Model: C1250 D6
Frequency: 60 Hz
Fuel type: Diesel
Standby Prime
Fuel consumption kW (kVA) kW (kVA)
Ratings 1270 (1588) 1120 (1400)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 27.5 45.8 65.4 87.3 23.6 41.6 58.7 76.9
L/hr 104 173 247 330 89 157 222 291
Fuel flow
Maximum fuel flow, L/hr 625
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70
power.cummins.com
©2017 Cummins Inc. | DS84-CPGK (10/17)
Air Standby rating Prime rating
Combustion air, m3/min 110.4 104.8
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 257.7 237.8
Exhaust gas temperature, °C 475 460
Maximum exhaust back pressure, kPa 6.7
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
power.cummins.com
©2017 Cummins Inc. | DS84-CPGK (10/17)
Alternator data
Ratings definitions
Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, BS 5514.
DIN 6271 and BS 5514.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS84-CPGK (10/17)
Specification sheet
Diesel
generator set
KTA50 series
engine
1250 kVA - 1675 kVA 50 Hz
1120 kW - 1545 kW 60 Hz
Description
This Cummins® commercial generator set is a Control system - Standard PowerCommand®
fully integrated power generation system, electronic control provides total system
providing optimum performance, reliability, and integration including remote start/stop, precise
versatility for stationary Standby, Prime Power, frequency and voltage regulation, alarm and
and Continuous duty applications. status message display, AmpSentryTM
protection, output metering, auto-shutdown.
Features
Cooling system - Standard integral set-
Cummins heavy-duty engine - Rugged 4-cycle
mounted radiator system, designed and tested
industrial diesel delivers reliable power, low
for rated ambient temperatures, simplifies facility
emissions and fast response to load changes.
design requirements for rejected heat.
Permanent Magnet Generator (PMG) - Offers
Enclosures - Optional weather-protective and
enhanced motor starting and fault clearing short
sound-attenuated enclosures are available.
circuit capability.
Warranty and service - Backed by a
Alternator - Several alternator sizes offer
comprehensive warranty and worldwide
selectable motor starting capability with low
distributor network.
reactance 2/3 pitch windings; low waveform
distortion with non-linear loads, fault clearing
short-circuits capability, and class F or H
insulation.
Emissions
Standby rating Prime rating compliance Data sheets
50 Hz 60 Hz 50 Hz 60 Hz TA Luft –
50 Hz 60 Hz
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) EU Stage
DS44-
C1400 D5 1400 (1120) 1250 (1000)
CPGK
DS46-
C1675 D5 1675 (1340) 1400 (1120)
CPGK
DS47-
C1675 D5A 1675 (1340) 1500 (1200)
CPGK
DS84-
C1250 D6 1270 (1588) 1120 (1400)
CPGK
DS85-
C1500 D6 1545 (1931) 1286 (1608)
CPGK
power.cummins.com
©2019 Cummins Inc. | SS16-CPGK (01/19)
Generator set specifications
Governor regulation class ISO 8528 compliant
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
EMC compatibility BS EN61000-6-4 / BS EN61000-6-2
Engine specifications
Design 4 cycle, V-block, turbocharged and after-cooled
Bore 158.8 mm (6.25 in.)
Stroke 158.8 mm (6.25 in.)
Displacement 50 L (3067 in3)
Cylinder block engine Sixteen-cylinder vee formation, direct injection, four-cycle diesel
Battery capacity 1800 amps at ambient temperature 32 ºF (0 °C)
Battery charging alternator 55 amps
Starting voltage 24 Volts, negative ground
Fuel system Direct injection
Fuel filter Dual spin on paper element fuel filters with standard water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin-on paper element full flow and bypass lube oil filters
Standard cooling system 104 ºF (40 ºC) ambient radiator
Alternator specifications
Design Brushless, 4 pole, drip proof revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise
Exciter type Permanent Magnet Generator (PMG)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) < 50% per NEMA MG1-22.43
Telephone Harmonic Factor (THF) No load < 1.5%. Non distorting balanced linear load < 5%
Available voltages
50 Hz Line – Neutral/Line – Line 60 Hz Line – Neutral/Line – Line
• 220/380* • 1905/3300 • 219/380 • 2400/4160
*Derate may be applicable at this voltage. Please consult the factory for details.
*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2019 Cummins Inc. | SS16-CPGK (01/19)
PowerCommand 3.3 control system Engine data
• DC voltage
• Engine speed
• Lube oil pressure and temperature
• Coolant temperature
• Comprehensive FAE data (where applicable)
Other data
The PowerCommand 3.3 control system is an integrated • Genset model data
microprocessor based generator set control system • Start attempts, starts, running hours, kW hours
providing voltage regulation, engine protection, alternator • Load profile (operating hours at % load in 5%
protection, operator interface and isochronous governing. increments)
AmpSentry – Includes integral AmpSentry protection,
• Fault history
which provides a full range of alternator protection functions
that are matched to the alternator provided. • Data logging and fault simulation (requires InPower)
Power management – Control function provides battery Standard control functions
monitoring and testing features and smart starting control Digital governing (optional)
system.
