Temperature Sensors (Celsius)

TC120, TC124

Wiring Diagram

VCC (+)

Com (-)

Pin A Power +

Temp Out
Pin B Common
-
Pin C Temperature Output

Com (-)

Applicable Sensors

Key Details
Tolerance = +4/-2 °C (-40-125 °C)
Tolerance = ±2 °C (0-70 °C)
Tolerance = ±1 °C at 25 °C
Measurement Range = -40 °C to 121 °C

VCC = 3-30 Vdc


*Temp out is a voltage output referenced to COM (-)
Temperature Sensors (Celsius)
TC120, TC124

Temperature Output
Celsius Sensors Output
1800

1600

1400

1200
VOUT (mV)

1000

800
Room Temperature (25°C) = 750mV
600

400

200

0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120
Temperature (°C)
Temperature Sensors (Celsius)
TA102, TA104, TA117, TA118, TA131, TA133, TA134, TA135, TA184

Wiring Diagram

- IEPE Constant

Vibration
Com (-)

Signal
Current Supply
+ 2-10 mA

Current Return

Pin A Power + Com (-)

Temp Out
Pin B Common
-
Pin C Temperature Output

Com (-)

Applicable Sensors
Temperature Sensors (Celsius)
TA102, TA104, TA117, TA118, TA131, TA133, TA134, TA135, TA184

Key Details
Tolerance = ±3 °C
Tolerance = ±2 °C at 25 °C
Measurement Range = 2.5 °C to 100 °C

*IEPE Open Circuit Voltage = 18-30 Vdc


*IEPE Constant Current = 2-10 mA
* Temp out is a voltage output referenced to COM (-)

Temperature Output
Celsius Sensors Output
1200

1000

800
Vout (mV)

600

400

200
Room Temperature (25°C) = 250mV

0
2.5 7.5 12.5 17.5 22.5 27.5 32.5 37.5 42.5 47.5 52.5 57.5 62.5 67.5 72.5 77.5 82.5 87.5 92.5 97.5
Temperature (°C)
M12 Temperature Sensors (Celsius)
TA102, TA104, TA184

Wiring Diagram

- IEPE Constant

Vibration
Com (-)

Signal
Current Supply
+ 2-10 mA

NC Current Return

Pin 1 Power + Com (-)

Temp Out
Pin 2 Common
-
Pin 4 Temperature Output

Com (-)

Applicable Sensors

Key Details
Tolerance = ±3 °C
Tolerance = ±2 °C at 25 °C
Measurement Range = 2.5 °C to 100 °C

*IEPE Open Circuit Voltage = 18-30 Vdc


*IEPE Constant Current = 2-10 mA
*Temp out is a voltage output referenced to COM (-)
M12 Temperature Sensors (Celsius)
TA102, TA104, TA184

Temperature Output
Celsius Sensors Output
1200

1000

800
Vout (mV)

600

400

200
Room Temperature (25°C) = 250mV

0
2.5 7.5 12.5 17.5 22.5 27.5 32.5 37.5 42.5 47.5 52.5 57.5 62.5 67.5 72.5 77.5 82.5 87.5 92.5 97.5
Temperature (°C)
M12 Temperature Sensors (Celsius)
TA312, TA314

Wiring Diagram

VCC (+)

Com (-)

Vibration Signal
+
Pin 1 Power +

Temp Out
-
Pin 2 Common
-
Pin 3 Signal Output
Pin 4 Temperature Output Com (-)
Com (-)
Applicable Sensors

Key Details
Tolerance = +4/-2 °C (-40-125 °C)
Tolerance = ± 2 °C (0-70 °C)
Tolerance = ±1 °C at 25 °C
Measurement Range = -40 °C to 121 °C

VCC = 3-5 Vdc


*Temp out is a voltage output referenced to COM (-)
M12 Temperature Sensors (Celsius)
TA312, TA314

Temperature Output
Celsius Sensors Output
1800

1600

1400

1200
VOUT (mV)

1000

800
Room Temperature (25°C) = 750mV
600

400

200

0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120
Temperature (°C)
Temperature Sensors (Kelvin)
TK120, TK124

Wiring Diagram

Constant Current
+

Temp Out
Supply
Com (-)
- .4-5 mA

Current Return

Pin A Power
Com (-)
Pin B Common

Applicable Sensors

Key Details
Tolerance = ±4 °C (typical); ± 9 MAX
Tolerance = ±2 °C at 25 °C (typical); ±6 MAX
Measurement Range = -40 °C to 100 °C (233.15 K to 373.15 K)

*Current supply can be IEPE, but must not exceed 5 mA


*Temp out is a voltage output referenced to COM (-)
Note: Kelvin sensors are sensitive to self heating, so the lowest possible
supply current should be used
Temperature Sensors (Kelvin)
TK120, TK124

Temperature Output
Kelvin Temperature Sensor Output (Celsius)
4000

3800

3600

3400

3200
VOUT (mV)

3000
Room Temperature (25°C) = 2981.5mV
2800

2600

2400

2200

2000
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100
Temperature (°C)

Kelvin Temperature Sensor Output (Kelvin)


4000

3800

3600

3400

3200
VOUT (mV)

3000
Room Temperature (298.15K) = 2981.5mV
2800

2600

2400

2200

2000
233.15 243.15 253.15 263.15 273.15 283.15 293.15 303.15 313.15 323.15 333.15 343.15 353.15 363.15 373.15
Temperature (K)
Temperature Sensors (Kelvin)
TA172, TA174, TA178

Wiring Diagram

- IEPE Constant

Vibration
Com (-)

Signal
Current Supply
+ 2-10 mA

Current Return

Com (-)
Pin A Power
Pin B Common
Pin C Temperature Output + .4-5 mA
Temp Out Constant Current
- Supply

Com (-)

Applicable Sensors

Key Details
Tolerance = ±4 °C (typical); ± 9 MAX
Tolerance = ±2 °C at 25 °C (typical); ±6 MAX
Measurement Range = -40 °C to 100 °C (233.15 K to 373.15 K)

IEPE supply can be used for the temperature circuit, however it cannot exceed 5mA.
Note: Kelvin sensors are sensitive to self heating, so the lowest possible supply current should be used
*IEPE Open Circuit Voltage = 18-30 Vdc
*IEPE Constant Current = 2-10 mA
*Temp out is a voltage output referenced to COM (-)
Temperature Sensors (Kelvin)
TA172, TA174, TA178

Temperature Output
Kelvin Temperature Sensor Output (Celsius)
4000

3800

3600

3400

3200
VOUT (mV)

3000
Room Temperature (25°C) = 2981.5mV
2800

2600

2400

2200

2000
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100
Temperature (°C)

Kelvin Temperature Sensor Output (Kelvin)


4000

3800

3600

3400

3200
VOUT (mV)

3000
Room Temperature (298.15K) = 2981.5mV
2800

2600

2400

2200

2000
233.15 243.15 253.15 263.15 273.15 283.15 293.15 303.15 313.15 323.15 333.15 343.15 353.15 363.15 373.15
Temperature (K)
M12 Temperature Sensors (Kelvin)
TA172, TA174, TA178

Wiring Diagram

- IEPE Constant

Vibration
Com (-)

Signal
Current Supply
+ 2-10 mA

Current Return
NC

Com (-)
Pin 1 Power
Pin 2 Common
Pin 3 Temperature Output + .4-5 mA
Temp Out Constant Current
- Supply

Applicable Sensors Com (-)

Key Details
Tolerance = ±4 °C (typical); ±9 MAX
Tolerance = ±2 °C @ 25 °C (typical); ±6 MAX
Measurement Range = -40 °C to 100 °C (233.15 K to 373.15 K)

IEPE supply can be used for the temperature circuit, however it cannot exceed 5mA.
Note: Kelvin sensors are sensitive to self heating, so the lowest possible supply
current should be used
*IEPE Constant Current = 2-10 mA
*IEPE Open Circuit Voltage = 18-30 Vdc
*Temp out is a voltage output referenced to COM (-)
M12 Temperature Sensors (Kelvin)
TA172, TA174, TA178

Temperature Output
Kelvin Temperature Sensor Output (Celsius)
4000

3800

3600

3400

3200
VOUT (mV)

3000
Room Temperature (25°C) = 2981.5mV
2800

2600

2400

2200

2000
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100
Temperature (°C)

Kelvin Temperature Sensor Output (Kelvin)


4000

3800

3600

3400

3200
VOUT (mV)

3000
Room Temperature (298.15K) = 2981.5mV
2800

2600

2400

2200

2000
233.15 243.15 253.15 263.15 273.15 283.15 293.15 303.15 313.15 323.15 333.15 343.15 353.15 363.15 373.15
Temperature (K)
1 1 2 2 3

CTCCTC
HIGHLY
HIGHLY
CONFIDENTIAL
CONFIDENTIAL
ANDAND
PROPRIETARY
PROPRIET

A A

RTD Sensors
2 TR102, TR104,
3 TR133, TR134 4

HIGHLY CONFIDENTIAL AND PROPRIETARY INFORMATION


Typical setup
Typical Wiring Diagram
utilizing
setup utilizing
4-wire configuration
4-wire configuration
to DAQ to DAQ

Typical setup utilizing 4-wire configuration to DAQ


RTD sensors can be wired in 2, 3, and 4-wire configurations.

Vibration Signal

Vibration Signal
Therefore, TR sensors should be usedIEPE withConstant
the M4TR conne c t o r
B B mated to the CB123 cable. A
- The CB123
- cable by default provides a
4-wire connection, but leadsCOM be Current
can (-) ommitted
COMIEPE Supply
to create
(-) Constant 2 andSupply
IEPECurrent
Constant 3-wire *IEPE Open
Current Supply *IEPE
Circuit
Ope
-
configurations. +
If possible though, a 4-wire connection +shoul d b+e

Vibration
utilized since(-)
it provides +2-10
+ the highest mA of measurement.
accuracy *IEPE Constant
*IEPE CoC
Com

Signal
2-10mA 2-10mA
Since RTD sensors are resistive elements, their accuracy is gre a t l y
+
affected -
by the resistance of connecting cables (represented
- by-
Power Power
1 1 resistors 1-4), especially at longer lengths. To compensate, 3 or
COM COM 4-wire configurations should be used. 2-wire configurations provi d e
2 2 COM (-) COM (-)
no lead resistance compensation and are therefore the least accura te. Typical RTD
Typi
RTD + RTD + 4-wire configurations are most accurate. 1 1
3 3
2 2
+ +
RTD - RTD - 3 Com
NOTE: These wiring diagrams are just generic 3 (-)
examples.
4 4 I
There are many different ways to wire and 4 measure
4 an RTD
- -
Typical setup utilizing 4-wire configuration to DAQ
sensor, and the user should reference the documentation of
Pin 1 Power TR SensorTR Sensor any equipment
Cable Shield
Cable are using toTypical
theyShield RTD DAQ
ensure proper setup

Pin 2 Common
Vibration Signal

B
- C C
PIn 3 RTD (+) *IEPE Open Circuit Voltage = 18-30VDCGND
+ +
COM (-) IEPE Constant Current Supply GND
+ I
Pin 4 RTD (-) *IEPE Constant Current = 2-10mA - -
+
2-10mA
3-wire configur
3-wire
-
wer

M
COM (-)
Typical RTD DAQ
D+ 1 3-wire configuration
3-wire configuration
to DAQ to DAQ 2-wire configuration
2-wire configuration
to DAQ to DAQ
2
+ + *I = Excitation current
D- 3 Typical RTD
Typical
IDAQRTD*DAQ
RTD element can handle a maximum of Typical RTD
2mA. 1mATypical
is DAQRTD DAQ
recomended. RTD + RTD + 1
4
RTD + RTD + 1 1 - -
RTD + RTD + 1 1
+ +
+ + + + RTD RTD
Jumper Jumper + + 3
Cable Shield RTD RTD
3 3
I I RTD RTD
Jumpers Jumpers I I RTD - RTD - 4
- -
RTD - RTD - 4 4 - - - -
RTD - RTD - 4 4 - -

D D C
GND

3-wire configuration to Wheatstone bridge


R1 = R2; should be chosen in
conjunction with Vin to
appropriately set the RTD current.
1 1 R1 R2 2 2 3

2-wire configuration to DAQ R1,R2 >> RTD,R3


+ - +
D DAQ RTD + 1 Vin R3 should be set close to the middle
Typical RTD DAQ R3
RTD + 1
- RTD resistance of the temperature
+ range being measured.
+ RTD
+ 3
I RTD
Jumpers I RTD - 4
- -
RTD - 4 -

D
Conenction Technology Center, Inc

Drawn By: Drawing No. Rev:


4/21/2020 Size: A Approval: Sheet of
2 3 4
RTD Sensors
TR102, TR104, TR133, TR134

Applicable Sensors

Key Details
R0 = R at 0°C = 100 Ω
R0 tolerance = ± .2 Ω
Temp Tolerance = ± .5 °C
(or .8% of temp, whichever is greater)

*IEPE Open Circuit Voltage = 18-30 Vdc


*IEPE Constant Current = 2-10 mA

Temperature Output
RTD Output
160.0000

150.0000

140.0000

130.0000
Resistance (Ω)

120.0000

110.0000
Room Temperature (25°C) =
100.0000 109.73Ω
R0 (0°C) = 100Ω
90.0000

80.0000

70.0000

60.0000
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120
Temperature (°C)
Loop Power Temperature Sensors
LP232, LP234, LP332, LP334

Wiring Diagram

VCC (+)
4-20 mA Signal

Com (-)

Pin A Power +

Temp Out
Pin B Common
-
Pin C Temperature Output

Com (-)
Applicable Sensors

Key Details
Tolerance = +4/-2 °C (-40-125 °C)
Tolerance = ±2 °C (0-70 °C)
Tolerance = ±1 °C at 25 °C
Measurement Range = -40 °C to 85 °C

VCC = 15-30 Vdc


*Temp out is a voltage output referenced to COM (-)
Loop Power Temperature Sensors
LP232, LP234, LP332, LP334

Temperature Output
LP23X/33X Temperature Output
1600

1400

1200

1000
VOUT (mV)

800
Room Temperature (25°C) = 750 mV
600

400

200

0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80
Temperature (°C)

You might also like