1-s2.0-S0011916420314119-main

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Desalination 496 (2020) 114733

Contents lists available at ScienceDirect

Desalination
journal homepage: www.elsevier.com/locate/desal

Thermal performance assessment of an evaporative condenser-based T


combined heat pump and humidification-dehumidification desalination
system
Meysam Faegh, Mohammad Behshad Shafii

Department of Mechanical Engineering, Sharif University of Technology, Tehran, Iran

ARTICLE INFO ABSTRACT

Keywords: A new design for heat pump integrated humidification-dehumidification (HDH-HP) desalination cycles was
Thermal desalination proposed in the current experimental study. An evaporative condenser was designed and fabricated instead of a
Humidification-dehumidification separate humidifier, heater, and air/water-cooled condensers find in previous HDH-HP systems. Meanwhile, the
Evaporative condenser air dehumidification process in this work directly occurred inside the heat pump evaporator. The effect of several
Heat pump
operating parameters such as ambient wet-bulb temperature, spraying saline water and airflow rates, compressor
Electronic expansion valve
speed, superheat, and evaporator saturation temperature control modes of the electronic expansion valve (EEV)
on freshwater production and GOR were studied. Analyzing the experimental results indicated that the system
productivity and GOR reached 1.08 kg/h and 2.00, respectively. Higher freshwater produced at decreased
airflow rates and increased ambient wet-bulb temperatures, spraying water flow rate and compressor speeds.
Moreover, it was observed that the system performance enhances at higher adjusted evaporator saturated
temperatures and lower superheats in the EEV controller. The experimental data for cooling capacity, com­
pressor power, and current consumption was in agreement with polynomials provided by the compressor
manufacturer. Additionally, the cost of generated freshwater was obtained as 0.019 $/L.

1. Introduction with an external cooling source in a dehumidifier to produce fresh­


water.
The need for freshwater is rising globally by a drastic increase in the Despite the significant advantages of HDH systems, the high energy
population and industrial development. It has been estimated that by consumption and low gained output ratio (GOR) act as significant
2040, the imbalance between the supply and demand for freshwater barriers to make HDH systems commercialized. To overcome this issue,
will result in a global water stress challenge in 167 countries [1]. The many research efforts have been made to improve the performance of
desalination of seawater has been proved to be a reliable solution to conventional HDH systems with different types of humidifiers, dehu­
meet the freshwater requirement. Despite the improvement and com­ midifiers, and heat sources [7]. It has been reported that the bubble
mercialization of various methods in recent years, current desalination column humidifiers [8] and dehumidifiers [9] enhanced the pro­
methods are energy-intensive processes [2]. This motivates the re­ ductivity of HDH cycles.
searchers to develop more cost-effective, reliable, and sustainable de­ A prominent method to enhance both the yield and overall energy
salination technologies [3]. Humidification-dehumidification (HDH) is performance of HDH cycles is to couple them with heat pumps. Heat
one of the under-development desalination methods, which has focused pumps, which are considered as high-performance energy conservation
on by various researchers due to its applicability in decentralized areas systems, can provide heating/cooling load demand of HDH systems
[4], low maintenance, and capital cost [5]. HDH desalination cycles through their condenser and evaporator, respectively. Some researchers
have simple structures, which mainly consisted of two components, i.e., tried to increase the productivity of combined HDH and heat pump
humidifier and dehumidifier. Besides, the HDH systems own the cap­ (HDH-HP) systems by lowering the temperature of the cooling medium
ability of being powered by various renewable energy resources [6]. In in the dehumidifier. In this regard, Lawal et al. [10] conducted a the­
these systems, air/saline water gets heated by a heating source and oretical investigation on a heat pump based desalination cycle. The
brought into contact with together in a humidifier and then cools down evaporator cooling load was delivered to the inlet saline water entering


Corresponding author.
E-mail address: behshad@sharif.edu (M.B. Shafii).

https://doi.org/10.1016/j.desal.2020.114733
Received 27 June 2020; Received in revised form 23 August 2020; Accepted 26 August 2020
Available online 10 September 2020
0011-9164/ © 2020 Elsevier B.V. All rights reserved.
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

Nomenclature Greek symbols

Ci=1–18 Performance coefficients of the compressor ηisentropic Isentropic efficiency of the compressor
Cp Specific heat (J/kg K) ηelectrical Electrical efficiency of the compressor
CPL Cost per liter ($/L) ρ Density (kg/m3)
EEV Electronic expansion valve ω Absolute humidity (kgw/kga)
GOR Gained output ratio
h Enthalpy (kJ/kg) Subscripts
hfg Latent heat (J/kg)
HDH Humidification-dehumidification a Air
HP Heat pump a1 Ambient air
I Electrical current (A) a2 Air exiting the evaporative condenser, air entering the
m Mass flow rate (kg/s) dehumidifying evaporator
MR Saline water to air mass flow rate ratio a3 Air exiting the dehumidifying evaporator
P Pressure (kPa) ec Evaporative condenser
Q Rate of heat transfer (W) e Evaporator (Dehumidifying evaporator)
RH Relative humidity fw Freshwater
RMSE Root mean square error r Refrigerant
SH Superheat (°C), (SH = Tr1-Te) sw Saline water
T Temperature (°C) r1 Refrigerant exiting the dehumidifying evaporator, re­
Te Saturation temperature of dehumidifying evaporator at frigerant entering the compressor
evaporator pressure (°C) r2 Refrigerant exiting the compressor
Tc Saturation temperature of evaporative condenser at con­ r3 Refrigerant entering the evaporative condenser
denser pressure (°C) r4 Refrigerant exiting the evaporative condenser, refrigerant
V Voltage (v) entering the electronic expansion valve
V Volumetric flow rate (m3/h) r5 Refrigerant exiting the electronic expansion valve, re­
W Power consumption (W) frigerant entering the dehumidifying evaporator

