Professional Documents
Culture Documents
Codes and Standards
Codes and Standards
Codes and Standards
FA LL ED I TI ON
Contents
2
Electrical grounding and bonding
per NEC Back to TOC
E lectrical grounding and bonding is one of the many misunderstood topics of dis-
cussion in the design and construction industry. There are two main reasons for
understanding grounding and applying the correct design for grounding and bonding:
safety and correct operation of sensitive electronic equipment.
NFPA 70: National Electrical Code Article 250 covers the minimum requirements for
grounding and bonding and, although the NEC lists requirements to abide by, it
should not be taken as a design manual. Some terms and requirements discussed
may be true for the European standards, however, the intent of this article is to clarify
grounding and bonding design seen in the United States.
Grounding and bonding practices are important and required per NEC because when
done properly, it will protect personnel from electrical shock hazards and ensure elec-
3
Electrical grounding and bonding per NEC
Back to TOC
current path) from the fault location back to supply source to facilitate the opera- Back to TOC
tion of overcurrent devices.
The requirements for grounding and bonding begin at the service. The NEC requires
the grounded conductor(s) to be routed with the ungrounded conductors to the ser-
vice entrance equipment and it shall connect to the grounded conductor(s) terminal or
bus. The grounded service conductor is required to be connected to a grounding elec-
trode conductor at each service. The main bonding jumper shall connect the grounded
conductor to equipment-grounding conductors and the service entrance enclosure via
the grounded conductor’s terminal or bus.
The GEC shall be used to connect the EGCs, the service equipment enclosures and
where the system is grounded, the grounded service conductor to the grounding elec-
trodes. Figure 1 details the grounding system connections.
The minimum sizes of the grounded conductor, EGC and GEC are determined based
on NEC Table 250.102(C)(1), Table 250.122 and Table 250.66, respectively. The sizes for
the main bonding jumpers, supply side bonding jumpers and system bonding jumpers
can also be sized from Table 250.102(C)(1).
5
Electrical grounding and bonding per NEC
Back to TOC
Although the grounded conductor is connected on the Figure 2: Ground rod spacing is shown in
this illustration. Courtesy: CDM Smith
supply side, it shall not be connected to the EGCs or
reconnected to ground on the load side of the service
disconnection means except as otherwise permitted in the 2017 NEC Article 250.142(B).
Common errors
There are a few errors commonly seen in design or during construction due to a lack of
understanding or misconception concerning grounding, bonding and the NEC Article
250. A few commonly seen errors are: 6
Electrical grounding and bonding per NEC
ERROR 1: Using the wrong tables for EGC, grounded conduc- Back to TOC
tor or GEC.
The sizing methods detailed in the NEC are the minimum requirements and it may not
be adequate for the scope and size of the project. Large available short-circuit currents
may require larger conductor sizes than the minimum NEC requirements.
The EGC should be sized per Table 250.122. A full-sized EGC is required to prevent
overloading and possible burnout of the conductor if a ground fault occurs along one
of the parallel branches. The EGC is sized in accordance with Table 250.122 based on
the rating of the overcurrent protective device upstream that protects the conductors
routed with the EGC.
However, the sizes for EGC in Table 250.122 does not account for voltage drop. There-
fore, ungrounded conductors shall be sized while taking into account the voltage drop
and per 250.122(B), the EGC shall be increased in size proportionately to the upsized
ungrounded conductors. For example, given a 480-volt branch feeder circuit breaker
rated 150 amperes, the EGC shall be sized 6 AWG copper or 4 AWG aluminum for a
voltage drop of at most 3%.
The grounded conductor at the service should be sized in accordance with Table
250.102(C)(1), based on the size of largest ungrounded conductor or equivalent area
for parallel conductors. This table can also be used to size the main bonding jumper,
system bonding jumper and supply-side bonding jumper for AC systems. As stated in
the notes of Table 250.102(C)(1), for ungrounded conductors larger than 1,100 kcmil
copper or 1,750 kcmil aluminum, the conductor shall have an area not less than 12.5%
of the area of the largest ungrounded supply conductor or equivalent area for paral-
7
Electrical grounding and bonding per NEC
lel supply conductors. If the ungrounded conductors are installed in parallel in two or Back to TOC
more sets, the grounded conductor shall also be installed in parallel.
For parallel sets, the equivalent size of the largest ungrounded supply conductor(s)
shall be determined by the largest sum of the areas of the corresponding conductors
of each set. For example, given that the electrical service is supplied by five sets of 500
kcmil copper conductors, the grounded conductor required in each set shall be 350
kcmil copper. The total equivalent area of the parallel supply conductors in each set is
2,500 kcmil (five times 500 kcmil given five parallel ungrounded conductors). Because
the equivalent area is above 1,100 kcmil for copper, the grounded conductor(s) shall
have an area not less than 12.5%. This is an area of roughly 312.5 kcmil, which accord-
ing to Table 8 of Chapter 9 in the 2017 NEC, is 350 kcmil copper.
The GEC should be sized per Table 250.66. The notes at the bottom of Table 250.66
needs to be considered if there are multiple service entrance conductors or no service
entrance conductors. Given the number of service entrance conductors, the size is
determined either by the largest ungrounded service-entrance conductor or the equiv-
alent area for parallel conductors. The size of the GEC is also dependent on the ma-
terial of the conductor and its connection to specified electrodes in Article 250.66(A)
through (C). The allowed materials are copper, aluminum, copper-clad aluminum and
items allowable in Article 250.68(C).
For example, given that the electrical service is supplied by one set of 500 kcmil cop-
per conductors, the GEC per Table 250.66 shall be 1/0 AWG copper. The location for
GEC installation is at the service, at each building or structure where supplied by a
feeder(s) or branch circuit(s) or at a separately derived system.
8
Electrical grounding and bonding per NEC
To reiterate, the GEC is the connection of the system grounded conductor or the Back to TOC
equipment to a grounding electrode or to a point on the grounding electrode system.
This leads on to error No. 2, errors in the grounding electrode system, which is com-
monly seen in design and construction.
These are the commonly seen issues in grounding electrode system that follows the
NEC, but does not satisfy project scope:
• Not installing a third grounding electrode. The NEC requires a minimum of two
grounding electrodes, unless one electrode has a resistance to earth less than 25
ohms. However, commonly in construction, the ground resistance is not measured
again after a supplemental grounding electrode is installed. Therefore, the ground
resistance of 25 ohms is not confirmed as having been met. Per the NEC, two
electrodes would meet code, but this doesn’t guarantee a low electrode-to-earth
resistance. Including a grounding ring with multiple grounding electrodes is con-
sidered a best practice to ensure low resistance. Also, specifications should also
9
Electrical grounding and bonding per NEC
require ground resistance measurements to be taken after grounding electrode Back to TOC
system is installed to determine if additional electrodes are required.
• The NEC only requires 25 ohms ground resistance; however, the industry
recognizes a lower resistance value may be more desirable. International
Electrical Testing Association ATS-201313 recommends 5 ohms or less
for large industrial systems.
• Installing grounding electrodes (in particular, rods) 6 feet apart because that is the
minimum separation required by code.
