1 Project description
1.1 Project general settings
Installation standard IEC60364
2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 1 NA 1 x 185 Al 16.4 353 24
0
3 Calculation notes
MV/LV transformer TA 0
Range Trihal
Technology Dry-type
Rated power 315 kVA
ukrT 6%
Type of losses Normal
PkrT 4 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 0
Parameters
Length 15 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 455 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Selected phase
Cross section area 1x185 mm²
Core Copper
Iz under real conditions 456 A
Selected neutral
Cross section area 1x185 mm²
Core Copper
Iz under real conditions 456 A
Selected PE
Cross section area 1x95 mm²
Core Copper
Cable WD 6
Parameters
Length 5m
Max length 120 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 10 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Project: New_project 28/06/2024
Page 9/20
Cable WD 7
Parameters
Length 5m
Max length 115 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 30 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 54 A
Project: New_project 28/06/2024
Page 12/20
Selected neutral
Cross section area 1x6 mm²
Core Copper
Iz under real conditions 54 A
Selected PE
Cross section area 1x4 mm²
Core Copper
Cable WD 8
Parameters
Length 5m
Max length 95.9 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 11 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 42 A
Project: New_project 28/06/2024
Page 15/20
Selected neutral
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 42 A
Selected PE
Cross section area 1x4 mm²
Core Copper
Cable WD 9
Parameters
Length 5m
Max length 120 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI 0%
Ib 7A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference A-52-14
Soil thermal resistivity factor 1
Standard table reference A-52-16
Loaded neutral factor 1
Standard table reference D-52-1
Touching conductor factor 1
Standard table reference A-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 42 A
Project: New_project 28/06/2024
Page 18/20
Selected neutral
Cross section area 1x4 mm²
Core Copper
Iz under real conditions 42 A
Selected PE
Cross section area 1x4 mm²
Core Copper
Load 6 QA 6 iC60N
Load 7 QA 7 iC60N
Load 9 QA 9 iC60N
Load 8 QA 8 iC60N
MVQA 0
Source 0
MVWD 0
10 m
Iz : 353 A
TA 0
315 kVA
20 kV / 400 V
TN-S
ukrT : 6 %
WD 0
15 m
Iz : 456 A
Σ∆u3p : 0.446 %
UC 4
No preference
QA 0
Undefined WC 3
Ib : 455 A
0A Ik3M:7.16 kA
Ik1m:5.84 kA
Ief : 6.11 kA
QA 6 QA 7 QA 8 QA 9
TN-S TN-S TN-S TN-S
Ib : 16 A Ib : 40 A Ib : 20 A Ib : 16 A
WD 6 WD 7 WD 8 WD 9
5m 5m 5m 5m
Load 6
Load 7
Load 8
Load 9
Iz : 42 A Iz : 54 A Iz : 42 A Iz : 42 A
Σ∆u3p : 0.555 % Σ∆u3p : 0.664 % Σ∆u3p : 0.57 % Σ∆u3p : 0.522 %
AA 6 AA 7 AA 8 AA 9
Ik3M:0 kA Ik3M:6 kA Ik3M:5.39 kA Ik3M:0 kA
Ik1m:0 kA Ik1m:3.51 kA Ik1m:2.77 kA Ik1m:0 kA
Ief : 0 kA Ief : 3.21 kA Ief : 2.85 kA Ief : 0 kA
Ief2m:0 kA Ief2m:0 kA