• Integrated digital electronic isochronous governor
Advanced control methodology – Three phase sensing,
full wave rectified voltage regulation, with a PWM output for • Temperature dynamic governing
stable operation with all load types. Digital voltage regulation
Communications interface – Control comes standard with • Integrated digital electronic voltage regulator
PCCNet and Modbus interface. • 3-phase, 4-wire Line-to-Line sensing
Regulation compliant – Prototype tested: UL, CSA and • Configurable torque matching
CE compliant. AmpSentry AC protection
Service – InPower™ PC-based service tool available for • AmpSentry protective relay
detailed diagnostics, setup, data logging and fault
simulation. • Over current and short circuit shutdown
Reliable design – The control system is designed for • Over current warning
reliable operation in harsh environment. • Single and three phase fault regulation
Multi-language support • Over and under voltage shutdown
Operator panel features • Over and under frequency shutdown
Operator panel features – The operator panel, in addition • Overload warning with alarm contact
to the alternator, displays the Utility/AC Bus data. • Reverse power and reverse Var shutdown
Operator/display functions • Field overload
• 320 x 240 pixels graphic LED backlight LCD Engine protection
• Auto, manual, start, stop, fault reset and lamp test/panel • Battery voltage monitoring, protection and testing
lamp switches • Over speed shutdown
• Alpha-numeric display with pushbuttons • Low oil pressure warning and shutdown
• LED lamps indicating genset running, remote start, not in • High coolant temperature warning and shutdown
auto, common shutdown, common warning, manual run
• Low coolant level warning or shutdown
mode, auto mode and stop
Paralleling control functions • Low coolant temperature warning
• Digital frequency synchronization and voltage matching • Fail to start (over crank) shutdown
• Isochronous kW and kVar load sharing controls • Fail to crank shutdown
• Droop kW and kVar control • Cranking lockout
• Sensor failure indication
• Sync check
• Low fuel level warning or shutdown
• Extended paralleling (peak shave/base load)
• Fuel-in-rupture-basin warning or shutdown
• Digital power transfer control (AMF) provides load
transfer operation in open or closed transition or soft • Full authority electronic engine protection
(ramping) transfer mode Control functions
Alternator data • Time delay start and cool down
• Line-to-Neutral and Line-to-Line AC volts • Real time clock for fault and event time stamping
• 3-phase AC current • Exerciser clock and time of day start/stop
• Frequency • Data logging
• kW, kVar, power factor kVA (three phase and total) • Cycle cranking
• Load shed
• Configurable inputs and outputs (4)
• Remote emergency stop
Options
• Auxiliary output relays (2)
power.cummins.com
©2019 Cummins Inc. | SS16-CPGK (01/19)
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a
reliable utility source. Emergency Standby Power
(ESP) is in accordance with ISO 8528. Fuel Stop
power in accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant
electrical load for limited hours. Limited-Time
This outline drawing is to provide representative configuration
Running Power (LTP) is in accordance with
details for model series only.
ISO 8528.
Prime Power (PRP): See respective model data sheet for specific model outline
drawing number.
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in Do not use for installation design
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours.
Continuous Power (COP) in accordance with
ISO 8528, ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Model Dim ‘A’ (mm) Dim ‘B’ (mm) Dim ‘C’ (mm) Set weight* dry (kg) Set weight* wet (kg)
C1400 D5 5105 2000 2238 9190 9613
C1675 D5 5811 2033 2330 10348 10967
C1675 D5A 5811 2033 2330 10348 10967
C1250 D6 5105 2000 2238 9190 9613
C1500 D6 5811 2033 2330 10348 10967
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.
©2019 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
SS16-CPGK (101/19)
KTA50-G3
Description Features
The KTA50-Series benefits from years of technical Coolpac Integrated Design - Products are supplied complete
development and improvement to bring customers an with cooling package and air cleaner kit for a complete power
innovative and future proof diesel engine that keeps pace package. Each component has been specifically developed and
with ever changing generator set requirements. rigorously tested for G-Drive products, ensuring high
performance, durability and reliability.
Recognised globally for its performance under even the
most severe climatic conditions, the KTA50-Series is Aftercooler – Large capacity aftercoolers result in cooler,
widely acknowledged as the most robust and cost- denser intake air for more efficient combustion and reduced
effective diesel engine in its power range for the internal stresses for longer life.
generator set market.
Cooling System – Gear driven centrifugal water pump. Large
This engine has been built to comply volume water passages provide even flow of coolant around
with CE certification. cylinder liners, valves and injectors.
This engine has been designed in Pistons – Aluminium alloy, cam ground and barrel shaped to
facilities certified to ISO9001 and compensate for thermal expansion assures precise fit at
manufactured in facilities certified to operating temperatures. Grooved skirt finish provides superior
ISO9001 or ISO9002. lubrication. Oil cooled for rapid heat dissipation.
Fuel Consumption 1500 rpm (50 Hz) Fuel Consumption 1800 rpm (60 Hz)
% kWm BHP L/ph US gal/ph % kWm BHP L/ph US gal/ph
Standby Power Standby Power
100 1227 1645 293 77.4 100 1380 1850 330 87.3
Prime Power Prime Power
100 1097 1470 261 69.0 100 1220 1635 291 76.9
75 822 1102 199 52.5 75 915 1226 222 58.7
50 548 735 139 36.6 50 610 818 157 41.6
25 275 368 76 20.0 25 305 409 89 23.6
Continuous Power Continuous Power
100 900 1206 216 57.1 100 1000 1340 242 63.8
Asia Pacific Europe, CIS, Middle Latin America Mexico North America
10 Toh Guan Road East and Africa Rua Jati, 310, Cumbica Cummins S. de R.L. de C.V. 1400 73rd Avenue N.E.
#07-01 Manston Park Columbus Ave Guarulhos, SP 07180-900 Eje 122 No. 200 Zona Industrial Minneapolis, MN 55432
TT International Tradepark Manston Ramsgate Brazil San Luis Potosí, S.L.P. 78090 USA
Singapore 608838 Kent CT12 5BF. UK Phone 55 11 2186 4552 Mexico Phone 1 763 574 5000
Phone 65 6417 2388 Phone 44 1843 255000 Fax 55 11 2186 4729 Phone 52 444 870 6700 USA Toll-free 1 877 769 7669
Fax 65 6417 2399 Fax 44 1843 255902 Fax 52 444 870 6811 Fax 1 763 574 5298
PowerCommand®
3.3 control system
equipment.
Warranty and service. Backed by a comprehensive
warranty and worldwide distributor service network.
Certifications - Suitable for use on gensets that are
designed, manufactured, tested and certified to
relevant UL, NFPA, ISO, IEC, Mil Std. and CE
standards.
power.cummins.
©2017 Cummins Inc. | S-1570 (08/17)
Exerciser clock and time of day start/stop initiate a test
PowerCommand digital with or without load, or a base load or peak shave
genset control session.
Digital power transfer control (AMF) provides load transfer
PCC 3300 operation in open transition, closed transition, or soft
(ramping) transfer modes.
Extended paralleling (peak shave/base load) regulates the
genset real and reactive power output while paralleled to
the utility. Power can be regulated at either the genset or
utility bus monitoring point.
Digital frequency synchronization and voltage matching.
Isochronous load share
Droop kW and KVAr control
Sync cCheck – The sync check function has adjustments
Description for phase angle window, voltage window, frequency
The PowerCommand genset control is suitable for use on a window and time delay.
wide range of diesel and lean burn natural gas gensets in Utility/AC Bus metering and protection
paralleling applications. The PowerCommand control is Advanced serviceability – using InPower™, a PC-based
compatible with shunt or PMG excitation style. It is suitable software service tool.
for use with reconnectable or non-reconnectable
generators, and it can be configured for any frequency, Environmental protection – The control system is
voltage and power connection from 120-600 VAC line- designed for reliable operation in harsh environments.
toline, 601-45,000 VAC with external PT. The main control board is a fully encapsulated module
Power for this control system is derived from the genset that is protected from the elements.
starting batteries. The control functions over a voltage range ModBus interface for interconnecting to customer
from 8 VDC to 30 VDC. equipment.
Features Configurable inputs and outputs – Four discrete inputs
and four dry contact relay outputs.
12 and 24 VDC battery operation.
Warranty and service – Backed by a comprehensive
Digital voltage regulation - Three phase full wave FET
warranty and worldwide distributor service network.
type regulator compatible with either shunt or PMG
systems. Sensing is three phase. Certifications – Suitable for use on gensets that are
designed, manufactured, tested and certified to relevant
Digital engine speed governing (where applicable) -
UL, NFPA, ISO, IEC, Mil Std. and CE standards.
Provides isochronous frequency regulation.
Full authority engine communications (where applicable) - Base control functions
Provides communication and control with the Engine
HMI capability
Control Module (ECM).
AmpSentry protection - for true alternator overcurrent Options – Local and remote HMI options.
protection. Operator adjustments – The HMI includes provisions for
Genset monitoring - Monitors status of all critical engine many set up and adjustment functions.
and alternator functions. Genset hardware data – Access to the control and software
part number, genset rating in kVA and genset model
Digital genset metering (AC and DC). number is provided from the HMI or InPower.
Genset battery monitoring system to sense and warn Data logs – Includes engine run time, controller on time,
against a weak battery condition. number of start attempts, total kilowatt hours, and load
Configurable for single or three phase AC metering. profile. (Control logs data indicating the operating hours at
Engine starting - Includes relay drivers for starter, Fuel percent of rated kW load, in 5% increments. The data is
Shut Off (FSO), glow plug/spark ignition power and switch presented on the operation panel based on total operating
hours on the generator).
B+ applications.
Fault history – Provides a record of the most recent fault
Genset protection – Protects engine and alternator. conditions with control date and time stamp. Up to 32
Real time clock for fault and event time stamping. events are stored in the control non-volatile memory.
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
Alternator data - Spark advance (up to 18 cylinders)
- Voltage (single or three phase line-to-line and line-to- - Knock count (up to 18 cylinders)
neutral) - Auxiliary supply disconnector status
- Current (single or three phase) - Engine heater status
- kW, kVAr, power factor, kVA (three phase and total) - Coolant circulating pump status
- Frequency - Lube oil priming pump status
For Lean burn natural gas engine applications: - Lube oil status
- Alternator heater status - Oil heater status
- Alternator winding temperature (per phase) - Derate authorization status
- Alternator drive end bearing temperature - Start system status
- Alternator non-drive end bearing temperature - Ventilator fan status
- Ventilation louvre status
Utility/AC Bus data
- Radiator fan status
- Voltage (three phase line-to-line and line-to-neutral)
- DC PSU status
- Current (three phase and total)
- Start inhibit/enable status and setup
- kW, kVAr, power factor, kVA (three phase and total)
Service adjustments – The HMI includes provisions for
- Frequency adjustment and calibration of genset control functions.
Engine data Adjustments are protected by a password. Functions
include:
- Starting battery voltage - Engine speed governor adjustments
- Engine speed - Voltage regulation adjustments
- Engine temperature - Cycle cranking
- Engine oil pressure - Configurable fault set up
- Engine oil temperature - Configurable input and output set up
- Intake manifold temperature - Meter calibration
- Coolant temperature - Paralleling setup
- Comprehensive Full Authority Engine (FAE) data (where - Display language and units of measurement
applicable)
Engine control
For lean burn natural gas engine applications:
SAE-J1939 CAN interface to full authority ECMs (where
- Safety shutoff valve status
applicable). Provides data transfer between genset and
- Valve proving status engine controller for control, metering and diagnostics. 12
- Downstream gas pressure VDC/24 VDC battery operations - PowerCommand will
- Gas inlet pressure operate either on 12 VDC or 24 VDC batteries.
Temperature dependent governing dynamics (with
- Gas mass flow rate
electronic governing) - modifies the engine governing
- Control valve position control parameters as a function of engine temperature.
- Gas outlet pressure This allows the engine to be more responsive when warm
- Manifold pressure and more stable when operating at lower temperature
levels.
- Manifold temperature
Isochronous governing - (where applicable) Capable of
- Throttle position controlling engine speed within +/-0.25% for any steady
- Compressor outlet pressure state load from no load to full load. Frequency drift will not
- Turbo speed exceed +/-0.5% for a 33 °C (60 °F) change in ambient
temperature over an 8 hour period.
- Compressor bypass position
Droop electronic speed governing - Control can be
- Cylinder configuration (e.g., drive end and non-drive end adjusted to droop from 0 to 10% from no load to full load.
configurations
Remote start mode - It accepts a ground signal from
- Coolant pressure 1 and 2 (e.g., HT and LT) remote devices to automatically start the genset and
- Coolant temperature 1 and 2 (e.g., HT and LT) immediately accelerates to rated speed and voltage or run
- Exhaust port temperature (up to 18 cylinders) at idle until engine temperature is adequate. The remote
start signal will also wake up the control from sleep mode.
- Pre-filter oil pressure The control can incorporate a time delay start and stop.
- Exhaust back pressure
- CM700 internal temperature
- CM700 isolated battery voltage
- Speed bias
- CM558 internal temperature
- CM558 isolated battery voltage
- Knock level (up to 18 cylinders)
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
Remote and local emergency stop - The control accepts a Paralleling functions
ground signal from a local (genset mounted) or remote TM
(facility mounted) emergency stop switch to cause the First Start Sensor system – PowerCommand provides
genset to immediately shut down. The genset is prevented a unique control function that positively prevents multiple
from running or cranking with the switch engaged. If in gensets from simultaneously closing to an isolated bus
sleep mode, activation of either emergency stop switch will under black start conditions. The First Start Sensor system
wake up the control. is a communication system between the gensets that
allows the gensets to work together to determine which
Sleep mode - The control includes a configurable low
genset is a system should be the first to close to the bus.
current draw state to minimize starting battery current draw
The system includes an independent backup function, so
when the genset is not operating. The control can also be
that if the primary system is disabled the required functions
configured to go into a low current state while in auto for
are still performed.
prime applications or applications without a battery
charger. Synchronizing – Control incorporates a digital
synchronizing function to force the genset to match the
Engine starting - The control system supports automatic
frequency, phase and voltage of another source such as a
engine starting. Primary and backup start disconnects are
utility grid. The synchronizer includes provisions to provide
achieved by one of two methods: magnetic pickup or main
proper operation even with highly distorted bus voltage
alternator output frequency. The control also supports
waveforms. The synchronizer can match other sources
configurable glow plug control when applicable.
over a range of 60-110% of nominal voltage and -24 to +6
Cycle cranking - Is configurable for the number of starting Hz. The synchronizer function is configurable for slip
cycles (1 to 7) and duration of crank and rest periods. frequency synchronizing for applications requiring a known
Control includes starter protection algorithms to prevent direction of power flow at instant of breaker closure or for
the operator from specifying a starting sequence that might applications where phase synchronization performance is
be damaging. otherwise inadequate.
Time delay start and stop (cooldown) - Configurable for Load sharing control – The genset control includes an
time delay of 0-300 seconds prior to starting after receiving integrated load sharing control system for both real (kW)
a remote start signal and for time delay of 0-600 seconds and reactive (kVar) loads when the genset(s) are operating
prior to shut down after signal to stop in normal operation on an isolated bus. The control system determines kW
modes. Default for both time delay periods is 0 seconds. load on the engine and kVar load on the alternator as a
For lean burn natural gas engine applications: percent of genset capacity, and then regulates fuel and
excitation systems to maintain system and genset at the
Engine start inhibit/enable – The function will allow same percent of load without impacting voltage or
application-specific processes to be started prior to the frequency regulation. The control can also be configured
genset/engine start (e.g., pumps, boosters, etc.). for operation in droop mode for kW or Kvar load sharing.
Alternator control Load govern control – When PowerCommand receives a
signal indicating that the genset is paralleled with an
The control includes an integrated three phase line-to-line infinite source such as a utility (mains) service, the genset
sensing voltage regulation system that is compatible with will operate in load govern mode. In this mode the genset
shunt or PMG excitation systems. The voltage regulation will synchronize and close to the bus, ramp to a pre-
system is a three phase full wave rectified and has an FET programmed kW and kVar load level, and then operate at
output for good motor starting capability. Major system that point. Control is adjustable for kW values from 0-
features include: 100% of Standby rating, and 0.7-1.0 power factor
Digital output voltage regulation - Capable of regulating (lagging). Default setting is 80% of Standby and 1.0 power
output voltage to within +/-1.0% for any loads between no factor. The control includes inputs to allow independent
load and full load. Voltage drift will not exceed +/-1.5% for control of kW and kVar load level by a remote device while
a 40 ºC in the load govern mode. The rate of load increase and
(104 ºF) change in temperature in an eight hour period. On decrease is also adjustable in the control. In addition, the
engine starting or sudden load acceptance, voltage is control can be configured for operation in kW or kVAr load
controlled to a maximum of 5% overshoot over nominal govern droop.
level. Load demand control – The control system includes the
The automatic voltage regulator feature can be disabled to ability to respond to an external signal to initiate load
allow the use of an external voltage regulator. demand operation. On command, the genset will ramp to
Droop voltage regulation - Control can be adjusted to no load, open its paralleling breaker, cool down, and shut
droop from 0-10% from no load to full load. down. On removal of the command, the genset will
immediately start, synchronize, connect, and ramp to its
Torque-matched V/Hz overload control - The voltage roll-
share of the total load on the system.
off set point and rate of decay (i.e. the slope of the V/Hz
curve) is adjustable in the control. Sync check – The sync check function decides when
permissive conditions have been met to allow breaker
Fault current regulation - PowerCommand will regulate the
closure. Adjustable criteria are: phase difference from 0.1-
output current on any phase to a maximum of three times
20 deg, frequency difference from 0.001-1.0 Hz, voltage
rated current under fault conditions for both single phase
difference from 0.5-10%, and a dwell time from 0.5-5.0
and three phase faults. In conjunction with a permanent
sec. Internally the sync check is used to perform closed
magnet generator, it will provide three times rated current
transition operations. An external sync check output is also
on all phases for motor starting and short circuit
available.
coordination purpose.
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
Genset and utility/AC Bus source AC metering – Extended paralleling – In extended paralleling mode (when
The control provides comprehensive three phase AC enabled) the controller will start the genset and parallel to a
metering functions for both monitored sources, utility source and then govern the real and reactive power
including: output of the genset based on the desired control point. The
3-phase voltage (L-L and L-N) and current, frequency, control point for the real power (kW) can be configured for
phase rotation, individual phase and totalized values of either the genset metering point ("base load") or the utility
kW, kVAr, kVA and Power Factor; totalized positive and metering point ("peak shave"). The control point for the
negative kW-hours, kVAr-hours, and kVA-hours. Three reactive power (kVAr or Power Factor) can also be
wire or four wire voltage connection with direct sensing independently configured for either the genset metering point
of voltages to 600V, and up to 45kV with external or the utility metering point. This flexibility would allow base
transformers. Current sensing is accomplished with kW load from the genset while maintaining the utility power
either 5 amp or 1 CT secondaries and with up to 10,000 factor at a reasonable value to avoid penalties due to low
amp primary. Maximum power readings are power factor. The System always operates within genset
32,000kW/kVAR/kVA. ratings. The control point can be changed while the system is
Power transfer control – provides integrated in operation. Set points can be adjusted via hardwired analog
automatic power transfer functions including source input or adjusted through an operator panel display or service
availability sensing, genset start/stop and transfer pair tool.
monitoring and control. The transfer/retransfer is Exerciser clock –The exerciser clock (when enabled) allows
configurable for open transition, fast closed transition the system to be operated at preset times in either test
(less than 100msec interconnect time), or soft closed without load, test with load, or extended parallel mode. A real
transition (load ramping) sequences of operation. Utility time clock is built in. Up to 12 different programs can be set
source failure will automatically start genset and for day of week, time of day, duration, repeat interval, and
transfer load, retransferring when utility source returns. mode. For example, a test with load for 1 hour every Tuesday
Test will start gensets and transfer load if test with load at 2AM can be programmed. Up to 6 different exceptions can
is enabled. Sensors and timers include: also be set up to block a program from running during a
Under voltage sensor: 3-phase L-N or L-L under voltage specific date and time period.
sensing adjustable for pickup from 85-100% of nominal. Application types – Controller is configured to operating in
Dropout adjustable from 75-98% of pickup. Dropout one of six possible application types. These topologies are
delay adjustable from 0.1-30 sec. often used in combinations in larger systems, with
Over voltage sensor: 3-phase L-N or L-L over voltage coordination of the controllers in the system either by external
sensing adjustable for pickup from 95-99% of dropout. device or by interlocks provided in the control. Topologies that
Dropout adjustable from 105-135% of nominal. Dropout may be selected in the control include:
delay adjustable from 0.5-120 sec. Standard Standalone: Control provides monitoring, protection and
configuration is disabled, and is configurable to enabled control in a non-paralleling application.
in the field using the HMI or InPower service tools.
Over/Under frequency sensor: Center frequency
adjustable from 45-65 Hz. Dropout bandwidth
adjustable from 0.3-5% of center frequency beyond
pickup bandwidth. Pickup bandwidth adjustable from
0.3-20% of center frequency. Field configurable to
enable.
Loss of phase sensor: Detects out of range voltage
phase angle relationship. Field configurable to enable.
Phase rotation sensor: Checks for valid phase rotation
of source. Field configurable to enable.
Breaker tripped: If the breaker tripped input is active, Synchronizer only: control will synchronize the genset to other
the associated source will be considered as source when commanded to either via a hardwired or Modbus
unavailable. driven input.
Timers: Control provides adjustable start delay from
0- 300 sec, stop delay from 0-800 sec, transfer delay
from
0- 120 sec, retransfer delay from 0-1800 sec,
programmed transition delay from 0-60sec, and
maximum parallel time from 0-1800 sec.
Breaker control – Utility and genset breaker interfaces
include separate relays for opening and closing breaker,
as well as inputs for both 'a' and 'b' breaker position
contacts and tripped status. Breaker diagnostics include
contact failure, fail to close, fail to open, fail to
disconnect, and tripped. Upon breaker failure,
appropriate control action is taken to maintain system
integrity.
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
Isolated Bus: allows the genset to perform a dead bus closure Power transfer control: control operates a single
or synchronize to the bus and isochronously share kW and genset/single utility transfer pair in open transition, fast
kVAR loads with other gensets. closed transition, or soft closed transition. Extended
paralleling functionality also provides base load and
peak shave options.
