 0 2 2 0
Accessories
No accessories
Maximum current B ON/OFF button lock
08 800 A Phase sequence K Key lock
16 1,600 A DN p/ 1,600 A - RST (N) K2 Key interlock
Mechanical interlock for 2 circuit
M breakers1)
Rated current
Number of poles Mechanical interlock for 3 circuit
08 800 A M3 breakers1)
3 3P
16 1,600 A D Door interlock
BK B+K
B2 B+K2
BM B+M
Version BD B+D
F Fixed Standard auxiliary contacts KM K+M
E Withdrawable C 4NO+4NC KD K+D
FF Fixed - Front Optional (withdrawable version) CP Profibus communication
D 4C position auxiliary contact CM Modbus communication
E 8C position auxiliary contact
Undervoltage release
Standard
Protection unit
0 No release
Standard unit
Optional
LSIG + current - electronics power supply 100~250 V ac/dc and measurement
AZ1 1 100~130 V ac/dc
frequency 60 Hz
2 200~250 V ac/dc
Optional units
3 24~30 V dc
000 No protection unit
4 48~60 V ac/dc
LSIG + current - electronics power supply 100~250 V ac/dc and measurement
AZ6 5 380~480 V ac
frequency 50 Hz
6 200~250 V ac/dc with delay
LSIG + current - electronics power supply 24~60 V dc and measurement frequency
AZ2 7 100~130 V ac/dc with delay
60 Hz
8 48~60 V ac/dc with delay
LSIG + current - electronics power supply 24~60 V dc and measurement frequency
AZ7 9 380~480 V ac with delay
50 Hz
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and
AF1 Standard opening coil
measurement frequency 60 Hz
LSI + earth leakage + current - electronics power supply 100~250 V ac/dc and 2 200~250 V ac/dc
AF6 Optional
measurement frequency 50 Hz
LSI + earth leakage + current - electronics power supply 24~60 V dc and 0 No release
AF2
measurement frequency 60 Hz 1 100~130 V ac/dc
LSI + earth leakage + current - electronics power supply 24~60 V dc and 3 24~30 V dc
AF7
measurement frequency 50 Hz 4 48~60 V ac/dc
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and 5 380~480 V ac
AC1
measurement frequency 60 Hz
LSIG + current + communication2) - electronics power supply 100~250 V ac/dc and Standard closing coil
AC6 Motorized operator
measurement frequency 50 Hz 2 200~250 V ac/dc
LSIG + current + communication2) - electronics power supply 24~60 V dc and Standard Optional
AC2
measurement frequency 60 Hz 0 No motor operator 0 No release
LSIG + current + communication2) - electronics power supply 24~60 V dc and Optional 1 100~130 V ac/dc
AC7
measurement frequency 50 Hz 1 100~130 V ac/dc 3 24~30 V dc
LSIG + voltage + current + communication2) - electronics power supply 2 200~250 V ac/dc 4 48~60 V ac/dc
PC1
100~250 V ac/dc and measurement frequency 60 Hz
3 24~30 V dc 5 380~480 V dc
LSIG + voltage + current + communication2) - electronics power supply
PC6
100~250 V ac/dc and measurement frequency 50 Hz
Accessories supplied as standard for the entire range
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc
PC2
and measurement frequency 60 Hz Auxiliary contacts (4NO+4NC)
LSIG + voltage + current + communication2) - electronics power supply 24~60 V dc Alarm contacts
PC7
and measurement frequency 50 Hz
Opening coil 200~250 V ac/dc
Accessories
Auxiliary Contacts
They indicate the circuit breaker status, ON or OFF. For ABW there are 5 Axa contacts (NO) and 5 Axb contacts (NC) and for
ABWC there are 4 Axc contacts (NOC).
Configuration Resistive load Inductive load
125 V ac 10 6
250 V ac 10 6
460 V ac 5 6
Switching capacity (A)
30 V dc 10 6
125 V dc 0.6 0.6
250 V dc 0.3 0.3
Auxiliary contact
Alarm Contacts
These contacts are incorporated in the protection units and indicate the occurrence of a trip by any of the protection functions.
The contacts are Alarm 1, Alarm 2 and Contacts 524, 534 and 544.
Configuration 2NO (generic) + 4NO (individual)
250 V ac 5
380 V ac 3
Switching capacity (A)
30 V dc 5
125 V dc 1
Minimum application levels 5 V dc / 10 mA
Accessories
Closing Coil
This coil allows closing the circuit breaker by means of electrical control. This remote control is valid only if the springs of the
operating mechanism are charged. This accessory is supplied as standard at voltage 250 V ac/V dc. The closing coils are
interchangeable with the ABWC line.
Characteristics Specification
Reference ABW-BF C34 ABW-BF E27 ABW-BF E10 ABW-BF E12 ABW-BF D85
Code 11193568 11193767 11193789 11193790 11193795
Power supply 24~28 V dc 48~60 V ac/dc 100~130 V ac/dc 200~250 V ac/dc 380~480 V ac
Operation voltage 0.75...1.1 x Un
Energization 200
Consumption (VA)
Steady-state 5
Closing time (ms) ≤80
Anti-pumping characteristic Yes, through electronic circuit
Minimum supply time for operation (ms) 200
Standard
Power supply Reference
200...250 V ac/dc ABW-BF E12
Closing coil
Accessories
Opening Coil
This coil allows opening the circuit breaker by means of Standard
electric control. This accessory is supplied as standard Power supply Reference
at voltage 250 V ac/V dc. The opening coils are 200...250 V ac/dc ABW-BA E12
interchangeable with the ABWC line.
Characteristics Specification
Reference ABW-BA C34 ABW-BA E27 ABW-BA E10 ABW-BA E12 ABW-BA D85
Code 11193796 11193875 11193879 11193880 11193881
Power supply 24~28 V dc 48~60 V ac/dc 110~130 V dc 200~250 V dc 380~480 V ac
Operation voltage 0.75...1.1 x Un
Energization 200
Consumption (VA)
Steady-state 5
Opening time (ms) ≤40
Anti-pumping characteristic Yes, through electronic circuit
Minimum supply time for operation (ms) 200
Opening coil
Motor Operator
The motorized drive is used for the automatic charging of the springs of the circuit breaker operating mechanism. The operation
begins immediately after the circuit breaker opens and, at the end of this process, an auxiliary contact indicates that the springs
are charged. Even if the motorized drive is installed, it is also possible to charge the springs manually through the front lever.
The standard circuit breaker allows charging the spring in the ON position.
Characteristics Specification
Reference ABW-AM E10 ABWC-AM E10 ABW-AM E12 ABWC-AM E12 ABW-AM C34 ABWC-AM C34 ABW-AM E27 ABW-AM D33 ABW-AM D74
Code 11193480 14794817 11193484 14794848 11193457 14794850 11193478 11193486 11193487
Power supply 100~130 V dc/ac 100~130 V dc/ac 200~250 V ac/dc 200~250 V ac/dc 24~28 V dc 24~28 V dc 48~60 V ac/dc 380 V ac 440 V dc
Rated current (A) 1 1 0.5 0.5 5 5 3 0.3 0.3
Starting current (A) 5 x rated current
Motor speed (rpm) 1,500~1,900 rpm
Charge time
≤5
(for spring charging) (s)
Motorized operator
Accessories
Charged Spring Auxiliary Contact
It is supplied incorporated to the motorized drive. This auxiliary contact sends a signal when the motor is charged. It has two
open contacts: 1 used for communication in general, and the other used for springs charged indication.
Undervoltage Release
It automatically disconnects the circuit breaker in cases of undervoltage or phase loss. Interchangeable with the ABWC line.
Characteristics Specification
Reference ABW-UVT E10 ABW-UVT E12 ABW-UVT E55 ABW-UVT C34 ABW-UVT E27
Code 11193884 11193888 11193854 11193882 11193883
Power supply 100~130 V ac/dc 200~250 V ac/dc 380~480 V ac 24~28 V dc 48~60 V ac/dc
Operation voltage range 0.65...0.85 x Un
Drop-out voltage range 0.4...0.6 x Un
Trip time (instantaneous) ≤50ms
Energization 200
Consumption (VA or W)
Steady-state 5
Undervoltage release
a c b
0.5 1
Signal for
Signal for
Characteristics Specification tripping
tripping
1.5
5 7
3
Reference ABW-UDC E10 ABW-UDC E12 ABW-UDC E55 ABW-UDC E27 DC48~60 V
AC48 [seg]
Code 11193451 11193452 11193453 11193406
ABW UDC
Power supply 100~130 V ac/dc 200~250 V ac/dc 380~480 V ac 48~60 V ac/dc 5 7
Time
Timedelay
delayfor
forUVT
UVT
Operation voltage range 0.65...0.85 x Un
14 16
Drop-out voltage range 0.4...0.6 x Un
Time delay (s) 0.5 - 1 - 1.5 - 3
Energization 200 Instantaneous
Consumption (VA) trip command
Steady-state 5
D1
D2
ABW UVT
Note: 18 = Common
19 = Normally Closed
20 = Normally Open.
Accessories
ABW Position Auxiliary Contact
It is a contact that indicates the current position of the ABW (CONNECTED, TEST, DISCONNECTED)
( � Common use for all models)
Operating Characteristics
Disconnected Connected
ABW position
Disconnected Test Connected
CL1, CL2 ON
Contact operation
OFF
(Connected)
CL3 ON
OFF
(TEST)
CL4 ON
(Disconnected) OFF
460 5 2.5
Contact capacity
AC 250
10 10
125
250 3 1.5
DC 125 10 6
30 10 10
342 344 332 334 322 324 312 314 382 384 372 374 362 364 352 354
NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO
Installation Method
Install the position auxiliary contact on the right plate, as
shown in the figure, since it is interlocked with the main
shaft in the truck.
