Professional Documents
Culture Documents
077625-S52-CP-0181-1002_C
077625-S52-CP-0181-1002_C
(HURL), Sindri
PROJECT REFERENCE
Originator
Project N° Unit Number Doc. Type Material Code Serial Number Revision Page
LT 077625 S52 CP 0181 1002 A Page 1 of 31
Document Type - OPERATION & MANTENANCE MANUAL FOR AMMONIA STORAGE FLARE
DOCUMENT TYPE
PR NO :
DOCUMENT CATEGORY
INFORMATION – Class 1
REVIEW – Class 2
CODE 1 (Not accepted. New document / CODE 1 (Not accepted. New document / drawing
drawing to be submitted) to be submitted)
CODE 2 (Accepted with comments as
CODE 2 (Accepted with comments as marked)
marked)
For information
CTR to note that Code-01 is given,
प्रोजेक एण् डेवलपम� ट इं�डया �ल�मटेड नोएडा
subject to incorporation of comments
PROJECTS & DEVELOPMENT INDIA LTD. NOIDA
07.04.2021
This Approval does not absolve the Supplier / Contractor of their contractual
obligations / responsibilities
CONFIDENTIAL INFORMATION – The information contained in this document belongs to LTHE. All IP rights relevant to this document are expressly reserved.
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 1 of 29
FLARE SYSTEM
MANUAL
FOR
OF
ISSUE : ZERO
DATE :
CONTENTS
Page no.
1.0 INTRODUCTION 5
4.0 UTILITIES 10
6.0 SAFETY 21
7.0 PRE-COMMISSIONING 22
8.0 COMMISSIONING 23
11.0 TROUBLESHOOTING 26
11.1 Troubleshooting of FFG Ignition System 26
11.2 Troubleshooting of Pilot Burner 27
11.3 Troubleshooting of Thermocouple Flame-Detection System 28
11.4 Troubleshooting of Molecular Seal 29
Attachment: Appendix 1 – Sketch for Thermocouple & Venturi Shutter Setting 1 sheet
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 4 of 29
1.0 INTRODUCTION
Flares are an integral part of the safety systems intended to prevent the
risks of accumulation of explosive, flammable, deleterious, toxic and
polluting gases in the atmosphere. A flare system is designed to dispose off
the specified gas stream safely and efficiently by flaring.
Under this Ammonia Urea Fertilizer Complex Project of M/s. HURL, Barauni;
total 3 nos. of Flare viz. Synthesis Gas Flare (S54-PK-0001), Ammonia
Gas Flare (S54-PK-0002) & Ammonia Storage Flare (S52-X-0001) are
implemented.
Supplied Unassisted Flare Tip FNS 24/14 is fitted with flame stabilizers and
three pilot burners, which maintains a constant source of ignition at all
times, and under all operating conditions. The flare tip is equipped with a
slatted windshield to prevent flame lick and help to cool the top of the flare
tip closest to the flame envelope. The tip is also provided with flame
retention lugs to provide flame stability at high flare gas discharge rates.
The Molecular Seal AFS 14 is located just below the Flare tip. The seal has
been designed to prevent air ingress into the flare riser thus preventing the
formation of an explosion mixture in the system. A small continuous bleed of
purge gas at specified flow must be maintained in order to ensure that the
air does not penetrate in the seal & below.
Following items are supplied by Airoil Flaregas for the Flare Package of this project:
Sr.
Qty. Item/Description
No.
1 1 off Flare Tip FNS 24/14 with 3 nos. Pilot Burners
2 1 off Molecular Seal AFS 14
3 1 off Flare Stack Riser
4 1 off Flame Front Generator Panel
5 1 off LPG Manifold System
Thermocouple cable (Flare tip To FFG Panel) & Temperature
6 1 lot
Transmitters
7 1 lot Utility Piping (Flare tip to FFG Panel)
8 1 off Retractable Davit Assembly
9 1 lot Mandatory Spares
10 1 lot Commissioning Spares
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 6 of 29
4.0 UTILITIES
Battery Limit
Utility required for Specified Service
Conditions
Sr.