the dehumidifier to reduce its temperature and raise the rate of dehu­ studied an HDH-HP system by using the heat pump heating/cooling
midification. At the same time, the condenser heating load was utilized load via separate heat exchanger loops. Utilizing the heat pump cooling
either to heat the inlet saline water to the humidifier or to raise the load in a secondary dehumidifier and its heating load to warm up the
temperature of the air entering the dehumidifier. It was shown that saline water entering the dehumidifier led to a GOR, freshwater yield,
higher GOR could be achieved in air heated cycle compared to water and CPL of 2.05, 22.26 kg/h and 0.05$/L, respectively. Moreover, a
heated one. An optimum value was reported for the saline water to air correlation for freshwater productivity was reported with ± 2% de­
mass flow rate ratio to maximize the GOR. Besides, it was shown that viation [17]. In a similar work, Xu et al. [18] conducted an experi­
the evaporator has the highest irreversibility within the system com­ mental study on a heat pump based HDH cycle, in which the air de­
ponents [11]. The exergy efficiency of 1.097% and cost of 4.61 to 5.49 humidification firstly is done by incoming saline water and then via the
$/m3 was reported for the proposed air heated HDH-HP cycle. heat pump cooling load as a secondary dehumidifier. As saline water
Another way to raise the freshwater yield is to use more efficient gets preheated in the first stage dehumidifier, it passes through the heat
dehumidifiers. He et al. theoretically calculated the productivity of an pump condenser to absorb its heating load. To further increase the
HDH-HP cycle with traditional [12] and packed-bed [13] dehumidifiers temperature of spraying saline water, it passes through a solar collector.
in which the waste heat of rejected brine was absorbed in the HP Results indicated that for an optimal airflow rate of 450 m3/h and a
evaporator and delivered to saline water through the HP condenser. It cooling saline water flow rate of 0.3 m3/h, GOR and productivity
was reported that the freshwater productivity increases with reducing reached 1.24 and 12.75 kg/h, respectively. Later, a secondary humi­
the condenser pinch temperature difference and increasing the heat difier was added to the system in a way that a part of saline water going
pump pressure ratio. At the balance condition of the dehumidifier, out through the pre-cooler was sprayed into the system, whereas the
freshwater production of 76.4 kg/h and 82.12 kg/h were obtained for remaining saline water was directed through the heat pump condenser
packed-bed and conventional dehumidifiers, respectively. In a similar and solar collector before entering the primary humidifier [19]. It was
work with that of [13], an HDH-HP system was theoretically examined reported that the GOR, freshwater productivity, and CPL increased by
based on the algorithm of particle swarm optimization [14]. By re­ 55.64%, 15.51%, and 17.36% compared to a conventional humidifi­
covering the evaporator cooling load in the second-stage air dehumi­ cation-dehumidification system. Besides, it was found that an increase
difier, an optimum yield and GOR of 89.27 kg/h and 4.17 were ob­ of 1 m2 in the collectors area led to a 0.68 kg/h rise in yield and 0.06
tained, respectively. Dehghani et al. [15] theoretically studied the drop-in GOR. Moreover, the optimization results revealed that by 1 m2
operation of an HDH-HP cycle integrated with a direct contact type increase in the area of solar collectors, the GOR drops by 0.06, while the
dehumidifier in which the evaporator cooling was utilized to cool down productivity rises by 0.68 kg/h [20].
the temperature of freshwater spraying into the dehumidifier, while the Previous HDH-HP systems at least consisted of four heat exchangers,
condenser heating load was used to increase the incoming saline water i.e., heat pump condenser, heat pump evaporator, humidifier, and de­
temperature to the humidifier. It was reported that a totally coupled humidifier. Shafii et al. [21] experimentally coupled an HDH cycle with
cycle can be achieved by adjusting the proper mass flow rate ratios. a heat pump in which the usual saline water-cooled dehumidifier was
In conventional HDH cycles, air passes through the coils carrying eliminated. In the proposed system, ambient air absorbs the heating
the incoming saline water inside the dehumidifier. To achieve higher load of the heat pump condenser initially. Afterward, humidified air
freshwater productivity, some researchers focused on additional dehu­ enters the heat pump evaporator to produce freshwater. It was con­
midifiers based on heat pump cooling load to reach lower air tem­ cluded yield and GOR increase at higher entering air flow rate and
peratures and more freshwater yield. Zhang et al. [16] experimentally relative humidity. At elevated ambient temperatures, freshwater

2
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

production rises, while GOR drops because of increased compressor various ambient wet-bulb temperatures, spraying saline water and
power consumption. In continuation of the previous work, the principle airflow rates, compressor speeds, superheat, and saturated evaporator
of estimating the operation of HDH-HP systems at off-design conditions temperature control modes of the electronic expansion valve. The
was examined by Faegh & Shafii [22] theoretically. In that system, the freshwater productivity, GOR, and cost of the produced freshwater
conventional dehumidifier was removed, and air dehumidification oc­ were reported, as well.
curred inside the heat pump evaporator. Meanwhile, the incoming
saline water was heated inside the heat pump condenser before entering 2. System description
the humidifier. By employing the characteristics method for balancing
the system performance, the procedure of calculating the basic rating 2.1. Experimental setup
coefficients for determining the productivity of a system with fixed heat
exchangers was proposed. A schematic drawing of the fabricated system is indicated in Fig. 1.
As discussed above, various researchers either utilized air-cooled or It can be seen that the system is mainly comprised of an evaporative
water-cooled heat exchangers in HDH-HP systems to provide the re­ condenser, an electronic expansion valve, a solenoid valve, a receiver
quired heating load through the heat pump condenser. The use of drier, a dehumidifying evaporator, a compressor, a fan, and a circu­
various heat exchangers in the previous HDH-HP cycles added more lating water pump. The experimental setup and a brief description of
complexity to the systems. To the best of the author's data, there isn't system components are shown in Fig. 2 and Table 1, respectively. The
any published study on HDH-HP systems equipped with evaporative evaporative condenser in the proposed cycle not only acts as a heat
condensers. Evaporative condensers are mainly used in the refrigeration pump condenser but also functions as a humidifier. Ambient air (state
industry over the years due to their outstanding advantages as having a1) enters the evaporative condenser and by flowing upward, gets hu­
higher heat transfer coefficients [23], energy-saving capability [24], midified (state a2) through the saline water sprayed downward via a
and compactness [25] compared to air/water-cooled condensers. In an circulating water pump located at the water sump. Meanwhile, the
evaporative condenser, both of the upward air and spraying downward superheated refrigerant (state r3) inside the cupper coils enters the
saline water streams are used to extract heat from the refrigerant evaporative condenser and, by rejecting its heat, exits from the lower
flowing inside the condenser coils. Therefore, an evaporative condenser part of the evaporative condenser as subcooled liquid (state r4). The
has the potential of being used as the humidifier and heater, simulta­ refrigerant at the outlet of the evaporative condenser (state r4), passes
neously while extracting heat from the condenser of the HDH-HP cycle. through a receiver drier, a solenoid valve (Danfoss-BG012DS), and an
In this study, a novel compact HDH-HP system with only two heat electronic expansion valve (Danfoss-ETS608), respectively. The two-
exchangers, i.e. an evaporative condenser and a dehumidifying eva­ phase refrigerant flow exiting the electronic expansion valve enters the
porator was manufactured and investigated experimentally. In the heat pump dehumidifying evaporator to provide cooling load (state r5).
proposed system, the hot refrigerant enters the coils of the evaporative A variable-speed fan (EBM-WIG200, 36-56 V) is incorporated at the
condenser. It gets cooled by transferring its heat to the upward airflow upper section of the evaporative condenser, which draws the humidi­
and downward spraying saline water stream, simultaneously. fied air (state a2) to the heat pump dehumidifying evaporator that acts
Meanwhile, ambient air gets humidified by passing within the eva­ as the dehumidifier in the system. By recovering the heat pump cooling
porative condenser and directly enters the evaporator of heat pump, load in the dehumidifying evaporator, freshwater is produced, and
which functions as the dehumidifier in the system. An adjustable speed dehumidified air (state a3) exits to the ambient. Also, the low-pressure
fan was used between the evaporative condenser and heat pump eva­ superheated refrigerant leaving the evaporator (state r1) and passing
porator, which draws the ambient air to the evaporative condenser and through the compressor (Danfoss-BD350GH, 48-56 V) gets hot and
sends it to the evaporator. This method eliminates two heat exchangers pressurized (state r2) and then passes through the evaporative con­
and reduces the total required heat exchangers from 4 to 8 to 2 units denser.
compared to conventional systems. In the current work, the perfor­ Several parameters, including the temperatures and pressures of
mance of the system was examined experimentally and thoroughly at various points, air velocity and relative humidity, voltage, and current

Fig. 1. Schematic view of the experimental setup.

