1. SAFETY
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY
OUT THE ELECTRICAL INSTALLATION!
This quick guide contains clearly marked warnings which are intended for your per-
sonal safety and to avoid any unintentional damage to the product or connected ap-
pliances.
1
installation vacon •2
2. INSTALLATION
MI1 MI2-3 1 2
=M 4 =M 5
2
3 • vacon installation
3~ (230V, 400V)
Strip the
plastic cable
coating for
360° earthing
MAINS MOTOR
1~ (230V) 1~ (115V)
Motor out
L1 L2/N L3 R+ R- U/T1 V/T2 W/T3
Strip the
plastic
cable
coating
for 360°
earthing
2
installation vacon •4
2.2.2 Control cabling
Control cable
tightening
torque: 0.4 Nm
2
5 • vacon control i/o
1 2 3 6 7 8 9 10 25 24
3
navigation & startup vacon •6
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
REFERENCE
MENU REF REF
Displays the MON MON
keypad reference
value PAR PAR
regardless of PUSH
the selected FLT Hz FLT Hz
control place. FWD REV I/O KEYPAD BUS
FWD REV I/O KEYPAD BUS
ROTATE
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
MONITORING REF
REF
MENU
In this menu MON MON
you can
browse the PAR PAR
monitoring PUSH
values. FLT FLT
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS
ROTATE
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
PARAMETER REF
MENU REF
In this menu MON MON
you can
browse and PAR PAR
edit the
parameters. FLT PUSH FLT
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS
ROTATE
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT
FAULT HISTORY REF REF
MENU
Here you will MON MON
be able
PAR PAR
to browse
through the FLT PUSH FLT
faults occurred.
FWD REV I/O KEYPAD BUS FWD REV I/O KEYPAD BUS
4
7 • vacon navigation & startup
Alternates
in the display
READY RUN STOP ALARM FAULT READY RUN STOP ALARM FAULT READY R UN STOP ALARM FAULT
REF REF REF
MON MON MON
PA R PAR PAR
FLT FLT rp m FLT
4
navigation & startup vacon •8
READY RUN STOP A LARM FAULT READY RUN STOP ALARM FAULT READY R UN STOP ALARM FAULT
REF REF REF
MON MON MON
PA R PAR PAR
Selections:
P1.1 P1.2 P1.7 P1.15 P2.1 P2.2 P2.3 P3.1 P3.2 P3.3 P4.2 P4.3
1,1 x 0= 0= 0= 0 0=
50/60 50/60
0 = Basic V* Hz INMOT Not I/O Ramp Coast. Hz Hz Ai1 3s 3s
used 0-10V
1,1 x 0= 0= 1= 20 0=
1 = Pump drive 50/60 Not I/O Ramp Ramp Hz 50/60 Ai1 5s 5s
V* Hz INMOT used Hz
0-10V
0= 0= 0= 20 0=
50/60 1,1 x 50/60
2 = Fan drive V* Hz Not
INMOT used
I/O Ramp Coast. Hz Hz Ai1 20 s 20 s
0-10V
1,5 x 1= 0= 0= 0 0=
3 = Conveyor V*
50/60
I/O Ramp Coast. Hz
50/60
Ai1 1s 1s
Hz INMOT Used Hz
drive 0-10V
*Same as drive voltage,
except in 115V drives
this value is 230V
Parameters P1.1 Motor Un (V) P2.3 Stop function
affected: P1.2 Motor fn (H z) P3.1 Min frequency
P1.7 Current limit (A) P3.2 Max frequency
P1.15 Torque boost P3.3 I/O reference
P2.1 Control place P4.2 Acc. time (s)
P2.2 Start function P4.3 Dec time (s)
PAR
FLT
4 Push to
confirm
drive setup
Figure 3: Drive setup
4
9 • vacon monitoring & parameters
5
monitoring & parameters vacon • 10
0 = Not used
P1.15 Torque boost 0 1 0 109
1 = Used
1 = I/O terminal
P2.1 Remote control place 1 2 1 172 2 = Fieldbus
(one selection removed)
P2.2 Start function 0 1 0 505 0 = Ramp 1 = Flying start
P2.3 Stop function 0 1 0 506 0 = Coasting 1 = Ramp
P3.1 Min frequency 0,00 P3.2 Hz 0,00 101
P3.2 Max frequency P3.1 320 Hz 50,00 102
0 = Preset Speeds (0-7)
1 = Keypad Reference
2 = Fieldbus Reference
P3.3 I/O reference 0 4 3 117
3 = AI1 (API FULL &
LIMITED)
4 = AI2 (API FULL)
P3.4 Preset speed 0 0,00 P3.2 Hz 5,00 124 Activated by digital inputs
P3.5 Preset speed 1 0,00 P3.2 Hz 10,00 105 Activated by digital inputs
P3.6 Preset speed 2 0,00 P3.2 Hz 15,00 106 Activated by digital inputs
P3.7 Preset speed 3 0,00 P3.2 Hz 20,00 126 Activated by digital inputs
Acceleration time from 0
P4.2 Acceleration time 0,1 3000 s 1,0 103
Hz to maximum frequency
Table 2: Quick setup parameters
5
11 • vacon monitoring & parameters
5
monitoring & parameters vacon • 12
5
13 • vacon monitoring & parameters
5
monitoring & parameters vacon • 14
5.6 Ramps and brakes setup (Control panel: Menu PAR -> P4)
5
15 • vacon monitoring & parameters
5
monitoring & parameters vacon • 16
5
17 • vacon monitoring & parameters
5.9 Digital and analogue outputs (Control panel: Menu PAR -> P7)
5
monitoring & parameters vacon • 18
5
19 • vacon monitoring & parameters
5.11 Fault autoreset parameters (Control panel: Menu PAR -> P10)
Code Parameter Min Max Unit Default ID Note
Delay before automatic
P10.1 Wait time 0,10 10,00 s 0,50 717 restart after a fault has dis-
appeared
Defines the time before the
frequency converter tries to
P10.2 Trial time 0,00 90,00 s 30,00 718 automatically restart the
motor after the fault has dis-
appeared
0 = Ramp
1 = Flying start
P10.3 Start function 0 2 0 719 2 = According to P4.2
Affects only to start after
autoreset!
