How to troubleshoot a control valve and How to do the preventive maintenance of the control
valve

How to troubleshoot a control valve and How


to do the preventive maintenance of the
control valve
Control Valve / 7 minutes of reading

How to do the control valve inspection and maintenance


The service life of a control valve could be increased by doing proper maintenance. The internal
parts of the control valves must be checked, before doing any inspection the valves must be
dismantled. The major parts of the control valve are the disc and seat. The leakage chances of
the valves would be high if there is any damage to these parts. These parts of the valve could
get damaged because of corrosion and erosion. The valves must be inspected to know if the
components are functioning properly in their operating conditions. In order to keep the valve in
a better operating condition sometimes certain adjustment to the packing or the operator is
needed. While doing the inspection of control valves the stuffing box and flanges must be
checked so that we could know if there is any leak in the packing or in the gasket. Periodic

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 1/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

maintenance could make the valve perform better if we use lubricants for the body and seat
rings.

Why do we need to do the maintenance of the control valve


The efficiency of the control valve could be improved
The repair of the valve can be done if we find out any damage during the inspection
The cost can be reduced
Periodic maintenance is done by without disassembling the valve, only if there is a loss of
operating efficiency valves are taken out of service
Before doing any maintenance we must check the manufacturer’s instructions
In certain cases, the parts of the control valves must be replaced instead of refurbishing
it, and it could be known by the inspection of the control valve.
By doing the maintenance the parts of the valves could be free from dirt.

How to do the inspection before starting the operation of


the control valve
Check whether the flow direction of the control valve is equal to the process fluid flow
direction
Diaphragms bolts and nuts must be checked
Check the bonnet clamp bolts and yoke clamp bolts
Check for any air leakage in the valve
Actuator spring and the gland packing must be checked

What are the testing methods of the control valve


Shell test
Backseat test
Low-pressure closure test

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 2/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

High-pressure closure test


Visual examination of casting

How to do the periodical inspection and maintenance of


the control valve
Air leak from the diaphragm must be checked
Check for any leak from flanges and bonnet
Yoke clamp must be tight and there should not be any air leak from the air piping of the
actuator
The stem connectors should be checked for a loose connection
The actuator stem and valve stem must be checked
Check for any vibrations from the control valve
Gland packing must be checked, and confirm there is no leak

How to do the actuator maintenance of the control valve


Before doing the maintenance of the actuator, it must be disassembled and the disassembly
must be done according to the manual. The disassembly and the reassembly of the actuator
must be done by an experienced person other-wise it would create many problems. After the
disassembly of the actuator, the parts must be cleaned so that we can remove or prevent rust
and corrosion. Grease must be provided to the cylinder for its smooth operation. The
diaphragm must be kept clean and we should check for any defects in the diaphragm. The
tightening of the diaphragm must be done according to the info provided by the manufacturer.
Check whether the stem seal is installed properly and proper lubricant must be provided to it.
The actuator stem must be checked so that we could know if there is any damage. If there is a
need for spring replacement in the actuator, then all the moving parts must be lubricated
before replacing the spring.

How to do the positioner maintenance of the control valve


While using an electronic positioner in the control valve we must check that if the control valve
makes a lot of vibration if so we must not use an electronic positioner for this type of control
valve. Electronic positioners should only be used in control valves that don’t make a lot of
vibrations. The important step is to mount the positioner into the control valve and this must be
done very carefully. The calibration and the operation are depended on how the positioner is
mounted if it is not mounted properly then it would cause a lot of problems. Check for any air
leaks from the positioner. Integral relays are the important part of the positioner if there is no
relay or didn’t get any replacement for the relay then the whole positioner must be changed.
While linking the positioner to the control valve it must be done properly without any wear or
tear. There must not be any wear in the linkage parts and the linkage binding must be properly
done.

