Professional Documents
Culture Documents
4555
4555
4555
A. Application
Power function for monitoring
· reverse power
· active power
· reactive power
· power direction.
B. Features
· definite time delay
· over or underpower
· adjustable characteristic angle
· provision for correction of phase errors caused by the input
circuit
· one, two or three-phase measurement
· wide setting ranges
(see Fig. 3.5.15.2 to Fig. 3.5.15.3)
· correction of c.t. and v.t. phase errors
· insensitive to DC components in voltage and current
· insensitive to harmonics in voltage and current.
I. C.t./v.t. inputs:
· current
· voltage
IV. Measurements:
· power.
3.5.15-1
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Explanation of parameters:
RunOnCPU
defines the processing unit which runs the function.
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip 01-08
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
Trip 09-16
corresponds to Trip 01-08 (providing tripping unit fitted).
3.5.15-2
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Power Automation Ltd
Trip 17-24
corresponds to Trip 01-08 (providing tripping unit fitted).
Trip 25-32
corresponds to Trip 01-08 (providing tripping unit fitted).
P-Setting
Power setting for tripping.
Setting restrictions:
Power amplitude not less than:
· 0.005 PN when connected to metering cores
· 0.020 PN when connected to protection cores
· also n x 0.005 PN should the sampling groups for voltage
and current be different in the analogue input circuit
(to allow for possible errors for f ¹ fN; n = 1...3 according
to the spacing of the sampling groups).
Allocation of the c.t./v.t. channels to the sampling groups:
1 1... 6
2 7...12
3 13...18
4 19...24
5 25...30
6 31...36
7 37...42
8 43...48
3.5.15-3
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Drop-Ratio
Reset value in relation to the pick-up value. Thus depending
on the sign of the pick-up value, the setting of the reset ratio
must be greater or less than 100 %.
Forbidden settings:
· Reset ratios >100 % for MAX and P-Setting >0
· Reset ratios <100 % for MAX and P-Setting <0
· Reset ratios <100 % for MIN and P-Setting >0
· Reset ratios >100 % for MIN and P-Setting <0.
A large hysteresis must be selected for low pick-up settings
and a small one for high pick-up settings (see Fig. 3.5.15.1).
Forbidden settings for hysteresis (= ½100% - reset ratio½)
settings:
· £ 0.5% P - Setting PN + 0.01
· ³ 10% P - Setting PN
· These conditions are fulfilled by setting, for example,
P - Setting
for 0,2 £ £ 1: 95%
PN
and
P - Setting
for 0.005 £ £ 0.2 : 60%.
PN
Delay
Time between the function picking up and tripping. The time
the function takes to reset is also influenced by the delay set
for operation, i.e.:
for t > 100 ms, the function resets after 50 ms, otherwise re-
setting is instantaneous.
MaxMin
defines whether over or underpower function.
Settings:
· MIN: overpower
· MAX: underpower.
Caution:
The number and its sign are relevant and not just the value,
i.e. “MIN” must be set for reverse power, because tripping
takes place for a power less than zero (P-Setting < 0).
3.5.15-4
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Power Automation Ltd
Phi-Comp
Input of an angle to compensate c.t. and v.t. errors in the
case of highly accurate power measurements.
The setting is determined by the difference between c.t. and
v.t. errors.
NrOfPhases
Number of phases measured:
· 1: single-phase
· 2: two-phase, i.e. for a three-phase measurement with V
connected v.t’s,
P = URS ´ IR ´ cos j - UST ´ IT ´ cos j
A two-phase power measurement is only possible when
connected to delta connected v.t’s.
· 3: three-phase
P = UR ´ IR ´ cos j + US ´ IS ´ cos j + UT ´ IT ´ cos j
(The measurement is only correct with delta connected
v.t’s if the three phase voltages are symmetrical.)
CurrentInp
defines the analogue c.t. input channel.
All current I/P's may be selected.
In the case of multi-phase measurement, the first channel of
the group of three selected must be specified. The other
phases are derived from the same group.
VoltageInp
defines the voltage input channel.
All voltage I/P's may be selected.
In the case of multi-phase measurement, the first channel of
the group of three selected must be specified. The other
phases are derived from the same group.
PN
Rated power as given by UN x IN. This enables the amplitude
of the power being measured to be compensated, e.g. to the
rated power factor of a generator.
BlockInp
I/P for blocking the function.
F: - not blocked
T: - blocked
xx: - all binary I/P’s (or O/P’s of protection functions).
3.5.15-5
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Trip
Output for signalling tripping.
(signal address)
Start
Output for signalling pick-up.
(signal address)
1
Reset ratio 95%
Reset ratio
60%
0.5
3.5.15-6
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Power Automation Ltd
E. Setting instructions
(function with two additional timers)
Settings:
Reference power PN
Setting P-Setting
Reset ratio Drop-Ratio
Over/underpower MaxMin
Characteristic angle Angle
Phase error compensation Phi-Comp
tripping delay Delay
The power function can be used for many applications. Some
examples are given in Fig. 3.5.15.2 and Fig. 3.5.15.3. The
angles given apply for connection according to Section 4.4.2.
Q Q
0 P 0 P
*) The values in brackets apply for a single-phase measurement with the v.t. connected
phase-to-phase (e.g. IR current and URS voltage) or for a three-phase measurement with
delta connected v.t’s.
3.5.15-7
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Q Q
Operates Restrains Operates
Restrains
0 P 0 P
Q
Restrains
0 60°
P
Operates
- P-Setting <0
- Max/Min MIN
- Drop-Ratio <100%
- Angle 60° (90° ) *)
HEST 965 018 FL
*) The values in brackets apply for a single-phase measurement with the v.t. connected
phase-to-phase (e.g. IR current and URS voltage) or for a three-phase measurement with
delta connected v.t’s.
3.5.15-8
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Power Automation Ltd
where:
SGN, PGN, UGN, IGN, cos jGN: ratings of the protected unit
UN1, IN1: primary v.t. and c.t. ratings
PN, UN, IN: protection ratings.
Example 1
Generator: 96 MVA, 13,8 kV, 4 kA, cosj = 0,8
14.4 100
V.t’s/c.t’s: kV V; 5 kA 5 A
3 3
Protection: 100 V; 5 A
Reverse power: 0.5 % PGN
Alternative 1: No modification of PN
Settings:
PN
Reference power = 10
.
UN ´ IN
Reverse power:
P U ´I 13.8 ´ 4
= 0.005 GN GN cos j GN = 0.005 0.8 = 0.003
PN UN1 ´ IN1 14.4 ´ 5
3.5.15-9
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Alternative 2: jGN
Modification for cosj
Settings:
PN P
Reference power = GN = cos j GN = 0.8
UN ´ IN SGN
P U ´I 13.8 ´ 4
Reverse power: = 0.005 GN GN = 0.005 = 0.004
PN UN1 ´ IN1 14.4 ´ 5
Rated power
PN U ´I 13.8 ´ 4
= GN GN cos j GN = ´ 0.8 = 0.614
UN IN UN1 ´ IN1 14.4 ´ 5
P
Reverse power = 0.005
PN
Characteristic angle
The power function is connected to the phase currents and a
phase-to-neutral or phase-to-phase voltage. The purpose of the
phase compensation is twofold:
· to compensate the phase difference between the phase volt-
age and the any measured phase-to-phase voltage
· to determine whether the function responds to active or re-
active power.
The following table summarises the most important operating
modes to simplify setting the corresponding parameters cor-
rectly. The angles given apply for connection according to
Section 4.4.2.
The phase compensation also provides facility for changing the
direction of measurement or to compensate incorrect v.t. or c.t.
polarity.
3.5.15-10
Function "MaxMin" "Drop-Ratio" "P-Setting" "Angle" *)
P
U RS
max MAX < 100%
0
Active power IR >0 +30°
P
min MIN > 100%
0
P
U RS 0
max MIN < 100%
Reverse power <0 +30°
P
IR 0
min MAX > 100%
voltage URS
RE. 216 1MDU02005-EN / 3 / Rev. I
*) Applicable for a single or three-phase measurement using phase-to-phase voltages (the setting is 30° HEST 965 019 C
3.5.15-11
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Phase compensation
This setting is for correcting the phase error between the v.t’s
and c.t’s, which have a considerable adverse influence on the
measurement of active power at low power factors.
Example 2
The active power error at rated current and a power factor of
cosj = 0 for a total phase error d of 10' is
DP = 0.03 ´ d = 0.03 ´ 10 = 0.3% [%; 1; min]
This is an error which is not negligible at a setting of 0.5%.
The total error corresponds to the difference between the v.t.
and c.t. errors. The case considered in this example of full reac-
tive current (100%) would scarcely occur in practice, but currents
from about 80% are possible.
3.5.15-12
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Power Automation Ltd
Block
t 1> Trip
U
P>
I Trip Trip
t 2>
Start
t 3>
Integrator
3.5.15-13
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Typical settings:
PN determined by the generator cosjGN
P-Setting (steam turbines of medium power) - 0.005
MaxMin MIN
Drop-Ratio 60 %
Angle connection to IR and UR 0°
connection to IR and URS +30°
connection to IR and UST -90°
connection to IR and UTR +150°
Phi-Comp 0.0
Stage 1:
Delay 0.5 s
Stage 2:
Delay 20 s
or
Integrator (“Delay” function) for delay on operation and reset
Trip time 20 s
Reset time 3s
Integration 1
Note:
The following must be set for a “Minimum forward power”
scheme according to Anglo-Saxon practice:
P-Setting >0
MaxMin MIN
Drop-Ratio 150%
3.5.15-14
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Power Automation Ltd
3.5.15-15