Professional Documents
Culture Documents
Substation Grounding Grid Diagnosis Applying Optimization Techniques Based on Measurements and Field Tests
Substation Grounding Grid Diagnosis Applying Optimization Techniques Based on Measurements and Field Tests
2, MARCH/APRIL 2020
Abstract—Considering urban substations ground grid diagnosis, verify if the touch and step voltages are below the tolerable
some real-physical constraints result in measurement process chal- limits [5].
lenges: 1) limited length between electrodes used to measure the In a short-circuit to earth, the total ground fault current is
equivalent impedance of the grounding system; 2) to determine the
current that flows from ground grid conductors to the earth; and distributed by the following:
3) to determine the grid resistance. In this scenario, an adequate 1) by the substation ground grid (Im );
diagnosis of the safety offered by the ground grid under test when 2) through the overhead ground wires of transmission lines
a ground fault occurs is not a trivial task. This article describes a (Iext );
methodology that allows a reliable diagnosis regarding the safety 3) the current via the neutral of power transformers.
provided by a substation ground grid. The methodology is applied
to the parameters obtained in performed field tests. The method has Regarding touch and step potentials, such voltages depend
two steps. First, the fall-of-potential method with reduced distances on ground current (Im ). If the portion of the fault current that
between electrodes is used to determine the equivalent impedance of is drained by the substation ground grid is neglected, it may
the grounding system. Then, the ground current is obtained. In both result in an inaccurate analysis of the safety provided by this
stages, optimization techniques are applied to the specific equations grid under test. Additionally, in the situation that the overhead
that govern the phenomenon under investigation. Comparative
case studies considering real-life data illustrate the effectiveness ground wires are connected to the substation ground grid, it is
of the method. difficult, or even impossible, to measure the portion of the test
current that circulates through the substation ground grid. It is
Index Terms—Optimization method, reduced distance between
electrodes, substation ground grid measurements.
important to highlight that it is very difficult to disconnect the
overhead ground wires of transmission lines from the grid during
I. INTRODUCTION the experiments.
The fall-of-potential method (FoPM) is commonly used to
N THE electrical power system, short-circuit levels increase
I continuously. This fact makes necessary periodic evaluation
of the safety offered by the substation ground grids [1]–[5]. This
measure the equivalent impedance of the grounding system
and consists of circulating a current between the ground grid
under test and an auxiliary current electrode (CE). Ground
evaluation is carried out through tests where the objective is to
resistance/impedance is obtained by measuring the potential,
at the soil surface, on several points between the ground grid
Manuscript received October 20, 2019; accepted December 15, 2019. Date of
publication January 12, 2020; date of current version March 17, 2020. Paper
and the CE. Such potentials are measured using an auxiliary
2019-PSEC-0218.R1, presented at the 2019 IEEE International Conference potential electrode (PE). In FoPM, the proper distance between
on Environment and Electrical Engineering and 2019 IEEE Industrial and the ground grid under test and the CE is at least five times the
Commercial Power Systems Europe, Genova, Italy, Jun. 10–14, and approved
for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by
largest diagonal of the ground grid [5].
the Power Systems Engineering Committee of the IEEE Industry Applications The application of FoPM presents limitations when the sub-
Society. (Corresponding author: Daniel S. Gazzana.) station is in urban regions or in the presence of surroundings
M. Telló is with CEEE-D, Federal University of Rio Grande do Sul, Porto
Alegre 90035-190, Brazil (e-mail: marcost@ceee.com.br).
obstacles (due to the impossibility of extending the CE at a
D. S. Gazzana and L. T. C. Pulz are with the Federal University of Rio Grande great distance), or when the ground grid is large. Several studies
do Sul, Porto Alegre 90035-190, Brazil (e-mail: daniel.gazzana@ufrgs.br; considering grounding resistance measurements using short dis-
lucastupicp@gmail.com).
V. B. Telló is with SIEMENS Ltd., Jundiaí 13213-080, Brazil (e-mail: vic-
tances between electrodes have been developed in recent years
tor.tello@siemens.com). [6]–[10].
R. C. Leborgne is with the Department of Electrical Systems of Automation Measurements with reduced distances between electrodes
and Energy, Federal University of Rio Grande do Sul, Porto Alegre 90035-190,
Brazil (e-mail: roberto.leborgne@ufrgs.br).
generally use the method called “compensation location” or
A. S. Bretas is with the Department of Electrical and Computer Engineering, “compensation point position,” which aims to determine where
University of Florida, Gainesville, FL 32611 USA (e-mail: arturo@ece.ufl.edu). the PE should be positioned in order to obtain the value of the
Color versions of one or more of the figures in this article are available online
at https://ieeexplore.ieee.org.
ground resistance of the substation under test. This method is
Digital Object Identifier 10.1109/TIA.2020.2966187 characterized by determining the point where the PE must be
0093-9994 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA MARIA. Downloaded on April 19,2024 at 12:02:25 UTC from IEEE Xplore. Restrictions apply.
TELLÓ et al.: SUBSTATION GROUNDING GRID DIAGNOSIS APPLYING OPTIMIZATION TECHNIQUES 1191
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA MARIA. Downloaded on April 19,2024 at 12:02:25 UTC from IEEE Xplore. Restrictions apply.
1192 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 2, MARCH/APRIL 2020
TABLE I
EXPERIMENTAL GROUND GRID (COMPARISON OF RESULTS)
Fig. 3. Resistance measured curves for various distances D and for various
positions of PE.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA MARIA. Downloaded on April 19,2024 at 12:02:25 UTC from IEEE Xplore. Restrictions apply.
TELLÓ et al.: SUBSTATION GROUNDING GRID DIAGNOSIS APPLYING OPTIMIZATION TECHNIQUES 1193
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA MARIA. Downloaded on April 19,2024 at 12:02:25 UTC from IEEE Xplore. Restrictions apply.
1194 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 2, MARCH/APRIL 2020
TABLE III
EXPERIMENTAL GROUND GRID (COMPARISON OF RESULTS)
0.443ρmin 0.443ρmax
√ ≤ Rm ≤ √ . (17c)
Sm Sm
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA MARIA. Downloaded on April 19,2024 at 12:02:25 UTC from IEEE Xplore. Restrictions apply.
TELLÓ et al.: SUBSTATION GROUNDING GRID DIAGNOSIS APPLYING OPTIMIZATION TECHNIQUES 1195
IV. CONCLUSION
This article presents a new methodology for determining
Fig. 10. Methodology for the diagnosis of substation grounding grid. (Im ), based on data acquired from field tests conducted in
substations. The values obtained for (Im ) were conservative.
It is important to point out that there are uncertainties of vari-
ables such as soil resistivities, current distribution along differ-
that the optimization method provides conservative values (in ent grounding elements and field measurements. Specifically,
favor of safety). considering that the geological complexity in which a grid is
b) Discussion about [12]: Reference [12] presented the installed results in inaccuracies of the soil structure model as well
field measurements of ground fault current distribution and as measurement uncertainties, it is difficult to obtain accurate
substation ground impedance of LG-2 complex in Québec. ground current values. However, the conservative values ob-
In [12], the grounding system is formed by the ground grid tained provide an indication that the grounding grid is safe even
impedance of 735 kV substation, the water intake ground if the models do not have the desired high accuracy. Addition-
grid impedance, the power houses grid and the equivalent ally, the developed methodology applied to field measurements
ground impedance (overhead ground wires, counterpoises, dis- results in a practical method for the safety assessment provided
tribution neutrals, communication cable shields, etc.). Know- by substation grounding grids, although it does not present the
ing the total current circulating in the grounding system, expected high precision due to the uncertainties mentioned.
the rest of the injected current will pass into the substation
ground grid. The measured voltage and injected current pha- REFERENCES
sors were 129@00 V and 554@220 A, respectively, and the [1] S. T. Sobral, C. A. Peixoto, D. Fernandes, and D. Mukhedkar, “Grounding
obtained ground current value into the substation ground grid measurements at the itaipu generating complex using the extended eleck
was 180@-270 A. Applying the optimization method, 32.85% method,” IEEE Trans. Power Del., vol. 3, no. 4, pp. 1553–1563, Oct. 1988.
[2] W. C. Boaventura, I. J. S. Lopes, P. S. A. Rocha, R. M. Coutinho,
of the injected current is drained by the substation ground F. Castro Jr., and F. C. Dart, “Testing and evaluating grounding systems of
grid (180@00 A). high voltage energized substations: Alternative approaches,” IEEE Trans.
Power Del., vol. 14, no. 3, pp. 923–927, Jul. 1999.
[3] T. Yuan, Y. Bai, W. Sima, C. Xian, Q. Peng, and R. Guo, “Grounding
resistance measurement method based on the fall of potential curve
III. CASE STUDY test near current electrode,” IEEE Trans. Power Del., vol. 32, no. 4,
pp. 2005–2012, Aug. 2017.
