COMMISSIONING TEST RECORD

Contract no.:

Customer: End Client: Page:


SEC-EOA Page 1 of 1
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation E03 CT CT TESTING

1. General Data & Information:

Manufacturer: ABB
Designation No.: CT2-3 Bus Section
CT2 Type: TAT UA311632P1459
CT3 Type: TAT UA311632P1460
Serial No.:

R-23020410 R-23020425
CT2 Y-23020408 CT3 Y-23020424
B-23020416 B-23020423

Feeder : E03-Bus Section


2. Insulation Resistance Test
a. Primary-Earth:
Applied Voltage: 5000V DC Primary-Earth
Phase R(GΩ) Phase Y(GΩ) Phase B(GΩ) Remarks
247 247 112.1 ok

b. Core-(Core-Earth):
Applied Voltage: 500V DC secondary-Earth/Core-Core
Core-(Core-Earth) Phase R(GΩ) Phase Y(GΩ) Phase B(GΩ) Remarks
CT2 Core C-1 2.46 4.05 3.21 ok
CT2 Core C-2 2.15 4.62 2.66 ok
CT2 Core C-3 3.31 5.48 3.31 ok
CT3 Core C-4 11.98 10.23 14.34 ok
CT3 Core C-5 12.78 11.73 15.49 ok
CT3 Core C-6 10.80 11.88 15.66 ok

c. Primary-Secondary
Applied Voltage: 2500V DC Primary – Secondary
Primary-Secondary Phase R(GΩ) Phase Y(GΩ) Phase B(GΩ) Remarks
CT2 Core C-1 184 31.8 25.2 ok
CT2 Core C-2 72 34.2 33.3 ok
CT2 Core C-3 118 34.5 36.8 ok
CT3 Core C-4 129 34.6 35.2 ok
CT3 Core C-5 114 38.1 35.5 ok
CT3 Core C-6 237 34.1 35.3 ok

Criteria: More than 1000 M Ohms for Core - Earth and between Core’s.
3.0 Test Equipment used
SET Make Serial No Calibration Expiry
IR Test Megger 101473861 17/09/2024

DATE: 04/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY