Professional Documents
Culture Documents
Electronic-Appendix_PBUC-Test-Networks
Electronic-Appendix_PBUC-Test-Networks
The IEEE 6-bus test system contains 6 buses (substations), 7 transmission lines, and 3 conventional generating units with a total capacity of 360 MW.
Network and generator configurations and data for the IEEE 6-bus test system are described as follows [1].
Unit 𝑃𝑃�𝑔𝑔 𝑃𝑃𝑔𝑔 𝑎𝑎𝑔𝑔 𝑏𝑏𝑔𝑔 𝑐𝑐𝑔𝑔 𝐶𝐶𝑔𝑔𝑢𝑢 𝐶𝐶𝑔𝑔𝑑𝑑 ℎ𝑔𝑔+ ℎ𝑔𝑔− ���
𝑆𝑆𝑔𝑔 𝑆𝑆𝑔𝑔 𝑀𝑀𝑔𝑔+ 𝑀𝑀𝑔𝑔−
(MW) (MW) ($/MW2) ($/MW) ($) ($/MW) ($/MW) (MW) (MW) (h) (h) (MW/min) (MW)
1 220 100 0.0004 13.5 177 100 50 55 55 4 4 60 0
2 100 10 0.001 40 130 200 100 50 50 3 2 60 30
3 40 10 0.005 17.7 137 0 0 20 20 1 1 60 30
Table II. Hourly Load Demand for IEEE 6-Bus Test System (Base Values)
The IEEE 24-bus test system contains 24 buses (substations), 38 transmission lines, and 12 conventional generating units with a total capacity of
3375 MW. Network and generator configurations and data for the IEEE 24-bus test system are described as follows [2], [5].
Unit 𝑃𝑃�𝑔𝑔 𝑃𝑃𝑔𝑔 𝑎𝑎𝑔𝑔 𝑏𝑏𝑔𝑔 𝑐𝑐𝑔𝑔 𝐶𝐶𝑔𝑔𝑢𝑢 𝐶𝐶𝑔𝑔𝑑𝑑 ℎ𝑔𝑔+ ℎ𝑔𝑔− ���
𝑆𝑆𝑔𝑔 𝑆𝑆𝑔𝑔 𝑀𝑀𝑔𝑔+ 𝑀𝑀𝑔𝑔−
(MW) (MW) ($/MW2) ($/MW) ($) ($/MW) ($/MW) (MW) (MW) (h) (h) (MW/min) (MW)
1 152 30.4 0.0128 13.32 108 1430.4 715.2 152 152 8 4 40 20
2 152 30.4 0.0697 13.32 108 1430.4 715.2 152 152 8 4 40 20
3 350 75 0.003 20.7 118 1725 862.5 350 350 8 8 70 35
4 591 206.85 0.0109 20.93 94 3056.7 1528.35 240 240 12 10 180 90
5 60 12 0.0283 26.11 84 437 218.5 60 60 4 2 60 30
6 155 54.25 0.0098 10.52 118 312 156 155 155 8 8 30 15
7 155 54.25 0.0109 10.52 118 312 156 155 155 8 8 30 15
8 400 100 0.0283 6.02 177 0 0 280 280 1 1 0 0
9 400 100 0.0283 5.47 177 0 0 280 280 1 1 0 0
10 300 60 0.0098 2 177 0 0 300 300 0 0 0 0
11 310 108.5 0.0128 10.52 118 624 312 180 180 8 8 60 30
12 350 140 0.0128 10.89 118 2298 1149 240 240 8 8 40 20
Table V. Hourly Load Demand for IEEE 24-Bus Test System (Base Values)
Table VI. Day-Ahead Price of Energy products for IEEE 24-Bus Test System (Base Values)
The IEEE 39-bus test system contains 39 buses (substations), 46 transmission lines, 10 conventional generating units with a total capacity of 1990
MW. Network and generator configurations and data for the IEEE 39-bus test system are described as follows [3], [5].
Unit 𝑃𝑃�𝑔𝑔 𝑃𝑃𝑔𝑔 𝑎𝑎𝑔𝑔 𝑏𝑏𝑔𝑔 𝑐𝑐𝑔𝑔 𝐶𝐶𝑔𝑔𝑢𝑢 𝐶𝐶𝑔𝑔𝑑𝑑 ℎ𝑔𝑔+ ℎ𝑔𝑔− ���
𝑆𝑆𝑔𝑔 𝑆𝑆𝑔𝑔 𝑀𝑀𝑔𝑔+ 𝑀𝑀𝑔𝑔−
(MW) (MW) ($/MW2) ($/MW) ($) ($/MW) ($/MW) (MW) (MW) (h) (h) (MW/min) (MW)
1 200 80 0.00048 12.1 82 42.6 42.6 90 90 3 2 70 35
2 320 120 0.00031 12.6 49 50.6 50.6 130 130 4 2 70 35
3 150 50 0.002 13.2 100 57.1 57.1 70 70 3 2 40 20
4 520 250 0.00211 13.9 105 47.1 47.1 250 250 5 3 40 24
5 280 80 0.00398 13.5 72 56.6 56.6 110 110 4 2 48 10
6 150 50 0.00712 15.4 29 141.5 141.5 60 60 3 2 20 10
7 120 30 0.00079 14 32 113.5 113.5 50 50 3 2 20 10
8 110 30 0.00413 13.5 40 42.6 42.6 45 45 3 2 0 0
9 80 20 0.00222 15 25 50.6 50.6 35 35 0 0 0 0
10 60 20 0.00173 14.3 15 57.1 57.1 30 30 0 0 0 0
Table VIII. Hourly Load Demand for IEEE 39-Bus Test System (Base Values)
Table IX. Day-Ahead Price of Energy products for IEEE 39-Bus Test System (Base Values)
The IEEE 118-bus test system contains 118 buses (substations), 186 transmission lines, 19 conventional generating units with a total capacity of 6859
MW. Network and generator configirations and data for the IEEE 118-bus test system are described as follows [4]-[6].
