2
Nomenclature
Outdoor Unit
Model Name
120 H F G H ID
(1) (2) (3) (4) (5) (6) (7) (8) Buyer
AM DVM V Inverter
M DVM S Eco
(2) Capacity
(6) Feature 2
x 1/10 HP (3 digits)
C STANDARD+TROPICAL+MODULE
F* STANDARD+TROPICAL+NON MODULE
J HIGH+TROPICAL+MODULE
M HIGH+TROPICAL+NON MODULE
(3) Version
X Outdoor Unit
N Indoor Unit
(8) Mode
H Heat Pump
R Heat Recovery
3
Features & Benefits
Samsung’s VRF system air conditioners offer instant temperature control, user-friendly installation and advanced
functionality, along with smart power usage. Our flagship VRF-based Samsung DVM S is a highly innovative system
that adopts the new third-generation Samsung Scroll Compressor (SSC) technology with Dual Digital Inverter.
DVM S provides world-class energy efficiency and the most powerful cooling and heating performance available on
the market. This ideal air conditioning system accomodates all variable environments, including large commercial
or residential buildings.
Samsung DVM S offers innovative features to benefit the indoor comfort as well operational coasts of the system
through technological advances such as:
Optimized the atmosphere and control costs with high energy efficiency
Samsung DVM S Desert features several smart technologies that combined deliver world-class energy efficiency for
today's eco and budget-conscious businesses. With these technologies, DVM S Desert boasts a superior 13 percent
higher Energy Efficiency Ratio (EER).
Heat Exchanger Performance 150% Reduce maintenance and energy costs with intercoolers
115% DVM S Desert features a PHE type intercooler, which
100% improves cooling and heating efficiency by 30 percent
compared to Shell & Tube and Double Tube type
intercoolers. The higher heat exchange rate means optimal
distribution, lowering maintenance and energy costs.
4
Features & Benefits
Hydrophilic layer acrylic Protect your investment with corrosion and frost
resin+surfactant resistance
Anti-corrosive DVM S Desert includes a hydrophilic coating that
layer epoxy acrylic
facilitates efficient heat exchange and delays the
Raw aluminum onset of frost formation to provide consistent
material heating performance. An anti-correosive coating
also helps units to resist corrosion from the
elements, with:
• Epoxy acrylic coating
Corrosion resistant finishing on heat exchanger fin • Acrylic and surfactant coating
PCB PCB
Smart management
Further improves system’s energy efficiency due to precise indoor
climate control. Web-based remote monitoring and management
system allows quick and easy HVAC control and breakdown alert.
5
Contents
1. Combination Table 7
2. Specification 11
3. Electrical Characteristics 25
4. Dimensional Drawing 26
5. Center of Gravity 28
6. Electrical Wiring Diagrams 30
7. Sound Data 31
8. Operation Range 36
9. Piping Diagram 38
10. Installation 43
11. Accessory 68
6
1. Combination Table
Outdoor Units
Standard
NOTE
• Make sure to use an indoor unit that is compatible with DVM S.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ( Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ( Outdoor unit capacity)
※ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQDEH∗∗∗, AM∗∗∗JNVDKH∗∗∗) can be connected.
7
1. Combination Table
Indoor Units
Capacity (kW)
Model
1.5 1.7 2.2 2.8 3.2 3.6 4.5 5.6 6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0
JSF-1
1Way
CST
JSF-2
2Way CST
4Way CST
360 CST
Floor
Standing Unit
4Way CST S
(600X600)
Duct S (MSP)
Slim Duct
MSP Duct
Ceiling
Console
Boracay
Boracay (with
EEV)
AR5000 (with
EEV)
8
1. Combination Table
Indoor Units
Capacity (kW)
Model 22.0/ 500 1000
6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0 18.0 25.0 28.0 32.0 50.0
22.4 CMH CMH
HSP Duct
OAP Duct
PAC
ERV Plus
NOTE
• Make sure to use an indoor unit that is compatible with DVM S.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
※ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQDEH∗∗∗, AM∗∗∗JNVDKH∗∗∗) can be connected.
9
1. Combination Table
External Appearance
Standard
Capa Capa
Model Name Model Model Name Model
[HP] [HP]
12 AM120HXVFGH/ID
8 AM080HXVFGH/ID
14 AM140HXVFGH/ID
10 AM100HXVFGH/ID
16 AM160HXVFGH/ID
18 AM180HXVFGH/ID
22 AM220HXVFGH/ID
20 AM200HXVFGH/ID
24 AM240HXVFGH/ID
26 AM260HXVFGH/ID
34 AM340HXVFGH/ID
28 AM280HXVFGH/ID
42 AM420HXVFGH/ID
30 AM300HXVFGH/ID
32 AM320HXVFGH/ID
36 AM360HXVFGH/ID
38 AM380HXVFGH/ID
40 AM400HXVFGH/ID
44 AM440HXVFGH/ID
46 AM460HXVFGH/ID
48 AM480HXVFGH/ID
10
2. Specification
Standard
11
2. Specification
Standard