Service Flow
No. Pressure Temp. Pressure
rate / Requirement Remarks
bar (g) Deg. C bar (g)
Wattage
A FUEL GAS
For FFG Panel Outlet of
Min: 5 4.8
1 Ignition Min: 3.5 Intermittent 1.4 S52-PCV-
Nor: 5 Kg/hr
(During Start-up) Nor: 4 0567
Max: 35.5
Pilot gas per Pilot Max: 5 Outlet of
Des: 1.9
2 (Continuous) – 3 Des: 6.5 Continuous 1.4 S52-PCV-
-28/90 Kg/hr
pilot 0567
B NITROGEN
Min: 6 Min: -
For Purging of Outlet of
Nor: 8 Nor: Amb. 1.1 ~0.5-1.0
1 Molecular Seal to 3 Continuous 2 S52-RO-
Max: - Max: - Nm /hr Kg/cm
avoid air ingress 0546
Des: 9 Des: 70
C INSTRUMENT AIR (Note-2)
For FFG Panel Outlet of
50
1 Ignition (During 3 Intermittent 1.4 S52-PCV-
Min: 6 Supply Nm /hr
Start-up) 0566
Nor: 8 Temp.:
For Flame Diverter
Max: - Amb
Valve; Air and FG 10
2 Des: 10.5 Des: 70 3 Intermittent 4.0 - 6.0
on-off valve on Nm /hr
FFG panel
D ELECTRICITY
For FFG Ignition
115V AC, 1 phase,50Hz
1 Panel 1.5 kW Intermittent - Note-3
(UPS)
(During Start up)
E DM Water
1 For U-Seal Filling 4 Amb. - Intermittent - Note-5
Notes:
DESCRIPTION
The flare tip is located at the top most portion of the flare where the flare
gas is ignited & destructed by means of combustion. The flare tips are
available in many different types of design & construction depending on the
application requirement and suitability as per composition of gases to be
flared.
The supplied Flare Tip FNS 24/14 is Un-assisted type flare tip.
The flare tip is supplied with a slatted type Windshield to prevent flame lick,
hold the flame above the tip and to help cool the top portion of the flare tip
closer to the flame envelope.
The flare tip is also provided flame retention lugs to provide flame stability at
high flare gas discharge rates.
The flare tip is also supplied with burn back thermocouple to detect the low
burning or lowering of the flame inside the flare tip body causing burn back,
which give indication at FFG Panel as well as at the DCS.
The FNS 24/14 Flare Tip is provided with 3 nos. pilot burner, which maintains
a constant source of ignition at all time and under all operating conditions.
The Flare pilot is of self-inspiriting type and utilizes a gas pressure in the
venturi to entrain combustion air. Sufficient combustion air is entrained to
ensure the pilots remain lit even when blanketed by inert gas.
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 11 of 29
The pilot nozzle has built-in flame retention and includes a shield to ensure a
stable flame and enable positive re-ignition even in condition of high winds.
Ignition of the pilot is via a flame front generated at a remote panel and fed
to the pilot nozzle via a 1” igniter tube. (The pilot gas is supplied via a ½”
inlet to the venturi with an air adjuster). The air is pre-mixed with gas in a
2” gas tube and is ignited at the pilot nozzle by the flame front.
The pilot venturi, for entrainment of air, is located at the lower end of the
assembly to ensure that gas free air is inspirited. Air adjuster should be set
approximately at 4 mm open.
Note: Do not open the air adjuster too much since a highly inspirited
flame can flash back into the pilot tube.
The Molecular seal is basically a gas inversion device causing the gas
normally flowing in an upward direction to be turned to 180 degrees and flow
downward for a short length before being redirected through 180 degrees
back in the original direction of flow. In a static condition, gases lighter than
air will tend to collect in the upper bend, sealing off the stack against the
back flow of air. Heavier gases will tend to settle in the lower bend with the
same effect. Some wind and atmospheric action will affect these interfaces
slightly and also molecular diffusion of the two gases will take place at the
interface. In order to counteract these effects, a small continuous bleed of
purge gas at specified flow must be maintained in order to ensure that the
air does not penetrate in the seal.
The seal only is not meant for reducing oxygen concentration in the flare tip
or any part effectively downstream from it. The presence of Flare seal results
in significant savings in purge gas consumption.
The Flame Front Generator panel provided is suitable for 3 nos. pilot burners
of flare.
If a tube is filled with a static mixture of fuel gas and air, within the fuel’s
combustibility limits and an ignition source is supplied to one end, a crescent
shaped flame front will travel along the full length of the tube, at or about
the burning velocity.