3
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

Fig. 2. Fabricated experimental setup.

Table 1 of electrical devices and freshwater yield, were measured during the
Specifications of fabricated heat exchangers. tests. A summary of measuring instruments, their operational range,
Parameter Value
accuracy, and resolution are reported in Table 2.

Evaporative condenser 2.2. Governing equations


Coil material Cupper
Coil outer diameter 3/8″
Coil thickness 0.75 mm
The energy balance and mass conservation in the evaporator can be
Coil arrangement Staggered written as follows:
Transverse pitch 0.019 m
Longitudinal pitch 0.025 m Qe = mr (hr1 hr5) = ma (ha2 ha3) mfw hfw (1)
Length 35 cm
Width 11.43 cm mfw = ma ( a2 a3) (2)
Number of columns 11
Also, the input power, electrical efficiency and isentropic efficiency
Number of rows per column 10
of the compressor can be calculated as shown:
Evaporator
Fin to fin dimension (length×height) 20 cm×20 cm Wcompressor = Vc Ic (3)
Number of rows 4
Fin material Aluminum mr (hr2,isentropic hr1)
Fin thickness 170 μm isentropic = [13]
Fin per inch 8
Wcompressor (4)
Coil material Cupper
Coil size 3/8 mr (hr2 hr1)
electrical = [26]
Coil thickness 0.20 Wcompressor (5)
Coil arrangement Staggered
Inlet distributor Brass, 4 holes 3/16″ to ½″ The energy equilibrium in the evaporative condenser is given as:
Outlet collector 5/8″
Qec = mr (hr3 hr4) = ma (ha2 ha1) mmakeuphmakeup (6)

Table 2
Specifications of measuring equipment.
Measurement device Operation range Accuracy Resolution

Kewtech KT203 clamp meter 0–400.0 V ± 1.5%rdg ± 5dgt 0.1 V


0–40.00 A ± 3.0%rdg ± 8dgt 0.01 A
Lutron LM-81AM anemometer 0.4–30.0 m/s ± 3% F.S. 0.1 m/s
HTC-2 thermo-hygrothermograph −50 °C–70 °C ± 1 °C 0.1 °C
10%–99% ± 5% 1%
Lutron BTM-4208SD K-type thermometer −100 °C–1300 °C ± 0.4% + 1 °C 1 °C
Danfoss AKS-32R pressure transmittera −1– 12 bar ± 0.3% F.S. 0.01 psi
Danfoss AKS 11-PT1000 superheat sensora −50 °C–100 °C – 0.1 °C
Asian first pressure gauge −1– 18 bar – 0.5 bar
Graduated cylinder 0–100 mL – 1 mL

a
Logged with EIM-336 EEV drive.

4
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

The subcooled liquid exiting the evaporative condenser undergoes


an isenthalpic process by passing through the electronic expansion
valve.
hr4 = hr5 (7)
The gained output ratio can be obtained by dividing the latent heat
of produced freshwater to total input energy of the system as [11, 26,
27]:
mfw hfg
GOR =
Wcompressor + Wfan + Wwater pump (8)
The cooling capacity of a compressor, its required input power and
current consumption for given evaporator and condenser saturation
temperatures can be estimated by various polynomial functions of sa­
turation temperatures of evaporator and condenser, provided by the
manufacturer via Danfoss Coolselector®2 software:

Qe
= c 0,e + c1,e Te + c 2,e Tc + c3,e T2e + c4,e TeTc + c5,e T2c + c6,e T3e + c7,e T2e
Tc + c8,e TeT2c + c 9,e T3c (9)

Wc Fig. 3. The effect of ambient wet-bulb temperature on yield and GOR of the
= c 0,w + c1,w Te + c2,w Tc + c3,w T 2e + c 4,w TeTc + c5,w T 2c + c 6,w T3e + c7,w T 2e Tc + c8,w Te cycle.
T 2c + c 9,w T3c (10)
898.5 kg/h and 67.5 m3/h, respectively. It can be seen that higher
Ic
ambient wet-bulb temperature results in higher freshwater productivity
= c 0,i + c1,i Te + c 2,i Tc + c3,i T2e + c4,i TeTc + c5,i T2c + c6,i T3e + c7,i T2e and GOR. As ambient wet-bulb temperatures varied from 16.6 to
Tc + c8,i TeT2c + c 9,i T3c (11) 25.1 °C, freshwater productivity and GOR increased by 16.7% and 7.3%
to reach 0.9 kg/h and 1.74, respectively. To explain the impact of
To explain more, the constants in these equations are provided by ambient wet-bulb temperature on system performance, p-h and T-S
the compressor manufacturer. By having evaporator and condenser diagrams are shown in Fig. 4. It is observed that the variation in am­
saturation temperatures and substituting in Eqs. (9) to (11), cooling bient wet-bulb temperature, considerably affects the system perfor­
capacity (Eq. (9)), compressor power (Eq. (10)), and also compressors' mance. As the temperature of ambient wet-bulb increases, the tem­
current consumption (Eq. (11)) can be estimated without the need for perature of saline water (Tsw), as well as saturation pressure (Pc) and
measurement. In this study, these equations were used to compare the saturation temperature (Tc) of condensing refrigerant inside the eva­
estimated values from the aforementioned equations with the true ex­ porative condenser, rise. Therefore, it is indicated that at higher
perimentally measured values. More details on the utilization of the sprayed water temperatures, the temperature (Ta2) and humidity ratio
compressor characteristic polynomials, can be found in [28]. (ωa2) of the air at its outlet boost as well. By entering hot and humid air
to the evaporator at higher ambient wet-bulb temperatures, the sa­
3. Results and discussion turation temperature (Te) and pressure (Pe) of evaporator increase as
well. It is seen that the evaporator (Te) and condenser (Tc) saturation
The goal of the present work was to experimentally examine the temperatures respectively change from 8.1 to 12.2 °C and 34.3 to
performance of a novel compact HDH-HP system using an evaporative 39.4 °C by increasing the ambient wet-bulb temperature from 16.6 to
condenser. As summarized in Table 3, system performance was ana­ 25.1 °C. The process of air humidification in the evaporative condenser
lyzed by selecting six scenarios with varying ambient wet-bulb tem­ (from state a1 to a2) and its dehumidification in the dehumidifying
peratures, sprayed mass flow rate of saline water, airflow rates, com­ evaporator (from state a2 to a3) are shown on a psychrometric chart
pressor speeds, and using two electronic expansion valve control (Fig. 5) for ambient wet-bulb temperatures of 16.6 and 25.1 °C. It can
methods. be inferred that the temperature of the humid air entering the dehu­
midifying evaporator (Ta2) rises at higher ambient wet-bulb tempera­
3.1. Test scenario 1: effect of ambient wet-bulb temperature tures (Ta1). As an intrinsic property of the psychrometric chart, the
slope of the saturated air curve increases at higher temperatures, which
The evaporative condensers are wet-bulb sensitive devices in which enhances the capability of humid air to hold more moisture at elevated
the ambient wet-bulb temperature plays a dominant role in the capacity temperatures (higher ωa2). Therefore, by raising the ambient wet-bulb
[28]. Fig. 3 demonstrates the impact of ambient wet-bulb temperature temperature from 16.6 to 25.1 °C, the difference between the humidity
on the yield and GOR for sprayed saline water and airflow rates of

Table 3
A summary of test conditions.
Test scenario Ambient wet-bulb temperature (°C) msw (kg/h) Va (m3/h) Compressor speed (RPM) EEV control mode

1 16.6 to 25.1 898.8 67.5 4000 SH adjustment (6 °C)


2 17.8 195.8 to 898.8 72.9 4000 SH adjustment (6 °C)
3 16.7 898.8 65.5 to 100.3 4000 SH adjustment (6 °C)
4 17.3 195.8 78.7 2500 to 4000 SH adjustment (6 °C)
5 16.5 898.8 66.3 4000 SH adjustment (6 °C to 10 °C)
6 28.7 898.8 69.3 4000 Te adjustment (2 °C to 14 °C)

5
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

Fig. 4. Impact of ambient wet-bulb temperature on the performance of the heat pump. a. p-h diagram and b. T-s diagram.

from 0.62 to 0.9 kg/h via increasing the saline water flow rate from
195.8 to 898.8 kg/h, respectively. At elevated flow rates of saline
water, the relative humidity of air exiting the evaporative condenser
approaches to the saturation state (RH = 100%) causing condensation
as soon as it enters the HP evaporator. At lower saline water mass flow
rates, the relative humidity of the air leaving the evaporative condenser
is reduced, and hence, so much of the cooling load of the dehumidifying
evaporator is used to cool the air (as sensible heat) and reduce its
temperature to dew point instead of producing water. Therefore, less
freshwater was produced at lower saline water flow rates. By increasing
the saline water flowrate, yield and total input power rose by 45.54%
and 6.51%, respectively, resulting in a 36.53% increase in GOR. From
another point of view, the relevant mass flow rate ratios of saline water
to air were depicted in Fig. 6. It can be observed that the ratio of saline
water to airflow rates changes from 2.1 to 10.9 with the change of
saline water flow rate from 195.8 to 898.8 kg/h indicating that raising
the mass flow rate ratio of saline water to air results in better perfor­
mance.

Fig. 5. Psychrometric chart for air process at two different ambient wet-bulb
temperatures.

ratio of air entering/exiting the dehumidifying evaporator (ωa2 − ωa3)


rises from 15.8 to 17.2 g/kg for a constant temperature difference of
8.69 ± 0.04 °C (Ta2-Ta3). In short, at the higher inlet wet-bulb tem­
perature to the evaporative condenser, the dew point rises and, as a
result, increases the amount of moisture in the air to be condensed. As
the studied system is an open-air evaporative condenser based HDH-HP
cycle, it is recommended that the effect of close air system (the re­
turning of the outlet saturated air back to the evaporative condenser)
on productivity be studied in future studies and compared with the
current open-air circuit system performance.

3.2. Test scenario 2: effect of sprayed saline water flow rate

Mass flow rate of sprayed saline water directly affects the humidi­
fication process and saturated temperature of refrigerant (Tc) inside the
evaporative condenser. Variations in yield and GOR of the system were
shown in Fig. 6 for an average ambient wet-bulb temperature of 17.8 °C Fig. 6. Variation of yield and GOR versus saline water flow rate and mass flow
and an airflow rate of 72.9 m3/h. It can be inferred that the yield rose rate ratio.

6
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

3.3. Test scenario 3: effect of airflow rate defined as the ratio of heat pump cooling load to the compressor power
input [29]. Since there is an optimal point for the COP of the com­
The airflow rate is another factor influencing the system perfor­ pressor by changing its speed, having an optimal point for system ef­
mance due to its direct impact on both the humidification and dehu­ ficiency named as gained output ratio (GOR) is not unexpected. The
midification processes. Variation of yield and GOR at different airflow various working conditions of the heat pump during this study led to
rates and their relevant mass flow rate ratios was depicted in Fig. 7 for electrical and isentropic efficiencies of 40.9–80.6% and 19.6–40.2%,
an average ambient wet-bulb temperature and saline water flow rate of respectively. Previous theoretical studies on HDH-HP systems con­
16.7 °C and 898.8 kg/h, respectively. It can be seen that higher fresh­ sidered constant efficiencies for the compressor. However, in this study,
water can be achieved at lower airflow rates. For airflow rates of 65.5, a comparison was done between the experimental results and correla­
76.9, and 100.3 m3/h, the produced hourly freshwater was 0.80, 0.77, tions provided by the manufacturer. To further explain this issue, by
and 0.71 kg/h, respectively. At the same time, the mass flow rate ratio knowing the temperatures of the evaporator and condenser and using
of saline water to air falls from 11.9 to 7.7. According to Eq. (1), it may polynomial characteristics provided by compressor manufacturer (Eqs.
seem that decreasing the airflow rate results in lower freshwater pro­ (9)–(11)), one can estimate the cooling capacity, power input, and
duction due to the reduced cooling capacity of the dehumidifying current consumption. These estimated values are compared with the
evaporator, but the opposite is true. It was observed that reducing the actual measured values obtained from the experiment in Table 4. The
airflow rate led to a more efficient humidification process inside the difference between estimated and measured values (errors) at similar
evaporative condenser due to the increased humidity of the air. As the saturation temperatures of the evaporator (Te) and condenser (Tc) are
enthalpy (ha2) and absolute humidity (ωa2) of air exiting the evapora­ reported in Table 4 for compressor speeds of 2500, 3300, and 4000
tive condenser rose by reducing airflow rate, the dehumidification RPM, respectively. It is apparent that the constants for Eqs. (9)–(11) are
process over HP evaporator enhanced and more freshwater was pro­ a function of compressor speeds. The experimental value for current
duced. Consequently, a combination of decreasing the airflow rate by consumption was measured by clamp meter (Table 2), and those for
34.7% and increasing the difference between absolute humidity of air cooling capacity and power input were calculated by Eqs. (1) and (3),
entering/exiting the dehumidifying evaporator (ωa2-ωa3) by 75.1%, respectively. It can be seen that higher cooling capacity can be provided
resulted in a 13.6% increase in yield according to Eq. (2). Moreover, at increased compressor speeds at the expense of higher power and
Fig. 7 shows that raising the airflow rate reduces the GOR of the system. current consumption. By increasing the compressor speed from 2500 to
By increasing the airflow rate from 65.5 to 100.3 m3/h (decreasing the 4000 RPM, the refrigerant mass flow rate rises from 8.96 to 15.64 kg/h
mass flow rate ratio of saline water to air from 11.9 to 7.7), the con­ leading to an increment of 0.43 and 0.74 kW in cooling capacity, re­
sumption power of air fan rose by 78.3% to reach 27.4 W, while the spectively. Besides, the required input power increases from 0.15 to
required input power of compressor dropped by 4.6% to 295.8 W. The 0.31 kW due to the elevated current consumption from 2.82 to 5.97 A.
combined effect of a 13.6% increase in freshwater production and a Comparing the experimental and correlated data (Table 4) reveals that
2.4% reduction in total required power, lead to higher values of GOR at the cooling capacity correlations over-predicts the experimental data by
lower airflow rates. The minimum air flow rate in the tests was 8.97% with a standard deviation of ± 5.57%, while the power and
achieved by adjusting the fan speed regulator to a ratio of 10%. Further current consumption correlations under-predict the experimental data
decrease in its speed adjustment resulted in the fan shut down. There­ by 13.83% and 19.38% with standard deviations of ± 5.12% and ±
fore, lower air flow rates in future studies can be tested with high re­ 4.80%, respectively. This may be attributed to the amount of re­
solution and finer speed control fans to acquire the exact optimal fan frigerant charging, heat losses from the evaporator, lubrication of the
speed value for a given system. compressor, etc. in the experimental setup.

