Professional Documents
Culture Documents
E01
E01
Contract no.:
Feeder : E01-LINE-A
b. Core-(Core-Earth):
Applied Voltage: 500V DC secondary-Earth/Core-Core
Core-(Core-Earth) Phase R(GΩ) Phase Y(GΩ) Phase B(GΩ) Remarks
Core C-1 4.89 3.41 4.85 ok
Core C-2 5.45 4.01 5.83 ok
Core C-3 5.93 6.42 6.85 ok
Core C-4 8.58 7.64 9.13 ok
Core C-5 12.85 12.75 3.27 ok
Core C-6 12.40 13.34 5.22 ok
c. Primary-Secondary
Applied Voltage: 2500V DC Primary – Secondary
Primary-Secondary Phase R(GΩ) Phase Y(GΩ) Phase B(GΩ) Remarks
CT2 Core C-1 111.5 20.4 31.5 ok
CT2 Core C-2 78.0 21.1 29.1 ok
CT2 Core C-3 79.4 23.6 34.1 ok
CT3 Core C-4 84.5 23.7 32.1 ok
CT3 Core C-5 64.0 29.6 33.2 ok
CT3 Core C-6 75.0 30.7 29.7 ok
Criteria: More than 1000 M Ohms for Core - Earth and between Core’s.
3.0 Test Equipment used
SET Make Serial No Calibration Expiry
IR Test Megger 101473861 17/09/2024
DATE: 04/07/2024
TESTING ENGINEER SEC- Engineer