Unit 𝑃𝑃�𝑔𝑔 𝑃𝑃𝑔𝑔 𝑎𝑎𝑔𝑔 𝑏𝑏𝑔𝑔 𝑐𝑐𝑔𝑔 𝐶𝐶𝑔𝑔𝑢𝑢 𝐶𝐶𝑔𝑔𝑑𝑑 ℎ𝑔𝑔+ ℎ𝑔𝑔− ���
𝑆𝑆𝑔𝑔 𝑆𝑆𝑔𝑔 𝑀𝑀𝑔𝑔+ 𝑀𝑀𝑔𝑔−
(MW) (MW) ($/MW2) ($/MW) ($) ($/MW) ($/MW) (MW) (MW) (h) (h) (MW/min) (MW)
1 550 150 0.01088 12.8875 6.78 440 17.78125 150 150 8 8 180 0
2 185 100 0.01088 12.8875 6.78 110 17.2375 150 150 8 8 180 0
3 320 100 0.01088 12.8875 6.78 100 17.2375 150 150 8 8 180 0
4 414 100 0.003 10.76 32.96 100 12.11 175 175 8 8 210 0
5 107 25 0.06966 26.2438 31.67 40 28.891 15 15 1 1 60 30
6 119 25 0.0128 17.82 10.15 59 19.42 50 50 5 5 60 0
7 304 50 0.0024 12.3299 28 100 13.05 125 125 8 8 150 0
8 148 50 0.0044 12.3299 28 100 13.05 125 125 8 8 60 0
9 255 50 0.0044 13.29 39 100 14.39 100 100 8 8 120 0
10 260 50 0.01059 13.29 39 100 14.39 100 100 8 8 120 0
11 491 100 0.01059 8.3391 64.16 250 13.8459 210 210 10 10 252 0
12 492 100 0.01088 8.3391 64.16 250 13.8459 210 210 10 10 252 0
13 805 80 0.01088 12.8875 6.78 100 17.02 150 150 8 8 180 0
14 577 150 0.01088 12.8875 6.78 440 17.78125 150 150 8 8 180 0
15 104 100 0.003 10.76 32.96 440 11.96 150 150 8 8 180 0
16 1100 200 0.01088 12.8875 6.78 100 17.2375 150 150 8 8 180 0
17 352 100 0.01088 12.8875 6.78 110 17.2375 150 150 8 8 180 0
18 140 25 0.0283 37.6968 17.95 30 38.48926 10 10 1 1 60 20
19 136 25 0.0128 17.82 10.15 50 19.42 50 50 5 5 60 0
Table XI. Hourly Load Demand for IEEE 118-Bus Test System (Based Values)
Table XII. Day-Ahead Price of Energy products for IEEE 118-Bus Test System (Base Values)
The Illinois 200-bus test system contains 200 buses (substations), 245 transmission lines, 40 conventional generating units with a total capacity of
3316.19 MW. Network and generator configirations and data for the Illinois 200-bus test system are described as follows [5].
Unit 𝑃𝑃�𝑔𝑔 𝑃𝑃𝑔𝑔 𝑎𝑎𝑔𝑔 𝑏𝑏𝑔𝑔 𝑐𝑐𝑔𝑔 𝐶𝐶𝑔𝑔𝑢𝑢 𝐶𝐶𝑔𝑔𝑑𝑑 ℎ𝑔𝑔+ ℎ𝑔𝑔− ���
𝑆𝑆𝑔𝑔 𝑆𝑆𝑔𝑔 𝑀𝑀𝑔𝑔+ 𝑀𝑀𝑔𝑔−
(MW) (MW) ($/MW2) ($/MW) ($) ($/MW) ($/MW) (MW) (MW) (h) (h) (MW/min) (MW)
1 4.53 1.36 0.002 19 236.12 440 17.78125 4.53 4.53 8 8 60 20
2 4.53 1.36 0.002 19 236.12 110 17.2375 4.53 4.53 8 8 60 20
3 4.53 1.36 0.002 19 236.12 100 17.2375 4.53 4.53 8 8 60 20
4 4.53 1.36 0.002 19 236.12 100 12.11 4.53 4.53 8 8 60 20
5 9.07 2.72 0.002 19 236.24 40 28.891 9.07 9.07 1 1 60 20
6 86.5 36.5 0.002 19 236.13 59 19.42 50 50 5 5 120 0
7 27.92 8.38 0.002 19 236.74 100 13.05 27.92 27.92 8 8 60 20
8 27.92 8.38 0.002 19 236.74 100 13.05 27.92 27.92 8 8 60 20
9 27.92 8.38 0.002 19 236.74 100 14.39 27.92 27.92 8 8 60 20
10 27.92 8.38 0.002 19 236.74 100 14.39 27.92 27.92 8 8 60 20
11 27.92 8.38 0.002 19 236.74 250 13.8459 27.92 27.92 10 10 60 20
12 27.92 8.38 0.002 19 236.74 250 13.8459 27.92 27.92 10 10 60 20
13 5 1.5 0.002 23.164 607.5 100 17.02 5 5 8 8 60 20
14 18 5.4 0.002 19 236.48 440 17.78125 18 18 8 8 60 20
15 67.6 17.6 0.002 23.146 603.6 440 11.96 50 50 8 8 120 0
16 154.8 54.8 0.002 23.157 606 100 17.2375 150 150 8 8 180 0
17 133.5 33.5 0.002 23.152 604.8 110 17.2375 125 125 8 8 180 0
18 130.05 39.02 0.002 19 610.14 30 38.48926 125 125 1 1 180 0
19 130.05 39.02 0.002 19 610.14 50 19.42 125 125 5 5 180 0
20 130.05 39.02 0.002 19 610.14 440 17.78125 125 125 8 8 180 0
21 446.4 133.92 0.002 19 1261.33 110 17.2375 175 175 8 8 252 0
22 446.4 133.92 0.002 19 1261.33 100 17.2375 175 175 8 8 252 0
23 92.4 42.4 0.002 19 236.14 100 12.11 50 50 8 8 120 0
24 77.22 23.17 0.002 19 253.01 40 28.891 40 40 1 1 120 0
25 77.22 23.17 0.002 19 253.01 59 19.42 40 40 5 5 120 0
26 77.22 23.17 0.002 19 253.01 100 13.05 40 40 8 8 120 0
27 77.22 23.17 0.002 19 253.01 100 13.05 40 40 8 8 120 0
28 138.6 41.58 0.002 24.07 807.9 100 14.39 150 150 8 8 180 0
29 12 3.6 0.002 23.211 618 100 14.39 12 12 8 8 60 20
30 26 7.8 0.002 23.306 639 250 13.8459 26 26 10 10 60 20
31 9.4 2.82 0.002 23.194 614.1 250 13.8459 9.4 9.4 10 10 60 20
32 9.4 2.82 0.002 23.194 614.1 100 17.02 9.4 9.4 8 8 60 20
33 9.4 2.82 0.002 23.194 614.1 440 17.78125 9.4 9.4 8 8 60 20
34 9.4 2.82 0.002 23.194 614.1 440 11.96 9.7 9.7 8 8 60 20
35 9.4 2.82 0.002 23.194 614.1 100 17.2375 9.4 9.4 8 8 60 20
36 17.5 5.28 0.002 19 236.47 110 17.2375 17.5 17.5 8 8 60 20
37 26.6 7.98 0.002 19 236.71 30 38.48926 26.6 26.6 1 1 60 20
38 569.15 170.75 0 6.71 1272.13 50 19.42 210 210 5 5 252 0
39 67.5 20.25 0.002 23.588 701.25 440 17.78125 50 50 8 8 120 0
40 67.5 20.25 0.002 23.588 701.25 110 17.2375 50 50 8 8 120 0
Table XIV. Hourly Load Demand for the Illinois 200-Bus Test System (Based Values)
Table XV. Day-Ahead Price of Energy products for the Illinois 200-Bus Test System (Base Values)
F. References
[1] H. Wu, X. Guan, Q. Zhai, F. Gao and Y. Yang, “Security-constrained generation scheduling with feasible energy delivery,” IEEE Power &
Energy Society General Meeting, Calgary, AB, Canada, 2009, pp. 1-6
[2] “An Updated Version of the IEEE RTS 24-Bus System for Electricity Market and Power System Operation Studies,” [Online] Available at:
https://orbit.dtu.dk/en/publications/an-updated-version-of-the-ieee-rts-24-bus-system-for-electricity- (Accessed on Feb. 2021).
[3] “UC: Unit Commitment,” [Online] Available at: https://www.gams.com/latest/psoptlib_ml/libhtml/psoptlib_UC.html (Accessed on Feb. 2021).
[4] P. Dehghanian, Power System Topology Control for Enhanced Resilience of Smart Electricity Grids. PhD Dissertation, Texas A&M University,
2017.
[6] “Power Systems Test Case Archive,” [Online] Available at: https://labs.ece.uw.edu/pstca/