Professional Documents
Culture Documents
ZIV_IRS-B
ZIV_IRS-B
Self Powered
Overcurrent
Protection
M0IRSB1905I
I IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Table of Contents
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection II
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Table of Contents
M0IRSB1905I
III IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Table of Contents
2.5.4 Auxiliary Outputs and Events of the Breaker Failure Element ............................ 2.5-5
2.5.5 Breaker Failure Element Test ............................................................................. 2.5-5
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection IV
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Table of Contents
B. Parameter Configurations...................................................................................B-1
B.1 Introduction ............................................................................................................ B-2
B.2 Nominal Values ...................................................................................................... B-2
B.3 Comunications ....................................................................................................... B-2
B.4 Test Mode .............................................................................................................. B-3
B.5 General .................................................................................................................. B-3
B.6 Phase Time Overcurrent Protection ...................................................................... B-3
B.7 Negative Sequence Time Overcurrent Protection ................................................. B-4
B.8 Neutral Time Overcurrent Protection ..................................................................... B-4
B.9 Phase Instantaneous Overcurrent Protection........................................................ B-5
B.10 Neutral Instantaneous Overcurrent Protection ...................................................... B-5
B.11 Negative Sequence Instantaneous Overcurrent Protection .................................. B-5
B.12 Harmonic Blocking ................................................................................................. B-6
B.13 Breaker Failure ...................................................................................................... B-6
B.14 Open Phase ........................................................................................................... B-6
B.15 Thermal Image ....................................................................................................... B-7
B.16 Phase Undercurrent ............................................................................................... B-7
B.17 Cold Load............................................................................................................... B-7
B.18 Trips ....................................................................................................................... B-8
B.19 Oscillography ......................................................................................................... B-9
B.20 Fault Records ...................................................................................................... B-10
M0IRSB1905I
V IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1.
This instruction manual provides a technical and functional description of the relay IRS-B. The
manual may be used as technical reference in engineering, installation, commissioning, and
normal operation of the relay since the manual contains operating and handling instructions
apart from descriptions relative to technical data, function lists, logic diagrams, input and
output signals, parameter settings and detail explanation of every function.
ZIV has attempted to make this manual as accurate and easy to understand as possible.
However, ZIV cannot guarantee that it is free of errors in the manuals and it could also be
subject to possible upgrades. Therefore, ZIV would be very grateful to receive customer
comments on possible errors or recommendations. Suggestions may be sent to ZIV through
the following link.
IRS-B relays need practically no maintenance since they are self-powered by the operating
current, although, depending on the selected model, relays can be provided with conventional
auxiliary power supply. Furthermore, all relays may be powered through the front USB port and
internal battery, which makes commissioning and data retrieval easier.
1.1.2 Symbols
The following symbols can be found in the manual as well as in the back of the relay.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.1-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.1 Introduction
Relay analog inputs capture currents transmitted by instrument and protection transformers
adapting them to internal processing level of the relay. IRS-B relays include 3 analog current
inputs. Analog measurements will be processed through an analog digital converter within the
CPU board, which will send the digitalized measurements to the microcontroller.
The microcontroller carries out all the management tasks and functions of the relay, which
include, for example, the filtering and re-sampling of the measurements, protection algorithms,
control functions, data storage, distribution of data to the communications ports, etc.
Relay configurable inputs may be used to receive data from switchgear or other equipment
through hardwiring. Also, the relay has two potential-free settable input that detects continuity,
which can be allocated as external trip, therefore tripping the protection directly when activated.
The relay includes one settable electrical mechanical bistable change-over output, one settable
electrical mechanical non bistable change-over output and an energy output, 0.1J, 24V to
activate the cubicle striker.
The relay includes a front screen 128x64 with capacity for 6 lines and 20 characters per line.
Also, additional data may be obtained by 2 red activated LEDs, the first one display when the
protection has triggered and the last one informs when the level of battery is low. The operating
status of the relay can be displayed through a non-configurable tri-colour LED
(green/red/orange).
The IRS-B family includes a type B USB front port for maintenance work and a rear port for
remote communications for three wire MODBUS communications. When the relay is only
powered through B type USB port, the relay measurement, protection, I/O and LED functions
will be complete.
This relay incudes an internal battery, although in this case, if the equipment is powered though
it, their capabilities will be limited. The user only will be able to access all the protection settings
to check or modify them and has access to the fault reports and will be able to reset all the
stored information (last trip, fault reports and LEDs), the tripping functions are not being
possible nor the status of the digital input nor the analog measurements.
Relay electronic tasks will be carried out thanks to a main feature of this family of relays. The
relay can work with the operating current collected through the current inputs (18% of RC with
current through one channel, 12% of RC with current through two channels and 8% of RC with
current through three channels). Conventional auxiliary power supply may be selected if desired
and the relay may also operate powered through the USB front port. Furthermore, the relay may
be powered through the battery button, although in this case, the relay capabilities will be
limited, as mentioned in the previous paragraph.
Other differentiating features of this family of relays are low power consumption below 2.5VA
and quick booting, protection elements being operative just 100ms after detecting proper power
supply conditions.
M0IRSB1905I
1.1-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
Relay impedance curve (Burden Curve) and Switch-on-to-Fault curve (SOTF) are listed below.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.1-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.1 Introduction
3. SOTF Curve.
M0IRSB1905I
1.1-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
- Main microprocessor module, memory to manage the relay functions and HMI.
- Analog board.
- Power supply board, digital inputs and outputs, energy outputs and communications.
Figure 1.1.5 (Measurement Processing) basically outlines the measurement processing from its
capture point at the relay terminals, passing through the 16 bit analog digital converter and
other elements up to having finally the measurement available.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.1-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.1 Introduction
1.1.3.c Memory
IRS-B relays include two different types of storage memory: FRAM and EEPROM. All the
relevant data will remain in non-volatile flash memory:
- Protection settings.
- Control logic.
- Events.
- Fault reports.
- Oscillography.
- Memorized LEDs.
Furthermore, the microcontroller itself includes RAM memory and the analog input board is
provided with a second EEPROM to store analog channel calibrations.
M0IRSB1905I
1.1-7 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.2 Model Selection
4 Function
B Non-directional overcurrent relay with internal
battery and external CTs.
5 User Interface
1 Standard with alphanumeric display.
6 Rated Current
A 1A
7 Power Supply Voltage
0 None. B 110 - 230 VDC (±20%); 110 - 230 VAC (-20%/+10%).
A 24 VDC (±10%).
8 DI Auxiliary Supply Voltage
0 Free of potential
9 Inputs
1 2 Free of potential
10 Outputs and LEDs
1 1DO+ 1 bistable DO+ 1 Energy Output + 4 2 2DO NO + 1 DO NC + 1 Energy Output + 4 Configurable
Configurable LEDs. LEDs + HMI with backlight.
11 Battery
1 Lithium 3.6V
12 Rear port
0 None. A RS485.
13 Shorting CTs
0 None.
14 Enclosure/Chassis and Conformal Coat
0 3U x 19" 1/2 Rack.
15 Reserved
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.2-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.2 Model Selection
• Analog Channels
Model Analog Channels
IRS-B IA, IB, IC
M0IRSB1905I
1.2-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.3 Technical Data
24 VDC (±10%)
110 - 230 VDC (±20%) and 110 - 230 VAC (-20%/+10%)
Note: With power supply voltage from 87 to 300 Vdc the power consumption may be 0.4 W higher. The
efficiency is a function of the power supply voltage and is maximum at 125 Vdc approximately.
30xIn (for 1 s)
Dynamic limit 60xIn
Current circuits burden <2.5VA
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.3-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.3 Technical Data
Measured currents
Phase ±3% or ±30 mA (the greater)
Calculated currents
Phase - Phase ±5% or ±50 mA (the greater)
I1, I2 and I0 ±5% or ±50 mA (the greater)
Angles ±2.5º
Sampling function adjustment of analog input signals is made by means of zero pass count of the positive
sequence current. The value of the calculated frequency is used to modify the sampling frequency used by the
metering device attaining a constant sampling frequency of 16 samples per cycle. The frequency value is saved
for later use in Protection and Control tasks.
When Protection and Control tasks are readjusted in accordance with the sampling function, phasor real and
imaginary components of analog signals are calculated by means of the Fourier transform. Fourier components
are calculated by means of said Discrete Fourier Transform (DFT) using 16 sample/cycle. Using DFT this way
the magnitude and phase angle of the fundamental component at power system frequency of every analog
input signal is obtained. The rest of measurements and calculations of Protection functions is obtained based
on the fundamental components calculated by the Fourier method. DFT gives a precise measurement of the
fundamental frequency component and it is an efficient filter for harmonics and noise.
For frequencies other than the rated frequency, harmonics are not fully attenuated. For small deviations of
±1Hz this is not a problem but, in order to admit higher operating frequency deviations, the setting automatic
conversion to the sampling frequency, PLL, is included. In the absence of an adequate signal to carry out the
conversion of the sampling frequency or with the setting PLL disabled, the frequency will be converted to the
rated frequency at which the relay is operating (50/60Hz).
M0IRSB1905I
1.3-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
Overcurrent Elements
Pickup of Phases and Neutral ±5% or 30mA of the theoretical value
(the greater) (In = 1A)
Reset of Phases and Neutral 1.5 cycles for 50 and 60Hz
Measuring Times
Fixed Time ±5% of the setting or ±60 ms
(the greater)
Inverse Time Class 5 or ±60 ms (the greater)
1.3.6 Repeatability
Expressed as: ST =
I −I
A T
x100
I A
<10% for totally inductive lines
<5% for lines with an impedance angle of 70º
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.3-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.3 Technical Data
Its activation takes place when there is continuity between both pins of the input. Therefore, it allows the
connection of a potential-free metal contact. When the contact closes, the digital input is activated.
All two relay contacts have the same physical features, and both are configurable.
All three relay contacts have the same physical features, and they are all configurable.
Note: if the relay is working just in self-powered mode, these three digital outputs will operate when the
single-phase current is greater than 30% of RC (rated current) or when the sum of the three-phase
current is greater than 3 times 16% of RC. The digital outputs will be deactivated when the single-phase
current is lower than 27% of RC or when the sum of the three-phase current is lower than 3 times 14%
of RC.
M0IRSB1905I
1.3-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
1.3.13 Battery
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.3-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
1.4.1 General
The equipments are made up of the following modules:
Except for the processor module and the HMI, boards will be mounted horizontally, consisting of
pull out modules. The external connection is made through a pluggable strip in case of input,
output, FA and communications modules (supported on a flange at the rear part of the module)
for pin terminals and a non-pluggable non-shorting strip for screws and ring terminals in case of
analog inputs.
Depending on the terminal configuration, all the inputs / outputs contacts may be used, or some
may remain as spare signals.
Next figures represent the external appearance of the IRS-B models. The alphanumeric keypad
and display, the local communication port type USB, the LED targets and battery push-button
are mounted on the front part of the equipment.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
1.4.2 Dimensions
Relays are designed for panel flush mounting or in cabinet racks. Dimensions are 1/2 rack of
19" and 3 standard heights and two relays IRS-B can be placed on the same rack.
M0IRSB1905I
1.4-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
The back plate and the printed circuit board are attached to the case with self-
tapping screws. These screws must be removed before the board is withdrawn.
This operation always requires the protection to be not in service.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
- Phase A current.
- Phase B current.
- Phase C current.
- Auxiliary power supply (as a function of the selected model).
- USB port (connection to PC or external battery).
- Internal battery (the relay capabilities will be limited).
1.4.4.a Self-Powered
The IRS-B is self-powered from the current transformers used for protection functions. To this
end, standard 1A secondary current transformers are used.
The minimum values of current for booting and operation will be as follows:
M0IRSB1905I
1.4-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
• Default Display
As shown in the figure, the home screen shows line current measurements to the upper left
corner and the status of the front and remote serial communications ports and the type of power
supply being used by the relay to the upper right corner, it being, from left to right, Battery,
auxiliary power supply, self – powered and USB.
• Backlight
Depending on the relay model the display will be provided with backlight according to the
autodimming settings. The backlight will be activated when the IED is operating with auxiliary
power supply. When the IED is just operating in self-power mode, the backlight will be activated
when the single-phase current is greater than 30% of RC or when the sum of the three-phase
current is greater than 3 times 16% of RC. The backlight will never be activated when the IED is
operating in battery mode.
• Autodimming
In those models which have backlight, their screen can be configured to keep the backlight
permanently active or to switch the backlight off after a given time. The user can modify the
Autodimming settings from the relay HMI by gaining access to the Configuration menu or else
from the ZIVercomPlus®. By default, autodimming will be enabled for 2 minutes so that the
screen will turn off by itself 2 minutes after the last interaction with the relay or after booting. If
the time is set to zero, the screen backlight will never light up, and will always be off. The screen
will always be lit up when the autodimming is disabled.
When a fault occurs, the relay backlight lights up according to the autodimming settings
automatically when the relay is powered externally through USB or auxiliary power supply, and
it will be off if it is only self-powered (the IED will switch off after the trip since it will open the
breaker). Once the relay has tripped and the autodimming time has experied, the relay will
automatically switch on the backlight with the following trip just if the previous trip has been
reset.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
The keypad also provides an Enter key (in the center) Escape (ESC) and Clear (CLR):
CLR: Access button to the reset menu of memorized LEDs, last trip screen reset and fault
report reset. Fault reports to be erased are displayed on the HMI. The relay will keep in memory
all the fault reports that could be retrieved out of the front port through ZIVercomPlus®). Press
the button CLR to switch between reset menus that will be displayed only if there are data or
information subject to be erased.
To proceed with the reset, from the corresponding menu, press Enter around two seconds
until the prompt reset done is displayed on the screen. In case of resetting memorized LEDs,
the relay will activate all LEDs and will reset the ones memorized without showing any message
on the screen. If after the reset command and the activation of the 2 LEDs, any LED remains lit,
it is because the signal associated to this LED is active.
It is also possible to erase the last trip through the ZIVercomPlus® communication program by
pressing the execute button, Reset Trip, in the Control Operation menu.
M0IRSB1905I
1.4-7 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
Confirmation key
The confirmation key is used for confirming an action: after making a selection, or
after editing a setting, or else to go on to visualize the totality of the registered
data. After an operation is carried out (selection, change of settings, information,
etc.), press ← again and return to the immediately previous level.
Escape key
The ESC key is used to exit the display if you do not wish to make any modification
in the setting, or if you simply wish to exit the information display. In any case,
when you press this key the system returns to the immediately previous level.
Reset key
Press the CLR key to gain access to the memorized LED reset menu, last trip
screen reset, oscillos reset, event reset and reset of fault reports shown in the HMI.
To proceed with the reset, from the corresponding menu, press Enter around
two seconds until the prompt reset done is displayed on the screen. In case of
resetting memorized LEDs, the relay will activate all LEDs and will reset the
memories without showing any message on the screen. If after the reset command
and the activation of the 2 LEDs, any LED remains lit, it is because the signal
associated to this LED is active.
Then, a bar with an arrow (⇑) will appear on the right-hand side of the display,
which will indicate, at the same time, the existence of these first options.
The key ◄ is also used for erasing digits within a setting when modifications are
being carried out on the same. It only has this function when the setting is being
introduced.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-8
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
When this key is pressed from the default display, it gives access to the
information provided by the registration of fault reports.
The key ► is used for consulting the unit as regards the data pertaining to current,
voltage, power, etc.
The function key ► is used for rejecting the changes undertaken on the settings
(when the unit requests the confirmation of these changes) and to reject the
activation of a table of reserve settings (also when this confirmation is requested).
By pressing ▼ you can visualize the status of digital inputs and outputs from the
unit.
Once the status of digital inputs is on screen, click the function key ► to visualize
the status of digital outputs.
By pressing ◄ you confirm the changes of settings undertaken (when the unit
requests that changes need to be confirmed) or the activation of a table of settings
is confirmed (when the unit requests that changes need to be confirmed). By
pressing ◄ you can visualize the information about last trip.
Auxiliary function keys are used for editing PHASE TOC PICKUP
the new value which must correspond with
the range specified in the last line of the
ACT: 0.10 A
display. If there is an error when a value is
introduced, you must use key ◄ to erase NEW:
the same. Once the new value has been Range: 0.1 to 125
edited, press key to confirm the same
and exit to the previous menu.
Figure 1.4.5 Range Settings.
M0IRSB1905I
1.4-9 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
Masks Settings
As can be observed in the figure, the different options are presented in vertical order. Its
current setting is: an empty square or a filled square which indicates enabled () or disabled
() respectively.
The mask is modified (in the line indicated OSCILLO CHANN. MASK
by brackets) using keys ◄ (1), enable,
and ► (0), disabled.
IA []
In the event that there are more options IB
than those that can represented in one IC
screen alone, an arrow (↓) will appear at IN
the end of the last line, which will indicate
the existence of that second screen. This Figure 1.4.8 Mask Settings.
second screen appears as soon as the
last option on the first screen has been
set.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-10
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
The last trip screen will appear only if after a reset a trip has taken place.
This last trip screen will remain as default screen until it is removed through the reset menu
accessed by the CLR key. When the trip has been reset using the CLR button, you can always
access the last trip information by pressing ◄.
1.4.5.e LEDs
The relay has five LEDs on the front, one of them with a fixed function and the rest are settable.
• Fixed function LED
The LED on the upper right part of the relay with the greatest separation from the other LEDs is
used to show the device status. It is a tricolor LED that will indicate the following conditions:
These LEDs will be configured through protection settings, 8 signals being allocated to an OR
gate in combination with an AND gate that may also be assigned 8 signals to perform a simple
logic. In addition, each LED will have a Memorized setting that can be set separately per LED
so that when the setting is set to YES and the defined activation condition is deactivated after
an activation, the LED will keep turned on until a LED reset command is received. The reset
command may be carried out by the CLR key or through a digital input, a command from the
control panel or communications command if the relay is configured in the control logic to do so.
M0IRSB1905I
1.4-11 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
After pushing the button, the relay will be switched on for 15 seconds. If during that
time other kind of power supply appears (self-powering, external power supply or
frontal port) the device will automatically start using that other power supply mode.
On the other hand, if the IED is already switched on by self-powering, external
power supply or frontal port, pressing the battery button will have no effect.
When the device has been switched on with battery and the device detects that the
amount of battery is less that the minimum defined, the low battery led starts
blinking red.
When the user replaces the battery, the relay must be switch on by pressing the
battery button to reset the low battery led.
Both inputs and outputs will be configured through protection settings, signals being able to be
assigned, per input, to an OR gate and 8 signals, per output, to an OR gate in combination with
an AND gate that can also be assigned 8 signals in order to have a simple logic for the
activation of the output in question, whose close time can be timed through a setting (Enabling
Time).
- Potential-free input: This is digital input 1 and input 2. It will generate a protection trip if
continuity is detected and the input is configured to do so.
Digital inputs are filtered so that the relay sampling takes place every 2ms, 3 consecutive
samples with the same value being needed to deem it good and record the change. This
filtering is not settable.
The IED's metering elements and logic functions use Logic Input Signals in their operation.
They are listed in the tables along with the description of each of them and can be assigned to
the Physical Digital Inputs. It must be taken into account that several logic inputs can be
assigned to one physical input, but the same logic input signal cannot be assigned to more than
one physical input.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-12
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
Each protection element has a Logic Input into the module to enable or disable it through
digital input by level. This logic input is known as Element enable input..., and taking into
account its value together with the element own setting In operation, results into the type of
logic below:
The default value of the logic input signal Element Enable Input... is a “1.” Therefore, when you
do not configure at all, putting the protection elements into service depends only on the value of
the In Service setting of each of them.
Those protection functions that are put “out of service” by any of these methods will not
generate or activate any of their associated logic signals, not even those that may be configured
in the programmable logic and are directly related to these functions.
that the
Digital
Inputs
ENTRADADIGITALFISICA001 ED 2 I corresponding
input has been
activated.
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the fault report (F).
M0IRSB1905I
1.4-13 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
- Electrical mechanical change over outputs: they are the digital outputs 1, 2 and 3. They
are configurable and can be activated by internal protection signals taking into account
their settings. Depending on the model, the outputs can be normally opened or normally
closed. The standard model (option 2) will have the first two digital outputs as normally
opened and the third one as normally closed in order to be used to notify that the device
is in alarm or switched off (watchdog output). If the relay is working just in self-powered
mode, these three digital outputs will be operative when the single-phase current is
greater than 30% of RC or when the sum of three-phase current is greater than 3 times
16% of RC. The digital outputs will be deactivated when the single-phase current is lower
than 27% of RC or when the sum of the three-phase current is lower than 3 times 14% of
RC. In case When the current is less than those levels the relay will generate one event
in order to know why the DOs will not operate in case they should (DOs disabled low
current).
- The relay has 1 non-settable energy output, which is activated by the relay trip signal. It is
used to activate the breaker trip striker since it can provide 0.1J. This energy output will
not be reset staying at high level until the equipment is turned off.
Metering elements and logic elements generate in operation a number of logic outputs. These
signals or any other enabled relay signal can be used to configure the activation of each digital
output through the combination of an OR gate and an AND gate available in the protection
settings.
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the fault report (F).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-14
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
1.4.7 Communications
1.4.7.a Communications Ports
The IEDs of the IRS-B platform are provided with different types of communications ports
depending on the selected model:
- 1 Front Local Port USB type B for connection with the configuration tool.
- 1 Serial Remote RS485 Port depending on the model selection.
Technical data for these communications links can be found in Technical Data section.
Information on model ports can be found in Model Selection section.
It is worth mentioning that communications through all ports can be maintained simultaneously.
PROCOME protocol complies with IEC-870-5 standards and is used for both protection and
control information management. On the other hand, protocol MODBUS can be used for control
information management.
Additional information on the MODBUS protocol can be found in the corresponding annex,
where the mapping of signals and measurements in memory are located.
M0IRSB1905I
1.4-15 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
Every time a communications session is started through one of these ports, the relay
communications port is displayed on the upper left corner of the relay alphanumeric screen
(HMI). From left to right would be local port and serial remote port.
That indication, in case of PROCOME 3.0 protocol, remains displayed during Communications
Password TimeOut setting for the PROCOME Protocol after the last communication carried
out; in case of MODBUS protocol the message remains displayed for one minute after the last
communication.
There are different time settings for each physical communications ports (Communications
Fail Timer), which, regardless of the protocol allocated, allow to configure the period of time
with no communications activity after which the corresponding alarms (digital signals and
events) of Communications Fail Remote Port and Protocol PROCOME are generated.
- Communication Failure Indication Time (0-600 s.): maximum time between messages
without indication of communication channel blocking.
