COMMISSIONING TEST RECORD

Contract no.:

Customer: End Client: Page:


SEC-EOA Page 1 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

1. General Data & Information

Panel No. =6TA+R CT Ratio of HV Side (87T) 600/1 A : ______


Relay Type P64392RE6S0910M CT Ratio of LV Side (87T) 3600/1 A
Manufacturer GE CT Ratio of LV Side (87REF) 3600/1 A
Serial No 36171881/08/22 CT Ratio of LV Side (51G) 300/1 A
Frequency Fn 50/60 Hz DC. Auxiliary. Voltage 125 VDC

1. Mechanical Checks and Visual Inspection

ITEM DESCRIPTION REMARKS


1. Inspect for any physical damage or defects.  Yes  N/A
2. Verify connections and ferrules as per approved drawings  Yes  N/A
3. Check tightness of all the connections.  Yes  N/A
4. Check Apparatus List  Yes  N/A
5. Check relay version and switching elements on printed circuit board  Yes  N/A

2. Electrical Tests

2.1. Function Test

ITEM DESCRIPTION REMARKS


1. Human Machine Interface (HMI) Checked.  Yes N/A
2. Case Earthing checked.  Yes N/A
3. Apply Test LEDs under commissioning menu to check all 8 programmable LEDs.  Yes N/A
4. Trip Contacts Checked.  Yes N/A
5. Reset Function Checked  Yes N/A
6. Group active Functions Checked  Yes N/A
7. Binary inputs checked.  Yes N/A
8. Output Relays Checked  Yes N/A
9. Event Display on HMI Screen Checked  Yes N/A
10. Test switch / plug checked for correct function.  Yes N/A
11. Watchdog contacts checked  Yes N/A
12. Current shorting facility  Yes N/A

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 2 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

- Setting Adopted:

Transformer Data:
Winding 1 ( HV ) Winding 2 ( LV ) Winding 3 (Tertiary.)
Connection Type YN yn d1
Capacity ( MVA ) 67 67 -
Rated Voltage ( KV ) 132 13.8 -
Rated Current ( A ) 293.05 2803.08 -

CT Data:
CT 1 ( HV ) CT 2 ( LV ) CT 3 (Tertiary.)
Connection Type Y Y -
Primary Current ( A ) 600 3600 -
Secondary Current (A ) 1 1 -

Secondary Injection Tests:


Measurements:
TRM
Injected Measured Values(A)
Channel DUTY CTR REMARKS
Values(A) Primary Sec
C24-C23 IA-HV 1.0 602.5∟0 1.005∟0 OK
C26-C25 IB-HV 600/1 1.0 602.9∟-119.9 1.004∟-119.9 OK
C28-C27 IC-HV 1.0 602.4∟120 1.005∟120 OK
C16-C15 IREF-HV(TN1) 600/1 1.0 603.8 1.001 OK

C14-C13 IREF-LV(TN3) 3600/1 1.0 3614 1.00 OK


E24-E23 IA-LV 1.0 3613∟0 1.004∟0 OK
E26-E25 IB-LV 3600/1 1.0 3611∟-120.1 1.003∟-119.8 OK
E28-E27 IC-LV 1.0 3616∟120 1.005∟120 OK

C12-C11 ISEF-TN2 300/1 1.0 3610 1.002 OK

Limits: Current: 0.05 to 3 In: ±1% or 3 mA of reading; Voltage: 0.05 to 2 Vn: ±1% of reading

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 3 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

Pick- up & Drop- off Test for Differential Current

1. Test for restrained Differential Current (Is1)


1.A. ZERO SEQ FIL ENABLED
HV –LV Winding (Star) zero Sequence on - AHV= 2/3
Measured Value
Is1 Operating Time @ 3X
Winding side Calculated value (A)
Phase Set Value(pu) I pickup (ms)
(A) Pick up Drop out
R 0.3 0.2198 0.219 0.211 25
Y 0.3 0.2198 0.219 0.211 25
HVS
B 0.3 0.2198 0.220 0.212 24
R-Y-B 0.3 0.1465 0.147 0.141 25
R 0.3 0.350 0.351 0.335 25
Y 0.3 0.350 0.350 0.335 26
LVS
B 0.3 0.350 0.349 0.336 27
R-Y-B 0.3 0.234 0.234 0.223 26
Limits: Pick-up: formula ±5%; Drop-off: 95% of formula ±5%; Operating time: <33 ms at 3x pickup level or
greater

1.B. ZERO SEQ FIL DISABLED


HV-LV Winding (Star) zero Sequence off AHV= 1
Is1 Measured Value
Winding Operating Time @ 3X
Set Calculated (A)
side Phase I pickup (ms)
Value(pu) value (A) Pick up Drop out
R 0.3 0.1465 0.147 0.141 25
Y 0.3 0.1465 0.147 0.141 24
HVS
B 0.3 0.1465 0.146 0.142 25
R-Y-B 0.3 0.1465 0.147 0.142 26
r 0.3 0.234 0.233 0.224 25
y 0.3 0.234 0.232 0.224 24
LVS
b 0.3 0.234 0.233 0.225 25
r-y-b 0.3 0.234 0.232 0.223 26
Limits: Pick-up: formula ±5%; Drop-off: 95% of formula ±5%; Operating time: <33 ms at

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 4 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

2. Test for Unrestrained Differential Current (Is-Hs2): AT Zero SEQ FIL Enabled only

Is-Hs2 Measured Value(Trip/No Trip)


Winding Operating Time
Set Calculated
side Phase At 1.1x I pickup (ms
Value(pu) value (A) At 1.1 x Is-Hs2 At 0.90 x Is-Hs2
R 6 4.396 Trip No Trip 20
Y 6 4.396 Trip No Trip 20
HVS
B 6 4.396 Trip No Trip 12
R-Y-B 6 2.931 Trip No Trip 10
r 6 7.014 Trip No Trip 12
y 6 7.014 Trip No Trip 11
LVS
b 6 7.014 Trip No Trip 14
r-y-b 6 4.676 Trip No Trip 11

Limits: Pick-up: formula ±5%; Drop-off: 95% of formula ±5%; Operating time: <33 ms at 3x pickup level or
greater

Calculated Amplitude Matching Factor (K):


KX = CTX / Rated Current of Ref.Wdg
Where Ref.Wdg is First Wdg with Y connection. if no Y connection then HV side selected automatically

KHV = 600/293.05 = 2.0474


KLV = 3600/2803 = 1.284

IDLx = A . KHV . Iw1Lx + B .( U2/U1) . KLV. Iw2Lx

Where x represents the concerted phase


Characteristic equation for the range: 0 ≤ Ibias ≤ Is1/K1

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 5 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

3.1.4. BIAS CHARACTERISTIC TESTING

Inject H.V and L.V phase with equal current on each, and angle 0 for H.V and 180 for L.V, then
decrease L.V Phase until trip, while leave H.V with fixed current which will be the bias current, and
record values and check that corresponds to following equation.
Test 1: Flat slope (Characteristic equation for the range: Is1/K1 ≤ Ibias ≤ Is2)

Idiff = Is1
Ibias (0-1.00) Is1 = 0.3 pu K1= 0.3 Vector Group = YNyn0

HV Current LV Current LV Current


Test Point Measured Idiff Measured
Phase Injected (Fixed) trip exp A at Operated
I bias Pu Ibias Pu
A at 0° 180° (Variable) A
A 0.4 0.403 0.292 0.296 0.298 0.403
B 0.4 0.403 0.292 0.295 0.299 0.402
C 0.4 0.403 0.292 0.297 0.298 0.402

Test 2: Slope 1
Idiff =K1 x Ibias
Ibias (1-2) Is1 = 0.3 pu K1= 0.3 Vector Group = YNyn0

HV Current
LV Current LV Current Operated
Test Point Injected Measured Measured
Phase trip exp A at Operated slope(K1)%
I bias (Fixed) A at Idiff Pu Ibias Pu
180° (Variable) A calculated

A 1.5 1.264 1.489 1.491 0.451 1.509 0.299
B 1.5 1.264 1.489 1.490 0.453 1.508 0.3004
C 1.5 1.264 1.489 1.490 0.452 1.507 0.2999

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 6 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

Test 3: Slope 2 (Characteristic equation for the range: Ibias ≥ Is2)


Idiff =K1 x Is2 + K2 (I bias – Is2)
Is1 = 0.3 pu Is2 = 2 pu K1=0.3 K2=0.8 Vector Group = YNyn0
Test HV Current LV Current LV Current Operated
Measured Measured
Phase Point Injected Injected (Initial) Operated slope
Idiff Pu Ibias Pu
I bias (Fixed) A at 0° A at 180° (Variable) A (K2)%
A 2.5 2.198 2.336 2.336 1.008 2.514 0.794
B 2.5 2.198 2.336 2.333 1.009 2.512 0.799
C 2.5 2.198 2.336 2.334 1.009 2.513 0.797

3.1.4. Test of 2nd Harmonics


I diff(2h)/I I2 ( F = 120 Hz ) A
Phase diff(fn) Current I1 ( F =60 Hz ) A
% Expected Blocking Measured Block Trip (Unblock)
R 15 1 0.150 0.147 0.146
Y 15 1 0.150 0.146 0.145
B 15 1 0.150 0.146 0.145

