Professional Documents
Culture Documents
NT 3036 Air Conditioning Systems
NT 3036 Air Conditioning Systems
NT 3036 Air Conditioning Systems
3
AIR CONDITIONING SYSTEMS
3.1 Introduction
Air conditioning systems may be classified according to the types of heating and cooling
media employed to provide the final heating and cooling effect within the space cooling
media include chilled water, brine and direct expansion refrigerants. Heating media
include steam, hot water, electricity and gas.
All-air systems
Air-water systems
Packaged unitary systems
These comprise a central air handling plant with distribution ductwork connected to the
various spaces served. Air velocity within the duct can be low, medium, and high
depending on the application, selection of the system and space within the building.
These systems may be classified as:-
H Kabbara© 1
NT 3036 Air conditioning systems
All-air systems from a very basic type of air conditioning with central plant, which is
scheduled to internal/external temperatures, controlling heating and cooling and
distributing air via grilles and diffusers. In all-air systems, return air is sometimes
extracted through light fittings to exploit the heat generated. This type of basic system
can only be used where the load is constant. This system may employ terminal reheat
units at either the perimeter of the building or inside it to cater for winter load, as shown
in figure 3.1 below.
RETURN
FAN
Exhaust
air
COOLING
SUPPLY
FILTER COIL HUMIDIFIER
FAN
Fresh
air
CONSTANT VOLUME BOX
DIFFUSER
Return
Supply
H Kabbara© 2
NT 3036 Air conditioning systems
This system supplies air from a central plant which may be used as either heating or
cooling source. The conditioned air is distributed via medium or high velocity ductwork
located within a suspended ceiling void. The amount of air distributed into an individual
room or zone is controlled by local thermostats, which promote a degree of flexibility as
shown in figure 3.2 below.
EXHAUST AIR
EXTERIOR ZONE
RETURN AIR
A A
STATIC PRESSURE REGULATOR
T T
FRESH AIR
T T
INTERIOR ZONE
Under partial load conditions the VAV system will allow a reduction in supply air
volume to compensate for reduced cooling load and take maximum advantage of load
diversities. A typical application of the VAV system would be laboratory building where
equipment loads are highly variable and where intermittent operation of fume extract
hoods cause variable make-up air requirements.
The main advantages of VAV systems are the savings in operating costs possible due to
reduction in fan horsepower under partial load, and reduction in energy losses since
H Kabbara© 3
NT 3036 Air conditioning systems
mixing and reheat losses are minimised. Elimination of excessive air movement in winter
may also offer advantages in some applications.
Advantages which may be overcome by proper design are unstable system operation
caused by variations in duct static pressure due to flow changes, stratification or draughts
from room outlets due to flow and/or temperature changes and acoustical problems due to
noise generated as air flow is throttled. Another advantage is air dumping from a diffuser
if it is required to turn down less than 40% of air. To overcome this problem the VAV
terminal unit is supplemented with a fan to boost the air flow from the diffuser by using
recovered air from the room drawn into the ceiling void to balance the variations in
primary supply air. A schematic diagram of a typical VAV fan assisted system is sown in
figure 3.3 below.
FILTER COOLER
SPACE
Variable air volume systems use terminal boxes called VAV boxes. Figures 3.4 & 3.5
show a diagram of a VAV fan assisted terminal box. The diagram includes the
following:-
H Kabbara© 4
NT 3036 Air conditioning systems
6 5
4 3 2 1
SUPPLY AIR
FRESH AIR
ROOM RETURN AIR
FLOOR SLAB
FLEXIBLE DUCTING
H Kabbara© 5
NT 3036 Air conditioning systems
This is an all-air system which conditions air in a central plant and distributes it, usually
at high velocity to the conditioned spaces through two parallel ducts. One duct conveys
cold air and the other hot air to a room unit which mixes the air, under instructions from a
room thermostat, in the proportions required to maintain the necessary space temperature.
See figure 3.6 below.
HOT DUCT
BALANCING
PRESSUR-REDUCING
DAMPER / ACOUSTIC
BAFFLE
CONSTANT
VOLUME ROOM SENSOR
REGULATOR
COLD DUCT
The dual duct system is particularly suited to applications with a highly variable sensible
load where temperature control is required for individual spaces or zones. This covers
multi-storey, multi-room applications, such as offices, hospitals, blocks of flats, hotels
and large laboratories. The dual duct system is generally an economic propositions for
buildings with less than about 60% glass area; above this air-water systems may be more
competitive. The best system arrangement is shown in figure 3.7 below.
H Kabbara© 6
NT 3036 Air conditioning systems
HEATER
SPACE
SPACE
FILTER +
SUPPLY FAN
COOLER MB MB
FRESH AIR
RETURN AIR
H Kabbara© 7
NT 3036 Air conditioning systems
This system employs one or more central air handling units which are usually of the
packaged type as shown in figure 3.8 below.
