Professional Documents
Culture Documents
[2017] - EEEIC17
[2017] - EEEIC17
Abstract—This paper investigates the problem of inertia es- works [5], [6] instead, proposed Extended Kalman Filters with
timation of power system equivalent areas by a PMU-based recurrent estimation, that depend on model calibration and
approach. Assuming measurements available on the borders of interpolation, but presented robust results independent on the
the area, a reduced model is built based on the data acquired
during a perturbation. An iterative method is proposed to perturbations tested. Although the cited methods work well,
calculate the parameters of an equivalent generator, and in a known limitation is the need of monitoring individually
particular its inertia. The dynamic behavior of the equivalents all the generators connected on the grid, which makes these
are compared with the behavior of the Center of Inertia (COI) of approaches unfeasible in real power systems nowadays.
each area, and the equivalent inertia is estimated using a Least
Squares approach. Results obtained for a 11-bus, 4 generators Reference [1] introduced an Interarea Model Estimation
test-system are presented and discussed. (IME) method to build dynamical equivalents based on mea-
Index Terms—Inertia estimation, dynamic equivalent, model surements of interarea oscillations, acquired from PMUs at
reduction, phasor measurement units. the boundaries. The areas are determined following coherency
criteria, and the parameters can be estimated solving equations
I. I NTRODUCTION
of bus voltage and bus frequency oscillations as function of
The behavior of the system during the transient period their location in the transmission path.
shortly after the occurrence of a perturbation in the grid is
However, one may be interested on the dynamical behavior
governed by the inertia of each machine in operation: it is the
of an area monitored by a PMU independent of the coherency
so-called inertial response. The increasing penetration of RES-
of the internal machines, especially for frequency stability
based intermittent fonts mainly connected to the power system
issues. This paper proposes an approach to determine dynam-
by means of converters, and the consequent disconnection
ical equivalents considering the measurements of the transient
of traditional synchronous generation, are more and more
period following a perturbation. Not dealing with oscillations,
reducing the overall power system inertia, thus increasing
the coherency and modal decomposition are not considered
the probability of large frequency transients following large
to build the equivalents. An IME technique similar to [1] is
perturbations. For that reason, estimating inertia in real-time
proposed, with the goal of determining the equivalent inertia
is becoming more and more important for the overall security
of the considered areas, taking into account also resistances of
assessment function.
transmission lines (neglected in other studies) by means of a
Recently, the installation of Phasor Measurement Units
novel iterative strategy; the proposed method requires at least
(PMUs) has brought the possibility of acquiring measurements
three measurement points, that could also be reduced to two,
in real-time in a precise and synchronized way in various
and it is based on the determination of equivalent reactances
points of the grid. Many studies concerning on-line inertia
first and on the estimation of inertias subsequently, by means
estimation were developed in the past few years, normally
of a combination of Least Squares Estimation and iterative
divided in small-perturbation [1], [2], large-perturbation [3]–
procedures.
[6] and steady-state [7], [8] approaches. The former approach
is based on analysis of oscillations, but some techniques can Numerical results obtained with a two-area 11-bus test
be applied for large-perturbation analysis too. The second system are presented to illustrate the proposed methodology.
approach is based on detection of perturbations on the system, The occurrence of a perturbation inside each one of the areas
and is the field of interest of this paper. The latter is based on is studied in two different cases, and the dynamic behavior of
probabilistic analysis of historical data. the equivalent built is compared to the dynamic behavior of
The post-detection methods are mainly based on solving the center of inertia of each area.
the swing equation to estimate the inertia of the machine. The remaining of this paper is organized as follows: Section
The works [3], [4] propose to restate the swing equation in 2 presents the methodology to build the dynamic equivalents
terms of only variables measured by PMUs, solving it for and estimate the inertia of the area from the measurements
selected data according to the moment of detection of the acquired. Section 3 presents numerical results and analysis of
perturbation. The approaches are simple enough to be easily the method performance. Main conclusions are presented in
implemented and present robustness to false detections. The Section 4.