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Cooling(46℃) : Indoor temperature 29°C DB, 19°C WB / Outdoor temperature 46°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed
or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
12
2. Specification
Standard
13
2. Specification
Standard
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Cooling(46℃) : Indoor temperature 29°C DB, 19°C WB / Outdoor temperature 46°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed
or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
14
2. Specification
Standard
15
2. Specification
Standard
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Cooling(46℃) : Indoor temperature 29°C DB, 19°C WB / Outdoor temperature 46°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed
or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
16
2. Specification
Standard
17
2. Specification
Standard
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Cooling(46℃) : Indoor temperature 29°C DB, 19°C WB / Outdoor temperature 46°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed
or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
18
2. Specification
Standard
19
2. Specification
Standard
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Cooling(46℃) : Indoor temperature 29°C DB, 19°C WB / Outdoor temperature 46°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed
or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
20
2. Specification
Standard
21
2. Specification
Standard
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Cooling(46℃) : Indoor temperature 29°C DB, 19°C WB / Outdoor temperature 46°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed
or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
22
2. Specification
Standard
23
2. Specification
Standard
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Cooling(46℃) : Indoor temperature 29°C DB, 19°C WB / Outdoor temperature 46°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed
or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
24
3. Electrical Characteristics
Standard
Capacity Power Supply Voltage Range Running Current [A] Current [A] ODU Fan Motor
Model Min. Max. Cooling
HP kW Hz Voltage Cooling Heating MCA MFA kW FLA [A]
(-10%) (+10%) (46℃)
8 22.4 AM080HXVFGH/ID 50 380-415 342 456 8.40 10.00 8.20 22.0 25 0.83 2.4
10 28 AM100HXVFGH/ID 50 380-415 342 456 11.60 14.45 12.20 24.0 32 0.83 2.4
12 33.6 AM120HXVFGH/ID 50 380-415 342 456 13.50 15.20 13.00 26.6 32 1.24 3.8
14 40 AM140HXVFGH/ID 50 380-415 342 456 16.79 21.60 17.93 34.0 40 1.24 3.8
16 45 AM160HXVFGH/ID 50 380-415 342 456 20.75 25.80 20.46 41.0 50 1.24 3.8
18 50.4 AM180HXVFGH/ID 50 380-415 342 456 20.00 24.45 20.40 46.0 63 1.66 4.8
20 56 AM200HXVFGH/ID 50 380-415 342 456 23.20 28.90 24.40 48.0 63 1.66 4.8
22 61.6 AM220HXVFGH/ID 50 380-415 342 456 25.10 29.65 25.20 50.6 63 2.07 6.2
24 67.2 AM240HXVFGH/ID 50 380-415 342 456 27.00 30.40 26.00 53.2 63 2.48 7.6
26 73.6 AM260HXVFGH/ID 50 380-415 342 456 30.29 36.80 30.93 60.6 75 2.48 7.6
28 78.6 AM280HXVFGH/ID 50 380-415 342 456 34.25 41.00 33.46 67.6 75 2.48 7.6
30 85 AM300HXVFGH/ID 50 380-415 342 456 37.54 47.40 38.39 75.0 90 2.48 7.6
32 90 AM320HXVFGH/ID 50 380-415 342 456 41.50 51.60 40.92 82.0 90 2.48 7.6
34 95.2 AM340HXVFGH/ID 50 380-415 342 456 38.60 44.85 38.20 77.2 90 3.31 10.0
36 100.8 AM360HXVFGH/ID 50 380-415 342 456 40.50 45.60 39.00 79.8 90 3.72 11.4
38 107.2 AM380HXVFGH/ID 50 380-415 342 456 43.79 52.00 43.93 87.2 100 3.72 11.4
40 112.2 AM400HXVFGH/ID 50 380-415 342 456 47.75 56.20 46.46 94.2 125 3.72 11.4
42 118 AM420HXVFGH/ID 50 380-415 342 456 53.10 66.05 53.12 106.0 125 3.31 10.0
44 123.6 AM440HXVFGH/ID 50 380-415 342 456 55.00 66.80 53.92 108.6 125 3.72 11.4
46 130 AM460HXVFGH/ID 50 380-415 342 456 58.29 73.20 58.85 116.0 150 3.72 11.4
48 135 AM480HXVFGH/ID 50 380-415 342 456 62.25 77.40 61.38 123.0 150 3.72 11.4
NOTE
• MCA : Minimum circuit amperes
• MFA : Maximum fuse amperes
• FLA : Full load amperes
25
4. Dimensional Drawing
Outdoor unit
• AM080~100HXVFGH
Units : mm [inches]
Pitch of foundation bolt holes
740
[2’-5”]
B B
[2’-6”]
761
[4 3/4”]
[4 3/4”]
120
11 8
7
239
[9 1/2”]
381
4-20 x 12 SLOT HOLE [1’-3”]
Foundation bolt holes
765
[2'-6"]
[5’-6 3/4”]
1695
40
75 [1 1/2”]
[3”] 55
55 [2 1/4”]
[2 1/4”] 95
[3 3/4”]
65
6 [2 1/2”]
4 6
3
616 A
[2’-1/4”]
87 492 47
[3 1/2”] 8 [2’-6”] [1 3/4”]
[9 1/2”]
65 65
241
[2 1/2”] [2 1/2”]
17 9
[7”]
[4 1/2”]
107
11 5
107
[4 1/4”] [4 1/4”]
625
5
89 202 5
[2’ -1/2”]
[3 1/2”] [8”]
803
[2’-7 1/2”] 653 74
[2’-1 3/4”] [3”]
880
[2’-10 3/4”]
