ES-236
ES-236
Pump Status 1,2,3 Station Status Alarms Level Simulation Setup (Access Code)
Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) #### (DE)
Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D)
Runtime ######.#(D) Low Water Alarm(D) View Alarm History(SLS) High Water Alarm(D) Go To (P) {ENT►}
H-O-A (Auto) (D) High Water Alarm (D) Clear Alarm History (CLS) Standby Pump (D) Go Back (P) {ESC◄}
High Temp (D) Phase Fault (D) Alarm Light Test (CLS) Lag Pump (D)
Start Fail (D) Station Low Temp (D) Lead Pump (D) Password: 0305 (DEFAULT)
Fault (D) Down Arrow (P) {▼} Low Water Alarm(D)
Down Arrow (P) {▼} Up Arrow (P) {▲}
Down Arrow (P) {▼} Up Arrow (P) {▲} Go To (P) {ENT►} Down Arrow (P) {▼}
Up Arrow (P) {▲} Go To (P) {ENT►} Go Back (P) {ESC◄} Up Arrow (P) {▲}
Go To (P) {ENT►} Go Back (P) {ESC◄} Go To (P) {ENT►}
Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Time/Date (D)
Logged Alarm (CLS) No (CLS) No (CLS)
Yes (CLS) Yes (CLS)
Down Arrow (P) {▼}
Up Arrow (P) {▲} Go To (P) {ENT►} Go To (P) {ENT►}
Go To (P) {ENT►} Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Go Back (P) {ESC◄}
Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D)
Alarm Tag (D) Units (SLS)
Alarm Tag Time/Date (D) Pump Count (SLS)
Condition Active (D) Digital Outputs (SLS)
Digital Inputs (SLS)
Go Back (P) {ESC◄} Analog Output (SLS)
Analog Input (SLS)
Analog Calibration (SLS)
Level Setpoints (SLS)
Pump Sequencer (SLS)
LEGEND Timer Setpoints (SLS)
SLS - Screen List Selector Set Time/Date (SLS)
CLS - Control List Selector Supervisor Password (SLS)
DE - Data Entry Adjust Pump Runtime (SLS)
D - Display Restore Defaults (SLS)
P - Push-Button
Down Arrow (P) {▼}
Up Arrow (P) {▲}
Go To (P) {ENT►}
Go Back (P) {ESC◄}
Note: Menu tree lists all possible options, some
options may not be in your specific configuration.
Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D)
English (CLS) Simplex (1 Pump) (CLS) Output 2 (SLS) Input 3 (SLS) 0 - 5 Volts (CLS) Internal Pressure (CLS)
Metric (CLS) Duplex (2 Pumps) (CLS) Output 3 (SLS) Input 4 (SLS) 0 - 10 Volts (CLS) External 0 - 5V (CLS)
Triplex (3 Pumps) (CLS) Output 4 (SLS) Input 5 (SLS) 4 - 20 mAmps (CLS) External 4 - 20mA (CLS)
Down Arrow (P) {▼} Output 5 (SLS) Input 6 (SLS)
Up Arrow (P) {▲} Down Arrow (P) {▼} Output 6 (SLS) Input 7 (SLS) Down Arrow (P) {▼} Down Arrow (P) {▼}
Go To (P) {ENT►} Up Arrow (P) {▲} Output 7 (SLS) Input 8 (SLS) Up Arrow (P) {▲} Up Arrow (P) {▲}
Go Back (P) {ESC◄} Go To (P) {ENT►} Output 8 (SLS) Input 9 (SLS) Go To (P) {ENT►} Go To (P) {ENT►}
Go Back (P) {ESC◄} Input 10 (SLS) Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Down Arrow (P) {▼} Input 11 (SLS)
Up Arrow (P) {▲}
Go To (P) {ENT►} Down Arrow (P) {▼}
Go Back (P) {ESC◄} Up Arrow (P) {▲}
Go To (P) {ENT►}
Go Back (P) {ESC◄}
Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Time/Date (D)
Not Used (CLS) Not Used (CLS) Zero Value = XXX ft (DE)
High Level Alarm (CLS) Pump 1 High Temp (CLS) Span Value = XXX ft (DE)
Low Level Alarm (CLS) Pump 2 High Temp (CLS)
All Level Alarms (CLS) Pump 3 High Temp (CLS)
Pump 1 High Temp (CLS) Pump 1 Fault (CLS) Down Arrow (P) {▼}
Pump 2 High Temp (CLS) Pump 2 Fault (CLS) Up Arrow (P) {▲}
Pump 3 High Temp (CLS) Pump 3 Fault (CLS) Go To (P) {ENT►}
All Pump High Temps (CLS) Pump 1 Overload (CLS) Go Back (P) {ESC◄}
Pump 1 Fault (CLS) Pump 2 Overload (CLS) Level Setpoints
Pump 2 Fault (CLS) Pump 1 VFD Fault (CLS)
Pump 3 Fault (CLS) Pump 2 VFD Fault (CLS) Wet Well Level Display (D) Analog Calibration
All Pump Faults (CLS) Pump 1 RVSS Fault (CLS) Time/Date (D)
General Alarm Light (CLS) Pump 2 RVSS Fault (CLS) Lead Pump Stop (DE) Wet Well Level Display (D)
General Alarm Horn (CLS) Pump 1 Moisture (CLS) Lead Pumps Start (DE) Time/Date (D)
Level Trig Output 1 (CLS) Pump 2 Moisture (CLS) Lag Pump Stop (DE) Analog In Zero (SLS)
Level Trig Output 2 (CLS) Pump 1 Thermal (CLS) Lag Pump Start (DE) Analog In Span (SLS)
Level Trig Output 3 (CLS) Pump 2 Thermal (CLS) Standby Pump Stop (DE) Analog Out Zero (SLS)
Pump 1 Moist/Therm (CLS) Standby Pump Start (DE) Analog Out Span (SLS)
Down Arrow (P) {▼} Pump 2 Moist/Therm (CLS) High Water Reset (DE)
Up Arrow (P) {▲} Pump 3 Moist/Therm (CLS) High Water Alarm (DE) Down Arrow (P) {▼}
Go To (P) {ENT►} Station Low Temp (CLS) Low Water Reset (DE) Up Arrow (P) {▲}
Go Back (P) {ESC◄} Phase Fault (CLS) Low Water Alarm (DE) Go To (P) {ENT►}
Go Back (P) {ESC◄}
Down Arrow (P) {▼} Down Arrow (P) {▼}
Up Arrow (P) {▲} Up Arrow (P) {▲}
Go To (P) {ENT►} Go To (P) {ENT►} Analog In Calibration
Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Wet Well Level Display (D)
Time/Date (D)
Adjust Pump Runtime Adjust Pump Runtime Set Time/Date Level Setpoints Zero Value = XXX (CLS)
Span Value = XXX ft (CLS)
Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Span Level (DE)
Time/Date (D) Time/Date (D) Time/Date (D) Time/Date (D)
######.# (DE) Pump 1 Runtime (SLS) Year (DE) Lead Pump (SLS) Down Arrow (P) {▼}
Pump 2 Runtime (SLS) Month (DE) Lag Pump (SLS) Up Arrow (P) {▲}
Down Arrow (P) {▼} Pump 3 Runtime (SLS) Day (DE) Standby Pump (SLS) Go To (P) {ENT►}
Up Arrow (P) {▲} Hour (DE) High Water Alarm (SLS) Go Back (P) {ESC◄}
Go To (P) {ENT►} Down Arrow (P) {▼} Minute (DE) Low Water Alarm (SLS)
Go Back (P) {ESC◄} Up Arrow (P) {▲}
Go To (P) {ENT►} Down Arrow (P) {▼} Down Arrow (P) {▼}
Go Back (P) {ESC◄} Up Arrow (P) {▲} Up Arrow (P) {▲}
Go To (P) {ENT►} Go To (P) {ENT►}
Go Back (P) {ESC◄} Go Back (P) {ESC◄}
Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D) Wet Well Level Display (D)
Time/Date (D) Time/Date (D) Control Timer Setpoints Time/Date (D) Time/Date (D)
No (CLS) #### (DE) Pump Start Delay (SLS) None (CLS)
Yes (CLS) Password: 0305 (DEFAULT) Wet Well Level Display (D) Pump Stop Delay (SLS) Tabular (CLS)
Time/Date (D) Start Fail Delay (SLS) Least Time (CLS)
Go To (P) {ENT►} Down Arrow (P) {▼} Pump Start Delay (DE) Alarm Input Delay (SLS) Pump 1 Lead (CLS)
Go Back (P) {ESC◄} Up Arrow (P) {▲} Pump Stop Delay (DE) Antiseptic Timer (SLS) Pump 2 Lead (CLS)
Go To (P) {ENT►} Start Fail Delay (DE) Alternation Interval (SLS) Pump 3 Lead (CLS)
Go Back (P) {ESC◄} Alarm Input Delay (DE)
Antiseptic Timer (DE) Down Arrow (P) {▼} Down Arrow (P) {▼}
LEGEND Alternation Interval (SLS) Up Arrow (P) {▲} Up Arrow (P) {▲}
SLS - Screen List Selector Go To (P) {ENT►} Go To (P) {ENT►}
CLS - Control List Selector Down Arrow (P) {▼} Go Back (P) {ESC◄} Go Back (P) {ESC◄}
DE - Data Entry Up Arrow (P) {▲}
D - Display Go To (P) {ENT►}
P - Push-Button Go Back (P) {ESC◄}
Table 1. Integrinex Standard Menu Tree 3 of 3