• Each ground rod has its own zone of influence as shown in Figure 2. The
optimal spacing between rods should be twice the length of the ground
rod. When the zones overlap, the net resistance of each rod increase,
thus making the ground system less effective.
There are many considerations that need to be taken into account when designing and
installing grounding electrode systems. These are:
• Size of service.
Back to TOC
While considering all of the above factors, some of the Figure 3: This compares a separately
derived system (right) to a nonseparately
best practices seen in the industry are using ground
derived system. Courtesy: CDM Smith
rings around buildings, ground triangles at smaller ser-
vices, exothermic welds for concealed or buried connections and ground rods and install-
ing ground testing/inspection wells that allow easy access for ground resistance testing.
Another issue that can arise out of multiple bonding locations is the risk the ground-
ed conductor being disconnected on the line side of the service. This could cause the 11
Electrical grounding and bonding per NEC
EGC and all conductive parts connected to it to become energized because the con- Back to TOC
ductive path back to the source that would normally allow the overcurrent device to
trip is not connected. In this case, the potential to ground of any exposed metal parts
can be raised to line voltage, which can result in arcing and severe shock hazard.
Grounded conductor: A
system or circuit conductor
that is intentionally ground-
ed (I.e., neutral conductor).
Grounding electrode: A
conducting object through
Figure 5: This is a delta-wye
which a direct connection to earth is established. Common
transformer with the high side
grounding electrodes include rods, plates, pipes, ground coming in from the bottom
rings, metal in-ground support structures and concrete-en- and the secondary coming out
from the top. As shown, the
cased electrodes. All grounding electrodes at each building
grounded conductor (neutral)
or structure shall be bonded together to form the grounding is grounded at the transformer.
electrode system. Courtesy: CDM Smith
Ground-fault current path: An electrically conductive path from the point of a ground fault
on a wiring system through normally noncurrent-carrying conductors, equipment or the
earth to the electrical supply source. Examples of ground-fault current paths are any combi-
nation of equipment grounding conductors, metallic raceways and electrical equipment. 15
Electrical grounding and bonding per NEC
Neutral conductor: The conductor connected to the neutral point of a system that is
intended to carry current under normal conditions.
Service: The conductors and equipment for delivering electric energy from the serving
utility to the wiring system of the premises served.
Back to TOC
2023 National Electrical Code Changes:
New energy Landscape and Sustainability |
Schneider Electric
Big changes were made around the energy management space in
the 2023 National Electrical Code. Learn more about how the code
is evolving along with technologies in the new energy landscape
— like backup power systems, microgrids, and more — and why
specifiers need to be aware of these changes from experts at
Schneider Electric and Gresham Smith.
17
Back to basics: Medical gas
storage under NFPA 99 Back to TOC
This covers the basics of medical gas storage and the requirements for health
care spaces detailed in NFPA 99
A t times, health care facilities use spaces to store medical gases — medical oxy-
gen, nitrogen, nitrous oxide and others — that are noncompliant based on the
requirements in the 2021 edition of NFPA 99: Health Care Facilities Code. This code
specifies many health care facility requirements including operational, mechanical,
electrical and architectural for the storage of such medical gases.
Misses on the code typically occur when closets, storage rooms and other spaces are repur-
posed for the storage of these gases. As a result, challenges for facility managers include:
The purpose of this article is to provide health care facility professionals with instruc-
tional guidance to help them reach NFPA 99 compliance associated with the storage of
medical gases. Readers are advised to consult the NFPA 99 text itself, and this article
will help with the initial understanding of the requirements.
18
Back to basics: Medical gas storage under NFPA 99
• Cylinder: A supply tank for high-pressure gases with pressures that may exceed
13.8 kilopascals (kPa) or 2,000 pounds per square inch (psi) gauge.
• Medical gas: See medical support gas or patient medical gas below.
• Medical support gas: Nitrogen or instrument air used for any medical support
purpose (e.g., to remove excess moisture from instruments, to operate medi-
cal-surgical tools). This gas may be used in laboratories and is not respired as part
of any treatment. It falls under the general requirements for medical gases.
• Manifold: A device for connecting the outlets of one or more gas cylinders to the
central piping system for that specific gas.
• Nonflammable: Not readily capable of burning with a flame and not liable to ig-
nite and burn when exposed to flame.
• Patient medical gas: Piped gases — such as oxygen, nitrous oxide, helium, car- Back to TOC
bon dioxide and medical air — that are used in the application of or calibration of
medical devices for human respiration.
In addition to supplying health care practitioners with essential resources, gas storage
rooms allow for safety in the storage and fulfillment of these gases. Although not cov-
ered in this article, medical gas storage compliance also requires an in-depth hazard
analysis which is outlined in NFPA 55: Compressed Gases and Cryogenic Fluids Codes,
2020 edition. These analyses take such subjects as flammability, toxicity and explosivity
of the gases into account.
• Reference Table 6.2.1 in NFPA 55 for the design and number of control areas per floor.
• Reference Table 6.3.1.1 in NFPA 55 for a list of all gases and the maximum allow-
able quantity (MAQ) of all varieties of gases within different sizes and types of
control areas.
There are several types of gas storage rooms and each has specific characteristics as
well as design and operational requirements depending on the type of gases being
20
Back to basics: Medical gas storage under NFPA 99
stored. First, gas storage rooms are characterized as either indoor rooms — a room Back to TOC
within the interior of the health care facility itself — or outdoor areas — an outdoor
enclosure that meets gas storage requirements.
Secondly, gas storage rooms are either with a central supply — a system for piping med-
ical gases to different functional areas within the health care facility — or without a cen-
tral supply, in which gases are stored independently and retrieved for use in other areas.
Requirements for all types of storage: All storage rooms (except for rooms with storage
only of less than 300 cubic feet of nonflammable gases at standard temperature and pres-
sure, known as STP) — whether they feature central supply systems or not — have shared
requirements in terms of signage, temperature
limits, accessibility, finishes and restraints.
Medical Gases
Proximity: In terms of proximity, full containers and cylinders must be segregated from Back to TOC
all others (empty cylinders, etc.) — a commonly missed requirement, especially consid-
ering the constant activity of medical practice.
High-temperature limit: All areas with cylinders, whether they have central supply or
not, must not exceed 125°F.
Finishes and racks: The finishes of the interior spaces or the exterior enclosures must
be made of noncombustible materials (interiors can be limited-combustible materials),
as well as any racks/shelves/supports for cylinders must be made of noncombustible
materials (or limited-combustible materials).
Other: In general, these areas should have access to move cylinders with hand trucks,
have lockable doors or gates and have proper restraints to prevent the cylinders from
falling (whether full or empty). Other requirements are exclusion of: any fuel-fired
equipment, heating elements greater than 266oF, flammable gas, flammable liquid or
flammable vapors.
Best practice: It is best to use oxygen sensors and alarms in gas storage rooms to
detect any harmful leaks and maintain 3 feet of clearance within each storage room
around cylinders/containers and walkways for easy movement of cylinders. Neither of
these suggestions is explicitly outlined in the language of NFPA 99.
located either within a single room in the health care facility (interior) or in an outdoor Back to TOC
enclosure (exterior).
• Interior: Interior central supply systems locations are permitted to store manifolds
for gas cylinders, manifolds for cryogenic liquid containers, in-building emergency
reserves, instrument air standby headers, individual components on the oxygen
side of the concentrator sources. Design and construction of interior central sup-
ply rooms, excluding cryogenic fluid center supply systems, have specific require-
ments outlined in NFPA 99. To highlight one of the indoor requirements specifically,
rooms containing oxygen, nitrous oxide or other oxidizers shall be separated from
the rest of the building by walls or floors with one-hour fire ratings and with doors
and other openings with a ¾-hour rating. These rooms also require emergency
power and specific ventilation
which includes low-wall in-
takes (see Figure 2).
Back to TOC
• Interior: Interior storage rooms have unique requirements based on the volume of
gases stored within those rooms. Specifically, storage spaces with fewer than 300
cubic feet of nonflammable gases
(at STP), 300 to 3,000 cubic feet of
nonflammable gases (at STP) or
greater than 3,000 cubic feet of
nonflammable gases (at STP) will
differ in requirements for the ven-
tilation, electrical and architectural
features. Rooms with greater than
3,000 cubic feet of nonflamma-
ble gases (at STP) require walls or
floors with one-hour fire ratings
and with doors and other open-
ings with a ¾-hour rating. Rooms
with greater than 300 cubic feet
of nonflammable gases (at STP)
Figure 4: Interior storage only for
require specific ventilation which includes low-wall medical air. Courtesy: Dewberry
intakes (see Figure 4).
• Exterior: Exterior storage locations without central supply have less stringent
requirements. One item to note is specific requirements for location as it relates
to building exits, wall openings, intakes, property lines and combustibles (see
Figure 5).
25
Back to basics: Medical gas storage under NFPA 99
Back to TOC
pletely understood or health care staff may place Figure 6: NFPA 99 medical gas
storage room design and construction
medical gas cylinders in a room not specifically requirements matrix. Courtesy:
designed for that use. In doing so, facilities may in-
advertently be out of compliance and at risk for penalties, citations and even human
injury or death.
Rooms are misapplied or not understood: The NFPA 99 requirements for medical Back to TOC
gas storage are different depending on the type of room involved. Additionally, non-
compliant storage rooms are often used for the storage of medical gases without tak-
ing compliance into consideration. It’s important to fully understand the type of room
in consideration and be familiar with the NFPA 99 requirements for that room type
based on the descriptions above.
The quantity of gas or number of containers exceeds the limits of the rooms:
NFPA 99 has specific requirements regarding the amount of gas that can be stored in a
room, with respect to less than 300 cubic feet of nonflammable gases at STP, between
300 cubic feet and 3,000 cubic feet of nonflammable gasses at STP and greater than
3,000 cubic feet of nonflammable gasses. It is critical not to exceed these thresholds.
Often, it is missed that a room is designed for a certain threshold and is exceeding that
threshold with the total cubic feet of stored gases in the room (not counting empty
cylinder’s volume). 28
Back to basics: Medical gas storage under NFPA 99
Manifolds or cryogenics are located too close to equipment in violation of re- Back to TOC
quirements: Manifolds and cryogenics have unique requirements in terms of their
proximity to other containers. If located outdoors, they must be installed in an enclo-
sure used only for the enclosure of those containers and they must comply with min-
imum distance requirements. If located indoors, they must be installed within a room
used only for those types of containers.
Design or construction does not include appropriate fire-rated walls and doors:
As noted above, NFPA 99 requires that storage rooms with central supply of oxidizers
and storage rooms without central supply and greater than 3,000 cubic feet of non-
flammable gases at STP must be separated from the rest of the building by walls and
floors having a one-hour fire resistance rating. They must also feature doors and other
opening protectives having a ¾-hour fire protection rating. This is often missed when
medical gases are placed in a room without proper design.
Outdoor storage is too close to building exits or air intakes: NFPA 99 requires that
outdoor storage areas for medical gases must be located at a specific distance from
building exits and air intakes. This is to prevent the spread of gas should a leak occur.
Medical gases are not stored behind locked doors: NFPA 99 requires that storage
areas for medical gases must be locked when not in use. This is to prevent unautho-
rized access to the gases.
Incompatible central supply systems stored together: As mention in a previous sec- Back to TOC
tion, NFPA 99 outlines central supply systems that can and cannot be stored together.
This precaution prevents hazardous mistakes and potential risks if gases were to mix
with machinery-based equipment, etc.
For example, NFPA 55 has additional limitations on hazardous materials per control
area. It includes limitations on the number of control areas per floor that should be ob-
served in accordance with NFPA 99 requirements. Similarly, the local fire codes should
be referenced when looking for additional limitations on storage quantities. Typically,
the local fire codes expand upon the limitations outlined within NFPA 99 and NFPA 55.
Additionally, facility professionals should understand the code edition(s) currently en-
forced for their facility and study each edition. This article is written based on the 2021
edition of NFPA 99, which may have different requirements than what is enforced at a
particular facility.
30
Back to basics: Medical gas storage under NFPA 99
Additionally, if a storage room was constructed under a different code edition and was Back to TOC
compliant at the time of construction, it is allowed to remain as it was originally con-
structed as long as the local authority having jurisdiction has determined the system
is not a hazard to life. This can be found specifically in Chapter 1, Administration, of
NFPA 99. Therefore, it is be important to study the edition that was enforced at the
time of construction as well.
31
The NFPA 70B
® Is your electrical system still in compliance?
Introduction
standard just got This eGuide outlines the changes in the National Fire Pro-
tection Association (NFPA®) 70B: Standard for Electrical
NFPA 70B
NFPA 70B background
NFPA 70B was first published in 1975 to outline recommended electrical maintenance
practices and serve as a guideline for establishing and implementing an effective, safe,
and reliable maintenance program.
33
The NFPA® 70B standard just got overhauled
Back to TOC
NFPA 70E, the “Standard NFPA 70, the National Electrical
1 for Electrical Safety in 2 Code ® (NEC), requires the safe
the Workplace,” provides installation of electrical wiring
requirements for protecting and equipment. The NEC®
workers from electrical hazards ensures electrical systems and
in the workplace. Primarily equipment are installed safely and
intended for those exposed reliably. It covers a wide range
to electrical hazards, it also of topics related to electrical
requires an electrical safety safety, including wiring methods,
program that must consider the grounding, and overcurrent
condition of maintenance. protection.
34
The NFPA® 70B standard just got overhauled
This shift from recommendation to standard came about with dedicated cooperation
across all industries and support from member organizations and technical committee
members.
This is a major, transformational change from the previous version with far-reaching im-
pacts related to maintenance, regardless of facility type.