3.1.5. Test of 5th Harmonics


I diff(5h)/I I5 ( F = 300 Hz ) A
Phase diff(fn) Current I1 ( F =60 Hz ) A
% Expected Blocking Measured Block Trip (Unblock)
R 25 1 0.250 0.25 0.249
Y 25 1 0.250 0.247 0.246
B 25 1 0.250 0.248 0.247

3.1.6. Cross Block test


Cross Cross Block
Winding IR IY IB Block on Off
Trip/No Trip
I > pickup with 2nd I > pickup without 2nd/
No Trip Trip
harmonic harmonic
I > pickup with 2nd I > pickup without
HV No Trip Trip
harmonic 2nd/ harmonic
nd
I > pickup with 2 I > pickup with 2nd
No Trip Trip
harmonic harmonic
I > pickup with 2nd I > pickup without 2 nd
No Trip Trip
harmonic harmonic
I > pickup with 2nd I > pickup without
l.V No Trip Trip
harmonic 2nd/ harmonic
I > pickup with 2nd I > pickup with 2nd
No Trip Trip
harmonic harmonic
Test done at I2/I1= 15%

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 7 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

Restricted earth-fault protection REF


I bias = 0.5x [max( Ia+ Ib + Ic) +K x IN]
I diff = [ Ia + Ib + Ic + K x IN]

Scaling factor = K = 600/600 = 1


IN = current measured by the neutral CT
Low impedance REF characteristic

Inject Single phase HV phase and HV neutral with equal current on each, and angle 0 for HV phase and
180 for HV neutral, then decrease HV neutral until trip, while leave HV phase with fixed current which
will be the bias current, and record values and check that corresponds to following equation.

1.1.1. HV REF (64NP) CTR: 600/1


Pick- up & Drop- off Test for Differential Current (Is1):
Characteristic equation for the range: 0 ≤ Ibias ≤ Is1/K1
Idiff = Is1 HV Winding - Phase CT

Is1 Set Measured Value ( A ) Operating Time @ 3X


HV Phase
Value(A) I pickup (ms)
CT
Pick up Drop out
3Io 0.06 0.061 0.59 37

HV Winding - Neutral CT

Is1 Measured Value ( A ) Operating Time @ 3X


HV Neutral
Set Value(pu) I pickup (ms)
CT
Pick up Drop out
IN 0.06 0.061 0.59 30
Accuracy: Pick-up: formula ±5%; Drop-off: 0.90 formula ±5%
Low impedance operating time: <45 ms for currents applied at 2x pickup level or greater

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 8 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

a. Slope 1
Characteristic equation for the range: Is1/K1 ≤ Ibias ≤ Is2 CTR: 600/1
Idiff = K1 x Ibias
Is1 = 0.06A Is2= 0.7A K1=0.2
Phase HV Phase HV Neutral HV Neutral Measured Measured Operated
Current Injected Current Injected Operated REF Idiff REF Ibias slope
(Fixed) A at 0° (Initial) A at 180° (Variable) A A A (K1)%
N 0.300 0.300 0.242 35.72 162.8 0.219

b. Slope 2
Characteristic equation for the range: Ibias ≥ Is2
Idiff = K1 x Is2 + K2 (I bias – Is2)
Is1 = 0.06A Is2= 0.7 A K1=0.2 K2=1.5
HV Current HV Neutral HV Current Operated
Measured Measured
Phase Injected (Fixed) A Current Injected Operated slope
REF Idiff A REF Ibias A
at 0° (Initial) A at 180° (Variable) A (K2)%
N 1.5 1.5 0.730 464.4 672.5 1.506
Accuracy: Pick-up: formula ±5%; Drop-off: 0.90 formula ±5%

1.1.2. LV REF (64NP) CTR:3600/1


Pick- up & Drop- off Test for Differential Current (Is1):
Characteristic equation for the range: 0 ≤ Ibias ≤ Is1/K1
Idiff = Is1 LV Winding -Phase CT
Measured Value
Is1 Operating Time @ 3X
LV Phase Calculated value (A)
Set Value(mA) I pickup (ms)
CT (A)
Pick up Drop out
3Io 0.080 0.080 0.081 0.078 27

LV Winding - Neutral CT

Measured Value
Is1 Operating Time @ 3X
LV Neutral Calculated value (A)
Set Value(mA) I pickup (ms)
CT (A)
Pick up Drop out
IN 0.080 0.080 0.081 0.076 27
Accuracy: Pick-up: formula ±5%; Drop-off: 0.90 formula ±5%
Low impedance operating time: <45 ms for currents applied at 2x pickup level or greater

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 9 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

c. Slope 1

Characteristic equation for the range: Is1/K1 ≤ Ibias ≤ Is2

Idiff = K1 x Ibias

Phase LV Phase LV Neutral LV Neutral Measured Measured Operated


Current Injected Current Injected Operated Idiff Ibias slope
(Fixed) A at 0° (Initial) A at180° (Variable) A A A (K1)%

