SECTION 3.4 INTEGRINEX STANDARD MENU TREE

DESCRIPTION Menu screen. Use the up and down arrow keys


( , ) to access the SETUP. Press the [ENT►]
The Integrinex STANDARD Interface provides a button on the front of the Integrinex Standard
means for the pump station operator to monitor controller to select SETUP. Enter the Access
process and equipment status as well as make Code, refer to the Integrinex Setup section 12.1.
adjustments to the control system. The Integrinex
interface is normally used for automatic operation. 2. Use the up and down arrow keys ( , ) to
The Integrinex STANDARD Menu Tree (Table 1) access the LEVEL SETPOINTS. Press the
indicates the operation and display functions, [ENT►] button on the front of the Integrinex
which have been programmed by Gorman-Rupp. Standard controller to select LEVEL SETPOINTS.
Use the menu tree as a quick reference index to
Use the up and down arrow keys ( , ) to select
available screens.
desired ON and OFF set points.
OPERATION
3. Use the up and down Arrow keys ( , ) to
Up / Down Arrow Keys: Some screens require adjust the set point levels. Press the [ENT ►]
object selection from a list. Use these keys to button to save set points.
position the cursor next to the object you desire,
then press the Enter key to make the selection. 4. Repeat steps 2, and 3 to set all other set point
ON and OFF levels.
Left / Right Arrow Keys: Some screens require
data to be entered from the interface. In such Refer to Table 1, Integrinex STANDARD Menu
cases, uses these keys to move the cursor next to Tree for available screens. Refer to Section 12 for
the data entry field you desire, then use the Up / specific instructions using the Integrinex
Down Arrow Keys to change the numeric value to STANDARD Unit.
be entered.
TROUBLESHOOTING
Enter Key: Use the Enter key to enter into the
menu and store a value. 1. If the Integrinex STANDARD interface fails
to function, make certain the control circuits are
ESC Key: Use the ESC key to move out of a energized, that the appropriate switches and
menu. circuit breakers are closed and that all fuses are
good. Power must be on at the Pressure/Logic
ADJUSTMENTS control panel.

2. Control assembly troubleshooting is


CAUTION provided in Pump Station section 11.1 or refer to
Adjustments are best made when the pumps the Integrinex STANDARD manuals in section
are off. If wet well level must be maintained, 12.1 for more detailed troubleshooting of this
operate the pumps manually during device.
adjustment procedures. Adjustments made
during automatic mode may cause unexpected SCHEDULED MAINTENANCE
operation.
The components of the Integrinex STANDARD
Set points interface are solid state requiring no scheduled
maintenance. Replace a defective unit as
1. Press the [ENT►] button on the front of the required. Please contact your Gorman-Rupp
Integrinex Standard controller to access the Main representative for replacement.

Section 3.4 1 of 3 ES-236


abcde InteGRinex Standard Menu

Process Display Main Menu


Wet Well Level Display (D) Wet Well Level Display (D)
Pump 1 Status (D) Time/Date (D)
Pump 2 Status (D) Pump Status (SLS)
Pump 3 Status (D) Station Status (SLS)
Alarms (SLS)
Go To (P) {ENT►} Level Simulation (SLS)
Setup (SLS)

Down Arrow (P) {▼}


Up Arrow (P) {▲}
Go To (P) {ENT►}
Go Back (P) {ESC◄}

Pump Status 1,2,3 Station Status Alarms Level Simulation Setup (Access Code)

Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) #### (DE)
Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D)
Runtime ######.#(D) Low Water Alarm(D) View Alarm History(SLS) High Water Alarm(D) Go To (P) {ENT►}
H-O-A (Auto) (D) High Water Alarm (D) Clear Alarm History (CLS) Standby Pump (D) Go Back (P) {ESC◄}
High Temp (D) Phase Fault (D) Alarm Light Test (CLS) Lag Pump (D)
Start Fail (D) Station Low Temp (D) Lead Pump (D) Password: 0305 (DEFAULT)
Fault (D) Down Arrow (P) {▼} Low Water Alarm(D)
Down Arrow (P) {▼} Up Arrow (P) {▲}
Down Arrow (P) {▼} Up Arrow (P) {▲} Go To (P) {ENT►} Down Arrow (P) {▼}
Up Arrow (P) {▲} Go To (P) {ENT►} Go Back (P) {ESC◄} Up Arrow (P) {▲}
Go To (P) {ENT►} Go Back (P) {ESC◄} Go To (P) {ENT►}
Go Back (P) {ESC◄} Go Back (P) {ESC◄}