Accessories
ABWC Position Auxiliary Contact
ABWC
position
auxiliary
contact
� It
is a contact that indicates
Operating Characteristics
Disconnected Connected
ABWC position
Disconnected Test Connected
CL1, CL2 ON
(Connected) OFF
CL3 ON
Contact operation OFF
(TEST)
CL4 ON
(Disconnected) OFF
460 5 2.5
AC 250
10 10
Contact capacity 125
250 3 1.5
DC 125 10 10
30 10
Accessories
Key Lock
Key Interlock
g Lock/ g g g
OFF OFF
circuit breaker OFF g g g
OFF ON Circuit
breaker
3
g g g
ON OFF
Notes: 1) W
hen the key releases the circuit breaker, it is not possible to remove it from the interlock. Only in this
position is it possible to close the circuit breaker.
2) It is not possible to actuate the air circuit breaker locally or remotely (by closing coil) with the key interlock
actuated. The key is able to be removed only when the interlock in actuated.
Accessories
Position Locked by Padlock
ON/OFF
button lock
Rear Terminals
ABW and ABWC circuit breakers can be supplied with the terminals in the Horizontal (Standard) or Vertical (Optional) position.
To change the terminals from horizontal to vertical on models ABWC and ABW up to 3,200 A, the terminal is simply rotated
and tightened according to the tightening torque table on page 10.
For models ABW40, ABW50 and ABW63, the terminals need to be replaced with different models to allow their rotation.
Below are the codes for the vertical terminal models.
This device electrically trips the circuit breaker within a preset time when the
control power is OFF. It discharges a capacitor by directly operating the
opening coil. It includes a lamp to indicate whether the capacitor is charged
and a discharge button. Installation on panel door.
Characteristics Specification
Reference ABW-CTD D58 ABW-CTD D64
Power supply (V ac) 100...110 200...220
Operation voltage 0.85...1.1 x Un
Frequency (Hz) 50/60
Charging time (s) Up to 5 seconds
Possible trip time (m) Up to 3 minutes Up to 2 minutes
Code 11193370 11193376
Accessories
Wiring Diagram
Circuit
Condenser trip device OFF breaker
button
Opening
C1 D1 R1 C6 S+
coil
SW1 R3
AC Discharge DC
TNR C button
(Input) (Output)
R2 Lamp
C3 S5 S-
124
117
75 15
15,3
66,5
75
Door Frame
Panel
Rubber Frame
Door
frame
Circuit breaker
Accessories
Door Frame
Installation Method
Insert the door frame into the panel door cut-out and secure it with 10 M5 screws.
Transparent Cover
Panel door
It allows viewing the circuit breaker without opening the panel door. It can be opened or
closed with the circuit breaker in all positions: withdrawn, in test or in operation. Also used
for the fixed version.
Notes: 1) Protection only against dust, which is the agent that causes faults in this type of product and installation.
2) The Transparent Cover can be closed even if the withdrawable circuit breaker is in the test position.
Accessories
Mechanical Interlock
For mechanical interlock between two circuit breakers, consider the following interlock options:
Accessories
Mechanical Interlock
For mechanical interlock between three circuit breakers, consider the following interlock options:
1 2 3
0: circuit breaker OFF
O O O
circuit I: circuit breaker ON
breaker circuit I O O It allows the status of two circuit breakers ON and a circuit
1 circuit breaker
breaker 2 3 I I O
O breaker OFF.
I I
O O The mechanical interlock cables length between circuit breaker
O O
I I 1 and 2 is 1.3m and between circuit breaker 2 and 3 is 1.3 m.
I O I
I O
I O I
Door Interlock
Accessories
Communication Module
The communication module is an optional item that has an I/O unit, enabling the
circuit breaker remote operation. All ABW and ABWC circuit breakers, with
protection units A and P, are able to communicate via network, allowing the user
to verify the status of the circuit breaker and operate it through a Modbus or
Profibus-DP network.
The communication module can be installed either on the circuit breaker
withdrawable rack (withdrawable version) or on a DIN rail.
1. Modbus/RS485 communication: two types of Modbus communication are
available:
� Reading: for an only-reading communication, the circuit breaker must be
Wiring diagram with the ABW-CP and ABW-CM modules: Circuit breakers Reference Code
ABW08...63
ABW-CP 11193400
ABWC08...16
CN4-1
CN4-1
ABW08...63
ABW-CM 11193398
ABW-CM
ADW-CM 485+
485+ terminal
terminal ABWC08...16
ou
or
ABW-CP CN4-3
CN4-3
485- terminal
485- terminal
DI_COM 7
9 RS485(-) 19
RS485(+) 20 *
10
11
Modbus
RS485 Profibus-DP
12
Note: if using Profibus-DP communication, it must communicate with the circuit breaker trip relay.
Accessories
Communication Module
J he remote I/O unit has the I/O contact that can remotely trip
T
or close the ACB via communication.
J For the general DO, the output of DI1 or DI2 is selectable.
J The remote I/O unit communicates basically via Modbus/
RS485; Profibus-DP has to be purchased separately.
J It supports the SBO (Select Before Operation) function and
ensures control reliability.
J The remote I/O unit can be installed on the ACB truck or
inside the panel.
