Professional Documents
Culture Documents
141
141
2 Solver controls
You can customize the variables that control the iterative linear equation solver.
Note: You can use the iterative linear equation solver only for Static,
General; Static, Linear perturbation; Visco; Heat transfer; Geostatic;
and Soils analysis steps.
You can access the solver controls by selecting Other Solver Controls from the
main menu bar. For more information, see “Iterative linear equation solver,” Section
6.1.6 of the Abaqus Analysis User's Guide.
You can access all the Step module tools through the main menu bar; in addition,
you can also access the tools through the Step module toolbox. Figure 14–4 shows
the icons for the tools in the Step module toolbox.
You use the Step Manager to create, edit, and manipulate the analysis steps
associated with the current model. To start the Step Manager, select Step
Manager from the main menu bar. Columns in the Step Manager dialog box display
the following information about each step:
Name
The name of the step. Names of linear perturbation steps are indented relative to
names of general steps.
Procedure
The analysis procedure that you selected for this step when the step was created.
You can change the analysis procedure after creating a step. Click Replace to select
a new procedure type for the selected step. The Procedure column also indicates
whether thermal and soils steps assume steady-state or transient conditions or if
neither is applicable.
Nlgeom
Whether the analysis step accounts for geometric nonlinearities. You use
the Nlgeom button to control the Nlgeom setting for a particular step. Once you have
set the Nlgeom option for a step, your setting remains in effect for all subsequent
steps.
Time
The time period for the step. The default value for the time period is 1.0 time unit.
Click Edit to display the step editor so that you can modify the time period.
You use the buttons across the bottom of the Step Manager dialog box to create a
step that follows the selected step or to manipulate the selected step. You use
the Dismiss button to close the Step Manager dialog box. You can perform the
same tasks using the pull-down menus available from the Step menu, located in the
main menu bar.
You can suppress an analysis step to exclude the procedure from the analysis. The
suppressed step is removed from the context bar, the restart request dialog box, and
the diagnostic print dialog box. Any step-dependent or propagating attributes created
in the step are automatically suppressed and ignored during the analysis. Upon
resuming the step, the status of each attribute will return to the original state. For
example, suppressing and resuming a step will not resume an associated load that
was previously suppressed. You can suppress or resume a step as long as the step
sequence remains valid.
Warning: If you use the Step Manager or the Step menu to delete a step, objects
associated with that step, such as prescribed conditions or output requests, are also
deleted. If you use the Step Manager or the Step menu to replace a step, objects
that are incompatible with the new analysis procedure are substituted with an
equivalent object, if possible, or deleted.
You can create any sequence of procedures that is allowed by the Abaqus analysis
products; the procedure list in the Create Step dialog box is updated to show only
the available procedures for the new step. For example, if your first step contains a
static stress/displacement procedure, you cannot follow it with a new step containing
a heat transfer procedure.
To create a step:
Tip: You can initiate the Create procedure in two other ways:
Click Create in the Step Manager. (You can display the Step
Manager by selecting Step Manager from the main menu
bar.)
Click the tool in the Step module toolbox.
2. If desired, use the Name text field to change the name of the new step.
All steps must have unique names, and you cannot name a step "Initial".
3. From the list of existing steps, select the step after which the new step will be
inserted.
4. Click the arrow next to the Procedure type field, and select
either General or Linear perturbation from the list that appears.
The lower half of the dialog box displays a list of available procedures.
6. Use the Edit Step dialog box to modify the settings from their default values
and to provide values for optional settings. (For detailed help on a particular
editor feature, select Help On Context from the main menu bar and then
click the feature of interest.)
7. Click OK.
Abaqus/CAE closes the Edit Step dialog box, and the new step appears in
the Step Manager.
To edit a step:
1. From the main menu bar, select Step Edit step name.
Tip: You can also select the step name in the Step Manager and
click Edit.
2. Use the tabs within the step editor to modify the settings. (For detailed help on
a particular editor feature, select Help On Context from the main menu bar
and then click the feature of interest.)
3. Click OK to close the step editor and save the new settings.
You can replace an existing procedure with any procedure that is allowed by the
Abaqus analysis products; the procedure list in the Replace Step dialog box is
updated to show only the available procedures for the revised step. For example, you
can change from a Static, General procedure to a Static, Riks procedure.
Abaqus/CAE copies compatible step-dependent objects to the new step, substitutes
equivalent objects, if possible, and deletes the remaining objects.
After you replace a step, you should verify that previously defined properties, element
types, jobs, and boundary conditions and fields in the inital step remain valid for the
model. For more information, see “What is step replacement?,” Section 14.3.4.
To replace a step:
1. From the main menu bar, select Step Replace step name.
Tip: You can also select the step name in the Step Manager and
click Replace.
2. Click the arrow next to the New procedure type field, and select
either General or Linear perturbation from the list that appears.
The lower half of the dialog box displays a list of available procedures.
3. Select the new procedure, and click Continue.
4. Use the Edit Step dialog box to modify the settings from their default values
and to provide values for optional settings. (For detailed help on a particular
editor feature, select Help On Context from the main menu bar and then
click the feature of interest.)
5. Click OK.
If step-dependent objects are not compatible with the new step, Abaqus/CAE
displays a list of the objects that were deleted during step replacement in the
message area and closes the Edit Step dialog box.
When you create, edit, or replace a step, you use the step editor to configure the
analysis procedure settings. You can use the replace function to reset the settings in
the step editor to their default values by replacing an existing step with a step of the
same procedure type.
1. From the main menu bar, select Step Replace step name.
The Replace Step dialog box appears with the current procedure highlighted
in the list of available procedures.
Tip: You can also select the step name in the Step Manager and
click Replace.
2. Click Continue.
The Edit Step dialog box appears with default values for the procedure
settings.
3. Use the Edit Step dialog box to modify the settings from their default values
and to provide values for optional settings. (For detailed help on a particular
editor feature, select Help On Context from the main menu bar and then
click the feature of interest.)
4. Click OK.
The Nlgeom setting for a step determines whether Abaqus will account for geometric
nonlinearity in that step. The Nlgeom setting is turned on by default for
Abaqus/Explicit steps and turned off by default for Abaqus/Standard steps.
The sequence of steps and the current Nlgeom setting determine whether you can
change the Nlgeom setting in a particular step. For example, if Abaqus is already
accounting for geometric nonlinearity, the Nlgeom setting is toggled on for all
subsequent steps, and you cannot toggle it off. Similarly, you cannot change
the Nlgeom setting during a linear perturbation step. For more information,
see “Linear and nonlinear procedures,” Section 14.3.2.
Note: When you create a step, you can click the Basic tab in the Step Editor and
select On or Off as the Nlgeom setting.
1. To display the Edit Nlgeom dialog box and to change the setting where
applicable, do one of the following:
From the main menu bar, select Step Nlgeom.
From the main menu bar, select Step Edit step name.
The Step Editor appears. From the Nlgeom field on the Basic tabbed
page, click .
The Step manager appears. From the buttons along the bottom of the
manager, click Nlgeom.
2. From the Edit Nlgeom dialog box, click the step name of interest to
turn Nlgeom on or off for that step.
When you create, edit, or replace a step, the step editor displays a set of tabbed
pages that allow you to configure the settings for the procedure you selected. The
pages are unique for each procedure; for example, when you configure a Static,
General procedure, the step editor displays the Basic, Incrementation,
and Other tabs. Settings you can configure with these tabbed pages include the time
period for the step, the maximum number of increments, the increment size, the
default load variation with time, and whether to account for geometric nonlinearity.
Abaqus stores the text that you enter in the Description field on the Basic tabbed
page in the output database, and it is displayed in the state block by
the Visualization module.
If you want to reset the procedure settings to their default values, you can replace an
existing step with a step of the same procedure type. For more information,
see “Resetting the default values in the step editor,” Section 14.9.5.
For detailed help on a specific feature of the editor, select Help On Context and
then click the feature of interest.