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
General engine protection Alternator protection
Low and high battery voltage warning - Indicates status AmpSentry protective relay - A comprehensive monitoring
of battery charging system (failure) by continuously and control system integral to the PowerCommand Control
monitoring battery voltage. System that guards the electrical integrity of the alternator
Weak battery warning - The control system will test the and power system by providing protection against a wide
battery each time the genset is signaled to start and array of fault conditions in the genset or in the load. It also
indicate a warning if the battery indicates impending provides single and three phase fault current regulation so
failure. that downstream protective devices have the maximum
Fail to start (overcrank) shutdown - The control system current available to quickly clear fault conditions without
will indicate a fault if the genset fails to start by the subjecting the alternator to potentially catastrophic failure
completion of the engine crack sequence. conditions. See document R1053 for a full size time over
current curve. The control does not included protection
Fail to crank shutdown - Control has signaled starter to required for interconnection to a utility (mains) service.
crank engine but engine does not rotate.
Cranking lockout - The control will not allow the starter to
attempt to engage or to crank the engine when the
engine is rotating.
Fault simulation –The control in conjunction with InPower
software, will accept commands to allow a technician to
verify the proper operation of the control and its interface
by simulating failure modes or by forcing the control to
operate outside of its normal operating ranges. InPower
also provides a complete list of faults and settings for the
protective functions provided by the controller.
For lean burn natural gas engine applications:
Off load running (protection) – This feature protects the
engine in the event the genset is being called to go off
load for too long.
Hydro mechanical fuel system engine
protection
Overspeed shutdown – Default setting is 115% of
nominal Low lube oil pressure warning/shutdown – Level
is preset (configurable with InPower or HMI) to match the
capabilities of the engine used. Control includes time
delays to prevent nuisance alarms.
High lube oil temperature warning/shutdown – Level is
preset (configurable with InPower or HMI) to match the
capabilities of the engine used. Control includes time High AC voltage shutdown (59) - Output voltage on any
delays to prevent nuisance alarms. phase exceeds preset values. Time to trip is inversely
High engine temperature warning/shutdown – Level is proportional to amount above threshold. Values adjustable
preset (configurable with InPower or HMI) to match the from 105-125% of nominal voltage, with time delay
capabilities of the engine used. Control includes time adjustable from 0.1-10 seconds. Default value is 110% for
delays to prevent nuisance alarms. 10 seconds.
Low coolant temperature warning – Indicates that engine Low AC voltage shutdown (27) - Voltage on any phase has
temperature may not be high enough for a 10 second dropped below a preset value. Adjustable over a range of
start or proper load acceptance. 50-95% of reference voltage, time delay 2-20 seconds.
Default value is 85% for 10 seconds. Function tracks
Low coolant temperature warning – Can be set up to be
reference voltage. Control does not nuisance trip when
a warning or shutdown.
voltage varies due to the control directing voltage to drop,
High intake manifold temperature shutdown – Level is such as during a V/Hz roll-off or synchronizing.
preset (configurable with InPower or HMI) to match the
Under frequency shutdown (81 u) - Genset output frequency
capabilities of the engine used. Control includes time cannot be maintained. Settings are adjustable from 2-10 Hz
delays to prevent nuisance alarms.
below reference governor set point, for a 5- 20 second time
Full authority electronic engine protection delay. Default: 6 Hz, 10 seconds. Under frequency
protection is disabled when excitation is switched off, such
Engine fault detection is handled inside the engine ECM. as when engine is operating in idle speed mode.
Fault information is communicated via the SAE-J1939
data link for annunciation in the HMI.
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
Over frequency shutdown/warning (81o) - Genset is Fail to disconnect warning: In the controller is unable to
operating at a potentially damaging frequency level. open either breaker, a fail to disconnect warning is
Settings are adjustable from 2-10 Hz above nominal initiated. Typically this would be mapped to a configurable
governor set point for a 1-20 second time delay. Default: 6 output, allowing an external device to trip a breaker.
Hz, 20 seconds, disabled. Fail to synchronize warning: Indicates that the genset
Overcurrent warning/shutdown (51) - Implementation of could not be brought to synchronization with the bus.
the thermal damage curve with instantaneous trip level Configurable for adjustable time delay of 10 -900 seconds,
calculated based on current transformer ratio and 120 default.
application power rating. Phase sequence sensing warning: Verifies that the genset
Loss of sensing voltage shutdown - Shutdown of genset phase sequence matches the bus prior to allowing the
will occur on loss of voltage sensing inputs to the control. paralleling breaker to close.
Field overload shutdown - Monitors field voltage to Maximum parallel time warning (power transfer control
shutdown genset when a field overload condition occurs. mode only): During closed transition load transfers, control
Over load (kW) warning - Provides a warning indication independently monitors paralleled time. If time is
when engine is operating at a load level over a set point. exceeded, warning is initiated and genset is disconnected.
Adjustment range: 80-140% of application rated kW, 0- Bus or genset PT input calibration warning: The control
120 second delay. Defaults: 105%, 60 seconds. system monitors the sensed voltage from the bus and
Reverse power shutdown (32) - Adjustment range: 5-20% genset output voltage potential transformers. When the
of Standby kW rating, delay 1-15 seconds. Default: 10%, 3 paralleling breaker is closed, it will indicate a warning
seconds. condition if the read values are different.