Serial Remote Port with 3 terminals has the following settings available for its configuration:
- Baud Rate: a value from 300 bauds to 57600 bauds can be chosen, default value being
38400 bauds
- Stop Bits: one of two stop bits can be selected.
- Parity: Even, Odd or No Parity (None) can be selected. No Parity is configured by
default.
- Comms Fail Timer (0-600 s.): maximum time between messages without indication of
communication channel blocking.
- Advanced settings:
1. Time
Stop Bytes Number RS-485 (0-4 bytes): it specifies the number of stop bytes
between transmit and receive when the port is configured as RS485.
2. Message modification
Number of Zeros (0-255): Number of zeros to insert as preamble to each
message.
3. Collisions
Type of Collision (NO / ECHO):
NO: Collision detection disabled.
ECHO: A collision is considered to have occurred when the characters received
do not coincide with the characters transmitted.
Number of Retries (0-3): Maximum number of retries in the transmission when
collisions are detected.
Minimum Time Between Retries (0-60000 ms): Minimum time between
retransmissions on collision detection.
Maximum Time Between Retries (0-60000 ms): Maximum time between retries
on collision detection.
Maximum Echo Delay (1-60000 ms)
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.4-16
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.4 Physical Description
- IED Address (0-254): it specifies the address of the IRS-B relay (acting as RTU or
Remote Terminal Unit) in relation to the rest of equipment that communicate with the
same master station (MTU or Master Terminal Unit).
- Communications Password Enable (YES-NO): this setting allows enabling the access
password function to establish communication with the relay through the rear port: YES
means enabling the permission and NO, disabling.
- Communications Password TimeOut (1-10 minutes): this setting allows establishing a
period of time for activating a communication blocking with the relay (whenever
communication is via the rear port): if the set time expires with no activity taking place in
the communications program, the system blocks, and the communication must be
reinitiated.
- Communications Password: the communications password allows establishing a
specific password to access communications with the relay through the rear port. This
password can have a maximum of 8 characters, which will be entered using the HMI keys
or through the communications program if communications are stablished via front port.
The only configuration setting of the MODBUS protocol is the Relay Number (0-254), which
specifies the IRS-B relay address (acting as RTU or Remote Terminal Unit) with reference to
the rest of relays communicating with the same master station (MTU or Master Terminal Unit).
This time and date may only be edited manually so that the relay may be synchronized from the
date and time assigned through HMI or by communications from the configuration tool.
M0IRSB1905I
1.4-17 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.5 Installation and
Commissioning
1.5.1 General
Improper handling of electrical equipment is extremely dangerous; therefore, only skilled and
qualified personnel familiar with appropriate safety procedures and precautions should work
with this equipment. Damage to equipment and injury to personnel can result when proper
safety precautions are not followed.
- High magnitude voltages are present in Power Supply and metering circuits even
after equipment has been disconnected.
- Equipment should be solidly grounded before handling or operating.
- Under no circumstances should the operating limits of the equipment be exceeded
(voltage, current, etc.).
- The power supply voltage should be disconnected from the equipment before
extracting or inserting any module; otherwise damage may result.
The tests defined next are those indicated for the start-up of an IED. They do not necessarily
coincide with the final manufacturing tests to which each manufactured equipment is subjected.
The number, the type and the specific characteristics of the acceptance tests are model
dependent.
1.5.2 Accuracy
The accuracy of the measuring instruments and test source signals (auxiliary power supply
voltage, AC currents and AC voltages) is key in electrical testing. Therefore, the information
specified in the Technical Data section (2.1) of this manual can only be reasonably verified with
test equipment under normal reference conditions and with the tolerances indicated in the UNE
21-136 and IEC 255 standards in addition to using precision instruments.
It is extremely important that there be little or no distortion (<2%) in the test source signals as
harmonics can affect internal measuring of the equipment. For example, distortions will affect
this IED, made up of non-linear elements, differently from an AC ammeter, because the
measurement is made differently in both cases.
It must be emphasized that the accuracy of the test will depend on the instruments used for
measuring as well as the source signals used. Therefore, tests performed with secondary
equipment should focus on operation verification and not on measuring accuracy.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.5-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.5 Installation and Commissioning
1.5.3 Installation
• Location
The place where the equipment is installed must fulfill some minimum requirements, not only to
guarantee correct operation and the maximum duration of useful life, but also to facilitate
placing the unit in service and performing necessary maintenance. These minimum
requirements are the following:
M0IRSB1905I
1.5-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
- The unit is in good physical condition, mechanical parts are securely attached and no
assembly screws are missing.
- The unit model number and specifications agree with the equipment order.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.5-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.5 Installation and Commissioning
1.5.5 Tests
1.5.5.a Isolation Test
While testing for isolation of switchgear and external wiring, the IED must be disconnected to
avoid damage in case the test is not performed properly or if there are shorts in the harness,
since the manufacturer has performed isolation testing on 100% of the units.
• Common Mode
All the terminals of the IED must be short-circuited, except those that relate to the power supply.
The enclosure ground terminal must also be disconnected. Then 2000 Vac are applied between
the interconnected terminals and the metal case for 1 min or 2500 Vac during 1s between the
terminal group and the metal enclosure. When the IED has the inputs, outputs and converters
expansion card, terminals of the transducers do not need to be short-circuited (See External
Connection Schemes).
• Between groups
The isolation groups are made up of the current and voltage inputs (independent channels),
digital inputs, auxiliary outputs, trip and close contacts and power supply. Refer to the
connection’s schematic to identify the terminals to group for performing the test. Then 2500
VAC are applied during 1 sec. between each pair of groups. For the transducers test 1000 VAC
are applied during one second between this group and all the rest.
There are internal capacitors that can generate high voltage if the test
points are removed for the insulation test without reducing the test voltage.
M0IRSB1905I
1.5-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
VDC PROT
B3(+) – B2(-)
And check that the “in operation” LED activates switching blinking green and the relay screen
displays the line current measurements.
• USB
Connect the relay through the USB port or external battery and check that the “in operation”
LED activates switching blinking green and the relay screen displays the line current
measurements.
• Self-Powered
Inject 1A into the relay through one phase and check that the “in operation” LED begins to blink
a green color to indicate the correct running of the device and the relay screen displays the line
current measurements.
• Battery
Press the button of battery and check that the relay screen shows the main menu with the date,
the hour, the name of the relay and the indicator of the battery supply situation. Note that in this
condition no LED activates.
Note: if high currents must be checked, these will be applied for the shortest possible time; for example, less
than 8 seconds for 20A. In order that phase angles can be displayed, the phase A current must be applied and
the injected current value must exceed the setting to this end. To measure the frequency, current must be
injected to any phase with a value above 0.1 times the rated current since frequency calculations are made
based on the number of zero crossings of the positive sequence current.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.5-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.6 Onload Test
1.6.1 Introduction
The objectives of Onload Test are the following ones:
- Confirm that the external wiring of the current analog input channels is correct.
- Check the polarity of the current transformers.
- Check the current measurements (module and angle).
In order to proceed with the test, primary injections will be done to check the polarity and
transformation ratios. These tests can only be carried out if there are no restrictions related to
the energization of the bay and all the other devices of the bay where the protection relay is
located have already been commissioned.
Before starting the tests, check that all the test leads have been removed and ensure that the
external wiring is properly connected (it is possible that during the commissioning tests external
wirings have been disconnected).
Check that when injecting a balanced system, the current which is flowing through the neutral
circuit of the transformer is negligible.
Ensure the current polarity is the correct one measuring the phase angle between the current
and the voltage which are being injected.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.6-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.7 Standards and Type Tests
The equipment satisfies the standards indicated below. When not specified, the standard is
IEC-60255.
1.7.1 Insulation
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.7-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.7 Standards and Type Tests
M0IRSB1905I
1.7-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 1. Description and Start-Up
The models comply with the EEC 89/336 standard of electromagnetic compatibility.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 1.7-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
1.8 Schemes and Drawings
TITULO:
TITLE:
"ATENCION" "WARNING" PROYECTO / PROJECT:
El contenido del presente documento es propiedad de ZIV Aplicaciones y Tecnología, y no puede
ser reproducido ni copiado sin la expresa autorización escrita de ZIV Aplicaciones y Tecnología.
The contents of this document belong to ZIV Aplicaciones y Tecnologia and may not be NUM.:
reproduced or copied without express written authorization from ZIV Aplicaciones y Tecnologia.
Fecha / Date Nombre / Name
Hoja / Sheet:
Dibujado / Drawn
Continua en Hoja:
Aprobado / Approved Continued on sheet:
Chapter 2.
In case of instantaneous elements, every protection element is provided with a settable output
timer, which allows for optional timing of the instantaneous elements whereas in the time
elements, the pickup activation enables the time function, which will perform the integration of
the measured values. This integration is carried out by applying increments, as a function of the
input current, to a counter whose timeout determines the time element operation.
In time elements, when inverse time curve characteristic is used, two reset systems are
available: Instantaneous and Disk Emulation. The Instantaneous option is adequate for
applications requiring coordination with static relays, whereas the Disk Emulation option can
be used in cases in which the relay must be coordinated with electromechanical protections,
mainly when they are located towards the system power source.
If the Instantaneous reset system is selected, the pickup is reset when the measured value
goes down to 1 time the setting value. Drop of the measured RMS value below the pickup
setting value results in a quick integrator reset. For output activation, pickup must be active
during the entire integration time; any integrator reset brings the integrator back to initial
conditions, so that new activations start timing from zero.
If the Disk Emulation reset system is selected, the relay uses a reset process based on the
decrements of a timer that starts when the current drops below 100% of the element pickup
setting, using the reset curve adequate to the trip characteristic used.
M0IRSB1905I
2.1-3 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Trip blocking inputs must be programmed before this blocking logic can be used.
Another programmable input exists that can turn a given time overcurrent element into
instantaneous. Said input is called Timer Disable and is available for all time-delayed elements.
In order to prevent overcurrent elements from operating upon said magnetizing currents,
overcurrent elements include the function Harmonics Blocking. In order that a distinction can
be made from a fault current and an inrush current, both with high fundamental frequency
component, the 2nd harmonic components are analysed, such that harmonic blocking elements
serve as inputs to overcurrent elements when they are so configured.
See the section corresponding to the Harmonics Blocking for more information.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
IEC CURVES
Inverse curve Inverse curve + time limit
Very inverse curve Very inverse curve + time limit
Extremely inverse curve Extremely inverse curve + time limit
Long time inverse curve Long time inverse curve + time limit
Short time inverse curve Short time inverse curve + time limit
IEEE CURVES
Moderately inverse curve Moderately inverse curve + time limit
Very inverse curve Very inverse curve + time limit
Extremely inverse curve Extremely inverse curve + time limit
US CURVES
Moderately inverse curve Moderately inverse curve + time limit
Inverse curve Inverse curve + time limit
Very inverse curve Very inverse curve + time limit
Extremely inverse curve Extremely inverse curve + time limit
Short time inverse curve Short time inverse curve + time limit
The RI Inverse Curve may be added to the above curves, mainly used with electromechanical
relays.
Time multiplier setting is the same as for IEC, IEEE, US and RI Inverse curves: range is 0.01 to
10 times.
M0IRSB1905I
2.1-5 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Curve types with Time Limit are regular time delayed functions with a time threshold, so that no
trip takes place before the specified time. This results in that beyond a specified time the
tripping curve turns into a horizontal straight line. This operate time limit coincides with the time
setting used in the Fixed Time option. Three different operating ways can result as a function of
the curve selected and the Fixed Time setting.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
Therefore, it could be said that whenever the Fixed Time setting value is above the time
defined by the curve for a current 1.5 times the setting value, the operating time will be limited to
1.5 times, the trip curve being turned into a horizontal straight line.
Curves without Time Limit are not affected by the Fixed Time setting of the element, although
the note below must be taken into account to consider full operating function.
Each trip curve IEC, IEEE and US account for a characteristic that emulates the reset time of
electric magnetic relay disks for those relays provided with Reset Type setting. The equation for
the reset duration is as follows:
where tr is the characteristic constant that varies
tr
t RESET = index × as a function of the selected trip curve.
2
l tr values are shown in the table below:
1 − I
pickup
M0IRSB1905I
2.1-7 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
When Inverse RI curve is selected, pick up resets instantaneously regardless the Reset Type
setting.
It should be noted that although curves are defined in the graphics for a given input of up to 20 times the
tap (the tap being the time element pick up setting), they will tend to be horizontal from 32 times the tap,
although, taking into account the analog input saturation, it is not always possible to guarantee this
range as shown below.
Bear in mind that current channel saturation limits are 32 A for phases. Based on these limits, the “times
the tap” for which curves are effective is a function of the setting:
Saturation Limit
If > 32 ,
Element Setting
curve operation is guaranteed for elements with said setting over the entire tap range (up to 32
times the setting).
Similarly, if a phase element is set with a value of 2A, as 32 times the setting is higher than the
saturation limit (64A > 32A), the curve will be effective up to 16 times the tap (32/2=16) so that, for any
higher value, the pickup time will be that of 16 times the tap instead of keeping different time values up
to 32 times the tap.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-8
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
0.14
t = × Index I measured
0.02 I =
IS −1 S I pickup
M0IRSB1905I
2.1-9 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
t =
13.5
x Index I measured
I =
IS −1 S I pickup
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-10
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
80
t = x Index I measured
2 I =
IS −1 S I pickup
M0IRSB1905I
2.1-11 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
t=
120
x Index I measured
I =
IS − 1 S I pickup
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-12
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
0.05
t = x Index I measured
0.04 I =
IS −1 S I pickup
M0IRSB1905I
2.1-13 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Figures 2.1.9, 2.1.10, 2.1.11, 2.1.12, 2.1.13, 2.1.14, 2.1.15 and 2.1.16 present the inverse
curves according to the IEEE and US Standards.
0.0515 I measured
=t 0.114 + x Index I =
IS
0.02
− 1 S I pickup
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-14
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
19.61 I measured
=t 0.491 + x Index I =
IS
2
− 1 S I pickup
M0IRSB1905I
2.1-15 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
28.2 I measured
=t 0.1217 + x Index I =
IS
2
− 1 S I pickup
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-16
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
0.0104 I measured
=t 0.0226 + 0.02 x Index I =
IS − 1 S I pickup
M0IRSB1905I
2.1-17 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
5.95 I measured
=t 0.180 + x Index I =
IS
2
− 1 S I pickup
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-18
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
3.88 I measured
=t 0.0963 + 2 x Index I =
I S − 1 S I pickup
M0IRSB1905I
2.1-19 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
5.67 I measured
=t 0.0352 + x Index I =
IS
2
− 1 S I pickup
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-20
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
0.00342 I measured
=t 0.00262 + x Index I =
IS
0.02
− 1 S I pickup
M0IRSB1905I
2.1-21 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
1
t = x Index
1 I measured
I =
0.339 − 0.236 ⋅ S I pickup
I
S
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-22
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
IA →
IB →
IC → → PU_TOC (per phase)
51P → TRIP_TOC (per phase)
INBLK_TOC PH → PHSPTOC → TRIP_TOCM (per phase)
ENBL_TOC_PH →
HARM_2_BLK →
M0IRSB1905I
2.1-23 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Once the element has picked up, the trip can be instantaneous or timed if used is made of the
applicable time setting so as to adjust its selectivity taking into account other protections or
relays upstream or downstream.
The instantaneous element will be reset when the current value drops to 1 time the setting value
and will operate in accordance with the blocking, enable, harmonics, saturation and direction
signals explained in Common Principles section. Meanwhile, the time element will be reset
either at 1 time the setting value or using a reset curve adequate to the trip characteristic used
as a function of the Reset Type setting as has been explained in Operation and Reset section.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-24
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
2.1.2.d Application
The phase overcurrent element is in charge of detecting fault currents flowing between two or
more phases in three phase power systems. The fault current can flow between the conductors
or between the conductors and ground, therefore, phase to phase, phase to ground and three
phase faults can be detected, phase to phase faults being typically more severe.
An example of a fault detected by the phase overcurrent element could be the contact between
two or more conductors due to a branch falling on a line.
The time set overcurrent element is of common use as backup for transformer differential and
distance protections, although it is also used as main element in medium voltage lines and
specific applications to detect close onto fault or in ring systems, among many others.
Starting values:
- CT: 1500/1.
- Load current: 1470 A.
- Lowest protection downstream: 400 A.
Relay settings must take into account both the load current and the reset current, such that it
operates only upon real faults. As the element picks up at 1.05 times the pickup setting, this
being exactly the minimum fault current value, the element will be set directly with this value,
referred to the secondary, as both the protection element and the settings are referred to the
secondary. Therefore, the pickup setting value must a minimum of 0.98 A.
When the relay is to be coordinated with other protections, their trip times must match as much
as possible, setting a proper definite time for each case.
M0IRSB1905I
2.1-25 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Protection / Overcurrent / Time Overcurrent / Phase Time Overcurrent (1, 2 and 3 Units)
Communications Program Range Step Default
Phase TOC Enable YES / NO NO
Phase TOC Pickup (0.1 - 30) In 0.01 A In
Phase TOC Curve See list of curves Fixed Time
Phase TOC Dial 0.01 - 1.5 (IEC) 0.01 1
0.01 - 10 (IEEE/US/RI) 0.01 1
Phase TOC Definite Time 0.05 - 300 s 0.01 s 0.05 s
Reset Type 0: Instantaneous Instantaneous
1: Induction Disk Emulation
Phase TOC Harm Blocking YES / NO NO
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-26
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
2.1-27 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-28
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
Table 2.1-3: Auxiliary Outputs and Events of the Phase Overcurrent Modules
Name Group Description Vis. Function
TRIP_IOC_A1 Phase A Instantaneous Unit 1 Trip I,F
TRIP_IOC_B1 Phase B Instantaneous Unit 1 Trip I,F
TRIP_IOC_C1 Phase C Instantaneous Unit 1 Trip I,F
TRIP_IOC_A2 Phase A Instantaneous Unit 2 Trip I,F
In low ranges pickup and reset interval can be extended up to X ± (5% x In) mA.
M0IRSB1905I
2.1-29 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
• Operating Times
For testing, at least one relay output must be configured with the trip signals of the element
under test. The output configuration will be carried out with the ZIVercomPlus® changing the
protection settings of the output to be used as shown in the Inputs, Outputs and LEDs
Configuration section.
A current equal to 1.5 times the selected pickup setting value will be applied. The operating time
must match the indication on the table and the reset time will be equal to 1.5 cycles (30ms for
50Hz and 25ms for 60Hz) after stopping the injection.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-30
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
→ PU_IOC_N
50N → TRIP_IOC_N
INBLK_IOC N → NPIOC → TRIP_IOCM_N
ENBL_IOC_N →
HARM_2_BLK →
I0 →
→ PU_TOC_N
51N → TRIP_TOC_N
INBLK_TOC N → NPTOC → TRIP_TOCM_N
ENBL_TOC_N →
HARM_2_BLK →
M0IRSB1905I
2.1-31 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Once the element has picked up, the trip can be instantaneous or timed if used is made of the
applicable time setting so as to adjust its selectivity taking into account other protections or
relays upstream or downstream.
The instantaneous element will be reset when the current value drops to 1 time the setting value
and will operate in accordance with the blocking, enable, harmonics, saturation and direction
signals explained in Common Principles section. Meanwhile, the time element will be reset
either at 1 time the setting value or using a reset curve adequate to the trip characteristic used
as a function of the Reset Type setting as has been explained in Common Principles section.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-32
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
2.1.3.d Application
Fault currents flowing to ground are detected by the neutral overcurrent element. The neutral
overcurrent element detects ground faults through the current calculated from the sum of phase
currents, namely, it does not use a magnitude directly read by a measurement transformer as is
the case for ground elements.
In most cases, the system will not be totally balanced and, thus, a small stable fault current flow
is permitted. Therefore, the residual current observed by the IED at the faulty bay can be slightly
higher, which implies that its settings must be based on actual current levels where possible.
M0IRSB1905I
2.1-33 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
I N = IA + IB + IC
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-34
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
current elements.
(50, 50N, 50Q)
Outputs
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
2.1-35 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
In low ranges pickup and reset interval can be extended up to X ± (5% x In) mA.
• Operating Times
For testing, at least one relay output must be configured with the trip signals of the element
under test. The output configuration will be carried out with the ZIVercomPlus® changing the
protection settings of the output to be used as shown in the Inputs, Outputs and LEDs
Configuration section.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-36
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
A current equal to 1.5 times the selected pickup setting value will be applied. The operating time
must match the indication on the table and the reset time will be equal to 1.5 cycles (30ms for
50Hz and 25ms for 60Hz) after stopping the injection.
M0IRSB1905I
2.1-37 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
→ PU_IOC_NS
50Q → TRIP_IOC_NS
INBLK_IOC NS → NGSPIOC → TRIP_IOCM_NS
ENBL_IOC_NS →
HARM_2_BLK →
I2 →
→ PU_TOC_NS
51Q → TRIP_TOC_NS
INBLK_TOC NS → NGSPTOC → TRIP_TOCM_NS
ENBL_TOC_NS →
HARM_2_BLK →
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-38
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
Once the element has picked up, the trip can be instantaneous or timed if used is made of the
applicable time setting so as to adjust its selectivity taking into account other protections or
relays upstream or downstream.
The instantaneous element will be reset when the current value drops to 1 time the setting value
and will operate in accordance with the blocking, enable, harmonics, saturation and direction
signals explained in Common Principles section. Meanwhile, the time element will be reset
either at 1 time the setting value or using a reset curve adequate to the trip characteristic used
as a function of the Reset Type setting as has been explained in Common Principles section.
M0IRSB1905I
2.1-39 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
2.1.4.d Application
The Negative Sequence Overcurrent element detects unbalanced currents. Any type of fault
(phase-phase or phase-ground) generates negative sequence current, so this element offers
higher sensitivity, this sensitivity being lost in phase overcurrent elements as their settings must
be above the maximum load value. Ground elements, mainly the Sensitive Ground elements,
give good sensitivity, but they may not be able to detect certain types of faults.
The Negative Sequence Overcurrent element may be used as a system anomaly alarm
indication, or as a backup protection element, which may provide higher sensitivity upon
resistive faults where phase elements do not operate, or that may detect ground faults, which,
because of the type of connection, a neutral or ground element would not detect, as could be
the case of a ground fault in a star winding operating with a ground element in the delta winding.
As the negative sequence element is normally used as a backup element, the time delay setting
will normally be high, it being higher than for the main protection elements: Phase, Neutral,
Open Phase, Thermal Image, etc. elements
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-40
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
I A + I B ⋅1∠240° + I C ⋅1∠120°
I2 =
3
Instantaneous Unit 2
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
2.1-41 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-42
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.1 Overcurrent Elements
In low ranges pickup and reset interval can be extended up to X ± (5% x In) mA.
