Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-HY 200 V3 + HAS-R 304/316 SS 5/8
Item number: 2045007 HAS-R 316 SS 5/8"x7 5/8" (element) / 2334276
HIT-HY 200-R V3 (adhesive)
Effective embedment depth: hef,act = 3.125 in. (hef,limit = - in.)
Material: ASTM F 593
Evaluation Service Report: ESR-4868
Issued I Valid: 11/1/2022 | 11/1/2024
Proof: Design Method ACI 318-19 / Chem
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.188 in.
Ledger Angle :
R L1 x L2 x tL1 x tL2 x l = 2.500 in. x 2.500 in. x 0.188 in. x 0.188 in. x 30.000 in.;
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kip] Capacity f Nn [kip] Utilization bN = Nua/f Nn Status
Steel Strength* 1.684 14.690 12 OK
Bond Strength** 3.369 4.738 72 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** 3.369 4.465 76 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
Variables
2
Ase,N [in. ] futa [psi]
0.23 100,000
Calculations
Nsa [kip]
22.600
Results
Nsa [kip] f steel f Nsa [kip] Nua [kip]
22.600 0.650 14.690 1.684
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
Nag = (AA ) y
Na
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-19 Eq. (17.6.5.1b)
f Nag ³ Nua ACI 318-19 Table 17.5.2
ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b)
2
ANa0 = (2 cNa) ACI 318-19 Eq. (17.6.5.1.2a)
t uncr
cNa = 10 da √ 1100
ACI 318-19 Eq. (17.6.5.1.2b)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-19 Eq. (17.6.5.3.1)
1+
cNa
Na
ACI 318-19 Eq. (17.6.5.4.1b)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-19 Eq. (17.6.5.5.1b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-19 Eq. (17.6.5.2.1)
Variables
t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] aoverhead t k,c [psi]
2,220 0.625 3.125 3.000 1.000 1,170
Calculations
cNa [in.] ANa [in. ]
2
ANa0 [in. ]
2
y ed,Na
8.839 395.74 312.50 0.802
Results
Nag [kip] f bond f Nag [kip] Nua [kip]
7.290 0.650 4.738 3.369
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1b)
f Ncbg ³ Nua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
2
ANc0 = 9 hef ACI 318-19 Eq. (17.6.2.1.4)
( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
1+
3 hef
ef
ACI 318-19 Eq. (17.6.2.4.1b)
= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
c ac ac
1.5
Nb = kc l a √ '
fc hef ACI 318-19 Eq. (17.6.2.2.1)
Variables
hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] y c,N
3.125 0.000 0.000 3.000 1.000
'
cac [in.] kc la fc [psi]
4.252 17 1.000 2,500
Calculations
ANc [in. ]
2
ANc0 [in. ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kip]
144.14 87.89 1.000 1.000 0.892 1.000 4.696
Results
Ncbg [kip] f concrete f Ncbg [kip] Nua [kip]
6.869 0.650 4.465 3.369
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
4 Shear load
Load Vua [kip] Capacity f Vn [kip] Utilization bV = Vua/f Vn Status
Steel Strength* 1.500 8.136 19 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout 3.000 9.617 32 OK
Strength controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A
Variables
2
Ase,V [in. ] futa [psi]
0.23 100,000
Calculations
Vsa [kip]
13.560
Results
Vsa [kip] f steel f Vsa [kip] Vua [kip]
13.560 0.600 8.136 1.500
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
Nc0
ec,N y ed,N y c,N y cp,N Nb ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
2
ANc0 = 9 hef ACI 318-19 Eq. (17.6.2.1.4)
( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
1+
3 hef
ef
ACI 318-19 Eq. (17.6.2.4.1b)
= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
c ac ac
1.5
Nb = kc l a √ '
fc hef ACI 318-19 Eq. (17.6.2.2.1)
Variables
kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.]
2 3.125 0.000 0.000 3.000
'
y c,N cac [in.] kc la fc [psi]
1.000 4.252 17 1.000 2,500
Calculations
ANc [in. ]
2
ANc0 [in. ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kip]
144.14 87.89 1.000 1.000 0.892 1.000 4.696
Results
Vcpg [kip] f concrete f Vcpg [kip] Vua [kip]
13.738 0.700 9.617 3.000
5 Combined tension and shear loads, per ACI 318-19 section 17.8
bN bV z Utilization bN,V [%] Status
0.755 0.312 5/3 77 OK
z z
bNV = bN + bV <= 1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-19,
Section 26.7.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
7 Installation data
Anchor type and diameter: HIT-HY 200 V3 + HAS-R
304/316 SS 5/8
Hole diameter in the fixture: df = 0.687 in. Item number: 2045007 HAS-R 316 SS 5/8"x7 5/8"
(element) / 2334276 HIT-HY 200-R V3 (adhesive)
Plate thickness (input): 0.188 in. Maximum installation torque: 0.06000 ft.kip
Recommended plate thickness: not calculated Hole diameter in the base material: 0.750 in.
Drilling method: Hammer drilled Hole depth in the base material: 3.125 in.
Cleaning: Compressed air cleaning of the drilled hole according to instructions Minimum thickness of the base material: 4.625 in.
for use is required
5/8 Hilti HAS Stainless steel threaded rod with Hilti HIT-HY 200 V3 Safe Set System
y
15.000 15.000
1.2501.250
1.2501.250
1.156
2 1 -0.000
x
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.91
www.hilti.com
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Feb 18, 2024 Date: 2/18/2024
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Angel bending
Fy = 240 MPa
Load width assumed 2*76 mm (double angle leg length)
Z=2*76*8^2/4 =2432 mm3
0.5 m
Table 4.1.5.9.
Specified Concentrated Live Loads on an Area of Floor or Roof
Forming Part of Sentence 4.1.5.9.(1)