REQUEST FOR QUOTATION

Attention: To whom it may concern


Date: 01/05/2024
From: Asyad DryDock Company LLC (ADC)
Our Reference: ADC-2024-040- Purchasing ACB (Air Circuit Breaker) and VCB ( Vacuum Circuit breaker)

1. Scope of Work

1.1. ACB (Air Circuit Breaker)

The ACB (Air Circuit breaker) this specification describes the general requirements governing the design
of 1kV /3200AMS with Cradle Indoor Switchgear and control gear fully type tested according to IEC
60947-2 standards. The design of the switchgear shall be exclusive and specific responsibility of Bidder
and shall comply with current good engineering practice, the relevant codes and recommendation, the
project specific requirements.
The Circuit Breaker shall confirm to IEC-60947-2.

1.2. Standards
The electrical switchgears and the relevant equipment shall be designed, manufactured and tested
according to the latest version of:
IEC-60947-2 Common Specifications for Switchgear & Control gear
IEC-60947-2 Circuit Breakers
Above 1kV and up to and including 12kV and the IEC Code herein
Referred, any other codes recognized in the country of origin of equipment might be considered
provided that they fully comply with IEC standards.
The design of the switchgear shall be based on safety to personnel and equipment during operation and
maintenance, reliability of service, ease of maintenance, mechanical protection of equipment,
interchangeability of equipment and ready addition of future loads.
1.3. Technical and System Conditions
• Bidder have to supply the unit as per the below the technical data and requirement:
 1EXSTING BRAND LS ELECTRIC / MADE IN KOREA
 LS ELECTRIC – MADE IN KOREA
 AIR CIRCUIT BREAKER details: -
 Insulating Medium : Air
 Module Number: AN-32E4-32A , M1D1D1AXAG1U0
 Ui – 1000V, Uimp – 12 KV, Ue – 690V, Icu -65KA, Icw- 65KA/1s, 42KA/3s.
 Rated Frequency (Hz) : 50 Hz
 Number of phases : 3 Phase + Neutral
 Rated normal current of breakers: 3200 Amp.
 Rated short time current (KARMS) : 12 KA
 Method of closing Normal : Motor operated Emergency : Manual
 Auxiliary voltage for closing Coil : 110 V DC
 Auxiliary voltage for Tripping Coil : 110 V DC
 Auxiliary voltage for spring charging Motor : 110V DC
 Auxiliary switches :3a3b
 OCR control source : 110 V DC

1.4. Attachment
1.5. VCB ( Vacuum Circuit breaker)

The VCB ( Vacuum Circuit breaker) This specification describes the general requirements governing
the design of 12kV /1250AMS Indoor Switchgear and control gear fully type tested according to IEC
62271-100 standards. The design of the switchgear shall be exclusive and specific responsibility of
Bidder and shall
comply with current good engineering practice, the relevant codes and recommendation, the project
specific requirements.
The Circuit Breaker shall confirm to IEC-62271-100.

2.2.1Standards
The electrical switchgears and the relevant equipment shall be designed, manufactured and tested
according to the latest version of:
IEC 62271-1 Common Specifications for Switchgear & Control gear
IEC 62271-100 Circuit Breakers
Above 1kV and up to and including 72kV and the IEC Code herein
Referred, any other codes recognized in the country of origin of equipment might be considered
provided that they fully comply with IEC standards.
The design of the switchgear shall be based on safety to personnel and equipment during operation
and maintenance, reliability of service, ease of maintenance, mechanical protection of equipment,
interchangeability of equipment and ready addition of future loads.

2.2.2Technical and System Conditions


 Bidder have to supply the unit as per the below the technical data and requirement:

 EXSTING BRAND LS ELECTRIC / MADE IN KOREA


 LS ELECTRIC – MADE IN KOREA
 VACUUM CIRCUIT BREAKER details: -
 TYPE: - LVB-12G-40L/12 1A2B-T2
 RATED VOLTAGE: - 12 KV
 RATED FREQENCY: - 50/60 HZ
 Ud – 28KV
 Isc - 40 KA
 Up - 75 KV
 Ip – 100/104 KA
 RATED OPERATING SEQUENCE: - O-0.3s-CO -3M-CO
 CLASSIFICATION: - E2C2M2
 RELEVANT STANDARD: - IEC62271-100
 RATED NORMAL CURRENT: - 1250 A
 RATED DURATION OF SHORT CIRCUIT: - 3 S
 MOTER VOLTAGE: -DC 110 V
 CLOSING VOLTAGE: DC110 V
 TRIPPING VOLTAGE DC 110 V
 WEIGHT: - 165 Kg
1.6. Attachment

 Stage 1: Mandatory Requirement

Mandatory Requirements
Comply with ADC’s Technical Data as per ADC requirement 2.1.2 & 2.2.2
Minimum 1 years Warranty of the unit

Brand should be (LS ELECTRIC – MADE IN KOREA)

Test Certificate. (General Inspection & functional test, Electronic trip by using test kit & ETU settings,
Secondary injection Test, Insulation resistance Test, Electrical/Functional Test)

All documents should be in English language. .(drawing, test certificate and manuals)

Bidder to provide all the electrical drawings for the units


Bidder to provide all the operation and the maintenance manuals

2. Instruction to Tenders.
1. Download attached ‘Request for Quotation’.
2. Clarifications only through ASYAD’s Drydock Services Procurement Portal (procureware.com) before the Clarif
ication deadline.
3. Submission only through ASYAD’s Drydock Services Procurement Portal (procureware.com) before the Due d
ate.
4. All documents and submission to be uploaded in ASYAD’s Drydock Services Procurement Portal (procureware
.com) in two separate envelops.
5. Clarification and submission outside of Procureware will NOT be entertained.
6. Submission beyond the Due Date will NOT be entertained.
7. ADC comes under free zone category and are considered as Zero rated
3. RFQ Process schedule

Activity Date
Invitation to RFQ 01/05/2024
Documents available for collection 01/05/2024
Tender Submission Date 22/05/2024

You might also like