The emergence of this flame front at the flare tip, adjacent to the pilot gas
tip, will thus provide a reliable ignition source to the pilot.
The ignition system is designed to ignite one pilot at a time. As the panel is
mounted remote from the flare, the gas and air pressure are required to be
regulated suitably to create a flammable mixture in the 1” ignition pipe.
Minor pressure adjustment required can be done by the needle valves
provided on the panel (V601 for Air & V602 of Gas). Flame front is
distributed by means of the flame front diverter and thus all pilots are
lighted up sequentially.
The pilot gas (continuous fuel gas is supplied in pilot line) and ignition gas
(fuel gas) (S52-PCV-0567) are supplied at 1.4 kg/cm2 (g) (S52-PG-0571)
pressure and around 0.1 to 0.2 kg/cm2 (g) (S52-PG-0570) pressure
respectively from the panel while the ignition air (instrument air) (S52-PCV-
0566) is supplied at 1.4 kg/cm2 (g) (S52-PG-0568). The pressures are
indicated individually by locally mounted pressure gauges. Actual pressure
of air & ignition gas should be adjusted at site during commissioning.
The milli-Volt (mV) signals for pilot flame detection are generated by
Thermocouples (TE-1001A/B / TE-1002A/B / TE-1003A/B) fitted internally in
the pilot nozzles. These signals are carried through Thermocouple cables up
to temperature transmitter to convert the mV signals to mA signals. The mA
signals are then carried to the control room/DCS from where signals are
carried to panel to suitably activate the pilots on / off indication lamps.
WHEN
Pilot – 1 is ON : Indicating Lamp L1 [GREEN] is ON
Pilot – 2 is ON : Indicating Lamp L3 [GREEN] is ON
Pilot – 3 is ON : Indicating Lamp L5 [GREEN] is ON
WHEN
Pilot – 1 Flame Fails : Indicating Lamp L2 [RED] is ON
Pilot – 2 Flame Fails : Indicating Lamp L4 [RED] is ON
Pilot – 3 Flame Fails : Indicating Lamp L6 [RED] is ON
WHEN
Burnback occurs : Indicating Lamp L9 [RED] is ON.
Power Supply to Panel is ON : Indicating Lamp L12 [RED] is ON.
System Lockout : Indicating Lamp L10 [RED] is ON
Pilot Gas Pressure Low : Indicating Lamp L11 [RED] is ON
Lamps L7 (Red) & L8 (Green) are spare.
5.3.6 Function of Various Push Buttons & Switches mounted on FFG Panel
(Pilot Monitoring box):
Ignition Principle:
The pilot monitoring panel (local panel) will have indication of pilot flames
`On’ or `Off’ for remote/control room indication. Pilot burners of flare
system can light up in auto or manual mode.
The Local / Remote Selector switch (SS-4) is provided on the FFG panel to
enable the operation from FFG panel when Local mode is selected or to
enable the operation from Control room (DCS).
Both Auto operations are possible from FFG panel (Local mode) and DCS
OWS (Remote mode) as described below.
mode as well as Manual mode, both operation will issue a command from
DCS only).
a) If Pilot `1’ is unlit (S52-TAL-1001 is at low level limit which is less than
100deg C), flame front line of pilot –1 will filled up as all the solenoid
valves of 3-way flame diverter valves S52-POV-001 & S52-POV-002 with
de-energized condition allows combustible mixture of air & gas to pilot–1
FFG Line.
b) 0-90 second flame front line fill up time delay (Ignition on delay timer) is
operated.
d) A 0-90 Sec flame propagation timer is actuated to give time for the pilot
to light-up & signal to control room/local panel.
g) If all the pilot burners are lighted up (by checking the corresponding pilot
TAH limit which is greater than or equal to 100deg C), the sequence will
not be repeated and XV-0707 and XV-0708 will be closed by de-
energization of SOV-003 and SOV-004.
i) After successful completion of light up sequence for all pilots, if any pilot
is extinguished in some time during auto mode operation. So,
Local/Remote switch (SS-4) is in remote position and Auto/Manual switch
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 16 of 29
B) Manual Mode
b) Select the pilot burner to be lit up by turning the selector switch (SS2) as
per table shown in wiring diagram to pilot-1, pilot-2 or pilot-3; the table
reproduced hereunder for ready reference:
d) Press the ignition push button (PB1) mounted at local panel and initiates
a spark through ignition transformer. Duration of spark will be controlled
by timer (0-60 sec) adjustable in the local control panel.
e) The flame thus created will travel up to the ignition/flame front line and
will emerge at the pilot nozzle thus lighting the pilot, which is selected.
f) The pilot ON/OFF status is indicated on FFG Ignition Panel. Steps (c) to
(e) are to be repeated till that particular pilot is light up.