Standard Code
35
The NFPA® 70B standard just got overhauled
Renewed focus on
2 maintenance
Creation and documentation
1 of an electrical maintenance Reduce operating costs by:
plan
• Minimizing repair and
• Survey and analysis of electrical replacement costs
equipment to determine
maintenance priorities • Optimizing energy efficiency
and extending equipment
• Developed and documented lifespan
maintenance procedures for
equipment • Reducing downtime
Back to TOC
Improved safety
4
• The standard requires power
systems studies and system
one lines to be kept up-to-
date to ensure worker safety Training
in performing maintenance. 6
This also helps improve the • Facilities can expect to invest
safety of electrical systems by more in the education and
providing clear requirements training of their maintenance
for maintenance and ensuring personnel.
organizations create a well-
planned electrical maintenance
program, transition to digital
electric infrastructure, and
Support services
follow best practices. 7
• Companies providing
preventive and condition-based
maintenance services can
Shared benchmarks and ensure electrical infrastructure
5 results is optimized and can easily
adapt to changing standards to
• The new 2023 standards regulations.
also help formalize electrical
maintenance practices across
different organizations
and industries, making
benchmarking and comparing
performance and results easier.
37
The NFPA® 70B standard just got overhauled
Safety Compliance
• The main purpose of NFPA • NFPA 70B is now a national
70B is to promote safety by consensus standard for
identifying and addressing electrical equipment
potential electrical hazards maintenance. Many local,
before they cause harm. By state, and federal regulations
following the recommended reference NFPA 70B compliance
practices in NFPA 70B, to help organizations avoid
organizations can help prevent penalties and legal liabilities.
electrical accidents and injuries.
2023 NFPA 70B – Electrical equipment maintenance drives services and new Back to TOC
provisions for EcoStruxure™ and Advisor platforms regulatory provision
• OSHA® regulations are federal and state laws for electrical worker safety
• NFPA 70E must contain elements that consider the condition of maintenance
39
The NFPA® 70B standard just got overhauled
Maintenance
procedures:
Safety: the standard
standards for
prioritizes safety and
conducting
provides guidance on
regular
identifying and mitigating
maintenance,
electrical hazards.
such as visual
inspections,
cleaning,
lubrication, and
Training: the importance testing.
of training personnel
responsible for
maintenance tasks and
emphasizing the need for
ongoing education and
Maintenance documentation:
certification.
standards requiring detailed records
of all maintenance activities, including
test results, repairs, and replacements
to ensure compliance and facilitate
continuous improvement.
40
The NFPA® 70B standard just got overhauled
A reduced skilled workforce and a lack of resources also challenge today’s facilities. They
also may not have digitized their power network and don’t have digital communicating
devices placed at key areas or on critical loads within their electrical infrastructure.
The answer lies in the digital transformation of your power network that fully enables
condition-based maintenance.
41
The NFPA® 70B standard just got overhauled
Improved
Predictive communication
analytics uses the between
data collected maintenance teams
to identify potential failure modes allows for better collaboration
and predict when components will and coordination. This can help
likely fail. Use this information to to ensure that maintenance
schedule maintenance activities in activities are scheduled efficiently
advance, reducing downtime and and that the right resources are
avoiding unexpected failures. available to complete the work.
Learn more 43
The NFPA® 70B standard just got overhauled
Back to TOC
Complying with regulations Extend the lifespan of the
5 and standards related 6 equipment by predicting
to energy efficiency and incidents, avoiding those
sustainability, including building equipment-damaging breakdowns,
codes, energy standards, and and extending the working life of
emission regulations. valuable electrical assets.
45
The NFPA® 70B standard just got overhauled
46
The NFPA® 70B standard just got overhauled
Back to TOC
Establish procedures
5 Develop procedures for
conducting each maintenance
task, including safety protocols,
required tools and materials, and
documentation requirements.
Assign responsibility
6 Determine who will be
responsible for each maintenance
task. This may include internal
staff or an external service
provider.
47
The NFPA® 70B standard just got overhauled
Results
Over 100 variables get measured
and computed through
EcoStruxure Asset Advisor to
provide accurate and reliable
condition monitoring for its new
Beaumont plant.
Results
EcoStruxure Asset Advisor allows
visibility into power systems and
is remotely managed around the
clock, delivering productivity,
efficiency, and maintenance
benefits.
“EcoStruxure Asset Advisor has allowed us
to identify hot spots and attack them be- Improved reliability of the
fore they become a problem – saving us facility’s electrical equipment
helps produce approximately one
costly downtime, greatly enhancing our
million jars daily.
ability to respond quickly to changes in
demand and ultimately better serve our Schneider Electric’s Connected
customers and reduce our operational car- Services Hub allowed engineers
bon footprint.” to react and avoid three
unplanned stoppages that could
have cost Nestlé up to $52,000
— Luis Gilberto López Páez,
per hour.
electricity specialist in Nestlé Toluca Cafés
49
The NFPA® 70B standard just got overhauled
Results
EcoStruxure services connect to
and monitor the University’s most
critical electrical distribution assets
via the cloud. Service experts analyze
performance data and provide
actionable insights to help facility
management deploy resources
efficiently and help avoid equipment
failure.
“In two incidents alone, we have saved sev- Optimized the energy infrastructure
eral hundred thousand dollars.” for predictive, condition-based
maintenance.
— Mark Schwartz,
Saved nearly $1 million through the
Director of Facility Operations, early discovery of equipment problems
URMC – a 20 to 1 return on investment (ROI).
Schneider Electric Services can help unlock these business advantages and support
critical business outcomes, including:
Sustainability and
circularity
N FPA 101: Life Safety Code has long stood as one of the most widely used resourc-
es for protecting people and mitigating the impact of fire and related hazards.
The code is updated every three years, so it is important to understand the 2024 edi-
tion of NFPA 101 as jurisdictions begin to work the code into their regulations. Ahead
of implementation, it’s critical that engineers are aware of changes and additions con-
tained in the new edition.
A sleep pod is also an occupiable, prefabricated structure that might include integral
electrical wiring, ventilation and furnishings. However, it is specifically designed and
used for sleeping purposes. When installing sleep pods, it is important to consider
52
A guide to upcoming changes in the 2024 edition of NFPA 101
the amount of ABHR permitted and the second is the addition of spill containment and Back to TOC
maintenance requirements. The updates clarified that these provisions do not apply to
individual use containers that are 16.9 ounces or smaller in size.
It’s also important to note that the requirements for ABHR dispensers in health care
and ambulatory health care occupancies did not change. The changes mentioned here
only apply to occupancies, such as business, mercantile, educational and assembly
buildings that require compliances with the provisions in Chapter 8.
The amount of ABHR solution permitted to be in use in fully sprinklered buildings has
doubled. The previous limit was 10 gallons and is now up to 20 gallons that are permit-
ted. There was also an increase in the allowable size of individual dispensers:
• In corridors and areas open to corridors: increased from 0.32 gallons to 0.53 gallons.
NFPA 101-2024 also adds requirements for spill containment and maintenance. Spill
containment must be provided and kept clear of trash and ABHR solution. If any ABHR
is spilled when refilling the dispensers, the spill must be cleaned up and removed as
soon as refilling is complete.
code, they often were not a part of NFPA 101. Previous reasoning has been that NFPA Back to TOC
101 is primarily concerned with getting occupants out of the building, and therefore
does not expect occupants to delay egress to try to extinguish a fire. However, in the
2024 edition of NFPA 101, both new and existing assembly occupancies now require
portable fire extinguishers.