NOTE
1. Detail A and SECTION B-B indicate the dimentsion
after fixing the attached piping. C
2. Item 3-8 : Knock-out hole.
3. View C indicate the dimension of kock-out hole(bottom).
4. Pipe [Ф, mm(inch)] : Brazing connection
View C
HP Liquid pipe Gas pipe 60 192
8 9.52(3/8) 19.05(3/4) [2 1/2”] [7 1/2”]
10 9.52(3/8) 22.22(7/8) 95
[3 3/4”]
12 12.70(1/2) 28.58(1 1/8)
14 12.70(1/2) 28.58(1 1/8) 90
[3 1/2”]
16 12.70(1/2) 28.58(1 1/8)
18 15.88(5/8) 28.58(1 1/8)
20 15.88(5/8) 28.58(1 1/8)
22 15.88(5/8) 28.58(1 1/8)
24 15.88(5/8) 34.92(1 3/8) 7
26 19.05(3/4) 34.92(1 3/8)
28 19.05(3/4) 34.92(1 3/8)
30 19.05(3/4) 34.92(1 3/8)
26
4. Dimensional Drawing
Outdoor unit
• AM120~160HXVFGH
Units : mm [inches]
Pitch of foundation bolt holes
115 0
[3’ - 9 1/4 ”]
Section B-B
[2’ - 6”]
761
7
[4 3/4”]
[4 3/4”]
11 8
120
344
[1'-1 1/2"]
486
4-20 x 12 SLOT HOLE [1'-7 1/4"]
Foundation bolt holes
765
[2'-6"]
[5'-6 3/4”]
1695
75 40
[3”] [1 1/2”]
55 55
[2 1/4”] [2 1/4”]
95
[3 3/4”]
6 65
[2 1/2”]
6
616
87
[2’-1/4”] A
[3 1/2”] 492 47
[2’-6”] [1 3/4”]
65
[2 1/2”]
[9 1/2”]
65
241
107 [2 1/2”]
17 9
[4 1/2”]
[7”]
[4 1/4”] 107
11 5
625
5 [4 1/4”]
[2’ -1/2”]
803 11 9 202 8 4 3 5
[2’-7 1/2”] [4 3/4”] [8”]
1069 74
[3’ - 6”] [3”]
1295
[4’ - 3”]
NOTE
1. Detail A and SECTION B-B indicate the dimentsion
after fixing the attached piping. C
2. Item 3-8 : Knock-out hole.
3. View C indicate the dimension of kock-out hole(bottom).
4. Pipe [Ф, mm(inch)] : Brazing connection
27
5. Center of Gravity
Outdoor unit
• AM080~100HXVFGH
Units : mm [inches]
[5'-6 3/4"]
1695
A B
761 740
[2’-6”] [2’-5”]
Model A B C
28
5. Center of Gravity
Outdoor unit
• AM120~160HXVFGH
Units : mm [inches]
[5'-6 3/4"]
1695
A B
761 1150
[2’-6”] [3’-9 1/4”]
Model A B C
29
6. Electrical Wiring Diagrams
Outdoor unit
• AM080~160HXVFGH
INV PBA1 Printed circuit board (inverter1) EEV1 Electronic expansion valve 1 LIQUID(10K) Thermistor (Liquid Tube Temp._10Kohm)
INV PBA2 Printed circuit board (inverter2) EEV2 Electronic expansion valve 2 HOTGAS1 V/V Solenoid valve (Hot Gas Bypass1)
EMI PBA1 Printed circuit board (emi1) EVI-OUT(10K) Thermistor (EVI-out_10kohm) EVI BYPASS V/V Solenoid valve (EVI BYPASS)
EMI PBA2 Printed circuit board (emi2) EVI-IN(10K) Thermistor (EVI-in_10kohm) RETURN V/V Solenoid valve (Accumulator Oil Return)
FAN PBA Printed circuit board (fan motor) SUCTION1(10K) Thermistor (Suction Temp.1_10Kohm) 4WAY V/V Solenoid valve (4 Way valve)
MAIN PBA Printed circuit board (main) SUCTION2(10K) Thermistor (Suction Temp.2_10Kohm) CCH1 Crank Case Heater (Compressor1)
HUB PBA Printed circuit board (hub) SNOW SENSOR SNOW SENSOR CCH2 Crank Case Heater (Compressor2)
COMM PBA Printed circuit board (communication) OIL-COMP1 Oil-Sensor (Compressor1) MAIN COOLING Solenoid valve (Main cooling)
COMP1 Motor (compressor1) OIL-COMP2 Oil-Sensor (Compressor2) HOTGAS2 V/V Solenoid valve (Hot Gas Bypass2)
COMP2 Motor (compressor2) OUT(10K) Thermistor (Ambient Temp._10Kohm) OD EEV V/V Solenoid valve (Outdoor EEV)
FAN1 Motor (fan1) COND(10K) Thermistor (Cond Out Temp._10Kohm) F101 FUSE (Inverter PBA)
FAN2 Motor (fan2) TOP1(200K) Thermistor (Compressor Top 1_200Kohm) 690V/T40A FUSE (EMI PBA)
EVI V/V 1 Solenode valve (EVI1) TOP2(200K) Thermistor (Compressor Top 2_200Kohm) MODE CHANGE Connector (Remote switching cool/heat selector)
EVI V/V 2 Solenode valve (EVI2) DIS1(200K) Thermistor (Discharge Temp.1_200Kohm) EXT CON Connector (Output EXT CON)
EVI EEV Electronic expansion valve (EVI) DIS2(200K) Thermistor (Discharge Temp.2_200Kohm) ERROR/COMP EXT Connector (Output ERROR/COMP EXT CON)
NOTE
• This wiring diagram applies only to the outdoor unit.
• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
• When operating, don’t shortcircuit the protection device (High Pressure switch)
• For connection wiring indoor-outdoor transmission F1-F2, outdoor_outdoor transmission OF1-OF2, refer to
the installation manual.
• Protective earth(screw), : connector, : The wire quantity
30
7. Sound Data
Summary
Standard
NOTE
• Sound Pressure Level
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB /
Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
• Sound Power Level
- Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level.
- Reference power : 1pW.
- Measured according to ISO 3741.
31
7. Sound Data
Sound Pressure level
Unit: dB(A)
• NR Curve
1) AM080HXVFGH/ID 2) AM100HXVFGH/ID
90 90 90 90
85 85 85 85
80 80 80 80
75 75 75 Cooling 75
Sound Pressure Level (dB)
Sound Pressure Level (dB)
70 Cooling 70 70 70
65 65 65 65
NC 70 NC 70
60 60 60 60
Silent 1 NC 60 Silent 1 NC 60
55 Silent 2 55 55 Silent 2 55
NC 55 NC 55
50 Silent 3 50 50 Silent 3 50
NC 50 NC 50
45 45 45 45
NC 45 NC 45
40 40 40 40
NC 40 NC 40
35 35 35 35
NC 35 NC 35
30 30 30 30
NC 30 NC 30
25 25 25 25
20 NC 25 20 20 NC 25 20
15 NC 20 15 15 Hearing threshold NC 20 15
Hearing threshold
10 NC 15 10 10 NC 15 10
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
3) AM120HXVFGH/ID 4) AM140HXVFGH/ID
90 90 90 90
85 85 85 85
80 80 80 80
75 Cooling 75 75 75
Sound Pressure Level (dB)
70 70 70 70
65 65 65 Cooling 65
NC 70 NC 70
60 60 60 60
Silent
Silent 12 NC 60 Silent
Silent 12 NC 60
55 55 55 55
NC 55 NC 55
50 Silent 3 50 50 Silent 3 50
NC 50 NC 50
45 45 45 45
NC 45 NC 45
40 40 40 40
NC 40 NC 40
35 35 35 35
NC 35 NC 35
30 30 30 30
NC 30 NC 30
25 25 25 25
20 NC 25 20 20 NC 25 20
15 Hearing threshold NC 20 15 15 Hearing threshold NC 20 15
10 NC 15 10 10 NC 15 10
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB /
Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
32
7. Sound Data
Sound Pressure level
Unit: dB(A)
1.5m Front
• NR Curve
1) AM160HXVFGH/ID
90 90
85 85
80 80
75 75
Sound Pressure Level (dB)
70 Cooling
70
65 65
NC 70
60 Silent 1
60
Silent 2 NC 60
55 55
NC 55
50 Silent 3 50
NC 50
45 45
NC 45
40 40
NC 40
35 35
NC 35
30 30
NC 30
25 25
20 NC 25 20
15 Hearing threshold NC 20 15
10 NC 15 10
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB /
Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
33
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM080HXVFGH/ID 77
AM100HXVFGH/ID 79
AM120HXVFGH/ID 81
AM140HXVFGH/ID 83
1) AM080HXVFGH/ID 2) AM100HXVFGH/ID
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
90 90 90 90
85 85 85 85
80 80 80 80
75 75 75 75
70 70 70 70
65 65 65 65
60 NC 70 60 60 NC 70 60
55 NC 60 55
55 NC 60 55
50 NC 55 50
50 NC 55 50 45 NC 50 45
45 NC 50 45 40 NC 45 40
40 NC 45 40 35 NC 40 35
35 NC 40 35 30 NC 35 30
30 NC 35 30 25 NC 30 25
25 NC 30 25 20 NC 25 20
20 NC 25 20 15 NC 20 15
15 NC 20 15 10 NC 15 10
10 NC 15 10 5 5
5 5 0 0
0 0 125 250 500 1000 2000 4000 8000 A
125 250 500 1000 2000 4000 8000 A Octave Band Center Frequency(Hz)
Octave Band Center Frequency(Hz)
3) AM120HXVFGH/ID 4) AM140HXVFGH/ID
110 110 110 110
105 105 105 105
100 100 100 100
95 95 95 95
Sound Power Level (dB)
Sound Power Level (dB)
90 90 90 90
85 85 85 85
80 80 80 80
75 75 75 75
70 70 70 70
65 65 65 65
60 NC 70 60 60 NC 70 60
55 NC 60 55 55 NC 60 55
50 NC 55 50 50 NC 55 50
45 NC 50 45 45 NC 50 45
40 NC 45 40 40 NC 45 40
35 NC 40 35 35 NC 40 35
30 NC 35 30 30 NC 35 30
25 NC 30 25 25 NC 30 25
20 NC 25 20 20 NC 25 20
15 NC 20 15 15 NC 20 15
10 NC 15 10 10 NC 15 10
5 5 5 5
0 0 0 0
125 250 500 1000 2000 4000 8000 A 125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)
NOTE
• Specifications may be subject to change without prior notice.
- Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level.
- Reference power : 1pW.
- Measured according to ISO 3741.
34
7. Sound Data
Sound Power level
Unit: dB(A)
Model Power
AM160HXVFGH/ID 84
1) AM160HXVFGH/ID
110 110
105 105
100 100
95 95
Sound Power Level (dB)
90 90
85 85
80 80
75 75
70 70
65 65
60 NC 70 60
55 NC 60 55
50 NC 55 50
45 NC 50 45
40 NC 45 40
35 NC 40 35
30 NC 35 30
25 NC 30 25
20 NC 25 20
15 NC 20 15
10 NC 15 10
5 5
0 0
125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz)
NOTE
• Specifications may be subject to change without prior notice.
- Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level.
- Reference power : 1pW.
- Measured according to ISO 3741.
35
8. Operation Range
Cooling Heating
55 30
54
24
45
20
35
10
25 Continuous
Operation Range
Outdoor(˚CDB)
Outdoor(˚CDB)
Warming
Up Continuous
15 0
Operation Operation Range
Range
5
-10
-5
“Expand Operational
Temperature Range” Option -20
-15
-25
-25 -30
10 15 20 25 27 30 5 10 15 20 25 27 30
Indoor(˚CWB) Indoor(˚CWB)
36
8. Operation Range
Defrosting correction factor
The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while
the defrosting operation is in progress.
The capacity values, which take these factors into account, in other words, the integrated heating capacity values,
can be calculated as follows :
Formula : A = B × C
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation (kW) = C
Outdoor temperature (°C, DB/WB) -10/-10.4 -8/-8.5 -6/-6.5 -4/-4.6 -2/-2.7 0/-0.7 2/1.2 5/4.1 7/6
Capacity coefficient 0.99 0.98 0.96 0.95 0.91 0.88 0.86 0.91 1.00
On heating operation, frost can be formed on heat exchanger according to outdoor temperature.
(Frost on heat exchanger results in decreasing the performance.)
To remove frost on heat exchanger of outdoor unit, defrost operation is carried out periodically.
During defrost operation, capacity of outdoor unit may decrease.
The decrement is not considered to the individual capacity tables.
This figure shows an effect of intelligence defrost operation
It is actually the frost occurrence section from 0 ℃ or less.
Since the outdoor temperature over 0 ℃, the heating performance is the same before and after applying intelligence
defrost operation
In outdoor conditions below 0 ℃, frost conditions reflect the actual entering the defrost opration because heating
performance is improved
37
9. Piping Diagram
Outdoor unit
(1) AM080~100HXVFGH
Thermistor -
Cond Out (T_CO)
Pressure Sensor -
High (PS_H)
Solenoid Valve -
Solenoid Valve - EVI Bypass Thermistor -
Check Valve - Hot Gas bypass (V_HG) (V_EB)
Discharge EVI Out (T_EO) Heat Exchanger -
(CV_D) Intercooler (HX_IC)
Thermistor -
Oil Separator EVI In (T_EI)
(OS)
Pressure
Switch -
High
(PW_H) Thermistor - Electronic
Discharge Expansion
pipe (T_D) Valve -
Thermistor - Accumulator EVI (E_EVI)
Compressor (AC)
Top Pressure
(T_CT) Sensor -
Low (PS_L) IPM Cooler
Compressor
(COMP) (IPMC)
Thermistor -
Liquid pipe (T_L)
Solenoid
Valve - Solenoid Valve -
EVI (V_EVI) Accumulator oil Return (V_AR)
Ball Valve -
Liquid pipe (BV_L)
38
9. Piping Diagram
Outdoor unit
(2) AM120HXVFGH
Thermistor -
Cond Out (T_CO)
Pressure Sensor -
High (PS_H)
Solenoid Valve -
Solenoid Valve - EVI Bypass Thermistor -
Check Valve - Hot Gas bypass (V_HG) (V_EB)
Discharge EVI Out (T_EO) Heat Exchanger -
(CV_D) Intercooler (HX_IC)
Thermistor -
Oil Separator EVI In (T_EI)
(OS)
Pressure
Switch -
High
(PW_H) Thermistor - Electronic
Discharge Expansion
pipe (T_D) Valve -
Thermistor - Accumulator EVI (E_EVI)
Compressor (AC)
Top
(T_CT)
Compressor Pressure Sensor - IPM Cooler
(COMP) Low (PS_L) (IPMC)
Thermistor -
Liquid pipe (T_L)
Solenoid
Valve - Solenoid Valve -
EVI (V_EVI) Accumulator oil Return (V_AR)
Ball Valve -
Liquid pipe (BV_L)
39
9. Piping Diagram
Outdoor unit
(3) AM140~160HXVFGH
Thermistor -
Cond Out (T_CO)
Thermistor -
Liquid pipe (T_L)
Solenoid
Valve - (V_EVI2) Solenoid Valve -
EVI 1 Accumulator oil Return (V_AR)
(V_EVI1)
Ball Valve -
Liquid pipe (BV_L)
40
Cooling System
9. Piping Diagram
• 16HP with indoor units
High Temperature & Pressure Gas
High Temperature & Pressure Liquid
↑
Low Temperature & Pressure Gas
Ball Valve - Low Temperature & Pressure Liquid
Outdoor Fan Motor 1 Outdoor Fan Motor 2 Gas pipe (BV_G)
(OFM1) (OFM2)
COOL
Thermistor - Ambient (T_A)
FAN ON
↑
↑
Thermistor -
↑
↑
Cond Out (T_CO)
↑
Heat Exchanger - Main (HX_M)
↑
↑
Solenoid Valve - 4Way (V_4W)
IPM Cooler 1
Pressure Sensor - (IPMC1)
High (PS_H) COOL
↑ FAN ON
↑
Solenoid Valve - IPM Cooler 2
Check Valve - Hot Gas bypass (V_HG) (IPMC2)
Discharge 1 (CV_D2)
↑
(CV_D1) ↑
Oil Separator 1 (OS2) Solenoid Valve -
(OS1) EVI Bypass Thermistor - OFF
(V_EB) EVI Out (T_EO) Heat Exchanger - FAN OFF
Pressure Intercooler (HX_IC)
↑ ↑
Switch - Thermistor -
(PW_H2)
High 1 EVI In (T_EI)
(PW_H1) Thermistor -
Discharge (T_D2)
Thermistor - pipe 1 (T_D1) Accumulator
Compressor COOL
(T_CT2) (AC)
Top 1 FAN ON
↑
(T_CT1)
Compressor 1 Pressure Sensor - Electronic
(COMP2) ↑ Expansion
(COMP1) Low (PS_L)
↑
↑
Valve -
EVI (E_EVI)
↑
Thermistor -
Liquid pipe (T_L) OFF
Solenoid FAN OFF
Valve - (V_EVI2) Solenoid Valve - Ball Valve -
EVI 1(V_EVI1) Accumulator oil Return (V_AR) Liquid pipe (BV_L)
↑
41
42
Heating System
9. Piping Diagram
• 16HP with indoor units
High Temperature & Pressure Gas
High Temperature & Pressure Liquid
↑
Low Temperature & Pressure Gas
Ball Valve - Low Temperature & Pressure Liquid
Outdoor Fan Motor 1 Outdoor Fan Motor 2 Gas pipe (BV_G)
(OFM1) (OFM2)
HEAT
Thermistor - Ambient (T_A)
FAN ON
↑
↑
Thermistor -
↑
↑
Cond Out (T_CO)
↑
Heat Exchanger - Main (HX_M)
O u tdoor Hea t E x ch an ger ( O HX )
↑
↑
Solenoid Valve - 4Way (V_4W)
IPM Cooler 1 O u tdoor Hea t E x ch an ger ( O HX )
Pressure Sensor - (IPMC1)
High (PS_H) HEAT
↑ FAN ON
↑
Solenoid Valve - IPM Cooler 2
Check Valve - Hot Gas bypass (V_HG) (IPMC2)
Discharge 1 (CV_D2)
↑
(CV_D1)
Oil Separator 1 (OS2) Solenoid Valve - ↑ O u tdoor Hea t E x ch an ger ( O HX )
↑ ↑
Switch - Thermistor -
(PW_H2)
High 1 EVI In (T_EI)
(PW_H1) Thermistor -
Discharge (T_D2) O u tdoor Hea t E x ch an ger ( O HX )
↑
(T_CT1)
Compressor 1 Pressure Sensor - Electronic
(COMP2) ↑ Expansion
(COMP1) Low (PS_L)
↑
↑
Valve -
EVI (E_EVI) O u tdoor Hea t E x ch an ger ( O HX )
↑
Thermistor -
Liquid pipe (T_L) OFF
Solenoid FAN OFF
Valve - (V_EVI2) Solenoid Valve - Ball Valve -
EVI 1(V_EVI1) Accumulator oil Return (V_AR) Liquid pipe (BV_L)
↑
• When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit
capacity. (Refer to the table for each model)
• Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Ex.) AM420✴XVA✴✴
ELCB ① AM420✴XVA✴✴
or
MCCB+ ② AM260✴XVA✴✴
ELB
③ AM100✴XVA✴✴
① ② ③
• This device is intended for the connection to a power supply system with a maximum permissible system
NOTE impedance shown in the table (on the left page) at the interface point (power service box) of the user’s supply.
• The user must ensure that this device is connected only to a power supply system which fulfills the requirement
above. If necessary, the user can ask the public power supply company for the system impedance at the interface
point.
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal
to Ssc(*2) at the interface point between the user’s supply and the public system. It is the responsibility of the
installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
Model Ssc[MVA]
AM080HXVFGH∗∗ 3.3
AM100HXVFGH∗∗ 4.7
AM120HXVFGH∗∗ 5.3
AM140HXVFGH∗∗ 7.7
AM160HXVFGH∗∗ 7.8
43
10. Installation
Electrical wiring work
44
10. Installation
Electrical wiring work
• Main power and the ground cable must be withdrawn through the knock-out hole on the bottom-right or right
side of the cabinet.
• Withdraw the communication cable from the designated knock-out hole on the bottom-right side of the front part.
• Install the power and communication cable using separate cable protection tube.
• Fix a protection tube to the knock-out hole on the outdoor unit by using a CD connector or bushing. Make sure to
use insulating bushing.
Protection
tube
45
10. Installation
Electrical wiring work
ELCB
or
MCCB+
ELB
Communication cable
Power·ground cable
46
10. Installation
Electrical wiring work
Main unit
Sub unit
Protection
tube
47
10. Installation
Space requirement for installation
f Space requirement was decided based on following conditions; Cooling mode, outdoor temperature of 35 °C.
Larger space is required if the outdoor temperature is higher than 35 °C or if the place is heated easily by quantity
of solar radiation.
f When you secure installation space, consider path for people and the direction of the wind.
f Secure installation space as shown in the below illustration, considering ventilation and the service space.
f If the installation space is narrow, installer or other worker may get injured during work and may also cause
problem to the product.
f If you install multiple number of outdoor units in one space, make sure to secure enough ventilation space if
there’s any walls around the product that may disturb the air flow. If enough ventilation space is not secured,
product may malfunction.
f You may install the outdoor units with 20mm of space between the product, but product’s performance may
decrease depending on the installation environment.
Single installation
(Unit : mm)
Over 100 (S2)
Over 300
Front side
Height of the wall is
Front side Over 100
unlimited
Over 500 (S1)
48
10. Installation
Space requirement for installation
Module installation
Over 300
(S2)
Over 300
Height of
Over 200
Over 100
the wall is
Over 100 unlimited
Over 500
Over 100
Front side Over 400 Front Over 400
(S1)
side
Over 100
Over 500
Over 600
Front side
Over 100
Over 100 Over 100
Over 500
Front side
<Case 3>
200
h2
Over200
Over
Grille/louver
Grille/louver
1500
Front side
500
Suction air
0
50
S1+h1/2 S2+h2/2 Ex.) Mechanical room ver
O
r5 00
Ove
49
10. Installation
Base construction and installation of the outdoor unit
f Construct the drainage ditch with reinforced concretes and make sure that water-proofing work is done.
f For smooth draining of defrost water, make sure to apply 1/50 slope.
f Construct a drainage around the outdoor unit to prevent the defrost water (from the outdoor unit) from
stagnating, overflowing or freezing near the installation space.
f When the outdoor unit is installed on the roof, check the strength and waterproof status of the roof.
(Unit : mm)
°
60
80
960
760
80 80
X
X’
100
150 100
50
100
<X-X’ SECTION>
°
°
60
60
80
80
80
80 80
80 80 80
50
10. Installation
Base construction and installation of the outdoor unit
(Unit : mm)
Classification DVM S Small Type DVM S Large A Type
A 940 1,350
B 740 1,150
f Anchor specification
m
Diameter of Anchor Sleeve Insert Fastening
Size
drill bit (a) length (b) length (c) depth torque
Ø 10 14 mm 75 mm 40 mm 50 mm 30 N·m
b
c
❇ Use the anchor bolts and nuts that is zinc plated or made of STS material.
a
Regular anchor bolts or nuts may get damaged by corrosion.
Block the part. (When withdrawing the pipe from the front side)
Liquid side pipe
XX
After installing the anti-vibration frame, untighten the fixing part on the top and bottom part of the frame.
51
10. Installation
Wind/snow prevention duct
f It is necessary to install a discharge guide duct(field supply) to direct exhaust from the fan horizontally, when it is
difficult to provide a minimum space of 2m between the air outlet and a nearby obstacle.
