DESIGN BASIS REPORT CONSTEL

INFRA

DECLARATION OF STRUCTURAL ENGINEER

The existing FOB at Rourkela Station, Rourkela, Odisha has been retrofitted and designed by
me as per codal provisions given in Indian Standards. All loads (Dead, Imposed and Wind)
and load combinations are considered according to IS 875 and for Earthquake load IS
1893:2016 have been followed. The entire analysis has been carried out with the help of
software ‘STAAD.Pro’ by giving all the design parameters and all loads as input. The design
of members, columns are also done by the same software as per IS 800-2007, while the
design of anchor bolt, baseplate and pile foundation are carried out by manual calculation
which is clearly worked out in the design document.

I declare that all information in this Design Basis Report is best of my knowledge and based
on several work experiences.

KANCHAN KANTI MONDAL


B.Sc, B.E.(CIVIL), M.E.(STRUCTURAL ENGG.)
LICENCE NO: KMC/ESE 240/I
CHARTERED ENGINEER

1
DESIGN BASIS REPORT CONSTEL
INFRA

INDEX

1. DETAILS OF FOB
2. LOADS CONSIDERED FOR DESIGN VERIFICATION
3. CALCULATION OF LOADS AND LOAD PARAMETERS
4. DIMENSONS OF STRUCTURAL ELEMENTS
5. MATERIAL PROPERTIES
6. DESIGN OF NEW SUPPORT (BUILTUP COLUMN)
7. DESIGN VERIFICATION FOR STRENGTHENING OF EXISTING
MEMBER
8. DESIGN OF CONNECTIONS
9. DESIGN OF SPLICE JOINT
10. DESIGN OF BASE PLATE
11. DESIGN OF ANCHOR BOLT
12. DESIGN OF FOUNDATION
13. STAAD OUTPUT

2
DESIGN BASIS REPORT CONSTEL
INFRA

1. DETAILS OF FOB
 FOB GEOMETRY
Span of FOB =9.44m

Width of FOB =1.75 m

Height of FOB=7.0m

2. LOADS CONSIDERED FOR DESIGN VERIFICATION


1. Dead Load (as per IS875 PART-1)
2. Live Load (as per IS875 PART-2, IRS- BRIDGE RULE)
3. Seismic Load (as per IS1893 PART-1)
4. Wind load (as per IS875 PART-3)

ORTHOGRAPHIC VIEW OF MODEL

3. CALCULATION OF LOADS
DEAD LOADS
ITEMS LOADS
LOAD DUE TO FLOOR SLAB (300MM THIK SLAB) 0.3X25X1.75/2 = 6.6 KN/M
LOAD DUE TO FLOOR SLAB ON STEPS (150MM THIK SLAB) 0.32x25x0.15 = 1.2 KN/M

3
DESIGN BASIS REPORT CONSTEL
INFRA

LIVE LOADS
LIVE LOAD ON FLOOR (5 KN/SQM) 5X1.75/2 = 4.4 KN/M
LIVE LOAD ON STEPS (5 KN/SQM) 0.32X5=1.6 KN/SQM

SEISMIC LOAD PARAMETERS


SEISMIC ZONE II
ZONE FACTOR 0.10
IMPORTANCE FACTOR 1.5
RESPONSE REDUCTION FACTOR 3
ROCK OR SOIL SITE FACTOR 2
TIME PERIOD ALONG X DIRECTION 0.085h^0.75 = 0.363 sec
TIME PERIOD ALONG Z DIRECTION 0.085h^0.75 = 0.363 sec

