electrical plan

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

LEGEND

LOAD COMPUTATION LOAD OF SCHEDULE


By occupancy PB1
LOAD
CKT # DESCRIPTION QTY WATT VOLT AMP BREAKER SIZE OF WIRE SIZE OF PIPE
RATING

1 LIGHTING OUTLET 5 500 230 2.17 15AT/50AF/2P 2-2.0mm^2 THHN COPPER WIRE 15mmØ PVC PIPE
Commercial = 16 va/sq.m 2
CONVINIENCE OUTLET 5 900 230 3.91 20AT/50AF/2P 2-3.5mm^2 THHN COPPER WIRE 20mmØ PVC PIPE

Total floor area = 500.00 sq.m 3 1HP ACU 1 746 230 3.24 30AT/50AF/2P 2-5.5mm^2 THHN COPPER WIRE 20mmØ PVC PIPE
PB

4 MOTOR PUMP 1HP 1 3.26 230 3.26 30AT/50AF/2P 2-5.5mm^2 THHN COPPER WIRE 20mmØ PVC PIPE M

General TOTAL 12.58

lighting load: 500.00 sq.m x 16 va/sq.m = 8,000 va I = 12.58 AMP

C
Small appliance load = 3,000 va PB2 S
11,000 va LOAD
S
CKT # DESCRIPTION QTY WATT VOLT AMP BREAKER SIZE OF WIRE SIZE OF PIPE
RATING
S
1 LIGHTING OUTLET 5 500 230 2.17 15AT/50AF/2P 2-2.0mm^2 THHN COPPER WIRE 15mmØ PVC PIPE
Applying demand factor CONVINIENCE OUTLET 5 900 230 3.91 20AT/50AF/2P 2-3.5mm^2 THHN COPPER WIRE 20mmØ PVC PIPE
2
first 3,000 va @ 100 % d.f = 3,000.00 va 3 1HP ACU 1 746 230 3.24 30AT/50AF/2P 2-3.5mm^2 THHN COPPER WIRE 20mmØ PVC PIPE
ACU
remaining 11,000 va @ 35% d.f = 3,850.00 va 4 SPARE
TOTAL 9.32
Net general lighting & small appliance load = 4,386.00 va
I = 9.32 AMP

Total computed current: 6,850 va / 230 v :29.78amps I TOTAL = 21.90 AMP


USE: 2- 14mm THW WIRES, COPPER IN 25mmØ RSC PIPE
AS MAIN FEEDER CONDUCTORS AND PIPE RESPECTIVELY
PROVIDE: 2-40AT, 2P, 220V, 60HZ ACB AS MAIN
ELECTRICAL NOTES

M M

RISER DIAGRAM
OWNER : PROFESSIONAL ELECTRICAL ENGINEER : PROJECT TITLE : CONTENTS : SHEET NO :

ASBUILT PLAN
CATHERINE P. ZAMORAS LOCATION : AS SHOWN
BARANGAY GREDU, PANABO CITY