ABBACUS D-Series
Enhancing power quality and energy
efficiency of your electrical network
ABBACUS D-Series MECB
Inrush design
Incomer module
Power module
Incomer module The type tested protection system utilises advanced sensing and
• Incoming cable termination busbars tripping relays in conjunction with a sophisticated fibre optic network
• Isolator/ earth switch to detect and extinguish an arc before any damage can occur.
• Surge arresters
• Circuit breakers Using Hitachi Energy’s Ultra-Fast Earthing Switch (UFES) device,
• Protection voltage transformers arc extinction occurs in less than four milliseconds leaving the metal
• Line current transformers enclosed capacitor bank and its components completely undam-
• Live line indication aged and operational after an arc fault.
1 2
Control cubicle
• Power factor controller with modbus communication
• Safety interlock keys
• Over current/ earth fault protection relay
• Unbalance protection relay
• Unbalance/ overload protection relay 3 4
Bank configuration Fixed, switched single or multi-step Isolator and earth switch
Interlocking (optional) Mechanical or solenoid
Type Air-insulated
Arc fault mitigation Hitachi Energy Q-ACT (optional) with full incomer
Phase Three
Busbar Hard drawn copper (tinned)
Current rating 1250 A1
Standards IEC, IEEE/ ANSI , CSA or equivalent
Fuses
Enclosure
Rated current Up to 315 A
Material Mild steel
Short time current 63 kA (max)
Base frame Hot dipped galvanized steel
Protection Up to IP54 indoor/ outdoor Power factor controller
Door locking Three point padlock handle with interlock option Microprocessor-based system for Insensitive to harmonics
Installation Base fixing single or three phase system
Handling Fork and crane lifting via base Control voltage 100 VAC to 240 VAC
Cable entry Bottom only Power factor setting 0.7 inductive to 0.7 capacitive
Capacitors
1. Higher ratings available on request
We reserve the right to make technical chang- We reserve all rights in this document and in
es or modify the contents of this document the subject matter and illustrations contained
without prior notice. With regard to purchase therein. Any reproduction, disclosure to third
For more information please contact your orders, the agreed particulars shall prevail. parties or utilization of its contents – in whole
local Hitachi Energy representative or visit Hitachi Energy Ltd. does not accept any or in parts – is forbidden without prior written
hitachienergy.com/offering/solutions/power-quality responsibility whatsoever for potential errors or consent of Hitachi Energy Ltd.
possible lack of information in this document.
www.hitachienergy.com