WIND LOAD CACULATION

WIND PRESSURES AND DESIGN FORCES ON FRAME WITH FLAT-


SIDED MEMBER AS PER IS-875 (PART-3) : 2015

LOCATION ROURKELA

Wind Zone = II

Basic wind speed (Vb) = 39 m/sce APPENDIX-A

Terrain category = 1

Structure type = Industrial

Structure class = C

Probability factor (k1) = 1 TABLE-1

h = 8.60 m TABLE-2

w = 1.75 m

l = 70.3 m

Terrain, height and structure size factor (k2) = 1.05 10 m

4
DESIGN BASIS REPORT CONSTEL
INFRA

= 1.09 15 m

k2 = 1.04 8.6 m

Upwind slope = 2.00 degree

Topography factor (k3) = 1

Importance factor for cyclonic region (k4) = 1.3

Vz = 52.67 m/s

pz = 1664.30 N/sqm

Wind directionality factor (Kd) = 0.900

Tributory area of lattice = 604.58 sq.m

= 1 10 Sqm or less

TABLE-4 Area averaging factor = 0.9 25 Sqm

Sqm or
= 0.8 100
greater

Area averaging factor for lattice tower (Ka) = 0.80

Combination factor (Kc) = 1.000

Design pressure (pd) = 1198.3 N/sqm

5
DESIGN BASIS REPORT CONSTEL
INFRA

CALCULATION OF WIND FORCE ON FRONT FACE

Calculated Solidarity Ratio (Ø) = 0.29 Cl -7.4.3.4

Ø Cf
FORCE CO-EFFICIENT FOR SINGLE 0.2 1.80 Table -31
FRAME
0.3 1.70

Force coefficient of the component (Cf) = 1.71

Pressure for design (Pd) = 2.05 Kn/sqm

Effective frontal area (Ae) = 177.282 sqm

Total force on structure = 362.6 Kn

Pressure input in STAAD = 0.600 Kn/sqm

CALCULATION OF WIND FORCE ON BACK FACE

Frame spacing = 1.57

Least lateral dimension = 1.75

Frame spacing ratio = 0.90

H FOR MULTIPLE FRAME

FSR

Øe 0.5 1 2 4 5

0 1 1 1 1 1

0.1 0.9 1 1 1 1
Table -32

0.2 0.8 0.9 1 1 1

0.3 0.7 0.8 1 1 1

0.4 0.6 0.7 1 1 1

0.5 0.5 0.6 0.9 1 1

0.7 0.3 0.6 0.8 0.90 1

6
DESIGN BASIS REPORT CONSTEL
INFRA

1 0.3 0.6 0.6 0.80 1

Calculated Solidarity Ratio (Ø) = 0.29

Effective Solidarity Ratio (Øe) = 0.61 Cl -7.4.3.4

Sheilding factor for multiple frame

Øe H

0 1.00
SHEILDING FACTOR FOR MULTILE FRAME

0.1 0.98

0.2 0.88

0.3 0.78

0.4 0.68
Table -32
0.5 0.58

0.6 0.56

0.7 0.54

0.8 0.54

0.9 0.54

1 0.54

Øe H

Sheilding Factor (H) 0.60 0.56

0.70 0.54

Sheilding Factor (H) = 0.557

Effective frontal area (Ae) = 177.3 sqm

Total force on structure = 201.9 Kn

Pressure input in STAAD = 0.334 Kn/sqm

7
DESIGN BASIS REPORT CONSTEL
INFRA

4. DIMENSONS OF STRUCTURAL ELEMENTS


ITEMS DIMENSIONS (MMXMM)
TOP CHORD ISA 150X90X8+ISA 130X130X8
BOTTOM CHORD ISA 150X150X6+ISA 130X130X8
VERTICAL MEMBER OF RAILING ISA 65X65X6, ISA 65X65X6+ISA 75X75X6
INCLINED MEMBER OF RAILING ISA 65X65X6, ISA 65X65X6+ISA 100X100X8
EXISTING COLUMN SEC ISMB225
NEW COLUMN SEC ISMB300D SP-0.05 AND 190 C/C

SLAB THICKNESS(MM)
FLOOR SLAB 300 MM THICK
STAIR SLAB 150 MM THICK

FOUNDATION DIMENSIONS
PILE DIA 450
PILE CAP 5250X900X1200

5. SPECIFICATION OF MATERIALS
GRADE OF CONCRETE-M25

GRADE OF REINFORCEMENT STEEL-Fe-500

GRADE OF STRUCTURAL STEEL-Fe-250

6. DESIGN OF NEW SUPPORT (BUILTUP COLUMN)

DESIGN OF BUILT-UP COLUMN


GRADE OF STEEL = 250 MPA

CALCULATION OF MOMENT CARRYING CAPACITY


MAX DESIGN BENDING MOMENT = 22.3 KN-M

MAX DESIGN AXIAL FORCE = 450.7 KN

MAX DESIGN BENDING MOMENT DUE TO LATERAL FORCE = 5.91 KN-M

THICKNESS OF FLANGE (TOP) = 13.1 MM

8
DESIGN BASIS REPORT CONSTEL
INFRA

THICKNESS OF FLANGE (BOTTOM) = 13.1 MM

THICKNESS OF WEB = 7.7 MM

WIDTH OF FLANGE (TOP) = 140 MM

WIDTH OF FLANGE (BOTTOM) = 140 MM

DEPTH OF WEB = 300 MM

b/tf = 5.05 < 9.4ε

d/tw = 38.96 < 84ε

SECTION IS PLASTIC βb = 1

LOCATION OF PLASTIC NEUTRAL AXIS (Z-Z) = 150.00 MM

PLASTIC SECTION MODULUS WITH RESPECT TO Z-Z = 1494951 MM3

PLASTIC SECTION MODULUS WITH RESPECT TO Y-Y = 292334 MM3

IYY = 4860000 MM4

CALCULATION OF SHEAR CENTRE

MAX SHEAR FLOW IN LOWER FLANGE = 0.00660 P

V2 = 0.6164 P

e = 193 MM

CALCULATION OF ELASTIC CRITICAL MOMENT Mcr

c1 = 0.972

c2 = 0.304 TABLE-42

c3 = 0.98

Ifc = 2995533 MM4

Ift = 2995533 MM4

βf = 0.5000

hy = 313.1 MM

yj = 0.000 MM

It = 221235 MM4

Iw = 1.19108E+11 MM6

9
DESIGN BASIS REPORT CONSTEL
INFRA

L = 6140 MM

LLT = 7368 MM

K = 0.5
ANNEX-E
Kw = 1

yg = 199.53 MM

THE ELASTIC CRITICAL MOMENT (M cr) = 47519464.42 N-MM

ELASTIC CRITICAL BENDING STRESS fcr,b = 31.79 MPA

λ LT = 0.400

α LT = 0.49

ϕ LT = 0.63

X LT = 0.897

fbd = 203.94 MPA

THE DESIGN BENDING STRENGTH ABOUT Z-Z AXIS = 304.88 KN-M

SAFE IN BENDING ABOUT Z-AXIS

SECTION IS PLASTIC βb = 1.00

THE DESIGN BENDING STRENGTH ABOUT Y-Y AXIS = 59.62 KN-M

SAFE IN BENDING ABOUT Y-AXIS

CALCULATION OF AXIAL LOAD CARRYING CAPACITY

AXIAL LOAD = 300.5 KN

UNSUPPORTED LENGTH = 5.125 M

GRADE OF STEEL = E 250

fy = 250 MPA

fu = 410 MPA

DESIGN LOAD = 450.7 KN

fcd = 150 MPA

SUPPORT CONDITION 1 BOTH END FIXED

10
DESIGN BASIS REPORT CONSTEL
INFRA

2 BOTH END PIN

3 ONE END FREE


3
ONE END FIXED

AREA REQUIRED = 3004.5 SQMM

AREA REQUIRED FOR EACH COMPONENT = 1051.6 SQMM

CHOICE OF SECTION

SECTION PROPERTY AS PER IS 808-1989

ISMB = 300 MM

WT. PER UNIT LENGTH = 46 KG/M

bf = 140 MM

tf = 13.1 MM

tw = 7.7 MM

d = 300 MM

A = 5860 SQMM

Ixx = 89900000 MM4

Iyy = 4860000 MM4

rxx = 124 MM

ryy = 28.6 MM

cxx = 0 MM

cyy = 0 MM

CALCULATION OF SPACING BETWEEN TWO MEMBERS

MEMBER ARRANGEMENT 1 END END

2 2 SIDE SIDE

MINIMUM SPACING REQUIRED = 240.9 MM

SPACING PROVIDED = 190 MM

IYY = 62606500 MM4

rmin = 103.36 MM

11
DESIGN BASIS REPORT CONSTEL
INFRA

Leff = 10250 MM

SLENDERNESS RATIO = 99.17

EFFECTIVE SLENDERNESS RATIO = 109.08

PASSED IN SLENDERNESS

BUCKLING CLASS = C 3

MODULUS OF ELASTICITY (E) = 200000 MPA

Ymo = 1.1

Ym1 = 1.25

IMPERFECTION FACTOR (ALPHA) = 0.49

fcc = 166.02 MPA

LAMDA = 1.23

PHI = 1.50

CHI (X) = 0.42

fcd = 95.69 MPA

Pd = 1121.48 KN

PASSED IN AXIAL COMPRESSION

DESIGN AXIAL LOAD (P) = 450.7 KN

DESIGN AXIAL STRENGTH (Pd) = 1121.5 KN

MAX DESIGN BENDING MOMENT ABOUT Z-Z AXIS (Mz) = 22.3 KN-M

THE DESIGN BENDING STRENGTH ABOUT Z-Z AXIS (Mdz) = 304.9 KN-M

MAX DESIGN BENDING MOMENT ABOUT Y-Y AXIS (My) = 5.91 KN-M

THE DESIGN BENDING STRENGTH ABOUT Y-Y AXIS (Mdy) = 59.62 KN-M

INTERACTION CHECKING OF CROSS SECTION FOR VERTICAL AND LATERAL FORCES

P/Pd+My/Mdy+Mz/ Mdz = 0.574

SAFE IN INTERACTION

DESIGN OF INTERMEDIATE BATTEN

12
DESIGN BASIS REPORT CONSTEL
INFRA

CLAUSE-7.7.3

NO. OF BATTEN PLANE (N) = 2


C/C HORIZONTAL DISTANCE BETWEEN TWO END
= 300 MM
CONNECTION(S)
VERTICAL DISTANCE BETWEEN TWO BATTEN POINT (C) = 900.0 MM

a1/r1 = 31.47 < 50

0.7(KL/r) = 69.42

31.47 < 69.42

SPACING OF BATTEN IS OK

TRANSVERSE SHEAR FORCE (Vt) = 7.5 KN

SHEAR FORCE IN BATTEN = 11.3 KN

BENDING MOMENT IN BATTEN = 1.7 KN-M

