PVsyst - Simulation report


Grid-Connected System

Project: SMKN 1 WINDUSARI


Variant: New simulation variant
No 3D scene defined, no shadings
System power: 13.92 kWp
WINDUSARI, MAGELANG - Indonesia

Author
Project: SMKN 1 WINDUSARI
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:54
with v7.4.0

Project summary
Geographical Site Situation Project settings
WINDUSARI, MAGELANG Latitude -7.40 °S Albedo 0.20
Indonesia Longitude 110.20 °E
Altitude 490 m
Time zone UTC+7

Meteo data
WINDUSARI, MAGELANG
Meteonorm 8.1 (2016-2021), Sat=100% - Synthetic

System summary
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 12 / 0 °

System information
PV Array Inverters
Nb. of modules 48 units Nb. of units 3 units
Pnom total 13.92 kWp Pnom total 12.00 kWac
Pnom ratio 1.160

Results summary
Produced Energy 21252 kWh/year Specific production 1527 kWh/kWp/year Perf. Ratio PR 79.87 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Predef. graphs 6
Single-line diagram 7

23/10/23 PVsyst Licensed to Page 2/7


Project: SMKN 1 WINDUSARI
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:54
with v7.4.0

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 12 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon No Shadings Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer Photowatt Manufacturer Omron
Model PW60HT-CB-XF-290 Model KP 40H
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 290 Wp Unit Nom. Power 4.00 kWac
Number of PV modules 48 units Number of inverters 3 units
Nominal (STC) 13.92 kWp Total power 12.0 kWac
Modules 6 Strings x 8 In series Operating voltage 100-370 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.16
Pmpp 12.63 kWp
U mpp 233 V
I mpp 54 A

Total PV power Total inverter power


Nominal (STC) 14 kWp Total power 12 kWac
Total 48 modules Number of inverters 3 units
Module area 80.8 m² Pnom ratio 1.16

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 71 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses Strings Mismatch loss


Loss Fraction 2.0 % at MPP Loss Fraction 0.2 %

IAM loss factor


Incidence effect (IAM): Fresnel smooth glass, n = 1.526

0° 30° 50° 60° 70° 75° 80° 85° 90°


1.000 0.998 0.981 0.948 0.862 0.776 0.636 0.403 0.000

23/10/23 PVsyst Licensed to Page 3/7


Project: SMKN 1 WINDUSARI
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:54
with v7.4.0

Main results
System Production
Produced Energy 21252 kWh/year Specific production 1527 kWh/kWp/year
Perf. Ratio PR 79.87 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 130.5 72.80 24.84 122.5 117.7 1447 1359 0.797
February 136.0 80.05 24.80 131.5 127.0 1559 1469 0.802
March 143.2 75.34 25.16 143.1 138.6 1681 1583 0.795
April 152.7 77.52 25.30 158.7 154.1 1871 1767 0.800
May 154.0 73.24 25.87 166.9 162.2 1971 1863 0.802
June 155.2 58.26 25.06 173.3 168.9 2051 1939 0.804
July 161.8 58.65 24.95 179.0 174.5 2113 1996 0.801
August 170.8 72.08 24.93 181.8 177.4 2142 2024 0.800
September 172.8 72.53 25.17 175.8 171.3 2058 1944 0.794
October 188.9 84.98 25.95 184.9 179.9 2159 2038 0.792
November 159.5 83.37 25.40 151.1 146.1 1781 1678 0.798
December 152.9 86.73 25.12 142.9 137.5 1690 1593 0.801
Year 1878.3 895.55 25.21 1911.6 1855.2 22523 21252 0.799

Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

23/10/23 PVsyst Licensed to Page 4/7


Project: SMKN 1 WINDUSARI
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:54
with v7.4.0

Loss diagram
1878 kWh/m² Global horizontal irradiation
+1.8% Global incident in coll. plane

-2.95% IAM factor on global

1855 kWh/m² * 81 m² coll. Effective irradiation on collectors

efficiency at STC = 17.24% PV conversion

25828 kWh Array nominal energy (at STC effic.)


-0.57% PV loss due to irradiance level

-10.08% PV loss due to temperature

+0.75% Module quality loss

-2.15% Mismatch loss, modules and strings

-1.07% Ohmic wiring loss


22523 kWh Array virtual energy at MPP

-5.61% Inverter Loss during operation (efficiency)

0.00% Inverter Loss over nominal inv. power


0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
-0.04% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
21252 kWh Available Energy at Inverter Output
21252 kWh Energy injected into grid

23/10/23 PVsyst Licensed to Page 5/7


Project: SMKN 1 WINDUSARI
Variant: New simulation variant

PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:54
with v7.4.0

Predef. graphs
Daily Input/Output diagram

System Output Power Distribution

23/10/23 PVsyst Licensed to Page 6/7


PVsyst V7.4.0
VC0, Simulation date:
23/10/23 11:54
with v7.4.0