SF832-D-080-SPC-002 - Technical Specification for F&G Cables
SF832-D-080-SPC-002 - Technical Specification for F&G Cables
SF832-D-080-SPC-002
REVISION HISTORY
CONTENTS
1 GENERAL ............................................................................................................................................. 4
2 DEFINITIONS ....................................................................................................................................... 4
3 REFERENCE DRAWINGS AND DOCUMENTS............................................................................. 4
4 FIRE AND GAS SYSTEMS CABLES ACCORDING TO BRITISH STANDARD BS5839
PART-1 .......................................................................................................................................................... 5
5 BS5839-1 CABLE PRODUCT SPECIFICATION - STANDARD / ENHANCED ......................... 5
6 OTHER STANDARDS REFERRED TO WITHIN BS5839-1 ......................................................... 5
7 ALARM, SYSTEMS & CABLE PRODUCTS COVERED WITHIN BS5839-1 ............................. 6
8 BS5389 CABLE PRODUCTS ............................................................................................................. 6
9 TECHNICAL SPECIFICATIONS FOR F&G CABLES .................................................................... 6
9.1 APPLICATION ....................................................................................................................................... 6
9.2 CHARACTERISTICS ............................................................................................................................ 6
9.3 CONSTRUCTION .................................................................................................................................. 6
9.4 STANDARDS ......................................................................................................................................... 7
9.5 DIMENSIONS......................................................................................................................................... 7
9.6 ELECTRICAL CHARACTERISTICS .................................................................................................. 7
9.7 CURRENT CARRYING CAPACITY ................................................................................................... 8
9.8 VOLTAGE DROP .................................................................................................................................. 8
9.9 DE-RATING FACTORS ........................................................................................................................ 9
1 GENERAL
The scope of work to be performed by the Contractor “ ALTHAAER ALARABI CO.” is for Power Transmission
Line to Siba Remote Areas, which mainly includes but not limits to the following works:
To supply power to various remote sites in Siba gas field, KEIL intends to construct the permanent power
transmission network to reduce the operation and maintenance expenditures. In the field there are multiple
locations that fed power through temporary and solar power sources to the various remote facilities. This
project is intended to supply permanent MV/ LV power supply to the below locations from single power
source and the existing power sources shall be used as backup.
• Siba1
• Siba4
• Hub 1
• BOC Camp
• Raw Water Intake Station (RWI)
• BOC Main Check Point
2 DEFINITIONS
COMPANY: Kuwait Energy Iraq Limited Company (KEIL)
CONTRACTOR : Al-Thaer Al-Arabi Company
SUB-CONTRACTOR: Tareq Al-Qudra Company.
Project: EPC Power Transmission Line to Siba Remote Areas.
Work: All items and services to be provided as described within this technical document.
May: Indicates freedom of choice to comply with requirements
Shall: Indicates a mandatory requirement
Should: Indicates that the requirement is strongly recommended, and should be adhered to as best as
possible.
4 FIRE AND GAS SYSTEMS CABLES ACCORDING TO BRITISH STANDARD BS5839 PART-1
BS5839 cable is designed to meet the comprehensive British Standard BS5839-1 detailing a code of practice
for the design, commissioning, installation and maintenance of fire detection and fire alarm systems in non-
domestic buildings. These range from single manual call points to complex networked systems with
numerous automatic fire detection and communicating control panels. The Standard covers the operation of
fire protection systems such as smoke control, emergency lighting, automatic door release, fire alarm
systems, voice alarm systems, fire extinguishing systems, and any associated safety measures such as
elevator grounding, valve closing, or air handling shutdowns.
In addition to complying with the specification set out in BS5839-1, when tested in accordance with EN
50200, Standard fire performance cables must achieve a class of at least PH30. They must also maintain
circuit integrity for at least 30 minutes when exposed to a sequence of flame, mechanical shock and water
spray. The requirement for Enhanced fire-resistant cables is 120 minutes.
Enhanced fire-resistant cables are also recommended for the following applications:
in un-sprinklered buildings (or areas) in which the fire strategy involves evacuation of occupants in
four or more phases
In un-sprinklered buildings of greater than 30m in height
In un-sprinklered premises and sites in which a fire in one area could affect cables of critical signal
path associated with areas remote from fire, in which it is envisaged people will remain in occupation
during the course of the fire
In any setting where, on the basis of a fire risk assessment, the designer, specifier or regulatory
authority considers that use of Enhanced fire resisting cables is required.
The different parts of this Standard cover the variations in practice for domestic and non-domestic usage
as well as other applications and should be referred to directly when commissioning and designing any
project.
Control and indicating equipment including voice alarm and power supplies
Wireless, flame, beam, aspirating, smoke, heat and multi-sensor detectors
Manual call points
Line units including input and output devices
Alarm warning devices including visual alarms, loudspeakers and sounders
Alarm transmission equipment
Signaling systems
9.1 APPLICATION
Standard fire-resistant cables for use primarily in fire detection, fire alarm, voice alarm, and emergency
lighting circuits. These cables are designed to continue to operate for a period of time in a fire situation.
‘Standard’ fire resistance is recommended for general use.
9.2 CHARACTERISTICS
Voltage Rating Uo/U
300/500V
Temperature Rating
-40°C to +90°C
Minimum Bending Radius
6 x overall diameter
9.3 CONSTRUCTION
Conductor
1.5mm2 - 2.5mm2: Class 1 solid Copper
4mm2 and over: Class 2 stranded Copper
Insulation
High-performance fire-resistant silicone rubber
Overall Screen
Al/PET (Aluminium/Polyester Tape)
Circuit Protective Conductor
Tinned copper
Outer Sheath
LSZH (Low Smoke Zero Halogen)
Core Identification
2 cores: Blue, Brown + Bare Earth
3 cores: Brown, Black, Grey + Bare Earth
4 cores: Blue, Brown, Black, Grey
Sheath Colour
Red, White
9.4 STANDARDS
BS 7629-1, BS 5839-1, BS EN 50200-PH30-PH60-PH90-
PH120, BS 6387, BS 5266-1, BS 8519, BS EN 60228
Low Smoke Zero Halogen to IEC/EN 60754-1/2,
IEC/EN 61034-1/2
9.5 DIMENSIONS
Class 1 Solid Plain Conductor