N 1 1 0.81 659.2 3281 0.201


Is1 = 0.08A Is2= 1A K1= 0.2 CTR:3600/1

d. Slope 2

Characteristic equation for the range: Ibias ≥ Is2

Idiff = K1 x Is2 + K2 (I bias – Is2)

Is1 = 0.08A Is2= 1A K1= 0.2 K2= 1.5


Phase LV Current LV Current LV Current Measured Measured Operated
Injected Injected (Initial) Operated Idiff Ibias slope (K2)%
(Fixed) A at 0° A at 180° (Variable) A A A
N 1.5 1.5 0.956 1963 4435 1.489
Accuracy: Pick-up: formula ±5%; Drop-off: 0.90 formula ±5%

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 10 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

HV Side Current Protection (CT Input T1)

- Pick up / Drop off test.


Accuracy: Setting ±5% or 20 mA whichever is greater
Measured Pick Up Value (A) Measured Drop Out Value (A)
Setting (A)
Function R Y B R Y B
1 0.995 0.995 0.996 .0974 0.975 0.976

- Timing test.

Operating Time Test: Iset= 1A Accuracy: ±5% or 40 ms, whichever is greater


Measured time (s)
Injected TMS/
Function Expected
Curve current
Time set time (S) R Y B
(A)

Overcurrent 2*Is 1.0 10.02 9.971 9.973 9.959


1
Normal 3*Is 6.289 6.313
1.0 6.302 6.291
Inverse
I >1 5*Is 1.0 4.28 4.282 4.300 4.301

- Instantaneous time test


Iset= 1A Accuracy: ±2% or 50 ms, whichever is greater
Measured Value (mSec)
Function Injected Current
R Y B
Overcurrent1 2 x Iset 30 29 30

I>1 3 x Iset 21 21 36

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 11 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

HV Side Earth fault Current Protection (TN1)

- Pick up / Drop off test.


Accuracy: Setting ±5% or 20 mA whichever is greater
Measured Pick Up Value (A) Measured Drop Out Value (A)
Function Setting (A)
N(3Io) N(3Io)
Earthfault1
0.5 0.499 0.478
IN > 2

- Timing test.

Iset = 0.2 A Accuracy: ±5% or 40 ms whichever is greater


Function
Expected time (s)
Curve Injected current (a) TMS/Time Measured time (s)
TMS = 1
set
Earthfault1 2*Is 1.0 10.02 10.03
Normal Inverse
IN > 1 5*Is 1.0 4.28 4.29

- Instantaneous time test

Iset= 0.5 A Accuracy: ±2% or 50 ms, whichever is greater


Measured Value (mSec)
Function Injected Current
N(3Io)
Earthfault1 2 x Iset 24.6

IN > 2 3x Iset 21.2

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY
COMMISSIONING TEST RECORD
Contract no.:

Customer: End Client: Page:


SEC-EOA Page 12 of 12
Site: Panel / Designation / Location no.: Description:
KUDMI Mobile Substation 6TA+R TRF.DIFF-REF- MICOM P643
TESTING

HV Side Breaker Fail Protection ( T1 CBF)


InI: ExtTrip from T1 CB1 Ext Prot Rst: I< only
Pickup / Drop-off Test:
D.O VALUE
Phase I<set P.U Value (A)
ABC 0.2 A 0.218 0.202
Accuracy: I > Pick-up: Setting ±5% or 20 mA whichever is greater
I > Drop-off: 100% of setting ±5% or 20 mA whichever is greater

Timing Test:
Trip Time Measured
Phase I<set CB Fail timer1 set(Sec)
seconds
ABC 1 A 0.150 0.176
Timers: ±2% or 50 ms whichever is greater

LV Side Breaker Fail Protection (T2 CBF)


Ini: ExtTrip 3Ph CB1 Ext Prot Rst: I< only
Pickup / Drop-off Test:

Phase I<set P.U Value (A) D.O VALUE

ABC 0.2 A 0.219 0.202


Accuracy: I > Pick-up: Setting ±5% or 20 mA whichever is greater
I > Drop-off: 100% of setting ±5% or 20 mA whichever is greater
Timing Test:
Trip Time Measured
Phase I<set CB Fail timer1 set(Sec)
seconds
ABC 0.2 A 0.150 0.177
Timers: ±2% or 50 ms whichever is greater
1. Binary inputs and output checked : []
2. Mechanical Protection Checked : []

TEST EQUIPMENT USED


Test Equipment Serial Number
Freja 300 7501720

DATE: 08/07/2024
TESTING ENGINEER SEC- Engineer

Signature: ________________ Signature: ________________


Name : ENG/ MOHAMMED AWAD Name : ENG/ FARIS BAHKLY