manufacture. The stock of the polyethylene sleeve shall be rotated on the first
in/first out basis.
2.16 VALVES
A. All Sluice Valves required under this clause shall be supplied according to
the specification Section 21 05 23- GENERAL DUTY VALVES FOR FIRE PROTECTION
PIPING.
B. A complete set of bolts and nuts and one gasket shall be supplied to each flange.
Gaskets shall be of rubber reinforced with cotton and of thickness not less than
3mm.
C. The Contractor shall submit with his offer detailed information and technical
information on the design of each type of valves.
B. Each post will be supplied with a steel backing plate use for SV and FH,
D. All posts and backing plates are to be grit blasted prior to the application of a
suitable three stages epoxy paint system. The color shall be light aircraft gray color