Discharged air
Grille/louver
Suction air
52
10. Installation
Refrigerant pipe installation
f The length of refrigerant pipe should be as short as possible and the height difference between an indoor and
outdoor unit should be minimized.
f Piping work must be done within allowable piping length, height difference, and the allowable length after
branching.
f The pressure of the R-410A is high. Use only certified refrigerant pipe and follow the installation method.
f After installing the pipes, calculate the total length of the pipe to check if additional refrigerant is needed. When
you need to charge the additional refrigerant, make sure to use R-410A refrigerant.
f Use clean refrigerant pipe and there shouldn’t be any harmful ion, oxide, dust, iron content or moisture inside
pipe.
f Use tools and accessories that fit on R-410A only.
53
10. Installation
Refrigerant pipe installation
f Install the refrigerant pipe according to main pipe size of each outdoor unit capacity.
f When the pipe length (including elbow) between an outdoor unit and the farthest indoor unit exceeds 90m, you
must increase the size of the pipe (main pipe) by one grade which connects between the outdoor unit to the first
branch joint.
H/P
33.6 kW 40.0 kW 61.6 kW Ex.) 135.2 kW
Pipe size (mm)
Capacity (kW) No.
Liquid pipe Gas pipe
(D) 33.6 kW (1) Ø 12.70 Ø 28.58
73.6 kW (2) Ø 19.05 Ø 34.92
(1) (2) (3) 135.2 kW (3) Ø 19.05 Ø 41.28
(C) (E)
(A)
(B)
54
10. Installation
Refrigerant pipe installation
Outdoor unit capacity (kW) *Maximum pipe length within 90m *Maximum pipe length over 90m
(Cooling) Liquid pipe (mm) gas pipe (mm) Liquid pipe (mm) gas pipe (mm)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1)
If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2)
If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3)
If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
55
10. Installation
Refrigerant pipe installation
Branch pipe length within 45m Branch pipe length between 45~90m
Indoor unit capacity (kW)
Liquid pipe (mm) Gas pipe (mm) Liquid pipe (mm) Gas pipe (mm)
Note1)
If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2)
If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3)
If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity.
56
10. Installation
Refrigerant pipe installation
(D)
Branch joint
f Branch joint between outdoor units (C)
Classification Outdoor unit capacity (kW) Model name of the branch joint
40.0 kW and below MXJ-YA2512M
40.1 kW ~ 45.0 kW MXJ-YA2812M
45.1 kW ~ 67.2 kW MXJ-YA2815M
Y-joint (D)
67.3 kW ~ 95.2 kW MXJ-YA3419M
95.3 kW ~ 135.2 kW MXJ-YA4119M
Over 135.2 kW MXJ-YA4422M
57
10. Installation
Refrigerant pipe installation
2) Distribution header
58
10. Installation
Refrigerant pipe installation
Additional refrigerant
H/P
46.4 kW
Ø12.70 (5 m)
4.5 kW
Ø12.70 (5 m)
Ø6.35 (5 m)
5.6 kW
Ø12.70 (5 m)
Ø6.35 (10 m)
5.6 kW Ø9.52 (10 m)
Ø6.35 (15 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
7.1 kW Ø6.35 (5 m)
7.1 kW
3.6 kW
7.1 kW
7.1 kW
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless
of the pipe size.
59
10. Installation
Refrigerant pipe installation
f If AHU kit is included among the indoor units, you must add 0.063kg of refrigerant for every 1kW of the AHU
capacity increase.
Note1)
In case the capacity conjunction of the Hydro Unit HT exceeds 50 % among the total indoor unit, please don’t put
the additional refrigerant.
60
10. Installation
Refrigerant pipe installation
61
10. Installation
Refrigerant pipe installation
• For pipes larger than Ø 19.05, drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be used. If a
annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure resistance and cause
CAUTION
personal injury.
62
10. Installation
Refrigerant pipe installation
200 ~
300 mm
When the piping length
1 m or less
between outdoor unit
and the branch joint Over 2 m Over 2 m
exceeds 2m, install a
vertical trap as show in
the figure.
63
10. Installation
Refrigerant pipe installation
Examples of refrigerant pipe installation
H/P
1. Using Y-joint
64
10. Installation
Refrigerant pipe installation
H/P
65
10. Installation
Refrigerant pipe installation
Outdoor unit 10 m or
Pipe length x ≤ 10 m, y ≤ 10 m, z ≤ 10 m
~ Outdoor less
unit (Module Equivalent 13 m or
installation) x ≤ 13 m, y ≤ 13 m, z ≤ 13 m
length less
66
10. Installation
Additional refrigerant
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 40m, but when the
indoor unit is located at lower level than outdoor unit, allowable height difference is 110m (If the height difference
is over 50m, decide if you need to install PDM kit) Model name of the PDM kit: MXD-A38K2A, MXD-A12K2A
It must be installed to the high-pressure pipe of the outdoor unit.
• The appropriate PDM kit corresponding to the capacity of the outdoor unit must be installed.
• In case of the combination of models higher than 24HP, PDM KIT must be installed to the high-pressure pipe of
each outdoor unit.
Ex) In case of 26HP, 2 PDM KIT units of MXD-A38K2A (10HP) and MXD-A12K2A (16HP) must be installed.
• Make sure to install after checking the appropriate model, confirming the PDM KIT specifications(pipe diameter,
capillary tube length).
