4921240618F
Generator, Mains and BTB
Data sheet
1. AGC 150 Generator, Mains and BTB
1.1 About...................................................................................................................................................................................................................................................4
1.1.1 Software packages.............................................................................................................................................................................................................4
1.2 Single-line application diagrams...................................................................................................................................................................................... 4
1.2.1 Single generator applications...................................................................................................................................................................................... 4
1.2.2 Multiple generator applications................................................................................................................................................................................. 5
1.2.3 Power management applications..............................................................................................................................................................................7
1.3 Power management.................................................................................................................................................................................................................. 9
1.3.1 Introduction............................................................................................................................................................................................................................9
1.3.2 Power management plant modes...........................................................................................................................................................................10
1.3.3 Power management features....................................................................................................................................................................................10
1.4 Functions and features......................................................................................................................................................................................................... 11
1.4.1 General controller functions........................................................................................................................................................................................11
1.4.2 Emulation............................................................................................................................................................................................................................. 12
1.4.3 Easy configuration with the utility software.....................................................................................................................................................13
1.5 Protections overview.............................................................................................................................................................................................................13
5. Compatible products
5.1 Touch display unit: TDU........................................................................................................................................................................................................31
5.2 Power management............................................................................................................................................................................................................... 31
5.3 Open PMS.....................................................................................................................................................................................................................................31
5.4 Remote monitoring service: Insight.............................................................................................................................................................................31
5.5 Digital voltage controllers................................................................................................................................................................................................. 32
5.6 Additional inputs and outputs........................................................................................................................................................................................ 32
5.7 Additional operator panel, AOP-2.................................................................................................................................................................................32
5.8 Remote display: AGC 150.................................................................................................................................................................................................. 32
5.9 Shutdown unit, SDU 104.................................................................................................................................................................................................... 32
5.10 Other equipment...................................................................................................................................................................................................................32
5.11 Controller types......................................................................................................................................................................................................................33
6. Technical specifications
6.1 Electrical specifications......................................................................................................................................................................................................34
6.2 Environmental specifications..........................................................................................................................................................................................37
6.3 UL/cUL Listed............................................................................................................................................................................................................................38
7. Legal information
7.1 Software version...................................................................................................................................................................................................................... 40
1.1 About
The AGC 150 Generator (Genset), AGC 150 Mains and AGC 150 BTB controllers provide flexible protection and control in a
wide range of applications.
In the simplest applications, you can use one AGC 150 Generator controller to control one genset. You can also use AGC 150
Generator controllers for CANshare load sharing by multiple gensets (without power management).
Several AGC 150 controllers can work together to make a power management system (PMS). These applications include
synchronisation, island operation, and running parallel to mains. The PMS can automatically start and stop gensets, and
open and close breakers. You can also use AGC 150 in power management systems with other DEIF controllers.
The AGC 150 Generator controller contains all the functions needed to protect and control a genset, and the genset
breaker. If you do not use power management, the controller can also protect and control the mains breaker.
The AGC 150 Mains controller protects and controls a mains breaker, and a tie breaker.
The AGC 150 BTB controller protects and controls a bus tie breaker. The PMS manages the busbar sections.
The AGC 150 is a compact, all-in-one controller. Each AGC 150 contains all necessary 3-phase measuring circuits.
The values and alarms are shown on the LCD display screen, which is sunlight-readable. Operators can easily control the
gensets and breakers from the display units. Alternatively, use the communication options to connect to an HMI/SCADA
system. The HMI/SCADA system can then control the plant.
You can choose the Core, Extended and Premium software packages. The functions depend on the controller type.
Island mode
Island mode operation is typically used in power plants that
are isolated from the national (or local) electricity
distribution network. There are two key types of island
mode operation:
• Stand-alone generators not connected to the electricity
grid.
• Generators connected to the electricity grid in parallel
G mode. This means that they can generate power
independently, and on demand.
These applications can share the load without using power management. However, the generators do not automatically
start, stop, connect, and disconnect.
G G G G
3rd party
product
G G G G
G G G G
Busbar 3
Busbar 1 Busbar 2
G G G G
In power management, the controllers have the information that they need to automatically start, stop, connect and
disconnect generators and/or mains. See Power management for more information.
G G G G
Power plant with synchronising generators. Can also be used in critical power plants with a start signal from an external
(ATS) controller.
PMS
PMS PMS
G G G G
Ethernet Ethernet
G G G G
CAN bus
1 2 3 4
ALC 5 6 7 8
ASC Solar
CAN bus
ASC Storage
NOTE You can use AGC 150 generator, mains, and bus tie breaker controllers for power management in a hybrid system.
However, the AGC 150 hybrid controller cannot be used in a power management application. To control the
photovoltaic (PV) power source(s), use ASC Solar.
The power management system automatically supplies the power that is necessary for the load efficiently, safely and
reliably.
You can monitor the complete power management system from a graphical supervision page in the utility software. You can
also see running status, hours in operation, breaker status, the condition of the mains and busbars, fuel consumption, and
so on.
Multi-master system
The power management system is a multi-master system, for increased reliability. In a multi-master system all vital data is
transmitted between the controllers, so that all the controller know the power management status (calculations and
position) in the application. As a result, the application does not have a single master controller.
The plant modes are configurable and can be changed at any time. All modes can be combined with Automatic Mains
Failure mode (AMF). You can use the controllers for the following applications:
Automatic Mains Failure Critical power/emergency standby plants, black start generator.
Fixed power Power plant with fixed kW set point (including building load).
Power plant where generator supplies peak load demand paralleled to the
Peak shaving
mains.
Plant mode where the load is moved from mains to generator. For example, peak
Load take-over
demand periods, or periods with a risk of power outages.
Mains power export Power plant with fixed kW set point (excluding building load).
EasyConnect ● ● ●
N + X (Secured mode) ● ●
NOTE * The ASC 150 controllers must have Extended or Premium software. However, ASC 150 controllers can be used in
an energy/power management system with AGC 150 controllers that have Core software.
ID 1 to 24 ID 25 to 32 ID 33 to 40
AGC 150 PMS lite: For simple load sharing and power management over CANshare, for up to 127 generators. Only for
generators - other power sources are not possible. You can also use AGC-4 Mk II generator controllers for PMS lite. See the
AGC 150 PMS lite Data sheet.
AGC 150 DG Hybrid: For a system that includes gensets, up to 16 inverters, and a mains connection. If there is a mains,
there can be one genset. If there is no mains, there can be up to two synchronising gensets, or up to four non-
synchronising gensets. See the AGC 150 Hybrid Data sheet.
Open PMS: Used to add solar, storage, and/or mains controllers to brownfield sites that have genset and/or mains
controllers from other suppliers. You can use AGC 150 Generator controllers as external gensets.
Counters, including: ● ● ●
• Breaker operations ● ● ●
• kWh meter (day, week, month, total) ● ● ●
• kvarh meter (day, week, month, total) ● ● ●
TDU support ●
Password-protected setup ● ● ●
Modbus RS-485 ● ● ●
Modbus TCP/IP ● ● ●
1.4.2 Emulation
AGC 150 includes an emulation tool to verify and test the functionality of the application, for example plant modes and
logics, breaker handling, mains and generator operation.
Application emulation is useful for training, customising plant requirements and for testing basic functionality that needs to
be set up or verified.
Operate
Protections Alarms ANSI Genset* Mains BTB
time
Over-voltage 2 59 <200 ms ● ● ●
De-load error 1 34 ●
Hz/V failure 1 53 ●
Not in Auto 1 34 ● ● ●
3 Navigation Move the selector up, down, left and right on the screen.
For generator controllers, the controller automatically starts and stops (and connects and
6 AUTO mode disconnects) gensets. No operator actions are needed. The controllers use the power
management configuration to automatically select the power management action.
7 Silence horn Stops an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Access the Jump menu, Mode selection, Test, Lamp test.
The operator or an external signal can start, stop, connect or disconnect the genset. The
SEMI-AUTO generator controller cannot automatically start, stop, connect or disconnect the genset.
9
mode The controller automatically synchronises before closing a breaker, and automatically deloads
before opening a breaker.
Green: Mains voltage and frequency are OK. The controller can synchronise and close the
10 Mains symbol breaker.
Red: Mains failure.
Green: Generator voltage and frequency are OK. The controller can synchronise and close the
breaker.
14 Generator Green flashing: The generator voltage and frequency are OK, but the V&Hz OK timer is still
running. The controller cannot close the breaker.
Red: The generator voltage is too low to measure.