MOTORIZED
DAMPERS MIXED AIR TO ZONE 1
FOR ZONE 1
OUTSIDE AIR
HOT
DECK
COLD
DECK
FILTER SECTION MOTORIZED MIXED AIR TO ZONE 2
DAMPERS
FOR ZONE 2
FAN SECTION
HEATER
COOLER
The heating and cooling coils are located in parallel, downstream of the supply fan, and
followed by a set of mixing dampers for each control zone to provide constant volume
variable temperature conditions as required. This system mixes, at the central plant, the
required proportions of cold and hot air required by each conditioned zone, and a separate
single duct for each zone distributes the mixed air to that particular zone. Individual zone
thermostats control the appropriate zone mixing dampers at the unit. A typical plant
arrangement is shown in figure 3.9 below.
H Kabbara© 8
NT 3036 Air conditioning systems
HEATER
RETURN AIR
FILTER +
S UPPLY FAN
COOLER
ZONE 1
FRES H AIR
RETURN AIR
ZONE 2
TO OTHER ZONES
H Kabbara© 9
NT 3036 Air conditioning systems
These systems comprise a central air handling plant to provide primary fresh air (100%)
with dew point control of heating and/or cooling plus humidifier if required to the space
to be conditioned. The primary fresh air can be supplied to local room units. These units
can be either induction units or fan coil units.
This system uses a main central air handling unit to provide 100% fresh air. An induction
unit uses the power in a high velocity primary jet to induce room air over a coil and hence
set up adequate air circulation within the conditioned space; i.e. it uses the principle of
entraining as employed by well designed supply air terminal but also acts as terminal re-
cooler or re-heater as required. See figure 3.10 below.
FRESH AIR
SUPPLY FAN SECONDARY
HEATER
FROST COIL ROOM AIR
The unit causes secondary air to be recirculated by the primary air passing through a
series of nozzles, then this passes over either heating or cooling coils as shown in figure
3.10. This means that primary air and distribution ductwork can be very much smaller
than all-air systems in most cases handling only the fresh air requirements of the
occupants. Induction units are rarely used to dehumidify room air due to the
H Kabbara© 10
NT 3036 Air conditioning systems
inconvenience of condensate disposal. Primary air is thus expected to deal with all latent
loads. These units tend to be noisy due to nozzle pressure.
+/-
ROOM
S ECONDARY AIR
NOZZLES
WATER RETURN
The maintenance of induction systems is rather more intensive than all-air systems with
regular cleaning of the lint screens, coils and nozzles being necessary to avoid reductions
in performance. This should normally be done quarterly. Routine maintenance is also
required for the automatic controls. Control over the system depends on the type of water
distribution system installed. It can be obtained either via the air flow through the unit
using thermostatically controlled dampers or valve control of the water flow.
H Kabbara© 11
NT 3036 Air conditioning systems
This system is generally used for perimeter areas of multi-room, multi-storey buildings
but also can be arranged to cater for interior zones. A fan coil system is in many ways
similar to an induction unit system, the basic difference being the substitution of a small
fan in the unit or may be a pair of centrifugal fans to recirculate room air across a water
coil in place of induction nozzles. the whole assembly is fitted in a sheet steel casing and
is usually located beneath a window to blow air upwards over the glass. Sometimes the
fan coil units are fixed above suspended ceilings in a horizontal position and supply air
across the ceiling. With these arrangements i.e. horizontal and vertical, good flexibility in
design and layout can be achieved. See figure 3.11 below.
6 9
1 1
2 5
4 2
3 3
FLOOR
8
WALL
FLOOR
H Kabbara© 12
NT 3036 Air conditioning systems
Fresh primary air can be obtained via different sources depending on the complexity and
layout of the building. These sources may be:-
Inward infiltration
A ventilation opening in the external wall behind the fan coil unit.
A separate mechanical ventilation system.
Conditioned primary low velocity air ducted to the unit from a central air handling
unit.
These arrangements are shown in figure 3.12 below.
3 3
2
2
2
4 4
1. 100% Reciculated air
1. Ventilation air theough wall aperture
2. Infiltration around window and door
2. Recirculated air
3. Power exhaust
3. Power exhaust 1
2 4. Conditioned air from fan coil unit 2
4. Conditioned air from fan coil unit
1
H Kabbara© 13
NT 3036 Air conditioning systems
1 1
Perimeter Corridor Perimeter
Space Space
Interior space Corridor Perimeter space
3 3
Ventilation from interior space system Ventilation from seperate duct system
Ventilation by primary air duct Ventilation by primary air duct at high level
Water distribution to the fan coil unit can be two-pipe or four-pipe. With a two-pipe
system there is a heating problem in the UK. A changeover system might be considered
but this is unsatisfactory in the British climate. Individual electric re-heat would be a
possibility if the electrical tariff supply was cheap enough or if the heating requirement
was very small.
Another possibility might be to warm the auxiliary ducted air to a temperature high
enough to offset the heat loss. This is seldom a success; the accuracy of air balancing and
the temperature drop because of duct heat loss make uniform, balanced heating
impossible. The solution is to use a four-pipe fan coil system.
Most units today offer the choice of three fan speeds, giving different levels of noise
output and a manual choice of unit capacity.
H Kabbara© 14
NT 3036 Air conditioning systems
Four-pipe fan coil systems have become popular and many installations in office blocks
fix them above suspended ceilings, the argument being that this arrangement uses less of
the floor area. A typical four-pipe fan coil system is shown in figures 3.13, 3.14 and 3.15.
STEAM
HUMIDIFIER
FILTER COOLING COIL
FRESH AIR
AIR CONDITIONED S PACE
SUPPLY FAN
HEATER
FROST COIL
CONDITIONED AIR
SECONDARY
ROOM AIR
CONDITIONED AIR
ROOM SENSOR
-
+
ROOM
CHILLED WATER FLOW
SECONDARY AIR
CHILLED WATER RETUR
PRIMARY AIR
HOT
WATER FLOW
HOT
WATER RETURN
H Kabbara© 15
NT 3036 Air conditioning systems
FLOOR SLAB
FLEXIBLE DUCTING
- +
ACCESS DOOR
H Kabbara© 16
NT 3036 Air conditioning systems
Heat pump systems are often used in narrow buildings having small floor areas and
where there are no specific requirements for serving central core areas.
The system is also called unitary room reversible heat pump (versatemp). the system
shown in figure 3.16 below represents a typical unitary heat pump system.
COOLING TOWER
T
TERMINAL HEAT RECOVERY UNITS (VERSATEMP)
BOILER PLANT
H Kabbara© 17
NT 3036 Air conditioning systems
The system employs room hermetic heat pump units, operating on a constant temperature
water circuit. The unit may either cool the space and reject the extracted heat to the water
circuit (refrigeration cycle) or warm the space by extracting heat from the water circuit
(heat pump cycle). See figure 3.17 below.
COMPRESSOR COMPRESSOR
ROOM COIL
ROOM COIL
OUT IN OUT IN
FIGURE 3.17 A Unitary Heat Pump Unit in Heating and Cooling Modes
In winter, when operating on the heat pump cycle, about one-third of the heating
requirements is met by power input to the compressor; the balance is obtained from a
boiler or other heat source.
In summer, on normal refrigeration cycle, excess heat is rejected to the cooling tower.
Operating economy is achieved in intermediate seasons by taking advantage of the out-
of-balance loads which occur (e.g. one zone in sun, other zones in shade; heat gains from
interior zones, heat losses from exterior zones etc.). The system permits heat to be
reclaimed from these sources and to be pumped via the water circuit to areas where a heat
requirement exists.
H Kabbara© 18
NT 3036 Air conditioning systems
In this system fresh air can be drawn in and discharged through the heat pump units via a
local fresh air intake. Fresh air can also be provided centrally via a centralised air plant
which filters air and tempers it to 10 oC all year round so that 'free' heating may be made
use of at units when available.
A packaged unit system means that this system has been pre-designed and engineered by
a manufacturer to specified standards incorporating a direct expansion vapour
compression refrigeration system. this system may be used to provide cooling only,
heating only or both. Packaged air conditioning is only concerned with 'comfort'
conditioning and, therefore, some latitude can be tolerated with various conditions. This
applies particularly to the question of relative humidity. The problem in comfort
conditioning is to limit the rise in relative humidity but it is not normally considered
necessary to install humidifiers to ensure a minimum relative humidity.
The operation of packaged air conditioning systems for comfort conditioning is generally
as follows:-
1. Air is drawn from the conditioned space into the equipment and mixed with
proportion of fresh air as required.
2. The mixed air passes through a filter which removes dirt and dust.
3. The air then passes through a coil which for cooling or for heating.
4. Where the system is to be used for heating as well as cooling, a heater battery or hot
water coil can be fitted to provide full heating in place of the coil above; or to provide
supplementary heating in conjunction with the coil above.
5. Finally the air passes through the fan and is returned to the conditioned space.
H Kabbara© 19
NT 3036 Air conditioning systems
Heater
Inside coil
Tray
Air supply fan
Filter
Compressor
Outside coil
Fan
H Kabbara© 20
NT 3036 Air conditioning systems
Inside coil
Tray
Filter
Compressor
Refrigerant pipes
Inside coil
Tray
H Kabbara© 21