3.4. Test scenario 4: effect of compressor speed

Previous tests for evaluation of ambient wet-bulb temperature,


saline water, and airflow rates were conducted for a fixed compressor
speed of 4000 RPM. As the cooling capacity in a heat pump is a function
of compressor speed, Danfoss BD350GH-48v variable speed compressor
was utilized in the fabricated system. System performance was experi­
mentally studied at various compressor speeds of 2500, 3300, and 4000
RPM and compared with the polynomials provided by Danfoss cool­
selector®2 software for the same saturation temperatures of the eva­
porator (Te) and condenser (Tc). It is worth mentioning that the com­
pressor speed was adjusted by Tool4Cool® Lab-Edition software
through connecting the electronic controller of the compressor via
Danfoss One Wire/LIN gateway to a laptop. In Fig. 8, the impact of
compressor speed on yield and GOR is illustrated. The ambient wet-
bulb temperature, saline water, and airflow rates were kept constant at
average values of 17.3 °C, 195.8 kg/h, and 78.7 m3/h, respectively. It is
evident that the freshwater productivity rises from 0.33 to 0.67 kg/h by
altering the compressor speed from 2500 to 4000 RPM. This can be
attributed to the higher achievable cooling capacities at elevated
compressor speeds, which is in accordance with the datasheet provided
by the manufacturer of the compressor [29]. Regarding the GOR, it is
noticeable that a maximum value of 1.72 could be achieved at 3300
RPM. An optimum in GOR at different compressor speeds can be at­
tributed to the simultaneous contribution of change in the numerator
(yield) and denominator (power input of compressor) according to the
Eq. (8). The same trend can be observed in the datasheet of the com­
pressor in terms of the heat pump coefficient of performance (COP), Fig. 7. Variation of yield and GOR versus airflow rate and mass flow rate ratio.

7
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

Average error (%)

−13.83 ± 5.12

−19.38 ± 4.8
8.97 ± 5.57
Deviation (%)

4.41
5.70

−17.92
−16.95
−12.62
−23.22
−22.31
16.82

−6.60
Correlation

0.50
0.66
0.79
0.14
0.19
0.26
2.46
3.34
4.64
Experiment

0.43
0.63
0.74
0.15
0.23
0.31
2.82
4.35
5.97
9.72E−06
1.32E−05
1.79E−05
0.000112
0.000143

0.000545
0.000739
0.00017
Fig. 8. The impact of compressor speed on yield and GOR.

0.001
c9
3.5. Test scenario 5: effect of superheat adjustment by the electronic

−6.3E−05

−9.6E−05
−4.5E−05
−6.2E−05
−8.3E−05
−8.1E−07
−1.1E−06
−1.5E−06
expansion valve

−8E−05
Electronic expansion valves afford a fast, precise, and stable control

c8
in heat pump systems due to their various advance active control

1.42E−05
1.92E−05
−0.00163
−0.00207
−0.00247
0.000793
0.001076
0.001456

2.6E−05
methods. The electronic expansion valve works in conjunction with a
superheat controller, which processes the data read out by EEV tem­
c7

perature sensor and pressure transducer mounted at the dehumidifying


evaporator outlet (Table 2) and controls the EEV opening degree and

−4.5E−06
−6.1E−06
−8.3E−06
−0.00025
−0.00034
−0.00046
0.001487
0.001773
refrigerant mass flow rate according to the adjusted and measured su­
0.00117

perheat value. The Danfoss EIM-336 superheat controller was used for
c6

controlling the operation of the Danfoss ETS6–08 electronic expansion


valve in the current study. This controller was chosen due to its superior
−0.00769
−0.00978
−0.01165
−0.06403
−0.08687

−0.00114
−0.00155
−0.1176

capability of precise controlling the refrigerant flow rate at variable −0.0021


cooling loads via different control modes [30]. The superheat control
c5

mechanism of the EEV is based on a fact that for a given fixed-size


0.001243
0.001686
0.002283
0.06959
−0.1474
−0.1873
−0.2234

0.0944
0.1278

evaporator and a fixed airflow rate, the electronic expansion valve can't
operate with a fixed refrigerant mass flow rate at higher adjusted su­
A comparison between experimental and correlated data at different compressor speeds.
c4

perheats due to the shortage of heat transfer area (dehumidifying sur­


face area for heat transfer is fixed). Therefore, at higher superheats the
−0.04022
−0.05458
−0.07388
−0.00072
−0.00097
−0.00132
0.2739
0.3479
0.4149

EEV closes to elevate the pressure difference across it and results in


increased temperature difference between the inlet air (state a2) and
c3

saturated temperature of the dehumidifying evaporator (Te) to achieve


0.088503
0.06523

0.11981
4.9565
−6.0305

the desired high superheat. The drop-in opening degree of the EEV at
3.653

6.709
−4.747

−7.192

higher superheats is equivalent to reduced refrigerant mass flow rate,


c2

decreased saturated temperature and pressure of evaporator, and de­


creased cooling load. In the same way, the principle of EEV operation at
−0.72225