KIT model name MXD-A38K2A MXD-A12K2A MXD-A58K2A
SET application model name AM080✴✴~120✴✴ AM140✴✴~160✴✴ AM180✴✴~240✴✴
67
11. Accessory
Controller
Wireless Remote
AR-KH00E 360 CST Only DVM, CAC
Controller
Wired Remote
MWR-WE11N DVM, CAC
Controller
Wired Remote
Controller MWR-SH00N DVM, CAC
- Simple Type
Wired Remote
Controller
MWR-SH10N DVM, CAC
- Touch Simple
Type
Wired Remote
MWR-WW00N EHS Only EHS
Controller
Master controller +
Zone Controller MWR-ZS00N DVM, CAC
Damper controller
68
11. Accessory
Controller
Touch Centralized
MCM-A300N DVM, CAC
Controller
ERV Interface
MIM-N10 DVM, CAC
Module
Lonworks
MIM-B18BN DVM, CAC
Gateway
External Contact
MIM-B14 DVM, CAC
Interface Module
Gate Way
MTFC (Multi
Tenant Function MCM-C210N DVM
Controller)
SIM (Signal
MIM-B12N DVM, CAC
Interface Module)
PIM (Pulse
MIM-B16N DVM, CAC
Interface Module)
69
11. Accessory
Controller
Installation /Test
S-Converter MIM-C02N DVM, CAC
run Solution
External Room
MRW-TA DVM, CAC
Sensor
Operation Mode
MCM-C200 DVM
Selection Switch
Others
FCU Interface
MIM-F10N CHILLER Only CHILLER
Module
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
70
11. Accessory
Controller & Control Accessory Compatibility
NASA Non-NASA
Item Remark
(DVM S) (DVM +3/+4)
Wireless Remote Controller MR-EH00 MR-EH00 DVM, CAC
Wireless Remote Controller AR-KH00E AR-KH00E DVM, CAC (360 CST)
Wired Remote Controller MWR-WE11N MWR-WE10 DVM, CAC
Wired Remote Controller
MWR-SH00N MWR-SH00 DVM, CAC
- Simple Type
Wired Remote Controller
MWR-SH10N - DVM, CAC
Individual - Touch Simple Type
Control System
ERV Wired Remote Controller MWR-VH12N - DVM, CAC (ERV)
Wired Remote Controller MWR-WW00N MWR-WW00 EHS
Receiver KIT MRK-A10N - DVM, CAC
Zone Controller MWR-ZS00N MWR-ZS00 DVM, CAC
Zone Controller MWR-ZS10N MWR-ZS10 DVM, CAC
Zone Controller MRW-TS MRW-TS DVM, CAC
Onoff Controller MCM-A202DN MCM-A202D DVM, CAC
Touch Centralized Controller MCM-A300N - DVM, CAC
Centralized
WIFI KIT MIM-H03N MIM-H03 DVM, CAC
Control System
Interface Module MIM-N01 MIM-N01 DVM, CAC
ERV Interface Module MIM-N10 MIM-N10 DVM, CAC
Integrated DMS2.5 MIM-D01AN MIM-D00A DVM, CAC
management
System S-NET3 MST-P3P MST-P3P DVM, CAC
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
71
11. Accessory
Piping
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
72
11. Accessory
Indoor unit
Motion detect
MCR-SMA 4Way Cassette S (600x600)
Sensor
73
11. Accessory
Indoor unit
External room
MRW-TA Casssette, Wall-mount, Ceiling, Duct, Console
sensor
NOTE
• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.Samsung.com site.
74
11. Accessory
Indoor unit's Accessory Compatibility
OAP
Floor Standing
1way MSP Duct
Duct
Mini 4way
Slim duct
B-Ceiling
HSP Duct
ERV Plus
Big Duct
Console
Ceiling
Duct-S
4way
2way
AHU
RAC
PAC
360
Product Model Remark
8,10HP
MSP-0
MSP-S
MSP-2
MSP-1
JSF-0
JSF-2
JSF-1
5HP
PC4NUDMAN Ceiling O
PC4NBDMAN Ceiling (Black) O
PC4NUNMAN Open O
PC4NBNMAN Open (Black) O
PC4NUSKAN Waffle O
PC4NBSKAN Waffle (Black) O
PC4NUSKEN Classic O
Panel PC4SUSMAN Waffle O
PC4SUSMEN Classic O
PC1NUSMAN Stripe O
PC1NUPMAN Z-Slide O
PC1MWSKAN O
PC1NWSMAN Fluid O
PC1BWSMAN O
PC2NUSMEN Stripe O
MDP-N047SNC0D - O
MDP-N047SNC1D - O O
MDP-M075SGU1D - O O
MDP-M075SGU2D - O
DRAIN
PUMP MDP-M075SGU3D - O
MDP-E075SEE3D - O
External, All
MDP-G075SP O O
Capacities
MDP-G075SQ Internal O O
S-Plasma MSD-CAN1 - O O
Ion KIT MSD-EAN1 - O
Motion -
detect MCR-SMA O
Sensor
ERV CO2 -
MOS-C1 O
Sensor
MEV-E**SA 1 Indoor O
EEV KITS
MXD-E**K***A 2,3 Indoor O
6 ports,
MCU-S6NEK2N O O O O O O O O O O O O O O O O O O O O O O
max 61.6kW
4 ports,
MCU-S4NEK3N O O O O O O O O O O O O O O O O O O O O O O
max 61.6kW
MCU-KIT
2 ports,
MCU-S2NEK2N O O O O O O O O O O O O O O O O O O O O O O
max 32.0kW
1 port,
MCU-S1NEK1N O O O O O O O O O O O O O O O O O O O O O O
max 16.0kW
MXD-K025AN only for 2.5Hp's AHU O
MXD-K050AN only for 5Hp's AHU O
MXD-K075AN only for 7.5Hp's AHU O
AHU-KIT
MXD-K100AN only for 10Hp's AHU O
only for 10~40Hp's
MCM-D201N O
AHU
NOTE
• In case you want to know more information the accessories, please refer to the control and accessories TDB on
pvi.samsung.com site
75
2017. 09
Ver.1.31
Samsung Electronics Co., LTD.
B2B PM / SE
Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, http://btsp.samsunggsbn.com Email : airconditioner@samsung.com
Images and data in this book may subject to change without prior notice.