• Operating Times
For testing, at least one relay output must be configured with the trip signals of the element
under test. The output configuration will be carried out with the ZIVercomPlus® changing the
protection settings of the output to be used as shown in the Inputs, Outputs and LEDs
Configuration section.
M0IRSB1905I
2.1-43 IRS-B: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
A current equal to 1.5 times the selected pickup setting value will be applied. The operating time
must match the indication on the table and the reset time will be equal to 1.5 cycles (30ms for
50Hz and 25ms for 60Hz) after stopping the injection.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.1-44
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.2 Open Phase Detector
2.2.1 Identification
Description of the protection unit ANSI/IEEE C37.2
Open Phase Detector 46
The operation of this function is conditioned to the position of the breaker and to the level of the
positive sequence current: if the breaker is open or the positive sequence current is below the
Min. Load Open Phase setting, the element will be disabled. In addition, the function is
annulled when any one of the phase or neutral time or instantaneous elements picks up.
Pickup occurs when the value measured exceeds 1.02 times the pickup setting and resets at
0.97 times the pickup setting.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.2-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.2 Open Phase Detector
2.2.4 Application
The function of the Open Phase element is to detect a fallen or broken conductor. It uses the
ratio between the negative sequence current, I2, and the positive sequence current, I1. When
the load is normal and balanced, this ratio is zero or very low, but when a severe load fault
occurs, an imbalance raises this ratio.
To avoid trips or pickups with no load or very low loads, this function is inhibited when the
positive sequence current I1 value is below the Min. Load Open Phase setting.
I A + I B ⋅1∠240° + I C ⋅1∠120°
I2 =
3
I A + I B ⋅1∠120° + I C ⋅1∠240°
I1 =
3
M0IRSB1905I
2.2-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
count.
Outputs
TRIP_OPH Open Phase Detector Trip I,F Trip of the Open Phase
Detector
Trip Protection
Outputs
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.2-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.2 Open Phase Detector
Ia = 1/0º and Ib = 1/60º (it is understood that these angles are inductive).
After setting the element to 0.2 I2/I1, it must not be picked up. After increasing the phase B
current, the element must pick up (the pickup flag at "1") with a current value in phase B
between 1.493 Aac and 1.348 Aac.
With the trip time set to 10 s, a current of 2 A / 60º in phase B is applied. A trip must be initiated
between 10.1 s and 9.9 s. Also the trip contacts must close.
It will also be checked that by adjusting the unit to 0.2 I2/I1 and the Min. Load Open Phase to
1.2 A, if we apply Ia = 1/0º and Ib = 2/60º, the unit should not operate. If, under the same
conditions, the Min. Load Open Phase is set to 0.8 A, the unit should pick up.
M0IRSB1905I
2.2-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.3 Phase Undercurrent Element
2.3.1 Identification
Description of the protection unit ANSI/IEEE C37.2
Phase Undercurrent Element 37
Element pickup is subject to breaker status, which must be closed. In this case, the element
compares the pickup setting with the operating magnitude that, as a function of the setting
Current Select, will be the positive sequence current or the lowest of the phase currents. If the
operating magnitude is less than the setting (0.98 times) for a set time, the element is activated.
2.3.4 Application
Undercurrent function is used in motor applications to detect a drop in current as a result of load
reduction, as is the case for pump motors. If current is below a setting value for a given time
while the motor is in operation, the element sends a trip signal.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.3-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.3 Phase Undercurrent Element
I A + I B ⋅1∠120° + I C ⋅1∠240°
I1 =
3
ENBL_MIN_I Enable Phase Undercurrent Unit I Activation of this input puts the
Enabling Commands
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
2.3-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
Keep current through two phases above element pickup setting and lower the current of the
other phase. Check that, for settings in Table 2.3-4, the pickup state flag of the Undercurrent
element sets to a permanent "1", when the current reaches a value between VA_MIN and
VA_MAX.
• Operating Times
Set timer to 0 s and check that operating time is less than 30 ms.
Repeat test with X s timer setting and check that measured time is within the margin X ±1% or
±20 ms.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.3-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.4 Thermal Image
2.4.1 Identification
Description of the protection unit ANSI/IEEE C37.2
Thermal Image Unit 49
The algorithms are based on modeling the heating of a resistive element when running an
electric current through it. The effect of radiation is not considered (since the impact is
considered negligible given the temperatures reached by the elements to be protected, less
than 400 ºC), nor are heat dissipation sources other than that deriving from the Joule effect.
Cooling of the equipment is also simulated if the current value returns to the nominal value after
a relatively short overload period.
The Thermal Image Unit does not have a threshold at which pickup starts: it is always “picked
up”. The trip time depends on the current flowing from a given instant up to when the
temperature limit is reached and the temperature value at a specific instant. The prior
temperature depends on what has happened before, the measured current and the time
applied.
The differential equation that controls any thermal phenomenon is the following:
dθ
I 2 = θ +τ ⋅
dt
Where:
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.4-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.4 Thermal Image
Temperature values (θ) are always stored in case there is a failure in the IED's power supply.
There is a Thermal Memory Enable setting that you can set to YES so that the initial
temperature value will be the stored one whenever the IED is reinitialized. The saved value can
be reset by activating the digital signal Thermal Image Dropout Input.
This element is prepared to protect lines, motors or transformers from overheating. The type to
be protected can be selected through the setting Type of Device. According to this selection,
the element will use different ways to calculate the thermal status.
Lines. In case of lines, the square of the maximum current is taken as measurement
current (the element will use the maximum current flow, namely, the maximum value
between phase A, phase B or phase C currents). It has two time constants, one for
heating (as long as there is current flow, setting Constant 1) and one for cooling (when
the positive sequence current is below 0.1 A, setting Constant 2).
Motors. For motors, the measuring current used is the sum of the square of the positive
sequence and the square of the negative sequence. This last value is multiplied by a
scaling factor (Motor Scaling Factor). It has two time constants, one for motor stopped
(when the positive sequence is under 0.15 times the maximum current, Constant 1
Setting) and another for motor running (when the positive sequence is above 0.30 times
the maximum current, Constant 2 Setting)
Transformers. In case of transformers, the square of the current flowing through the
reference winding current is taken as measurement current (the element will use the
maximum current flow, namely, the maximum value between phase A, phase B or phase
C currents of the reference winding). It has two time constants, one in case it is ventilated
(Constant 1) and one in case it is not (Constant 2). They are switched from one to
another by means of a digital input named Thermal Constant Switched. By default, the
time constant is With Ventilation. It can be changed by configuring the Thermal
Constant Switched input. When this input is activated, the constant switches to Without
Ventilation.
M0IRSB1905I
2.4-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
When the element is using the maximum current flow, it will use the maximum fundamental
current RMS value for the calculations according to the setting Type of Magnitude.
The thermal element estimates the thermal status in each case (line / motor / transformer) and,
when this reaches the set Alarm level, it activates the signal Thermal Image Alarm. When it
reaches the level equivalent to the level obtained by steady state Imax flow (Max. Operating
Current), a trip output is issued.
The value of θ is calculated as a % of the maximum value. The Thermal Image Trip output is
activated when the corresponding θ value reaches the maximum current:
θtrip = Imax 2
Thermal Image Trip signal resets taking into account the setting Reset Threshold:
Reset Threshold(%)
θ Reset_trip = θtrip
100
Thermal Image Alarm output activates when θ reaches a value defined by the setting Alarm
Level:
AlarmLevel(%)
θalarm = θtrip
100
The Thermal Image Alarm signal resets when θ descends below 95%:
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.4-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.4 Thermal Image
2 2
I −Ip
t = τ ⋅ Ln 2 2
I − Imax
Where:
I: Measured current
used by the element.
Ip: Steady state pre-
load current before
applying the overload.
τ: Is the cooling and
heating time constant
(Constant 1 and
Constant 2 settings).
Imax:Value of the
maximum admissible
sustained current.
Max. Operating
Current Setting.
As τ is expressed in
minutes, the result of the
equation, namely, the
calculated time, is also in
minutes.
M0IRSB1905I
2.4-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
The protections that are regularly used in these cases use overcurrent, causing trips both
instantly and after a timed sequence using inverse “current / time” characteristics or set fixed
times. However, in some applications, this protection system presents certain limitations.
An example might be a system with two transformers set in parallel powering the same bus,
each of them running at loads below the rated load. If one of the transformers is out of service,
the other transformer steps in and takes on the full load, very likely running at a load above its
rated load.
With an overcurrent protection it can be disconnected in a very short period of time even when
power transformers are designed to run with excess loads for several minutes without suffering
any damage. During this period of time, there is no possibility of performing any action to reset
the situation.
Given its operating principle, the Thermal Image unit is highly indicated in these types of
situations. In general, it can be said that this function is complementary to other protection types
for cables or all kinds of machines (transformers, generators, etc.).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.4-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.4 Thermal Image
I A + I B ⋅1∠120° + I C ⋅1∠240°
I1 =
3
I A + I B ⋅ 1∠240° + I C ⋅ 1∠120°
I2 =
3
M0IRSB1905I
2.4-7 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.4-8
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.4 Thermal Image
Image Unit.
Outputs
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
2.4-9 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
An example: a time constant without ventilation of 0.5 minutes and a maximum current of 5 A. A
current of 6 A is injected in phase A of the first winding. The time transpired until the unit trips
must be between 33.05 s and 38.18 s.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.4-10
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.5 Breaker Failure Unit
2.5.1 Introduction
The Breaker Failure unit detects malfunctions following trip commands and generates a signal
to trip other breakers to clear the fault. The operation of this function is outlined in the block
diagram of Figure 2.5.1.
A trip command generated by the IED's internal protection elements (TRIP) or an external
protection device (EXT_TRIP) activates The Breaker Failure Initiate signal (I_BF).
When the I_BF signal is activated and current is still detected by the unit (P_CUR signal), starts
the counter for the breaker failure time delay (T_BF). If T_BF times out before I_BF resets,
indicating that the initial breaker failure conditions are no longer present, or P_CUR resets,
indicating that the unit no longer detects current, the BF output will activate.
The reset of either of the signals, I_BF or P_CUR, will immediately reset the timer, impeding the
generation of the BF signal.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.5-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.5 Breaker Failure Unit
In models that include retrip function, the PU_BF signal not only starts timer T_BF but also
starts timer T_RETRIP. Once this last timer times out, signal RETRIP activates aiming at
issuing a new trip command to the failed breaker before generating a Breaker Failure
command (BF). Obviously, the retrip time setting must be less than the breaker failure time. The
IEDs include, also, detection of breaker failure with no phase overcurrent. Trip signals, whether
from the same relay or external relay, which would produce the initiation of the breaker failure,
can be activated without the pickup of the phase current detection elements. This situation can
take place, in general, upon any type of disturbance tripped by elements independent from the
measured current, such as voltage elements, frequency elements, transformer own protection
elements etc. In this case, breaker failure detection is made based on breaker contact position:
when logic input No Load Breaker Failure Initiation (IN_BF_NLOAD) activates, the breaker
remaining closed, the timer T_BF_NLOAD will start. When said timer times out, signal BF
activates. The No Load Breaker Failure Input can be configured with the trip of the
transformer own protection elements, frequency elements, voltage elements, etc. The pickup of
the no load breaker failure element also causes a breaker to retrip (see figure 2.5.1).