G L3
s1 s2
P1
s1
P2
s2
L3
N N
GB MB
F4 K2 K1 F5
P2 s2 + ‐ ‐
‐
MB GB
F3 K1 K2 feedback feedback
P1 s1
56 57 58 59 60 61 62 63 64 65 8 9 10 11 12 13 14 15 16 17 18 39 40 41 42 43 44 45 46 47 48 49 50 66 67 68 69
GB/TB off
GB/TB on
GB/TB off
Com (s2)
GB/TB on
L4 (s2)
L4 (s1)
L3 (s1)
L2 (s1)
L1 (s1)
DC (+)
MB off
MB off
MB on
MB on
Out
Out
Out
Out
Out
Out
L3
L3
L2
L2
L1
L1
In
In
In
In
In
In
In
In
N
AC current CT-side
AC voltage
DC output (configurable) Digital input (configurable) AC voltage USB
A-side B-side
RS485 RS485
Ethernet
Supply Engine start Analogue input Tacho CAN A ECU CAN B PMS Analogue output
Port 1 Port 2
Data + (A)
Data + (A)
Data (GND)
Data - (B)
Data (GND)
Data - (B)
Data (GND)
Data (GND)
GOV (+)
AVR (+)
GOV (‐)
Run coil
AVR (‐)
DC (+)
Emerg.
DC (‐)
Crank
High
High
Low
GND
SCR
Neg
Low
Pos
stop
D+
In
In
In
In
1 2 4 5 6 7 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 51 52 54 55
120 120 120 120
% P T
Tacho
F1 F2
+
B+ GOV
Fuel
M G D+
+
‐
ECU
AVR
120
+ ‐
Engine GND
Fuses
• F1: 2 A DC max. time-delay fuse/MCB, c-curve
• F2: 6 A AC max. time-delay fuse/MCB, c-curve
• F3: 4 A DC max. time-delay fuse/MCB, b-curve
• F4, F5: 2 A AC max. time-delay fuse/MCB, c-curve
Grounding guidelines
More information
See Wiring guidelines - best practice for grounding in the Installation instructions.
Synchronising (dynamic) ● ● ●
Synchronising (static) ● ●
Short-time parallel ● ● ●
Vector jump ● ●
df/dt (ROCOF) ● ●
Ground relay ● ●
Ventilation ● ● ●
Dry alternator ● ● ●
Engine functions
Start and stop functions Core Extended Premium
Derate engine ● ●
Overspeed 2 12 <400 ms
Crank failure 1 48
Start failure 1 48
Stop failure 1 48
Engine heater 1 26
ANGLE - ANGLE
CM 500, CM 558, CM
Cummins 570, CM 850, CM 2150 - ECU-dependent Cummins Generic*
and CM 2250
Detroit Diesel DDEC III Series 50, 60 and 2000 - DDEC III
Detroit Diesel DDEC III, DDEC IV Series 50, 60 and 2000 - DDEC Generic*
FOCUS controls
John Deere - ● John Deere Stage V
(version 2.1)
MTU MDEC module M.302 Series 2000 and 4000 - MDEC 2000/4000 M.302
MTU MDEC module M.303 Series 2000 and 4000 - MDEC 2000/4000 M.303
1 After-treatment status -
4 Page name -
5 Controller status -
9 Engine emission system failure level Emission failure or malfunction, with the severity.
10 Diesel Particle Filter (DPF) level Regeneration needed, with the severity.
Mid-level inducement.
Severe inducement.
Engine dashboard
3 Page name - -
4 Controller status -
NOTE Grey symbols show that communication is available for the referent. An engine type might not support all of the
referents.
3 Navigation Move the selector up, down, left and right on the screen.
For mains controllers, the controller automatically connects and disconnects the mains. No
6 AUTO mode operator actions are needed. The controllers use the power management configuration to
automatically select the power management action.
7 Silence horn Stops an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Access the Jump menu, Mode selection, Test, Lamp test.
The operator or an external signal can connect or disconnect the mains. The mains controller
SEMI-AUTO cannot automatically connect or disconnect the mains.
9
mode The controller automatically synchronises before closing a breaker, and automatically deloads
before opening a breaker.
Green: Mains voltage and frequency are OK. The controller can synchronise and close the
10 Mains symbol breaker.
Red: Mains failure.