When you configure general procedures, you use the Basic tab in the step editor to
enter the total time period for the step. You use the Incrementation tab to configure
the approach that Abaqus will use to divide the total time period for the step into
increments. For a general, static step as well as for many other kinds of steps you
can set the following options on the Incrementation tabbed page:
Time incrementation
Abaqus limits the number of increments in a step to the value that you enter for the
maximum number of increments. If the step exceeds this number of increments, the
analysis stops, and diagnostic information is reported to the Job module and written
to the message file. By default, Abaqus/CAE sets the maximum number of
increments to 100.
Abaqus starts the step using the value entered for the initial increment size.
Abaqus checks for the minimum increment size only when you analyze your model
using automatic time incrementation. If Abaqus needs a smaller time increment than
this value to reach a convergent solution, it terminates the analysis, reports to
the Job module, and writes diagnostic information to the message file. If you do not
enter a minimum increment size, Abaqus uses 10-5 times the total time period.
Abaqus checks for the maximum increment size only when you analyze your model
using automatic time incrementation. Abaqus will not increase the increment size
beyond this value during the analysis. If you do not specify this value, Abaqus/CAE
sets the value to that of the total time period (with the exception of dynamic, implicit
procedures, in which the default maximum increment size depends on a variety of
analysis settings; see “Configuring a dynamic, implicit procedure” in “Configuring
general analysis procedures,” Section 14.11.1).
Note: A value must be entered for each of the incrementation options described
above. Abaqus/CAE does not allow you to create the step if you delete the default
value for an incrementation option but fail to provide another.
This section provides instructions for using the step editor to configure different types
of general analysis procedures. The following topics are covered:
A static stress procedure is one in which inertia effects are neglected. The analysis
can be linear or nonlinear and ignores time-dependent material effects. For more
information, see “Static stress analysis,” Section 6.2.2 of the Abaqus Analysis User's
Guide.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Static, General),
or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as the time period for the step, the maximum number of increments, the
increment size, the default load variation with time, and whether to account for
geometric nonlinearity as described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. In the Time period field, enter the time period of the step. For more
information, see “Time period” in “Static stress analysis,” Section 6.2.2 of the
Abaqus Analysis User's Guide.
4. Select an Nlgeom option:
Toggle Nlgeom Off to perform a geometrically linear analysis during
the current step.
Toggle Nlgeom On to indicate that Abaqus/Standard should account
for geometric nonlinearity during the step. Once you have
toggled Nlgeom on, it will be active during all subsequent steps in the
analysis.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
Click the arrow to the right of Automatic stabilization, and select a method
for defining the damping factor:
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
2. Choose an Equation Solver Method option:
Choose Direct to use the default direct sparse solver.
Choose Iterative to use the iterative linear equation solver. The
iterative solver is typically most useful for blocky structures with millions
of degrees of freedom. For more information, see “Iterative linear
equation solver,” Section 6.1.6 of the Abaqus Analysis User's Guide.
3. Choose a Matrix storage option:
Choose Use solver default to allow Abaqus/Standard to decide
whether a symmetric or unsymmetric matrix storage and solution
scheme is needed.
Choose Unsymmetric to restrict Abaqus/Standard to the unsymmetric
storage and solution scheme.
Choose Symmetric to restrict Abaqus/Standard to the symmetric
storage and solution scheme.
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
8. Toggle on Stop when region region name is fully plastic if “fully plastic”
analysis is required with deformation theory plasticity. If you toggle on this
option, enter the name of the region being monitored for fully plastic behavior.
The step ends when the solutions at all constitutive calculation points in the
element set are fully plastic (defined by the equivalent strain being 10 times
the offset yield strain). However, the step can end before this point if either the
maximum number of increments that you specified on
the Incrementation tabbed page or the time period that you specified on
the Basic tabbed page is exceeded.
You can use this method for cases where the load magnitudes are governed by a
single scalar parameter. It is also useful for solving ill-conditioned problems such as
limit load problems or almost unstable problems that exhibit softening. For more
information, see “Unstable collapse and postbuckling analysis,” Section 6.2.4 of the
Abaqus Analysis User's Guide.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Static, Riks), or “Editing
a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as stopping criteria, the maximum number of increments, the arc
increment length, and whether to account for geometric nonlinearity as
described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. Select an Nlgeom option:
Toggle Nlgeom Off to perform a geometrically linear analysis during
the current step.