DIMENSIONS OF BATTEN PLATE

CLAUSE-7.7.2.3

THICKNESS OF BATTEN PLATE = 6.00 MM

THICKNESS OF BATTEN PLATE PROVIDED = 8.00 MM

C/C DISTANCE BETWEEN TWO MAIN MEMBERS = 190.0 MM

WIDTH OF BATTEN PLATE = 143 MM

WIDTH OF BATTEN PLATE 280 MM

WIDTH OF BATTEN PLATE PROVIDED (d) = 300.00 MM

EFFECTIVE AREA IN SHEAR(Av) = 2400 SQMM

NOMINAL PLASTIC SHEAR RESISTANCE (Vn) = 314.9 KN

PASSED IN SHEAR CHECK

Bb = 1

PLASTIC SECTION MODULUS (Zp) = 180000 MM4

DESIGN BENDING STRENGTH = 40.9 KN-M

13
DESIGN BASIS REPORT CONSTEL
INFRA

PASSED IN BENDING

DESIGN OF END BATTEN

THICKNESS OF BATTEN PLATE = 6.00 MM

THICKNESS OF BATTEN PLATE PROVIDED = 8.00 MM

WIDTH OF BATTEN PLATE PROVIDED (d) = 300.00 MM

7. DESIGN VERIFICATION FOR STRENGTHENING OF EXISTING


MEMBER

CALCULATION OF COMBINED SECTION PROPERTY


BOTTOM CHORD STRENGTHENING
SECTION ISA 150X150X6
SINGLE ANGLE PROPARTY
LENGTH OF EACH LIMB L = 150 MM

THICKNESS t = 6 mm

AREA (AX) = 1764 SQMM

AREA (AX1) = 900 SQMM

AREA (AX2) = 864 SQMM

Cxx = 38.3 mm

Cyy = 38.3 mm

IXX = 3598227.18 MM4

IYY = 3598227.18 MM4

rxx = 45.16 MM

ryy = 45.16 MM

SECTION ISA 110X110X8


SINGLE ANGLE PROPARTY

14
DESIGN BASIS REPORT CONSTEL
INFRA

AREA (AX) = 1702 SQMM

IXX = 1950000 MM4

IYY = 1950000 MM4

Cxx = 30 MM

Cyy = 30 MM

rxx = 33.8 MM

ryy = 33.8 MM

110X110X8D
AREA REQD (AX) = 3404 SQMM

IXX = 3900000 MM4

IYY = 6963600 MM4

rxx = 33.8 MM

ryy = 45.2 MM

PROPERTY REQD FROM STAAD


AREA REQD (AX) = 3420 SQMM

IXX = 3985880 MM4

IYY = 7159470 MM4

rxx = 33.8 MM

ryy = 45.8 MM

ADDITIONAL PROPERTY REQUIRED

AREA REQD (AX) = 1656 SQMM

IXX = 387653 MM4

IYY = 978335 MM4

RECOMMENDED ADDITIONAL SECTION


ISA130X130X8
AREA REQD (AX) = 2022 SQMM

IXX = 3283000 MM4

IYY = 3283000 MM4

rxx = 40.3 MM

15
DESIGN BASIS REPORT CONSTEL
INFRA

ryy = 40.3 MM

Cxx = 35 MM

Cyy = 35 MM

COMBINED PROPERTY
AREA REQD (AX) = 3786 SQMM OK

IXX = 5233000 MM4 OK

IYY = 12956404.4 MM4 OK

TOP CHORD STRENGTHENING


SECTION ISA 150X75X8
SINGLE ANGLE PROPARTY
LENGTH OF EACH LIMB L = 150 MM

LENGTH OF EACH LIMB L = 75 MM

THICKNESS t = 8 mm

AREA (AX) = 1742 SQMM

Cxx = 52.3 mm

Cyy = 15.3 mm

IXX = 702000 MM4

IYY = 4072000 MM4

rxx = 20.07 MM

ryy = 48.35 MM

PROPERTY REQD FROM STAAD (100X75X8D)


AREA REQD (AX) = 2680 SQMM

IXX = 2697350 MM4

IYY = 7159470 MM4

rxx = 33.8 MM

ryy = 51.7 MM

ADDITIONAL PROPERTY REQUIRED

16
DESIGN BASIS REPORT CONSTEL
INFRA

AREA REQD (AX) = 938 SQMM

IXX = 1995350 MM4

IYY = 2679685 MM4

RECOMMENDED ADDITIONAL SECTION


ISA130X130X8
AREA REQD (AX) = 2022 SQMM

IXX = 3283000 MM4

IYY = 3283000 MM4

rxx = 40.3 MM

ryy = 40.3 MM

Cxx = 35 MM

Cyy = 35 MM

COMBINED PROPERTY
AREA REQD (AX) = 3764 SQMM OK

IXX = 3284742 MM4 OK

IYY = 13903950 MM4 OK

INCLINED MEMBER STRENGTHENING


SECTION ISA 65X65X6
SINGLE ANGLE PROPARTY
LENGTH OF EACH LIMB L = 65 MM

LENGTH OF EACH LIMB L = 65 MM

THICKNESS t = 6 mm

AREA (AX) = 744 SQMM

Cxx = 18.1 mm

Cyy = 18.1 mm

IXX = 291000 MM4

IYY = 291000 MM4

17
DESIGN BASIS REPORT CONSTEL
INFRA

rxx = 19.78 MM

ryy = 19.78 MM

PROPERTY REQD FROM STAAD (75X75X8D)


AREA REQD (AX) = 2280 SQMM

IXX = 1203630 MM4

IYY = 2276630 MM4

rxx = 33.8 MM

ryy = 31.6 MM

ADDITIONAL PROPERTY REQUIRED

AREA REQD (AX) = 1536 SQMM

IXX = 912630 MM4

IYY = 1741888 MM4

RECOMMENDED ADDITIONAL SECTION


ISA100X100X8
AREA REQD (AX) = 1540 SQMM

IXX = 1450000 MM4

IYY = 1450000 MM4

rxx = 30.7 MM

ryy = 30.7 MM

Cxx = 35 MM

Cyy = 35 MM

COMBINED PROPERTY
AREA REQD (AX) = 2284 SQMM OK

IXX = 1450744 MM4 OK

IYY = 3918500 MM4 OK

VERTICAL MEMBER STRENGTHENING


SECTION ISA 65X65X6
SINGLE ANGLE PROPARTY

18
DESIGN BASIS REPORT CONSTEL
INFRA

LENGTH OF EACH LIMB L = 65 MM

LENGTH OF EACH LIMB L = 65 MM

THICKNESS t = 6 mm

AREA (AX) = 744 SQMM

Cxx = 18.1 mm

Cyy = 18.1 mm

IXX = 291000 MM4

IYY = 291000 MM4

rxx = 19.78 MM

ryy = 19.78 MM

PROPERTY REQD FROM STAAD (75X75X8)


AREA REQD (AX) = 1140 SQMM

IXX = 590000 MM4

IYY = 590000 MM4

rxx = 22.7 MM

ryy = 22.7 MM

ADDITIONAL PROPERTY REQUIRED

AREA REQD (AX) = 396 SQMM

IXX = 299000 MM4

IYY = 55258 MM4

RECOMMENDED ADDITIONAL SECTION


ISA75X75X6
AREA REQD (AX) = 866 SQMM

IXX = 457000 MM4

IYY = 457000 MM4

rxx = 23.0 MM

ryy = 23.0 MM

Cxx = 35 MM

Cyy = 35 MM

19
DESIGN BASIS REPORT CONSTEL
INFRA

COMBINED PROPERTY
AREA REQD (AX) = 1610 SQMM OK

IXX = 748000 MM4 OK

IYY = 2099850 MM4 OK

8. DESIGN OF CONNECTIONS

T-CONNECTION FOR MOMENT AND SHEAR

GRADE OF BOLT M 25 6.8

fub = 600 MPA

fyb = 480 MPA

GRADE OF STEEL E 250

fu = 410 MPA

fy = 250 MPA

NOMINAL DIAMETER OF BOLT d = 25 MM

THICKNESS OF WEB OF SECTION t1 = 8 MM

THICKNESS OF COVER PLATE t2 = 10 MM

DIA OF HOLE do = 27 MM

NUMBER OF SHEAR PLANE IN THREADED PORTION nn = 1

NUMBER OF SHEAR PLANE IN NON-THREADED


ns = 1
PORTION

PITCH p = 70 MM

GAUGE g = 75 MM

END DISTANCE e1 = 46 MM

SHANK AREA OR AREA OF NON-THREADED PORTION


As = 491.09 SQMM
OF BOLT

20
DESIGN BASIS REPORT CONSTEL
INFRA

AREA OF THREADED PORTION OF BOLT An = 383.1 SQMM

SHEAR STRENGTH OF BOLT Vdsb = 242.25 KN

Kb = 0.57

BEARING STRENGTH OF BOLT Vdpb = 116.2 KN

BOLT VALUES B = 116.2 KN

DESIGN LOADS FOR T- MEMBER FROM STAAD (MEMBER-185)-L/C-23

DESIGN AXIAL COMPRESSION Pu = 12.7 KN

DESIGN MOMENT Mu = 23.5 KN-M

LEVER ARM l = 0.5 M

MAXIMUM TENSION /COMPRESSION C/T = 52.2 KN

NO. OF BOLTS IN A ROW n = 4.0

= KN
TENSION IN EACH BOLT 13.1
TENSION CARRYING CAPACITY OF EACH BOLT = 165.48 KN

BOLTS ARE SAFE UNDER TENSION

TOTAL NO. OF BOLTS IN CONNECTION N = 10

SHEAR FORCE IN EACH BOLT = 1.27 KN

INTERACTION CHECK = 0.006 <1

HENCE CONNECTION IS SAFE

Y-CONNECTION

DESIGN LOADS FOR INCLINED MEMBER FROM STAAD (MEMBER-491)-L/C-24

DESIGN AXIAL COMPRESSION Pu = 218.3 KN

21
DESIGN BASIS REPORT CONSTEL
INFRA

=
DESIGN MOMENT Mu 5.6 KN-M

ULTIMATE STRENGTH OF WELD fu = 410 MPA

SIZE OF WELD s = 8 MM

THROAT THICKNESS t = 5.6 MM

DESIGN STRENGTH OF WELD fwd = 189.38 MPA

DESIGN COMPRESSIVE CONCENTRATED LOAD P = 218.3 KN

INCLINATION WITH VERTICAL θ = 31.3 DEGREE

θ = 0.55 RAD

VERTICAL COMPONENT OF FORCE Pcosθ = 186.5 KN

HORIZONTAL COMPONENT OF FORCE Psinθ = 113.5 KN

SHORTER LENGTH OF WELD AT TOP AND BOTTOM = 300 MM

LONGER LENGTH OF WELD ALONG TWO SIDES OF PLATE = 600 MM

TOTAL LENGTH OF WELD T = 1800.0 MM

DIRECT COMPRESSIVE STRESS q1 = 11.3 MPA

DIRECT SHEAR STRESS ALONG Y DIRECTION τ = 18.5 MPA

BENDING MOMENT M = 5.6 KN-M

LEVER ARM l = 0.6 M

MAXIMUM TENSION /COMPRESSION C/T = 9.4 KN

TENSILE/COMPESSIVE STRESS GENERATED DUE TO


q2 = 5.6 MPA
BENDING

MAXIMUM COMPRESSIVE STRESS DUE TO DIRECT


q = 16.8 MPA
COMPRESSION AND BENDING

EFFECTIVE STRESS ON WELD fe = 36.2 MPA

22
DESIGN BASIS REPORT CONSTEL
INFRA

THE CONNECTION IS SAFE UNDER GIVEN LOAD

9. DESIGN OF SPLICE JOINT

DESIGN OF SPLICE PLATE


FLANGE SPLICE
OVERALL DEPTH OF THE SECTION (D) = 150 MM

FLANGE THICKNESS = 6 MM

COVER PLATE THICKNESS = 8 MM

GRADE OF STEEL = 250 E

MAXIMUM DESIGN B.M = 7.35 KN-M

MAXIMUM DESIGN SHEAR = 77.8 KN

HEIGHT = 0.138 M

TENSION /COMPRESSION IN FLANGE = 53.3 KN

GRADE OF STEEL E 250

fu = 410 Mpa

fy = 250 Mpa

ULTIMATE STRENGTH OF WELD = 410 MPA

SIZE OF WELD = 8 MM

THROAT THICKNESS = 5.6 MM

DESIGN STRENGTH OF WELD = 1060.51 N/MM

LENGTH OF WELD = 50 MM

WIDTH OF FLANGE SPLICE PLATE = 100 MM

LENGTH OF SPLICE PLATE IN EACH SIDE = 200.0 MM

23
DESIGN BASIS REPORT CONSTEL
INFRA

THICKNESS OF SPLICE PLATE = 8 MM