Reverse Var shutdown - Shutdown level is adjustable: 15- Field control interface
50% of rated Var output, delay 10-60 seconds. Default:
20%, 10 seconds. Input signals to the PowerCommand control
Short circuit protection - Output current on any phase is include:
more than 175% of rating and approaching the thermal - Coolant level (where applicable)
damage point of the alternator. Control includes algorithms
to protect alternator from repeated over current conditions - Fuel level (where applicable)
over a short period of time. - Remote emergency stop
Negative sequence overcurrent warning (46) – Control - Remote fault reset
protects the generator from damage due to excessive - Remote start
imbalances in the three phase load currents and/or power
factors. - Rupture basin
Custom overcurrent warning/shutdown (51) – Control - Start type signal
provides the ability to have a custom time overcurrent - Battle short
protection curve in addition to the AmpSentry protective - Load demand stop
relay function.
- Synchronize enable
Ground fault overcurrent (51G) – Control detects a ground
fault either by an external ground fault relay via a contact - Genset circuit breaker inhibit
input or the control can measure the ground current from - Utility circuit breaker inhibit
an external current transformer. Associated time delays - Single mode verify
and thresholds are adjustable via InPower or HMI.
- Transfer inhibit – prevent transfer to utility (in power
Paralleling protection transfer control mode)
- Retransfer inhibit – prevent retransfer to genset (in power
Breaker fail to close warning: When the control signals a
transfer control mode)
circuit breaker to close, it will monitor the breaker auxiliary
contacts and verify that the breaker has closed. If the - kW and kVAr load setpoints
control does not sense a breaker closure within an - Configurable inputs - Control includes (4) input signals
adjustable time period after the close signal, the fail to from customer discrete devices that are configurable for
close warning will be initiated. warning, shutdown or status indication, as well as
Breaker fail to open warning: The control system monitors message displayed
the operation of breakers that have been signalled to
For lean burn natural gas engine applications:
open. If the breaker does not open within and adjustable
time delay, a Breaker Fail to Open warning is initiated. - Gearbox oil pressure/temperature protection
Breaker position contact warning: The controller will - Fire fault
monitor both ‘a’ and ‘b’ position contacts from the breaker.
- Earth fault
If the contacts disagree as to the breaker position, the
breaker position contact warning will be initiated. - Differential fault
Breaker tripped warning: The control accepts inputs to - DC power supply fault
monitor breaker trip / bell alarm contact and will initiate a - Genset Interface Box (GIB) isolator open fault
breaker tripped warning if it should activate.
- Start inhibit/enable (x3)
- Radiator fan trip
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
- Ventilator fan trip Mechanical drawing
- Ventilation louvers closed
- Start system trip
- Alternator heater trip
- Alternator heater status
- Alternator winding temperature (PT100 RTDx3)
- Alternator drive end bearing temperature (PT100 RTD)
- Alternator non-drive end bearing temperature (PT100
RTD)
Output signals from the PowerCommand
control include:
- Load dump signal: Operates when the genset is in an
overload condition.
- Delayed off signal: Time delay based output which will
continue to remain active after the control has
removed the run command. Adjustment range: 0 - 120
seconds.
Default: 0 seconds.
- Configurable relay outputs: Control includes (4) relay
output contacts (3 A, 30 VDC). These outputs can be
configured to activate on any control warning or
shutdown fault as well as ready to load, not in auto,
common alarm, common warning and common
shutdown.
- Ready to load (genset running) signal: Operates when
the genset has reached 90% of rated speed and
voltage and latches until genset is switched to off or
idle mode.
- Paralleling circuit breaker relays outputs: Control
includes (4) relay output contacts (3.5 A, 30 VDC) for
opening and closing of the genset and utility breakers.
For lean burn natural gas engine applications:
- Start inhibit/enable event
- Emergency stop event
- Ventilator fan run control
- Louvre control
- Radiator fan control
- Alternator heater control
- Engine at idle speed event
Communications connections include:
- PC tool interface: This RS-485 communication port
allows the control to communicate with a personal
computer running InPower software.
- ModBus RS-485 port: Allows the control to
communicate with external devices such as PLCs
using ModBus protocol.
Note - An RS-232 or USB to RS-485 converter is
required for communication between PC and control.
- Networking: This RS-485 communication port allows
connection from the control to the other Cummins
products.
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
Six tactile feel membrane switches dedicated to control for
PowerCommand Human auto, stop, manual, manual start, fault reset and lamp
Machine Interface test/panel lamps.
Two tactile feel membrane switches dedicated to control of
HMI320 circuit breaker (where applicable).
Allows for complete genset control setup.
Certifications: Suitable for use on gensets that are
designed, manufactured, tested and certified to relevant
UL, NFPA, ISO, IEC, Mil Std. and CE standards.
LCD languages supported: English, Spanish, French,
German, Italian, Greek, Dutch, Portuguese, Finnish,
Norwegian, Danish, Russian and Chinese characters.
Communications connections include:
- PC tool interface - This RS-485 communication port allows
Description the HMI to communicate with a personal computer running
This control system includes an intuitive operator InPower.
interface panel that allows for complete genset control - This RS-485 communication port allows the HMI to
as well as system metering, fault annunciation, communicate with the main control board.
configuration and diagnostics. The interface includes
five genset status LED lamps with both internationally Mechanical drawing
accepted symbols and English text to comply with
customer’s needs. The interface also includes an LED
backlit LCD display with tactile feel soft-switches for
easy operation and screen navigation. It is configurable
for units of measurement and has adjustable screen
contrast and brightness.
The run/off/auto switch function is integrated into the
interface panel.
All data on the control can be viewed by scrolling
through screens with the navigation keys. The control
displays the current active fault and a time-ordered
history of the five previous faults.
