PVsyst - Simulation report


Grid-Connected System

Project: SMKN 1 BULAKAMBA


Variant: New simulation variant
No 3D scene defined, no shadings
System power: 8.68 kWp
BULAKAMBA - Indonesia

Author
Project: SMKN 1 BULAKAMBA
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:20
with v7.4.0

Project summary
Geographical Site Situation Project settings
BULAKAMBA Latitude -6.87 °S Albedo 0.20
Indonesia Longitude 108.91 °E
Altitude 10 m
Time zone UTC+7

Meteo data
BULAKAMBA
Meteonorm 8.1 (2016-2021), Sat=100% - Synthetic

System summary
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 11 / 0 °

System information
PV Array Inverters
Nb. of modules 28 units Nb. of units 2 units
Pnom total 8.68 kWp Pnom total 8.00 kWac
Pnom ratio 1.085

Results summary
Produced Energy 13082.85 kWh/year Specific production 1507 kWh/kWp/year Perf. Ratio PR 79.45 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Predef. graphs 6
Single-line diagram 7

23/10/23 PVsyst Licensed to Page 2/7


Project: SMKN 1 BULAKAMBA
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:20
with v7.4.0

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 11 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon No Shadings Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer Photowatt Manufacturer Omron
Model PW60HT-CB-XF-310 Model KP 40H
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 310 Wp Unit Nom. Power 4.00 kWac
Number of PV modules 28 units Number of inverters 2 units
Nominal (STC) 8.68 kWp Total power 8.0 kWac
Modules 4 Strings x 7 In series Operating voltage 100-370 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.09
Pmpp 7.88 kWp
U mpp 210 V
I mpp 38 A

Total PV power Total inverter power


Nominal (STC) 9 kWp Total power 8 kWac
Total 28 modules Number of inverters 2 units
Module area 47.1 m² Pnom ratio 1.09

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 93 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses Strings Mismatch loss


Loss Fraction 2.0 % at MPP Loss Fraction 0.2 %

IAM loss factor


Incidence effect (IAM): Fresnel smooth glass, n = 1.526

0° 30° 50° 60° 70° 75° 80° 85° 90°


1.000 0.998 0.981 0.948 0.862 0.776 0.636 0.403 0.000

23/10/23 PVsyst Licensed to Page 3/7


Project: SMKN 1 BULAKAMBA
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:20
with v7.4.0

Main results
System Production
Produced Energy 13082.85 kWh/year Specific production 1507 kWh/kWp/year
Perf. Ratio PR 79.45 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 151.6 83.43 27.25 142.8 137.4 1042 981 0.791
February 147.0 85.12 27.10 142.1 137.3 1041 982 0.796
March 160.5 85.55 27.53 160.8 156.3 1172 1105 0.792
April 155.0 79.00 27.74 161.5 157.1 1180 1114 0.794
May 150.4 73.92 28.24 161.6 157.3 1181 1116 0.795
June 144.7 68.31 27.51 158.2 154.0 1163 1099 0.800
July 151.2 69.21 27.43 163.5 159.5 1200 1133 0.798
August 160.4 80.85 27.43 169.0 164.5 1237 1167 0.796
September 161.3 86.42 27.65 163.8 159.1 1195 1128 0.794
October 177.2 97.13 28.47 173.7 168.7 1263 1193 0.791
November 158.5 87.02 28.02 150.8 145.8 1099 1036 0.792
December 159.1 90.55 27.62 149.3 143.9 1091 1029 0.794
Year 1876.8 986.53 27.67 1897.2 1841.0 13865 13083 0.794

Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

23/10/23 PVsyst Licensed to Page 4/7


Project: SMKN 1 BULAKAMBA
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:20
with v7.4.0

Loss diagram
1877 kWh/m² Global horizontal irradiation
+1.1% Global incident in coll. plane

-2.96% IAM factor on global

1841 kWh/m² * 47 m² coll. Effective irradiation on collectors

efficiency at STC = 18.44% PV conversion

15989 kWh Array nominal energy (at STC effic.)


-0.62% PV loss due to irradiance level

-10.56% PV loss due to temperature

+0.75% Module quality loss

-2.15% Mismatch loss, modules and strings

-1.04% Ohmic wiring loss


13865 kWh Array virtual energy at MPP

-5.59% Inverter Loss during operation (efficiency)

0.00% Inverter Loss over nominal inv. power


0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
-0.06% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
13083 kWh Available Energy at Inverter Output
13083 kWh Energy injected into grid

23/10/23 PVsyst Licensed to Page 5/7


Project: SMKN 1 BULAKAMBA
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:20
with v7.4.0

Predef. graphs
Daily Input/Output diagram

System Output Power Distribution

23/10/23 PVsyst Licensed to Page 6/7