Vn2II ΨA2 ΨB2 sin (µA2 − µB2 − δ1I − δ2I ) Area 1 is defined by the boundary bus 5, and contain only
= (22)
Vn1II ΨA1 ΨB1 sin (µA1 − µB1 − δ1I − δ2I ) one generating machine. Area 2 is defined by the boundary
bus 6, composed by three non-coherent generating units.
where the underline denotes vector and the subscript II Supposing PMUs installed in those boundary buses, the data
denotes the present step, considering RT L 6= 0. acquired from the simulator are highlighted in Figure 3, that is
Calling αII the right hand side of equation (21), and βII the a snipping of Figure 2. The voltage at bus 5 is represented as
right hand side of equation (22), both underdetermined sytems V5 ∠θ5 and the current injection exiting Area 1 is I56 ∠φ56 .
can be solved using least squares method to obtain X1II and Similar for the other area, V6 ∠θ6 is the voltage at bus 6
X2II , similar to what was done in Step 6. and and I65 ∠φ65 is the current injection exiting Area 2. The
At this point, again, the updated internal voltages EiII (t) sampling time used in the simulations was 20ms.
can be computed by Ohm’s law, using the newly estimated Case 1 is based on a simulated step increase of 20%
X1II and X2II . in the load of bus 9 (see Figure 2). In this case, Area 1
Step 9: Test if XjI − XjII is lower than a tolerance oscillates against Area 2. However, G2 oscillates against G3
(10−3 p.u. used), where j = 1, 2 denotes the Area of the and G4 locally in Area 2. The idea is to estimate the inertia
calculated equivalent reactance. If not, set XjI = XjII and of Area 1 (that is equal to the inertia of G1) and Area 2
go back to Step 7. If yes, the iterative process of reactance (that is an equivalent including G2, G3 and G4). For the
estimation converged. Proceed to Step 10. data considered, the process converged in 8 iterations, and
Step 10: In this step, the area equivalent inertia is estimated. the internal reactances estimated were X1 = 0.034p.u. and
HAj d2 δi (t) X2 = 0.185p.u. With X1 and X2 , the internal voltages
= ∆PAj (t), p.u. (23) E1 (t)∠δ1 (t) and E2 (t)∠δ2 (t) are calculated.
πf 0 dt2
LS_IME_cr2
1.0005
f1
1 f COI
1
0.9995
Frequency (p.u.)
0.999
0.9985
0.998
0.9975
0.999
reference machine. After calculating fj (t) with equation (24),
a median filter is applied to reduce the peaks caused by the 0.9985
finite difference method.
The electrical frequency of each equivalent machine is 0.998
0.9985
a step increase of 20% in the active power consumption is
simulated in this area, instead of the previous perturbation. For
0.998 this case, the reactances estimated were X1 = 223.0201p.u.
0.9975 and X2 = 0.1249p.u. The increase of load in Area 1 was
f2
f
reflected direclty on the estimated X1 , much higher than in
0.997 G2
f G3 Case 1, while the estimations of X2 were not so different
0.9965 f G4 in between each other. This happens because the presence
of three generating units in Area 2 partially compensates the
0.996
17 18 19 20 21 22 23 24 25 26 27 perturbation locally, such that the load increase has not a big
Time(s) impact seen from the equivalent point of view. In Area 1,
instead, the impact of a local load increase is much bigger
Fig. 6. Frequencies - Area 2
because the area is limited to only one generating unit. The
estimated reactance not only represents the real impedances of
TABLE I the area but also has the effect of imposing to the estimated
I NERTIA ESTIMATIONS FOR C ASE 1 internal voltage the impact of the perturbation viewed from
Area 1 Area 2 the interconnection path.
Hest (s) 6.2504 -0.7719 Table II present the inertia estimations obtained for the
HCOI (s) 6.5000 18.8500 named Case 2.