Features
LED indicating lamps:
Genset running
Remote start
Not in auto
Shutdown
Warning
Auto
Manual and stop
Circuit breaker open (if equipped)
Circuit breaker closed (if equipped)
320 x 240 pixels graphic LED backlight LCD.
Four tactile feel membrane switches for LCD defined
operation. The functions of these switches are defined
dynamically on the LCD.
Seven tactile feel membrane switches dedicated
screen navigation buttons for up, down, left, right, ok,
home and cancel.
power.cummins.com
©2017 Cummins Inc. | S-1570 (08/17)
Software Warranty
InPower (beyond 6.5 version) is a PC-based software All components and subsystems are covered by an express
service tool that is designed to directly communicate to limited one year warranty. Other optional and extended
PowerCommand gensets and transfer switches, to facilitate factory warranties and local distributor maintenance
service and monitoring of these products. agreements are available.
Environment
The control is designed for proper operation without
recalibration in ambient temperatures from -40 ºC (-40 ºF) to
+70 ºC (158 ºF), and for storage from -55 ºC (-67 ºF) to +80
ºC (176 ºF). Control will operate with humidity up to 95%,
non-condensing.
The HMI is designed for proper operation in ambient
temperatures from -20 ºC (-4 ºF) to +70 ºC (158 ºF), and for
storage from -30 ºC (-22 ºF) to +80 ºC (176 ºF).
The control board is fully encapsulated to provide superior
resistance to dust and moisture. Display panel has a single
membrane surface, which is impervious to effects of dust,
moisture, oil and exhaust fumes. This panel uses a sealed
membrane to provide long reliable service life in harsh
environments.
The control system is specifically designed and tested for
resistance to RFI/EMI and to resist effects of vibration to
provide a long reliable life when mounted on a genset. The
control includes transient voltage surge suppression to
provide compliance to referenced standards.
Certifications
PowerCommand meets or exceeds the requirements of the
following codes and standards:
- NFPA 110 for level 1 and 2 systems.
- ISO 8528-4: 1993 compliance, controls and switchgear.
- CE marking: The control system is suitable for use on
generator sets to be CE-marked.
- EN 50081-1,2 residential/light industrial emissions or
industrial emissions.
- EN 50082-1,2 residential/light industrial or industrial
susceptibility.
- ISO 7637-2, level 2; DC supply surge voltage test.
- Mil Std 202C, Method 101 and ASTM B117: Salt fog test.
- UL 508 recognized or Listed and suitable for use on UL
2200 Listed generator sets.
- CSA C282-M1999 compliance
- CSA 22.2 No. 14 M91 industrial controls.
- PowerCommand control systems and generator sets are
designed and manufactured in ISO 9001 certified facilities.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1570 (08/17)
PI734B - Winding 13
APPROVED DOCUMENT
Technical Data Sheet
PI734B
SPECIFICATIONS & OPTIONS
STANDARDS TERMINALS & TERMINAL BOX
Stamford industrial generators meet the requirements of BS Standard generators feature a main stator with 6 ends
EN 60034 and the relevant sections of other national and brought out to the terminals, which are mounted on the
international standards such as BS5000, VDE 0530, NEMA frame at the non-drive end of the generator. A sheet steel
MG1-32, IEC60034, CSA C22.2-100, AS1359. terminal box contains the AVR and provides ample space
Other standards and certifications can be considered on for the customers' wiring and gland arrangements. It has
request. removable panels for easy access.
2
PI734B
WINDING 13
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
PROTECTION IP23
WINDING LEADS 6
MAIN STATOR RESISTANCE 0.0013 Ohms PER PHASE AT 22°C STAR CONNECTED
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
1 BEARING 2 BEARING
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.13s
T''d SUB-TRANSTIME CONST. 0.01s
T'do O.C. FIELD TIME CONST. 2.14s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd
3
PI734B
Winding 13
APPROVED DOCUMENT
4
PI734B
Winding 13
Locked Rotor Motor Starting Curve
380V 400V 416V
30
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
APPROVED DOCUMENT
5
0
0 500 1000 1500 2000 2500 3000
LOCKED ROTOR kVA
SYMMETRICAL
ASYMMETRICAL
CURRENT (Amps)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
Note 1 Note 2
The following multiplication factors should The following multiplication factor should be used to convert the values
be used to adjust the values from curve calculated in accordance with NOTE 1 to those applicable to the various
between time 0.001 seconds and the types of short circuit :
minimum current point in respect of nominal
operating voltage :
3-phase 2-phase L-L 1-phase L-N
Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380 X 1.00 Minimum x 1.00 x 1.80 x 3.20
400 X 1.05 Sustained x 1.00 x 1.50 x 2.50
416 X 1.09 Max. sustained duration 10 sec. 5 sec. 2 sec.
All other times are unchanged
The sustained current value is constant
irrespective of voltage level 5
PI734B
Winding 13 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
60Hz Star (V) 380 400 416 380 400 416 380 400 416 380 400 416
kVA 1455 1455 1455 1560 1560 1560 1625 1625 1625 1670 1670 1670
kW 1164 1164 1164 1248 1248 1248 1300 1300 1300 1336 1336 1336
Efficiency (%) 94.7 94.9 95.0 94.5 94.7 94.8 94.3 94.6 94.7 94.2 94.5 94.6
kW Input 1229 1227 1225 1321 1318 1316 1379 1374 1373 1418 1414 1412
APPROVED DOCUMENT
DIMENSIONS
6
APPROVED DOCUMENT
www.cumminsgeneratortechnologies.com
PI7B-13-TD-EN-SG-A