DIMENSION OF SPLICE PLATE 400 100 8

NET AREA OF FLANGE SPLICE PLATE = 800.0 SQMM

FLANGE CAPACITY = 181.8 KN

FLANGE IS SAFE UNDER BM

WEB SPLICE

ULTIMATE STRENGTH OF WELD = 410 MPA

SIZE OF WELD = 8 MM

THROAT THICKNESS = 5.6 MM

DESIGN STRENGTH OF WELD = 189.38 MPA

LENGTH OF WELD REQUIRED = 73 MM

REQUIRED LENGTH OF WELD ON EACH SIDE = 37 MM

WIDTH OF WEB SPLICE PLATE = 100 MM

LENGTH OF SPLICE PLATE IN EACH SIDE = 200.0 MM

THICKNESS OF SPLICE PLATE = 8 MM

NET AREA OF WEB SPLICE PLATE = 800.0 SQMM


SHEAR CARRYING CAPACITY OF WEB SPLICE PLATE = 92.4 KN

WEB SPLICE IS SAFE UNDER SHEAR

24
DESIGN BASIS REPORT CONSTEL
INFRA

10. DESIGN OF ANCHOR BOLT

REACTIONS FOR DESIGN OF ANCHOR BOLTS AND BASE PLATE

NODE L/C FX FY FZ MX MY MZ

71 109 GENERATED INDIAN CODE FOUNDATION 1 0.001 303.734 1.057 0 0 0


110 GENERATED INDIAN CODE FOUNDATION 2 1.895 303.872 1.051 0 0 0
111 GENERATED INDIAN CODE FOUNDATION 3 0.001 302.637 -0.744 0 0 0
112 GENERATED INDIAN CODE FOUNDATION 4 4.001 304.003 1.06 0 0 0
113 GENERATED INDIAN CODE FOUNDATION 5 0.019 324.131 1.315 0 0 0
114 GENERATED INDIAN CODE FOUNDATION 6 -1.893 303.596 1.063 0 0 0
115 GENERATED INDIAN CODE FOUNDATION 7 0.001 304.831 2.858 0 0 0
116 GENERATED INDIAN CODE FOUNDATION 8 -3.999 303.465 1.054 0 0 0
117 GENERATED INDIAN CODE FOUNDATION 9 -0.017 283.337 0.799 0 0 0
118 GENERATED INDIAN CODE FOUNDATION 10 0.505 303.734 1.057 0 0 0
119 GENERATED INDIAN CODE FOUNDATION 11 0.001 300.915 0.904 0 0 0
120 GENERATED INDIAN CODE FOUNDATION 12 -0.503 303.734 1.057 0 0 0
121 GENERATED INDIAN CODE FOUNDATION 13 0.001 300.915 0.904 0 0 0
122 GENERATED INDIAN CODE FOUNDATION 14 1.895 303.872 1.051 0 0 0
123 GENERATED INDIAN CODE FOUNDATION 15 0.001 302.637 -0.744 0 0 0
124 GENERATED INDIAN CODE FOUNDATION 16 4.001 304.003 1.06 0 0 0
125 GENERATED INDIAN CODE FOUNDATION 17 0.019 324.131 1.315 0 0 0
126 GENERATED INDIAN CODE FOUNDATION 18 -1.893 303.596 1.063 0 0 0
127 GENERATED INDIAN CODE FOUNDATION 19 0.001 304.831 2.858 0 0 0
128 GENERATED INDIAN CODE FOUNDATION 20 -3.999 303.465 1.054 0 0 0
129 GENERATED INDIAN CODE FOUNDATION 21 -0.017 283.337 0.799 0 0 0
130 GENERATED INDIAN CODE FOUNDATION 22 0.505 303.734 1.057 0 0 0
131 GENERATED INDIAN CODE FOUNDATION 23 0.001 300.915 0.904 0 0 0
132 GENERATED INDIAN CODE FOUNDATION 24 -0.503 303.734 1.057 0 0 0
133 GENERATED INDIAN CODE FOUNDATION 25 0.001 306.552 1.21 0 0 0

DESIGN OF ANCHOR BOLT


NO. OF BOLTS IN EACH SIDE PARALELL TO X = 4 NOS.
NO. OF BOLTS IN EACH SIDE PARALELL TO Z = 4 NOS.
TOTAL NO. OF BOLTS = 12 NOS.

25
DESIGN BASIS REPORT CONSTEL
INFRA

VERTICAL LOAD (P) = 324.0 KN


Hx = 0.02 KN
Hz = 1.32 KN
MAXIMUM UPLIFT = 0 KN

C/C DISTANCE BETWEEN BOLT LINES PARALELL TO X = 0.425 M


C/C DISTANCE BETWEEN BOLT LINES PARALELL TO Z = 0.425 M
MOMENT (Mx) = 0.0 KN-M
MOMENT (Mz) = 0.00 KN-M
MAX TENSION IN BOLT = 0.0 KN
MAX SHEAR IN EACH BOLT = 0.11 KN
GRADE OF BOLT = 6.8
YEILD STRENGTH OF BOLT = 480 MPA
ULTIMATE STRENGTH OF BOLT = 600 MPA
NOMINAL DIAMETER OF BOLT = 25 MM
NUMBER OF SHEAR PLANE IN THREADED PORTION = 1
NUMBER OF SHEAR PLANE IN NON-THREADED PORTION = 0
PITCH = 75 MM
GAUGE = 75 MM
END DISTANCE = 47.6 MM
SHANK AREA OR AREA OF NON-THREADED PORTION OF BOLT = 491.1 SQMM
AREA OF THREADED PORTION OF BOLT = 383.1 SQMM

SHEAR STRENGTH OF BOLT = 106.15 KN


BOLT SAFE UNDER SHEAR
DESIGN TENSILE STRENGTH OF BOLT = 188.0 KN
BOLT SAFE UNDER TENSION
GRADE OF CONCRETE = 25 MPA
BOND STRENGTH OF CONCRETE = 1.4 MPA

