AC/DC ELECTRIC MOTOR TEST REPORT (BEFORE)

COSTUMER F.F. CRUZ CORPORATION


ADDRESS BRGY. TAMBOBONG BOCAUE, BULACAN

UNIT 1 NO. OF SLOTS 36


RATING 10HP/ 7.5 kw SIZE OF WIRE #20 AWG DOUBLE
VOLTAGE 440V COIL PITCH 1-9/ 1-7
AMPS 29.4A WIEGHT 150KLS
DE 530922c3
RPM/POLES 1800 / 4 BEARINGS
NDE 630622c3
PHASE 3 SERIAL NO. SP-0052B9
MAKE/MADE KBARRA / CHINA DATE RECEIVED 3RD WEEK OF MARCH 2021
DATE MFD. 2015 DATE DELIVERED

REWINDING OF STATOR, REPLACE OF BEARING DE / NDE, METALIZED OF SHAFT JOURNAL,


SCOPE OF METALIZE OF SHAFT JOURNAL, REPLACE OF MECHANICAL SEAL DOUBLE HEAD (SILICONE CARBIDE)
WORK OILSEAL AND ORING, REPLACEMENT OF 2PCS. RUBBER HOLDER TERMINAL , REPLACEMENT OF 3
CONDUCTOR -3.5 mm. squared ROYAL CORD (10m), AND REPLACEMENT OF 4 CONDUCTOR -3.5
mm. squared ROYAL CORD (10m),

TEST DONE
I. INSULATION RESISTANCE TEST
MAIN STATOR VOLTAGE SETTING INSULATION RESULT

1min 10min
LINE – GROUND 500
0 0

Equipment Used INSULATION TESTER, KYORITSU, MODEL 3125

Remarks FAILED

POLARIZATION INDEX
0/0 ; UNDEFINED ( FAILED)
(P.I.)

TEST DONE

II. WINDING RESISTANCE TEST


MAIN STATOR

L1 – L2 L1-L3 L2-L3

TEST
350.2mΩ 50.05mΩ 150.15mΩ
VALUE

Equipment Used WINDING RESISTANCE METER (BRAND TELDAR MODEL TRM-10P)

Remark FAILED

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
TEST DONE

III. NO LOAD TEST


AMPERE READING(A)

L1 – L2 L1-L3 L2-L3

TEST
NA NA NA
VALUE

Remark NA

TEST DONE
IV. SURGE COMPARISON TEST
TEST CONNECTIONS

L1 – L2 L1-L3 L2-L3

GOOD WINDING GOOD WINDING GOOD WINDING

TURN TO TURN SHORT TURN TO TURN SHORT TURN TO TURN SHORT

COIL TO COIL SHORT COIL TO COIL SHORT COIL TO COIL SHORT

REVERSED COIL CONNECTION REVERSED COIL CONNECTION REVERSED COIL CONNECTION

OPEN COIL CONNECTION OPEN COIL CONNECTION OPEN COIL CONNECTION

COMPLETE GROUND COMPLETE GROUND COMPLETE GROUND

PARTIAL GROUND PARTIAL GROUND PARTIAL GROUND

PHASE TO PHASE SHORT PHASE TO PHASE SHORT PHASE TO PHASE SHORT

Equipment Used SURGE COMPARISON TESTER (BAKER INSTRUMENT CO.)

Remark FAILED

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
TEST DONE
V.VIBRATION ANALYSIS TEST

INSTRUMENT USED

AMBENT TEMP.

