DEC 2022 - EDG logsheet

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

SM240 COAL-FIRED POWER PLANT

SARANGANI ENERGY CORPORATION


Date: 6/4/2022
LOGSHEET FOR BSEDG TEST RUN
After 5
Description KKS No. Unit minutes
After 10 minutes After 15 minutes

BSEDG UNIT # 1
Generator Real Power 8 kW 1217 1278 1134
Generator Reactive Power 8 kVAr 615 596 613
Generator Apparent Power 8 kVA 1357 1448 1321
Generator Power Factor 4 0.9 0.9 0.9
Generator Frequency 4 Hz 59.9 59.97 59
Total Generation 0 kWh 1338836 1338898 1339003
Runing Hours 0 Hrs 1056 1056 1056
Generator Current L1 6 A 128 134 134
Generator Current L2 6 A 126 133 137
Generator Current L3 6 A 130 137 136
Generator Voltage - L12 10 V 6021 6017 6010
Generator Voltage - L23 10 V 6026 6024 6019
Generator Voltage - L31 10 V 6007 6001 5999
Exhaust Gas Temperature ᵒC 370 374 378
Generator Winding Temp- L1 ᵒC 44.4 45.9 47.6
Generator Winding Temp- L2 ᵒC 44.8 46.4 48.1
Generator Winding Temp- L3 ᵒC 45.2 46.6 48.4
Generator Bearing Temp. DE ᵒC 35 35.6 36.5
Generator Bearing Temp. NDE ᵒC 38.1 37.7 37.4
Coolant Level % 100 100 100
Lube oil Level % - - -
Lube Oil Pressure kPa 345 345 345
Lube Oil Temperature ᵒC 90 90 90
Speed rpm 1800 1800 1800
Water Temperature ᵒC 75 75 75
Battery Voltage V 28 28 28
Fuel Oil Tank No. 1 Level 0BDY01CL001X % 69.9 69.9 69.5
Fuel Oil Tank No. 2 Level 0BDY03CL001X % 71.8 71.8 71.8
REMARKS:
Note: Please refer to provided test run procedure available at BSEDG control room
OPERATOR: SUPERVISOR:
KAP RAI
Name and Signature Name and Signature

SM240 COAL-FIRED POWER PLANT


SARANGANI ENERGY CORPORATION
Date: 6/4/2022
LOGSHEET FOR BSEDG TEST RUN
After 5
Description KKS No. Unit minutes
After 10 minutes After 15 minutes

BSEDG UNIT # 2
Generator Real Power 8 kW 1184 1195 1253
Generator Reactive Power 8 kVAr 606 625 604
Generator Apparent Power 8 kVA 1310 1406 1363
Generator Power Factor 4 0.9 0.9 0.9
Generator Frequency 4 Hz 59.94 59.92 60
Total Generation 0 kWh 929784 929842 929946
Runing Hours 0 Hrs 760 760 760
Generator Current L1 6 A 130 133 131
Generator Current L2 6 A 138 139 130
Generator Current L3 6 A 131 135 131
Generator Voltage - L12 10 V 6022 6017 6013
Generator Voltage - L23 10 V 6029 6026 6022
Generator Voltage - L31 10 V 6009 6007 6004
Exhaust Gas Temperature ᵒC 298 324 322
Generator Winding Temp- L1 ᵒC 42.4 46.6 46.2
Generator Winding Temp- L2 ᵒC 42.4 46.8 46.2
Generator Winding Temp- L3 ᵒC 44.4 49.1 48.7
Generator Bearing Temp. DE ᵒC 34.3 36.7 35.7
Generator Bearing Temp. NDE ᵒC 39.3 37.8 38.7
Coolant Level % 100 100 100
Lube oil Level % - - -
Lube Oil Pressure kPa 340 345 345
Lube Oil Temperature ᵒC 85 85 85
Speed rpm 1800 1800 1800
Water Temperature ᵒC 85 85 85
Battery Voltage V 28 28 28
Fuel Oil Tank No. 1 Level 0BDY01CL001X % 69.9 69.9 69.5
Fuel Oil Tank No. 2 Level 0BDY03CL001X % 71.8 71.8 71.8
REMARKS:
Note: Please refer to provided test run procedure available at BSEDG control room
OPERATOR: SUPERVISOR:
KAP RAI
Name and Signature Name and Signature

SM240 COAL-FIRED POWER PLANT


SARANGANI ENERGY CORPORATION
Date: 6/4/2022
LOGSHEET FOR BSEDG TEST RUN
After 5
Description KKS No. Unit minutes
After 10 minutes After 15 minutes
BSEDG UNIT # 3
Generator Real Power 8 kW 1246 1217 1315
Generator Reactive Power 8 kVAr 592 609 600
Generator Apparent Power 8 kVA 1432 1319 1442
Generator Power Factor 4 0.9 0.9 0.9
Generator Frequency 4 Hz 59.89 60.08 59.99
Total Generation 0 kWh 936222 936278 936399
Runing Hours 0 Hrs 752 752 752
Generator Current L1 6 A 131 126 132
Generator Current L2 6 A 130 125 32
Generator Current L3 6 A 133 128 135
Generator Voltage - L12 10 V 6014 6014 6018
Generator Voltage - L23 10 V 6022 6023 6025
Generator Voltage - L31 10 V 5998 6001 6002
Exhaust Gas Temperature ᵒC 356 360 364
Generator Winding Temp- L1 ᵒC 45 46 47.8
Generator Winding Temp- L2 ᵒC 44.4 45.6 47.7
Generator Winding Temp- L3 ᵒC 45.9 47 48.7
Generator Bearing Temp. DE ᵒC 39.7 41.9 51
Generator Bearing Temp. NDE ᵒC 43.9 43.7 42.9
Coolant Level % 100 100 100
Lube oil Level % - - -
Lube Oil Pressure kPa 340 340 340
Lube Oil Temperature ᵒC 85 85 85
Speed rpm 1800 1800 1800
Water Temperature ᵒC 80 80 80
Battery Voltage V 27 27 27
Fuel Oil Tank No. 1 Level 0BDY01CL001X % 69.5 69.5 69.8
Fuel Oil Tank No. 2 Level 0BDY03CL001X % 71.8 71.8 71.7
REMARKS:
Note: Please refer to provided test run procedure available at BSEDG control room
OPERATOR: SUPERVISOR:
KAP RAI
Name and Signature Name and Signature

SM240 COAL-FIRED POWER PLANT


SARANGANI ENERGY CORPORATION
Date: 6/4/2022
LOGSHEET FOR BSEDG TEST RUN
After 5
Description KKS No. Unit minutes
After 10 minutes After 15 minutes

BSEDG UNIT # 4
Generator Real Power 8 kW 1269 1262 1233
Generator Reactive Power 8 kVAr 607 610 616
Generator Apparent Power 8 kVA 1394 1354 1350
Generator Power Factor 4 0.9 0.9 0.9
Generator Frequency 4 Hz 59.91 59.97 59.98
Total Generation 0 kWh 1209042 1209088 1208882
Runing Hours 0 Hrs 910 910 910
Generator Current L1 6 A 140 133 139
Generator Current L2 6 A 139 132 139
Generator Current L3 6 A 135 135 133
Generator Voltage - L12 10 V 6016 6017 6019
Generator Voltage - L23 10 V 6025 6029 6031
Generator Voltage - L31 10 V 6012 6011 6010
Exhaust Gas Temperature ᵒC 368 305 373
Generator Winding Temp- L1 ᵒC 44.1 39.1 47.5
Generator Winding Temp- L2 ᵒC 44.2 39.2 47.6
Generator Winding Temp- L3 ᵒC 43.7 38.2 47
Generator Bearing Temp. DE ᵒC 34.6 33.3 36.3
Generator Bearing Temp. NDE ᵒC 60.9 65.4 59.5
Coolant Level % 90 90 90
Lube oil Level % 95 95 95
Lube Oil Pressure kPa 343 343 343
Lube Oil Temperature ᵒC 80 80 80
Speed rpm 1800 1800 1800
Water Temperature ᵒC 78 78 78
Battery Voltage V 28 28 28
Fuel Oil Tank No. 1 Level 0BDY01CL001X % 69.5 69.5 69.8
Fuel Oil Tank No. 2 Level 0BDY03CL001X % 71.8 71.8 71.7
REMARKS:
Note: Please refer to provided test run procedure available at BSEDG control room
OPERATOR: SUPERVISOR:
KAP RAI
Name and Signature Name and Signature