26
DESIGN BASIS REPORT CONSTEL
INFRA

SIZE OF ANCHOR PLATE = 0 0


BEARING STRENGTH OF CONCRETE = 11.25 MPA
RESULTANT TENSION IN CRITICAL BOLT = 0.0 KN
ANCHORING LENGTH OF BOLT = 450.0 MM
PROVIDED LENGTH OF ANCHOR BOLT = 1200 MM

11. DESIGN OF BASE PLATE

DESIGN OF GUSSETED BASE PLATE


AXIAL LOAD ON COLUMN = 324 KN

MOMENT ON COLUMN = 0 KN-M

ECCENTRICITY = 0.000 M

COLUMN SECTION BUILTUP 300

WEB THICKNESS = 7 MM

FLANGE THICKNESS = 13 MM

GRADE OF CONCRETE = 25 MPA

BEARING STRENGTH OF CONCRETE = 15 MPA

LENGTH OF BASE PLATE = 550 MM

CALCULATION OF WIDTH OF BASE PLATE

WIDTH OF BASE PLATE REQUIRED (B) = 39.27 MM

MINIMUM WIDTH OF BASE PLATE = 550 MM

CALCULATION OF ORIGINAL BEARING PRESSURE

MAX BEARING PRESSURE (Pmax) = 1.07 MPA

MIN BEARING PRESSURE (Pmin) = 1.07 MPA

ALLOWABLE BEARING PRESSURE = 15.00 MPA

SAFE IN BEARING

VERTICAL PRESSURE AT XX = 1.07 MPA

MINIMUM PROJECTION = 125.00 MM

BENDING MOMENT AT PROJECTED PART PER MM WIDTH = 12551.7 N-MM

THICKNESS OF BASE PLATE REQUIRED = 16.62 MM

27
DESIGN BASIS REPORT CONSTEL
INFRA

NO. OF GUSSET PLATE PROVIDED IN EACH SIDE = 3.00

SPACING BETWEEN GUSSET PLATE = 75.00 MM

CANTILEVER PROJECTION IN CROSS DIRECTION = 271.50 MM


BENDING MOMENT IN THE GUSSET IN THE VERTICAL
= 2.96 KN-M
PLANE
HEIGHT OF GUSSET PLATE AT SUPPORT = 350 MM

THICKNESS OF GUSSET PLATE = 10 MM

SHEAR CARRYING CAPACITY OF GUSSET PLATE = 459.27 KN

VERTICAL SHEAR FORCE AT X-X ON EACH GUSSET PLATE = 73.64 KN

0.6 Vd = 275.56 KN

HENCE LOW SHEAR CASE

MOMENT CARRYING CAPACITY OF GUSSET PLATE = 46.40 KN-M

HENCE O.K.

SPACING BETWEEN GUSSET PLATE = 100.00 MM

BENDING MOMENT AT PROJECTED PART PER MM WIDTH = 1338.8 N-MM

THICKNESS OF BASE PLATE REQUIRED = 5.43 MM

PROVIDE THICKNESS OF BASE PLATE = 25.00 MM

28
DESIGN BASIS REPORT CONSTEL
INFRA

12. DESIGN OF FOUNDATION

REACTIONS FOR DESIGN OF PILE FOUNDATION

NODE L/C FX FY FZ MX MY MZ

255 109 GENERATED INDIAN CODE FOUNDATION 1 0.001 308.277 2.758 7.572 0 -0.001
110 GENERATED INDIAN CODE FOUNDATION 2 1.895 308.415 2.748 7.549 -0.001 -1.065
111 GENERATED INDIAN CODE FOUNDATION 3 0.001 307.241 0.326 3.967 0 -0.001
112 GENERATED INDIAN CODE FOUNDATION 4 4.016 308.529 2.764 7.585 0.001 2.256
113 GENERATED INDIAN CODE FOUNDATION 5 0.019 328.657 3.306 9.071 0 0.009
114 GENERATED INDIAN CODE FOUNDATION 6 -1.893 308.138 2.769 7.595 0.001 1.064
115 GENERATED INDIAN CODE FOUNDATION 7 0.001 309.313 5.19 11.176 0 -0.001
116 GENERATED INDIAN CODE FOUNDATION 8 -4.014 308.025 2.752 7.558 -0.001 -2.257
117 GENERATED INDIAN CODE FOUNDATION 9 -0.017 287.897 2.21 6.072 0 -0.011
118 GENERATED INDIAN CODE FOUNDATION 10 0.499 308.277 2.758 7.572 -0.001 -0.281
119 GENERATED INDIAN CODE FOUNDATION 11 0.001 305.469 2.304 6.282 0 -0.001
120 GENERATED INDIAN CODE FOUNDATION 12 -0.496 308.277 2.758 7.572 0.001 0.279
121 GENERATED INDIAN CODE FOUNDATION 13 0.001 305.469 2.304 6.282 0 -0.001
122 GENERATED INDIAN CODE FOUNDATION 14 1.895 308.415 2.748 7.549 -0.001 -1.065
123 GENERATED INDIAN CODE FOUNDATION 15 0.001 307.241 0.326 3.967 0 -0.001
124 GENERATED INDIAN CODE FOUNDATION 16 4.016 308.529 2.764 7.585 0.001 2.256
125 GENERATED INDIAN CODE FOUNDATION 17 0.019 328.657 3.306 9.071 0 0.009
126 GENERATED INDIAN CODE FOUNDATION 18 -1.893 308.138 2.769 7.595 0.001 1.064
127 GENERATED INDIAN CODE FOUNDATION 19 0.001 309.313 5.19 11.176 0 -0.001
128 GENERATED INDIAN CODE FOUNDATION 20 -4.014 308.025 2.752 7.558 -0.001 -2.257
129 GENERATED INDIAN CODE FOUNDATION 21 -0.017 287.897 2.21 6.072 0 -0.011
130 GENERATED INDIAN CODE FOUNDATION 22 0.499 308.277 2.758 7.572 -0.001 -0.281
131 GENERATED INDIAN CODE FOUNDATION 23 0.001 305.469 2.304 6.282 0 -0.001
132 GENERATED INDIAN CODE FOUNDATION 24 -0.496 308.277 2.758 7.572 0.001 0.279
133 GENERATED INDIAN CODE FOUNDATION 25 0.001 311.085 3.212 8.862 0 -0.001