TABLE II
I NERTIA ESTIMATIONS FOR C ASE 2
the inertia of G1). However, the method failed to estimate
the inertia for Area 2. This happens because the assumption Area 1 Area 2
for the mechanical power assumed in Step 8 of the method Hest (s) -22.2999 18.7216
HCOI (s) 6.5000 18.8500
doesn’t hold for this area, due to the fact that the perturbation
is located inside. The perturbation alters the moving power
such that it oscillates together with the loads of the area, as The first line of the table shows that the method was
shown in Figure 7. The legend P eA2 stands for the active accurate to estimate the equivalent inertia of Area 2, but
power exiting Area 2 and P mA2 represents the moving power struggled again when trying to estimate the inertia of the area
related to the area. that contains the perturbation (for the same reasons presented
in Case 1). When the moving power of Area 1 is considered
as known, the estimations improve to Hest = 7.179, such that
-0.75
Pe
a next step for the research is to estimate the moving power
A2
[9] J. H. Chow. Power System Coherency and Model Reduction. New York:
25
Springer, 2013.
20 [10] Y. Wehbe, L. Fan and Z. Miao. Least Squares Based Estimation of Syn-
chronous Generator States and Parameters with Phasor Measurement
15 Units. IEEE, 2012.
[11] P. Kundur. Power System Stability and Control. McGraw-Hill.,
10
[12] IEEE. Guide for Synchronous Generator Modelling Practices and Ap-
5 plications in Power System Stability Analyses. Tech. Rep. 1110-2002,
IEEE, 2002.
0 [13] H. Golpı̂ra and A. Messina. A Center-of-Gravity-based Approach to
19.5 20 20.5 21 Estimate Slow Power and Frequency Variations. IEEE Transactions on
Time (s) Power Systems, 2018.
[14] F. Milano and A. Ortega. Frequency Divider. IEEE Transactions on
Fig. 8. Inertias estimated - Case 2 Power Systems, 2017.
IV. C ONCLUSIONS
A PMU-based method for building dynamic equivalents and
estimating the equivalent inertia following a perturbation was
presented. The method is based on the approach proposed in
[9] for study of oscillations, and adapted in a novel iterative
approach to consider losses without increasing the number of
measurement points needed.
The method was tested with data produced by a 11-bus test
system simulated in PowerFactory, considering detailed model
2.2 (IEEE standard) for the generators and considering the
presence of frequency control. Results for two test cases were
presented, variating the location of the perturbation considered.
The results were accurate and practical when estimating the
inertia of the areas that doesn’t include the perturbation inside.
For the area that contains a perturbation, the method works but
requires the knowledge of the equivalent moving power of the
area in time, which estimation is a possible topic of interest
for a future work.
V. ACKNOWLEDGMENTS
The authors gratefully acknowledge the financial and tech-
nical support from the Italian TSO, Terna.
R EFERENCES
[1] J. H. Chow, A. Chakrabortty, L. Vanfretti, and M. Arcak. Estimation of
power system inertia constant and capacity of spinning-reserve support
generators using measured frequency transients. IEEE Transactions on
Power Systems, 2008.
[2] L. Fan, Z. Miao and Wehbe Y. Application of Dynamic State and Pa-
rameter Estimation Techniques on Real-World Data. IEEE Transactions
on Smart Grid, 2013.
[3] P. Wall and V. Terzija. Simultaneous Estimation of the Time of Distur-
bance and Inertia in Power Systems. IEEE, 2014.
[4] P. M. Ashton, G. A. Taylor, A. M. Carter, M. E. Bradley, and W. Hung.
Application of phasor measurement units to estimate power system
inertial frequency response. IEEE Power and Energy Soc. General
Meeting, 2013.
[5] H. Zhenyu, D. Pengwei, D. N. Kosterev, and Y. Bo. Application
of extended kalman filter techniques for dynamic model parameter
calibration. IEEE Power and Energy Soc. General Meeting (PES), 2009.