SPEED/RPM

PARTICULAR D.E. RESULT (mm/s) REMARKS

V NA NA

H NA NA

A NA NA

PARTICULAR N.D.E. RESULT (mm/s)

V NA NA

H NA NA

A NA NA

APPROVED BY:
CHECKED BY:
TESTED BY:

NORVEN LEBRILLA RITCHIE UNTARAN Engr. Jezrel James Casipe


EIS Inc. TECHNICIAN EIS Inc. MECHANICAL TECHNICIAN EIS Inc. Project Engineer

DATE: OCTOBER 4, 2021

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
MECHANICAL MEASUREMENT

CUSTOMER: F.F. CRUZ CORPORATION DATE: 10 /04 / 21

ADDRESS: BUCAUE , BULACAN J.O. NO.:

QTN NO. : P.O. NO.:

SPECIFICATIONS LKG-SE12
RATING 1 Kw 7.5 CURRENT 24.4A ADC ARM SN 100AEP437
VOLTAGE 440V VDC ARM BRAND ADC FIELD D.E. BEARING DE 530922C3
N.D.E.
VDC ARM BEARING NDE 630622C3
SUBMERSSIBLE
SPEED 1800 RPM TYPE PUMP USAGE

A. BEARING HOUSING (DRIVE-END) B. BEARING JOURNAL (DRIVE-END)

INSIDE DIAMETER GUIDE JOURNAL


PARTICULARS PARTICULARS
X Y Z X Y Z
A-B 100.01mm 100.01mm 100.01mm A-B 40.02mm 40.02mm 40.01mm
C-D 100.01mm 100.01mm 100.01mm C-D 40.02mm 40.01mm 40.02mm
E-F 100.01mm 100.01mm 100.01mm E-F 40.02mm 40.01mm 40.01mm
Tolerance 100.00mm - 100.012mm Tolerance 40.012mm - 40.025mm
Remarks Within tolerance Remarks Within tolerance

A. BEARING HOUSING (NON- DRIVE-END) B. BEARING JOURNAL (NON-DRIVE-END)

INSIDE DIAMETER GUIDE JOURNAL


PARTICULARS PARTICULARS
X Y Z X Y Z
A-B 72.01mm 72.01mm 72.01mm A-B 30.02mm 30.01mm 30.02mm
C-D 72.01mm 72.01mm 72.01mm C-D 30.02mm 30.01mm 30.01mm
E-F 72.01mm 72.01mm 72.01mm E-F 30.01mm 30.01mm 30.02mm
Tolerance 72.00mm - 72.012mm Tolerance 30.012mm - 30.025mm
Remarks Within tolerance Remarks Within tolerance

C. T.I.R (TOTAL INDICATOR RUN-OUT)

PARTICULARS 3 2 1

A 0mm 0mm 0mm


B 0.01mm 0.02mm 0.02mm
C 0mm 0mm 0mm

D 0.01mm 0.01mm 0.01mm

Tolerance 0.0102mm- 0.0185mm

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
Remarks
PASSED

MECHANICAL SEAL MEASUREMENT

SUBJECT TO: METALIZING OF SHAFT JOURNAL IN MECHANICAL SEAL DOUBLE HEAD,


SILICONE CARBIDE

C MECHANICAL SHAFT JOURNAL (DRIVE-END)


PARTICUL GUIDE JOURNAL
ARS X Y Z
A-B 34.90mm 34.95mm 34.95mm
C-D 34.95mm 34.90mm 34.95mm
E-F 35.00mm 34.90mm 34.95mm
Tolerance 35.00mm - 35.012mm
Remarks Out of tolerance

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
CAPTURED IMAGES (BEFORE): REWINDING OF STATOR, REPLACE OF
BEARING DE / NDE, METALIZED OF SHAFT JOURNAL, METALIZE OF SHAFT JOURNAL,
REPLACE OF MECHANICAL SEAL DOUBLE HEAD (SILICONE CARBIDE) OILSEAL AND
ORING, REPLACEMENT OF 2PCS. RUBBER HOLDER TERMINAL , REPLACEMENT OF 3
CONDUCTOR -3.5 mm. squared ROYAL CORD (10m), AND REPLACEMENT OF 4
CONDUCTOR -3.5 mm. squared ROYAL CORD (10m).

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 9974239/ (02) 9424835 EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal