Input data
Refrigerant R407F
Reference temperature Dew point temperature
Calculation mode Refrigeration / Air Cond.
Operating mode Subcritical
Power supply 230/3/50
Condensing temperature °C 50
Condensing pressure psi 321.5
Liquid subcooling K 6
Liquid temperature °C 40.01
Evaporating temperature °C -5
Evaporating pressure psi 63.36
Suction gas superheating K 10
Useful fraction of superheating % 100
Output data
Compressor : B1.5-9.1Y
Number of compressors : VSx1
Refrigerating capacity TR 2.03
Refrigerating capacity [ *ref ] TR 1.932
Evaporator capacity TR 2.03
Power input W 3335
Condenser capacity, theor. TR 2.978
Current A 10.18
COP/EER W/W 2.14
Mass flow kg/h 160
Operating frequency Hz 69
Connection - DOL-DELTA
Operating mode - Inverter
Discharge temperature °C 105.84
Ratio (%) % 100.0%
Note -
FRASCOLD SPA - via Barbara Melzi 103/105, IT 20027 Rescaldina MI - +39-0331-742201 - frascold@frascold.it - www.frascold.it
1/2
Customer: Ecofrost Technologies
Model: B1.5-9.1Y
Refrigerant: R407F
Power supply: 230/3/50 DOL-DELTA
Technical data:
Displacement 8.96 m³/h
Nominal compressor speed 1450 rpm
Motor voltage 230 V
Nominal operating frequency 50 Hz
Maximum allowed operating current (MRA) 10.2 A
Locked rotor current (LRA) 46.6 A
Number of pistons 2
Net weight 38 kg
Lubricant FRASCOLD POE32
Oil charge 1l
Maximum static pressure LP 297.33 psi
Maximum operating pressure HP 435.11 psi
Motor connections:
W V U
Y X Z
FRASCOLD SPA - via Barbara Melzi 103/105, IT 20027 Rescaldina MI - +39-0331-742201 - frascold@frascold.it - www.frascold.it
2/2
VARIABLE FREQUENCY DRIVE VFD
All Frascold compressors are designed to be compatible with inverter technology. Inverters, also known as variable
frequency drives, can greatly improve performance and efficiency in many applications.
(For 400V motors in certain application conditions there might be a narrowing of the frequency range. Always
check on the Frascold Selection Software. For capacity data at the various frequencies see the Frascold selection
software FSS3.)
A-B-D Series
Operating range 50
40 60
30 70
25 75 17
87
0
Q-S Series
Operating range 50
40 60
30 70
25 75
87
0
V-Z-W Series
Operating range 50
40 60
30 70
25 75
87
0
www.frascold.it