Signal P_CUR will be activated while the value of any current is above the pick-up level set for
any of the phases or neutral currents. The most important characteristic of these current
detectors is their fast reset time to stop the timer as soon as the breaker has opened and made
the current disappear, not allowing the erroneous activation of BF.
The operating principle is based not only on the measurement of the RMS value but on the
measurement of instantaneous values. This last principle significantly reduces the reset time.
In order to detect as fast as possible that the current value is going down to zero, the device will
not check the RMS value but will check if at least 3 instantaneous and consecutive sampled
values are under the phases and neutral breaker failure pick-up value. If reset time would be too
long there would be high risk of non-stopping duly on time the counter and then cause false
trips on other circuit breakers different from the one on the faulty circuit, even when the current
went to zero.
To be able to use the external operation signal (EXT_TRIP) as part of this function, you must
program one of the IED's status contact inputs to be connected to this signal. Otherwise, the
EXT_TRIP signal will default to a logic "0". The same applies to the No Load Breaker Failure
Initiation Input (IN_BF_NLOAD). Likewise, the external use of the logic output of Breaker
Failure (BF) requires programming the connection between it and one of the auxiliary contact
outputs.
M0IRSB1905I
2.5-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.5-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.5 Breaker Failure Unit
The phase and neutral instantaneous overcurrent pickups are set to 0.5 A and their time delay
to zero. The reset levels of the breaker failure units are set to the desired current reset and
operating time values. A trip is provoked by applying a 1 A current phase to neutral and
maintaining the current after the phase and neutral units trip. The breaker failure element will
operate in a period of time between ±1% and ±20 ms of the set value. To verify the operation of
this unit, an auxiliary output is configured as Breaker Failure.
The current is gradually reduced until the breaker failure unit reaches a stable reset. This must
occur for a value between ±1% of the set value.
M0IRSB1905I
2.5-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.6 Harmonic Blocking
2.6.1 Identification
Description of the Protection Unit ANSI/IEEE C37.2
Harmonic Blocking 68
In order to avoid the operation of overcurrent elements under the mentioned magnetizing
currents, the Harmonic Blocking function is included. In order to differentiate between a fault
current and an inrush current, both with high fundamental component, the 2nd harmonic
component is analyzed.
Energizing currents have a high 2nd harmonic content. Blocking by 2nd harmonics is enabled
through the setting 2nd Blocking Enable. The 2nd harmonic content is calculated for the three
phase currents and neutral current. When the ratio between the 2nd harmonic current and the
fundamental current exceeds, in percentage, the setting 2nd Blocking Pickup, the signals
Phase A Blocking by 2nd Harmonic, Phase B Blocking by 2nd Harmonic and Phase C
Blocking by 2nd Harmonic will activate, as a function of the type of current analyzed. The
signals Phase A Blocking by Harmonics, Phase B Blocking by Harmonics, Phase C
Blocking by Harmonics and Sensitive Neutral Blocking by Harmonics are OR functions of
the corresponding blocking signals by 2nd harmonic.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.6-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.6 Harmonic Blocking
All overcurrent elements include the setting Harmonic Blocking. When this setting is set to
YES, the applicable overcurrent element will be blocked by the corresponding blocking by
harmonics signal. The Phase A overcurrent element will be blocked by signal Phase A
Blocking by Harmonics, the phase B overcurrent element will be blocked by signal Phase B
Blocking by Harmonics, etc.
The calculation of the ratio harmonic current / fundamental current will only be carried out when
the fundamental current exceeds the setting Minimum Current (phase or neutral). This setting
must equal the minimum pickup level setting of the applicable overcurrent element (phase or
neutral).
For phase overcurrent elements, there is the possibility to enable a Cross-Blocking logic. This
logic allows for extending the blocking by harmonics to the rest of phases when at least in one
phase (OR option) or in two phases (2 out of 3 option) the harmonic level is high. The cross-
blocking logic keeps the safety under inrush situations when phase harmonic content is too low.
The 2 out of 3 option has a better response than the OR option. When the energized
transformer winding has the neutral connected to ground and another winding is delta
connected, the logic 2 out of 3 will never be met if the transformer is closed onto fault (internal
fault at the same time than the inrush current). If it is a single phase fault, the zero sequence
current from the ground connection will substantially reduce the harmonic content of the healthy
phases. If it is a polyphase fault the 2 out of 3 option will not be met either.
The AND option of the setting Harmonic Blocking Logic disables the Cross-Blocking logic.
The setting Cross Blocking Time limits the duration of the Cross-Blocking logic. In new
transformers, the inrush current has a smaller percentage of second harmonic than in old
transformers. As a result of the difference in current phase angle between the three phases
when switching on (voltage phase difference is 120º to each other), generating different DC
level in the flux associated to each phase, one phase could exist in which the inrush current
harmonic content is very small. In this case, cross-blocking logic must be used to keep the
safety. However, this logic will only be necessary during the first 4 or 5 energizing cycles, since
after this, as a result of the reduction of the inrush current, the 2nd harmonic content will have
increased. Hence, a recommended cross-blocking time is 100 ms. However, as mentioned
above, if the transformer is grounded star / delta and it is energized from the star side, the 2 out
of 3 logic will always be met. In this case the Cross-Blocking time could be extended to several
seconds.
The signal Cross Blocking by Harmonics indicates the Cross-Blocking logic setting: OR or 2
out of 3 is met. This signal will be used to block the negative sequence overcurrent elements,
provided the setting Harmonic Blocking is enabled.
M0IRSB1905I
2.6-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Ground, Sensitive
HAR_2_BLK_SN Sensitive Ground Blocking by 2nd Harmonic I Ground and
Ungrounded
HAR_BLK_A Phase A Blocking by Harmonics I
Harmonic Blocking.
HAR_BLK_B Phase B Blocking by Harmonics I
HAR_BLK_C Phase C Blocking by Harmonics I
HAR_BLK_N Neutral Blocking by Harmonics
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.6-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.7 Cold Load Element
2.7.1 Identification
Description of the Protection Element ANSI/IEEE C37.2
Cold Load Unit CLP
Assuming the relay works using Table 1 and a breaker trips, a timer starts timing (Time for
Group 2 Activation after Trip setting) and if breaker remains open after time-out, settings in
Table 2 apply. Table 2 will be the active table while breaker remains open.
When breaker closes, the equipment will be working with higher settings, and trips caused by
starting motors will not take place.
A timer starts timing after closing (Time for Previous Group Activation after Closing setting),
and if breaker remains closed after time-out, Table 1 activates.
If this function is disabled, Table 2 can be used in the same way as Table 1.
Since the IED will normally be in self-powered operation, it will shut down when the breaker is
open or when there is no current flowing through the position. For this reason, the unit has a
setting, Cold Load On, which allows the equipment to pickup always with Table 2 so that once
the time set in the Time for Previous Group Activation after Closing setting is restored,
Table 1 will be recovered again.
The equipment does not allow the Cold Load unit to be enabled when Table 2 is active. When
the Cold Load unit is active, the table change commands are disabled.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.7-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.7 Cold Load Element
Therefore, the operation of the unit will be as follows depending on the type of power supply
selected:
• Self-Powered Relay:
When the relay is switched off, regardless the status of the breaker (breaker open and
current cut-off or breaker closed with no current flow through the bay), the relay stores
the switch-off date. When the relay is switched-on again (indicating current is flowing
again through the bay) and the breaker is closed, before the protection elements start,
the relay compares the time during which it has been switched-off (without supplying
power to the load) with the Act Time Table 2 setting. If the time is above it, then Table 2
will apply. If the relay has been switched-off for very long time, the internal supercap that
supplies power to the RTC will be completely discharged and the relay date and time will
be lost. The relay will boot-up using Table 2.
If the Cold Load Start setting is set to YES, the relay will always switch to Table 2 when
booting-up.
The relay will start a timer after switching to Table 2. When the Prev. Table Time setting
value is reached, it will switch again automatically to Table 1. If the breaker opens and
thus the relay switches off before reaching the setting value, when booting again, the
process will start from zero.
• Externally Powered Relay (Power Supply or USB)
The element will be based on the breaker status, namely, on the Breaker Status Input:
Open(1) / Closed(0) internal signal value, which must be assigned to a digital input
The element will start operating when a change in the breaker status is detected. When
the breaker opens and the time lapse with the breaker open reaches the Table 2 Act.
Time setting value, Table 2 will apply. In this status, when the breaker closes and the
time lapse with the breaker closed reaches the Prev. Table Time setting value, Table 1
will automatically apply. If the breaker opens before the setting value is reached, when
booting again, the process will start from zero.
If Cold Load Start is set to YES, the relay will always switch to Table 2. Then, once the
closed breaker status is detected, the Prev. Table Time will count down and it will return
to Table1.
If Cold Load Start is set to YES, the relay will see the breaker open and switches to
Table 2 after the activation time. The relay switches off and when it is switched on, it
confirms that the breaker is open and remains in Table 2, which was already active. It will
return to Table 1 when it confirms that the breaker is closed and Prev. Table Time
counts down.
If the relay is switched off with the element operating, namely, the breaker has opened,
Table 2 Act Time has timed out and Table 2 applies, then, the relay can be switched on,
either because the external power supply is recovered, or current flows through the bay:
o Self-powered: the relay boots with Table 2, starts counting the time from booting and,
when Prev. Table Time setting value is reached, will switch again to Table 1.
o With Cold Load Start set to NO, External power supply: the relay is switched on and
the breaker remains open: the relay boots with Table 2 and does not switch to Table 1
until it confirms that the breaker is closed and Prev. Table Time counts down.
o With Cold Load Start set to NO, External power supply: the relay is switched on and
the breaker has closed: the relay boots with Table 2 and switches to Table 1 when
Prev. Table Time times out.
o If the relay recovers the external power supply at the same time than the self-power
supply, the condition defined for self-power will be followed.
If the relay loses the external power supply when the breaker is closed (namely, breaker
closed condition with no current flowing through the bay) and the external power supply is
recovered, the relay detects that the breaker has switched to open status and the
element will operate switching to Table 2 after 100ms.
M0IRSB1905I
2.7-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 2. Current Protection Units
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.7-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
2.8 Configuration Settings
2.8.1 Description
The following setting groups are included into the Configuration group:
Passwords.
Date and Time.
Communications.
Select the Configuration option to change access password for configuration group options.
Also, different passwords can be configured for operations and settings modification options.
These settings are only available through HMI and the passwords are numerical consisting of
four digits.
2.8.1.c Communications
See paragraph 1.4.7 on Communications.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 2.8-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 3.
Records
3.1 Oscillographic Recording
The Oscillography function is composed of two different sub functions: Capture and Display.
The first captures and stores protection data inside the IED and is part of the relay's software;
the second retrieves and presents the stored data graphically with one or more programs
running on a PC connected to the protection.
The sampling and storing frequency is 16 samples per cycle with 500 cycles total storing
capacity (10 seconds at 50Hz, 8.33 seconds at 60Hz) recording analog values and digital
signals. The maximum number of files of the oscillogram register is limited to 10, so that the
memory of each oscillogram register is fixed (50 cycles). Data will be saved in COMTRADE
format in a non volatile circular FIFO memory (FRAM memory) which is the same memory used
to save events and fault reports.
When a trip signal is activated and its corresponding initiate function mask setting is set to YES,
this activation signal activates the oscillogram start. On the other hand, this activation signal, will
not initiate the Oscillogram function if its corresponding mask setting is set to NO.