How to select a control valve

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 3/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

It must be selected according to the operating pressure and temperature


Rate of flow and type of fluid
It must be selected according to the cost of installation and maintenance
It must be selected according to the viscosity and temperature of the fluid
According to the inlet pressure, flow capacity, and outlet pressure
Noise level
Pressure drop during normal conditions and pressure difference during shutoff

How to troubleshoot a control valve and what are the


preventive maintenance of the control valve
Check the day to day operation of the control valve and if there are any sudden changes in the
operating conditions then the chances of faults are high. By doing the visual inspection we can
detect the faults in control valves like if the fault is caused by dirt or something. In certain cases,
control valves are not able to achieve full closure and it could be because the valve disc and
seat could have some foreign materials or other products. So in order to prevent or remove
these faults, we must polish the seat and take preventive measures for corrosion. If there is cuts
or scratches in certain parts of the control valve like the disc, then it must be replaced

Valve stem leak – It can be caused by worn stem seals or because of the damaged stem.
So the valve stem must be removed or if it is a metal valve then stem packing nut can be
tightened.
Valve leakage past ball – it could be because of damaged stem or bore, so it can be
removed by installing repair kit or adjust the limit switches of the actuator
Body leak of the valve – It may be caused because of not tightening the body bolts or
due to the operating pressure. The proper solution for this fault could be checking the
bolt and the valve should be used for the applications that match its pressure ratings
another solution is replacing the valve or installing a repair kit
Excessive operating torque of the valve – it can be caused because of the over-tightening
of the valve bolts or stem nut. The solution for this fault could be the loosening of the
stem nut or valve bolts. Another solution will be cleaning or replacing the valve.

If the Valve fails to open or close, it could be because of diaphragm damage or stem binding.

Diaphragm damage

This problem can be removed by loosening the tubing connection in the bonnet which
would remove the residual pressure.
All diaphragm plates must be tightened
Remove the diaphragm
Spring replacement
Control tubing reinstallation

Stem binding

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 4/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

Tubing connection must be loosened so the residual pressure can be removed


Removal of the bonnet nuts
Check the stem for cuts and scratches and polish it if necessary
Reinstall the spool assembly

Preventive maintenance

Visual inspection is an important step for this, before installing the valve check the valve for any
damages in the piping, fittings. The valve must be cleaned so the foreign materials in the valve
can be removed and it would affect the valve operation. The valve must be installed in the line
based on the inlet flange arrow. Valve lubrication must be done. Motor operated valve must be
operated electrically.

How to prevent cavitation in control valves

In some of the control valves, the cavitation is reduced by increasing the distance between the
trim parts and implosion of vapor bubbles, and this is done by providing a flow aiding to close
direction. In certain anti-cavitation valves, the chances of the cavitation are reduced by
dropping the pressure by steps.

To get more info about the control valve check the following link

Air valve
Float valve
Control valve positioner
Control valve actuator
Pressure control valve
Safety valve
Solenoid valve
Hydraulic valve
Pressure relief valve
Pneumatic valve
Shuttle valve
Foot valve
Check valve
Spool valve
Piston valve
Pinch valve
Control valve calibration
Plug valve
Ball valve
Gate valve
Butterfly valve
Globe valve
Needle valve

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 5/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

Diaphragm valve
Control valve installation
Share your love

Facebook Twitter Pinterest Linkedin

About The Author

Ashlin
post-graduate in Electronics & communication.

← Previous Post Next Post →

Related Posts

Working of control valve Control Valve positioners

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 6/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

Basics of Needle valves Basics of Check valves

Basic parts of control valves Different types of control valve


actuators

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 7/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

How to select a control valve Control valve characteristics


Actuator ?

Self-regulated valve flow control

100+ Electrical Calculators

Categories

Select Category

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 8/9
24/02/2024, 23:44 How to troubleshoot a control valve and How to do the preventive maintenance of the control valve | Instrumentation and Co…

Recent Posts
6 Factors to Consider When Choosing an Oxygen Analyzer for your Application

Troubleshooting of Oxygen Analyzer : Paramagnetic Type

Collection of Preventive Maintenance (PM) Procedures for Instrumentation and Control Systems

Step by Step Preventive Maintenance Procedure for O2 Analyzers : Paramagnetic Type

4 – 20 mA to 1 – 5V, 3 -15 Psi and 0.2 – 1.0 Bar Signal Conversion Calculator

Calibration Instrumentation Instrumentation

Procedures Tools Symbols


Maintenance Electrical Instrumentation

Procedures Calculators MCQ


Drawings and How to Read Electrical Blog

Documents Diagrams? Automation


Calibration PLC Learning Series Community
Template

Copyright © 2024 Instrumentation and Control Engineering | Powered by Infohe.com

https://automationforum.co/how-to-troubleshoot-a-control-valve-and-how-to-do-the-preventive-maintenance-of-the-control-valve/ 9/9

You might also like