Notes:
2) Lamp test on local panel can be carried out using push button (PB4).
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 17 of 29
6) During ignition process of pilots from DCS OWS or from FFG, if any one of
the inline solenoid valve S52-SOV-003 or S52-SOV-004 are open and
feedback signal is/ are not indicated in DCS OWS within a certain time
period i.e. 90 seconds after starting the sequence, then sequence to be
stopped and close command to be generated for air s52-SOV-003 &
Ignition Gas S52-SOV-004.
a) To install & keep davit assembly ready for operation, the wire rope (Part
no. 45) is to be inserted from bottom of davit pipe (Part no. 1) and is to
passed (Part no.3) over the pulley on davit arm (Part no. 2) & then to be
fixed on lifting beam (Part no. 5).
b) Rope is to be guided by guiding pulley (Part no. 46) which is provided on
every platform & it is also passed through directional pulley (Part no. 44,
at ground level) & manual ground winch located at grade level.
c) The rope (Part no. 24) of platform winch (Part no. 28) is to be passed
through the directional pulley (Part no. 29) & guide pulley (Part no. 23)
which is to be fixed with the davit bottom bracket (Part no. 22).
d) During normal operation (when flare tip is not required to be handled),
the davit will remain at lower elevation on the top platform.
a) The sling with D-Shackle (Part No. 10) is to be fixed on lifting beam (part
no.5).
b) Use of platform winch is to lift the davit pipe from rest position to proper
height, above of the flare tip & then to be turned towards over flare tip
with the help of rod of davit turning table (Part no. 38) which is nearer to
the mounting/Bearing block (Part no 14 to 17).
c) Once the davit is positioned properly over the flare tip then davit is to be
locked with the help of rod (Part no. 20).
d) When the davit is position over the flare tip then the sling with D-Shackle
(Part no. 10) is also to be fixed on lifting lugs of flare tip.
e) Once this all done, all studs & nuts of flanges between the tip & stack
riser are to be removed and start raising through manual ground winch.
f) Raising the flare tip approximately 700 mm in upward direction with the
help of manual ground winch.
g) Once this is done, the davit along with flare tip is to be turned towards
dropout zone direction with the help of rod of davit turning handle (Part
no. 38) which is nearer to the mounting/bearing block (Part no. 14 to
17).
h) Push the down for lowering the flare tip & watch the flare tip moment.
i) Make sure that flare tip is lowered down very slowly i.e. 2 to 3 minute per
meter.
j) Lifting beam and slings are to be released, once the flare tip is reaches at
grade level.
k) For erection of the flare tip, all the activity explained above are to be
carried out reverse sequence. Use the manual ground winch for raising
the tip.
l) Once flare tip is erected as per indicated sequence, davit is to be kept in
a rest position.
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 19 of 29
5 cylinders to be
corrected. 5.5 LPG Manifold System:
(Drawing No. 077625-S52-DW-0181-1015)
LPG Manifold system is provided as back-up for Alternate Fuel gas supply
during start-up. The LPG Manifold system shall comprise of:
LPG from the cylinders can be used as Pilot gas when Fuel Gas is not
available. The change over from Fuel Gas to LPG cylinder is a manual
operation, which is explained further. The Pressure Transmitter (S52-PT-
0183) located on Pilot Gas line will give Low Pressure signal when the
pressure is less than the required set pressure of 1.4 kg/cm2 (g). The lamp
L11 on the Panel will reflect this signal. Also, this signal is provided to control
room. Upon receipt of Low Pressure Signal to control room, an operator
should open the Ball Valve V709 located on LPG Manifold system. Then, the
regulator of one cylinder and ball valve provided on connection between
respective cylinder and LPG manifold to be opened by the operator. The
pressure of LPG gas can be checked by the Pressure gauge S52-PG-0547.