29
DESIGN BASIS REPORT CONSTEL
INFRA

DESIGN OF 2-PILE CAP


COLUMN SIZE = 600 600

PILE DIA = 450 MM

LENGTH OF PILE CAP ALONG X = 900 MM

LENGTH OF PILE CAP ALONG Z = 5250 MM

DEPTH OF PILE CAP = 1200 MM

COVER = 75 MM

MAIN BAR BOTTOM = 25 MM

MAIN BAR TOP = 20 MM

EFFECTIVE DEPTH OF CAP = 1087.5 MM

AXIAL LOAD CARRYING CAPACITY OF PILE = 510 KN

DEPTH OF FIXITY OF PILE = 3.53 M

GRADE OF CONCRETE M = 25 MPA

GRADE OF STEEL Fe = 500 MPA

X Z

CO-ORDINATE OF PILE LOCATION P1 0 2.25

P2 0 -2.25

SUM X2 = 0.00 SQM

SUM Z2 = 10.13 SQM

MOMENT W. R. T X-AXIS = 9.1 KN-M

MOMENT W. R. T Z-AXIS = 0.01 KN-M

AXIAL LOAD = 328.7 KN

WT. OF PILE CAP = 141.75 KN

WT. OF SOIL ABOVE PILE CAP = 22.68 KN

TOTAL AXIAL LOAD = 491.43 KN

REACTION OF PILE 1 = 247.74 KN

30
DESIGN BASIS REPORT CONSTEL
INFRA

REACTION OF PILE 2 = 243.69 KN

PILE IS SAFE UNDER AXIAL LOAD

MAXIMUM RESULTANT LATERAL FORCE = 5.2 KN

MOMENT DUE TO LATERAL FORCE = 18.4 KN-M

MOMENT W. R. T Z-AXIS = 0.01 KN-M

MOMENT ON EACH PILE 9.2 KN-M

P1 0 2.25

P2 0 2.25

MAXIMUM DISTANCE OF PILE CENTRE ALONG X = 0.000 M

MAXIMUM DISTANCE OF PILE CENTRE ALONG Z = 2.250 M

WIDTH OF COLUMN ALONG X = 0.60 M

WIDTH OF COLUMN ALONG Z = 0.60 M

MAX MOMENT FOR EACH LOAD CASE = 483.1 KN-M

LENGTH OF CRITICAL SECTION OF PUNCHING SHEAR = 900.0 MM

EFFECTIVE AREA IN PUNCHING SHEAR = 1957500 SQMM

PUNCHING SHEAR STRESS = 0.251 N/SQMM

DESIGN PUNCHING SHEAR STRENGTH ks x τc = 1.25 MPA


SAFE IN PUNCHING SHEAR

MAX MOMENT OF RESISTANCE = 20644.74 KN-M

DESIGN MOMENT FOR PILE CAP = 724.63 KN-M

PILE CAP IS UNDER REINFORCED

LEVER ARM DEPTH FACTOR (j) = 0.968

AREA OF STEEL (Ast) = 1583.0 SQMM

MINIMUM AREA OF STEEL (Ast min) = 6851.3 SQMM


DOUBLE
NUMBER OF REINFORCEMENT BAR = 20.0
LAYER
SPACING OF BAR REQUIRED = 75.0 MM

SPACING OF BAR PROVIDED = 75.0 MM

31
DESIGN BASIS REPORT CONSTEL
INFRA

NUMBER OF REINFORCEMENT BAR PROVIDED = 20.0

AREA OF STEEL PROVIDED = 9812.5 SQMM

PERCENTAGE OF STEEL = 0.17 %

DESIGN SHEAR STRENGTH OF CONCRETE (τc) = 0.309 MPA

ONEWAY SHEAR AREA = 978750 SQMM

MAX SHEAR = 247.74 KN

(τv) = 0.253 MPA

SAFE IN ONEWAY SHEAR

DESIGN OF PILE
DIAMETER = 450 MM
GRADE OF CONCRETE = 25 MPA
MODULUS OFELASTICITY OF CONCRETE ( E ) = 25000 MPA
GRADE OF STEEL = 500 MPA
DEPTH OF FIXITY OF PILE = 3.53 M
LATERAL FORCE = 5.20 KN
MAXIMUM LATERAL LOAD ON EACH PILE = 2.6 KN
MOMENT ON EACH PILE DUE TO LATERAL FORCE = 9.2 KN-M
MAX AXIAL FORCE = 247.7 KN
DESIGN MOMENT FOR PILE = 13.8 KN-M
DESIGN AXIAL FORCE FOR PILE = 371.61 KN
d/D = 0.17
Pu/fckD*D = 0.07
Mu/fckD*D*D = 0.01
CHART 62 OF SP-
P/fck = 0
16
p = 0
pmin = 0.4
pmax = 0.4

32
DESIGN BASIS REPORT CONSTEL
INFRA

AREA OF STEEL REQUIRED = 635.9 SQMM


AREA OF STEEL PROVIDED = 1608 SQMM
8-16Ø BAR
REINFORCEMENT IS ADEQUATE

13. STAAD OUTPUT