Professional Documents
Culture Documents
97777
97777
97777
A. Application
Protection of generators against excessive heating of the rotor
due to asymmetrical load.
B. Features
· definite time delay
· insensitive to DC component
· insensitive to harmonics
· three-phase measurement.
I. C.t./v.t. inputs:
· current
IV. Measurements:
· proportion of negative-sequence current component
3.5.9-1
ABB Switzerland Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
Explanation of parameters:
RunOnCPU
defines the processing unit which runs the function.
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip 01-08
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
Trip 09-16
corresponds to Trip 01-08 (providing tripping unit fitted).
Trip 17-24
corresponds to Trip 01-08 (providing tripping unit fitted).
Trip 25-32
corresponds to Trip 01-08 (providing tripping unit fitted).
3.5.9-2
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Switzerland Ltd
Delay
time delay between pick-up and tripping.
I2-Setting
NPS current setting for tripping.
Setting restriction:
not < 0.05 IN when supplied from protection cores.
CurrentInp
defines the current input channel. All three-phase current
I/P's may be selected. The first channel (R phase) of the
group of three selected must be specified.
BlockInp
Binary address used as blocking input.
(F®FALSE, T®TRUE, binary input or output of a protection
function).
Trip
Output for signalling tripping
(signal address).
Start
Output for signalling pick-up
(signal address).
3.5.9-3
ABB Switzerland Ltd RE. 216 1MDU02005-EN / 3 / Rev. I
E. Setting instructions
Settings:
Negative-sequence component of stator current I2-Setting
Delay Delay
I2-Setting = 15 % IGN
The NPS protection is always delayed to avoid false tripping
during transient phenomena and especially during phase-to-
phase and earth faults on the power system. The delay may be
relatively long, because the temperature rise of the endangered
parts of the rotor is relatively slow.
3.5.9-4
RE. 216 1MDU02005-EN / 3 / Rev. I ABB Switzerland Ltd
In cases where both stages are used for tripping, the one with
the higher setting must be faster.
I2
Tripping stage
I2
Alarm stage
Typical settings:
1st. stage (alarm)
I2-Setting 0.1 IN
Delay 5s
2nd. stage (tripping)
I2-Setting 0.15 IN
Delay 10 s
3.5.9-5