This change was based on findings from research studies, which identified that occu-
pants will try to extinguish a fire in its early stages to avoid embarrassment, inconve-
nience and damage to the premises or property. The research also found that concerns
for people, pets and possessions are strong drivers of behavior in the event of a fire.
Studies have shown that people will almost always attempt to extinguish a fire if it’s
small enough and they believe they can mitigate the hazard. If a fire extinguisher is not
available, people typically use makeshift means to try to extinguish the fire, which is far
less safe than using a portable extinguisher. Thus, it is important to give the public the
tools necessary to be successful.
A 2022 report from the Fire Protection Research Foundation, Carbon Monoxide Inci-
dents: A Review of the Data Landscape, led to some recommended changes in the
2024 edition of NFPA. Notably, the 2024 edition requires carbon monoxide detectors in
certain areas in existing educational and day care occupancies, as well as in new health
care, ambulatory and detention and correctional occupancies.
55
A guide to upcoming changes in the 2024 edition of NFPA 101
There are two major concerns with such devices: anchoring and fire safety. ASTM F2374
primarily addresses the anchoring issue, although a variety of other topics are also
covered. The requirements in NFPA 101 were added to address the issue of fire safety,
including the materials of construction, the materials associated with electrical wiring
and portable generators if they are to be provided. Key points are:
• Any electrical equipment associated with the device must comply with NFPA 70:
National Electrical Code (NEC).
• If a portable generator is to be provided, it must comply with and portable fire ex-
tinguishers must be in accordance with NFPA 10: Standard for Portable Fire Extin-
guishers must be provided.
56
A guide to upcoming changes in the 2024 edition of NFPA 101
Newly created Annex expands the definition of ACS and provides the user with recom-
mendations for how to establish and operate these facilities as temporary health care
facilities. The information found in Annex D supports new language in Chapters 18 and
19, which permit ACS, provided they have an approved fire emergency plan and com-
ply with approved alternate construction, design, protection, operational and occupan-
cy classification requirements.
• Operations and maintenance: Considerations include maintenance of life safety Back to TOC
systems, fire watch, building services, operating features and inspection, testing
and maintenance of fire protection systems.
The 2024 edition of NFPA 101 expands one of those conditions and allows up to 75%
of the required number of exit enclosures and capacity to be permitted to discharge
through the interior provided that:
• The interior exit discharge only occurs in a vestibule or foyer that is separated from
the remainder of the floor by one hour fire-resistance rated fire barriers (existing
installations of wired glass in steel frames is permitted in lieu of the fire barriers)
• The vestibule or foyer is not more than 10 feet from the exterior of the building
and not more than 30 feet in length
58
A guide to upcoming changes in the 2024 edition of NFPA 101
The 2024 edition of NFPA 101 requires that emergency action plans consider the secu-
rity features in place. This helps ensure both safety and security are considered when
developing plans for emergency response. New and existing educational and day care
occupancies added additional language, reiterating that both security and life safety
need to be considered and documented in the emergency action plan.
Val Ziavras
Val Ziavras, PE, is a senior engineer in the NFPA technical services.
59
NFPA 20: Fire pump design
Back to TOC
When designing a fire pump, there are a number of factors to keep in mind,
particularly NFPA 20
N FPA 20: Standard for the Installation of Stationary Pumps for Fire Protection pro-
tects life and property by providing requirements for the installation of fire pumps
to ensure that systems will work as intended to deliver adequate and reliable water
supplies in a fire emergency.
A fire sprinkler system is a critical component of life safety in a building. The Interna-
tional Building Code grants a number of exceptions when a building is “fully sprin-
klered,” such as reductions in rated separations, reductions in fire hydrant flow de-
mands, increased egress travel distances and increased building heights and areas.
These exceptions are permitted with an expectation that, in the event of a fire, the
sprinkler system will suppress the fire to a sufficient degree that occupants can safely
evacuate the building and the growth of the fire will be controlled until the fire depart-
ment arrives to fully extinguish it.
Often, the municipal water system has sufficient pressure to operate the sprinkler sys-
tem. A fire pump is required when the available water source does not have adequate
pressure. When a sprinkler system relies on a fire pump, the performance of the system
is dependent on the pressure created by the pump.
Because of the critical importance of the fire pump, careful consideration should be
employed when selecting and designing a fire pump.
A fire pump’s size is dictated by the most hydraulically demanding area of the fire pro- Back to TOC
tection system. In many high-rise buildings, this can be the automatic fire standpipe
system demand which requires 500 gallons per minute at 100 pounds per square inch
at the top of the most remote standpipe, plus 250 gpm for each additional standpipe,
up to a maximum of 1,000 gpm for wet systems or 1,250 gpm for dry systems.
For nonhigh-rise buildings, the most demanding area could be any number of differ-
ent hazards. Though the IBC requires buildings with a highest finished floor located
more than 30 feet above the lowest fire department vehicle access to be equipped
with Class III standpipes or Class I if the building is fully sprinklered, NFPA 14: Stan-
dard for the Installation of Standpipe and Hose Systems allows the standpipes to be
manual type with the necessary pressure provided by the fire department pumper truck
through the fire department connection (2013 NFPA 14, Section 5.4.1.1), thus elimi-
nating the standpipe demand from consideration. It is important to perform a hazard
analysis of the building before attempting to size the fire pump.
For example, a new sprinkler system might be installed in a five-story medical office
building with a partial basement (overall building height of 69 feet). The building con-
struction is noncombustible, Type II-B and each floor is approximately 18,000 square
feet. The basement level contains electrical rooms, general storage rooms, a small ox-
ygen storage room (250 square feet) enclosed by a two-hour fire rating and a covered
exterior loading dock.
Floors one through four are comprised of offices, exam rooms and outpatient proce-
dure rooms. The fifth floor is a large mechanical penthouse with a roof slope of 3:12.
The center core areas on levels zero through four contain elevator lobbies, public cor-
61
NFPA 20: Fire pump design
ridors and public restrooms. The building is equipped with a Class I wet manual stand- Back to TOC
pipe system.
The predominate hazard classification for the overall building is that of light hazard
occupancy, however, the building contains spaces that warrant higher hazard desig-
nations. While the oxygen storage room requires the highest density (0.30 gpm for
extra hazard occupancy), this space is not the most hydraulically demanding. The two-
hour rated enclosure provides an effective barrier to prevent fire spread outside of the
room. For this reason, the calculated area need only extend to the perimeter walls of
the room (NFPA 13-2013, Section 11.2.3.3).
The exterior loading dock requires the second highest density: 0.20 gpm for ordinary
hazard group 2. It also requires a 30% increase to the remote area size because the sys-
tem type must be dry due to exposure to freezing conditions (NFPA 13-2013, Section
11.2.3.2.5). The estimated flow demand for this area is approximately 507 gpm (0.20
gpm x 1,950 square feet = 390 gpm + 30% for sprinkler head overflow = 507 gpm). A
preliminary hydraulic calculation for this area indicates a required system pressure of
65 psi.