As stated above, the oscillogram recording function can be activated from the IED itself taking
into account the protection functions or could be activated if the oscillogram External Trip
signal has been configured in any of the IED digital inputs and the corresponding digital input
has been activated.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 3.1-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
3.1 Oscillographic Recording
Instantaneous Pickup
Time Overcurrent Pickup
Open Phase Detector Pickup
Breaker Failure Actuation
Instantaneous Trip
Time Overcurrent Trip
Open Phase Detector Trip
Undercurrent Trip
Thermal Image Trip
Protection Trip
External Protection Trip
Oscillo External Trip
Digital Output 1
Digital Output 2
Digital Output 3
Digital Input 1
Data will be stored with a resolution time equal to the sampling rate.
When there is no angle reference magnitude, all angles will be displayed in the relay with an
invalid value (***) and the oscillogram will display them at 0˚.
If the start function mask setting is YES, this signal activates the Oscillography startup. This
signal will not start the Oscillography function if its mask setting is NO.
M0IRSB1905I
3.1-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 3. Records
This setting will not affect the external trip, which always generates an oscillogram.
Although the length of the oscillogram previous to the fault can be configured down to 0 cycles,
the relay will be without power supply after issuing the trip command. Therefore, the oscillogram
recording function will stop:
- When the internal power loss signal generated by the IED switches to active status.
- When the oscillogram pickup is deactivated. This can happen when the Trip Required
setting is set to NO and no trip occurs
- 50 cycles after pickup previous to the fault when the Trip Required setting is set to NO,
no trip occurs and the oscillogram pickup is not deactivated at that time
- 50 cycles after inception previous to the fault when the oscillogram recorder function has
been activated by the external trip.
When the Trip Required setting is set to YES and the trip command is not generated within 50
cycles after the pre-fault, no file will be saved to the oscillogram.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 3.1-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
3.1 Oscillographic Recording
Trigger Mask
Setting Range Step Default IEC61850
IOC PH1 YES / NO - YES -
M0IRSB1905I
3.1-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 3. Records
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
is on process.
Note: The Visualization column (Vis.) indicates whether the signal is shown as indication in the relay status (I)
through the communications program and in the Fault Report (F).
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 3.1-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
3.2 Event Record
Event storage is optimized so that the events occurring in the same ms are stored in the same
register. The number of registers is 500.
The text related to an event is the text of the internal signal preceded by "ON" (or "activation")
and OFF (or "deactivation").
Events can be exported or imported with the following formats: XML, XLS and SQL. The All or
Selection options may be applied when exporting.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 3.2-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
3.3 Fault Report
The Fault Report records the most important data related to the last 10 faults recorded by the
IED. The fault reports are saved in a non volatile circular memory, which is a maintenance free
memory that can store the records with no time limitation, even if the relay is not powered from
any power supply. Once 10 fault reports have been stored and a new one is generated, the
oldest fault report will be deleted to make room for the new one (FIFO circular register).
The fault notification system initiates when any element picks up and resets and all elements
reset. By default, fault report files are only generated if a trip occurs during a fault condition,
namely, when a trip command is issued. The Pickup Report setting allows selecting the option
to generate the report file when no trip has occurred. When the Pickup Report is set to YES,
the corresponding report is written to the fault report file with no need for a trip.
Access to Fault Report data is available through the communications ports using the
communications program and the relay HMI. Data stored in each fault report is described in the
following chapters.
Data stored in each register is distributed in three tags: Fault Start Time Tag, Trip command
Time Tag and End of Fault Time Tag.
- Pre-fault measurements. Relay measurements two cycles before the fault; This is, two
cycles before the first element captured, which is the element that initiates the generation
of the fault report. Recorded measurements:
o Measured phase currents: IA, IB, IC.
o Calculated currents: IN, negative sequence current (NSC), positive sequence current
(PSC), zero sequence current (ZSC).
o Angles of IA, IB, IC and IN.
- Elements collected during the total duration of the fault:
o Phase instantaneous overcurrent.
o Phase time overcurrent.
o Neutral instantaneous overcurrent.
o Neutral time overcurrent.
o Negative sequence instantaneous overcurrent.
o Negative sequence time overcurrent.
o Open Phase Detector.
o Undercurrent.
There is a special case. When the Thermal Image protection element is involved in a trip, and
no other protection element captures the date and time of the Fault Start Time Tag, the fault
report will be opened and closed with the element trip time.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 3.3-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
3.3 Fault Report
- Fault measurements. Relay measurements two and a half cycles after fault start; This is,
two and a half cycles after the capture of the first element. Recorded measurements:
o Measured phase currents: IA, IB, IC.
o Calculated currents: IN, NSC, PSC, ZSC.
o IA, IB, IC and IN are recorded with their angles.
- Elements tripped:
o Phase instantaneous overcurrent.
o Phase time overcurrent.
o Neutral instantaneous overcurrent.
o Neutral time overcurrent.
o Negative sequence instantaneous overcurrent.
o Negative sequence time overcurrent.
o Open Phase Detector.
o Undercurrent.
o Thermal Image.
In the case of thermal image protection, the trip time will be two milliseconds more than the time
mark stored in the Fault Start Time Tag.
- Frequency.
- Thermal Image.
3.3.5 Measurements
By default, measurements recorded in the Fault Report will be referred to the secondary, but
they can be stored in primary values through a setting (Fault Report Primary / Secondary).
When fault report primary / secondary values are set to Primary, the measurements stored will
be multiplied by the corresponding transformation ratio setting:
IA, IB, IC, NSC, PSC and ZSC will be multiplied by the Phase CT Ratio setting
M0IRSB1905I
3.3-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 3. Records
Once a fault report has been selected, press the down arrow key to display all the data stored.
- First information:
o Recorded units.
- Second information:
o Activated units.
- Third information:
o Thermal Image.
o Measurements with angles: IA, IB, IC, IN.
o NSC, PSC, ZSC.
o Frequency.
On the default screen, press the left button to display summary information related to the last
trip:
- Type of fault.
- Time and date.
Fault Report
Communications Program Range Step By Default
Pickup Reports YES / NO NO
Fault Report Primary / Secondary Primary / Secondary Primary
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 3.3-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 4.
Test Mode
4.1 Test Mode
The Test Mode function can be enabled as long as the relay is powered up by USB or by
external power supply. Furthermore, the correct way of executing the Test Mode is by means of
a command given through the HMI (Actions menu) or ZIVercomPlus® (Control Operations).
At the moment when the IED is switched to function in the Test Mode:
The simulated values of the digital inputs and the analog inputs will be applied when a
protection test is being performed. In this situation, the user can decide if the relay outputs will
get activated or deactivated through a setting. In any case the events, the fault records and the
oscillography will be generated normally while the relay is still performing in Test Mode.
The Test Mode will be switched off manually by employing a command or automatically if a
configurable time is exceeded.
1. Automatically. The automatic test will activate one by one all the different digital outputs
of the relay. Once all the DOs have been initiated, the IED will activate the energy output.
Each of the digital outputs activates for 2 seconds and then waits for 1 second until the
activation of the following DO.
2. Manually. This way the user will be able to activate or deactivate any digital output
including the energy output, so as to check the appropriate functioning.
There are different commands to select the process wanted (automatically or manually) to
proceed with the tests.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 4.1-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
4.1 Test Mode
Each one of the LEDs will activate for 2 seconds and will wait for 1 second until the activation of
the following one. Once all the LEDs have been activated and after waiting another second, all
the LEDs will turn on again for another 2 seconds. This is the way of implying that the LED test
has ended properly.
Just like in the previous tests, the IED has to be in Test Mode in order to execute the desired
test.
The user will be able to test each of the protection units with the actual protection settings of the
relay and with all the values that were defined in the Test Mode configuration, such as, analog
and digital inputs.
If the setting of the activation of the DO associated with the protection test is activated and if the
protection test is being executed, the digital outputs will take the value of its signal or the values
of its associated intern signals provided that they are configured. This is the only moment when
the energy output will activate.
M0IRSB1905I
4.1-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Chapter 4. Test Mode
4.1.6 Actions
Test Mode
Communications Program HMI IEC 61850 Range Step Default
Test Mode Activation ACTIVATE TEST Activated Execute Deactivated
Deactivated
Protection Test Activation Protection Test Activated Execute Deactivated
Deactivated
LED Test Activation LEDs Test Activated Execute Deactivated
Deactivated
Output Test Activation
Test Mode Timer AUTO TEST Activated Execute Deactivated
Deactivated
Digital Output 1 DO1 Activated Execute Deactivated
Deactivated
Digital Output 2 DO2 Activated Execute Deactivated
Deactivated
Digital Output 3 DO3 Activated Execute Deactivated
Deactivated
Energy Output Energy 1 Activated Execute Deactivated
Deactivated
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection 4.1-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
A. MODBUS RTU. Documentation.
Address Map
This document provides a detailed MODBUS address map (input status, coil status and input
registers) and their equivalent in the IRS-B relay.
As previously mentioned, the protocol implemented is MODBUS RTU, where the IRS-B model
will always act as a slave and, therefore, will never start the communications. The user can
define the parameters to establish the communication, i.e. the Baud rate, Stop Bits, Parity, RX
Time between Characters and Communication Fail Time.
The mapping signals, i.e. the addresses of input status, coil status and input registers signals,
are fixed and are defined in the following sections of this Annex. This mapping will depend on
the FW version of the equipment, so if new units or signals were added in the future, these new
elements would be located from the last available address in order to maintain compatibility with
the previous models
The communication is carried out by data grouped in frames that are sent asynchronously. In
order to minimize the number of errors that may occur due to noise in the communications
channel, it is recommended to use a twisted shielded cable. If a 3-wire cable is used, the
ground terminals should be connected to the ground wire. If a 2-wire cable is used, the ground
terminals should be connected to the shield and the cable should be connected in a single point
to ground. When using long communication cables, it is convenient to use terminating resistors
whose value should be similar to the impedance of the cable.
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection A-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
M0IRSB1905I
A-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection A-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
M0IRSB1905I
A-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection A-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
Answer:
Answer:
M0IRSB1905I
A-7 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
A.6.2 Function 02
Correct request of 6 BITs starting from address 1:
Request:
Answer:
Answer:
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection A-8
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
A.6.3 Function 04
Correct request of 6 registers starting from address 1:
Request:
Answer:
Slave Function
Lenght Measurement 1 Measurement 2 Measurement 3 CRC
Address Code
01 04 0C FB 03 3A B4 88 EF 3B 1F C1 45 3A 3E 22 E9
Answer:
M0IRSB1905I
A-9 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex A. MODBUS RTU. Documentation. Address Map
A.6.4 Function 03
Correct request of 2 registers starting from address 512 (digital signals):
Request:
Answer:
Slave Function
Lenght Register 1 Register 2 CRC
Address Code
01 03 04 00 03 00 00 0A 33
Answer:
Slave Function
Lenght Register 1 Register 2 CRC
Address Code
01 03 04 00 03 00 00 0A 33
Slave Function
Lenght Measurement 1 Measurement 2 CRC
Address Code
01 03 08 4E 21 3A 35 51 53 3A 28 5A 64
Answer:
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection A-10
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
B. Parameter Configurations
B.1 Introduction
This document provides a detailed explanation of each of the settings that can be configured on
the IED, both in the communications program and in the HMI. The configurable settings are
detailed in the following sections.