View Alarm History Clear Alarm History Alarm Light Test

Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Time/Date (D)
Logged Alarm (CLS) No (CLS) No (CLS)
Yes (CLS) Yes (CLS)
Down Arrow (P) {▼}
Up Arrow (P) {▲} Go To (P) {ENT►} Go To (P) {ENT►}
Go To (P) {ENT►} Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Go Back (P) {ESC◄}

View Alarm Detail Setup

Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D)
Alarm Tag (D) Units (SLS)
Alarm Tag Time/Date (D) Pump Count (SLS)
Condition Active (D) Digital Outputs (SLS)
Digital Inputs (SLS)
Go Back (P) {ESC◄} Analog Output (SLS)
Analog Input (SLS)
Analog Calibration (SLS)
Level Setpoints (SLS)
Pump Sequencer (SLS)
LEGEND Timer Setpoints (SLS)
SLS - Screen List Selector Set Time/Date (SLS)
CLS - Control List Selector Supervisor Password (SLS)
DE - Data Entry Adjust Pump Runtime (SLS)
D - Display Restore Defaults (SLS)
P - Push-Button
Down Arrow (P) {▼}
Up Arrow (P) {▲}
Go To (P) {ENT►}
Go Back (P) {ESC◄}
Note: Menu tree lists all possible options, some
options may not be in your specific configuration.

Table 1. Integrinex Standard Menu Tree 2 of 3


Units Pump Count Digital Outputs Digital Inputs Analog Output Analog Input

Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D)
English (CLS) Simplex (1 Pump) (CLS) Output 2 (SLS) Input 3 (SLS) 0 - 5 Volts (CLS) Internal Pressure (CLS)
Metric (CLS) Duplex (2 Pumps) (CLS) Output 3 (SLS) Input 4 (SLS) 0 - 10 Volts (CLS) External 0 - 5V (CLS)
Triplex (3 Pumps) (CLS) Output 4 (SLS) Input 5 (SLS) 4 - 20 mAmps (CLS) External 4 - 20mA (CLS)
Down Arrow (P) {▼} Output 5 (SLS) Input 6 (SLS)
Up Arrow (P) {▲} Down Arrow (P) {▼} Output 6 (SLS) Input 7 (SLS) Down Arrow (P) {▼} Down Arrow (P) {▼}
Go To (P) {ENT►} Up Arrow (P) {▲} Output 7 (SLS) Input 8 (SLS) Up Arrow (P) {▲} Up Arrow (P) {▲}
Go Back (P) {ESC◄} Go To (P) {ENT►} Output 8 (SLS) Input 9 (SLS) Go To (P) {ENT►} Go To (P) {ENT►}
Go Back (P) {ESC◄} Input 10 (SLS) Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Down Arrow (P) {▼} Input 11 (SLS)
Up Arrow (P) {▲}
Go To (P) {ENT►} Down Arrow (P) {▼}
Go Back (P) {ESC◄} Up Arrow (P) {▲}
Go To (P) {ENT►}
Go Back (P) {ESC◄}