The most hydraulically demanding area in this example is the level five mechanical
room. Though the density for this remote area is only 0.15 gpm (ordinary hazard group
1), the top floor location requires additional pressure to overcome the head loss from
elevation. The remote area size is increased to 1,950 square feet due to a 30% increase
for slopes exceeding 2:12 (NFPA 13-2013, Section 11.2.3.2.4). The estimated flow de-
mand for this area is approximately 380 gpm (0.15 gpm x 1,950 square feet = 292.5
gpm + 30% for sprinkler head overflow = 380 gpm). A preliminary hydraulic calculation
62
NFPA 20: Fire pump design
Once a hazard analysis and preliminary hydraulic calculations have established the fire
flow and pressure required to meet the standpipe or sprinkler system demand, a re-
view of a recent water flow test can identify if a fire pump is necessary. The water flow
test used to size the fire pump is required to have been completed within the last 12
months (NFPA 20-2013, Section 4.6.1.2).
In the example scenario, the water flow test indicates pressures of 54 psi static, 48 psi
residual, flowing at 940 gpm. When the required outside hose demand is added to
the system flow demand (380 gpm + 250 hose = 630 gpm) and plotted on a graph, the
available city water pressure is approximately 49 psi when flowing at 630 gpm.
Typically, a minimum safety factor of 10 psi is required. To meet the demand, the fire
pump size should be at least 400 gpm rated at 51 psi (100 psi – 49 psi city pressure =
51 psi). Fire pumps are typically sized by pressure range, therefore a 400 gpm pump
with a revolutions per minute speed of 3,550 can deliver a rated pressure from 40 to 56
psi without increasing the size of the pump. Because there is no cost difference be-
tween the rated pressure of 51 and 56 psi, and high pressure is not a concern, the 400
gpm pump rated at 56 psi is acceptable. Fire pump pressures will be explored in fur-
ther detail later.
For exceptionally tall buildings, more than one fire pump may be necessary to deliver
the pressure required to the higher floors. NFPA 20 permits a maximum of three pumps
to operate in series (NFPA 20-2013, Section 4.19.2.1).
63
NFPA 20: Fire pump design
Fire pumps cannot operate in parallel because the discharge check valve is forced Back to TOC
closed when the pressure on the outlet side of the valve is higher than that on the inlet
side. For this reason, it is not possible to add a parallel fire pump to boost the pressure
and/or flow to a system.
In buildings that are not equipped with enough power to supply an electric motor, a
diesel fire pump may be utilized. A fuel storage tank with the capacity to hold 1 gallon
of fuel per horsepower plus an additional volume to provide room for thermal expan-
sion is required. A dike must be provided beneath the fuel storage tank to contain any
potential fuel spills. Often, a pressure–relief valve is required on the discharge side of
the pump to relieve excess pressure in the event the engine revs out of control or if
a combination of suction pressure and pump pressure rise above a certain threshold.
The diesel motor exhaust must be routed through a muffler to the outside.
A diesel fire pump must be located in a separate enclosure or in a room with direct
access to the exterior. The enclosure size is substantially larger than normally required
for an electric fire pump because of the stored fuel and batteries necessary to provide
a backup power source. Diesel fire pumps are more expensive to install and maintain
because of the large number of mechanical parts, which can be prone to failure.
64
NFPA 20: Fire pump design
In buildings where the electrical capacity is not a concern, an electric driver is the pre- Back to TOC
ferred choice. Electric motors are more compact, require fewer mechanical parts and
produce fewer negative environmental impacts.
Though NFPA 20 provides guidelines for various types of pumps (centrifugal, vertical
shaft turbine, positive displacement and multistage multiport), centrifugal fire pumps
are — including horizontal split case and vertical in-line — the most common among
commercial buildings and thus highlighted in this example. Vertical in–line pumps are
generally more compact, with a smaller footprint. While horizontal split case pumps
must be mounted on a concrete housekeeping pad, vertical in-line pumps can instead
be mounted on pipe stand supports. For these reasons, vertical in–line pumps are of-
ten a preferred choice for replacements or retrofits.
The impeller rotation in a vertical in-line pump is less susceptible to mechanical dam-
age from water turbulence, allowing for more flexibility in the piping arrangement on
the suction side of the pump. Horizontal split case pumps are only permitted to have
elbows and tees installed perpendicular to the pump when the fitting is located at
least 10 pipe size diameters from the suction flange (NFPA 20-2013, Sections 4.14.6.3.1
to 4.14.6.3.3). These requirements are not applicable to vertical in-line styles.
Back to TOC
Fire pump pressures
The total head of a fire pump is the energy imparted to the liquid as it passes through
the pump, usually expressed in psi. For fire pumps such as horizontal split-case and
vertical in-line centrifugal pumps that are required to operate under net positive suc-
tion head, the total head of a fire pump is calculated by adding the suction head (city
pressure) to the discharge head. The discharge head of the pump varies along a per-
formance curve that is determined by three limiting points: the shut-off, the rating and
the overload.
The shut-off represents the maximum allowable total head pressure when the pump
is operating at zero flow; this is sometimes also referred to as the churn pressure. The
rating is the listed pressure and flow that the pump should produce when operating
at 100% of pump capacity. The total head pressure should not be less than 65% of the
rated total head when the pump is operating at 150% of rated flow capacity, this is the
overload point. System flow demands that exceed the overload point can expose the
pump to possible cavitation and damage.
A fire pump performance curve has an allowable operating range not to exceed 140%
of the rated pressure of the pump. Consider the previous example of a 400 gpm pump
rated at 56 psi. This pump will produce 400 gpm at 56 psi when operating at 100%
of pump capacity. It also can produce a maximum volume of 600 gpm at 36 psi when
operating at 65% of pump capacity. The available volume and pressure vary along the
pump curve.
Referring back to the medical building example, the loading dock required an estimat-
66
NFPA 20: Fire pump design
ed 507 gpm at 65 psi. From the pump curve in Figure 3, the pump will deliver approx- Back to TOC
imately 47 psi when flowing 507 gpm. When this discharge pressure is combined with
the city supply (47 + 48 psi = 95 psi), it is evident that the selected pump can easily
satisfy the hydraulic demand for the loading dock dry system.
A fire pump’s churn pressure is the amount of pressure generated when the pump is
operating at zero flow. The churn pressure is combined with the static water pressure
from the connected source, resulting in a combined static pressure for which all com-
ponents must be rated. As an example, a churn pressure rating of 126% will produce
71 psi of static discharge pressure from the aforementioned pump. When the churn
pressure is combined with the static city pressure, the total amount of static pressure
expected on the discharge side of the pump is 122 psi (71 psi discharge pressure + 51
static city pressure = 122 psi).
If the static pressure exceeds 175 psi (the pressure rating for standard sprinkler com-
ponents and maximum pressure allowed for fire hose valve connections), pressure–re-
ducing valves may be required unless all components of the system are rated for high
pressure. It is important to include the pump churn rating in the factors to consider
when weighing all of the options to make a proper pump selection.