1.076548 −0.00951

1.520883 −0.01746
−0.5323

−0.9777

1.203045 −0.0129
26.025

lower superheats can be analyzed. This principle was observed and


20.48

31.03

validated in the current study as well. Fig. 9 demonstrates the effect of


c1

superheat adjustment in heat pump performance for an ambient wet-


bulb temperature of 16.5 °C, a saline water flow rate of 898.8 kg/h, and
707.95

60.29
67.37
85.17

an airflow rate of 66.5 m3/h. It can be seen that the refrigerant mass
558

838
c0

flow rate, EEV opening degree, and evaporator saturation temperature


drop at higher superheats. The saturation temperature of the dehumi­
Compressor speed (RPM)

difying evaporator is influenced by the operation of the electronic ex­


pansion valve due to the change of superheating and mass flow rate of
refrigerant. It was observed that by increasing the superheat from 6.3 to
10.7 °C, freshwater yield dropped from 0.81 to 0.75 kg/h due to a 8.2%
reduction in mass flow rate of the heat pump refrigerant. Because of the
2500
3300
4000
2500
3300
4000
2500
3300
4000

lower heat transfer coefficient in the superheated region of the eva­


porator, the electronic expansion valve decreases the mass flow rate of
Parameter

refrigerant at higher superheats to produce fast cooling at lower sa­


Table 4

turation temperatures of the evaporator [31]. The suction temperature


rises from 15.3 to 18.2 °C by increasing the superheat from 6.3 to
Wc
Qe

8
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

Fig. 9. Effect of superheat adjustment via EEV on heat pump performance.

Fig. 10. A comparison between measured and adjusted superheat (SH).

Fig. 12. A comparison between adjusted and measured evaporator saturation


temperatures.

Table 5
Cost of the system constituents.
Constituents Cost ($)

Compressor 330
Electronic expansion valve 41
EEV pressure transmitter 99
EEV drive 149
EEV superheat sensor 32
Fan 172
Evaporative condenser 150
Evaporator 60
Water pump 23
DC converters, etc. 30
Total equipment cost 1087

Fig. 11. Effect of evaporator saturation temperature on yield and GOR.


slow responding speed and the low precision of thermal expansion
valves associated with the adoption of the mechanical control method
10.7 °C, which may lead to overheating of the compressor and poor
highlight the importance of utilizing the electronic expansion valves
system performance (Fig. 9). On the other hand, a further drop in the
[32]. A comparison between the adjusted and experimentally measured
superheating led to instabilities in the evaporator and misfunction of
superheat among the 112 tests at various ambient wet-bulb tempera­
the compressor due to the possible entrainment of the liquid refrigerant
tures, the sprayed saline water flow rate, airflow rate, and compressor
into it. Therefore, it is desirable to adjust the minimum stable superheat
speeds were shown in Fig. 10. It is observed that the Danfoss-ETS608
both in view point of energy efficiency and compressor lifetime. The
electronic expansion valve and EIM 336 superheat controller

9
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

Table 6 It can be inferred that for evaporator saturation temperatures of 2 to


Economic analysis of the fabricated system. 8 °C the controller sets the evaporator saturation temperatures with a
Parameters Unit Current study maximum root mean square error of 0.08. For the evaporator saturation
temperature of 14 °C, the controller well-match the adjusted value with
Principle cost (P) $ 1087 a root mean square error of 0.01 at higher ambient wet-bulb tem­
Salvage value (S) (10% of principle value) $ 108.7
peratures. However, there exists a deviation for the evaporator sa­
Life of the system (n) Yrs. 20 years
interest rate (i) % 10
turation temperature of 14 °C at lower ambient wet-bulb temperatures.
Capital recovery factor (CRF) – 0.117 This can be attributed to the EEV algorithms to avoid entering liquid
Sink fund factor (SFF) – 0.017 refrigerant to the compressor as well as the combined effect of input
Annual first cost (AFC = CRF ∗ P) $ 127.160 operational conditions and heat exchanger geometry in system perfor­
Annual salvage value (ASV = SFF ∗ S) $ 1.848
mance. It is good to note that there exists a safety control algorithm in
Annual maintenance cost (AMC = 0.15 annual first cost) $ 19.074
Annual current cost (ACC = CC × Power) $ 38.474 the controller named as maximum operating pressure function that
Annual cost = (AFC + AMC + ACC-ASV) $ 182.861 takes precedence over both the superheat control and evaporator sa­
Average daily yield L 25.920 turation temperature control modes to reduce the probable extra cur­
Annual yield (average daily yield ∗ 365) L 9460.800
rent to the compressor. In conclusion, it was observed that the cooling
Cost per liter (CPL = Annual cost/Annual yield) $/L 0.019
capacity of the system increases at higher saturated temperatures of the
evaporator due to its higher refrigerant flow rate in spite of the lower
successfully controls the superheat in the proposed cycle with a root temperature difference potential (Ta2-Te). Therefore, utilization of the
mean square error of 0.52 at different operational conditions. Te control mode at higher adjusted Te values results in more freshwater
production.
3.6. Test scenario 6: effect of saturated evaporator temperature adjustment
by the electronic expansion valve 4. Economic analysis

In addition to the superheat control mode used in previous tests, the The economic analysis of the fabricated system was carried out
EIM-336 controller has a distinct feature of a separate PI control of the based on the reference [33]. The cost of system components is reported
evaporator saturation temperature (Te) for dehumidifying applications in Table 5. It can be seen that the total equipment cost of the fabricated
such as the proposed cycle in the current study. At a lower adjusted system is 1087 $, in which the compressor and electronic expansion
saturated temperature of the evaporator, the opening degree of the valve own approximately 30% of the total equipment cost.
valve decreases to provide higher pressure reduction. This results in Table 6 represents a summary of the conducted economic analysis.
lower refrigerant mass flow rate and cooling capacity of the dehumi­ By considering a daily operation and current cost of CC = 0.012$/
difying evaporator. To explain more, the negative impact of the re­ (kWh) [8], the cost of freshwater for the current study is 0.019 $/L. A
duction in refrigerant mass flow rate caused by adjusting a lower sa­ comparison between various experimental studies on HDH-HP systems
turated temperature on cooling capacity and water productivity is far is shown in Table 7. It can be seen that most of the previous HDH-HP
greater than the resulting positive effect of the higher temperature systems were used several heat exchangers, while the current study
difference between the inlet air (state a2) and saturated temperature of intended to fabricate and test the performance of a novel HDH-HP
the evaporator (Te). Effect of adjusting the evaporator saturation tem­ system with just two heat exchangers. The principle operation and
perature via EEV controller on yield and GOR of the system is depicted design of the previous HDH-HP systems that utilize separate heat ex­
in Fig. 11 for an average ambient wet-bulb temperature of 28.7 °C, changers i.e., the humidifiers, heat pump condensers, air/water heaters,
saline water, and airflow rates of 898.8 kg/h and 69.3 m3/h at a etc. are well known. However, the compact evaporative condenser
compressor speed of 4000 RPM. It is evident that by increasing the based HDH-HP system proposed in this work still needs to be modified
evaporator saturation temperature from 2 to 14 °C, the freshwater to reach enhanced performance with lower costs. As indicated in
production rose from 0.61 to 1.08 kg/h. This can be attributed to the Table 7, the freshwater production of the fabricated system is 1.08 kg/
57.1% increase in the EEV opening degree and 80.3% rise in the re­ h, which is the minimum yield among previous studies. The reason for
frigerant mass flow rate. Consequently, the cooling capacity increases this behavior is that productivity is a function of the cooling load
from 0.11 to 0.55 kW by altering the adjusted evaporator saturation provided by the system compressor. The Danfoss BD-350GH 48v com­
temperature from 2 to 14 °C. It is worth mentioning that according to pressor used in the current system is a small compressor with less than
the manufactures datasheet, the maximum allowable saturated tem­ 1 kW cooling load. This is worth mentioning that the HDH-HP cycles
perature of the BD-350GH 48v compressor used in this study was re­ are mainly utilized in remote areas, where providing the electrical en­
ported to be 15 °C [29]. Further increase in the evaporator saturation ergy from the main utility grid would be a challenging problem.
temperatures results in failure of compressor electrical coil and damage Therefore, the DC compressor used in the current system gives an ad­
of its electromotor. Also, the minimum allowable temperature must be ditional option of being powered by photovoltaic panels. However, to
greater than zero to avoid freezing on the evaporator coil. A comparison analyze the system performance in various input conditions, the re­
between adjusted and measured evaporator saturation temperatures for quired DC electrical current of the system was supplied by an AC to DC
55 tests is shown in Fig. 12 at different ambient wet-bulb temperatures. converter in all of the tests. It is evident that by using larger