MB TB
F4 K1 K2 F5
+ ‐ ‐
‐
MB TB
F3 K1 K2 feedback feedback
56 57 58 59 60 61 62 63 64 65 8 9 10 11 12 13 14 15 16 17 18 39 40 41 42 43 44 45 46 47 48 49 50 66 67 68 69
GB/TB on
GB/TB off
Com (s2)
GB/TB on
GB/TB off
L1 (s1)
L2 (s1)
L3 (s1)
L4 (s1)
L4 (s2)
MB on
MB off
DC (+)
MB on
MB off
Out
Out
Out
Out
Out
Out
L3
L2
L1
L2
L3
N
L1
In
In
In
In
In
In
In
In
N
USB
AC current CT-side AC voltage DC output (configurable) Digital input (configurable) AC voltage
A-side B-side
RS485 RS485
Ethernet
Supply Engine start Analogue input Tacho CAN A ECU CAN B PMS Analogue output
Port 1 Port 2
Data + (A)
Data + (A)
Data (GND)
Data (GND)
Data (GND)
Data (GND)
Data - (B)
Data - (B)
GOV (+)
AVR (+)
GOV (‐)
Run coil
AVR (‐)
DC (+)
Emerg.
DC (‐)
Crank
SCR
GND
High
High
Low
Low
Neg
Pos
stop
D+
In
In
In
In
1 2 4 5 6 7 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 51 52 54 55
120 120 120
F1
+ ‐
+ ‐
Fuses
• F1: 2 A DC max. time-delay fuse/MCB, c-curve
• F3: 4 A DC max. time-delay fuse/MCB, b-curve
• F4, F5: 2 A AC max. time-delay fuse/MCB, c-curve
Synchronising
ATS control
Load management
Plant PF control
3 Navigation Move the selector up, down, left and right on the screen.
For BTB controllers, the controller automatically joins and splits the busbar. No operator actions
6 AUTO mode are needed. The controllers use the power management configuration to automatically select
the power management action.
7 Silence horn Stops an alarm horn (if configured) and enters the Alarm menu.
The operator or an external signal can join or split the busbar. The BTB controller cannot
SEMI-AUTO automatically join or split the busbar.
9
mode The controller automatically synchronises before closing a breaker, and automatically deloads
before opening a breaker.
L1 P1 P2 L1
s1 s2
L2 P1 P2 L2
s1 s2
L3 P1 P2 L3
s1 s2
N N
BTB
F4 K2 F5
+ ‐
‐
BTB
F3 K2 feedback
56 57 58 59 60 61 62 63 64 65 8 9 10 11 12 13 14 15 16 17 18 39 40 41 42 43 44 45 46 47 48 49 50 66 67 68 69
GB/TB on
GB/TB off
Com (s2)
GB/TB on
GB/TB off
L1 (s1)
L2 (s1)
L3 (s1)
L4 (s1)
L4 (s2)
MB on
MB off
DC (+)
MB on
MB off
Out
Out
Out
Out
Out
Out
L1
L2
L3
L1
L2
L3
In
In
In
In
In
In
In
In
N
USB
AC voltage AC voltage
AC current CT-side A-side DC output (configurable) Digital input (configurable) B-side
RS485 RS485
Ethernet
Supply Engine start Analogue input Tacho CAN A ECU CAN B PMS Analogue output
Port 1 Port 2
Data + (A)
Data + (A)
Data (GND)
Data (GND)
Data (GND)
Data (GND)
Data - (B)
Data - (B)
GOV (+)
AVR (+)
GOV (‐)
Run coil
AVR (‐)
DC (+)
Emerg.
DC (‐)
Crank
SCR
GND
High
High
Low
Low
Neg
Pos
stop
D+
In
In
In
In
1 2 4 5 6 7 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 51 52 54 55
120 120 120
F1
+ ‐
+ ‐
Fuses
• F1: 2 A DC max. time-delay fuse/MCB, c-curve
• F3: 4 A DC max. time-delay fuse/MCB, b-curve
• F4, F5: 2 A AC max. time-delay fuse/MCB, c-curve
Synchronising
You can also use AGC 150 Generator, AGC-4 Mk II Genset and/or AGC-4 Genset as external gensets. That is, the genset
controllers are not part of the open PMS. They can send their power measurements to the open PMS controllers over CAN
bus.
DVC 550 is an advanced digital AVR designed for alternators with SHUNT, AREP or PMG excitation. The DVC 550 monitors
and regulates the alternator output voltage. AGC 150 can control all the DVC 550 features and receive fault information
directly with the CAN bus communication. For more information, see www.deif.com/products/dvc-550
You can configure and connect two AOP-2s if the controller has the premium software package.