Only one cylinder can be used at a time.
In case of loss of Pilot Flame, the procedure for lighting the Pilots using LPG
shall remain the same as using Fuel Gas. Once the desired gas pressure is
achieved (please refer section 5.3.3 for Gas & Air Supply) the stepwise
procedure as mentioned in the Section – 5.3.7 (FFG PANEL CONTROL LOGIC
DESCRIPTION) can be followed to light the unignited pilot.
While using LPG from Cylinder to light up the pilots during Commissioning,
please follow procedures as detailed under Section – 7: Pre-Commissioning &
Section – 8: Commissioning to put the Flare in service.
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 20 of 29
6.0 SAFETY
Ensure that all lines are drained and properly closed prior to commissioning.
Particular care must be taken at all times to ensure that flammable or
explosive mixtures do not accumulate in the Flare system headers. This
means that air must be excluded and prevented from any part of the Flare
system during operation or maintenance. To ensure this, maintain a
continuous bleed of purge rate as specified elsewhere.
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 21 of 29
7.0 PRE-COMMISSIONING
The complete Flare system should be checked to ensure that it is gas tight
and that drain valves are installed at all low points.
The Flare pilots incorporate small diameter orifices, which are located at the
pilot venturies. Therefore, it is essential that these systems are thoroughly
cleaned to avoid the possible blockage of the orifices by pipe scale and
debris, which would otherwise render the system inoperative.
a) Open the drain valves at all low points in the system to remove any
accumulated water condensate. All lines should be self-drainage back to
the drain valves.
b) Blind off the flare header at the inlet to the Flare Stack.
c) Check that the pilot venturi, air adjusters are set 4 mm open and locked
in this position. This may be suitably adjusted to a maximum of 6 mm
based on the actual requirement.
d) Set the temperature alarm (adjustable) unit in P.M. Box for pilot on/off
indication at around 1000C.
f) Check the proper functioning of the Ignition Transformer and Spark Plug
before going to final operation. Press the Ignition push button and
observe spark formation through the viewing port. If the spark is not
produced adjust the spark gap as follows:
Release the lock nut, securing the electrode adjustment bolt. Screw-in
the adjusting screw until the two spark electrodes touch, then unscrew
the adjusting bolt 1.5 – 2.0 mm and tighten the lock nut.
With pilot / ignition gas isolation, switch on the power to the panel and
operate the ignition push button. A strong spark should be produced.
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 22 of 29
8.0 COMMISSIONING
The entire relief system must therefore be purged of to eliminate air before
the process plant approaches an operating condition where a relief situation
may occur.
b) Ensure that the stack area is cleared of personnel and that the
necessary authority has been obtained to commission the Flare.
c) Remove the blind from the flare header at the inlet of Flare stack.
e) Initiate a supply of ignition and pilot gas and set pressure to 0.2
Kg/cm2g & 1.4 Kg/cm2g respectively. Similarly set air pressure to 1.4
Kg/cm2g. Allow sufficient time for the gas to pass through the venturies
to inspirit air for ignition and to fill the ignition and pilot tubes.
g) Under certain conditions the gas / air mixture will explode with a loud
bang when the igniter is operated. If this happens it can be reduced by
slightly reducing the air pressure.
h) If the igniter fails to create flame front, then the air pressure should be
slightly reduced and another attempt should be made. This should be
repeated until the ignition is successful.
i) When ignition of the pilot is successful, turn off the igniter / flame front
gas supply to the igniter.
j) The pilot flame on the forced draught pilot should be stable and about
0.6 meters in length.
Before starting flare, ensure that all pilots are lighted up. Procedure for
lighting up the pilot is explained under section 7.0 (Pre- Commissioning)
Note:
Before leaving, ensure that all personnel are aware that the unit is alive and
take all necessary precautions to prevent personnel climbing the stack.
AIROIL FLAREGAS PRIVATE LIMITED
OPERATION & MAINTENANCE MANUAL Page 24 of 29
On weekly basis all low point drain valves should be opened to discharge any
accumulated liquids.
1. Isolate the elevated Flare gas inlet and fit a spectacle blind between the
inlet flanges.
11.0 TROUBLESHOOTING
12.1 DO’S:
Isolate the elevated Flare gas inlet and fit a spectacle blind.
12.2 DON’T: