Professional Documents
Culture Documents
Hitachi_Energy_Resibloc_Transformer_General_Brochure_Eng-FINAL
Hitachi_Energy_Resibloc_Transformer_General_Brochure_Eng-FINAL
RESIBLOC®
Transformer technology
reducing environmental impact
2 | R E S I B L O C ® T R A N S F O R M E R T E C H N O LO GY R E D U C I N G E N V I R O N M E N TA L I M PAC T
Environmental protection,
reliability, and enhanced safety
The challenge In addition, the glass-fibers extend the range of temperatures at
Hitachi Energy offers a complete portfolio of dry-type which the transformer can be utilized; unrestricted use is
transformers utilizing unique and proven technologies, which possible even at a temperature of -60°C.
meet the varying needs of customers across various segments
and applications. A reliable transformer technology is essential Other advantages of RESIBLOC® technology relate to protection
in many industries such as nuclear, oil and gas, marine, mining, of the environment. It is entirely oil-free, and the use of other
metals, cement, pulp and paper, hydrogen, and chemical. flammable materials has also been reduced to a minimum, thus
avoiding any contamination in the transformer’s surroundings
At Hitachi Energy, we always go above and beyond. Our dry- and eliminating any additional fire risk.
type transformer solutions deliver reliability, protection, and
safety in even the harshest environments. Conventional RESIBLOC® provides a lot of potential for cost savings: its
solutions often fall short of these important requirements. special construction minimizes both the requirement for spares
inventories and the amount of maintenance work needed.
The solution
Hitachi Energy's RESIBLOC® cast-resin transformer:
• No risk for humans and the natural environment due to
contamination
• Non-explosive and flame-retardant
• Heavy load cycles (cold start to maximum load)
• High short-circuit withstand capability
• Stress due to tough ambient conditions
• Stress due to harmonics
• Overvoltage peaks
• Variable power factor control
• Minimized maintenance
The technology
The RESIBLOC® cast-resin transformer is a path-breaking innovation in the field
of naturally cooled dry-type transformers. The RESIBLOC® technology has been
continually design enhanced.
Fiberglass reinforcement – a guarantee against This is also applicable under extreme operating situations, such
crack formation as low ambient temperatures or sudden peak overloads.
Epoxy resin, reinforced with fiberglass rovings, is a material of
superior mechanical and dielectric strength. The low- and high- Since no molds are required for manufacturing a RESIBLOC®
voltage windings are positively joined to create a single transformer, windings can be individually dimensioned to a
compact block. This design gives RESIBLOC® a higher short- customer’s specific requirements. To ensure adequate cooling,
circuit withstand capability compared to conventionally dry-type for example, axial cooling channels can also be incorporated in
transformers. This unique technology protects the transformer the windings.
against crack formation even when exposed to extremely tough
operating conditions. Core construction
The construction of the core is one of the main drivers
Low-voltage winding determining the quality of a transformer. The material used and
Aluminum or copper foils are used for the low voltage winding of its geometrical configuration substantially influence loss figures
the RESIBLOC® transformer with a winding insulation of thermal and noise emissions. For the core of RESIBLOC®, grain-oriented
class F. The foil winding concept ensures a significant reduction transformer laminations are used, which are layered to form leg
in axial short-circuit forces. Low-voltage windings for and yoke stacks. Meticulous dimensional accuracy ensures that
transformers with a relatively low rating are constructed as layer noise emissions and losses are rigorously minimized.
windings to increase the filling factor.
The joints between the leg and yoke laminations are executed
High-voltage winding with 45° cuts and arranged in overlapping layers to ensure
The layered design ensures outstanding lightning impulse optimum matching of the flow pattern to the magnetic
voltage withstand capability thanks to its linear impulse voltage preferential direction. In modern-day step-lap technology, the
distribution. Round (or rectangular, as i the case of the more joints between the leg and yoke laminations exhibit multiple
sizable cross-sectional areas) conductors are made of offsets. An epoxy resin coating protects the core against
aluminum or copper. The windings' layer insulation and outer potential corrosion.
encapsulation are made from fiberglass-reinforced epoxy resin
of thermal class F. The individual conductor layers are coated Climate, environmental, and fire classes
using the roving wet winding process. After the winding The standard versions of RESIBLOC® dry-type transformers
operation is completed, the block windings are hardened in meet the most stringent requirements for climate,
special ovens. environmental, and fire classes certified as C4, E4, and F1 in
conformity with IEC 60076-11, with an additional verification of
The high-voltage winding is wound directly onto its low-voltage operation at -60°C. RESIBLOC® dry-type transformers can
counterpart. The positive connection between the high- and directly access environments with a high density of industries
low-voltage windings can be relied upon to prevent the windings and environments exposed to strong wind from the sea, such as
from shifting axially or radially against each other when exposed offshore oil and gas applications.
to short-circuit forces. The mutual spacing between the high-
and low-voltage windings, important for the dielectric strength,
is assured even in the event of a short-circuit or after a lengthy
period in transit.
www.hitachienergy.com/contact-us
hitachienergy.com
©Hitachi Energy 2021. All rights reserved.
Specifications subject to change without notice. 5233 EN Rev. A – printed in Germany (05.21)