See www.deif.com/products/agc-150-remote-display
See www.deif.com/products/sdu-104
• Synchroscopes
◦ CSQ-3 (www.deif.com/products/csq-3)
• Battery chargers/power supplies
◦ DBC-1 (www.deif.com/products/dbc-1)
• Current transformers
◦ ASK (www.deif.com/products/ask-asr)
◦ KBU (www.deif.com/products/kbu)
Minimum
Parameter Setting Controller type
software
• S1 = Stand-alone
◦ You can change the controller type to any other controller that uses S1 software.
• S2 = Core
• S3 = Extended
◦ You can change the controller type to any other controller type*.
◦ * To change to an ASC 150, the controller must have the sustainability option (S10).
• S4 = Premium
◦ You can change the controller type to any other controller type*.
◦ * To change to an ASC 150, the controller must have the sustainability option (S10).
◦ All functions are supported.
You can select the controller type under Basic settings > Controller settings > Type.
Power supply
Nominal voltage: 12 V DC or 24 V DC
Power supply range
Operating range: 6.5 to 36 V DC
Power supply load dump protection Load dump protected according to ISO16750-2 test A
5 W typical
Power consumption
12 W max.
0 V to 36 V DC
Measuring range
Max. continuous operating voltage: 36 V DC
Resolution 0.1 V
Accuracy ±0.35 V
Voltage measurement
Nominal range: 100 to 690 V phase-to-phase (above 2000 m derate to max. 480
Voltage range
V)
±1 % of nominal within 10 to 75 Hz
Voltage accuracy
+1/-4 % of nominal within 3.5 to 10 Hz
Current measurement
Number of CT input 4
3 A (-/1 A)
Max. measured current
15 A (-/5 A)
7 A continuous
Current withstand 20 A for 10 seconds
40 A for 1 second
From 10 to 75 Hz:
Current accuracy • ±1 % of nominal from 2 to 100% current
• ±1 % of measured current from 100 to 300 % current
Power measurement
D+
210 mA, 12 V
Excitation current
105 mA, 24 V
Tacho input
W 8 to 36 V
Digital inputs
12 x digital inputs
Number of inputs
Negative switching
DC outputs
10 x outputs
Number of 0.5 A outputs
2 A DC inrush and 0.5 A continuous, supply voltage 4.5 to 36 V DC
Common 12/24 V DC
Analogue inputs
Configurable as:
• Negative switching digital input
Electrical range • 0 V to 10 V sensor
• 4 mA to 20 mA sensor
• 0 Ω to 2.5 kΩ sensor
Accuracy Current:
Display unit
Operation conditions
Damp Heat Cyclic, 20/55 °C at 97 % relative humidity, 144 hours. To IEC 60255-1
Operating humidity Damp Heat Steady State, 40 °C at 93 % relative humidity, 240 hours. To IEC
60255-1
IEC/EN 60529
• IP65 (front of module when installed into the control panel with the supplied
Protection degree
sealing gasket)
• IP20 on terminal side
Response:
• 10 to 58.1 Hz, 0.15 mmpp
• 58.1 to 150 Hz, 1 g. To IEC 60255-21-1 (Class 2)
Endurance:
Vibration
• 10 to 150 Hz, 2 g. To IEC 60255-21-1 (Class 2)
Seismic vibration:
• 3 to 8.15 Hz, 15 mmpp
• 8.15 to 35 Hz, 2 g. To IEC 60255-21-3 (Class 2)
Requirements
Installation To be installed in accordance with the NEC (US) or the CEC (Canada)
6.4 Communication
Communication
You can connect these in a daisy chain (and operate them at the same time):
• Engine CAN Port
• DVC 550
• CIO 116, CIO 208, and CIO 308
CAN A • IOM 220 and IOM 230
Data connection 2 wire + common
Not isolated
External termination required (120 Ω + matching cable)
DEIF engine specification (J1939 + CANopen)
CAN B • AOP-2
Data connection 2 wire + common
Isolated
External termination required (120 Ω + matching cable)
PMS 125 kbit and 250 kbit
Used for:
• Modbus to PLC, SCADA, and so on
• Backup power management system (PMS) communication between AGC 150
RJ45 Ethernet
controllers
• NTP time synchronisation with NTP servers
Isolated
6.5 Approvals
Standards
CE
44.7 mm
(1.76 in)
Weight 0.79 kg
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF
does not take responsibility for the accuracy of translations, and translations might not be updated at the same time as the
English document. If there is a discrepancy, the English version prevails.