Output 2-8 Input 3-11 Analog Out Calibration

Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Time/Date (D)
Not Used (CLS) Not Used (CLS) Zero Value = XXX ft (DE)
High Level Alarm (CLS) Pump 1 High Temp (CLS) Span Value = XXX ft (DE)
Low Level Alarm (CLS) Pump 2 High Temp (CLS)
All Level Alarms (CLS) Pump 3 High Temp (CLS)
Pump 1 High Temp (CLS) Pump 1 Fault (CLS) Down Arrow (P) {▼}
Pump 2 High Temp (CLS) Pump 2 Fault (CLS) Up Arrow (P) {▲}
Pump 3 High Temp (CLS) Pump 3 Fault (CLS) Go To (P) {ENT►}
All Pump High Temps (CLS) Pump 1 Overload (CLS) Go Back (P) {ESC◄}
Pump 1 Fault (CLS) Pump 2 Overload (CLS) Level Setpoints
Pump 2 Fault (CLS) Pump 1 VFD Fault (CLS)
Pump 3 Fault (CLS) Pump 2 VFD Fault (CLS) Wet Well Level Display (D) Analog Calibration
All Pump Faults (CLS) Pump 1 RVSS Fault (CLS) Time/Date (D)
General Alarm Light (CLS) Pump 2 RVSS Fault (CLS) Lead Pump Stop (DE) Wet Well Level Display (D)
General Alarm Horn (CLS) Pump 1 Moisture (CLS) Lead Pumps Start (DE) Time/Date (D)
Level Trig Output 1 (CLS) Pump 2 Moisture (CLS) Lag Pump Stop (DE) Analog In Zero (SLS)
Level Trig Output 2 (CLS) Pump 1 Thermal (CLS) Lag Pump Start (DE) Analog In Span (SLS)
Level Trig Output 3 (CLS) Pump 2 Thermal (CLS) Standby Pump Stop (DE) Analog Out Zero (SLS)
Pump 1 Moist/Therm (CLS) Standby Pump Start (DE) Analog Out Span (SLS)
Down Arrow (P) {▼} Pump 2 Moist/Therm (CLS) High Water Reset (DE)
Up Arrow (P) {▲} Pump 3 Moist/Therm (CLS) High Water Alarm (DE) Down Arrow (P) {▼}
Go To (P) {ENT►} Station Low Temp (CLS) Low Water Reset (DE) Up Arrow (P) {▲}
Go Back (P) {ESC◄} Phase Fault (CLS) Low Water Alarm (DE) Go To (P) {ENT►}
Go Back (P) {ESC◄}
Down Arrow (P) {▼} Down Arrow (P) {▼}
Up Arrow (P) {▲} Up Arrow (P) {▲}
Go To (P) {ENT►} Go To (P) {ENT►} Analog In Calibration
Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Wet Well Level Display (D)
Time/Date (D)
Adjust Pump Runtime Adjust Pump Runtime Set Time/Date Level Setpoints Zero Value = XXX (CLS)
Span Value = XXX ft (CLS)
Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Span Level (DE)
Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D)
######.# (DE) Pump 1 Runtime (SLS) Year (DE) Lead Pump (SLS) Down Arrow (P) {▼}
Pump 2 Runtime (SLS) Month (DE) Lag Pump (SLS) Up Arrow (P) {▲}
Down Arrow (P) {▼} Pump 3 Runtime (SLS) Day (DE) Standby Pump (SLS) Go To (P) {ENT►}
Up Arrow (P) {▲} Hour (DE) High Water Alarm (SLS) Go Back (P) {ESC◄}
Go To (P) {ENT►} Down Arrow (P) {▼} Minute (DE) Low Water Alarm (SLS)
Go Back (P) {ESC◄} Up Arrow (P) {▲}
Go To (P) {ENT►} Down Arrow (P) {▼} Down Arrow (P) {▼}
Go Back (P) {ESC◄} Up Arrow (P) {▲} Up Arrow (P) {▲}
Go To (P) {ENT►} Go To (P) {ENT►}
Go Back (P) {ESC◄} Go Back (P) {ESC◄}

Restore Defaults Supervisor Password Timer Setpoints Pump Sequencer

Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Control Timer Setpoints Time/Date (D) Time/Date (D)
No (CLS) #### (DE) Pump Start Delay (SLS) None (CLS)
Yes (CLS) Password: 0305 (DEFAULT) Wet Well Level Display (D) Pump Stop Delay (SLS) Tabular (CLS)
Time/Date (D) Start Fail Delay (SLS) Least Time (CLS)
Go To (P) {ENT►} Down Arrow (P) {▼} Pump Start Delay (DE) Alarm Input Delay (SLS) Pump 1 Lead (CLS)
Go Back (P) {ESC◄} Up Arrow (P) {▲} Pump Stop Delay (DE) Antiseptic Timer (SLS) Pump 2 Lead (CLS)
Go To (P) {ENT►} Start Fail Delay (DE) Alternation Interval (SLS) Pump 3 Lead (CLS)
Go Back (P) {ESC◄} Alarm Input Delay (DE)
Antiseptic Timer (DE) Down Arrow (P) {▼} Down Arrow (P) {▼}
LEGEND Alternation Interval (SLS) Up Arrow (P) {▲} Up Arrow (P) {▲}
SLS - Screen List Selector Go To (P) {ENT►} Go To (P) {ENT►}
CLS - Control List Selector Down Arrow (P) {▼} Go Back (P) {ESC◄} Go Back (P) {ESC◄}
DE - Data Entry Up Arrow (P) {▲}
D - Display Go To (P) {ENT►}
P - Push-Button Go Back (P) {ESC◄}
Table 1. Integrinex Standard Menu Tree 3 of 3