Toggle Nlgeom On to indicate that Abaqus/Standard should account
for geometric nonlinearity during the step. Once you have
toggled Nlgeom on, it will be active during all subsequent steps in the
analysis.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
3. In the Maximum number of increments field, enter the upper limit to the
number of increments in the step. The analysis stops if this maximum is
exceeded before Abaqus/Standard arrives at the complete solution for the
step.
4. If you selected Automatic in Step 2, enter values for Arc length increment:
a. In the Initial field, enter the initial increment in arc length along the
static equilibrium path in scaled load-displacement space, .
b. In the Minimum field, enter the minimum arc length increment, .
If you enter zero, Abaqus assumes a default value of the smaller of the
suggested initial arc length or 10–5 times the total arc length.
c. In the Maximum field, enter the maximum arc length increment,
. If this value is not specified, no upper limit is imposed.
d. In the Estimated total arc length field, enter the total arc length scale
factor associated with this step, . If this entry is zero or is
unspecified, Abaqus/Standard assumes a default value of .
5. If you selected Fixed in Step 2, enter a value for the constant arc length
increment in the Arc length increment field.
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
4. Click the arrow to the right of the Extrapolation of previous state at start of
each increment field, and select a method for determining the first guess to
the incremental solution:
Select Linear to indicate that the process is essentially monotonic, and
Abaqus/Standard should use a 1% linear extrapolation of the previous
incremental solution to begin the nonlinear equation solution for the
current increment.
Select None to suppress any extrapolation.
(The Parabolic option is not relevant for Riks analyses.) For more information,
see “Extrapolation of the solution” in “Defining an analysis,” Section 6.1.2 of
the Abaqus Analysis User's Guide.
5. Toggle on Stop when region region name is fully plastic if “fully plastic”
analysis is required with deformation theory plasticity. If you toggle on this
option, enter the name of the region being monitored for fully plastic behavior.
The step ends when the solutions at all constitutive calculation points in the
element set are fully plastic (defined by the equivalent strain being 10 times
the offset yield strain). However, the step can end before this point if the
maximum number of increments that you specified on
the Incrementation tabbed page is exceeded.
When you have finished configuring settings for the static, Riks step, click OK to
close the Edit Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Dynamic, Explicit),
or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, Mass scaling, and Other tabbed pages,
configure settings such as the time period for the step, the maximum time
increment, the increment size, mass scaling definitions, and bulk viscosity
parameters as described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. In the Time period field, enter the time period of the step.
4. Select an Nlgeom option:
Toggle Nlgeom Off to perform a geometrically linear analysis during
the current step.
Toggle Nlgeom On to indicate that Abaqus/Explicit should account for
geometric nonlinearity during the step. Once you have
toggled Nlgeom on, it will be active during all subsequent steps in the
analysis.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Mass scaling tabbed page. For
background information on mass scaling, see “Mass scaling,” Section 11.6.1
of the Abaqus Analysis User's Guide.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
8. If you toggle on both Scale by factor and Scale to target time increment,
Abaqus/Explicit first scales the masses by the factor value that you enter and
then possibly scales them again, depending on the value you enter for target
time increment and the option you select for applying that target.
9. If you selected Automatic mass scaling, enter the following values:
In the Feed rate field, enter the estimated average velocity of the
workpiece in the rolling direction at steady-state conditions.
In the Extruded element length field, enter the average element
length in the rolling direction.
In the Nodes in cross-section field, enter the number of nodes in the
cross-section of the workpiece. Increasing this value decreases the
amount of mass scaling.
For more information, see “Automatic mass scaling for analysis of bulk metal
rolling” in “Mass scaling,” Section 11.6.1 of the Abaqus Analysis User's Guide.
10. If you selected Semi-automatic mass scaling throughout the step
or Automatic mass scaling, specify when, during the step, you want
Abaqus/Explicit to perform mass scaling calculations:
Choose Every n increments to specify the frequency, in increments, at
which Abaqus/Explicit is to perform mass scaling calculations. Enter the
desired frequency in the field provided.
11. Click OK to close the Edit mass scaling dialog box and return to the Mass
scaling tabbed page of the Edit Step dialog box.
The mass scaling definition that you have just created appears in
the Data table.
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
2. Enter a value for the Linear bulk viscosity parameter. Linear bulk viscosity
is included by default in Abaqus/Explicit.
3. Enter a value for the Quadratic bulk viscosity parameter. This form of bulk
viscosity pressure is found only in solid continuum element and is applied only
if the volumetric strain rate is compressive.
When you have finished configuring settings for the dynamic, explicit step,
click OK to close the Edit Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Heat transfer),
or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as the time period for the step, the maximum allowable temperature
change per increment, and equation solver preferences as described in the
following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. Choose a Response option:
Choose Steady-state to omit the internal energy term (the specific heat
term) in the governing heat transfer equation. For more information,
see “Steady-state analysis” in “Uncoupled heat transfer
analysis,” Section 6.5.2 of the Abaqus Analysis User's Guide.
Choose Transient to perform time integration with the backward Euler
method in the pure conduction elements. This method is unconditionally
stable for linear problems. For more information, see “Transient
analysis” in “Uncoupled heat transfer analysis,” Section 6.5.2 of the
Abaqus Analysis User's Guide.
4. In the Time period field, enter the time period of the step.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
When you have finished configuring settings for the heat transfer step, click OK to
close the Edit Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Dynamic, Implicit),
or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as the time period for the step, increment size, and equation solver
preferences as described in the following procedures.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
3. In the Maximum number of increments field, enter the upper limit to the
number of increments in the step. The analysis stops if this maximum is
exceeded before Abaqus/Standard arrives at the complete solution for the
step.
4. If you selected Automatic in Step 2, do the following:
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
When you have finished configuring settings for the step, click OK to close the Edit
Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Coupled temp-
displacement), or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as the time period for the step, increment size, and solution technique
preferences as described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. Indicate whether you want Steady-state or Transient response. See the
following sections for more information:
“Steady-state analysis” in “Fully coupled thermal-stress
analysis,” Section 6.5.3 of the Abaqus Analysis User's Guide
“Transient analysis” in “Fully coupled thermal-stress analysis,” Section
6.5.3 of the Abaqus Analysis User's Guide
4. In the Time period field, enter the time period of the step.
5. Choose an Nlgeom option:
Toggle Nlgeom Off to perform a geometrically linear analysis during
the current step.
Toggle Nlgeom On to indicate that Abaqus/Standard should account
for geometric nonlinearity during the step. Once you have
toggled Nlgeom on, it will be active during all subsequent steps in the
analysis.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
Click the arrow to the right of Automatic stabilization, and select a method
for defining the damping factor:
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
When you have finished configuring settings for the step, click OK to close the Edit
Step dialog box.
Joule heating arises when the energy dissipated by an electrical current flowing
through a conductor is converted into thermal energy. Abaqus/Standard provides a
fully coupled thermal-electrical procedure for analyzing this type of problem; the
coupled thermal-electrical equations are solved simultaneously for both temperature
and electrical potential at the nodes. For more information, see “Coupled thermal-
electrical analysis,” Section 6.7.3 of the Abaqus Analysis User's Guide.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Coupled thermal-
electric), or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as the time period for the step, increment size, and solution technique
preferences as described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. Choose a Response option:
Choose Steady-state to omit the internal energy term (the specific heat
term) in the governing heat transfer equation. Only direct current is
considered in the electrical problem, and it is assumed that the system
has negligible capacitance. (Electrical transient effects are so rapid that
they can be neglected.) For more information, see “Steady-state
analysis” in “Coupled thermal-electrical analysis,” Section 6.7.3 of the
Abaqus Analysis User's Guide.
Choose Transient to perform time integration with the same backward
Euler method used in uncoupled heat transfer analyses. This method is
unconditionally stable for linear problems. For more information,
see “Transient analysis” in “Coupled thermal-electrical
analysis,” Section 6.7.3 of the Abaqus Analysis User's Guide.
4. In the Time period field, enter the time period of the step.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
When you have finished configuring settings for the step, click OK to close the Edit
Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Coupled thermal-
electric-structural), or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as the time period for the step, type of incrementation, and solution
technique preferences as described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. Choose a Response option:
Choose Steady-state to omit the internal energy term (the specific heat
term) in the governing heat transfer equation. A static displacement
solution is assumed. Only direct current is considered in the electrical
problem, and it is assumed that the system has negligible capacitance.
(Electrical transient effects are so rapid that they can be neglected.) For
more information, see “Steady-state analysis” in “Fully coupled thermal-
electrical-structural analysis,” Section 6.7.4 of the Abaqus Analysis
User's Guide.
Choose Transient to perform a transient analysis. As with the steady-
state response, electrical transient effects are neglected and a static
displacement solution is assumed. You can control the time
incrementation in a transient analysis directly, or Abaqus/Standard can
control it automatically. Automatic time incrementation is generally
preferred. For more information, see “Transient analysis” in “Fully
coupled thermal-electrical-structural analysis,” Section 6.7.4 of the
Abaqus Analysis User's Guide.
4. In the Time period field, enter the time period of the step.
5. Choose an Nlgeom option:
Toggle Nlgeom Off to perform a geometrically linear analysis during
the current step.
Toggle Nlgeom On to indicate that Abaqus/Standard should account
for geometric nonlinearity during the step. Once you have
toggled Nlgeom on, it will be active during all subsequent steps in the
analysis.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
6. Select an automatic stabilization method if you expect the problem to have
local instabilities such as surface wrinkling, material instability, or local
buckling. Abaqus/Standard can stabilize this class of problems by applying
damping throughout the model. For more information, see “Unstable
problems” in “Static stress analysis,” Section 6.2.2 of the Abaqus Analysis
User's Guide, and “Automatic stabilization of static problems with a constant
damping factor” in “Solving nonlinear problems,” Section 7.1.1 of the Abaqus
Analysis User's Guide.
Click the arrow to the right of Automatic stabilization, and select a method
for defining the damping factor:
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
When you have finished configuring settings for the step, click OK to close the Edit
Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Direct cyclic),
or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, Fatigue, and Other tabbed pages, configure
settings such as the cycle time period, maximum number of increments,
increment size, low-cycle fatigue options, and equation solver preferences as
described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. In the Cycle time period field, enter the time of a single loading cycle.
4. Toggle on Use displacement Fourier coefficients from previous direct
cyclic step to indicate that the current step is a continuation of the previous
direct cyclic step. See “Direct cyclic analysis” in “Direct cyclic
analysis,” Section 6.2.6 of the Abaqus Analysis User's Guide, for more details.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Fatigue tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
4. Click the arrow to the right of the Extrapolation of previous state at start of
each increment field, and select a method for determining the first guess to
the incremental solution:
Select Linear to indicate that the process is essentially monotonic and
Abaqus/Standard should use a 100% linear extrapolation, in time, of
the previous incremental solution to begin the nonlinear equation
solution for the current increment.
Select Parabolic to indicate that the process should use a quadratic
extrapolation, in time, of the previous two incremental solutions to begin
the nonlinear equation solution for the current increment.
Select None to suppress any extrapolation.
When you have finished configuring settings for the direct cyclic step, click OK to
close the Edit Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Dynamic, Temp-disp,
Explicit), or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, Mass scaling, and Other tabbed pages,
configure settings such as the time period for the step, the increment size,
mass scaling definitions, and bulk viscosity parameters as described in the
following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. In the Time period field, enter the time period of the step.
4. Select an Nlgeom option:
Toggle Nlgeom Off to perform a geometrically linear analysis during
the current step.
Toggle Nlgeom On to indicate that Abaqus/Explicit should account for
geometric nonlinearity during the step. Once you have
toggled Nlgeom on, it will be active during all subsequent steps in the
analysis.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
5. If desired, enter a Time scaling factor to adjust the stable time increment
computed by Abaqus/Explicit. (This option is unavailable if you have specified
a User-defined time increment for the Fixed time incrementation scheme.)
For more information, see “Scaling the time increment” in “Fully coupled
thermal-stress analysis,” Section 6.5.3 of the Abaqus Analysis User's Guide.
1. In the Edit Step dialog box, display the Mass scaling tabbed page. For
background information on mass scaling, see “Mass scaling,” Section 11.6.1
of the Abaqus Analysis User's Guide.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
8. If you toggle on both Scale by factor and Scale to target time increment,
Abaqus/Explicit first scales the masses by the factor value that you enter and
then possibly scales them again, depending on the value you enter for target
time increment and the option you select for applying that target.
9. If you selected Automatic mass scaling, enter the following values:
a. In the Feed rate field, enter the estimated average velocity of the
workpiece in the rolling direction at steady-state conditions.
b. In the Extruded element length field, enter the average element
length in the rolling direction.
c. In the Nodes in cross-section field, enter the number of nodes in the
cross-section of the workpiece. Increasing this value decreases the
amount of mass scaling.
For more information, see “Automatic mass scaling for analysis of bulk metal
rolling” in “Mass scaling,” Section 11.6.1 of the Abaqus Analysis User's Guide.
11. Click OK to close the Edit mass scaling dialog box and return to the Mass
scaling tabbed page of the Edit Step dialog box.
The mass scaling definition that you have just created appears in
the Data table.
1. In the Edit Step dialog box, display the Other tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
2. Enter a value for the Linear bulk viscosity parameter. Linear bulk viscosity
is included by default in Abaqus/Explicit.
3. Enter a value for the Quadratic bulk viscosity parameter. This form of bulk
viscosity pressure is found only in solid continuum element and is applied only
if the volumetric strain rate is compressive.
When you have finished configuring settings for the step, click OK to close the Edit
Step dialog box.
A geostatic stress field procedure allows you to verify that the initial geostatic stress
field is in equilibrium with applied loads and boundary conditions. It also allows you to
iterate, if necessary, to obtain equilibrium; or you can allow Abaqus to compute
equilibrium automatically for cases in which the initial state is unknown. This type of
procedure is usually the first step of a geotechnical analysis, followed by a coupled
pore fluid diffusion/stress or static analysis procedure. For more information,
see “Geostatic stress state,” Section 6.8.2 of the Abaqus Analysis User's Guide.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Geostatic), or “Editing a
step,” Section 14.9.3.
2. On the Basic and Other tabbed pages, configure settings such as controls to
include nonlinear effects of large displacements and equation solver
preferences as described in the following procedures.
1. In the Edit Step dialog box, display the Basic tabbed page.
2. In the Description field, enter a short description of the analysis step. Abaqus
stores the text that you enter in the output database, and the text is displayed
in the state block by the Visualization module.
3. Select an Nlgeom option:
Toggle Nlgeom Off to perform a geometrically linear analysis during
the current step.
Toggle Nlgeom On to indicate that Abaqus/Standard should account
for geometric nonlinearity during the step. Once you have
toggled Nlgeom on, it will be active during all subsequent steps in the
analysis.
For more information, see “Linear and nonlinear procedures,” Section 14.3.2.
1. In the Edit Step dialog box, display the Incrementation tabbed page.
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
(For information on displaying the Edit Step dialog box, see “Creating a
step,” Section 14.9.2, or “Editing a step,” Section 14.9.3.)
For more information on matrix storage, see “Matrix storage and solution
scheme in Abaqus/Standard” in “Defining an analysis,” Section 6.1.2 of the
Abaqus Analysis User's Guide.
When you have finished configuring settings for the step, click OK to close the Edit
Step dialog box.
1. Display the Edit Step dialog box following the procedure outlined in “Creating
a step,” Section 14.9.2 (Procedure type: General; Mass diffusion),
or “Editing a step,” Section 14.9.3.
2. On the Basic, Incrementation, and Other tabbed pages, configure settings
such as steady-state or transient response and automatic or fixed