Table 7
A comparison between various experimental studies on HDH-HP systems.
Ref. Year Type of heat pump condenser No. of heat exchangers GOR Yield (kg/h) CPL ($/L)

Amin & Hawlader [36] 2015 Water-cooled 5 0.43–0.88 1.38 –


Zhang et al. [16] 2018 Water-cooled 6 2.05 22.26 0.05
Xu et al. [18] 2018 Water-cooled 6 1.24 12.75 0.03
Shafii et al. [21] 2018 Air-cooled 3 2.08 2.79 0.01
Xu et al. [19] 2019 Water-cooled 8 1.93 17.45 0.03
Zhang et al. [26] 2019 Water-cooled 5 2.57 29.2 0.04–0.14
Current study 2020 Evaporative condenser 2 2.00 1.08 0.019

10
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

compressors, the provided cooling load and daily freshwater production to the increased cooling capacity at higher evaporator temperature.
increase as well. Therefore, the dimensionless GOR values were re­
ported in Table 7 to compare the performance of different HDH-HP Declaration of competing interest
cycles better. It can be observed that the GOR of the current setup
reaches 2.00, which is one of the highest values of the table compared The authors declare that they have no known competing financial
to those of previous HDH-HP systems. It is estimated that by designing interests or personal relationships that could have appeared to influ­
large-scale modified prototypes in future studies, the ratio of losses to ence the work reported in this paper.
useful energy of the system drops, and much higher GOR values can be
attained. The CPL of the current system reached 0.019 $/L, according to Acknowledgments
Table 7. The obtained lower CPL compared to most of the previous
systems may be attributed to fewer heat exchangers. This is good to The authors would like to declare their appreciation to the Deputy
note that all of the electrical components utilized in this study were DC for Research and Technology of Sharif University of Technology and
devices that have the capability of being powered by solar photovoltaic Sharif Energy Research Institute (SERI) for supporting this research
panels. Commercial DC refrigeration compressors are generally small- study.
sized, and a limited range of products are available for selection. It was
observed that using small scale compressor led to lower productivity, it References
is recommended to investigate the performance of larger capacity AC
compressors in the future. According to a general rule, the cost of a [1] T. Luo, R. Young, P. Reig, Aqueduct Projected Water Stress Country Rankings,
compressor increases non-linearly with its capacity [34]. Therefore, Technical Note (2015).
utilizing larger compressors not only will boost the daily yield sig­ [2] H.S. Son, M.W. Shahzad, N. Ghaffour, K.C. Ng, Pilot studies on synergetic impacts of
energy utilization in hybrid desalination system: multi-effect distillation and ad­
nificantly but also result in much lower production costs. Besides, the sorption cycle (MED-AD), Desalination 477 (2020) 114266.
prices for electronic expansion valves remain almost constant by in­ [3] W.J. Lee, Z.C. Ng, S.K. Hubadillah, P.S. Goh, W.J. Lau, M.H.D. Othman, A.F. Ismail,
creasing the refrigeration capacity up to an extend according to the N. Hilal, Fouling mitigation in forward osmosis and membrane distillation for de­
salination, Desalination 480 (2020) 114338.
Danfoss list pricing [35]. Therefore, by designing large-scale systems [4] G.P. Narayan, M.H. Sharqawy, E.K. Summers, J.H. Lienhard, S.M. Zubair,
and conducting more detailed economic analysis as done in [11], the M.A. Antar, The potential of solar-driven humidification–dehumidification desali­
current cycle may attain more commercial attention in the future. nation for small-scale decentralized water production, Renew. Sust. Energ. Rev. 14
(2010) 1187–1201.
[5] S. Al-Hallaj, S. Parekh, M. Farid, J. Selman, Solar desalination with humidifica­
5. Conclusion tion–dehumidification cycle: review of economics, Desalination 195 (2006)
169–186.
[6] A. Kasaeian, S. Babaei, M. Jahanpanah, H. Sarrafha, A. Sulaiman Alsagri,
A novel compact design was proposed for integrating a humidifi­
S. Ghaffarian, W.-M. Yan, Solar humidification-dehumidification desalination sys­
cation-dehumidification cycle with a heat pump and was studied ex­ tems: a critical review, Energy Convers. Manag. 201 (2019) 112129.
perimentally. The condenser of the heat pump was utilized as both the [7] A. Giwa, N. Akther, A. Al Housani, S. Haris, S.W. Hasan, Recent advances in hu­
conventional humidifier and heating source of the HDH cycle. This was midification dehumidification (HDH) desalination processes: improved designs and
productivity, Renew. Sust. Energ. Rev. 57 (2016) 929–944.
done by exploiting an evaporative condenser in an HDH-HP cycle for [8] P. Behnam, M.B. Shafii, Examination of a solar desalination system equipped with
the first time. Moreover, the evaporator of the heat pump was used as an air bubble column humidifier, evacuated tube collectors and thermosyphon heat
the sole dehumidifier of the fabricated system. The influence of various pipes, Desalination 397 (2016) 30–37.
[9] K.M. Chehayeb, G.P. Narayan, S.M. Zubair, Thermodynamic balancing of a fixed-
parameters as ambient wet-bulb temperature, flow rate of spraying size two-stage humidification dehumidification desalination system, Desalination
saline water in the evaporative condenser, airflow rate, compressor 369 (2015) 125–139.
speed, superheat, and evaporator saturation temperature control modes [10] D. Lawal, M. Antar, A. Khalifa, S. Zubair, F. Al-Sulaiman, Humidification-dehumi­
dification desalination system operated by a heat pump, Energy Convers. Manag.
of the electronic expansion valve was examined on the system perfor­ 161 (2018) 128–140.
mance. The following results were obtained: [11] D.U. Lawal, S.M. Zubair, M.A. Antar, Exergo-economic analysis of humidification-
dehumidification (HDH) desalination systems driven by heat pump (HP),