B.3 Comunications
Settings Communications Program Settings HMI Description
Baudrate -- The rate of the dats in Bauds
Stop Bits -- Stop Bits
Parity -- Parity
Rx Time between characters -- Rx Time between characters
Comms Fail Timer Maximum time between
messages without indication of
--
communication channel
blocking.
Tx Time Factor -- Factor to Tx Time
Tx Timeout Const. -- Constant to Tx Timeout
Stop Bytes Number RS.485 it specifies the number of stop
bytes between transmit and
--
receive when the port is
configured as RS485.
IED Address -- The address of the IED
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection B-2
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
B.5 General
Settings Communications Program Settings HMI Description
Name -- Name of IED
Breaker -- Name of the position
Unit in service Unit in service Unit in service
Phase CT Ratio Phase CT Ratio Phase CT Ratio
Phase Sequence Phase Sequence Phase Sequence
PLL enable PLL enable PLL enable
M0IRSB1905I
B-3 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection B-4
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
M0IRSB1905I
B-5 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection B-6
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
M0IRSB1905I
B-7 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
B.18 Trips
Settings Communications Settings HMI Description
Program
IOC PH1 IOC PH1 Indication of enabled or disabled status of the
instantaneous overcurrent phase 1 unit
IOC PH2 IOC PH2 Indication of enabled or disabled status of the
instantaneous overcurrent phase 2 unit
IOC PH3 IOC PH3 Indication of enabled or disabled status of the of the
instantaneous overcurrent phase 3 unit
IOC N1 IOC N1 Indication of enabled or disabled status of the
instantaneous overcurrent neutral 1 unit
IOC N2 IOC N2 Indication of enabled or disabled status of the
instantaneous overcurrent neutral 2 unit
IOC N3 IOC N3 Indication of enabled or disabled status of the
instantaneous overcurrent neutral 3 unit
IOC NEG SEQ1 IOC NEG SEQ1 Indication of enabled or disabled status of the
instantaneous overcurrent negative sequence 1 unit
IOC NEG SEQ 2 IOC NEG SEQ 2 Indication of enabled or disabled status of the
instantaneous overcurrent negative sequence 2 unit
IOC NEG SEQ 3 IOC NEG SEQ 3 Indication of enabled or disabled status of the
instantaneous overcurrent negative sequence 3 unit
TOC PH1 TOC PH1 Indication of enabled or disabled status of the time
overcurrent phase 1 unit
TOC PH2 TOC PH2 Indication of enabled or disabled status of the time
overcurrent phase 2 unit
TOC PH3 TOC PH3 Indication of enabled or disabled status of the time
overcurrent phase 3 unit
TOC N1 TOC N1 Indication of enabled or disabled status of the time
overcurrent neutral 1 unit
TOC N2 TOC N2 Indication of enabled or disabled status of the time
overcurrent neutral 2 unit
TOC N3 TOC N3 Indication of enabled or disabled status of the time
overcurrent neutral 3 unit
TOC NEG SEQ1 TOC NEG SEQ1 Indication of enabled or disabled status of the time
overcurrent negative sequence 1 unit
TOC NEG SEQ 2 TOC NEG SEQ 2 Indication of enabled or disabled status of the time
overcurrent negative sequence 2 unit
TOC NEG SEQ 3 TOC NEG SEQ 3 Indication of enabled or disabled status of the time
overcurrent negative sequence 3 unit
OPHEN PHASE OPHEN PHASE Indication of enabled or disabled status of the of the
open phase unit
THERMAL IMG THERMAL IMG Indication of enabled or disabled status of the
thermal image unit
UNDERCURRE Min LOAD Indication of enabled or disabled status of the of the
undercurrent unit
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection B-8
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
B.19 Oscillography
Settings Communications Settings HMI Description
Program
Required Trip Trip Required Generate the oscillogram record
Pre-fault recording length Preting. Length Length of the oscillogram record in pre-fault
Trigger Mask
OPHEN PHASE OPHEN PHASE To activate the Oscillography start up for the ophen
phase unit
THERMAL IMG THERMAL IMG To activate the Oscillography start up for the
thermal image unit
UNDERCURRE Min LOAD To activate the Oscillography start up for the
undercurrent unit
EXTERNAL TRIGGER Ext. Trigger To activate the Oscillography start up with external
triggering signal.
IOC PH1 IOC PH1 To activate the Oscillography start up for the
instantaneous overcurrent phase 1 unit
IOC PH2 IOC PH2 To activate the Oscillography startup for the
instantaneous overcurrent phase 2 unit
IOC PH3 IOC PH3 To activate the Oscillography startup for the
instantaneous overcurrent phase 3 unit
IOC N1 IOC N1 To activate the Oscillography startup for the
instantaneous overcurrent neutral 1 unit
IOC N2 IOC N2 To activate the Oscillography startup for the
instantaneous overcurrent neutral 2 unit
IOC N3 IOC N3 To activate the Oscillography startup for the
instantaneous overcurrent neutral 3 unit
IOC NEG SEQ1 IOC NEG SEQ1 To activate the Oscillography startup for the o
instantaneous overcurrent negative sequence 1 unit
IOC NEG SEQ 2 IOC NEG SEQ 2 To activate the Oscillography startup for the
instantaneous overcurrent negative sequence 2 unit
IOC NEG SEQ 3 IOC NEG SEQ 3 To activate the Oscillography startup for the
instantaneous overcurrent negative sequence 3 unit
TOC PH1 TOC PH1 To activate the Oscillography startup for the of the
time overcurrent phase 1 unit
TOC PH2 TOC PH2 To activate the Oscillography startup for the time
overcurrent phase 2 unit
TOC PH3 TOC PH3 To activate the Oscillography startup for the time
overcurrent phase 3 unit
TOC N1 TOC N1 To activate the Oscillography startup for the time
overcurrent neutral 1 unit
TOC N2 TOC N2 To activate the Oscillography startup for the time
overcurrent neutral 2 unit
TOC N3 TOC N3 To activate the Oscillography startup for the time
overcurrent neutral 3 unit
TOC NEG SEQ1 TOC NEG SEQ1 To activate the Oscillography startup for the time
overcurrent negative sequence 1 unit
TOC NEG SEQ 2 TOC NEG SEQ 2 To activate the Oscillography startup for the time
overcurrent negative sequence 2 unit
TOC NEG SEQ 3 TOC NEG SEQ 3 To activate the Oscillography startup for the time
overcurrent negative sequence 3 unit
M0IRSB1905I
B-9 IRS-B: Self Powered Overcurrent Protection
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
Annex B. Parameter Configurations
M0IRSB1905I
IRS-B: Self Powered Overcurrent Protection B-10
ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. Zamudio, 2019
C. List of Illustrations and Tables
Annex C. List of Illustrations and Tables
M0IRSA1904I
IRS: Self Powered Overcurrent Protection C-2
ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Annex C. List of Illustrations and Tables
M0IRSA1904I
C-3 IRS: Self Powered Overcurrent Protection
© ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
Annex C. List of Illustrations and Tables
M0IRSA1904I
IRS: Self Powered Overcurrent Protection C-4
ZIV GRID AUTOMATION, S.L.U. Zamudio, 2019
License agreement for Software Embedded in Equipment
1. License Grant. Licensor hereby grants to you, and your accept, a nonexclusive and non-
transferable license to use the embedded programs and the accompanying documentation, if any
(collectively referred to as the “Software”), only as authorized in this License Agreement.
2. Restrictions. You may not (a) use, copy, modify or transfer the Software except as expressly
provided in this or another Agreement with Licensor, (b) reverse engineer, decompile or
disassemble or separate the components of the Software, or (c) rent, sell or lease the Software or
make the Software available to others to do any of the foregoing.
3. No Assignment. This License is intended for your exclusive use with the purchased equipment.
You agree that you will not assign, sublicense, transfer, pledge, lease, rent or share your rights
under this License Agreement.
4. Licensor’s Rights. You acknowledge and agree that the Software is the proprietary product of
Licensor protected under U.S. copyright law and international treaties.. You further
acknowledge and agree that all right, title and interest in and to the Software, including
associated intellectual property rights, are and shall remain with Licensor. This License
Agreement does not convey to you an ownership interest in or to the Software, but only a
limited right of use revocable in accordance with the terms of this License Agreement.
5. Confidentiality. The Software is confidential and no details or information relating to the same
shall be disclosed to any third party without the prior written consent of Licensor. For the
purposes of this clause, sub-contract staff, employed or retained by the Licensee to perform
computer systems development work, shall not be deemed to be third parties provided such staff
are subject to the disclosure restrictions set forth above. In no event, except with a prior written
authorization duly signed by an officer of Licensor, may you disclose any such confidential
information, even for subcontracted jobs, to persons or entities that may be considered to be
direct competitors of Licensor.
6. Term. The License Agreement is effective upon delivery of the equipment to you and shall
continue until terminated. You may terminate this License Agreement at any time by returning
the equipment to Licensor, or by destroying the equipment. Licensor may terminate this License
Agreement upon your breach of any term hereof. Upon such termination by Licensor, you agree
to return the equipment to Licensor.
7. Warranty and Disclaimer. Licensor warrants, for your benefit only, that the Software, when
and as delivered to you, will conform to the specifications described in the instruction manuals
for the equipment purchased, or any specifications agreed to in writing by Licensor with a
particular customer. This warranty does not cover any minor errors or deviations from the
specifications that do not affect the proper functioning of the equipment. EXCEPT FOR THE
WARRANTIES SET FORTH ABOVE, THE SOFTWARE IS LICENSED “AS IS”, AND
LICENSOR DISCLAIMS ANY AND ALL OTHER WARRANTIES, WHETHER
EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE.
8. Licensee’s Remedy. You sole and exclusive remedy for any breach of Licensor’s warranty
shall be the repair or replacement, at Licensor’s sole option, of any Software that does not
conform to stated specifications. Licensor shall not be responsible for any failure arising from
inadequate or improper use of the Software.
9. Limitation of Liability. Licensor’s cumulative liability to you or any other party for any loss or
damages resulting from any claims, demands, or actions arising out of or relating to this
Agreement shall not exceed the purchase price paid to Licensor for the equipment. In no event
shall Licensor be liable for any indirect, incidental, consequential, special, or exemplary
damages or lost profits, even if licensor has been advised of the possibility of such damages.
10. Trademark. All ZIV trademarks (including ZIVERCOM, ZIVERLOG and ZIVERSYS) are
common law trademarks of Licensor. No right, license or interest to such trademarks is granted
hereunder, and you agree that no such right, license or interest shall be asserted by you with
respect to such trademark.
11. Licensee’s Indemnity. You shall defend, indemnify and hold Licensor harmless against any
loss or damage of any kind arising from a breach by you of this License Agreement, or any use
or misuse of the Software by you or your employees, agents or representatives, and from any
other of your conduct or from any claim or action by any of your customers in connection with
the Software or this License Agreement.
12. Governing Law. This License Agreement shall be construed and governed in accordance with
the internal laws of the State of Illinois, U.S.A.
13. No Waiver. The failure of either party to enforce any rights granted hereunder or to take action
against the other party in the event of any breach hereunder shall not be deemed a waiver by that
party as to subsequent enforcement of rights or subsequent actions in the event of future
breaches.
14. Entire Agreement. This License Agreement is the entire agreement between you and Licensor
with respect to the use of the software and supersedes all prior understandings or agreements
between the parties. This License Agreement may be amended only by a writing signed by an
officer of Licensor.