Professional Documents
Culture Documents
6SL3210-1KE22-6UB1_datasheet_en
6SL3210-1KE22-6UB1_datasheet_en
Line voltage 380 ... 480 V +10 % -20 % Switching level: 0→1 11 V
Output Number 1
Rated voltage 400V IEC 480V NEC 1) Number as relay changeover contact 1
150 % base load current IL for 3 s, followed by 110 % base load current IL for 57 s PTC/ KTY interface
in a 300 s cycle time
1 motor temperature sensor input, sensors that can be connected PTC, KTY and
High Overload (HO) Thermo-Click, accuracy ±5 °C
200% base load current IH for 3 s, followed by 150% base load current IH for 57 s Closed-loop control techniques
in a 300 s cycle time
V/f linear / square-law / parameterizable Yes
General tech. specifications V/f with flux current control (FCC) Yes
Power factor λ 0.70 ... 0.85
V/f ECO linear / square-law Yes
Offset factor cos φ 0.95
Sensorless vector control Yes
Efficiency η 0.97
Vector control, with sensor No
Sound pressure level (1m) 66 dB
Encoderless torque control No
Power loss 292.0 W
Torque control, with encoder No
Filter class (integrated) Unfiltered
Communication
Communication USS/MODBUS RTU
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 2 Generated Wed Jun 19 05:11:25 CET 2024
Data sheet for SINAMICS G120C
Cooling air requirement 0.018 m³/s (0.636 ft³/s) Comparison with the reference
32.5 %
converter (90% / 100%)
Installation altitude 1,000 m (3,280.84 ft)
Ambient temperature
I 227.0 W (1.3 %) 254.0 W (1.5 %) 292.0 W (1.7 %)
Operation -10 ... 40 °C (14 ... 104 °F) 100%
Relative humidity
Connections
126.0 W (0.7 %) 132.0 W (0.8 %)
Signal cable 25%
Mechanical data
Degree of protection IP20 / UL open type
Dimensions
Standards
Compliance with standards UL, cUL, CE, C-Tick (RCM)
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 2 Generated Wed Jun 19 05:11:25 CET 2024