• The highest yield, GOR, and CPL of the current system for an Desalination 443 (2018) 11–25.
[12] W. He, D. Han, C. Ji, Investigation on humidification dehumidification desalination
average wet-bulb temperature of 28.1 °C sprayed saline water flow system coupled with heat pump, Desalination 436 (2018) 152–160.
rate of 898.8 kg/h, airflow rate of 83.8 m3/h, compressor speed of [13] W. He, H. Yang, D. Han, Thermodynamic analysis of a novel humidification de­
humidification desalination system driven by heat pump, Energy Procedia 158
4000 RPM and EEV evaporator saturation temperature adjustment
(2019) 6030–6037.
of 14.05 °C, were achieved as 1.08 kg/h, 2.00, and, 0.019$/L, re­ [14] W. He, H. Yang, D. Han, Thermodynamic investigation and optimization of a heat
spectively. pump coupled open-air, open-water humidification dehumidification desalination

• Higher ambient wet-bulb temperatures and sprayed saline water system with a direct contact dehumidifier, Desalination 469 (2019) 114101.
[15] S. Dehghani, A. Date, A. Akbarzadeh, Performance analysis of a heat pump driven
flow rate resulted in more produced freshwater and GOR, while the humidification-dehumidification desalination system, Desalination 445 (2018)
opposite occurred for the airflow rate. 95–104.

• By analyzing the system performance at various compressor speeds [16] Y. Zhang, C. Zhu, H. Zhang, W. Zheng, S. You, Y. Zhen, Experimental study of a
humidification-dehumidification desalination system with heat pump unit,
of 2500, 3300, and 4000 RPM, it was shown that increasing the Desalination 442 (2018) 108–117.
compressor speed raises the freshwater productivity. This occurred [17] Y. Zhang, H. Zhang, W. Zheng, S. You, Y. Wang, Numerical investigation of a hu­
because of increased refrigerant mass flow rate and heat pump midification-dehumidification desalination system driven by heat pump, Energy
Convers. Manag. 180 (2019) 641–653.
cooling load at higher compressor speeds.

[18] H. Xu, Y. Zhao, T. Jia, Y. Dai, Experimental investigation on a solar assisted heat
The experimental data were compared with correlated data of pump desalination system with humidification-dehumidification, Desalination 437
Danfoss coolselector®2 characteristic polynomials. It was observed (2018) 89–99.
[19] H. Xu, Y. Zhao, Y. Dai, Experimental study on a solar assisted heat pump desali­
that the cooling capacity correlations over-predicts the experimental
nation unit with internal heat recovery based on humidification-dehumidification
data by 8.97% with a standard deviation of ± 5.57%, while the process, Desalination 452 (2019) 247–257.
power and current consumption correlations under-predict the data [20] H. Xu, Y. Dai, Parameter analysis and optimization of a two-stage solar assisted heat
pump desalination system based on humidification-dehumidification process, Sol.
by 13.83% and 19.38% with standard deviations of ± 5.12%
Energy 187 (2019) 185–198.
and ± 4.8%, respectively. [21] M.B. Shafii, H. Jafargholi, M. Faegh, Experimental investigation of heat recovery in
a humidification-dehumidification desalination system via a heat pump,
It was concluded that higher freshwater was produced by increasing Desalination 437 (2018) 81–88.
[22] M. Faegh, M.B. Shafii, Performance evaluation of a novel compact humidification-
the adjusted evaporator saturation temperature from 2 °C to 14 °C, due

11
M. Faegh and M.B. Shafii Desalination 496 (2020) 114733

dehumidification desalination system coupled with a heat pump for design and off- pdf.
design conditions, Energy Convers. Manag. 194 (2019) 160–172. [30] http://files.danfoss.com/TechnicalInfo/Dila/01/DKRCC.PS.RQ0.B7.02_EIM336_
[23] H.M. Ettouney, H.T. El-Dessouky, W. Bouhamra, B. Al-Azmi, Performance of eva­ sw.pdf.
porative condensers, Heat Transfer Engineering 22 (2001) 41–55. [31] A. Tambovtsev, H. Quack, Increasing the Evaporation Temperature With the Help
[24] H. Liu, Q. Zhou, Y. Liu, P. Wang, D. Wang, Experimental study on cooling perfor­ of an Internal Heat Exchanger, Technische Universität Dresden, Dresden, Germany,
mance of air conditioning system with dual independent evaporative condenser, 2000.
Int. J. Refrig. 55 (2015) 85–92. [32] J. Liu, J. Chen, Q. Ye, Z. Chen, A new model for depicting mass flow rate char­
[25] A. Ilie, R. Dumitrescu, L. Drughean, R. Calotă, A. Girip, Experimental investigation acteristic of electronic expansion valves, Exp. Thermal Fluid Sci. 32 (2007)
of condensation heat transfer in ammonia evaporative condensers, Energy Procedia 214–219.
112 (2017) 150–157. [33] R. Dev, S.A. Abdul-Wahab, G.N. Tiwari, Performance study of the inverted absorber
[26] Y. Zhang, H. Zhang, W. Zheng, S. You, Y. Wang, Optimal operating conditions of a solar still with water depth and total dissolved solid, Appl. Energy 88 (2011)
hybrid humidification-dehumidification and heat pump desalination system with 252–264.
multi-objective particle swarm algorithm, Desalination 468 (2019) 114076. [34] M. Sadeghi, A. Chitsaz, S. Mahmoudi, M.A. Rosen, Thermoeconomic optimization
[27] D.U. Lawal, S.A. Jawad, M.A. Antar, Experimental and theoretical study on a heat using an evolutionary algorithm of a trigeneration system driven by a solid oxide
pump driven open-air humidification dehumidification desalination system, Energy fuel cell, Energy 89 (2015) 191–204.
118252 (2020). [35] https://assets.danfoss.com/documents/DOC289376635817/DOC289376635817.
[28] W.F. Stoecker, W.F. Stoecker, Industrial Refrigeration Handbook, McGraw-Hill, pdf.
New York, 1998. [36] Z.M. Amin, M.N.A. Hawlader, Analysis of solar desalination system using heat
[29] https://assets.danfoss.com/documents/DOC017486436307/DOC017486436307. pump, Renew. Energy 74 (2015) 116–123.

12

You might also like