Field tests were performed on a new high voltage substation
[4] H. G. Sarmiento, J. Fortin, and D. Mukhedkar, “Substation ground
located in southern Brazil (SE Iguatemi). The results obtained impedance: Comparative field measurements with high and low current
by applying the optimization method were compared with the injection methods,” IEEE Trans. Power App. Syst., vol. PAS-103, no. 7,
pp. 1677–1683, Jul. 1984.
ground grid design data. The 69 kV SE Iguatemi is a GIS indoor
[5] IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and
substation with two power transformers of 20 MVA–69/13.8 kV Earth Surface Potentials of a Grounding System, IEEE Std 81-2012, 2012.
including one double circuit of transmission line. Fig. 7 shows [6] H. Huang et al., “Analysis of a large grounding system and subsequent
field test validation using the fall of potential method,” Energy Power Eng.,
a layout of the referred substation ground grid, with dimension
vol. 5, pp. 1266–1272, 2013.
of 34 m × 17 m. [7] R. Zeng, J. He, and Z. Guan, “Novel measurement system for ground-
The soil has the following structure: ρ1 = 500 Ωm, h1 = 8.6 m; ing impedance of substation,” IEEE Trans. Power Del., vol. 21, no. 2,
ρ2 = 5000 Ωm and h2 = infinite. The total ground fault current, pp. 719–725, Apr. 2006.
[8] G. Parise, L. Martirano, L. Parise, S. Celozzi, and R. Araneo, “Simplified
Isc , is 24 540 A. The tests were carried out with the overhead conservative testing method of touch and step voltages by multiple auxil-
ground wires of transmission lines connected to the SE ground iary electrodes at reduced distance,” IEEE Trans. Ind. Appl., vol. 51, no. 6,
grid. Additionally, the SE was de-energized during the tests. pp. 4987–4993, Nov./Dec. 2015.
[9] M. Telló, D. S. Gazzana, G. A. D. Dias, R. C. Leborgne, and
The FoPM with short distance between electrodes was ap- A. S. Bretas, “New methodology to measure the grounding grid resistance
plied. Fig. 8 shows the measurement scheme used and the of substations applying short distance among electrodes,” in Proc. 20th
distances adopted for current and potential auxiliary electrodes. Int. Conf. Comput. Electromagn. Fields, Montreal, QC, Canada, 2015, pp.
1–4.
In the test, the current was injected at 60 Hz and the angular [10] “R&D Project: Development of methodology for measuring potentials
difference between the quantities of interest was not considered. in ground grids of urban substations,” (in Portuguese), CEEE-UFSC,
Fig. 9 shows the measured resistance value corresponding to Florianopolis, Brazil, 2014.
[11] J. He, R. Zeng, and B. Zhang, Methodology and Technology for Power
each position of the PE. The test current (It ) was 1.6 A. System Grounding, 1st ed. Hoboken, NJ, USA: Wiley, 2013.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA MARIA. Downloaded on April 19,2024 at 12:02:25 UTC from IEEE Xplore. Restrictions apply.
1196 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 2, MARCH/APRIL 2020
[12] J. Fortin, H. G. Sarmiento, and D. Mukhedkar, “Field measurements of Lucas T. C. Pulz was born in Porto Alegre, Rio
ground fault current distribution and station ground impedance at LG-2, Grande do Sul, Brazil, on December 8, 1989. He
québec,” IEEE Trans. Power Del. vol. PWRD-1, no. 3, pp. 48–60, Jul. 1986. received the B.Eng. and M.Sc. degrees in electri-
[13] M. Telló, D. S. Gazzana, V. B. Telló, L. T. C. Pulz, R. C. Leborne, and cal engineering from the Federal University of Rio
A. S. Bretas, “Substation grounding grid diagnosis applying optimization Grande do Sul (UFRGS), Porto Alegre, Brazil, in
techniques based on measurements and field tests,” in Proc. 19th IEEE Int. 2014 and 2017, respectively.
Conf. Environ. Elect. Eng., Genoa, Italy, Jun. 2019, pp. 1–6. He is one of the Founders and Director at Vör
Electric. His research interests include power quality
and grounding systems.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DE SANTA MARIA. Downloaded on April 19,2024 at 12:02:25 UTC from IEEE Xplore. Restrictions apply.