The cost of a fire pump is largely based on the horsepower rating of the pump and the
type of controller. Vertical inline pumps are usually more cost effective when compared
to horizontal split-case pumps in smaller sizes (less than 1,000 to 1,250 gpm ratings). It
is recommended to consult a local fire pump representative to compare the horsepow-
er ratings between horizontal split-case and vertical in-line pumps, as the horsepower
rating can drive up costs related to controls and electrical connections.
67
NFPA 20: Fire pump design
Consult with the electrical engineer to discuss the pros and cons of the different con-
troller styles. The cost savings to the overall project may be greater by selecting the
more expensive soft start controller to reduce the size of the generator.
other sections of the standard. These valves must be electrically supervised through Back to TOC
the fire alarm system.
Where the local AHJ and/or municipal water department requires a backflow preventer
to be installed in the fire pump suction line, it must be located a minimum distance of
10 times the pipe size diameter from the pump suction flange (NFPA 20-2013, Section
4.27.3). This distance requirement is specific to backflow preventers equipped with
outside screw and yoke gate valves. If a backflow preventer is equipped with butterfly
valves, the minimum distance to the suction flange is increased to 50 feet (NFPA 20-
2013, Section 4.27.3.1). This increased distance is provided to allow for dissipation of
air bubbles that may form as water passes across the center disk of a fully open but-
terfly valve. Other nontraditional methods of backflow prevention, such as break tanks,
are not addressed within the purview of this article.
On the discharge side of the pump, a check valve and an indicating control valve are
required. The control valve must be installed after the check valve (NFPA 20-2013, Sec-
tion 4.15.7). If the fire pump is equipped with a flowmeter bypass, the bypass connec-
tion to the discharge pipe should be between the check valve and control valve. Where
fire pumps are installed in a series, butterfly valves are not permitted to be installed
between the pumps.
69
NFPA 20: Fire pump design
Back to TOC
A fire pump bypass is required on all fire pumps where the suction supply is of suffi-
cient pressure to be of material value without the pump (NFPA 20-2013, Section 4.14.4).
The bypass must be at least as large as the discharge pipe and should be equipped
with a check valve installed between two normally open control valves oriented in a
manner to prevent backflow to the suction side of the pump. The bypass line should
be connected before the outside screw and yoke on the suction side and after the con-
trol valve on the discharge side of the pump.
Every fire pump must be equipped with a metering device or fixed nozzles to accom-
modate pump testing. This equipment must be capable of water flow not less than
175% of rated pump capacity (NFPA 20-2013, Section 4.20.2.2). When the metering
device is installed in a loop arrangement for fire pump flow testing, an alternate means
of measuring the flow must also be provided.
The minimum pipe diameter and number of outlets required for a fire pump test head-
er is dictated by the flow capacity of the pump. These minimum requirements are
70
NFPA 20: Fire pump design
outlined in NFPA 20 (NFPA 20-2013, Table 4.26(a)). When the pipe between the test Back to TOC
header and the pump discharge flange exceeds 15 linear feet, the pipe diameter must
be increased to the next size up.
When transitional fittings are required to reduce or increase the pipe diameter at the
pump flange, care should be taken to select the proper reducing fitting. On the suction
side of the pump, the flanged reducer must be the eccentric tapered type, installed in
a manner to avoid air pockets. The reducer on the discharge side of the pump should
be the concentric type.
The fire department connection should tie into the system on the discharge side of the
pump. When an FDC is located upstream of a fire pump, the result can be high veloci-
ties that increase water turbulence and expose the fire pump to damaging conditions.
Many fire pumps have maximum suction pressure ratings that can be exceeded by the
pressures distributed through the FDC.
71
NFPA 20: Fire pump design
The enclosure should be large enough to provide adequate clearance for installation Back to TOC
and maintenance of the fire pump and related components. A good rule of thumb is to
provide at least 12 inches of clearance behind the fire pump and a minimum distance
of 12 inches from the edges of the entire fire pump assembly, piping and valves to the
walls. If the room consists of multiple sprinkler and/or standpipe risers, a minimum
clear distance of 12 inches between risers should be maintained to allow for easy ac-
cess to equipment. An approach clearance of at least 3 feet should be maintained in
front of the fire pump and related equipment. Minimum clearances in accordance with
NFPA 70 must be maintained around energized electrical equipment.
The fire pump room is intended solely for fire protection equipment and is not to be
shared by other mechanical trades. This rule is applicable to all equipment that is
nonessential to the operation of the fire pump except equipment related to domestic
water distribution. NFPA 20 provides an exception for domestic water equipment to be
located within the fire pump room.
There are many factors to consider when designing a fire pump. NFPA 20 contains
valuable requirements, which should be strictly followed to ensure that the fire pump
will perform as intended, should it ever be needed.
72
Back to basics: Introduction to
dedicated outdoor air systems Back to TOC
M ost building codes require mechanical ventilation with few exceptions. Many
building occupancy types require large volumes of outdoor air. Dedicated out-
door air systems (DOAS) provide 100% fresh outdoor air to a building or space. Unlike
traditional heating, ventilation and air conditioning (HVAC) systems, which usually recir-
culate air inside the building, DOAS units bring in outdoor air and condition it before
distributing it throughout the building.
DOAS usually run alongside other HVAC equipment serving the building or space
to meet the need for outdoor air. Where traditional cooling and heating equipment
can’t meet latent loads, special equipment is needed, increasing costs and space
requirements.
According to the ASHRAE Handbook 2020: Heating, Ventilating and Air Conditioning
Systems and Equipment, DOAS can help bridge that gap by centralizing the conditions
of the outdoor air and in some cases incorporating an energy recovery ventilator (ERV).
Benefits of DOAS
Although the main reason for using a DOAS unit is to meet minimum ventilation re-
quirements, these systems also provide other benefits. Conditioning the outdoor air
separately from recirculated air makes it easier to verify that each zone is being provid-
ed with sufficient outdoor air.
73
Back to basics: Introduction to dedicated outdoor air systems
Back to TOC
The requirements for ventilation rates by building codes and other standards are the
main driving factors for installing DOAS. With the growing popularity of DOAS to meet
ventilation needs, these systems are provided by various manufacturers and suppliers.
Manufacturers are beginning to provide an array of configurations that meet different
design needs.
74
Back to basics: Introduction to dedicated outdoor air systems
The type of equipment used with a DOAS unit may vary depending on building type, Back to TOC
spatial constraints and end-user needs. The benefit of a DOAS is that it, unlike a lot of
other HVAC equipment, can meet these high ventilation rate requirements.
DOAS units are designed to accommodate a diverse range of entering air conditions,
ranging from the hottest summer days to the coldest winter nights. Units can temper
the outdoor air using different methods. The system configuration types include water
source heat pumps, air source heat pumps, water-cooled direct expansion, air-cooled,
direct expansion or chilled water. These configuration options are chosen based on
client site utilities, client preference and even an energy model’s least-cost estimates.
Manufacturers also provide customization options for DOAS units. Cabinets can be
outfitted with insulated foam to reduce heat transfer losses and corrosion-resistant
coatings to withstand challenging environments. There is also the option to provide
human machine interface, which allows a simpler way to program different unit settings
such as temperature and humidity.
The DOAS unit typically cools and dehumidifies air in the summer and humidifies and
75
Back to basics: Introduction to dedicated outdoor air systems
heats air in the winter. The most basic unit consists of a preheating coil, a cooling coil, Back to TOC
a reheating coil and a humidifier. DOAS units can also be provided with a wide range
of additional components to meet specific design needs and climate conditions. The
below outlines common equipment components:
Supply and/or exhaust fans. DOAS units come standard with supply fans and also
can be equipped with an optional exhaust fan and/or heat recovery component. Ple-
num supply fans are also common in DOAS applications.
Cooling modules. Cooling modules are useful for cooling and/or dehumidifying out-
door air.
Heating modules. When a space requires heat greater than what the base unit can
provide, DOAS units can be provided with electricity, natural gas, liquefied petroleum
gas (propane), steam or hot water as a heating source. The heating systems have multi-
ple options for control including multistage, silicon-controlled rectifier or modulating.
Humidifiers. DOAS units can be fitted with humidifiers to be used during the dry out-
door conditions to bring moisture into the air, providing greater occupant comfort.
76
Back to basics: Introduction to dedicated outdoor air systems
Hot gas reheat. Manufacturers offer hot gas reheat options on their units for dehu- Back to TOC
midification purposes. On a mild but humid day when air needs to be dehumidified,
the only way to remove moisture is to cool the air. To avoid creating cold clammy air
if it is not warm enough, this additional option allows cooled, dehumidified air to be
heated to a more comfortable temperature, providing neutral dry air. Heating and heat
recovery of air above 60°F in DOAS units that provide ventilation air to multiple zones
and operate in conjunction with zone heating and cooling systems when building loads
or outside air temperature indicate the majority of zones are in cooling is prohibited
by ASHRAE Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential
Buildings. In other words, heated “room neutral” air from a DOAS can cause energy
waste when downstream units must recool it to meet zone temperature setpoints.
Air-to-air energy recovery devices. Energy recovery for these units is typically air-to-
air. This can be provided through polymer enthalpy wheels, aluminum enthalpy wheels
or enthalpy plate heat exchangers. Energy is recovered when two streams of air —
fresh air and return air — pass through the energy recovery device and transfer mois-
ture and heat from one air source to the other.
Filters and other cleaning devices. Air purity can be improved through different fil-
tration options provided for units including MERV 8, 11 or 14 filters; metal mesh filters;
or some manufacturers even offer bipolar ionization. Bipolar ionization systems gen-
erate positively and negatively charged particles to help HVAC systems remove them
from the airstream.
Back to TOC
in various measurements, which include, outdoor, dis- Figure 2: This figure provides a
basic arrangement of a dedicated
charge, space and return humidity and air temperature
outdoor air systems (DOAS) unit
measures. in combination with a variable air
volume system to condition a building
space. Courtesy: CDM Smith
Unit configurations. Unit orientations can be modified
to meet space requirements. This is especially useful
in retrofit applications where available space is limited. Manufacturers typically allow
either vertical or horizontal supply air discharge placement and vertical, horizontal or
no return air arrangements.
When designing a building’s HVAC system, the engineer or designer may opt to provide
multiple smaller units to have more zone controllability in lieu of single, large units.
Air distribution
DOAS units can be integrated with almost any type of heating and cooling system de- 78
Back to basics: Introduction to dedicated outdoor air systems
sign. DOAS units are often used in conjunction with fan coil units, variable air volume Back to TOC
(VAV) systems, variable refrigerant flow systems or packaged terminal air conditioners.
In any configuration type, the DOAS selection would consider the outdoor air and latent
loads for the building and the local equipment would be sized for each space’s sensible
loads. This allows for a reduction in the local equipment’s sizing because it will only need
to be sized to handle the sensible load generated within the space. One configuration
type is ducting directly from the DOAS unit to each space the unit serves.
Another system configuration for the DOAS is to duct the outdoor air directly to the
return of the local unit. When the DOAS is ducted directly to the return, it allows the
local unit to mix the outdoor air with the recirculated air and condition this mixture.
The final HVAC system configuration discussed occurs where the DOAS is ducted to
a ceiling plenum, closet or mechanical room plenum, which the local unit uses as an
intake. This method is typically not recommended as it is challenging to guarantee that
each space receives its allotted outdoor air requirement.
DOAS Controls
In different design climates, DOAS can provide different modes of operation. For hot
and humid areas, the DOAS unit should run in dehumidification and cooling mode. In
other climate zones where ambient conditions are hot and dry, the DOAS unit may only
need to run in sensible cooling mode. In cold climate areas, the DOAS may need to
heat the incoming outdoor air in heating mode and provide humidification.
During occupied hours, the DOAS may need to run in these different operating modes
79
Back to basics: Introduction to dedicated outdoor air systems
and provide ventilation air. During unoccupied hours, because ventilation is not re- Back to TOC
quired, the DOAS may only need to provide dehumidification to ensure the building
stays dry. This is done by closing the outdoor air intake damper and just recirculating
return air to allow it to be dehumidified. This control method reduces wasted energy
and provides cost savings for the building owner.
Code requirements
ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality was first pub-
lished in 1973 and provides industry standards for outdoor air requirements for various
occupied building types and spaces. ASHRAE Standard 62.1 is continuously updating
and evolving to ensure minimum IAQ is provided for building occupants.
In some cases, there is a benefit to providing more outdoor air to a space than mini-
mum required by code. One U.S. Green Building Council LEED point can be achieved
by providing 30% more outdoor air to each breathing zone than the minimum required
by ASHRAE Standard 62.1. LEED Certification is the most widely used global rating
system that recognizes the design and construction of high-performance buildings that
are better for occupants and the environment.
Another benefit of providing more outdoor air than is required by code minimums is
an increase in employee production by reducing quantities of carbon dioxide. Studies
have shown that higher concentrations of carbon dioxide may lead to slower reaction
times and increased tiredness. Providing additional outdoor air can also help reduce
the infection rate of viruses. By providing fresh air, the concentration of viruses in the
space also decreases.
80
Back to basics: Introduction to dedicated outdoor air systems
Back to TOC
DOAS units that provide 100% ventilation air are be- Figure 3: This figure displays four
dedicated outdoor air systems (DOAS)
coming more widely used. In building spaces where control modes. Courtesy: CDM Smith
outdoor air requirements are high due to energy
codes and ASHRAE standards, DOAS units are often most efficient. DOAS units are
also best used for buildings with large occupancies or zones that require all or large
amounts of air to be exhausted, such as commercial kitchens.
The below are common building and space occupancy types that are best served by
DOAS:
• Animal shelters.
• Conference rooms.
• Locker rooms.
81
Back to basics: Introduction to dedicated outdoor air systems
Back to TOC
• Multifamily housing.
• Nursing homes.
• Retail stores.
• Veterinary hospitals.
DOAS systems are an innovative approach for HVAC design that have proven to be
highly efficient while providing occupant comfort and meeting the needs for outdoor
air requirements. Many design applications benefit from the use of DOAS systems and
these systems can be used in a wide variety of building types.
82
Codes &
Standards
Thank you for visiting the Codes & Standards eBook!