0 = Disabled
P10.4 Fault auto reset 0 1 0 731
1 = Enabled
Table 11: Fault autoreset parameters
5
monitoring & parameters vacon • 20
5.13 Easy usage menu (Control panel: Menu PAR -> P0)
Code Parameter Min Max Unit Default ID Note
0 = All parameters visible
Parameter
P13.1 0 1 1 115 1 = Only quick setup param-
conceal
eter group visible
0 = Basic
1 = Pump drive
2 = Fan drive
P13.2 Drive setup 0 3 0 540
3 = Conveyor drive (HP)
NOTE! Visible only during
Startup wizard
Table 13: Easy usage menu
5
21 • vacon monitoring & parameters
5
fault tracing vacon • 22
6. FAULT TRACING
1 Overcurrent
2 Overvoltage
3 Earth fault
8 System fault
9 Undervoltage
Frequency converter undertempera-
13 ture
15 Motor stalled
16 Motor overtemperature
17 Motor underload
35 Application fault
41 IGBT Overtemperature
Analogue input Iin < 4mA (selected
50 signal range 4 to 20 mA)
51 External fault
53 Fieldbus fault
57 Identification fault
Table 1: Fault codes. See User Manual for detailed fault
descriptions.
6
23 • vacon general data
7. GENERAL DATA
Dimensions Frame Height Width Depth (mm) Weight (kg)
and weight MI1 160,1 65,5 98,5 0,55
MI2 195 90 101,5 0,70
MI3 254,3 100 108,5 0,99
Supply network Networks Vacon 10 cannot be used with corner grounded networks
Short circuit current Maximum short circuit current has to be < 50kA
Motor Output voltage 0 - Uin
connection Output current Continuous rated current IN at ambient temperature max. +50ºC
(depends on the unit size), overload 1.5 x IN max. 1min/10min
Ambient Ambient operating -10°C (no frost)…+50°C: rated loadability IN
conditions temperature
Storage temperature -40°C…+70°C
Enclosure class IP20
Relative humidity 0…95% RH, non-condensing, non-corrosive, no dripping water
Altitude 100% load capacity (no derating) up to 1000m. 1% derating for each
100m above 1000m; max. 2000m
Pollution degree PD2
EMC Immunity Complies with EN50082-1, -2, EN61800-3
Emissions 230V : Complies with EMC category C2; With an internal RFI filter
(See detailed 400V: Complies with EMC category C2: With an internal RFI filter
descriptions in Vacon 115V and 575V: Comply with EMC category C4
10 User Manual at: All: No EMC emission protection (Vacon level N): Without RFI filter
www.vacon.com)
Standards For EMC: EN61800-3, For safety: UL508C, EN61800-5-1
Certificates
and manufac- For safety: CB, CE, UL, cUL,
turer’s declara- For EMC: CE, CB, c-tick
tions of (see unit nameplate for more detailed approvals)
conformity
Cable and fuse require- Frame Fuse Mains cable Cu Terminal cable min-max (mm2)
ments (A) (mm2) Main & earth Control & relay
(See detailed data in Vacon
MI1 6
10 User Manual at: 3*1.5+1.5 1.5-4
www.vacon.com) MI2 10
380 - 480V MI3 20 3*2.5+2.5 1.5-6
208-240V 3~
0.5-1.5
575V
MI1 10 2*1.5+1.5
115V 1.5-4
MI2 20 2*2.5+2.5
208 - 240V 1~
MI3 32 2*6+6 1.5-6
- With above-mentioned fuses, the drive can be connected to power supply the short
circuit current of which is max. 50kA
- Use cables with heat resistance of at least +70°C.
- The fuses function also as cable overload protection.
7
general data vacon • 24
- These instructions apply only to cases with one motor and one cable connection
from the frequency converter to the motor.
- To fulfil standard EN61800-5-1, the protective conductor should be at least 10mm2
Cu or 16mm Al. Another possibility is to use an additional protective conductor of
at least the same size as the original one.
Vacon 10 power ratings
7
25 • vacon general data
7
general data vacon • 26
Note: The input currents are calculated values with 100 kVA line transformer supply.