LED Status
1 DI1 Indicates the condition of digital input 1
2 DI2 Indicates the condition of digital input 2
- Baud rate settings 3 DO ON Indicates that the temperature alarm output is ON
- Communication 4 DO OFF Indicates that the temperature alarm output is OFF
address settings 5 Circuit breaker ON Indicates the closed circuit breaker condition
- Temperature settings 6 Circuit breaker OFF Indicates the open circuit breaker condition
7 Operation LED Indicates the operating condition of the unit
Circuit breaker Indicates a disconnection/circuit breaker terminal control error
8
ERROR condition
Dimensions
WEG CT (Ratio 30/5 A)
A
C
F G
Accessories
Protection Units
On the ABW and ABWC air circuit breakers, the ABW-OCR microprocessed electronic protection units perform the protections.
The AZ1 unit is supplied as standard for all circuit breakers and offers protection against overload (L), timed short circuit
(S), instantaneous short circuit (I) and ground fault (G)—functions which are set on the front dials. Other models are
supplied as optional accessories, allowing network communication, voltage measurement, earth leakage protection (external
CT required - supplied as optional accessory) and other protections.
Circuit breaker model Code Reference Protection unit supply voltage Protection unit measurement frequency
ABWC-AZ1 100~250 V ac/dc 60 Hz 60 Hz
14794814
ABWC-AZ6 100~250 V ac/dc 50 Hz 50 Hz
LSIG protection + current reading
ABWC-AZ2 24~60 V dc 60 Hz
15019080
ABWC-AZ7 24~60 V dc 50 Hz
ABWC-AC1 100~250 V ac/dc 60 Hz 60 Hz
14794811
ABWC-AC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + current reading
ABWC-AC2 24~60 V dc 60 Hz + communication
ABWC 15019085
ABWC-AC7 24~60 V dc 50 Hz
ABWC-AF1 100~250 V ac/dc 60 Hz 60 Hz LSIG protection + ground fault +
14794810
ABWC-AF6 100~250 V ac/dc 50 Hz 50 Hz current reading
ABWC-PC1 100~250 V ac/dc 60 Hz 60 Hz
14794812
ABWC-PC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + voltage and
ABWC-PC2 24~60 V dc 60 Hz current reading + communication
15019083
ABWC-PC7 24~60 V dc 50 Hz
ABW-AZ1 100~250 V ac/dc 60 Hz 60 Hz
11321384
ABW-AZ6 100~250 V ac/dc 50 Hz 50 Hz
LSIG protection + current reading
ABW-AZ2 24~60 V dc 60 Hz
11912860
ABW-AZ7 24~60 V dc 50 Hz
ABW-AC1 100~250 V ac/dc 60 Hz 60 Hz
11321408
ABW-AC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + current reading
ABW-AC2 24~60 V dc 60 Hz + communication
11912797
ABW-AC7 24~60 V dc 50 Hz
ABW
ABW-AF1 100~250 V ac/dc 60 Hz 60 Hz
11321386
ABW-AF6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + ground fault +
ABW-AF2 24~60 V dc 60 Hz current reading
12670394
ABW-AF7 24~60 V dc 50 Hz
ABW-PC1 100~250 V ac/dc 60 Hz 60 Hz
11321410
ABW-PC6 100~250 V ac/dc 50 Hz 50 Hz LSIG protection + voltage and
ABW-PC2 24~60 V dc 60 Hz current reading + communication
11912858
ABW-PC7 24~60 V dc 50 Hz
Accessories
AZ1
Reading Communication Power supply
A Current Z No communication Code OCR Line reading frequency
P Current and voltage C With communication 1 100~250 V ac/dc 60 Hz
F Earth leakage 2 24~60 V dc 60 Hz
6 100~250 V ac/dc 50 Hz
7 24~60 V dc 50 Hz
AZ AC AF PC
110...250 V ac/dc 110...250 V ac/dc 110...250 V ac/dc 110...250 V ac/dc
Power supply
24...60 V dc 24...60 V dc 24...60 V dc 24...60 V dc
Consumption 5 VA 5 VA 5 VA 5 VA
1/2 60 Hz 60 Hz 60 Hz 60 Hz
Line frequency
6/7 50 Hz 50 Hz 50 Hz 50 Hz
L - Overload 3 3 3 3
S - Short circuit (timed) 3 3 3 3
Standard
I - Short circuit (instantaneous) 3 3 3 3
G - Ground fault 3 3 7 3
Earth leakage (external CT required - option) 7 7 3 7
Protection
ZSI (protective coordination) 3 3 3 3
functions
Under and overcurrent 7 7 7 3
Optional Frequency out of range 7 7 7 3
Unbalance (current/voltage) 7 7 7 3
Pre-trip alarm 7 7 7 3
Discrimination / trip type indication 3 (LEDs / aux. cont.) 3 (LEDs / aux. cont.) 3 (LEDs / aux. cont.) 3 (LEDs / aux. cont.)
Current (R / S / N / T) 3 3 3 3
Current / Voltage RMS 7 7 7 3
Measurements
Power (P, Q, S), FP (3 phases) 7 7 7 3
Frequency 7 7 7 3
Fault recording 3 3 3 3
Number of records 10 10 10 256
Event sequence 3 3 3 3
Broken current value 3 3 3 3
Total breaking time 3 3 3 3
Event recording 7 7 7 256
Digital outputs 3 fixed 3 fixed 3 fixed 3 programmable
Front adjustment knobs 3 3 3 3
Parameterization Display + navigation keys 3 3 3 3
Parameterization password 3 3 3 3
Door 7 RS485 7 RS485
Network communication Protocol 7 Modbus / Profibus1) 7 Modbus / Profibus1)
9,600 bps, 19,200 bps, 9,600 bps, 19,200 bps,
Baud rate 7 7
38,400 bps 38,400 bps
Note: 1) In order to use network communication, see the Communication Module topic in this catalog.
Accessories
Type A
Technical Data
The ABW-OCRAZ1 protection unit has
characteristics that meet the requirements of most
systems and applications. It is supplied as standard
for ABW08...63 circuit breakers.
g Overload protection (L)
g Long timing
g Instantaneous (I)
g I2 t ON/OFF optional
g Up to 10 faults
g Modbus/RS485
g Profibus-DP
Display
The home screen indicates the instantaneous current
values per phase. It is also possible to check other
information, available in different menus.
Indication LEDs
Accessories
Type A
Protection
t Long time
Iu = In×... 0.5 0.6 0.7 0.8 0.9 1.0 -
Ir Current setting (A)
Ir = Iu×... 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1.0
t tr@ (1.5×lr) 12.5 25 50 100 200 300 400 500 OFF
Time delay (s)
Precision ±15% tr@ (6.0×lr) 0.5 1 2 4 8 12 16 20 OFF
t Ir 100ms
tr tr@ (7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 OFF
Ir Short time
lsd Current setting (A)
Precision ±10%
Isd = Ir×... 1.5 2 3 4 5 6 8 10 OFF
tr
tsd tsd
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
tr lsd Time delay (s) I2t ON 0.1 0.2 0.3 0.4 -
Ii @ 10×Ir Minimum 20 80 160 260 360 -
(I2t OFF) opening
lsd tsd time 80 140 240 340 440 -
I
tsd Ii Instantaneous
Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 OFF
Ii I Opening time Below 50ms
I
t
t
t
Ig
Ground fault
Operating current (A)
Precision: ±10% (Ig>0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 OFF
Ig ±20% (Ig≤0.4In)
tg
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
Ig tg
I2t ON 0.1 0.2 0.3 0.4 -
tg Time delay (s)
Minimum
opening 20 80 160 260 360 -
I @ 1×In time
tg (I2t OFF)
Maximum
opening 80 140 240 340 440 -
I time
I
I
Accessories
Type P
Technical Data
This unit was developed for applications with high technical
requirements. Available for the entire ABW line.
g Overload protection (L)
g Long timing
g Instantaneous (I)
g I2 t ON/OFF optional
g Network communication
g Modbus/RS485
g Profibus-DP
Display
The home screen indicates the instantaneous current values per phase.
It is also possible to check other information, available in different
menus.
Indication LEDs
LED Function
Alarm Overload alarm (L)
SP Indicates self-protection and battery test
IR Indicates timed short circuit tripping (S)
Isd/Ii Indicates instantaneous short circuit tripping (I) Setting of the Protection Functions
Ig Indicates ground fault (G)
Comm Indicates communication status (optional)
Navigation Keys
Accessories
Type P
Protection
Long time
Current setting (A) Ir = In×... 0.4 0.5 0.6 0.7 0.8 0.9 1.0 -
t tr@ (1.5×lr) 12.5 25 50 100 200 300 400 500 OFF
Time delay (s)
t Ir Precision: ±15% tr@ (6.0×lr) 0.5 1 2 4 8 12 16 20 OFF
100ms
tr@ (7.2×lr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 OFF
Ir Short time
Current setting (A)
Isd = Ir×... 1.5 2 3 4 5 6 8 10 OFF
tr Precision: ±10%
tr tsd
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
lsd I2t ON - 0.1 0.2 0.3 0.4 -
lsd tsd Time delay (s)
Minimum
opening 20 80 160 260 360 -
@ 10×Ir time
tsd Ii (I2t OFF)
Maximum
opening 80 140 240 340 440 -
Ii time
I
Instantaneous
I Current setting (A) Ii = In×... 2 3 4 6 8 10 12 15 OFF
Opening time Below 50ms
t
t Ground fault
Operating current (A)
Precision: ±10% (Ig>0.4In) Ig = In×... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1.0 OFF
±20% (Ig≤0.4In)
I2t OFF 0.05 0.1 0.2 0.3 0.4 -
tg
Ig I2t ON - 0.1 0.2 0.3 0.4 -
Ig Time delay (s)
Minimum
opening 20 80 160 260 360 -
@ 1×In time
(I2t OFF)
tg Maximum
opening 80 140 240 340 440 -
tg time
I
I
I
I
Operation Time delay (s)
Other protections
Setting range Measurement Precision Setting range Measurement Precision
Undervoltage 80 V ~ 0 V_Operation 1V ±5%
Overvoltage UV_Operation ~ 980 V 1V ±5% 1.2 ~ 40s
Unbalance voltage 6% ~ 99% 1% ±2.5% ou (*±10%)
Reverse power 10~500 kW 1 kW ±10%
0.2 ~ 40s
Overpower 500~5,000 kW 1 kW ±10%
0.1s ±0.1s
Unbalance current 6% ~ 99% 1% ±2.5% ou (*±10%)
60 Hz UF_Operation ~ 65 1 Hz ±0.1 Hz
Over-frequency
50 Hz UF_Operation ~ 55 1 Hz ±0.1 Hz 1.2 ~ 40s
60 Hz 55 Hz ~ OF_Operation 1 Hz ±0.1 Hz
Under-frequency
50 Hz 45 Hz ~ OF_Operation 1 Hz ±0.1 Hz
Dimensions
ABWC08...16DN3F_H - Fixed Version
Front View Horizontal Rear Terminal - Side Vertical Rear Terminal - Side
View View
Ø9 33
15
15
50
322
283
261.1
150
125
248
150
2-Ø11
25
15
49.5
62
32
13 37.5
37.5
87.1 92.5 51.5
87.1 92.5 51.5
72.5 72.5
13
15 10
13
15 10 2-Ø11
15
50
322
70
70
70
70
15
72,5
25
15
.5
.5
R4
R4
50
50
25
15
15
25
Ø1111
Dimensions
Front View Horizontal Rear Terminal - Side Vertical Rear Terminal - Side
View View
272.2
93.8
111.3
15
50
364.3
150
150
25
Ø8,5
Ø8,5
70.5
88
56
56
256
75 170.5 75 170.5
2-Ø11
57.7
15
57.7
50
70
4-Ø8.5
70
140
140
70
70
4-Ø8.5
25
2,205 15 56
56
3,461
87,91
50
0,984
25
15 15
25
2x0,433
Ø11
2x 11
Dimensions
ABWC08...16 - Fixed Version - Front Terminal
9 99
15
1155
72,5
2,5
772.5
9 353,37
353,37
353.37
125
125
125
15
15
15
15
72,5
Ø99 9
353,37
272,4272,4
272.4
246,4
246.4 246,4
272,4
46,4
Side View
190,5190,5
190,5
190.5
Dimensions
ABW08...16 - Fixed Version
Front View Horizontal Rear Terminal - Side View
90
300
280 Insulation
barrier
150
15
Operating panel
center
15
270
118
133
300
270
320
59.5 15
67
35
65 20 165 45
35
20
295 32.5
12 165 165 12
354
Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
90 85 85
(Insulation
(Insulation 50
barrier)
barrier)
15
15
45
25
50
270
165
133
83
83
42 50
20
67
35
35
4 - Ø14 Assembly
hole
65 20 165
165 45
45
20 295 32.5 330
354
15
15
15
45
45
25
25
50
165
165
2 - Ø13
20
4- Ø14
4- 14
Mountinghole
Assembly hole
330
330
354
354
3P
3P
Dimensions
ABW08...16 - Withdrawable Version
Front View Horizontal Rear Terminal - Side View
20 394 20 Disconnected & Test Zero arc space
50 Connected
167
Insulation
15 55
barrier
90
2-M12 Tap
CMB-U/F
15
430
405
270
350
133
41 18
97
60 200 115
6
260 375
10 38.5
334
4 - Ø13 Mounting hole
Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected
Disconnected & Test& Test 85 85
50
50 Connected
Connected 50
15
15 55
55 Arc chutesurface
ARC Chute surface
90
90
(Insulation
(Insulation
barrier)
barrier)
115
50
50
270
270
200
133
350
350
133
41 18
18
97
97
41
60
60 200
200 115
115
66
10
10 375
375 38.5
38.5 260
6- 6
13-Mounting
Ø13 Mounting
hole hole 334
15
115
115
50
25
2 - Ø13
200
200
260
260
334
334
33PP
Dimensions
ABW20...32 - Fixed Version
Front View Horizontal Rear Terminal - Side View
378 90
189 189
Insulation
280 barrier
15
Operating panel
center
20
270
300
270
113
133
320
20
67
57
35
35
20
Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
90
90 115 115
(Insulation
(Insulation 75
barrier)
barrier)
15
45
25
75
165
270
133
133
58
58
20
75
75
4 - Ø14
Mounting hole
67
67
35
35
408
432
65
65 20 165 45
45
29.5
29.5
295 32.5
32.5
25
75
165
25
3 - Ø13
20
20
4- 14
4 - Ø14
Mounting hole
Mounting hole
408
408
432
432
33PP
Dimensions
ABW20...32 - Withdrawable Version
Front View Horizontal Rear Terminal - Side View
20 472 20 Disconnected & Test
206 50 Connected Zero arc space
15 55
Insulation
barrier
90
2-M12 Tap
CMB-U/F
20
430
405
270
350
133
41 18
97
260 6 60 200 115
412 10 375 38.5
6 - Ø13 Mounting hole
Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected & Test
Disconnected & Test 115 115
50
50 Connected
Connected 75
15
15 55
55
ARCchute
Arc Chute surface
surface
90
90
(Insulation
barrier)
barrier)
115
75
75
270
270
200
350
350
133
133
41 18
18
97
97
41
60
60 200
200 115
115 260
6
10
10 375
375 38.5
38.5 412
6- 13 Mounting hole
6 - Ø13 Mounting hole
25
75
25
200
200
3 - Ø13
260
260
412
412
3P
3P
Dimensions
ABW40...50 - Fixed Version
Front View Horizontal Rear Terminal - Side View
90
595
280 Insulation
150 barrier
15
Operating panel
center
20
70
20
270
270
300
193
83
380
70 20
60 35
95
80
42 20
97
95
18
12 460 165 12
649
65 20 165 45
295 67.5
Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
90 190 190
(Insulation
(Insulation 125
barrier)
15
45
125
125
270
270
165
183
183
58
20
125
4 - Ø14
Mounting hole
625
102
102
95
95
649
39.5
20.5
39.5
20.5
65
65 20 165
165 45
45
295
295 67.5
67.5
20 70 20 15
20 70 20
25
45
25
125
25
165
165
25
20
20
5 - Ø13
4- 14
4 - Ø14
Mounting hole
625
625 Mounting hole
649
649
3P
3P
Dimensions
ABW40...50 - Withdrawable Version
Front View Horizontal Rear Terminal - Side View
Disconnected & Test Zero arc space
20 689 20
50 Connected
147.5 Operating panel
center 15 55
90
Insulation
barrier
2-M12 Tap
CMB-U/F
20
460
110
70
435
20
270
193
380
83
110
295 260
36 41 18
629
97
42
200 115
10 375 63.5
Vertical Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected &&Test
Disconnected Test 190 190
50 Connected
Connected
125
15
15 55
55 Arc chute surface
Arc surface
90
(Insulation
barrier)
barrier)
115
125
125
A
270
270
200
183
380
58
380
58
125
18
4118
36 41
120
102
295 260
39.5
39.5
36
200
200 115
115
10
10 375
375 53 .5
53.5
6-- 13
6 Ø13Mounting
Mountinghole
hole
25
125
25
200
200
25
5 - Ø13
295
295 260
260
33PP
Dimensions
ABW63 - Fixed Version
15
center
20
70
300
270
20
270
380
193
83
20
60 35
95
80
70
12 577 204 12
18
42 20
805
97
95
65 20 165 45
295 67.5
0 A ~5 0 0Vertical
0 A Rear Terminal - Side View Horizontal Rear Terminal - Top View
90
244 244
(Insulation
(Insulation 150
barrier)
barrier)
15
45
125
165
270
270
183
58
20
4 - Ø14
125
Mounting
781 hole
805
102
102
95
95
39.5
39.5
20.5
20.5
65 20 165
165 45
295 67.5
25
165
165
150
25
25
20
20
44-- 14
25
Ø14
Mounting
781
781 Mounting
hole
hole
805
805
6 - Ø13
3P
4 0 0 0 A ~5 0 0 0 A
90
(Insulation
barrier)
15
Dimensions
70 20
460
435
110
20
270
193
380
83
260 113 260
110
36 41 18
785
97
42
200 115
10 375 63.5
6 - Ø13 Mounting hole
3P
4 0 0 0 A ~Vertical
5 0 0 0 A Rear Terminal - Side View Horizontal Rear Terminal - Top View
Disconnected & Test 244 244
Disconnected & Test
50
50 Connected
Connected 150
Arc chute
Arc chutesurface
surface
15
15 55
55
90
90
(Insulation
(Insulation
barrier)
barrier)
115
125
125
A
270
270
183
380
58
183
380
58
200
125
125
36 4118
41 18
102
102
39,5
39.5
36
200
200 115
115 260 113 260
10
10 375
375 53.5
53.5
6- 13 Mounting hole
102 6 - Ø13 Mounting hole
Vertical type
Vertical Rear Terminal - Top View Rear Terminal Dimensions
244
244 244
244 34
20
20 70
70 20
20 15
25
115
115
25
150
25
25
200
200
25
6 - Ø13
260
260 113
113 260
260
3P
3P
4 0 0 0 A ~5 0 0 0 A
Disconnected & Test
50 Connected
15 55 Arc chute surface
90 Air Circuit Breakers 45
(Insulation
barrier)
www.weg.net
Dimensions
Panel Cutout - Fixed Version
ABW08...32
10 - Ø9
315 (Panel cutout)
100
100
165 165
ABW40...63
10 - Ø9
315 (Panel cutout)
100
165 165
Dimensions
Panel Cutout - Withdrawable Version
ABW08...16
Door frame
10 - Ø5
315 (Panel cutout)
330
120
304
170
120
109
Lower part of the withdrawable rack
11.5
165 165
Lower part of the withdrawable rack
ABW20...32
Door frame
10 - Ø5
315 (Panel cutout)
408
120
304
170
120
109
Lower part of the withdrawable rack
11.5
165 165
Lower part of the withdrawable rack
ABW40...50
Door frame
10 - Ø5 315 (Panel cutout)
625
120
334
200
120
ABW63
10 - Ø5 Door frame
315 (Panel cutout)
781
120
334
200
120
Dimensions
Minimum Distances
150
50 50
106
131
118 7.5
15
75
75
108
Installation Recommendations
Busbar Connections Cable
Connections
Make sure there are no excessive mechanical forces applied to the circuit breaker back terminals.
Curves
IDMTL Instantaneous - Ground Fault
10,000 100
5,000 50
40
30
2,000
20
1,000
10
500
5
4
200 3
2
100
t(s) t(s) 1
50
0.4
20
0.3
0.2
10
5 0.1
0.05
2
1 0.02
0.05
0.01
7
10
20
0.5
0.7
3
4
5
7
10
2
3
0.05
0.07
0.1
0.2
0.3
0.4
0.5
0.7
1
X Ir
X In
200
100
50
40
30
20
10
5
4
3
t(s)
2
0.4
0.3
0.2
0.1
0.05
0.02
0.01
5
10
20
0.5
0.7
30
7
X Ip
Curves
Long Delay
5,000
2,000
1,000
500
200
100
50
40
30
20
10
t(s) 5
4
3
2
0.4
0.3
0.2
0.1
0.05
0.02
0.01
10
20
1
4
5
7
0.5
0.7
X Ir
Short Delay
5,000
2,000
1,000
500
200
100
50
40
30
20
10
t(s) 5
4
3
2
0.4
0.3
0.2
0.1
0.05
0.02
0.01
0.5
0.7
10
20
X Ir
ABW ABWC
Internal Wiring Diagram for RTC Contact Internal Wiring Diagram for RTC Contact
xx
xx 32 34
21
Auxiliary switch
Axb
Auxiliary switch
Axb
31
22
U3 U1
83 413
Axb
Springs Loaded 81
84 414
Alarm TRIP 1
KT KT
YY
82 U2
KT KT
KT = CWCA auxiliary contactor (not included in circuit breaker supply)
External terminals XX-YY=0 (command not enabled) YY
External terminals XX-YY=1 (command enabled)
The current transformer has a secondary of 5 A, and a conductor must be provided to connect the CT signal to the circuit
breaker for such current.
ZCT
J Primary CT terminals: K, L
J Secondary CT terminals: K, L
1)
354
351
CL1 (Connected)
352
361
364
Cell switch
14
CL2 (Connected)
13
Axa
NO
362
23
24
Axa
374
371
CL3 (Test)
34
33
372
Axa
384
381
44
43
382
53
Axa 54
21
12
314
311
Axb CL1 (Connected)
OFF
312
21
22
Axb
Cell switch 4C
324
321
32
31
322
41
42
Axb
331
334
CL3 (Test)
51
52
Axb
332
344
341
61
342
414
413
Charged
U2
M
Axb
Axa, Axb Auxiliary switch
A2
A1
C2
C1
Axa
G Ground fault trip indicator
C11
C12
or
D2
M Motor
183
184
CC Closing coil
83
84
251
252
R1
534 524
Common L
485+ R11 R22
SI Z1 Z2 ZSI input
Z3 Z4 ZSI output
485- 544
Reset G
E1 E2 ZCT
VN ~ V3 Voltage module
Z1
Z2
ZSI Input
311 ~ 314 Position switch
Z3
Z4
ZSI Output
Trip relay
ZCT
E1
E2
VN
V3
V2
V1
U1 U2 Motor charging
1
3
5
7
A1 A2 Closing coil
C1 C2 Shunt trip
Main circuit
83 84 Alarm trip 1
R1 R2 Control power
1)
351
11
14
Axc
ON
361
12
Cell switch
CL2 (Connected)
21
24
Axc
371
CL3 (Test)
22
34
31
381
Axc CL1 (Connected)
32
44
41
Axc
311
OFF
321
Cell switch
CL2 (Connected)
331
CL3 (Test)
341
CL4 (Disconnected)
U2
U1
Charged
A2
A1
D1 C11 C1
C12 C2
D2
/RES(-)
181
182
M Motor
Power supply
R1
CC Closing coil
R2
Common L
485-
Z1 Z2 ZSI input
Z1
Z2
ZSI Input
Z3 Z4 ZSI output
Z3
Z4
ZSI Output
Trip relay
ZCT
E1 E2 External CT
E1
E2
VN ~ V3 Voltage module
VN
module
Voltage
U3 U2 Spring loaded
A1 A2 Closing coil
Main circuit
C1 C2 Shunt trip
81 82 Alarm trip 1
R1 R2 Control power
Global Presence
With more than 30,000 employees worldwide, WEG is one of the largest electric motors, electronic equipments and systems
manufacturers. We are constantly expanding our portfolio of products and services with expertise and market knowledge. We
create integrated and customized solutions ranging from innovative products to complete after-sales service.
WEG’s know-how guarantees our Air Circuit Breakers are the right choice for your application and business, assuring safety,
efficiency and reliability.
Know More
High performance and reliable
products to improve your
production process.
www.weg.net
+55 47 3276.4000
automacao@weg.net