Integrinex
Alpha/Numeric LCD Display: Displays wet well ESC Button [◄]: Press the [◄ESC] button to
level, set points, pump status, and setup back out of each menu and display the Process
parameters. Display Screen.
Output Status Colored LED’s: P1, P2 and P3 Increment/Decrement Button [▼▲]: Changes
Illuminates Orange when a pump is called to run, level set points and setup parameter values.
Illuminates Green when a pump is running, flashes
Green when a pump not called for with a running
The back of the Integrinex STANDARD includes Digital Input Terminal Strip: Connects pump and
the following: (refer to Figure 2) alarm inputs to controller for pump and alarm
status display and operation.
Air Bubbler Transducer Input: Accepts tubing
connection from air bubbler line.
4. Repeat steps 2, and 3 to set all other set point Low Water Alarm
ON and OFF levels. High Water Alarm
Phase Fault
An “X” is in the box if condition is Active.
NOTE
Pump ON levels should be set at least 0.3 feet or
PRESS [◄ESC] to exit.
more above the pump OFF levels. Closer settings
may cause short cycling of the pumps.
Alarms
NOTE
The set points are independent and do not interact PRESS [ENT►] The screen will display:
with other set points. The set point may be
adjusted at any time without effecting pump View Alarm History
operation. If pumps are operating when set points Clear Alarm History
are changed, pumps need to complete that Alarm Light Test
pumping cycle before new set points take effect.
Main Menu PRESS [ENT►] The screen will display the last
16 alarms: PRESS [ENT►] The screen will
Press the [ENT►] button on the front of the
display Date and Time alarm occurred and if alarm
Integrinex Standard controller to access the Main
is active.
Menu screen. Use the up and down arrow keys
( , ) to select one of the following screens:
Are You Sure? Press the [ENT►] button on the front of the
Integrinex Standard controller to access the Main
[◄] = NO YES =[ ►] Menu screen. Use the up and down arrow keys
( , ) to access the SETUP. Press the [ENT►]
PRESS [ENT►] to Clear Alarm History. button on the front of the Integrinex Standard
PRESS [◄ESC] to Return to active settings. controller to select SETUP. You must enter the
access code to unlock setup. The valid access
Alarm Light Test code is 0305.
Press [ENT►] to display:
PRESS [ENT►] The screen will display: Access Code:
XXXX
Are You Sure? (Digits are only displayed when [▲▼] is
depressed)
[◄] = NO YES =[ ►]
1. Press [ENT►] to accept the digit “0”. The
PRESS [ENT►] to Test Alarm Light. cursor shifts to the next digit to the right.
Supervisor Password
Adjust Pump Runtime PRESS [▲▼] to toggle between options and
Restore Defaults PRESS [ENT►] The screen will display:
Not Used
7. After setup adjustments have been made,
High Level Alarm
setup may be password protected. The
Low Level Alarm
Integrinex Standard controller will return to the
All Level Alarms
Normal Operation screen automatically after a
Pump 1 High Temp
short delay or immediately by pressing the
Pump 2 High Temp
[◄ESC] button twice.
All Pump High Temps
Pump 1 Fault
Pump 2 Fault
All Pump Faults
SETUP ADJUSTMENTS General Alarm Light
General Alarm Horn
Level Trig Output 1
NOTE Level Trig Output 2
Setup programming that follows is shown as Level Trig Output 3
default unless otherwise noted.
Pump 2 Thermal
Pump 1 Moist/Therm
Pump 2 Moist/Therm
Station Low Temp Analog In Zero Value
Phase Fault
Zero calibration sets the value displayed when the
transducer is exposed to zero water (atmospheric)
pressure. To set:
PRESS [▲▼] to toggle between options. PRESS
1. Apply zero pressure to the Integrinex
[ENT►] to accept change.
STANDARD input. Allow several seconds for
the Integrinex STANDARD reading to stabilize.
0-5 Volts Span calibration sets the value displayed when the
0-10 Volts transducer is exposed to a known water pressure
4-20 mAmps (depth). To set:
Analog In Zero PRESS [▲▼] to select xx.x ft for span value and
Analog In Span PRESS [ENT►] to accept change.
Analog Out Zero
Analog Out Span
Set Time/Date
Lead Pump
Lag Pump PRESS [ENT►] The screen will display:
High Water Alarm
Low Water Alarm Year = 2014
Month = 1
PRESS [▲▼] to toggle between options and Day = 5
PRESS [ENT►] The screen will display: Hour = 3pm
Minute = 50
Stop = 2.0
Start = 4.0
PRESS [▲▼] to toggle between options and
1. Use the up and down Arrow keys [▲▼] to PRESS [ENT►] to accept change.
adjust the set point levels. Press [ENT►]
to save set points.
Supervisor Password
2. Repeat steps to set all other set point ON
and OFF levels.
PRESS [ENT►] The screen will display
Restore Defaults
PRESS [ENT►] The screen will display:
[◄] = NO YES =[ ►]
Notes: