Professional Documents
Culture Documents
UE_2005
UE_2005
Main Catalogue
Lightning Protection
Surge Protection
Indexes 305
3
DEHN – Safety with At first there was the idea of
diverting lightning to the
ground without endange-
Tradition. ring home or people. This
was the challenge, Hans
Dehn met in his company
founded in Nuremberg in
1910. Since the beginning of
the 1920s DEHN has produ-
ced lightning protection and
earthing components. Over
the years, a diversified pro-
duct range for external
lightning protection came
into existence.
Production in 2004.
4
In the course of its history of
more than 90 years, the ini-
tial handicraft business has
DEHN – Products for Safety.
become a worldwide opera-
ting industrial company with
three product ranges:
Lightning Protection
Surge Protection
1954 – 2004
Safety Equipment
50 Years of surge protection
DEHN + SÖHNE is a booster
of technological progress.
We do intensive, application-
related research work for
customer-orientated solu-
tions. The performance
parameters of our impulse
current test laboratories is
unique worldwide.
5
DEHN – Quality DEHN + SÖHNE produce
more than 3,500 devices and
components for your safety.
and Safety. Our products protect human
lives and material assets.
High quality requirements
and the awareness in the
treatment of the environ-
ment is therefore a must.
In order to ensure this and
make it also transparent for
you as our customer, the
company was certified in
accordance with DIN EN ISO
9001 and DIN EN ISO 14001.
Annual examinations and a
complete reaudit every
three years show the central
significance of quality and
environmental management
in the company.
We cooperate intensively
with international and
national standard commit-
tees and take part in con-
gresses worldwide. We are
active members of the
“Ausschuss für Blitzschutz
und Blitzforschung“ (ABB)
[Commission for Lightning
Protection and Research]
and in the “Verband Deut-
scher Blitzschutzfirmen
(VDB)“ [Association of Ger-
man Lightning Protection
Companies]. Thus, we foster
nationally and internationally
the aims and further devel-
opment of lightning pro-
tection.
Our aim is to provide sophis-
ticated, customer-orientated
solutions to increase the
economy of companies. Only
those who are accessible can
be quick, flexible and effi-
cient.
6
DEHN + SÖHNE supplies
equipment and provides
services covering lightning
DEHN – Global Safety.
and surge protection world-
wide. We have committed
ourselves to continuous mar-
ket presence, productivity,
product quality and delivery
in time. Developing innova-
tive and market-related
products requires closeness
to our customers. They
benefit from our strength in
innovation, flexibility and
short decision processes.
7
DEHN – Worldwide.
Austria Pakistan
Argentina Peru
Australia Poland
Belgium Portugal
Bolivia Russia
Brasil Saudi Arabia
Bulgaria Sweden
Cape Verde Switzerland
Chile Serbia
China / Hong Kong Singapore
Colombia Slovakia
Croatia Slowenia
Cuba Spain
Denmark Sri Lanka
Estonia South Africa
Finland Syria
France Taiwan
Greece Thailand
Great Britain Czech Republic
India Turkey
Indonesia Hungary
Italy USA (Florida)
Iran Vietnam
Israel
Japan We shall be pleased to name
Korea you the right contact
Latvia person at our subsidiaries or
Lebanon representatives.
Lithuania Please contact our export
Luxembourg department under
Malaysia
Tel.: +49 181 906 462
Macedonia
Fax: +49 181 906 444
Mexico
New Zealand or send an Email to
Netherlands export@dehn.de
Norway
8
9
DEHN – Safety according to Specification.
Lightning Protection Zones Concept
Failures of technical systems and installations are
Fire Theft
very unpleasant for the operators. These require Water
4.6 % Vandalism
faultless operation from the equipment both 5.6 %
27.1 %
under “normal“ conditions and in case of thun-
derstorms. Loss reports of insurance companies
show clearly that there is a backlog demand
both in the private (Fig. 1) and the commercial
sector (Fig. 2).
A comprehensive protection concept would help 22.9 %
to compensate it. Negligence 15.3 % 0.8 % 23.7 %
The Lightning Protection Zones Concept enables Others Elemental Surges
designers, constructors and operators to plan, (lightning discharges,
perform and control protection measures. Thus, switching operations)
all relevant devices, installations and systems are Fig. 1: Causes of damage to electronic equipment in 2001
protected reliably and furthermore with econo- Analysis of 7370 damage claims
mically acceptable efforts. (Ref..: Württemberigsche Versicherung AG)
10
Direct/Close Lightning Stroke: For ensuring a continuous availability of complex electri-
1
Lightning stroke into the external lightning
protection system, process framework
cal and IT systems, even in case of a direct lightning
(in industrial installations), cables etc.
effect, further measures for the surge protection of elec-
Voltage drop at the impulse earthing
1a resistance R
st 2b trical and electronic installations are necessary, based on
2a
1b Induced voltage in loops 1 a building lightning protection system. Taking all causes
20 kV
L1
L2
of surges into consideration is very important. For this
L3
2c
PEN purpose, the Lightning Protection Zones Concept descri-
bed in IEC 62305-4 is applied (Fig. 5).
Distant Lightning Stroke
A structure is subdivided in different risk zones. With
1b Stroke in medium voltage
2a
overhead lines these zones the necessary devices and components can
Surge travelling waves on
Rst 2b overhead lines due to
be defined for lightning and surge protection.
1a cloud-to-cloud lightning
Part of an EMC-conform lightning protection zones con-
low voltage power Fields of the lightning
IT system
supply system 2c channel
cept is an external lightning protection system (including
air-termination system, down-conductor system, eart-
Fig. 3: Causes of surges at lightning discharges
hing), equipotential bonding, spatial shielding and the
surge protection for the power supply and IT systems.
(kA) 1 2
The definition of the lightning protection zones is sub-
100 kA Wave form [µs] 10/350 8/20
ject to the predeterminations made in Table 1.
imax [kA] 100 5
Q [As] 50 0.1
i 80 kA
W/R [J/Ω] 2.5 · 106 0.4 · 103 In correspondence with the requirements and loads on
Standard IEC 62305-1 EN 60060-2
60 kA
surge protective devices regarding their installation site,
50 kA 1 these are classified as lightning current arresters, surge
40 kA arresters and combined lightning current and surge
arresters.
20 kA The highest requirements regarding the discharge capa-
2 city are made on lightning current and combined light-
200 µs 350 µs 600 µs 800 µs 1000 µs
ning current and surge arresters, which realise the transi-
t (µs) tion from Lightning Protection Zone 0A to 1 or 0A to 2.
11
DEHN – Technical Definitions.
12
Max. Transmission Capacity Short-circuit Withstand Capability
defines the max. HF capacity that can be trans- is the value of the prospective power-frequen-
mitted via a coax surge protective device with- cy short-circuit current controlled by the surge
out interfering with the protective component. protective device in case it is furnished with an
upstream backup fuse.
Nominal Discharge Current In
is the peak value of an impulse current, wave- Mains-side Overcurrent Protection /
form 8/20 µs, which the surge protective device Backup Fuse
is rated for, according to a certain test pro- is an overcurrent protective device (e.g. fuse or
gramme. circuit breaker), which is installed outside of
the surge arrester on the supply side to inter-
Max. Discharge Current Imax rupt the power-frequency follow currents, if
is the max. peak value of the impulse current the breaking capacity of the surge protective
8/20 µs, which can be safely discharged by the device is exceeded.
device.
Operating Time ta
Lightning Impulse Current Iimp is the time passing until the automatic dis-
is a standardised impulse current curve, with a connection from the power supply at a failure
waveform 10/350 µs. Its parameters (peak of the electrical circuit or equipment to be pro-
value, charge, specific power) simulate the tected. The response time is an application-
loads of natural lightning currents. specific value resulting from the intensity of
the fault current flowing and the characteri-
Lightning current and combined lightning
stics of the protective device.
current and surge arresters must be capable of
discharging such lightning impulse currents
Combined Impulse UOC
several times without consequential damage
is generated by a hybrid generator (1.2/50 µs,
to the equipment.
8/20 µs) with a virtual impedance of 2 Ω. The
open-circuit voltage of this generator is de-
Voltage Protection Level Up
fined as UOC. UOC is preferably indicated for
The voltage protection level of a surge protec-
SPDs Type 3.
tive device is the max. instantaneous value of
the voltage on the terminals of a surge protec-
N-PE Surge Arresters
tive device, defined out of the standardised
are surge protective devices exclusively de-
individual tests:
signed for installation between the N- and
– Lightning impulse sparkover voltage
PE conductor.
1.2/50 µs (100%)
– Response voltage at a steepness of 1 kV/µs
Operating Temperature Range ϑ
– Residual voltage at a nominal discharge
indicates the range where the devices can be
current Ures
used. In case of devices without self-heating, it
The voltage protection level characterises the is equal to the ambient temperature range.
capability of a surge protective device to limit The temperature rise at devices with self-hea-
surges to a residual level. If used in power net- ting must not exceed the max. value indicated.
works, the voltage protection level defines the
location of use via the overvoltage category Response Time tA
according to DIN VDE 0110-1:1997-04 (EN Response times generally characterise the res-
60664-1, IEC 60664-1). For surge protective ponse performance of the individual protec-
devices designed for protection of IT networks, tion elements used in surge protective devices.
the voltage protection level has to be adjusted
Depending on the steepness du/dt of the
to the immunity of the equipment to be pro-
impulse voltage or di/dt of the impulse cur-
tected (DIN EN 61000-4-5: 2001-12).
rent, the response times can change within
certain limits.
Disconnection Capacity / Follow Current
Extinguishing Capability Ifi
Thermal Disconnection Device
The disconnection capacity is the uninterfered
Surge protective devices for power supply
(prospective) rms-value of the mains follow
systems, which are furnished with voltage-con-
current, which can automatically be extin-
trolled resistors (varistors), mostly have an inte-
guished by the surge protective device at the
grated disconnection device isolating the surge
presence of UC. It is proved at the operating
protective device from mains at overloads and
duty test according to E DIN VDE 0675-6/A1:
indicating this state of operation.
1996-03.
The disconnection device reacts on the “joule
heat“ generated by an overloaded varistor and
disconnects the surge protective device from
mains, if a certain temperature is exceeded.
13
The disconnection device is designed to dis- Shield Attenuation
connect the overloaded surge protective device Relation of the power feeded into a coaxial
in time to avoid a fire hazard. It is not designed cable to the power radiated through the cable
to ensure the protective measure of “protection from the outer conductor.
at indirect contact“.
Protective Conductor Current IPE
The function of these thermal disconnection ... is the current flowing through the PE connec-
devices is tested via simulated overloads/ageing tion when the surge protective device is connec-
of the SPD. ted with the max. permanent voltage UC , corre-
sponding to the installation instructions and
Degree of Protection without load-side consumers.
The degree of protection IP corresponds to the
subdivision into the degrees of protection in Categories according to IEC 61643-21:2000
accordance with DIN EN 60529 (VDE 0470 Part 1). (DIN VDE 0845 Part 3-1)
For testing the current carrying capability as well
Protective Circuit as the voltage limitation at influences by impul-
Protective circuits are multi-stage, cascaded pro- ses, a variety of impulse voltages and impulse
tective devices. The individual protection stages currents are described in E DIN EN 61644-1
can consist of discharge paths, varistors, semi- (VDE 0845 Part 3-1). They are sorted in Table 3
conductor elements. The energy coordination of and provide preferred values. These categories
the individual protection stages is realised with (A ... to D ...) are not comparable to the classes
decoupling elements. stated in E DIN VDE 0675-6:1989-11,-6/A1:1996-
03 and –6/A2:1996-10. E DIN EN 61644-1 (VDE
Series Impedance 0845 Part 3-1):1999-07 classifies impulse currents
is the impedance in the direction of the signal out of surge interferences as category C and par-
flow between input and output of the SPD. tial lightning currents as category D (max. load
class).
Bandwidth fG
defines the frequency-dependent performance The technical data indicate a classification upon
of an SPD. Bandwidths are frequencies causing the fulfilled categories.
an insertion loss (aE) of 3 dB under certain test DEHN + SÖHNE surge protective devices exceed
conditions (see EN 61643-21:2000). the values indicated in the categories. The expli-
cite value for the impulse current carrying capa-
If nothing else is indicated, the value of the fre- bility is therefore indicated by the stated nomi-
quency refers to a 50 Ω system. nal discharge current (8/20) and lightning im-
pulse current (10/350).
Frequency Range
characterises the transmission band or the let-
through frequency of an SPD according to the
described attenuation characteristics.
Return Loss aR
indicates at high-frequency applications, how
many rates of the “forward“ wave are reflected
at the protective device (“transition point“).
Insertion Loss
At an indicated frequency, the insertion loss of a
surge protective device is defined via the relation
of the voltage value at the installation site be-
fore and after the insertion of the SPD. If no
other value is indicated, the value refers to a
50 Ω system.
14
POWER SUPPLY SYSTEMS
Accessories 121
www.dehn.de 15
Quick Product Choice POWER SUPPLY SYSTEMS
DEHNventil TNC 3-pole 255 V ac 75 kA < 1.5 kV 50 kArms 315*/125 6 directly with SPDs DV TNC 255 900 373 28
DEHNventil TNS 4-pole 255 V ac 100 kA < 1.5 kV 50 kArms 315*/125 8 Type 2 and 3 of the DV TNS 255 900 374 29
DEHNventil TT 4-pole 255 V ac 100 kA < 1.5 kV 50 kArms 315*/125 8 Red/Line-Family, DV TT 255 900 375 30
DEHNventil 2P TN 2-pole 255 V ac 50 kA < 1.5 kV 50 kArms 315*/125 6 as well as terminal DV 2P TN 255 900 371 32
DEHNventil 2P TT 2-pole 255 V ac 50 kA < 1.5 kV 50 kArms 315*/125 8 devices DV 2P TT 255 900 370 33
with UN = 230 V
DEHNbloc Maxi 1-pole 255 V ac 25 kA < 2.5 kV 25 kArms encapsulated 315/125 2 directly with DBM 1 255 900 025 40
DEHNguard DBM 1 255 L 900 026 40
DEHNbloc/3 3-pole 255 V ac 100 kA < 4 kV 3 kArms encapsulated 500** 4 with DB 3 255 900 110 44
DEHNbloc/1 255 1-pole 255 V ac 50 kA < 4 kV 3 kArms encapsulated 500** 2 DEHNguard DB 1 255 900 111 43
DEHNbloc/1 255 H 1-pole 255 V ac 25 kA < 4 kV 50 kArms encapsulated 315/125 2 via > 15m DB 1 255 H 900 222 42
DEHNbloc/1 440 1-pole 440 V ac 50 kA < 4 kV 1.5 kArms encapsulated 500** 2 line or DB 1 440 900 159 43
DEHNbloc/NH NH, size 00 255 V ac 50 kA < 4 kV 3 kArms encapsulated 500** – DEHNbridge DB NH00 255 900 260 45
DEHNport 255 1-pole 255 V ac 75 kA < 3.5 kV 4 kArms exhausting 500** 2 DP 255 900 100 49
DEHNport 440 1-pole 440 V ac 75 kA < 3.5 kV 750 Arms exhausting 500** 2 DP 440 900 101 49
DEHNport Maxi 1-pole 255 V ac 50 kA < 4 kV 50 kArms exhausting 500** 2 DPM 255 900 104 47
* Requirement only in accordance with the short circuit conditions of the connecting cable
** Operating time ta ≤ 0.2 s
DEHNgap Maxi 1-pole 255 V ac 100 kA < 1.5 kV 100 Arms encapsulated – 2 with DGPM 255 900 055 51
DEHNgap B/n 1-pole 255 V ac 100 kA < 4 kV 100 Arms encapsulated – 2 DEHNgap C/T DGP BN 255 900 132 52
DEHNgap B 1-pole 255 V ac 100 kA < 4 kV 100 Arms exhausting – 2 via > 15 m DGP B 255 900 130 52
DEHNgap B/NH/n NH, size 00 255 V ac 50 kA < 4 kV 100 Arms encapsulated – – line or DGP B NH00 900 269 53
N 255
DEHNbridge
16 www.dehn.de
POWER SUPPLY SYSTEMS Quick Product Choice
DEHNguard TNC 3-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 3 – DG TNC 230 400 900 510 56
DEHNguard TNC FM 3-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 3 1 FC DG TNC 230 400 FM 900 540 56
DEHNguard TNS 4-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 4 – DG TNS 230 400 900 530 57
DEHNguard TNS FM 4-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 4 1 FC DG TNS 230 400 FM 900 560 57
DEHNguard TT 4-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 4 – DG TT 230 400 900 520 58
N-PE 255 V ac < 1.5 kV
DEHNguard TT FM 4-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 4 1 FC DG TT 230 400 FM 900 550 58
N-PE 255 V ac < 1.5 kV
DEHNguard IT 3-pole, pluggable 500 V ac 15 kA 30 kA < 2 kV < 2.5 kV 100 3 – DG IT 500 900 516 59
600 V ac
DEHNguard IT FM 3-pole, pluggable 500 V ac 15 kA 30 kA < 2 kV < 2.5 kV 100 3 1 FC DG IT 500 FM 900 546 59
600 V ac
DEHNguard TN 2-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 2 – DG TN 230 900 506 61
DEHNguard TN FM 2-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 2 1 FC DG TN 230 FM 900 507 61
DEHNguard TT 2-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 2 – DG TT 230 900 508 62
N-PE 255 V ac < 1.5 kV
DEHNguard TT FM 2-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 2 1 FC DG TT 230 FM 900 509 62
N-PE 255 V ac < 1.5 kV
www.dehn.de 17
Quick Product Choice POWER SUPPLY SYSTEMS
DEHNguard T 1-pole, pluggable 75 V ac 10 kA 40 kA < 350 V < 400 V 125 1 – DG T 75 900 654 67
100 V dc
DEHNguard T 1-pole, pluggable 150 V ac 15 kA 40 kA < 550 V < 700 V 125 1 – DG T 150 900 653 67
200 V dc
DEHNguard T 1-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 1 – DG T 275 900 650 67
350 V dc
DEHNguard T 1-pole, pluggable 320 V ac 20 kA 40 kA < 1.2 kV < 1.5 kV 125 1 – DG T 320 900 652 67
420 V dc
DEHNguard T 1-pole, pluggable 385 V ac 20 kA 40 kA < 1.35 kV < 1.75 kV 125 1 – DG T 385 900 641 67
500 V dc
DEHNguard T 1-pole, pluggable 440 V ac 20 kA 40 kA < 1.7 kV < 2 kV 125 1 – DG T 440 900 655 67
585 V dc
DEHNguard T 1-pole, pluggable 600 V ac 15 kA 30 kA < 2 kV < 2.5 kV 100 1 – DG T 600 900 651 67
600 V dc
DEHNguard T FM 1-pole, pluggable 75 V ac 10 kA 40 kA < 350 V < 400 V 125 1 1 FC DG T 75 FM 900 684 68
100 V dc
DEHNguard T FM 1-pole, pluggable 150 V ac 15 kA 40 kA < 550 V < 700 V 125 1 1 FC DG T 150 FM 900 683 68
200 V dc
DEHNguard T FM 1-pole, pluggable 275 V ac 20 kA 40 kA < 1 kV < 1.25 kV 125 1 1 FC DG T 275 FM 900 680 68
350 V dc
DEHNguard T FM 1-pole, pluggable 320 V ac 20 kA 40 kA < 1.2 kV < 1.5 kV 125 1 1 FC DG T 320 FM 900 682 68
420 V dc
DEHNguard T FM 1-pole, pluggable 385 V ac 20 kA 40 kA < 1.35 kV < 1.75 kV 125 1 1 FC DG T 385 FM 900 691 68
500 V dc
DEHNguard T FM 1-pole, pluggable 440 V ac 20 kA 40 kA < 1.7 kV < 2 kV 125 1 1 FC DG T 440 FM 900 685 68
585 V dc
DEHNguard T FM 1-pole, pluggable 600 V ac 15 kA 30 kA < 2 kV < 2.5 kV 100 1 1 FC DG T 600 FM 900 681 68
600 V dc
VNH NH, size 00 280 V ac 15 kA 30 kA < 1 kV < 1.25 kV – – – V NH00 280 900 261 81
280 V dc
VNH FM NH, size 00 280 V ac 15 kA 30 kA < 1 kV < 1.25 kV – – fault V NH00 280 FM 900 263 82
280 V dc indicator
VNH NH, size 1-3 280 V ac 15 kA 30 kA < 1 kV < 1.25 kV – – – V NH1 3 280 900 265 83
280 V dc
VAV 1-pole 1000 V ac 5 kA 10 kA < 4.2 kV < 4.2 kV 100 3 – VAV 1000 901 000 79
1000 V dc
18 www.dehn.de
POWER SUPPLY SYSTEMS Quick Product Choice
DEHNrail 2-pole, 30 V ac 1 kA 2 kA 16 A < 220 V < 850 V 16//B16 1.5 gn, rd 1 BC DR 24 FML 901 104 98
DIN rail 30 V dc
DEHNrail 2-pole, 60 V ac 1 kA 2 kA 16 A < 350 V < 850 V 16//B16 1.5 gn, rd 1 BC DR 48 FML 901 103 98
DIN rail 60 V dc
DEHNrail 2-pole, 75 V ac 2.5 kA 5 kA 16 A < 500 V < 850 V 16//B16 1.5 gn, rd 1 BC DR 60 FML 901 102 98
DIN rail 75 V dc
DEHNrail 2-pole, 150 V ac 2.5 kA 5 kA 16 A < 700 V < 1.1 kV 16//B16 1.5 gn, rd 1 BC DR 120 FML 901 101 98
DIN rail 150 V dc
DEHNrail 2-pole, 255 V ac 3 kA 5 kA 16 A < 1.25 kV < 1.5 kV 16//B16 1.5 gn, rd 1 BC DR 230 FML 901 100 98
DIN rail 255 V dc
DEHNrail 4-pole, 255 V ac 3 kA 5 kA 16 A < 1.25 V < 1.5 V 16//B16 3 3 x gn, 1 BC DR 230 3N FML 901 130 100
230/3N FML DIN rail 440 V ac 1 x rd
SPS Protector 2-pole, 255 V ac 3 kA 5 kA 3A < 800 V < 1 kV 3//C3 7 gn 1 BC SPS PRO 912 253 103
with filter
DIN rail
DEHNsafe for cable 255 V ac 3 kA 5 kA 16 A < 1.5 kV < 1.5 kV 16//B16 – gn, rd; – DSA 230 LA 924 370 105
ducts, etc. acoustic
DEHNflex M for cable 255 V ac 1.5 kA 3 kA – < 1.25 kV < 1.5 kV 16//B16 – acoustic – DFL M 255 924 396 107
ducts, etc.
DEHNflex A for cable 255 V ac 3 kA 5 kA – < 1.25 kV < 1.5 kV 16//B16 – acoustic – DFL A 255 924 389 108
ducts, etc.
DEHNflex D for cable 255 V ac 3 kA 5 kA 16 A < 1.25 kV < 1.5 kV 16//B16 – acoustic – DFL D 255 924 395 109
ducts, for
through-wiring
STC Module for socket 255 V ac 2.5 kA 5 kA – < 1.25 kV < 1.5 kV 16//B16 – acoustic – STC 230 924 350 111
outlets
VC 280/2 2-pole, for 280 V ac 3 kA 5 kA – < 1.25 kV < 1.5 kV 16//B16 – – 1 BC VC 280 2 900 471 113
installation
into devices
S Protector socket outlet 255 V ac 2.5 kA 5 kA 16 A < 1.5 kV < 1.5 kV 16//B16 – gn, rd – S PRO 909 821 115
adapter
SF Protector socket outlet 255 V ac 2.5 kA 5 kA 16 A < 1.5 kV < 1.5 kV 16//B16 – gn, rd – SF PRO 909 820 116
adapter
with filter
SFL Protector multiple 255 V ac 3 kA 5 kA 16 A < 1.5 kV < 1.5 kV 16//B16 – gn, rd – SFL PRO 912 260 118
socket outlet
with filter
NSM Protector surge 255 V ac 3 kA 5 kA 16 A < 1.25 kV < 1.5 kV 16//B16 – gn, rd – NSM PRO TW * 924 335 120
protective
socket outlet
www.dehn.de 19
Easy Choice POWER SUPPLY SYSTEMS
L1 L2 L3 N PE
Socket Outlet
ÜS-Schutz
DEHNflex
cable leng 1x DSA 230 LA Part No. 924 370 1x DFL M 255 Part No. 924 396 1x STC 230 Part No. 924 350
th ≥ 5 m
for cable ducts for flush-mounted systems for existing socket outlets
indication of interference
16 A
Subdistribution Board
PE PE
L1 L2 L3 N L1 L2 L3 N
1 1
125 A 125 A
H1 H2 H3
DEHNbloc DEHNbloc DEHNbloc DEHNbloc Maxi DEHNbloc Maxi DEHNbloc Maxi ®
DB 1 255 H DB 1 255 H DB 1 255 H DBM 1 255 L DBM 1 255 L DBM 1 255 L DEHNventil DV TNC 255
N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN PEN
D D D D D D - only for DEHNsignal -
S S S S S S
I I I I I I - nur für DEHNsignal -
! ! ! ! ! !
3x DB 1 255 H Part No. 900 222 3x DBM 1 255 L Part No. 900 026 1x DV TNC 255 Part No. 900 373
1x MVS 1 8 Part No. 900 611 1x MVS 1 8 Part No. 900 611 also available as
Alternative: DV TNS 255 variant Part No. 900 374
EB
3x DBM 1 255 Part No. 900 025
1x MVS 1 8 Part No. 900 611 1) only required, if a fuse of the same or a
lower nominal value is not already provided
in the upstream power supply.
TN-Systems: Example: Office Building – Separation of the PEN in the main distribution board
20 www.dehn.de
POWER SUPPLY SYSTEMS Easy Choice
L1 L2 L3 N PE
Überspannungsschutz
Socket Outlet
S-PROTECTOR
230V~ Defect
0
1
SFL-Protector
cable leng 1x NSM PRO EW Part No. 924 342 1x SF PRO Part No. 909 820 1x SFL PRO Part No. 912 260
th ≥ 5 m
1x S PRO Part No. 909 821
indication of interference
16 A
Subdistribution Board
PEN PEN
L1 L2 L3 L1 L2 L3
1 1
125 A 125 A
H1 H2 H3
DEHNbloc DEHNbloc DEHNbloc DEHNbloc Maxi DEHNbloc Maxi DEHNbloc Maxi ®
DB 1 255 H DB 1 255 H DB 1 255 H DBM 1 255 L DBM 1 255 L DBM 1 255 L DEHNventil DV TNC 255
N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN PEN
D D D D D D - only for DEHNsignal -
S S S S S S
I I I I I I - nur für DEHNsignal -
! ! ! ! ! !
3x DB 1 255 H Part No. 900 222 3x DBM 1 255 L Part No. 900 026 1x DV TNC 255 Part No. 900 373
1x MVS 1 8 Part No. 900 611 1x MVS 1 8 Part No. 900 611 also available as
Alternative: DV TNS 255 variant Part No. 900 374
EB
3x DBM 1 255 Part No. 900 025
1x MVS 1 8 Part No. 900 611 1) only required, if a fuse of the same or a
lower nominal value is not already provided
in the upstream power supply.
TN-Systems: Example: Office Building – Separation of the PEN in the subdistribution board
www.dehn.de 21
Easy Choice POWER SUPPLY SYSTEMS
1
L1 L2 L3 N PE 16 A
3 A1 16 A also 16 A 1
Switchgear / Machine
possible
without NF10
Mains filter
1 2
L L N N
IN N L1 L2 L3
SPS-Protector
DEHNrail
PLC electronic
PLC DR ... FML
10 A N L1 L2 L3
cable leng
th ≥ 5 m
1x SPS PRO Part No. 912 253 1x DR 230 FML Part No. 901 100 1x DR 230 3N FML Part No. 901 130
1x NF 10 Part No. 912 254
16 A
Subdistribution Board
PEN
2 L1 L2 L3
1
125 A
3x V NH00 280 Part No. 900 261 1x DG TNC 230 400 Part No. 900 510
or with remote signalling contact:
1x DG TNC 230 400 FM Part No. 900 540
indication of
interference
H1 H2 H3
DEHNbloc Maxi DEHNbloc Maxi DEHNbloc Maxi DEHNsignal DEHNsignal
DBM 1 255 L DBM 1 255 L DBM 1 255 L DEHNventil® DV TNC 255
® ® ® DSI DBM DSI DV
DEHNbloc NH DEHNbloc NH DEHNbloc NH
DB NH00 255 DB NH00 255 DB NH00 255
3x DB NH00 255 Part No. 900 260 3x DBM 1 255 L Part No. 900 026 1x DV TNC 255 Part No. 900 373
Alternative: 1x MVS 1 8 Part No. 900 611 also available as
EB
3x DB 1 255 H Part No. 900 222 Alternative: DV TNS 255 variant Part No. 900 374
1x MVS 1 8 Part No. 900 611 3x DBM 1 255 Part No. 900 025 Option:
1) only required, if a fuse of the same or a lower nominal 1x MVS 1 8 Part No. 900 611 1x DSI DV Art.-Nr. 910 620
value is not already provided in the upstream power Option:
supply 1x DSI DBM Art.-Nr. 910 623
2)without separate backup fuse in case of earth and
short-circuit-proof wiring
22 www.dehn.de
POWER SUPPLY SYSTEMS Easy Choice
L1 L2 L3 N PE
indication of
interference
Heating Control
Socket Outlet
1 2
S-PROTECTOR
DEHNrail
DR ... FML 230V~ Defect
heating
3 4
1x DR 230 FML Part No. 901 100 1x S PRO Part No. 909 821
1x SF PRO Part No. 909 820
16 A 1x SFL PRO Part No. 912 260
DEHNsignal DSI DV
Subdistribution Board
Remote signalling module
with floating changeover contact and optical fibre
Note:
L1 L1' L2 L2' L3 L3'
As an alternative, surge arresters
125 A
H1
L1 L2 L3 N PE
indication of
interference
Heating Control
Socket Outlets
1 2
S-PROTECTOR
DEHNrail
DR ... FML 230V~ Defect
heating
3 4
1x DR 230 FML Part No. 901 100 1x S PRO Part No. 909 821
16 A 1x SF PRO Part No. 909 820
1x SFL PRO Part No. 912 260
RCD
DEHNsignal DSI DV
Subdistribution Board
Note:
As an alternative, surge arresters
125 A L1 L1' L2 L2' L3 L3' N N' (e.g. DG TT 230 400 Part No. 900 520)
H1
®
DEHNventil DV TT 255
H2 H3
can also be applied, if no
− lightning protection system
EB
− electrical power supply via the service entry mast
- only for DEHNsignal -
PE
− antenna on the roof
- nur für DEHNsignal -
is available.
www.dehn.de 23
Easy Choice POWER SUPPLY SYSTEMS
L1 L2 L3 N PE
Socket Outlet
ÜS-Schutz
DEHNflex
cable leng 1x DSA 230 LA Part No. 924 370 1x DFL M 255 Part No. 924 396 1x STC 230 Part No. 924 350
th ≥ 5 m
for cable ducts for flush-mounted systems for existing socket outlets
indication of
interference
16 A
Subdistribution Board
RCD
PE PE
L1 L2 L3 N L1 L2 L3 N
1 1
125 A 125 A
PE
N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N/PEN N
D D D D D D D
S S S S S S S
I I I I I I I
! ! !
! ! ! !
3x DB 1 255 H Part No. 900 222 3x DBM 1 255 L Part No. 900 026 1x DV TT 255 Part No. 900 375
1x DK 35 Part No. 900 699 1x DGPM 255 Part No. 900 055
1x DGP BN 255 Part No. 900 132 1x MVS 1 8 Part No. 900 611
EB
1x MVS 1 8 Part No. 900 611 Alternative: 1) only required, if a fuse of the same or a
3x DBM 1 255 Part No. 900 025 lower nominal value is not already provided
1x DGPM 255 Part No. 900 055 in the upstream power supply
1x MVS 1 8 Part No. 900 611
24 www.dehn.de
POWER SUPPLY SYSTEMS Easy Choice
1
L1 L2 L3 N PE 16 A
16 A also
1
possible 16 A
3 A1 without NF10
Switchgear / Machine
mains filter
1 2
L L N N
IN N L1 L2 L3
SPS-Protector
DEHNrail
PLC electronic
PLC DR ... FML
10 A N L1 L2 L3
cable leng
th ≥ 5 m
1x SPS PRO Part No. 912 253 1x DR 230 FML Part No. 901 100 1x DR 230 3N FML Part No. 901 130
1x NF 10 Part No. 912 254
16 A
indication of
interference
Subdistribution Board
RCD
PE PE
L1 L2 L3 N L1 L2 L3 N
1
125 A 125 A 1
cable leng
th ≥ 15 m
with floating changeover contact and with floating changeover contact and optical
optical fibre connection fibre connection
DEHNbridge according to nominal current
4x DBR 35 Part No. 900 121 DSI DV Part No. 910 620 DSI DV Part No. 910 620
4x DBR 63 Part No. 900 122
315 A 1
indication of
interference
500 A 1 315 A 1
14 11 12
L1 L1' L2 L2' L3 L3' N N'
H1 H2 H3
® ® ® ®
DEHNsignal ®
DEHNventil DV TT 255
DEHNbloc NH DEHNbloc NH DEHNbloc NH DEHNbloc NH 14 11 12 L L' L L' L L' N N' DSI DV
DB NH00 255 DB NH00 255 DB NH00 255 DB NH00 255
3x DB NH00 255 Part No. 900 260 3x DBM 1 255 L Part No. 900 026 1x DV TT 255 Part No. 900 375
1x DGP B NH00 N 255 Part No. 900 269 1x DGPM 255 Part No. 900 055 Option:
EB
Alternative: 1x MVS 1 8 Part No. 900 611 1x DSI DV Part No. 900 620
Alternative:
3x DB 1 255 H Part No. 900 222 3x DBM 1 255 Part No. 900 025
1x DK 35 Part No. 900 699 1x DGPM 255 Part No. 900 055
1x DGP BN 255 Part No. 900 132 1x MVS 1 8 Part No. 900 611 1) only required, if a fuse of the same or a
Option: lower nominal value is not already provided
1x MVS 1 4 Part No. 900 610 in the upstream power supply.
1x DSI DV Part No. 900 620
www.dehn.de 25
Information about Standards POWER SUPPLY SYSTEMS
Table 1: Types of SPDs for power supply systems according to E DIN VDE 0675-6:1989-11 and E DIN VDE 0675-6/A1:1996-03
26 www.dehn.de
POWER SUPPLY SYSTEMS DEHNventil® TNC / ... TNS / ... TT
COMBINED SPDS – TYPE 1 Multipole Combined Lightning Current
SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
and Surge Arrester
SPD Class I according to IEC 61643-1;
• Prewired combined spark gap based
arrester
• Max. follow current limitation thanks to
RADAX Flow technology
• No tripping of 32/35 A gL/gG fuses up
to short circuit currents of 50 kArms
• Lightning current discharge capacity up
to 100 kA (10/350)
• Allows protection of terminal
equipment
• Provides max. system availability
• Replaces up to 12 components of a
For protection of low voltage consumer’s installations against surges,
conventional application
even at direct lightning strikes. For use according to the lightning
protection zones concept at boundaries 0A – 2.
DV TNC 255: Combined lightning current and surge arrester for TN-C systems
DV TNS 255: Combined lightning current and surge arrester for TN(C)-S systems
DV TT 255: Combined lightning current and surge arrester for TT systems
The multipole combined lightning current and surge arresters of the Using the double terminals of DEHNventil devices, which are suitable for
DEHNventil TNC ... / ... TNS / ... TT product family offer an “all-in-one solu- all types of conductors, allows a serial connection up to nominal currents
tion”, i.e. lightning equipotential bonding and surge protection in one of 125 A in a space- and cost-saving way, as preferred by standard IEC
device. 60364-5-53. The multifunctional terminal is suitable for simultaneous
Energy coordination with downstream Red/Line surge protective devices connection of conductors and busbars. This allows an easy wiring with
in low voltage consumer’s installations is ensured without additional other DIN rail mounted devices.
cable lengths or decoupling inductances. For connection with further DIN rail mounted devices, busbars type
In compact electrical installations and a short distance between MVS 3 8 6 and MVS 4 11 8 can be used.
DEHNventil and the consumers ( ≤ 5 m), DEHNventil devices alone can DEHNventil devices can be chosen easily upon the system configuration
protect the terminal equipment. of the existing low voltage consumer’s installation in connection with the
Especially the small dimension of the combined arresters allows multiple type description of the devices.
possibilities for the installation of switchgears or distribution boards. A high availability of the electrical consumer’s installation to be protected
Using encapsulated non-exhausting cree- is achieved by the patented RADAX Flow technology for follow current
page discharge spark gaps, no additional limitation and follow current extinction. Even at great short circuit cur-
safety distances need to be observed. rents up to 50 kArms , arising mains follow currents are reduced conside-
For expanded electrical installations, addi- rably to ensure the selectivity to small fuse values (e.g. 32 A gL/gG), i.e.
tional surge protective devices have to be upstream fuses do not trip upon arising mains follow currents.
provided in downstream distribution For indicating the presence of the three line-to-line voltages and readi-
boards and directly upstream of the termi- ness for operation of DEHNventil on site, the devices have an integrated
nal equipment, according to the procee- visual indication of the operating voltage
ding in the lightning protection zones con- for each outer conductor. Furthermore, the
cept. readiness for operation of the device and
the existence of operating voltages can be
signalised to a superior control system via
the remote signalling module DEHNsignal.
Accessory Part:
DEHNsignal Remote Signalling
Module
www.dehn.de 27
DEHNventil® TNC / ... TNS / ... TT POWER SUPPLY SYSTEMS
900 373 DV TNC
255
DV TNC 255
DEHNventil TNC, 3-pole 900 373
PEN
DV TNC 255: Combined lightning current and surge arrester for TN-C systems
DV TNC 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Nominal ac voltage UN 230 / 400 V
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) [L1+L2+L3-PEN] Iimp 75 kA
Lightning impulse current (10/350) [L-PEN] Iimp 25 kA
Nominal discharge current (8/20) In 25 / 75 kA
Voltage protection level UP ≤ 1.5 kV
Follow current extinguishing capability ac Ifi 50 kArms
Follow current extinction/Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ≤ 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG
Max. backup fuse (L) at IK > 50 kArms 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG
TOV voltage UT 335 V / 5 sec.
Operating temperature range (parallel wiring) TUP -40°C...+80°C
Operating temperature range (through-wiring) TUS -40°C...+60°C
Operation indicator green light
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, PEN, E) min. 10 mm2 solid / flexible
Cross-sectional area (L1, L2, L3, PEN) max. 50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L1´, L2´, L3´, E) max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 6 mods., DIN 43880
Approvals, Certifications KEMA, VDE
Ordering information
Type DV TNC 255
Part No. 900 373
Packing unit 1 pc(s)
28 www.dehn.de
POWER SUPPLY SYSTEMS DEHNventil® TNC / ... TNS / ... TT
00 374 DV TNS
55
PE
DV TNS 255: Combined lightning current and surge arrester for TN(C)-S systems
DV TNS 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Nominal ac voltage UN 230 / 400 V
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) [L1+L2+L3+N-PE] Iimp 100 kA
Lightning impulse current (10/350) [L,N-PE] Iimp 25 kA
Nominal discharge current (8/20) In 25 / 100 kA
Voltage protection level [L-PE] UP ≤ 1.5 kV
Voltage protection level [N-PE] UP ≤ 1.5 kV
Follow current extinguishing capability ac Ifi 50 kArms
Follow current extinction/Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ≤ 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG
Max. backup fuse (L) at IK > 50 kArms 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG
TOV voltage [L-N] UT 335 V / 5 sec.
Operating temperature range (parallel wiring) TUP -40°C...+80°C
Operating temperature range (through-wiring) TUS -40°C...+60°C
Operation indicator green light
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE, E) min. 10 mm2 solid / flexible
Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L1´, L2´, L3´, N´, E) max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 8 mods., DIN 43880
Approvals, Certifications KEMA, VDE
Ordering information
Type DV TNS 255
Part No. 900 374
Packing unit 1 pc(s)
www.dehn.de 29
DEHNventil® TNC / ... TNS / ... TT POWER SUPPLY SYSTEMS
900 375 DV TT 255
DV TT 255
DEHNventil TT, 4-pole 900 375
PE
DV TT 255: Combined lightning current and surge arrester for TT- and TN(C)-S systems
DV TT 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Nominal ac voltage UN 230 / 400 V
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) [L1+L2+L3+N-PE] Iimp 100 kA
Lightning impulse current (10/350) [L-N] Iimp 25 kA
Lightning impulse current (10/350) [N-PE] Iimp 100 kA
Nominal discharge current (8/20) In 25 / 100 kA
Voltage protection level [L-N] UP ≤ 1.5 kV
Voltage protection level [N-PE] UP ≤ 1.5 kV
Follow current extinguishing capability [L-N] ac Ifi 50 kArms
Follow current extinguishing capability [N-PE] ac Ifi 100 Arms
Follow current extinction/Selectivity no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ≤ 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG
Max. backup fuse (L) at IK > 50 kArms 200 A gL/gG
Max. backup fuse (L-L´) 125 A gL/gG
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [N-PE] UT 1200 V / 200 ms
Operating temperature range (parallel wiring) TUP -40°C...+80°C
Operating temperature range (through-wiring) TUS -40°C...+60°C
Operation indicator green light
Cross-sectional area (L1, L1´, L2, L2´, L3, L3´, N, N´, PE, E) min. 10 mm2 solid / flexible
Cross-sectional area (L1, L2, L3, N, PE) max. 50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L1´, L2´, L3´, N´, E) max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 8 mods., DIN 43880
Approvals, Certifications KEMA, VDE
Ordering information
Type DV TT 255
Part No. 900 375
Packing unit 1 pc(s)
30 www.dehn.de
POWER SUPPLY SYSTEMS DEHNventil 2P
COMBINED SPDS – TYPE 1 Two-pole Combined Lightning Current
SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
and Surge Arrester
SPD Class I according to IEC 61643-1;
• Prewired combined spark-gap based
arrester
• Max. follow current limitation thanks to
RADAX Flow technology
• No tripping of 32/35 A gL/gG fuses up
to short circuit currents of 50 kArms
• Lightning current discharge capacity
50 kA (10/350)
• Allows protection of terminal
equipment
• Provides max. system availability
• 2-pole unit for ac voltage systems
For protection of low voltage consumer’s installations against surges, • Replaces up to 6 single components of
even at direct lightning strikes. For use according to the lightning pro-
tection zones concept at boundaries 0A – 2.
a conventional application
DV 2P TN 255: Combined lightning current and surge
arrester for single-phase TN systems
DV 2P TT 255: Combined lightning current and surge
arrester for single-phase TT systems
The multipole combined lightning Using the double terminals of DEHNventil devices, which are suitable for
current and surge arresters of the all types of conductors, allows a serial connection up to nominal currents
DEHNventil 2P product family offer of 125 A in a space- and cost-saving way, as preferred by standard
an “all-in-one solution”, i.e. light- IEC 60364-5-53.
ning equipotential bonding and DEHNventil devices can be chosen easily upon the system configuration
surge protection in one device. of the existing low voltage consumer’s installation in connection with the
Energy coordination with downst- type description of the devices.
ream Red/Line surge protective A high availability of the electrical consumer’s installation to be protected
devices in low voltage consumer’s is achieved by the patented RADAX Flow technology for follow current
installations is ensured without additional cable lengths or decoupling limitation and follow current extinction. Even at great short circuit cur-
inductances. rents up to 50 kArms , arising mains follow currents are reduced conside-
In compact electrical installations and a short distance between rably to ensure the selectivity to small fuse values (e.g. 32 A gL/gG),
DEHNventil and the consumers ( ≤ 5 m), DEHNventil 2P devices alone can i.e. upstream fuses do not trip upon arising mains follow currents.
protect the terminal equipment. For indicating the presence of phase voltages and readiness for operation
Especially the small dimension of the combined arresters allows multiple of DEHNventil 2P on site, the devices have an integrated indication of
possibilities for the installation of switchgears or distribution boards. operating voltages. Furthermore, the readiness for operation of the devi-
Using encapsulated non-exhausting creepage discharge spark gaps, no ce and the existence of operating voltages can be signalised to a superior
additional safety distances need to be observed. control system via the remote signalling module DEHNsignal DSI DV 2P.
For expanded electrical installations, additional surge protective devices
have to be provided in downstream distribution boards and directly
upstream of the terminal equipment, according to the proceeding in the
lightning protection zones concept.
www.dehn.de 31
DEHNventil 2P POWER SUPPLY SYSTEMS
900 371 DV 2P TN
255
ICE H ICE
PE
DV 2 P TN 255: Combined lightning current and surge arrester for single-phase TN systems
DV 2P TN 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Nominal ac voltage UN 230 V
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) [L+N-PE] Iimp 50 kA
Lightning impulse current (10/350) [L,N-PE] Iimp 25 kA
Nominal discharge current (8/20) In 25 / 50 kA
Voltage protection level [L-PE] UP ≤ 1.5 kV
Voltage protection level [N-PE] UP ≤ 1.5 kV
Follow current extinguishing capability ac 50 kArms
Follow current extinction/Selectivity No tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ≤ 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG
Max. backup fuse (L) at IK > 50 kArms 200 A gL/gG
Max. backup fuse (l-L´) 125 A gL/gG
TOV voltage [L-N] UT 335 V / 5 sec.
Operating temperature range (parallel wiring) TUP -40°C...+80°C
Operating temperature range (through-wiring) TUS -40°C...+60°C
Cross-sectional area (L, L´, N, N´, PE, E) min. 10 mm2 solid / flexible
Cross-sectional area (L, N, PE) max. 50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L´, N´, E) max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 6 mods., DIN 43880
Certifications, Approvals KEMA, VDE
Ordering information
Type DV 2P TN 255
Part No. 900 371
Packing unit 1 pc(s)
DEHNsignal DV 2 P
DSI DV 2P: Remote signalling module for two-pole SPDs with 2-wire
DSI DV 2P interface “DSI DV 2P” (e.g. DEHNventil 2P TN / ... TT)
PU Part
Type pc(s) No.
DSI DV 2P 1 910 621
32 www.dehn.de
POWER SUPPLY SYSTEMS DEHNventil 2P
00 370 DV 2P TT
55
DV 2P TT 255
DEHNventil TT, 2-pole 900 370
L L' N N'
ICE H ICE
PE
DV 2P TT 255: Combined lightning current and surge arrester for single-phase TT- and TN systems
DV 2P TT 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Nominal ac voltage UN 230 V
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) [L+N-PE] Iimp 50 kA
Lightning impulse current (10/350) [L-N] Iimp 25 kA
Lightning impulse current (10/350) [N-PE] Iimp 50 kA
Nominal discharge current (8/20) In 25 / 50 kA
Voltage protection level [L-N] UP ≤ 1.5 kV
Voltage protection level [N-PE] UP ≤ 1.5 kV
Follow current extinguishing capability [L-N] ac Ifi 50 kArms
Follow current extinguishing capability [N-PE] ac Ifi 100 Arms
Follow current extinction/Selectivity No tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ≤ 100 ns
Max. backup fuse (L) up to IK = 50 kArms 315 A gL/gG
Max. backup fuse (L) at IK > 50 kArms 200 A gL/gG
Max. backup fuse (l-L´) 125 A gL/gG
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [N-PE] UT 1200 V / 200 ms
Operating temperature range (parallel wiring) TUP -40°C...+80°C
Operating temperature range (through-wiring) TUS -40°C...+60°C
Cross-sectional area (L, L´, N, N´, PE, E) min. 10 mm2 solid / flexible
Cross-sectional area (L, N, PE) max. 50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L´, N´, E) max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94-V-0
Degree of protection IP 20
Dimension 8 mods., DIN 43880
Certifications, Approvals KEMA, VDE
Ordering information
Type DV 2P TT 255
Part No. 900 370
Packing unit 1 pc(s)
DSI DV 2P: Remote signalling module for two-pole SPDs with 2-wire
interface “DSI DV 2P” (e.g. DEHNventil 2P TN / ... TT)
DSI DV 2P
PU Part
Type pc(s) No.
DSI DV 2P 1 910 621
www.dehn.de 33
DEHNsignal POWER SUPPLY SYSTEMS
Remote Signalling ACCESSORY FOR TYPE 1 – ARRESTER
and Reception Module EN 61010-1; EN 61010-1/A2;
The remote signalling modules of the DEHNsignal product family do the luating the signal. The optical
remote signalling of complex surge protective devices of the Red/Line pro- fibre connection between remote
duct range with 4-wire interface “DEHNsignal DV” or 2-wire interface signalling and reception module
“DEHNsignal DV 2P”. Supplied by the surge protective devices to be con- can be established easily thanks
trolled, DEHNsignal remote signalling devices provide the remote signal to the simple plug-in system for
as a floating changeover contact and an optical fibre output. optical fibres integrated in all
An evaluable group signal is generated out of the signals of individual DEHNsignal devices. The recepti-
protective circuits. This allows a continuous telemonitoring of the devices. on module in DEHNsignal E DV
As also phase failures are registered in addition to the function of the transforms the optical fibre signal
surge protection, the possibilities for using DEHNsignal devices can be into an electrical signal. The user
amplified. Whenever high safety and availability requirements have to be is then provided with a floating
fulfilled, DEHNsignal devices always provide the perfect solution. If the changeover contact like in the
optical fibre connection is chosen for the use of a DEHNsignal remote sig- DEHNsignal remote signalling module. The green light of DEHNsignal E DV
nalling module instead of the floating changeover contact, the correspon- signalises the readiness for operation of the reception module and the
dingly adapted reception module DEHNsignal E DV has to be used for eva- functional readiness of the surge protective device to be controlled. With
the optical fibre transmission system, the remote signalling of surge pro-
tective devices can be realised even for controlling highly sensitive facili-
ties (e.g. explosive areas).
34 www.dehn.de
POWER SUPPLY SYSTEMS DEHNsignal
10 620 DSI DV
DSI DV
DEHNsignal 910 620
1
optical fibre
2 12
& 14
3 evaluation
4 11
Note:
Change of contacts at present
mains voltage and functioning
surge protective device!
DSI DV
Version for three-phase ac systems
Power input P 500 mW
Operating temperature range -40°C...+80°C
Connection of the module only at the provided terminal of the surge protective device
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 1.5 mods., DIN 43880
Type of remote signalling contact floating changeover contact
Switching capacity ac 250 V / 0.5 A
Switching capacity dc 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area min. 0.5 mm2 solid / flexible; max. 4 mm2 solid / flexible
Optical fibre interface 660 nm
Reach with LWL DSI and reception module DEHNsignal DSI E DV (Part No. 910630) max. 100 m
Test standards EN 61010-1:1993; EN 61010-1/A2:1995
Ordering information
Type DSI DV
Part No. 910 620
Packing unit 1 pc(s)
www.dehn.de 35
DEHNsignal POWER SUPPLY SYSTEMS
910 621 DSI DV 2P
DSI DV 2P
DEHNsignal, 2-pole 910 621
12
optical fibre
1 14
2 11
Note:
Change of contacts at present
mains voltage and functioning
surge protective device!
DSI DV 2P: Remote signalling module for two-pole SPDs with 2-wire interface “DSI DV 2P”
(e.g. DEHNventil 2P TN / ... TT)
DSI DV 2P
Version for single-phase ac systems
Power input P 400 mW
Operating temperature range -40°C...+80°C
Connection of the module only at the provided terminal of the surge protective device
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 1.5 mods., DIN 43880
Type of remote signalling contact floating changeover contact
Switching capacity ac 250 V / 0.5 A
Switching capacity dc 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area min. 0.5 mm2 solid / flexible; max. 4 mm2 solid / flexible
Optical fibre interface 660 nm
Reach with LWL DSI and reception module DEHNsignal DSI E DV (Part No. 910630) max. 100 m
Test standards EN 61010-1:1993; EN 61010-1/A2:1995
Ordering information
Type DSI DV 2P
Part No. 910 621
Packing unit 1 pc(s)
36 www.dehn.de
POWER SUPPLY SYSTEMS DEHNsignal
10 623 DSI DBM
DSI DBM
DEHNsignal DB M Remote Signalling Module 910 623
1
optical fibre
2 12
& 14
3 evaluation
11
Note:
Change of contacts at present
mains voltage and functioning
surge protective device!
DSI DBM: Remote signalling module for single-pole SPDs with single-wire interface “DSI DV” in
TN-C systems (e.g. DEHNbloc Maxi)
DSI DBM
Version for three-phase ac systems
Power input P 500 mW
Operating temperature range -40°C...+80°C
Connection of the module only at the provided terminal of the surge protective device
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 1.5 mods., DIN 43880
Type of remote signalling contact floating changeover contact
Switching capacity ac 250 V / 0.5 A
Switching capacity dc 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area min. 0.5 mm2 solid / flexible; max. 4 mm2 solid / flexible
Optical fibre interface 660 nm
Reach with LWL DSI and reception module DEHNsignal DSI E DV (Part No. 910630) max. 100 m
Test standards EN 61010-1:1993; EN 61010-1/A2:1995
Ordering information
Type DSI DBM
Part No. 910 623
Packing unit 1 pc(s)
www.dehn.de 37
DEHNsignal POWER SUPPLY SYSTEMS
910 630 DSI E DV
L/N DSI E DV
DEHNsignal Reception Module 910 630
optical fibre
signal
12
evaluation
14
N/L 11
Note:
Change of contacts at present
main voltage and optical fibre
signal!
DSI E DV: Reception module for optical fibre transmission of DEHNsignal remote signalling
modules
DSI E DV
Version optical fibre connection to DEHNsignal remote signalling modules
Supply voltage ac UN 230 V
Power input P 400 mW
Backup fuse (only required, if not already provided in mains) 16 A gL/gG or C 16 A
Operating temperature range -40°C...+80°C
Signal input via optical fibre plug-in system (LWL ST DSI)
Indication green LED: reception / operation
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 1.5 mods., DIN 43880
Type of remote signalling contact floating changeover contact
Switching capacity ac 250 V / 0.5 A
Switching capacity dc 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area min. 0.5 mm2 solid / flexible; max. 4 mm2 solid / flexible
Test standards EN 61010-1:1993 and EN 61010-1/A2:1995
Ordering information
Type DSI E DV
Part No. 910 630
Packing unit 1 pc(s)
LWL ST DSI
LWL DSI Optical
Synthetic optical fibre Plug for synthetic optical fibre
LWL ST DSI Plug for
38 www.dehn.de
POWER SUPPLY SYSTEMS DEHNbloc® Maxi
LIGHTNING CURRENT ARRESTERS – TYPE 1 Coordinated Lightning Current Arrester
SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
SPD Class I according to IEC 61643-1;
• Encapsulated RADAX Flow spark gap
with high follow current limitation
• No tripping of 32/35 A gL/gG fuses
• Coordinated directly with DEHNguard
surge protective device without addi-
tional cable length or decoupling coil
• Low protection level
• Allows installation upstream of supply
meters thanks to its high insulation
resistance
• Double terminals for serial connection
For protection of low voltage consumer’s installations against surges • Multifunctional connection for
even at direct lightning strikes. For use in the lightning protection zones
concept at boundaries 0A – 1.
conductors and busbars
• Available with operating voltage
indication
DBM 1 255: Coordinated, single-pole lightning current
arrester with high follow current limitation
DBM 1 255 L:Coordinated, single-pole lightning current
arrester with high follow current limitation
and operating voltage indication
The coordinated lightning current arresters of the DEHNbloc Maxi family Using the double terminals
adjust themselves to every kind of application. Whether being used in an of DEHNbloc Maxi devices,
exposed position or in rough industrial applications: DEHNbloc Maxi which are suitable for all
always offers the right solution. The single-pole devices are originally types of conductors, allows
coordinated with the approved DEHNguard surge arresters of the to realise a serial connecti-
Red/Line family. Independent from cable lengths and without requiring on up to nominal currents
additional decoupling coils, the surge protection concept can be adapted of 125 A in a space- and
individually to all conditions at the installation. cost-saving way, as prefer-
red by standard IEC 60364-
DEHNbloc Maxi devices provide the patented technologies of an encap- 5-53. The multifunctional
sulated creepage discharge spark gap and RADAX-Flow follow current terminal is suitable for
limitation. Special safety distances from busbars or equipment belong to simultaneous connection of
the past as well as tripped backup fuses due to lacking selectivity bet- conductors and a busbars.
ween the protective device and overcurrent protection. This ensures the This allows an easy wiring
highest possible system availability. to other DIN rail mounted
devices.
For indicating the presence of phase voltages and readiness for operation
on site, DEHNbloc Maxi Type DBM 1 255 L provides an integrated opera-
ting voltage indication. Optionally, DEHNbloc Maxi devices can also be
used for signalling the readiness for opera-
tion of the equipment as well as the pre-
sence of operating voltage to a superior
control system via remote signalling con-
tact.
www.dehn.de 39
DEHNbloc® Maxi POWER SUPPLY SYSTEMS
900 025 DBM 1
255
N/PEN N/PEN
Basic circuit diagram DBM 1 255 L Dimension drawing DBM 1 255 (L)
DBM 1 255: Coordinated lightning current arrester with high follow current limitation.
DBM 1 255 L: Coordinated lightning current arrester with high follow current limitation and
operating voltage indication.
Ordering information
Type DBM 1 255 DBM 1 255 L
Part No. 900 025 900 026
Packing unit 1 pc(s) 1 pc(s)
Accessory Part for DEHNbloc® Maxi Accessory Part for DEHNbloc® Maxi
910 620 DSI DV
DEHNsignal DV 910 623 DSI DBM
DEHNsignal DBM
DSI DV: Remote signalling module for DSI DBM: Remote signalling module for single-pole SPDs with single-
DSI DBM
DSI DV
DEHNsignal DB M Remote Signalling Module 910 623
wire interface “DSI DV” in TN-C systems (e.g. DEHNbloc Maxi)
DEHNsignal 910 620
– multipole SPDs with 4-wire interface “DSI DV”
(e.g. DEHNventil TNC / ... TNS / ... TT) PU Part
Type pc(s) No.
– single-pole SPDs with single-wire interface “DSI DV” in TN-S and DSI DBM 1 910 623
TT systems (e.g. DEHNbloc Maxi)
PU Part
Type pc(s) No.
DSI DV 1 910 620
40 www.dehn.de
POWER SUPPLY SYSTEMS DEHNbloc®
LIGHTNING CURRENT ARRESTERS – TYPE 1 Lightning Current Arrester
SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
SPD Class I according to IEC 61643-1;
• Encapsulated, non-exhausting creepage
discharge spark gaps
• “Wavebreaker function” allows energy
coordination with downstream varistor-
based surge arresters, e.g. DEHNguard
and/or the equipment to be protected
• Installation also possible upstream of
supply meters thanks to its high
insulation resistance
• Multifunctional connection for
conductors and busbars
• 1- and 3-pole unit (according to net-
work configuration, lightning impulse
For protection of low voltage consumer’s installations against surges currents of up to 100 kA)
even at direct lightning strikes. For use in lightning protection zones
concept at boundaries 0A – 1.
DB 1 255 H: Single-pole lightning current arrester with high follow current limitation
DB 1 ...: inued Single-pole lightning current arrester with high discharge capacity
discont
DB 3 ...: 3-pole lightning current arrester with high discharge capacity
DB NH00 ...: Lightning current arrester in NH 00 design with high discharge capacity
The patented spark gaps of the DEHNbloc devices allow a compact Following the requirements
structure of a low voltage distribution board. DEHNbloc lightning current of users for a high system
arresters require no safety distances from busbars or other equipment and availability, DEHNbloc 1
no special flameproof enclosures. With a discharge capacity of 50 kA 255 H has been developed.
(10/350) per pole the DB 1 ... and/or DB 3 ... devices fulfil the highest With a follow current extin-
requirements made on such kinds of devices by national and internatio- guishing capability of
nal lightning protection standards. The distinct “wavebreaker function” of 50 kArms it safely extinguis-
the arresters allows a simple energy coordination with downstream surge hes mains follow currents
protective devices of the Red/Line product family. The leakage current free of 50 Hz without causing a
spark gap based arresters feature a high sturdiness and durability. With system interruption due to
these characteristics, they are very suitable for use in areas upstream of tripping upstream overcur-
supply meters according to national regulations (e.g. Germany: VDN gui- rent protection devices. The
delines). Coming up to the commonly used TN-C systems, there is, apart patented RADAX-Flow fol-
from the universal single-pole type, the 3-pole DEHNbloc 3, that forms a low current limitation
prewired unit for the conductors L1, L2, L3 and PEN. allows a disconnection DB NH00 255 in a busbar terminal field
selectivity even for small- of a meter installation
sized installation fuses.
www.dehn.de 41
DEHNbloc® POWER SUPPLY SYSTEMS
900 222 DB 1 255
H
DB 1 255 H
DEHNbloc/1 900 222
L L'
N/PEN N/PEN
DB 1 255 H: Single-pole lightning current arrester with high follow current limitation
DB 1 255 H
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) Iimp 25 kA
Nominal discharge current (8/20) In 25 kA
Voltage protection level UP ≤ 4 kV
Follow current extinguishing capability ac Ifi 50 kArms
Follow current limitation / Selectivity no tripping of a 35 A gL/gG fuse up to 25 kArms (prosp.)
Response time tA ≤ 100 ns
Max. backup fuse up to IK = 25 kArms 315 A gL/gG
Max. backup fuse at IK > 25 kArms 200 A gL/gG
TOV voltage UT 335 V / 5 sec.
Operating temperature range (parallel wiring) TUP -40°C...+80°C
Operating temperature range (through wiring) TUS -40°C...+60°C
Cross-sectional area (L, L´, N/PEN) min. 10 mm2 solid / flexible
Cross-sectional area (L, N/PEN) max. 50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L´, N/PEN) max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 2 mods., DIN 43880
Ordering information
Type DB 1 255 H
Part No. 900 222
Packing unit 1 pc(s)
42 www.dehn.de
POWER SUPPLY SYSTEMS DEHNbloc®
00 111 DB 1 255
00 159 DB 1 440
DB 1 255 DB 1 440
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Classification according to E DIN VDE 0675-6 B B
Max. continuous ac voltage UC 255 V 440 V
Lightning impulse current (10/350) Iimp 50 kA 50 kA
Nominal discharge current (8/20) In 50 kA 50 kA
Voltage protection level UP ≤ 4 kV ≤ 4 kV
Follow current extinguishing capability ac Ifi 3 kArms 1.5 kArms
Response time tA ≤ 100 ns ≤ 100 ns
Max. backup fuse up to IK = 25 kArms (ta ≤ 0.2 s) 500 A gL/gG 500 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ≤ 5s) 250 A gL/gG 250 A gL/gG
Max. backup fuse at IK > 50 kArms 160 A gL/gG 160 A gL/gG
TOV voltage UT 335 V / 5 sec. —
TOV voltage TN system UT — 580 V / 5 sec.
TOV voltage IT system UT — 1200 V + U0 / 200 ms
Operating temperature range -40°C...+80°C -40°C...+80°C
Min. cross-sectional area 10 mm2 solid / flexible 10 mm2 solid / flexible
Max. cross-sectional area 50 mm2 stranded / 35 mm2 flexible 50 mm2 stranded / 35 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, CSA —
Ordering information
Type DB 1 255 DB 1 440
Part No. 900 111 900 159
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 43
DEHNbloc® POWER SUPPLY SYSTEMS
900 110 DB 3 255
N/PEN
DB 3 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Nominal voltage ac UN 230/400 V
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) [L1+L2+L3-PEN] Iimp 100 kA
Lightning impulse current (10/350) [L-PEN] Iimp 50 kA
Nominal discharge current (8/20) In 50 / 100 kA
Voltage protection level UP ≤ 4 kV
Follow current extinguishing capability ac Ifi 3 kArms
Response time tA ≤ 100 ns
Max. backup fuse up to IK = 25 kArms (ta ≤ 0.2 s) 500 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ≤ 5s) 250 A gL/gG
Max. backup fuse at IK > 50 kArms 160 A gL/gG
TOV voltage UT 335 V / 5 sec.
Operating temperature range -40°C...+80°C
Min. cross-sectional area 10 mm2 solid / flexible
Max. cross-sectional area 50 mm2 stranded / 35 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 4 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL, CSA
Ordering information
Type DB 3 255
Part No. 900 110
Packing unit 1 pc(s)
44 www.dehn.de
POWER SUPPLY SYSTEMS DEHNbloc®
00 260 DB NH00
55
DB NH00 255: Single-pole lightning current arrester with high discharge capacity, NH 00 design
DB NH00 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) Iimp 50 kA
Nominal discharge current (8/20) In 50 kA
Voltage protection level UP ≤ 4 kV
Follow current extinguishing capability ac Ifi 3 kArms
Response time tA ≤ 100 ns
Max. backup fuse up to IK = 25 kArms (ta ≤ 0.2 s) 500 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ≤ 5s) 250 A gL/gG
Max. backup fuse at IK > 50 kArms 160 A gL/gG
TOV voltage UT 335 V / 5 sec.
Operating temperature range -40°C...+80°C
Mounting on NH fuse holder, size 00
Enclosure material red thermoplastic, UL 94-0
Ordering information
Type DB NH00 255
Part No. 900 260
Packing unit 1 pc(s)
www.dehn.de 45
DEHNport® Maxi POWER SUPPLY SYSTEMS
Lightning Current Arrester with LIGHTNING CURRENT ARRESTERS – TYPE 1
high Follow Current Extinguishing Capability SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
SPD Class I according to IEC 61643-1;
• Creepage discharge spark gap with
RADAX Flow technology
• Follow current extinguishing capability
up to 50 kArms
• No tripping of 40 A gL/gG fuses up to
50 kArms
• Installation possible upstream of supply
meters according to national regula-
tions (e.g. Germany: VDN guidelines)
• 50 kA (10/350) lightning impulse
current
inued
discont
DPM 255: Single-pole lightning current arrester with high For protection of low voltage consumer’s installations against surges
follow current extinguishing capability even at direct lightning strikes. For use in the lightning protection zones
concept at boundaries 0A – 1.
The groundbreaking development of the RADAX Flow technology for The leakage current free spark gap based arrester DEHNport® Maxi is very
extinction of follow currents and follow current limitation has been reali- suitable for installation upstream of supply meters in accordance with
sed for the first time in the “heavy-duty” lightning current arrester national regulations (e.g. Germany: VDN guidelines). With a discharge
DEHNport® Maxi. With a follow current extinguishing capability of 50 capacity of 50 kA (10/350) per device, all system-specific types of
kArms , it safely extinguishes follow currents of 50 Hz without causing a DEHNport® Maxi fulfil the highest requirements of national and interna-
system interruption due to tripping upstream overcurrent protective tional lightning protection standards. The multifunctional terminal can be
devices. Therefore, DEHNport® Maxi is always the right choice for reali- connected simultaneously to conductors and busbars and thus allows an
sing lightning equipotential bonding in industrial low voltage main distri- easy wiring with other DIN rail mounted devices.
bution boards. The patented RADAX Flow technology allows a dis-
connecting selectivity even for small-sized fuses. This ensures the highest
system availability possible.
46 www.dehn.de
POWER SUPPLY SYSTEMS DEHNport® Maxi
00 104 DPM 255
DPM 255: Single-pole lightning current arrester with high follow current extinguishing capability
DPM 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) Iimp 50 kA
Nominal discharge current (8/20) In 50 kA
Voltage protection level UP ≤ 4 kV
Follow current extinguishing capability ac Ifi 50 kArms
Follow current limitation / Selectivity no tripping of a 40 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA ≤ 100 ns
Max. backup fuse up to IK = 25 kArms (ta ≤ 0.2 s) 500 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ≤ 5 s) 315 A gL/gG
Max. backup fuse at IK > 50 kA rms 200 A gL/gG
TOV voltage 335 V / 5 sec.
Operating temperature range -40°C...+80°C
Min. cross-sectional area 10 mm2 solid / flexible
Max. cross-sectional area 50 mm2 stranded / 35 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 2 mods., DIN 43880
Approvals, Certifications KEMA, VDE, UL
Ordering information
Type DPM 255
Part No. 900 104
Packing unit 1 pc(s)
www.dehn.de 47
DEHNport® POWER SUPPLY SYSTEMS
Lightning Current Arrester LIGHTNING CURRENT ARRESTERS – TYPE 1
SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
SPD Class I according to IEC 61643-1;
• Tandem creepage discharge spark gap
with “wavebreaker function”. Allows
energy coordination with downstream
varistor based surge arresters, e.g.
DEHNguard and/or the device to be
protected
• 75 kA (10/350) lightning impulse
current
• Suitable for installation upstream of
supply meters in accordance with
national regulations (e.g. Germany:
VDN guidelines)
• Single-pole unit – therefore optional
use of single-, 2-, 3- or 4-pole devices For protection of low voltage consumer’s installations against surges
according to system configuration (up even at direct lightning strikes. For use in the lightning protection zones
to lightning impulse currents of 100 kA concept at boundaries 0A – 1.
48 www.dehn.de
POWER SUPPLY SYSTEMS DEHNport®
00 100 DP 255
00 101 DP 440
DP 255 DP 440
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Classification according to E DIN VDE 0675-6 B B
Max. continuous ac voltage UC 255 V 440 V
Lightning impulse current (10/350) Iimp 75 kA 75 kA
Nominal discharge current (8/20) In 75 kA 75 kA
Voltage protection level UP ≤ 3.5 kV ≤ 3.5 kV
Follow current extinguishing capability ac Ifi 4 kArms 0.75 kArms
Response time tA ≤ 100 ns ≤ 100 ns
Max. backup fuse up to IK = 25 kArms (ta ≤ 0.2 s) 500 A gL/gG 500 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ≤ 5 s) 250 A gL/gG 250 A gL/gG
Max. backup fuse at IK > 50 kArms 160 A gL/gG 160 A gL/gG
TOV voltage 335 V / 5 sec. —
TOV voltage TN system — 580 V / 5 sec.
TOV voltage IT system — 1200 V + U0 / 200 ms
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Min. cross-sectional area 10 mm2 solid / flexible 10 mm2 solid / flexible
Max. cross-sectional area 50 mm2 stranded / 35 mm2 flexible 50 mm2 stranded / 35 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications VDE, KEMA —
Ordering information
Type DP 255 DP 440
Part No. 900 100 900 101
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 49
DEHNgap ... POWER SUPPLY SYSTEMS
N-PE Lightning Current Arrester LIGHTNING CURRENT ARRESTERS – TYPE 1
SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
SPD Class I according to IEC 61643-1;
• Lightning impulse current 100 kA
(10/350)
• Total current arrester, especially for use
in TT systems in “3+1” circuits accor-
ding to IEC 60364-5-53 between neutral
conductor N and protective conductor PE
• Creepage discharge spark gap
technology
The single-pole N-PE lightning current arresters DEHNgap Maxi, DEHNgap DEHNgap B NH has been developed especi-
BN, DEHNgap B and DEHNgap B NH, being total current arresters bet- ally for industrial installations as well as for
ween neutral and protective conductor in TT systems, are designed to supply networks. This device can be integra-
ensure the fulfilment of the socalled “3+1” requirements regarding pro- ted very easily into existing NH fuse holders,
tection of persons and material assets. Especially for this challenge the size 00. The DIN rail mounted devices
creepage discharge spark gaps used have been developed. With a disch- DEHNgap Maxi, DEHNgap BN and DEHNgap
arge capacity of up to 100 kA (10/350) they fulfil the highest require- B provide multifunctional terminals for con-
ments made on such kinds of devices by national and international light- necting conductors and busbars for easy
ning protection standards. Their leakage current free spark gap design wiring in connection with other DIN rail
allows the devices to be used in areas upstream of supply meters accor- mounted terminals. The integrated feed-
ding to national regulations (e.g. Germany: VDN guidelines). through terminal in DEHNgap Maxi allows
Being a coordinated N-PE lightning current arrester, DEHNgap Maxi has a an especially compact, space-saving design.
special position among the total current arresters: Thanks to its response
performance, DEHNgap Maxi can be coordinated directly with N-PE surge
arrester DEHNgap C/T without additional decoupling coil. If lightning cur-
rent and surge arresters have to be installed together at one site,
DEHNgap C/T has no longer to be additionally installed thanks to the low
voltage protection level of DEHNgap Maxi.
50 www.dehn.de
POWER SUPPLY SYSTEMS DEHNgap ...
00 055 DGPM
55
DGPM 255
Maxi
DEHNgap
900 055
N N'
DGPM 255
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1 Class I
Classification according to E DIN VDE 0675-6 B
Max. continuous ac voltage UC 255 V
Lightning impulse current (10/350) Iimp 100 kA
Voltage protection level UP ≤ 1.5 kV
Follow current extinguishing capability ac Ifi 100 Arms
Response time tA ≤ 100 ns
TOV voltage 1200 V / 200 ms
Operating temperature range (parallel wiring) TUP -40°C...+80°C
Operating temperature range (through wiring) TUS -40°C...+60°C
Cross-sectional area (N,N´,PE) min. 10 mm2 solid / flexible
Cross-sectional area (N,PE) max. 50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (N´) max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 2 mods., DIN 43880
Ordering information
Type DGPM 255
Part No. 900 055
Packing unit 1 pc(s)
www.dehn.de 51
DEHNgap ... POWER SUPPLY SYSTEMS
900 132 DGP BN
255
Basic circuit diagram DGP BN 255 Dimension drawing DGP B(N) 255
inued
discont
Ordering information
Type DGP BN 255 DGP B 255
Part No. 900 132 900 130
Packing unit 1 pc(s) 1 pc(s)
52 www.dehn.de
POWER SUPPLY SYSTEMS DEHNgap ...
00 269 DGP B
NH00 N 255
Dimension drawing DGP B NH00 N 255 Basic circuit diagram DGP B NH00 N 255
DGP B NH00 N 255: Encapsulated N-PE lightning current arrester, NH design, size 00
Ordering information
Type DGP B NH00 N 255
Part No. 900 269
Packing unit 1 pc(s)
www.dehn.de 53
POWER SUPPLY SYSTEMS
54 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® TNC / ... TNS / ... TT /... IT
SURGE ARRESTERS – TYPE 2 Multi-pole Surge Arrester
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• Complete prewired unit for common
system configurations, consisting of
a base part and plug-in protection
modules
• Energy coordination possible with
upstream lightning current arresters,
e.g. DEHNbloc Maxi
• High discharge capacity thanks to
powerful zinc oxide varistors or zinc
oxide varistors/spark gaps (DEHNguard
TT ...)
• Reliable control thanks to Thermo
Dynamic Control disconnector with dual
For protection of low voltage consumer´s installations against surges.
monitoring
For use in the lightning protection zones concept at boundaries 0B – 1 • Fault indication by red mark in the
and higher.
inspection window
• Multifunctional terminals for con-
necting conductors and busbars
DEHNguard TNC 230/400: Complete unit for TN-C systems
DEHNguard TNS 230/400: Complete unit for TN(C)-S systems
DEHNguard TT 230/400: Complete unit for TT- and TN-S systems
DEHNguard IT 500: Complete unit for IT systems without included neutral conductor with
500 V phase-to-phase voltage
DEHNguard ... FM: With remote signalling contact for monitoring device (floating changeover contact)
The multi-pole surge arresters of the luates the intensity of the discharge currents. Thus, it ensures that the
DEHNguard TNC / ... TNS / ... TT / ... IT fami- arrester does not only change into a safe and isolated state at “standard”
ly offer high safety and easy utilisation. The overloads but also remains safe if the device parameters are significantly
application-orientated product description exceeded.
makes it easier to choose the right com-
plete prewired unit. Reduced installation Apart from the standard visual indication with green and red coloured
errors and work are unbeatable advan- marks, type DEHNguard... FM provides a 3-pole terminal for remote sig-
tages that can be offered to the customer. nalling. As the remote signalling contact works also as a floating
Both the dual monitoring unit for each cir- changeover contact, the remote signal can be used as a break or make
cuit with Thermo Dynamic Control and the contact according to circuit concept. The
code of the plug-in protection module types preset by the manufacturer surge arresters of the DEHNguard TNC /
characterise the high reliability of the equipment. Damage caused by sub- ... TNS / ... TT / ... IT family provide multi-
sequent installation errors of the installer or the operator is unlikely. Apart functional terminals for connection of con-
from measuring the surface temperature of the high-capacity varistor, the ductors and busbars for easy wiring with
Thermo Dynamic Control monitoring and disconnection device also eva- other DIN rail mounted devices.
www.dehn.de 55
DEHNguard® TNC / ... TNS / ... TT / ... IT POWER SUPPLY SYSTEMS
900 510 DG TNC
230 400 900 540
DEHNguard TNC
DG TNC 230 400 FM
12
11 FM
14
L1 L2 L3
Basic circuit diagram DG TNC 230 400 FM Dimension drawing DG TNC 230 400 (FM)
Ordering information
Type DG TNC 230 400 DG TNC 230 400 FM
Part No. 900 510 900 540
Packing unit 1 pc(s) 1 pc(s)
Type T 275
T 275 DGT
Surge protection Module, 275 Venglish 900670
Nominal discharge current (8/20) 20 kA
Max. continuous ac voltage 275 V
Max. continuous dc voltage 350 V
PU Part
Type pc(s) No.
T 275 1 900 670
56 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® TNC / ... TNS / ... TT / ... IT
00 530 DG TNS
30 400 900 560
DEHNguard TNS
DG TNS 230 400 FM
12
11 FM
14
L1 L2 L3 N
Dimension drawing DG TNS 230 400 (FM) Basic circuit diagram DG TNS 230 400 FM
Ordering information
Type DG TNS 230 400 DG TNS 230 400 FM
Part No. 900 530 900 560
Packing unit 1 pc(s) 1 pc(s)
Type T 275
T 275 DGT
Surge protection Module, 275 Venglish 900670
Nominal discharge current (8/20) 20 kA
Max. continuous ac voltage 275 V
Max. continuous dc voltage 350 V
PU Part
Type pc(s) No.
T 275 1 900 670
www.dehn.de 57
DEHNguard® TNC / ... TNS / ... TT / ... IT POWER SUPPLY SYSTEMS
900 520 DG TT
230 400 900 550
DEHNguard TT
DG TT 230 400 FM
12
11 FM
14
L1 L2 L3 N
Basic circuit diagram DG TT 230 400 FM Dimension drawing DG TT 230 400 (FM)
DG TT 230 400 (FM): Surge arrester for TT- and TN-S systems
Ordering information
Type DG TT 230 400 DG TT 230 400 FM
Part No. 900 520 900 550
Packing unit 1 pc(s) 1 pc(s)
Accessory Part for DEHNguard® TNC / ... TNS / ... TT / ... IT Accessory Part for DEHNguard® TNC / ... TNS / ... TT / ... IT
Varistor-based Protection Module N-PE Spark-Gap based Protection Module
900670 T 275
900134 T C 255
58 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® TNC / ... TNS / ... TT / ... IT
00 516 DG IT 500
00 546 DG IT 500
DEHNguard IT
M
DG IT 500
PE
DEHNguard IT, 500 V 900 516
DG IT 500 FM
DEHNguard IT FM, 500 V 900 546
12
11 FM
14
L1 L2 L3
DG IT 500 (FM): Surge arrester for IT systems with 500 V phase-to-phase voltage
DG IT 500 DG IT 500 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Classification according to E DIN VDE 0675-6 C C
Nominal voltage ac UN 500 V 500 V
Max. continuous ac voltage UC 600 V 600 V
Nominal discharge current (8/20) In 15 kA 15 kA
Max. discharge current (8/20) Imax 30 kA 30 kA
Voltage protection level UP ≤ 2.5 kV ≤ 2.5 kV
Voltage protection level at 5 kA UP ≤ 2.0 kV ≤ 2.0 kV
Response time tA ≤ 25 ns ≤ 25 ns
Max. mains-side overcurrent protection 100 A gL/gG 100 A gL/gG
Short circuit withstand capability at max. mains-side overcurrent protection 25 kArms 25 kArms
TOV voltage UT 600 V / 5 sec. 600 V / 5 sec.
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Cross-sectional area (min.) 1.5 mm2 solid / flexible 1.5 mm2 solid / flexible
Cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 3 mods., DIN 43880 3 mods., DIN 43880
Type of remote signalling contact — changeover contact
Switching capacity ac — 250 V/0.5 A
Switching capacity dc — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid / flexible
Ordering information
Type DG IT 500 DG IT 500 FM
Part No. 900 516 900 546
Packing unit 1 pc(s) 1 pc(s)
Type T 600
T 600 DGT
www.dehn.de 59
DEHNguard TN 230 / ... TT 230 POWER SUPPLY SYSTEMS
Two-pole Surge Arrester SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• Complete prewired unit for common ac
current system configurations, consis-
ting of a base part and plug-in protec-
tion modules
• Energy coordination possible with up-
stream lightning current arresters,
e.g. DEHNbloc Maxi
• High discharge capacity thanks to high-
capacity zinc oxide varistors and/or zinc
oxide varistors/spark gaps (DEHNguard
TT ...)
• Reliable control thanks to Thermo
Dynamic Control disconnector with
dual monitoring For protection of low voltage consumer´s installations against surges.
• Fault indication via red mark in the For use in the lightning protection zones concept at boundaries 0B – 1
and higher.
inspection window
• Multifunctional terminals for connec-
tion of conductors and busbars
DEHNguard TN 230: Complete unit for 230 V-TN systems
DEHNguard TT 230: Complete unit for 230 V-TT and TN systems
DEHNguard TN 230 FM: Complete unit for 230 V-TN systems; with remote signalling contact for monitoring device
(floating changeover contact)
DEHNguard TT 230 FM: Complete unit for 230 V-TT and TN systems; with remote signalling contact for monitoring device
(floating changeover contact)
The 2-pole surge arresters of the Apart from the standard visual indication with green and red coloured
DEHNguard TN/...TT family provide marks, type DEHNguard ... FM provides a 3-pole terminal for remote sig-
the highest possible safety and nalling. As the remote signalling contact works also as a floating chan-
comfort. geover contact, the remote signal can be used as a break or make contact
according to circuit concept.
The application-orientated product
description makes it considerably The surge arresters of the DEHN-
easier to choose the right complete guard TN/...TT family provide multi-
prewired unit. Reduced installation functional terminals for connection
mistakes and work are unbeatable of conductors and busbars for easy
advantages that can be offered to wiring with other DIN rail mounted
the customer. Both the dual moni- devices.
toring unit for each circuit with Thermo Dynamic Control and the code of
the plug-in protection module types preset by the manufacturer characte-
rise the high reliability of the equipment. Damage caused by subsequent
installation errors of the installer or the operator is unlikely. Apart from
measuring the surface temperature of the high-capacity varistor, the
Thermo Dynamic Control monitoring and disconnection device also eva-
luates the intensity of the discharge currents. Thus, it ensures that the
arrester does not only change into a safe and isolated state at “standard”
overloads but also remains safe if the device parameters are significantly
exceeded.
60 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard TN 230 / ... TT 230
00 506 DG TN
30
DEHNguard TN 230
00 507 DG TN
DG TN 230
DEHNguard TN, 2-pole, 230 V 900 506
DG TN 230 FM
DEHNguard TN FM, 2-pole, 230 V 900 507
DG TN 230 DG TN 230 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Classification according to E DIN VDE 0675-6 C C
Nominal voltage ac UN 230 V 230 V
Max. continuous ac voltage UC 275 V 275 V
Nominal discharge current (8/20) In 20 kA 20 kA
Max. discharge current (8/20) Imax 40 kA 40 kA
Voltage protection level Up ≤ 1.25 kV ≤ 1.25 kV
Voltage protection level at 5 kA UP ≤ 1 kV ≤ 1 kV
Response time tA ≤ 25 ns ≤ 25 ns
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG
Short circuit withstand capability at max. mains-side overcurrent protection 50 kArms 50 kArms
TOV voltage UT 335 V / 5 sec. 335 V / 5 sec.
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Min. cross-sectional area 1.5 mm2 solid / flexible 1.5 mm2 solid / flexible
Max. cross-sectional area 35 mm2 stranded / 25 mm2 flexible 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity ac — 250 V / 0.5 A
Switching capacity dc — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid / flexible
Ordering information
Type DG TN 230 DG TN 230 FM
Part No. 900 506 900 507
Packing unit 1 pc(s) 1 pc(s)
Type T 275
Nominal discharge current (8/20)
T 275
Surge protection Module, 275 Venglish
DGT
900670 20 kA
Max. continuous ac voltage 275 V
Max. continuous dc voltage 350 V
PU Part
Type pc(s) No.
T 275 1 900 670
www.dehn.de 61
DEHNguard TN 230 / ... TT 230 POWER SUPPLY SYSTEMS
900 508 DG TT
230
DEHNguard TT 230
900 509 DG TT
PE DG TT 230
DEHNguard TT, 2-pole 900 508
DG TT 230 FM
DEHNguard TT FM, 2-pole 900 509
12
11 FM
14
L N
DG TT 230 DG TT 230 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Classification according to E DIN VDE 0675-6 C C
Nominal voltage ac UN 230 V 230 V
Nominal discharge current (8/20) In 20 kA 20 kA
Max. discharge current (8/20) Imax 40 kA 40 kA
Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG
Short circuit withstand capability at max. mains-side overcurrent protection 50 kArms 50 kArms
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Min. cross-sectional area 1.5 mm2 solid / flexible 1.5 mm2 solid / flexible
Max. cross-sectional area 35 mm2 stranded / 25 mm2 flexible 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 2 mods., DIN 43880 2 mods., DIN 43880
Approvals, Certifications KEMA KEMA
Type of remote signalling contact — changeover contact
Switching capacity ac — 250 V / 0.5 A
Switching capacity dc — 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid / flexible
Ordering information
Type DG TT 230 DG TT 230 FM
Part No. 900 508 900 509
Packing unit 1 pc(s) 1 pc(s)
Accessory Part for DEHNguard TN 230 / ... TT 230 Accessory Part for DEHNguard TN 230 / ... TT 230
900670 T 275
62 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® / DEHNguard® ... FM
SURGE ARRESTERS – TYPE 2 Single-pole, compact Surge Arrester
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• High discharge capacity thanks to
powerful zinc oxide varistors
• Quick response
• Reliable control thanks to Thermo
Dynamic Control disconnector with
dual monitoring
• Energy coordination possible with
upstream lightning current arresters,
e.g. DEHNbloc Maxi
• Fault indication via red mark in the
inspection window
• Slim design (modular construction)
according to DIN 43880
For protection of low voltage consumer´s installations against surges.
For use in the lightning protection zones concept at boundaries 0B – 1 • Multifunctional terminals for connec-
and higher. tion of conductors and busbars
DEHNguard: Single-part (compact unit)
DEHNguard FM: Single-part (compact unit); with remote signalling contact for control device
(floating changeover contact)
The devices of the compact DEHNguard family are distinctively versatile. Especially the DEHN-specific Thermo Dynamic Control disconnector ensu-
Whether in single-phase systems, in dc power supplies or at high system res the arresters to change to a safe isolated state even at extreme over-
voltages – there is always the right arrester for every kind of application. loads. Apart from the surface temperature of the high-capacity varistor,
The multifunctional terminals provide the devices with an almost unlimi- also the intensity of the discharge current is evaluated.
ted flexibility for connection with each other, but also with other DIN rail
mounted devices in the same distribution board. Not only flexibility Apart from the standard visual indication with green and red coloured
characterises the DEHNguard family. Moreover, it is the striking perfor- marks, the variants of DEHNguard ... FM provide a 3-pole terminal for
mance parameters setting trends all over the world. remote signalling. As the remote signalling contact works as a floating
changeover contact, the remote signal can be used as a break or make
A high discharge capacity, low protection level and dual safety Thermo contact, according to circuit concept.
Dynamic Control disconnector define the high reliability of the devices.
www.dehn.de 63
DEHNguard® / DEHNguard® ... FM POWER SUPPLY SYSTEMS
900 604 DG 75
900 603 DG 150
DEHNguard
900 600 DG 275
DG 75
DEHNguard, 75 V 900 604
DG 150
DEHNguard, 150 V 900 603
DG 275
DEHNguard, 275 V 900 600
DG 320
DEHNguard, 320 V 900 605
DG 385
DEHNguard, 385 V 900 602
DG 440
DEHNguard, 440 V 900 607
DG 600
DEHNguard, 600 V 900 601
Ordering information
Type DG 75 DG 150 DG 275 DG 320 DG 385 DG 440 DG 600
Part No. 900 604 900 603 900 600 900 605 900 602 900 607 900 601
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
64 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® / DEHNguard® ... FM
00 624 DG 75 FM
00 623 DG 150
DEHNguard FM
M
DG 75 FM
DEHNguard FM, 75 V 900 624
DG 150 FM
DEHNguard FM, 150 V 900 623
DG 275 FM
DEHNguard FM, 275 V 900 620
DG 320 FM
DEHNguard FM, 320 V 900 625
DG 385 FM
DEHNguard FM, 385 V 900 622
12
DG 440 FM
DEHNguard FM, 440 V 900 627
DG 600 FM
11 FM
DEHNguard FM, 600 V 900 621
14
DG ... FM: Single-pole compact surge arrester with floating remote signalling contact
Ordering information
Type DG 75 FM DG 150 FM DG 275 FM DG 320 FM DG 385 FM DG 440 FM DG 600 FM
Part No. 900 624 900 623 900 620 900 625 900 622 900 627 900 621
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 65
DEHNguard® T / DEHNguard® T ... FM POWER SUPPLY SYSTEMS
Single-pole, pluggable Surge Arrester SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• High discharge capacity thanks to
high-capacity zinc oxide varistor
• Quick response
• Two-part unit, consisting of a base part
and plug-in protection component
• Reliable control thanks to Thermo
Dynamic Control disconnector with
dual monitoring
• Energy coordination possible with
upstream lightning current arrester,
e.g. DEHNbloc Maxi
• Fault indication via red mark in the
inspection window
For protection of low voltage consumer´s installations against surges.
• Slim design (modular construction) For use in the lightning protection zones concept at boundaries 0B – 1
according to DIN 43880 and higher.
DEHNguard T: Two-part unit, consisting of base part and plug-in protection module
DEHNguard T FM: Two-part unit, consisting of base part and plug-in protection module; with remote signalling contact
for control device (floating changeover contact)
The pluggable DEHNguard T surge arresters are real all-rounders. Especially the DEHN-specific Thermo Dynamic Control disconnector ensu-
res the arresters to change to a safe isolated state even at extreme over-
Whether in single-phase systems, in dc power supplies or at high system loads. In parallel to the surface temperature of the high-capacity varistor,
voltages – there is always the right arrester for every kind of application. the intensity of the discharge current is also evaluated. Apart from the
The multifunctional terminals provide the devices with an almost unlimi- standard visual indication with green and red coloured marks, the vari-
ted flexibility for connection with each other, but also with other DIN rail ants of DEHNguard T ... FM provide a 3-pole terminal for remote signal-
mounted devices in the same distribution board. Not only flexibility cha- ling. As the remote signalling contact works also as a floating changeover
racterises the DEHNguard T family. Moreover, it is the striking perfor- contact, the remote signal can be used as a break or make contact accor-
mance parameters setting trends all over the world. ding to circuit concept.
A high discharge capacity, Should, nevertheless, the varistor unit be overloaded despite the high
low voltage protection discharge capacity of the DEHNguard T devices, its two-part structure
level and the dual safety allows an easy exchange of the protection module without tools.
Thermo Dynamic Control
disconnector define the
high reliability of the devi-
ces.
66 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® T / DEHNguard® T ... FM
00 654 DG T 75
00 653 DG T 150
DEHNguard T
00 650 DG T 275
DG T 75
DEHNguard T, 75 V 900 654
DG T 150
DEHNguard T, 150 V 900 653
DG T 275
DEHNguard T, 275 V 900 650
DG T 320
DEHNguard T, 320 V 900 652
DG T 385
DEHNguard T, 385 V 900 641
DG T 440
DEHNguard T, 440 V 900 655
DG T 600
DEHNguard T, 600 V 900 651
DG T ...: Single-pole, pluggable surge arrester, consisting of a base part and plug-in protection module
Ordering information
Type DG T 75 DG T 150 DG T 275 DG T 320 DG T 385 DG T 440 DG T 600
Part No. 900 654 900 653 900 650 900 652 900 641 900 655 900 651
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
Max. continuous dc voltage 100 V 200 V 350 V 420 V 500 V 585 V 600 V
PU Part
Type pc(s) No.
T 75 1 900 674
T 150 1 900 673
T 275 1 900 670
T 320 1 900 672
T 385 1 900 679
T 440 1 900 675
T 600 1 900 671
www.dehn.de 67
DEHNguard® T / DEHNguard® T ... FM POWER SUPPLY SYSTEMS
900 684 DG T 75
FM
DEHNguard T FM
900 683 DG T 150
DG T 75 FM
DEHNguard T FM, 75 V 900 684
DG T 150 FM
DEHNguard T FM, 150 V 900 683
DG T 275 FM
DEHNguard T FM, 275 V 900 680
DG T 320 FM
DEHNguard T FM, 320 V 900 682
DG T 385 FM
DEHNguard T FM, 385 V 900 691
12 DG T 440 FM
DEHNguard T FM, 440 V
DG T 600 FM
900 685
14
DG T ... FM: Single-pole, pluggable surge arrester, consisting of base part and plug-in protection
module; with floating remote signalling contact
Ordering information
Type DG T 75 FM DG T 150 FM DG T 275 FM DG T 320 FM DG T 385 FM DG T 440 FM DG T 600 FM
Part No. 900 684 900 683 900 680 900 682 900 691 900 685 900 681
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
Max. continuous dc voltage 100 V 200 V 350 V 420 V 500 V 585 V 600 V
PU Part
Type pc(s) No.
T 75 1 900 674
T 150 1 900 673
T 275 1 900 670
T 320 1 900 672
T 385 1 900 679
T 440 1 900 675
T 600 1 900 671
68 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® Y PV
SURGE ARRESTERS – TYPE 2 Multi-pole Surge Arrester
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
for Photovoltaic Systems
SPD Class II according to IEC 61643-1;
• Complete prewired unit for photovol-
taic systems, consisting of a base part
and plug-in protection modules
• Fault-resistant Y-circuit with 3 high-
capacity varistors, avoids damage at
the surge protection in case of insula-
tion faults in the generator circuit
• Use in accordance with IEC 60364-7-712
“Electrical installations of buildings –
Part 7-712: Requirements for special
installations or locations; Solar photo-
voltaic (PV) power supply systems”
• High discharge capacity thanks to
For protection of low voltage consumer´s installations against surges.
powerful zinc oxide varistors
For use according to IEC 60364-7-712:2002-05 “Electrical installations • Reliable control thanks to Thermo
of buildings – Part 7-712: Requirements for special installations or loca-
tions; Solar photovoltaic (PV) power supply systems”. Dynamic Control disconnector with
dual monitoring
• Fault indication by red mark in the
inspection window
DEHNguard Y PV 1000: Complete unit for photovoltaic systems with UOC STC ≤ 1000 V dc
DEHNguard Y PV 1000 FM: Complete unit for photovoltaic systems with UOC STC ≤ 1000 V dc with remote signalling
contact for control device (floating changeover contact)
The multipole surge arresters DEHNguard Y PV 1000 (FM) pass approved The fault-resistant Y-circuit with 3 high-capacity varistors avoids damage
DEHNguard safety to the field of photovoltaic generating plants. at the surge protection in case of isolation faults in the generator circuit
of the photovoltaic generator.
Both the dual monitoring unit for each circuit with Thermo Dynamic
Control and the code of the plug-in protection modules preset by the Apart from the standard visual indication with green and red coloured
manufacturer characterise the high reliability of the equipment. Damage marks, type DEHNguard Y PV 1000 FM provides a 3-pole terminal for
caused by subsequent installation errors of the installer or the operator is remote signalling. As the remote signalling contact works also as a
unlikely. Apart from the surface temperature of the high-capacity varistor, floating changeover contact, the remote signal can be used as a break or
the Thermo Dynamic Control monitoring and disconnection device evalua- make contact, according to the circuit concept. The surge arresters of the
tes also the intensity of the discharge currents. Thus it ensures the arres- DEHNguard Y PV family provide multifunctional terminals for connection
ter not to change into a safe and isolated state at “standard” overloads of conductors and busbars for easy wiring with other DIN rail mounted
only but to remain safe also if the device parameters are significantly devices.
exceeded.
www.dehn.de 69
DEHNguard® Y PV POWER SUPPLY SYSTEMS
900 517 DG Y PV
1000
DG Y PV
900 547 DG Y PV
DG Y PV 1000
DEHNguard Y PV 900 517
DG Y PV 1000 FM
DEHNguard Y PV 900 547
12
11 FM
14
+ -
DG Y PV 1000 ...: Complete circuit for photovoltaic systems with UOC STC ≤ 1000 V dc
DG Y PV 1000 DG Y PV 1000 FM
SPD according to EN 61643-11 Type 2 Type 2
SPD according to IEC 61643-1 Class II Class II
Classification according to E DIN VDE 0675-6 C C
PV voltage acc. to IEC 60364-7-712 UOC STC ≤ 1000 V ≤ 1000 V
Max. continuous dc voltage [(L+/L-) —> PE] Uc 500 V 500 V
Nominal discharge current (8/20) In 20 kA 20 kA
Max. discharge current (8/20) Imax 40 kA 40 kA
Voltage protection level UP ≤ 4 kV ≤ 4 kV
Voltage protection level at 5 kA UP ≤ 3.5 kV ≤ 3.5 kV
Response time tA ≤ 25 ns ≤ 25 ns
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Cross-sectional area (min.) 1.5 mm2 solid / flexible 1.5 mm2 solid / flexible
Cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 3 mods., DIN 43880 3 mods., DIN 43880
Type of remote signalling contact — changeover contact
Switching capacity ac — 250 V / 0.1 A
Switching capacity dc — 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminals — max. 1.5 mm2 solid / flexible
Ordering information
Type DG Y PV 1000 DG Y PV 1000 FM
Part No. 900 517 900 547
Packing unit 1 pc(s) 1 pc(s)
70 www.dehn.de
POWER SUPPLY SYSTEMS DEHNgap C/T
SURGE ARRESTERS – TYPE 2 N-PE Surge Arrester
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• Especially for use in TT systems in 3+1
circuits acc. to IEC 60364-5-53 between
neutral conductor N and protective
conductor PE
• Very high discharge capacity
• Two-part unit, consisting of a base part
and a plug-in spark gap based protec-
tion module
Being a total current arrester between neutral and protective conductor The spark gap based surge arrester DEHNgap C/T fulfils the requirements
in TT systems, the single-pole N-PE surge arrester DEHNgap C/T ensures of safe electrical isolation between neutral and protective conductor in TT
the keeping of the protection requirements for persons and material systems. The high lightning current discharge capacity (10/350) underlines
assets in form of socalled “3+1” circuits. A combination with the appro- the high safety requirements on the two-part protective device.
ved surge arresters of the DEHNguard and DEHNguard T families shows
the flexibility provided by the multifunctional terminals of DEHNgap C/T.
Being designed for connection of conductors and busbars, they allow a
system-specific connection in distribution boards.
www.dehn.de 71
DEHNgap C/T POWER SUPPLY SYSTEMS
900 133 DGP C T
255
DGP C T 255
SPD according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 255 V
Nominal discharge current (8/20) In 20 kA
Max. discharge current (8/20) Imax 40 kA
Follow current extinguishing capability Ifi 100 Arms
Lightning impulse current (10/350) Iimp 12 kA
Voltage protection level UP ≤ 1.5 kV
Response time tA ≤ 100 ns
VOV voltage UT 1200 V / 200 ms
Operating temperature range TU -40°C...+80°C
Cross-sectional area (min.) 1.5 mm2 solid / flexible
Max. cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 1 mod., DIN 43880
Approvals, Certifications KEMA, ÖVE, VDE, UL
Ordering information
Type DGP C T 255
Part No. 900 133
Packing unit 1 pc(s)
T C 255 TC
Type T C 255
Protection Module, 255 Venglish 900134
72 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® T ... VA / DEHNguard® T ... VA FM
SURGE ARRESTERS – TYPE 2 Varistor/Spark Gap based Surge Arrester
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• Two-part unit, consisting of a base part
and a plug-in protection module
• High-capacity zinc oxide varistor, con-
trol device Thermo Dynamic Control
and spark gap in series connection
• Energy coordination possible with
upstream lightning current arrester,
e.g. DEHNbloc Maxi
• Fault indication via red mark in the
inspection window
• Slim design (modular construction)
according to DIN 43880
• Multifunctional terminals for connec-
For protection of low voltage consumer´s installations against surges.
For use in the lightning protection zones concept at boundaries 0B – 1
tion of conductors and busbars
and higher.
DEHNguard T ... VA: Two-part unit, consisting of base part and plug-in protection module
DEHNguard T ... VA FM: Two-part unit, consisting of base part and plug-in protection module; with remote signalling
contact for control device (floating changeover contact)
The single-pole DEHNguard T ... VA surge arresters complete the approved Especially the DEHN-specific Thermo Dynamic Control disconnector ensu-
DEHNguard and DEHNguard T families. The special series connection of res the arresters to change to a safe isolated state even at extreme over-
spark gap and varistor module opens up new fields of application. For loads. In parallel to the surface temperature of the high-capacity varistor,
example, DEHNguard T ... VA devices provide reliable protection for sys- the intensity of the discharge current is also evaluated. Apart from the
tems with permanent isolation control. standard visual indication with green and red coloured marks, type
DEHNguard T VA ... FM provides a 3-pole terminal for remote signalling.
The multifunctional terminals provide the devices with a nearly unlimited As the remote signalling contact works also as a floating changeover con-
flexibility for connection with each other but also with other DIN rail tact, the remote signal can be used as a break or make contact according
mounted devices in the same distribution board. Not only flexibility to circuit concept.
characterises the DEHNguard T ... VA family but also the striking perfor-
mance parameters setting trends all over the world:
A high discharge capacity, low voltage protection level and the dual
safety Thermo Dynamic Control disconnector ensure the high reliability of
the devices.
www.dehn.de 73
DEHNguard® T ... VA / DEHNguard® T ... VA FM POWER SUPPLY SYSTEMS
900 667 DG T 75
VA
DEHNguard T ... VA
900 659 DG T 275
DG T 75 VA
DEHNguard T VA, 75 V 900 667
DG T 275 VA
DEHNguard T 275 VA, 275 V 900 659
DG T ... VA: Single-pole surge arrester with varistor/spark gap based terminal module
DG T 75 VA DG T 275 VA
SPD according to EN 61643-11 Type 2 Type 2
SPD acc. to IEC 61643-1 Class II Class II
Classification according to E DIN VDE 0675-6 C C
Max. continuous ac voltage UC 75 V 275 V
Max. continuous dc voltage UC 100 V 350 V
Nominal discharge current (8/20) In 10 kA 10 kA
Max. discharge current (8/20) Imax 20 kA 20 kA
Voltage protection level UP ≤ 1.5 kV ≤ 1.5 kV
Response time tA ≤ 100 ns ≤ 100 ns
Max. mains-side overcurrent protection 100 A gL/gG 100 A gL/gG
Short circuit withstand capability
at max. mains-side overcurrent protection 25 kArms 25 kArms
TOV voltage UT — 335 V / 5 sec.
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Cross-sectional area (min.) 1.5 mm2 solid / flexible 1.5 mm2 solid / flexible
Cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 1 mod., DIN 43880 1 mod., DIN 43880
Ordering information
Type DG T 75 VA DG T 275 VA
Part No. 900 667 900 659
Packing unit 1 pc(s) 1 pc(s)
74 www.dehn.de
POWER SUPPLY SYSTEMS DEHNguard® T ... VA / DEHNguard® T ... VA FM
00 692 DG T 75
VA FM
DEHNguard T ... VA FM
00 689 DG T 275
DG T 75 VA FM
DEHNguard T VA FM, 75 V 900 692
DG T 275 VA FM
DEHNguard T 275 VA FM, 275 V 900 689
12
11 FM
14
DG T ... VA FM: Single-pole surge arrester with varistor/spark gap based terminal module, with
floating remote signalling contact
DG T 75 VA FM DG T 275 VA FM
SPD according to EN 61643-11 Type 2 Type 2
SPD acc. to IEC 61643-1 Class II Class II
Classification according to E DIN VDE 0675-6 C C
Max. continuous ac voltage UC 75 V 275 V
Max. continuous dc voltage UC 100 V 350 V
Nominal discharge current (8/20) In 10 kA 10 kA
Max. discharge current (8/20) Imax 20 kA 20 kA
Voltage protection level UP ≤ 1.5 kV ≤ 1.5 kV
Response time tA ≤ 100 ns ≤ 100 ns
Max. mains-side overcurrent protection 100 A gL/gG 100 A gL/gG
Short circuit withstand capability
at max. mains-side overcurrent protection 25 kArms 25 kArms
TOV voltage UT — 335 V / 5 sec.
Operating temperature range TU -40°C...+80°C -40°C...+80°C
Cross-sectional area (min.) 1.5 mm2 solid / flexible 1.5 mm2 solid / flexible
Cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 1 mod., DIN 43880 1 mod., DIN 43880
Type of remote signalling contact changeover contact changeover contact
Switching capacity ac 250 V / 0.5 A 250 V / 0.5 A
Switching capacity dc 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid / flexible max. 1.5 mm2 solid / flexible
Ordering information
Type DG T 75 VA FM DG T 275 VA FM
Part No. 900 692 900 689
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 75
Protection Module for DEHNguard® T ... / DEHNgap C/T POWER SUPPLY SYSTEMS
Plug-in Protection Module SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• High discharge capacity thanks to
powerful zinc oxide varistors (T ...)
or spark gaps (T C ...)
• Reliable control thanks to Thermo
Dynamic Control disconnector with
dual monitoring
• Energy coordination possible with
upstream lightning current arrester,
e.g. DEHNbloc Maxi
• The plug-in protection module can be
exchanged without disconnection of the
mains voltage and without removing
the cover plate of the distribution
board. For protection of low voltage consumer´s installations against surges.
• Fault indication by red mark in the For use in the lightning protection zones concept 0B – 1 and higher.
inspection window.
T ...: Varistor-based protection module
T C ...: N-PE spark-gap-based protection module
The varistor-based protection modules for DEHNguard T and the spark- family provide the dual control and Thermo Dynamic Control discon-
gap-based protection module of DEHNgap C/T show the synergy between nector, which ensures the arresters to change to a safe, isolated state even
comfort and safety. Should DEHNguard T ... / DEHNgap C/T protection at extreme overloads. In parallel to the surface temperature of the high-
modules be overloaded despite their high performance parameters, they capacity varistor, also the intensity of the discharge current is evaluated.
can be easily removed and exchanged without tools. Any wrong furnish-
ment is prevented by the coding of the DEHNguard T ... / DEHNgap C/T The DEHNguard T and DEHNgap C/T protection modules provide remov-
devices and their corresponding pro- able enclosure lugs that prevent the protection modules from being remo-
tection modules preset by the manu- ved from current distribution boards with isolated cover (protection
facturer. Of course, also the (spare) pro- level 2) by electrical laypersons.
tection modules of the DEHNguard T
76 www.dehn.de
POWER SUPPLY SYSTEMS Protection Module for DEHNguard® T ... / DEHNgap C/T
00 674 T 75
00 673 T 150
75 DGT
urge Protection Module, 75 V 900 674
150 DGT
urge Protection Module, 150 V 900 673
275 DGT
urge protection Module, 275 V 900 670
320 DGT
urge Protection Module, 320 V 900 672
385 DGT
urge Protection Module, 385 V 900 679
440 DGT
urge Protection Module, 440 V 900 675
600 DGT
urge Protection Module, 600 V 900 671
Ordering information
Type T 75 T 150 T 275 T 320 T 385 T 440 T 600
Part No. 900 674 900 673 900 670 900 672 900 679 900 675 900 671
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
00 134 T C 255
C 255 TC
rotection Module, 255 V 900 134
T C 255
Nominal discharge current (8/20) In 20 kA
Max. discharge current (8/20) Imax 40 kA
Max. continuous ac voltage UC 255 V
Ordering information
Type T C 255
Part No. 900 134
Packing unit 1 pc(s)
www.dehn.de 77
VAV 1000 POWER SUPPLY SYSTEMS
Single-pole Arrester up to 1000 V ac/dc SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• Fault indication by tripping of a black
signal head
• Zinc oxide varistor with thermal control
and disconnection device
Both the terminals with safety cover and the thermal control and discon-
nection devices with a great safety distance come up to the elevated
safety requirements for such high system voltages.
78 www.dehn.de
POWER SUPPLY SYSTEMS VAV 1000
01 000 VAV 1000
VAV 1000
SPD according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 1000 V
Max. continuous dc voltage UC 1000 V
Nominal discharge current (8/20) In 5 kA
Max. discharge current (8/20) Imax 10 kA
Voltage protection level UP ≤ 4.2 kV
Response time tA ≤ 25 ns
Max. mains-side overcurrent protection 50 A aM
Short circuit withstand capability at max. mains-side overcurrent protection 25 kArms
TOV voltage UT 1000 V / 5 sec.
Operating temperature range TU -40°C...+80°C
Cross-sectional area (min.) 1.5 mm2 solid / flexible
Cross-sectional area (max.) 25 mm2 stranded / 16 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 3 mods., DIN 43880
Ordering information
Type VAV 1000
Part No. 901 000
Packing unit 1 pc(s)
www.dehn.de 79
V NH / VA NH POWER SUPPLY SYSTEMS
Surge Arresters in NH Design SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• Surge arrester for use in NH fuse
holders (size 00 or 1 ... 3)
• Zinc oxide varistor with control device,
disconnector and integrated backup
fuse (VA NH with additional spark gap
in series connection)
• Energy coordination possible with
upstream lightning current arrester
• Visual indication of faults by tripping
indicator
The single-pole V NH and VA NH surge arresters show that surge protec- A further considerable advantage of the V NH / VA NH family is the alrea-
tive devices do not have to be designed for DIN rails or socket outlets dy integrated backup fuse. Using an earth fault and short circuit proof
only. Being adjusted to the conditions at industrial sub-circuit distribution wiring, this is really a decisive contribution for saving space and costs in
boards, V NH and VA NH devices are designed in form of a NH fuse hol- distribution boards. Type VA NH of the high-capacity zinc oxide varistor
der. This allows an easy integration into busbar systems, as often used in with thermal control and disconnection device of the V NH devices has
the zones belonging to the operators of the power supply systems or in been amended by a spark gap in series connection. VA NH devices provi-
industrial installations. Thus the advantages of busbar systems like easy de reliable protection especially for widely expanded systems with perma-
installation, less installation time and less wiring, apply also to surge pro- nent isolation control. Apart from the standard visual indication via fault
tection. The idea of such a busbar system is continued consistently via the indicator, V(A) NH ... FM units provide a microswitch already set into the
arresters in NH design. V NH and VA NH surge arres- NH fuse base for remote signalling.
ters can be installed and removed by means
of a fuse switch disconnector and a fuse
handle. This means a considerable sim-
plification for measuring the iso-
lation of the installation as dis-
connecting the arrester is no
longer required.
80 www.dehn.de
POWER SUPPLY SYSTEMS V NH / VA NH
00 261 V NH00
80
V NH00 280
SPD Type according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 280 V
Nominal discharge current (8/20) In 15 kA
Max. discharge current (8/20) Imax 30 kA
Voltage protection level UP ≤ 1.25 kV
Voltage protection level at 5 kA UP ≤ 1 kV
Response time tA ≤ 25 ns
Short circuit withstand capability 25 kArms
TOV voltage UT 335 V / 5 sec.
Indication of disconnector red fault indicator
Operating temperature range TU -40°C...+80°C
Mounting on NH fuse holder, size 00
Enclosure material red thermoplastic, UL 94-0
Degree of protection IPX4W
Ordering information
Type V NH00 280
Part No. 900 261
Packing unit 1 pc(s)
www.dehn.de 81
V NH / VA NH POWER SUPPLY SYSTEMS
900 263 V NH00
280 FM
V NH00 FM: Surge arrester for use in NH fuse holders, size 00, with fault indicator for remote
signalling
V NH00 280 FM
SPD Type according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 280 V
Nominal discharge current (8/20) In 15 kA
Max. discharge current (8/20) Imax 30 kA
Voltage protection level UP ≤ 1.25 kV
Voltage protection level at 5 kA UP ≤ 1 kV
Response time tA ≤ 25 ns
Short circuit withstand capability 25 kArms
TOV voltage UT 335 V / 5 sec.
Indication of disconnector red fault indicator (tripping distance 7 mm)
Operating temperature range TU -40°C...+80°C
Mounting on NH fuse holder, size 00
Enclosure material red thermoplastic, UL 94 V-0
Ordering information
Type V NH00 280 FM
Part No. 900 263
Packing unit 1 pc(s)
82 www.dehn.de
POWER SUPPLY SYSTEMS V NH / VA NH
00 265 V NH1 3
80
V NH1 3 280
SPD Type according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 280 V
Nominal discharge current (8/20) In 15 kA
Max. discharge current (8/20) Imax 30 kA
Voltage protection level UP ≤ 1.25 kV
Voltage protection level at 5 kA UP ≤ 1 kV
Response time tA ≤ 25 ns
Short circuit withstand capability 25 kArms
TOV voltage UT 335 V / 5 sec.
Indication of disconnector red fault indicator
Operating temperature range TU -40°C...+80°C
Mounting on NH fuse holder, size 1-3
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IPX4W
Ordering information
Type V NH1 3 280
Part No. 900 265
Packing unit 1 pc(s)
www.dehn.de 83
V NH / VA NH POWER SUPPLY SYSTEMS
900 262 VA NH00
280
VA NH00: Surge arrester with varistor/spark gap based terminal module: for use in NH fuse
holders, size 00
VA NH00 280
SPD Type according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 280 V
Nominal discharge current (8/20) In 10 kA
Max. discharge current (8/20) Imax 20 kA
Voltage protection level UP ≤ 2.0 kV
Response time tA ≤ 100 ns
Short circuit withstand capability 25 kArms
TOV voltage UT 335 V / 5 sec.
Indication of disconnector red fault indicator
Operating temperature range TU -40°C...+80°C
Mounting on NH fuse holder, size 00
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IPX4W
Ordering information
Type VA NH00 280
Part No. 900 262
Packing unit 1 pc(s)
84 www.dehn.de
POWER SUPPLY SYSTEMS V NH / VA NH
00 264 VA NH00
80 FM
VA NH00 280 FM: Surge arrester with varistor/spark gap based terminal module: for use in
NH fuse holders, size 00, with fault indicator for remote signalling
VA NH00 280 FM
SPD Type according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 280 V
Nominal discharge current (8/20) In 10 kA
Max. discharge current (8/20) Imax 20 kA
Voltage protection level UP ≤ 2.0 kV
Response time tA ≤ 100 ns
Short circuit withstand capability 25 kArms
TOV voltage UT 335 V / 5 sec.
Indication of disconnector red fault indicator (tripping distance 7 mm)
Operating temperature range TU -40°C...+80°C
Mounting on NH fuse holder, size 00
Enclosure material red thermoplastic, UL 94 V-0
Ordering information
Type VA NH00 280 FM
Part No. 900 264
Packing unit 1 pc(s)
www.dehn.de 85
V NH / VA NH POWER SUPPLY SYSTEMS
900 266 VA NH1 3
280
VA NH1 3 280: Surge arrester with varistor/spark gap based terminal module: for use in NH fuse
holders, size 1 ... 3
VA NH1 3 280
SPD Type according to EN 61643-11 Type 2
SPD according to IEC 61643-1 Class II
Classification according to E DIN VDE 0675-6 C
Max. continuous ac voltage UC 280 V
Nominal discharge current (8/20) In 10 kA
Max. discharge current (8/20) Imax 20 kA
Voltage protection level UP ≤ 2.0 kV
Response time tA ≤ 100 ns
Short circuit withstand capability 25 kArms
TOV voltage UT 335 V / 5 sec.
Indication of disconnector red fault indicator (tripping distance 7 mm)
Operating temperature range TU -40°C...+80°C
Mounting on NH fuse holder, size 1-3
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IPX4W
Ordering information
Type VA NH1 3 280
Part No. 900 266
Packing unit 1 pc(s)
86 www.dehn.de
POWER SUPPLY SYSTEMS VA NH in Insulating Enclosure
SURGE ARRESTERS – TYPE 2
SPD Type 2 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class II according to IEC 61643-1;
• Insulating enclosure with approved
VA NH ... surge arresters, consisting of
a varistor series connection, spark gap
and integrated backup fuse
• Degree of protection: IP 55
• With sealable transparent cover
• With pre-embossed cable entries
• Dimension of enclosure:
180 x 180 x 130 mm
VA NH00 280 ... IG: Available as 3- and 4-pole unit; with NH fuse holders, size 00
VA NH00 280 ... IG FM: With NH fuse holders, size 00, with integrated microswitch for remote fault indication
The prewired, system-specific VA NH arrester combinations in the insula- Apart from the standard visual indication via fault indicator, the devices
ting enclosure allow the operator to use the backup-fuse-free installation VA NH 00 280 .... IG FM provide the option of remote signalling from the
of surge arresters, even if there is no NH fuse switch disconnector or NH arrester unit via existing microswitches. As the microswitch works also as
fuse base available in the installation for using VA NH devices. The inte- a floating changeover contact, the remote signal can also be used as a
grated backup fuse is also an important characteristic of the VA NH fami- break or make contact, according to circuit concept.
ly like the series connection of the high-capacity varistor and spark gap.
The advantages of the series connection become clear especially at wide-
ly expanded installations with isolation control.
www.dehn.de 87
VA NH in Insulating Enclosure POWER SUPPLY SYSTEMS
902 385 VA NH00
280 3 IG
VA NH ... IG
902 386 VA NH00
Basic circuit diagram VA NH00 280 3 IG Basic circuit diagram VA NH00 280 4 IG
VA NH00 ... IG: Insulated enclosure with surge arresters VA NH 280 mounted on NH fuse
holders, size 00
Ordering information
Type VA NH00 280 3 IG VA NH00 280 4 IG
Part No. 902 385 902 386
Packing unit 1 pc(s) 1 pc(s)
88 www.dehn.de
POWER SUPPLY SYSTEMS VA NH in Insulating Enclosure
02 375 VA NH00
80 3 IG FM
VA NH ... IG FM
02 376 VA NH00
Basic circuit diagram VA NH00 280 4 IG FM Basic circuit diagram VA NH00 280 3 IG FM
VA NH00 ... IG FM: Insulated enclosure with surge arresters VA NH 280 mounted on NH fuse
holders size 00 with integrated microswitch for remote fault indication
Ordering information
Type VA NH00 280 3 IG FM VA NH00 280 4 IG FM
Part No. 902 375 902 376
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 89
POWER SUPPLY SYSTEMS
90 www.dehn.de
POWER SUPPLY SYSTEMS Netz-AK
MAINS CONNECTION BOX Lightning Current Tested Mains Connection Unit
For integrating power lines into the lightning equipotential bonding. For NAK 35 A ...: Prewired compact unit for 35 A permanent
use in the lightning protection zones concept at boundaries 0A – 2. inued current
discont
NAK 63 A ...: Prewired compact unit for 63 A permanent
inued current
discont
The prewired system-specific arrester units of the Netz AK family unify combination to remain safe even under extreme conditions, the compact
lightning equipotential bonding and surge protection in a compact way. Netz AK units have been subject to extensive tests in the lightning current
test laboratory. The devices of the Netz AK family can be used especially
Using the coordinated lightning current and surge arresters of the for supporting the individual components, if no distribution board is avai-
Red/Line family, the Netz-AK devices come up to the highest requirements lable.
made on these kinds of devices by national and international lightning
protection standards. In order to ensure the construction of the arrester
www.dehn.de 91
Netz-AK POWER SUPPLY SYSTEMS
900 968 NAK 35A
3
Netz-AK 35A
900 966 NAK 35A
inued
discont
NAK 35A 3 Mains
Connection Box 35 A, 3-pole 900 968
NAK 35A 4 Mains
Connection Box 35 A, 4-pole 900 966
L1 L1'
NAK 35A 3+1 Mains
L1 L1' Connection Box 35 A, 3+1-pole 900 967
L2 L2' L2 L2'
L3 L3' L3 L3'
N N'
N N'
PE/PA PE PE/PA PE
Basic circuit diagram NAK 35A 3+1 Basic circuit diagram NAK 35A 4
NAK 35A ...: Prewired compact unit consisting of lightning current arrester (Type 1 / Class I / B)
and surge arrester (Type 2 / Class II / C) for nominal load currents of 35 A
Ordering information
Type NAK 35A 3 NAK 35A 4 NAK 35A 3+1
Part No. 900 968 900 966 900 967
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
92 www.dehn.de
POWER SUPPLY SYSTEMS Netz-AK
00 965 NAK 63A
Netz-AK 63A
00 964 NAK 63A
00 969
+1
NAK 63A
L1 L1' L1 L1'
NAK 63A 3+1 Mains
Connection Box 63 A, 3+1-pole 900 969
L2 L2' L2 L2'
L3 L3' L3 L3'
N N'
Basic circuit diagram NAK 63A 3 Basic circuit diagram NAK 63A 4
NAK 63A ...: Prewired compact unit consisting of lightning current arrester (Type 1 / Class I / B)
and surge arrester (Type 2 / Class II / C) for nominal load currents of 63 A
Ordering information
Type NAK 63A 3 NAK 63A 4 NAK 63A 3+1
Part No. 900 965 900 964 900 969
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 93
Netz-AK TAB POWER SUPPLY SYSTEMS
Lightning Current Arrester in Insulating Enclosure MAINS CONNECTION BOX
For integrating power lines into the lightning equipotential bonding. For
use in the lightning protection zones concept at boundaries 0A – 1.
NAK TAB 3: Mains connection box for use upstream of supply meters in TN-C systems
NAK TAB 4: Mains connection box for use upstream of supply meters in TN(C)-S systems
NAK TAB 3+1: Mains connection box for use upstream of supply meters in TT- and TN(C)-S systems
The devices of the Netz AK TAB family have been developed especially for rents. The leakage current free spark gap based arresters DEHNport Maxi
application upstream of supply meters according to national regulations and DEHNgap B/n fulfil the requirements on lightning current arresters
(e.g. Germany: VDEW guidelines) for using protective devices in primary upstream of supply meters. With a discharge capacity of 100 kA (10/350)
power supplies, where the prewired and approved lightning current arres- all Netz AK TAB devices are designed for the max. lightning protection
ters DEHNport Maxi and DEHNgap B/n are used. The patented RADAX- level. The N-PE lightning current arrester DEHNgap B/n integrated in Netz
Flow technology for extinction and limitation of follow currents provides AK TAB 3+1 has been developed especially as a total current arrester for
the highest system availability possible. With a follow current extinguis- installation between neutral and protective conductor in TT systems. The
hing capability of 50 kArms DEHNport Maxi isolates mains follow currents “3+1” unit DEHNgap B/n fulfils the requirements for protection of per-
of 50 Hz safely without causing an interruption within the installation. sons and material assets in correspondence with national and internatio-
Thus a disconnecting selectivity is provided even at low nominal fuse cur- nal regulations on installation.
94 www.dehn.de
POWER SUPPLY SYSTEMS Netz-AK TAB
02 492 NAK TAB
NAK TAB
02 494 NAK TAB
02 493
+1
NAK TAB
NAK TAB 3
Connection Box TAB, 3-pole
NAK TAB 4
Connection Box TAB, 4-pole
Mains
902 492
Mains
902 494
L1 L2 L3 N
NAK TAB 3+1 Mains
Connection Box TAB, 3+1-pole 902 493
L1 L2 L3 N
Basic circuit diagram NAK TAB 3+1 Basic circuit diagram NAK TAB 4
NAK TAB 3: Mains connection box for use upstream of meters in TN-C systems
NAK TAB 4: Mains connection box for use upstream of meters in TN(C)-S systems
NAK TAB 3+1: Mains connection box for use upstream of meters in TT and TN(C)-S systems
Ordering information
Type NAK TAB 3 NAK TAB 4 NAK TAB 3+1
Part No. 902 492 902 494 902 493
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 95
POWER SUPPLY SYSTEMS
96 www.dehn.de
POWER SUPPLY SYSTEMS DEHNrail
SURGE ARRESTERS – TYPE 3 Two-pole Surge Arrester
SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Two-pole surge protection with control
device and disconnector
• Visual function indication (green), visual
fault indication (red)
• Floating remote signalling contact
(break contact) for fault indication (no
simultaneous disconnection from mains)
The two-pole surge arresters of the DEHNrail family have been developed DEHNrail devices already includes the
especially for protection of terminal equipment in industrial electronic approved disconnector. This isolates an
systems. Adjusted to this kind of environment, the arresters have been overloaded circuit without interrupting
designed for 35 mm DIN rails. The low protection level as well as the com- the supply circuit. Apart from the stan-
prehensive protection against common-mode and differential-mode inter- dard visual indication with a green
ferences is characterising for DEHNrail devices. In order to provide the low light for each phase as well as a red
protection levels in an optimal way for the terminal equipment to be pro- light for fault indication, DEHNrail
tected, the device has been designed with input and output terminals for devices provide a 2-pole terminal for
through-wiring. Thus DEHNrail adapts itself ideally to the cable run remote signalling.
upstream of the terminal equipment without requiring additional termi-
nal blocks for the outgoing cables. The very compact design of the
www.dehn.de 97
DEHNrail POWER SUPPLY SYSTEMS
901 100 DR 230
FML
DR FML
901 101 DR 120
FM FM
DR 230 FML DEHNrail
230 FML, 230 V 901 100
DR 120 FML DEHNrail
120 FML, 120 V 901 101
DR 60 FML DEHNrail
L(N) L(N) 60 FML, 60 V
DR 48 FML
901 102
DEHNrail
48 FML, 48 V 901 103
J DR 24 FML
24 FML, 24 V
DEHNrail
901 104
J
N (L) N (L)
PE PE
DR ... FML: Two-pole surge arrester with control device and disconnector
Ordering information
Type DR 230 FML DR 120 FML DR 60 FML DR 48 FML DR 24 FML
Part No. 901 100 901 101 901 102 901 103 901 104
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
98 www.dehn.de
POWER SUPPLY SYSTEMS DEHNrail 230 3N
SURGE ARRESTERS – TYPE 3 Four-pole Surge Arrester
SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Four-pole surge protection with control
device and disconnector
• Visual function indication for the three
phase conductors (green) and visual
fault indication (red)
• Floating remote signalling contact
(break contact) for fault indication (no
simultaneous disconnection from mains)
The 4-pole surge arrester DEHNrail 230 3N has been developed especially through-wiring. Thus DEHNrail 230 3N adapts itself ideally to the cable
for protection of 3-phase terminal equipment in industrial electronic sys- run upstream of the terminal equipment without requiring additional ter-
tems. Adjusted to this kind of environment, the arrester has been desig- minal blocks. The very compact design of DEHNrail 230 3N already in-
ned for 35 mm DIN rails. The low protection level as well as the compre- cludes the approved disconnector. This isolates an overloaded circuit with-
hensive protection against common-mode and differential-mode interfe- out interrupting the supply circuit. Apart from the standard visual indi-
rences is characterising for DEHNrail 230 3N. In order to provide the low cation with a green light for each phase as well as a red light for fault
protection levels in an optimal way for the terminal equipment to be pro- indication, DEHNrail 230 3N provides a 2-pole terminal for remote signal-
tected, the device has been designed with input and output terminals for ling.
www.dehn.de 99
DEHNrail 230 3N POWER SUPPLY SYSTEMS
901 130 DR 230
3N FML
J J J
Def.
N FM
DR 230 3N FML: Four-pole surge arrester with control device and disconnector
DR 230 3N FML
SPD Type according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230/400 V
Max. continuous ac voltage UC 255/440 V
Nominal load current ac IL 16 A
Nominal discharge current (8/20) [L-N] In 3 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 6 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level [L-N] UP ≤ 1.25 kV
Voltage protection level [L/N-PE] UP ≤ 1.5 kV
Response time [L-N] tA ≤25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector red light
Operating state indication green light
Operating temperature range TU -40°C...+80°C
Cross-sectional area min. 0.5 mm2 solid / flexible
Cross-sectional area max. 4 mm2 stranded / flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 3 mods., DIN 43880
Type of remote signalling contact break contact
Switching capacity ac 250 V/0.5 A
Switching capacity dc 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid / flexible
Ordering information
Type DR 230 3N FML
Part No. 901 130
Packing unit 1 pc(s)
100 www.dehn.de
POWER SUPPLY SYSTEMS Mains Filter
SURGE ARRESTERS – TYPE 3 NF 10
NF 10 mains filter is the ideal completion of surge protection for industri- tion. The separate input and output terminals of the mains filter ensure
al terminal equipment. Being a DIN rail mountable device, the mains that the protective effect of the device is provided optimally to the equip-
filter can be ideally installed downstream of surge protective devices (e.g. ment to be protected. This allows also the realisation of requirements on
DEHNrail 230 FML). This provides protection against balanced and unba- electromagnetic compatibility which exceeds surge protection for con-
lanced induced high-frequency interferences in addition to surge protec- struction of control systems and installations.
12 254 NF 10
NF 10 Mains
ilter 10 A 912 254
L1 L1
mains SPD
N N
PE PE
NF 10: Mains filter for protection against balanced and unbalanced interferences
NF 10
Nominal voltage ac UN 230 V
Nominal load current ac IL 10 A
Discharge current (at UN) ≤ 3.5 mA
Attenuation at f = 1 MHz, balanced > 64 dB
Attenuation at f = 1 MHz, unbalanced > 69 dB
Total circuit capacity [L-N] 660 nF
Total circuit capacity [L (N)-PE] 66 nF
Total circuit inductance 1.8 mH per line
Backup fuse 10 A gL/gG
Operating temperature range -25°C...+40°C
Cross-sectional area min. 2.5 mm2 stranded, max. 4 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material thermoplastic GF (polycarbonate)
Degree of protection IP 20
Dimension 110 x 45 x 75 mm
Ordering information
Type NF 10
Part No. 912 254
Packing unit 1 pc(s)
www.dehn.de 101
SPS Protector POWER SUPPLY SYSTEMS
Two-pole Surge Arrester with Filter SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Surge protection with control device
and disconnector
• Interference suppressor filter with
increased attenuation
• Installed into a shielded enclosure
• Visual function indication (green) and
floating remote signalling contact
(break contact) for fault indication
SPS Protector includes surge protection and interference suppressor filter the device to be protected. The metal enclosure of SPS Protector ensures
in a compact construction. Therefore the device is ideal for protection of that the high-frequency interferences are conducted without interfering
sensitive terminal equipment in industrial automation (e.g. a programm- with other devices close the installation. The compact construction of SPS
able logic control “PLC“). The coordinated functions of surge protection Protector already includes the approved disconnector. In case of over-
and filter complement one another and prevent the core saturation of the loads, this isolates the arrester without interrupting the supply circuit.
filter at high-energy transients. The separate input and output terminals Apart from the green light, SPS Protector offers also a standard optional
ensure in an optimal way that the high protective effect is provided for remote signalling.
102 www.dehn.de
POWER SUPPLY SYSTEMS SPS Protector
12 253 SPS PRO
L L'
J
N J N'
PE PE
SPS PRO
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous voltage ac UC 255 V
Nominal load current ac IL 3A
Nominal discharge current (8/20) [L-N] In 3 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 6 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level [L-N] UP ≤ 0.8 kV
Voltage protection level [L/N-PE] UP ≤ 1.0 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Short circuit withstand capability at max. mains-side overcurrent protection 6 kArms
Indication of disconnector green light off
Operating state indication green light
Operating temperature range TU -10°C...+40°C
Cross-sectional area min. 0.14 mm2 solid / flexible
Cross-sectional area max. 2.5 mm2 stranded / flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material aluminium, red powder coating
Degree of protection IP 20
Dimension 7 mods., DIN 43880
Type of remote signalling contact break contact
Switching capacity ac 250 V / 0.5 A
Switching capacity dc 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid / flexible
Mains filter according to DIN VDE 0565 Part 3
Attenuation at f = 1 MHz balanced ≥ 73 dB
Attenuation at f = 1 MHz unbalanced ≥ 45 dB
Ordering information
Type SPS PRO
Part No. 912 253
Packing unit 1 pc(s)
www.dehn.de 103
DEHNsafe POWER SUPPLY SYSTEMS
Surge Arrester for Cable Ducts SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11;
Classification C according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Two-pole surge protection for 230 V
terminal devices
• For use in wiring sockets and cable ducts
• Increased safety thanks to distinctive
Y protective circuit
• Multiple visual function indication
• Programmable acoustic function
• Terminals for through-wiring
• Independent from the design of socket
outlets
Especially the flexible application of DEHNsafe surge arresters inspires the For covering, a triple TAE cover plate is used,
users. DEHNsafe is a two-pole surge protective device for 230 V terminal made by any manufacturer of switch program-
equipment for installation in cable ducts, but also in flat wiring sockets. mes. Thus DEHNsafe can adapt itself ideally to
This is possible thanks to the minor installation depth of only 31 mm. every socket outlet design.
DEHNsafe includes a control device and a thermally based disconnector. The two available terminals for L, N and PE allow
In addition to a visual function, indication the device provides a pro- through-wiring. Thus the surge protection is
grammable acoustic fault indication. With such an acoustic signal, the situated in parallel to the circuit to be protected.
fault indication can be programmed for three different functions: This does not necessarily interrupt the circuit to
– Acoustic fault indication, be protected by the surge protection due to eventual overloads at
DEHNsafe. DEHNsafe surge arresters provide the users with a green and
– Test function,
red coloured light for visual control of the protective device.
– Muting of the acoustic signal
104 www.dehn.de
POWER SUPPLY SYSTEMS DEHNsafe
24 370 DSA 230
A
L PE N
DSA 230 LA: Surge protective device for cable ducts and wiring sockets
DSA 230 LA
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous ac voltage UC 255 V
Nominal load current IL 16 A
Nominal discharge current (8/20) [L-N] In 3 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 6 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level [L-N] UP ≤ 1.5 kV
Voltage protection level [L/N-PE] UP ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector red light + acoustic signal
Operating state indication green light
Switch -function test / -acoustic signal off
Operating temperature range TU -25°C...+40°C
Cross-sectional area max. 2.5 mm2 stranded / 2.5 mm2 flexible
Mounting on supporting ring (Ø60 mm) for installation into switchboxes, depth 40 mm
Enclosure material grey thermoplastic, UL 94 V-2
Degree of protection IP 20
Cover TAE
Ordering information
Type DSA 230 LA
Part No. 924 370
Packing unit 1 pc(s)
Single unit, alpha exclusive Single unit, alpha exclusive AR1 STW Covering
Frame for DEHNsafe, studio white 924 328
www.dehn.de 105
DEHNflex POWER SUPPLY SYSTEMS
Flexible Protection for Terminal Equipment SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Two-pole surge protection with control
device and disconnector
• More safety thanks to distinctive
Y-protective circuit
• Acoustic fault indication
• Compact design
Already the name of the DEHNflex family points to the nearly unlimited even if phase and neutral conductor can not be assigned definitely. Apart
application possibilities of the devices. Being 2-pole surge arresters, the from the powerful Y-circuit, even a disconnector and an acoustic fault
compact modules are suitable for protecting electronic consumers in final indication can still be installed into the compact enclosure. Whether in
circuits. The design has been adapted to the most common installation cable ducts, flush-mounted systems, branching boxes or in device tubs –
sites, i.e. cable ducts and wiring sockets. DEHNflex devices show very DEHNflex can always be installed in the right place close to terminal
impressively that small and compact sizes do not necessarily mean a low equipment.
capacity performance. The distinctive Y-protective circuit is always safe,
106 www.dehn.de
POWER SUPPLY SYSTEMS DEHNflex
24 396 DFL M
55
J J
N PE L
DFL M: Surge arrester for all kinds of installation systems on terminal equipment level; compact
dimension
DFL M 255
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous voltage ac UC 255 V
Nominal discharge current (8/20) [L-N] In 1.5 kA
Nominal discharge current (8/20) [L+N-PE] In 3 kA
Combined impulse [L-N] UOC 3 kV
Combined impulse [L+N-PE] UOC 6 kV
Voltage protection level [L-N] UP ≤ 1.25 kV
Voltage protection level [L/N-PE] UP ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector acoustic signal on
Operating temperature range TU -25°C...+40°C
Terminal wires 1 mm2, length 120 mm
Enclosure material red thermoplastic, UL 94 V-2
Degree of protection of installed device IP 20
Dimension 36 x 62 x 19 mm
Ordering information
Type DFL M 255
Part No. 924 396
Packing unit 1 pc(s)
www.dehn.de 107
DEHNflex POWER SUPPLY SYSTEMS
924 389 DFL A 255
L DFL A 255
A
DEHNflex
924 389
J J
PE
DFL A: Surge arrester for all kinds of installation systems on terminal equipment level; with test
function
DFL A 255
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous voltage ac UC 255 V
Nominal discharge current (8/20) [L-N] In 3 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 6 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level [L-N] UP ≤ 1.25 kV
Voltage protection level [L/N-PE] UP ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector acoustic signal on
Operating temperature range TU -25°C...+40°C
Terminal wires 1 mm2, length 120 mm
Enclosure material red thermoplastic, UL 94 V-2
Degree of protection of installed device IP 20
Dimension 36 x 62 x 19 mm
Ordering information
Type DFL A 255
Part No. 924 389
Packing unit 1 pc(s)
108 www.dehn.de
POWER SUPPLY SYSTEMS DEHNflex
24 395 DFL D 255
DFL D 255
D
DEHNflex
924 395
L
J J
PE
DFL D: Surge arrester for all kinds of installation systems on terminal equipment level; with test
function; allows through-wiring
DFL D 255
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous voltage ac UC 255 V
Nominal load current ac IL 16 A
Nominal discharge current (8/20) [L-N] In 3 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 6 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level [L-N] UP ≤ 1.25 kV
Voltage protection level [L/N-PE] UP ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector acoustic signal on
Operating temperature range TU -25°C...+40°C
Terminal wires 2.5 mm2, length 120 mm
Enclosure material red thermoplastic, UL 94 V-2
Degree of protection of installed device IP 20
Dimension 36 x 62 x 19 mm
Ordering information
Type DFL D 255
Part No. 924 395
Packing unit 1 pc(s)
www.dehn.de 109
STC Module POWER SUPPLY SYSTEMS
Surge Arrester for Socket Outlets SURGE ARRESTERS – TYPE 3
with Earth Contact SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Two-pole surge protection with control
device and disconnector
• Acoustic fault indication with optional
test function
• For installation upstream of conventio-
nal socket outlets with earth contact
• Independent from the design of the
socket outlets used
The popular STC surge protection module presents itself modestly. Being vides an acoustic fault indication with optional manual test function. As
a two-pole surge arrester, the module can be installed in parallel to the surge protection module is installed in parallel to the socket outlet,
conventional socket outlets with earth contact. Thus, the STC surge pro- the power supply of the connected consumer remains uninterrupted, even
tection module adapts itself to every design of socket outlets with earth if the surge arrester is overloaded.
contact. In addition to a thermal disconnector, the protective device pro-
110 www.dehn.de
POWER SUPPLY SYSTEMS STC Module
24 350 STC 230
PE
STC 230: Two-pole surge arrester for snapping onto socket outlets with earth contact
STC 230
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous ac voltage UC 255 V
Nominal discharge current (8/20) [L-N] In 2.5 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 5 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level [L-N] UP ≤ 1.25 kV
Voltage protection level [L/N-PE] UP ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Operating temperature range TU -25°C...+40°C
Terminal wires 1 mm2, 100 mm long
Mounting on conventional socket outlets with earth contact
Enclosure material grey thermoplastic, UL 94-V-2
Degree of protection of installed device IP 20
Dimension 53 x 53 x 32
Indication of disconnector acoustic signal on
Ordering information
Type STC 230
Part No. 924 350
Packing unit 1 pc(s)
www.dehn.de 111
VC 280/2 POWER SUPPLY SYSTEMS
Compact Protection for Terminal Equipment SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Two-pole surge protection with control
device and disconnector
• Complete surge protective circuit for
devices with ac power supply
• More safety thanks to distinctive
Y-protective circuit
• Floating remote signalling contact (break
contact) with test option for fault indica-
tion
• For soldering on printed circuit boards
(PCBs)
VC 280 2: Surge protective mains module for installation For protection of electronic equipment against surges. For installation
into the terminal equipment to be protected into enclosures or directly into the device to be protected. German
design patent.
Small-sized, but still equipped with all required characteristics – this is a device for optional testing of the fault indication has been integrated
surge arrester VC 280/2. The two-pole module includes the distinctive into the devices. With VC 280/2, electronic equipment can be protected
Y-protective circuit, control device and disconnector and floating remote safely against surges. Providing solders, the protection can be installed
signalling contact. This means the highest compact safety possible. Even directly into the device on PCBs.
112 www.dehn.de
POWER SUPPLY SYSTEMS VC 280/2
00 471 VC 280 2
J J
11
FM
12
VC 280 2: Surge protective mains module for installation into the terminal device to be protected
VC 280 2
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous ac voltage UC 280 V
Nominal discharge current (8/20) [L-N] In 3 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 6 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level [L-N] UP ≤ 1.25 kV
Voltage protection level [L/N-PE] UP ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector break contact
Operating temperature range UT -25°C...+40°C
Mounting on printed circuit board
Enclosure material red thermoplastic, UL 94 V-2
Degree of protection IP 20
Dimension 32 x 24 x 15 mm
Type of remote signalling contact break contact
Switching capacity ac 250 V / 0.5 A
Switching capacity dc 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Ordering information
Type VC 280 2
Part No. 900 471
Packing unit 1 pc(s)
www.dehn.de 113
SF Protector / S Protector POWER SUPPLY SYSTEMS
Surge Protective Adapter SURGE ARRESTERS – TYPE 3
SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Surge protection with control device and
disconnector
• Visual function indication (green) and
visual fault indication (red)
• Mains filter (SF Protector only)
• More safety thanks to distinctive
Y-protective circuit
The surge protective adapters of the S/SF Protector family protect electro- alliance between surge protection and filter prevents the core saturation
nic consumers in final circuits against surges. In SF Protector, the high- of the filter at high-energy transients. With a nominal current carrying
capacity surge protective circuit of S Protector has been amended by an capacity of 16 A, S and SF Protector can be used flexibly in final electrical
interference suppressor filter with balanced and unbalanced effect. This circuits. The distinctive Y-protective circuit takes the lacking assignment of
phase and neutral conductor in conventional socket outlets with earth
contact into consideration. The integrated disconnector makes a further
contribution for the safety of devices and equipment. The standard green
and red lights inform the user about the present operating state of the
surge protective devices.
114 www.dehn.de
POWER SUPPLY SYSTEMS SF Protector / S Protector
09 821 S PRO
PRO S-
L/N
rotector+B247 909 821
red
L'/N'
PE green PE
N'/L'
N/L
S PRO
SPD according ot EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous ac voltage UC 255 V
Nominal load current ac IL 16 A
Nominal discharge current (8/20) [L-N] In 2.5 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 5 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level Up ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector red light
Operating state indication green light
Operating temperature range TU -25°C...+40°C
Mounting plug-in system with earth contact DIN 49440 / DIN 49441
Enclosure material pure white thermoplastic, UL 94 V-2
Degree of protection IP 20
Dimension 128 x 71 x 40 mm
Approvals, Certifications VDE
Ordering information
Type S PRO
Part No. 909 821
Packing unit 1 pc(s)
www.dehn.de 115
SF Protector / S Protector POWER SUPPLY SYSTEMS
909 820 SF PRO
red
L'/N'
PE green PE
N'/L'
N/L
SF PRO
SPD according ot EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous ac voltage UC 255 V
Nominal load current ac IL 16 A
Nominal discharge current (8/20) [L-N] In 2.5 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 5 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level Up ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 6 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector red light
Operating state indication green light
Operating temperature range TU -25°C...+40°C
Mounting plug-in system with earth contact DIN 43440 / DIN 49441
Enclosure material pure white thermoplastic, UL 94 V-2
Degree of protection IP 20
Dimension 128 x 71 x 40 mm
Approvals, Certifications VDE
Mains filter acc. to DIN VDE 0565 Part 3
Attenuation at f = 1 MHz balanced ≥ 54 dB
Attenuation at f = 1 MHz unbalanced ≥ 42 dB
Ordering information
Type SF PRO
Part No. 909 820
Packing unit 1 pc(s)
116 www.dehn.de
POWER SUPPLY SYSTEMS SFL Protector
SURGE ARRESTERS – TYPE 3 Surge Protective Multiple Socket Outlet
SPD Type 3 according to EN 61643-11;
Classification D according to E DIN VDE 0675-6;
with Filter
SPD Class III according to 61643-1;
• Surge protection with control device
and disconnector
• Interference suppressor filter
• More safety thanks to distinctive
Y-protective circuit
• Mains switch with function indication
• Visual fault indication (red)
SFL Protector completes the various Red/Line programme of surge pro- balanced high-frequency interferences. With a nominal current carrying
tective devices. The connection between surge protection and mains filter capacity of 16 A, SFL Protector can be used flexibly in final electrical
turns the 5-fold socket outlet into a powerful device for protection of circuits. The distinctive Y-protective circuit takes the lacking assignment of
electronic consumers in final electrical circuits. The coordinated functions phase and neutral conductor in conventional socket outlets with earth
of surge protection and filter complement one another and prevent the contact into consideration. The standard green and red lights inform the
core saturation of the filter at high-energy transients. The integrated user at a glance about the present operating state of the surge protective
mains filter has been optimised for protection against balanced and un- device.
www.dehn.de 117
SFL Protector POWER SUPPLY SYSTEMS
912 260 SFL PRO
PE
N/L
SFL PRO: Multiple socket outlet with surge protection and mains filter
SFL PRO
SPD according to EN 61643-11 Type 3
SPD according to IEC 61643-1 Class III
Classification according to E DIN VDE 0675-6 D
Nominal voltage ac UN 230 V
Max. continuous ac voltage UC 255 V
Nominal load current ac IL 16 A
Nominal discharge current (8/20) [L-N] In 3 kA
Nominal discharge current (8/20) [L+N-PE] In 5 kA
Combined impulse [L-N] UOC 6 kV
Combined impulse [L+N-PE] UOC 10 kV
Voltage protection level UP ≤ 1.5 kV
Response time [L-N] tA ≤ 25 ns
Response time [L/N-PE] tA ≤ 100 ns
Max. mains-side overcurrent protection 16 A gL/gG or B 16 A
Short circuit withstand capability
at mains-side overcurrent protection with 16 A gL/gG 1.5 kArms
TOV voltage [L-N] UT 335 V / 5 sec.
TOV voltage [L/N-PE] (I) UT 400 V / 5 sec.
TOV voltage [L/N-PE] (II) UT 1200 V + U0 / 200 ms
Indication of disconnector red light
Operating state indication green light
Operating temperature range TU -25°C...+40°C
Connecting cable length: 200 cm
Quantity of socket outlets 5
Mounting on plug-in system with earth contact DIN 49440 / DIN 49441
Enclosure material black/anthracite thermoplastic, UL 94 V-2
Degree of protection IP 20
Dimension 560 x 55 x 47 mm
Approvals, Certifications VDE
Mains filter acc. to DIN VDE 0565 Part 3
Attenuation at f = 1 MHz balanced ≥ 43 dB
Attenuation at f = 1 MHz unbalanced ≥ 48 dB
Ordering information
Type SFL PRO
Part No. 912 260
Packing unit 1 pc(s)
118 www.dehn.de
POWER SUPPLY SYSTEMS NSM Protector
SURGE ARRESTERS – TYPE 3 Surge Protective Socket Outlet
SPD Type 3 according to EN 61643-1;
Classification D according to E DIN VDE 0675-6;
SPD Class III according to IEC 61643-1;
• Surge protection with control device
and disconnector
• More safety thanks to distinctive
Y-protective circuit
• Visual function indication (green) and
visual fault indication (red)
• With supporting ring (dimension:
60 mm) for installation into switch-
boxes Ø60 mm, depth: 40 mm
The devices of the NSM Protector family include surge protection and NSM Protector family. The distinctive Y-protective circuit takes the often
socket outlet with earth contact in one device. The two-pole surge lacking assignment of phase and neutral conductors in final circuits into
arresters are designed especially for protection of electronic consumers in consideration. The integrated disconnector makes a further contribution
final circuits. The very compact construction of NSM Protector devices for safety of devices and installations. The standard green and red lights
already includes the approved disconnector. This isolates overloaded inform the user about the operating state of the surge protective devices.
surge arresters without interrupting the supply circuit. The low protection
level as well as the comprehensive protection against common-mode and
differential mode interferences is characterising for the devices of the
www.dehn.de 119
NSM Protector POWER SUPPLY SYSTEMS
924 335 NSM PRO
TW
NSM PRO
924 337 NSM PRO
L/N L/N
NSM PRO TW NSM-
Protector DELTA profile, titan white 924 335
NSM PRO SI NSM-
Protector DELTA profile, silver 924 337
NSM PRO AZ NSM-
Protector DELTA profile, anthracite 924 339
NSM PRO EW NSM-
Protector DELTA profile, studio white 924 342
J J
PE
Ordering information
Type NSM PRO TW NSM PRO SI NSM PRO AZ NSM PRO EW
Part No. 924 335 924 337 924 339 924 342
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
120 www.dehn.de
POWER SUPPLY SYSTEMS DEHNbridge
ACCESSORIES Decoupling Coil
1 DBR 35
2 DBR 63
5
bridge, 35 A 900 121
3
bridge, 63 A 900 122
DBR 35 DBR 63
DBR ...: Decoupling coil with 35 A or 63 A nominal load current carrying capacity
DBR 35 DBR 63
Nominal voltage ac/dc UN 500 V 500 V
Nominal frequency fN 50 Hz 50 Hz
Nominal load current ac IL 35 A 63 A
Nominal inductance LN 15 µH +/- 20% 15 µH +/- 20%
Backup fuse (only required, if not already provided in mains) 35 A gL/gG 63 A gL/gG
Short circuit withstand capability at max. backup fuse 50 kArms 50 kArms
DC resistance approx. 4 mOhm approx. 2 mOhm
Operating temperature range (device with self-heating) TU -40°C...+115°C -40°C...+115°C
Cross-sectional area min. 1.5 mm2 solid / flexible, min. 10 mm2 solid / flexible,
max. 35 mm2 stranded / 25 mm2 flexible max. 50 mm2 stranded / 35 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 2 mods., DIN 43880 4 mods., DIN 43880
Ordering information
Type DBR 35 DBR 63
Part No. 900 121 900 122
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 121
Feed-through Terminal POWER SUPPLY SYSTEMS
DK 35 ACCESSORIES
EN 60947-7-1:1991-10;
based on: E DIN VDE 0675-6:1989-11,-6/A1:1996-03;
DIN VDE 0611-1:1992-08;
• Allows change of the wiring level
• Supports a lightning impulse current
conform installation of arrester
combinations
900 699 DK 35
DK 35 Feed-
through Terminal, 35 mm√ 900 699
DK 35
Nominal voltage ac/dc UN 500 V
Nominal load current ac IL 100 A
Test current according to EN 60947-7-1 125 A
Lightning impulse current (10/350) 100 kA
Backup fuse at application of arrester only ≤ 250 A gL/gG
Backup fuse carrying operating current ≤ 100 A gL/gG
Short circuit withstand capability at max. backup fuse 50 kArms
Operating temperature range TU -40°C...+80°C
Cross-sectional area min. 1.5 mm2 solid / flexible, max. 35 mm2 stranded / 25 mm2 flexible
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0
Degree of protection IP 20
Dimension 1 mod., 43880
Approvals, Certifications UL
Ordering information
Type DK 35
Part No. 900 699
Packing unit 1 pc(s)
122 www.dehn.de
POWER SUPPLY SYSTEMS Insulating Enclosure
ACCESSORIES
309 IGA 10
P54 Insulating
e, 10 mods. 900 309
IGA 10 IP54
Degree of protection IP 54
Tested with lightning currents 3
Type of cover transparent cover
Colour of enclosure grey
Quantity of cable entries 2 x for cables Ø16...32 mm; 3 x for cables Ø8...15 mm
Available installation space 10 mods., DIN 43880
Dimension 235 x 300 x 130 mm
Ordering information
Type IGA 10 IP54
Part No. 900 309
Packing unit 1 pc(s)
www.dehn.de 123
Insulating Enclosure POWER SUPPLY SYSTEMS
902 485 IGA 6
IP54
Ordering information
Type IGA 6 IP54
Part No. 902 485
Packing unit 1 pc(s)
IGA 11 IP54
IGA 11 IP54
Insulating Enclosure 11 mods.
902 486
IGA 11 IP54
Degree of protection IP 54
Tested with lightning currents 3
Type of cover transparent cover
Colour of enclosure grey
Quantity of cable entries 2 self-sealing grommets for cables Ø16...32 mm
Available installation space 11 mods., DIN 43880
Dimension 313 x 313 x 210 mm
Ordering information
Type IGA 11 IP54
Part No. 902 486
Packing unit 1 pc(s)
124 www.dehn.de
POWER SUPPLY SYSTEMS Busbars / Modular Wiring System
ACCESSORIES
00 610 MVS 1 4
MVS 1 4 MVS 1 4
Single-phase unit 3
MVS 1 4 Busbar
ingle-phase, 4-pole 900 610
Ordering information
Type MVS 1 4
Part No. 900 610
Packing unit 1 pc(s)
Ordering information
Type MVS 1 8
Part No. 900 611
Packing unit 1 pc(s)
Ordering information
Type MVS 1 57
Part No. 900 612
Packing unit 1 pc(s)
00 616
6
MVS 2 7
MVS 2 7 16 MVS 2 7 16
Two-phase unit 3
MVS 2 7 16
hase, 16-pole
Busbar 2-
900 616
Number of contact studs 7 poles
Max. installation width 16 mods., DIN 43880
Nominal cross section 16 mm2
Ordering information
Type MVS 2 7 16
Part No. 900 616
Packing unit 1 pc(s)
www.dehn.de 125
Busbars / Modular Wiring System POWER SUPPLY SYSTEMS
900 619 MVS 2 7
22
MVS 2 7 22 MVS 2 7 22
Two-phase unit 3
Number of contact studs 7 poles MVS 2 7 22 Busbar 2-
phase, 22-pole 900 619
Ordering information
Type MVS 2 7 22
Part No. 900 619
Packing unit 1 pc(s)
MVS 3 6 MVS 3 6
Three-phase unit 3
900 595 MVS 3 6
Ordering information
Type MVS 3 6
Part No. 900 595
Packing unit 1 pc(s)
Three-phase unit 3
Number of contact studs 57 poles MVS 3 57
phase, 57-pole
Busbar 3-
900 613
Ordering information
Type MVS 3 57
Part No. 900 613
Packing unit 1 pc(s)
MVS 3 6 8 MVS 3 6 8
Three-phase unit 3 900 813
8
MVS 3 6
Ordering information
Type MVS 3 6 8
Part No. 900 813
Packing unit 1 pc(s)
MVS 4 56 MVS 4 56
Four-phase unit 3
900 614 MVS 4 56
Ordering information
Type MVS 4 56
Part No. 900 614
Packing unit 1 pc(s)
Four-phase unit 3
Number of contact studs 8 poles MVS 4 8 11 Busbar 4-
phase, 11-pole 900 814
Ordering information
Type MVS 4 8 11
Part No. 900 814
Packing unit 1 pc(s)
126 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS
RJ Connection 205
Accessories 273
www.dehn.de 127
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
0-20 mA, 4-20 mA DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V / 34.8 V BLITZDUCTOR CT 919 623/624 149
(also with HART) +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 26.8 V / 34.8 V BLITZDUCTOR CT 919 523/524 156
+919 506 147
DIN rail, spring terminals 2 5 kA 33 V DEHNconnect RK 919 921 168
compact, space-saving
DIN rail, spring terminals 2 300 A 28 V DEHNconnect RK 919 988 173
compact, space-saving
screwed gland of the screw terminals 2 5 kA 34.8 V DEHNpipe 929 921 253
process field device npt 1/2”
4-20 mA DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V / 34.8 V BLITZDUCTOR CT 919 643/644 152
+919 506 147
(also with HART)
acc. to NAMUR-recom- DIN rail, pluggable screw terminals 2 10 kA 26.8 V / 34.8 V BLITZDUCTOR CT 919 543/544 159
mendation NE 21 or +919 506 147
acc. to EN 61000-4-5, DIN rail, spring terminals 2 5 kA 33 V DEHNconnect RK 919 941 169
open-circuit voltage compact, space-saving
0.5 kV A-A, 1 kV A-PG
DIN rail, compact screw terminals 4 10 kA 26.8 V BLITZDUCTOR VT 918 407 178
screwed gland of the screw terminals 2 5 kA 34.8 V DEHNpipe 929 941 252
process field device M20
ADVANT DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
in-/direct shield earthing
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
AS-i coupling modules via coupling 2x2 10 kA – AS-i surge protective 925 010 249
FK, FK-E, PG, PG-E module module
Binary signals DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6 V – 170 V BLITZDUCTOR CT 919 620-627 149
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6 V – 170 V BLITZDUCTOR CT 919 520-527 156
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 14 V – 170 V DEHNconnect RK 919 920-923 168
space-saving
DIN rail, compact, spring terminals 2 300 A 13 V – 70 V DEHNconnect RK 919 987-990 173
space-saving
Bitbus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
BLN DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 17.8 V BLITZDUCTOR CT 919 642 152
(building level +919 506 147
network) DIN rail, pluggable screw terminals 2 10 kA 17.8 V BLITZDUCTOR CT 919 542 159
+919 506 147
DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 645 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 545 159
+919 506 147
CAN-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
(data line only) +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
128 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice upon Interface
C-Bus (Honeywell) DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
Control Net coax plug-in adapter BNC 1 5 kA 8V UGKF 929 010 220
Delta Net Peer Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
Device Net DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
(data line only) +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
Dupline DIN rail, pluggable screw terminals 2 10 kA 17.8 V BLITZDUCTOR CT 919 542/S –
+919 506 147
E-Bus (Honeywell) DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 645 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 545 159
+919 506 147
EIB DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 510 148
+919 506 147
bus clamping point wires 2 5 kA 45 V BUStector 925 001 247
ET 200 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
Ex (i) circuits, DIN rail, pluggable screw terminals 2 10 kA 26.8 V / 34.8 V BLITZDUCTOR CT 919 580/581 258
4-20 mA, NAMUR, +919 507 257
HART DIN rail, compact, spring terminals 2 5 kA 30 V DEHNconnect RK 919 960 264
space-saving
screwed gland of the screw terminals 2 5 kA 30 V DEHNpipe 929 960 267
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 961 268
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 963 268
process field device npt 1/2”
wall, metall enclosure screw terminals 2 10 kA 34.8 V ITAK EXI 989 406 261
Ex (i)-RS 485 DIN rail, pluggable screw terminals 2 10 kA 4.2 V BLITZDUCTOR CT 919 583 259
Fieldbus +919 507 257
Fieldbus Foundation DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 34.8 V BLITZDUCTOR CT 919 644 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 34.8 V BLITZDUCTOR CT 919 544 159
+919 506 147
www.dehn.de 129
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
Fieldbus Foundation DIN rail, pluggable screw terminals 2 10 kA 26.8 V / 34.8 V BLITZDUCTOR CT 919 580/581 258
Ex (i) +919 507 257
DIN rail, compact, spring terminals 2 5 kA 30 V DEHNconnect RK 919 960 264
space-saving
screwed gland of the screw terminals 2 5 kA 30 V DEHNpipe 929 960 267
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 961 268
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 963 268
process field device npt 1/2”
wall, metall enclosure screw terminals 2 10 kA 34.8 V ITAK EXI 989 406 261
FIPIO/FIPWAY DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 34.8 V BLITZDUCTOR CT 919 644 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 34.8 V BLITZDUCTOR CT 919 544 159
+919 506 147
FIP I/O DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
FSK DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
Genius I/O Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 14.5 V BLITZDUCTOR CT 919 641 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 14.5 V BLITZDUCTOR CT 919 541 159
+919 506 147
DC Power supply + DIN rail, compact screw terminals 2 1 kA 35 V BLITZDUCTOR VT 918 402 181
24 V dc
IEC-Bus (RS 485) DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
INTERBUS-INLINE DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 645 152
(I/O) +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 545 159
+919 506 147
INTERBUS-Loop DIN rail, compact, spring terminals 2 300 A 28 V DEHNconnect RK 919 988 173
space-saving
Interbus-S DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
in-/direct shield earthing
K-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 643 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 543 159
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 33 V DEHNconnect RK 919 941 169
space-saving
KBR-Energiebus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
130 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice upon Interface
CP installations, DIN rail, compact, screw terminals 2 20 kA 3.5 kA 36.8 V BLITZDUCTOR VT KKS 918 421 184
Sensor circuit remote signalling 918 405 186
Anode circuit DIN rail, compact, screw terminals 2 20 kA 3.5 kA 75 V BLITZDUCTOR VT KKS 918 420 183
remote signalling 918 404 185
KNX-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 510 148
+919 506 147
bus clamping point wires 2 5 kA 45 V BUStector 925 001 247
LON DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 640 152
– TP/XF 78 +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 540 159
+919 506 147
– TP/FTT10 and DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 645 152
TP/LPT10 (up to 1 A) +919 506 147
– (up to 1 A) DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 545 159
+919 506 147
– (up to 1.7 A) DIN rail, compact, spring terminals 2 5 kA 55 V DEHNconnect RK 919 942 170
space-saving
– TP/FTT 10 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 671 155
+919 506 147
DIN rail, pluggable screw terminals 2 10 6V BLITZDUCTOR CT 919 571 162
+919 506 147
LUXMATE-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 643 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 543 159
+919 506 147
M-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 645 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 545 159
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 55 V DEHNconnect RK 919 942 170
space-saving
Melsec Net 2 coax plug-in adapter BNC 1 5 kA 8V UGKF 929 010 220
MODBUS DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
MPI Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
N1 LAN DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 671 155
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 571 162
+919 506 147
DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
coax plug-in adapter BNC 1 5 kA –8 V / +1 V UGKF 929 017 221
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
www.dehn.de 131
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
N2 Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 671 155
+919 506 147
(Johnson Controls,
LON, FTT 10) DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 571 162
+919 506 147
Optocoupler- DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6 V – 34.8 V BLITZDUCTOR CT 919 660-663 151
interface +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6 V – 34.8 V BLITZDUCTOR CT 919 560-563 158
+919 506 147
DIN rail, compact screw terminals 4 10 kA 26.8 V BLITZDUCTOR VT 918 400 177
Procontic CS31 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 17.8 V BLITZDUCTOR CT 919 622 149
(RS 232) +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 17.8 V BLITZDUCTOR CT 919 522 156
+919 506 147
Procontic T200 DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
(RS 422) in-/direct shield earthing
PROFIBUS-DP/FMS DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
Plug-in adapter D-Sub 9-pole 4 200 A 7V FS 924 017 232
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
PROFIBUS-DP Ex (i) DIN rail, pluggable screw terminals 2 10 kA 4.2 V BLITZDUCTOR CT 919 583 259
+919 507 257
PROFIBUS-PA DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 34.8 V BLITZDUCTOR CT 919 644 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 34.8 V BLITZDUCTOR CT 919 544 159
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 33 V DEHNconnect 919 941 169
space-saving
screwed gland of the screw terminals 2 5 kA 34.8 V DEHNpipe 929 941 252
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 962 271
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 964 271
process field device npt 1/2”
PROFISBUS-PA Ex (i) DIN rail, pluggable screw terminals 2 10 kA 26.8 V / 34.8 V BLITZDUCTOR CT 919 580/581 258
+919 507 257
DIN rail, compact, spring terminals 2 5 kA 30 V DEHNconnect RK 919 960 264
space-saving
screwed gland of the screw terminals 2 5 kA 30 V DEHNpipe 929 960 267
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 961 268
process field device M20
screwed gland of the wires 2 5 kA 30 V DEHNpipe 929 963 268
process field device npt 1/2”
wall, metall enclosure screw terminals 2 10 kA 34.8 V ITAK EXI 989 406 261
PROFIBUS DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
SIMATIC NET +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
PSM-EG-RS 422 DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
in-/direct shield earthing
PSM-EG-RS 485 DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
in-/direct shield earthing
132 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice upon Interface
Rackbus (RS 485) DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
in-/direct shield earthing
R-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 640 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 540 159
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
RS 485 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
in-/direct shield earthing
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
RS 422, V11 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, screw terminals 5 10 kA 6V BLITZDUCTOR VT 918 401 180
in-/direct shield earthing
Plug-in adapter with/ D-Sub 15-pole 6 2,5 kA 8.5 V USD 924 051/050 238
without data cable
Plug-in adapter D-Sub 15-pole 6 200 A 8V FS 924 016 234
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
S-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
SafetyBUS p DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
SDLC DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
SDLS DIN rail, compact RJ45, screw 4 2,5 kA 7.5 V BLITZDUCTOR VT 918 410 208
terminals
LSA disconnection block, insulation piercing 2 5 kA 7.5 V DPL 907 144 190
type series 2 connecting devices
Securilan-LON-Bus DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 640 152
+919 506 147
(LONWORKS Technology-
Standard Bus based DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 540 159
on Echelon) +919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
www.dehn.de 133
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
SIGMASYS LSA disconnection block, insulation piercing 2 5 kA 80 V DPL 907 124 192
type series2 connecting devices
(Siemens
Fire alarm system) DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 645 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 545 159
+919 506 147
DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 625 149
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 525 156
+919 506 147
SINEC L1 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 14.5 V BLITZDUCTOR CT 919 661 151
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 14.5 V BLITZDUCTOR CT 919 561 158
+919 506 147
SINEC L2 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 570 161
+919 506 147
Plug-in adapter D-Sub 9-pole 4 200 A 7V FS 924 017 232
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
SS97 SINIS (RS 232) DIN rail screw terminals 2 20 kA 2.5 kA 17.8 V BLITZDUCTOR CT 919 622 149
+919 506 147
DIN rail screw terminals 2 10 kA 17.8 V BLITZDUCTOR CT 919 522 156
+919 506 147
SUCONET DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 640 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 540 159
+919 506 147
TELEPERM M DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 14.5 V BLITZDUCTOR CT 919 621 149
Analogue input +919 506 147
DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 623 149
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 14.5 V BLITZDUCTOR CT 919 521 156
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 523 156
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 14 V DEHNconnect RK 919 920 168
space-saving
DIN rail, compact, spring terminals 2 5 kA 33 V DEHNconnect RK 929 921 253
space-saving
LSA disconnection block, insulation piercing 2 5 kA 14 V DPL 907 121 191
type series 2 connecting devices
LSA disconnection block, insulation piercing 2 5 kA 80 V DPL 907 123 191
type series 2 connecting devices
TELEPERM M DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 55.1 V BLITZDUCTOR CT 919 625 149
Binary input/output +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 55.1 V BLITZDUCTOR CT 919 525 156
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 55 V DEHNconnect RK 919 942 170
space-saving
LSA disconnection block, insulation piercing 2 5 kA 29 V DPL 907 124 192
type series 2 connecting devices
134 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice upon Interface
TELEPERMMES100K DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 14.5 V BLITZDUCTOR CT 919 621 149
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 14.5 V BLITZDUCTOR CT 919 521 156
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 14 V DEHNconnect RK 919 920 168
space-saving
LSA disconnection block, insulation piercing 2 5 kA 14 V DPL 907 121 191
type series 2 connecting devices
TELEPERM MFM 100 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 14.5 V BLITZDUCTOR CT 919 641 152
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 14.5 V BLITZDUCTOR CT 919 541 159
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 14 V DEHNconnect RK 919 940 169
space-saving
TELEPERM M DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 623 149
Coupling AG S5 +919 506 147
ET 100 DIN rail, pluggable screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 523 156
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 33 V DEHNconnect RK 919 921 168
space-saving
LSA disconnection block, insulation piercing 2 5 kA 29 V DPL 907 123 191
type series 2 connecting devices
TELEPERM M DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 510 148
Relay output +919 506 147
LSA terminal block, insulation piercing 2 5 kA 180 V DPL 907 220 188
type series 2 connecting devices
Temperature DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 620 149
measurement +919 506 147
PT 100, PT 1000 DIN rail, pluggable screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 520 156
Ni 1000, NTC, PTC +919 506 147
DIN rail, compact, spring terminals 2 5 kA 6V DEHNconnect RK 919 970 172
space-saving
TTL DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 14.5 V BLITZDUCTOR CT 919 621 149
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 14.5 V BLITZDUCTOR CT 919 521 156
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 14 V DEHNconnect RK 919 920 168
space-saving
Plug-in adapter with/ D-Sub 25-pole 4, 9 2.5 kA 12.5 V USD 924 041-045 239
without data cable
Plug-in adapter D-Sub 9-pole 9 100 A 15 V FS 924 019 233
TTY DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 6 V – 26.8 V BLITZDUCTOR CT 919 660-663 151
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 6 V – 26.8 V BLITZDUCTOR CT 919 560-563 158
+919 506 147
DIN rail screw terminals 4 10 kA 26.8 V BLITZDUCTOR VT 918 400 177
Plug-in adapter with/ D-Sub 25-pole 5 2.5 kA 26.5 V USD 924 047/048 240
without data cable
www.dehn.de 135
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
Telecommunication, Telephony
Interface/ Connection Protected Discharge capacity/line Max. dc Part
Signal Mounting on system lines 8/20 µs 10/350 µs voltage SPD No. Page
ADSL DIN rail, pluggable, screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 647 153
approved by German TELEKOM +919 506 147
DIN rail, pluggable, screw terminals 2 20 kA 170 V BLITZDUCTOR CT 919 547 160
approved by German TELEKOM +919 506 147
LSA disconnection block, insulation piercing 2 5 kA 175 V DPL 907 145 189
type series 2 connecting devices
in installation boxes / wires 2 5 kA 170 V DSM 924 271 245
distribution boards
socket outlet adapter, TAE 2 2.5 kA 170 V NT-Proctector 909 958 282
approved by German TELEKOM
in enclosure RJ45, LSA 8x2 2.5 kA, 5 kA 170 V NET-Protector 929 069/070 203
EG NET PRO 19”
DIN rail, compact RJ45, screw 2 2.5 kA 170 V BLITZDUCTOR VT 918 411 209
terminals
Datex-P DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 675 155
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 575 162
+919 506 147
G.703 koax coax plug-in adapter 1.6/5.6 connector 1 300 A 6V DEHNgate 929 040 226
coax plug-in adapter 1.6/5.6 connector 1 5 kA 48 V DEHNgate 929 041 227
G.703 / G.704 LSA terminal block, insulation piercing 2 10 kA 180 V DPL 907 214 195
type series 2 connecting devices
in enclosure RJ45, RJ45 8x8 100 A 30 V NET-Protector 929 037 201
EG NET PRO 19”
Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
HDSL
up to 30 dBm at DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 675 155
600 Ω +919 506 147
DIN rail, pluggable screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 575 162
+919 506 147
up to 15 dBm at LSA disconnection block, insulation piercing 2 5 kA 7.5 V DPL 907 144 190
600 Ω type series 2 connecting devices
ISDN S0 DIN rail, pluggable, screw terminals 2 20 kA 2.5 kA 6V BLITZDUCTOR CT 919 671 155
approved by German TELEKOM +919 506 147
DIN rail, pluggable, screw terminals 2 10 kA 6V BLITZDUCTOR CT 919 571 162
approved by German TELEKOM +919 506 147
surface (with indicator) RJ45 4 2.5 kA 7.5 V DEHNlink 929 024 213
LSA disconnection block, insulation piercing 2 5 kA 7.5 V DPL 907 144 190
type series 2 connecting devices
in installation boxes / wires 4 5 kA 7.5 V DSM 924 270 244
distribution boards
socket outlet adapter RJ 45 4 2.5 kA 6V ISDN-Protector 909 954 283
in enclosure RJ45, LSA 8x2 2.5 kA, 5 kA 7.5 V NET-Protector 929 067/068 202
EG NET PRO 19”
DIN rail, compact RJ45, screw 4 2.5 kA 7.5 V BLITZDUCTOR VT 918 410 208
terminals
in installation boxes / RJ45, screw 4 5 kA 6V DSM 924 274 211
distribution boards terminals
Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
ISDN S2m / U2m DIN rail, pluggable, screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 675 155
approved by German TELEKOM +919 506 147
DIN rail, pluggable, screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 575 162
approved by German TELEKOM +919 506 147
LSA disconnection block, insulation piercing 2 5 kA 7.5 V DPL 907 144 190
type series 2 connecting devices
136 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice upon Interface
Telecommunication, Telephony
Interface/ Connection Protected Discharge capacity/line Max. dc Part
Signal Mounting on system lines 8/20 µs 10/350 µs voltage SPD No. Page
ISDN UK0 / UP0 DIN rail, pluggable, screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 647 153
approved by German TELEKOM +919 506 147
DIN rail, pluggable, screw terminals 2 20 kA 170 V BLITZDUCTOR CT 919 547 160
approved by German TELEKOM +919 506 147
DIN rail, compact, spring terminals 2 5 kA 170 V DEHNconnect RK 919 943 171
space-saving
LSA disconnection block, insulation piercing 2 5 kA 175 V DPL 907 145 189
type series 2 connecting devices
in enclosure RJ45, LSA 8x2 2.5 kA, 5 kA 170 V NET-Protector 929 069/070 203
EG NET PRO 19”
socket outlet adapter, TAE 2 2.5 kA 170 V NT-Protector 909 958 282
approved by German TELEKOM
DIN rail, compact RJ45, screw 2 2.5 kA 170 V BLITZDUCTOR VT 918 411 209
terminals
Modem M1 DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 17.5 V BLITZDUCTOR CT 919 622 149
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 17.5 V BLITZDUCTOR CT 919 522 156
+919 506 147
SHDSL DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 26.8 V BLITZDUCTOR CT 919 675 155
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 26.8 V BLITZDUCTOR CT 919 575 162
+919 506 147
Telephony, DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 647 153
System telephony +919 506 147
e.g. Siemens DIN rail, pluggable screw terminals 2 20 kA 170 V BLITZDUCTOR CT 919 547 160
HICOM, Alcatel +919 506 147
DIN rail, compact, spring terminals 2 5 kA 170 V DEHNconnect RK 919 943 171
space-saving
DIN rail screw terminals 4 10 kA 170 V BLITZDUCTOR VT 918 403 179
surface (with indicator) RJ45, RJ11 2 2.5 kA 170 V DEHNlink 929 027 214
surface (with indicator) RJ45, RJ11 4 2.5 kA 170 V DEHNlink 929 028 214
surface RJ45 2 2.5 kA 170 V DEHNlink 929 080 215
surface RJ12 2 2.5 kA 170 V DEHNlink 919 081 215
LSA disconnection block, insulation piercing 2 5 kA 175 V DPL 907 145 189
type series 2 connecting devices
LSA disconnection block, insulation piercing 2 5 kA 120 V DPL 907 111 194
type series 2 connecting devices
in installation boxes / wires 2 5 kA 170 V DSM 924 271 245
distribution boards
in installation boxes / wires 4 5 kA 170 V DSM 924 272 245
distribution boards
in enclosure RJ45, insulation 8x2 2.5 kA, 5 kA 170 V NET-Protector 929 069/070 203
EG NET PRO 19” piercing connecting devices
in enclosure RJ45, insulation 8x4 2.5 kA, 5 kA 170 V NET-Protector 929 071/072 203
EG NET PRO 19” piercing connecting devices
socket outlet adapter RJ11 2 2.5 kA 170 V FAX-Protector 909 950 286
RJ45 2 909 956 287
TAE 4 909 957 285
DIN rail, compact RJ45, screw 2 2.5 kA 170 V BLITZDUCTOR VT 918 411 209
terminals
www.dehn.de 137
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
Telecommunication, Telephony
Interface/ Connection Protected Discharge capacity/line Max. dc Part
Signal Mounting on system lines 8/20 µs 10/350 µs voltage SPD No. Page
T-DSL DIN rail, pluggable, screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 647 153
approved by German TELEKOM +919 506 147
DIN rail, pluggable, screw terminals 2 20 kA 170 V BLITZDUCTOR CT 919 547 160
approved by German TELEKOM +919 506 147
LSA disconnection block, insulation piercing 2 5 kA 175 V DPL 907 145 189
type series 2 connecting devices
in installation boxes / wires 2 5 kA 170 V DSM 924 271 245
distribution boards
socket outlet adapter, TAE 2 2.5 kA 170 V NT-Protector 909 958 282
approved by German TELEKOM
in enclosure RJ45, LSA 8x2 2.5 kA, 5 kA 170 V NET-Protector 929 069/070 203
EG NET PRO 19”
DIN rail, compact RJ45, screw 2 2.5 kA 170 V BLITZDUCTOR VT 918 411 209
terminals
Universal DIN rail, pluggable, screw terminals 2 20 kA 2.5 kA 170 V BLITZDUCTOR CT 919 647 153
coarse protection approved by German TELEKOM +919 506 147
LSA terminal block, insulation piercing 2 5 kA 180 V DPL 907 220 188
type series 2 connecting devices
LSA terminal block, insulation piercing 20 20 kA 180 V DPL 907 210 195
type series 2 connecting devices
LSA terminal block, insulation piercing 20 10 kA 180 V DPL 907 214 195
type series 2 connecting devices
LSA terminal block, insulation piercing 20 10 kA 180 V DPL 907 215 195
type series 2 connecting devices
138 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice upon Interface
Data Networks
Interface/ Connection Protected Discharge capacity/line Max. dc Part
Signal Mounting on system lines 8/20 µs 10/350 µs voltage SPD No. Page
Arcnet coax plug-in adapter BNC 1 2.5 kA 8V UGKF 929 010 220
ATM Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
in enclosure RJ45 8x8 300 A 6V NET-Protector 929 035/036 201
EG NET PRO 19” LSA 100 A 30 V 929 037 201
flush-mounted Cat. 5 RJ45, LSA 8 300 A 6V DSM 924 263 242
socket outlet
socket outlet adapter RJ45 8 300 A 6V DATA-Protector 909 955 284
Ethernet 10 Base 2 coax plug-in adapter BNC 1 5 kA –8 V / +1 V UGKF 929 017 221
(Thinwire)
Ethernet 100 Base TX Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
in enclosure RJ45 8x8 300 A 6V NET-Protector 929 035/036 201
EG NET PRO 19” LSA 100 A 30 V 929 037 201
flush-mounted Cat. 5 RJ45, LSA 8 300 A 6V DSM 924 263 242
socket outlet
socket outlet adapter RJ45 8 300 A 6V DATA-Protector 909 955 284
Ethernet 10 Base T LSA disconnection block, LSA 2 5 kA 7.5 V DPL 907 144 190
type series2
in installation boxes / RJ45, screw 4 5 kA 6V DSM 924 274 211
distribution boards terminals
FDDI, CDDI LSA disconnection block, LSA 2 5 kA 7.5 V DPL 907 144 190
type series 2
Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
in enclosure RJ45 8x8 300 A 6V NET-Protector 929 035/036 201
EG NET PRO 19” LSA 100 A 30 V 929 037 201
flush-mounted Cat. 5 RJ45, LSA 8 300 A 6V DSM 924 263 242
socket outlet
socket outlet adapter RJ45 8 300 A 6V DATA-Protector 909 955 284
Gigabit Ethernet Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
in enclosure RJ45 8x8 300 A 6V NET-Protector 929 035/036 201
EG NET PRO 19” LSA 100 A 30 V 929 037 201
flush-mounted Cat. 5 RJ45, LSA 8 300 A 6V DSM 924 263 242
socket outlet
Industrial Ethernet LSA disconnection block, LSA 2 5 kA 7.5 V DPL 907 144 190
type series 2
Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
in enclosure RJ45 8x8 300 A 6V NET-Protector 929 035/036 201
EG NET PRO 19” LSA 100 A 30 V 929 037 201
flush-mounted Cat. 5 RJ45, LSA 8 300 A 6V DSM 924 263 242
socket outlet
socket outlet adapter RJ45 8 300 A 6V DATA-Protector 909 955 284
Industrial Ethernet, coax plug-in adapter N-Connector 1 5 kA –8 V / +1 V UGKF 929 012 222
H1
Power over Ethernet Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
(POE) Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
www.dehn.de 139
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
Data Networks
Interface/ Connection Protected Discharge capacity/line Max. dc Part
Signal Mounting on system lines 8/20 µs 10/350 µs voltage SPD No. Page
Token Ring LSA disconnection block, LSA 2 5 kA 7.5 V DPL 907 144 190
type series 2
Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
in enclosure RJ45 8x8 300 A 6V NET-Protector 929 035/036 201
EG NET PRO 19” LSA 100 A 30 V 929 037 201
flush-mounted Cat. 5 RJ45, LSA 8 300 A 6V DSM 924 263 242
socket outlet
socket outlet adapter RJ45 8 300 A 6V DATA-Protector 909 955 284
V 24 (RS 232 C) DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 14.5 V BLITZDUCTOR CT 919 621 149
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 14.5 V BLITZDUCTOR CT 919 521 156
+919 506 147
DIN rail, compact, spring terminals 2 5 kA 14 V DEHNconnect RK 919 921 168
space-saving
LSA disconnection block, LSA 2 5 kA 19 V DPL 907 121 191
type series 2
Plug-in adapter with/ D-Sub 9-, 4, 9 2.5 kA 12.5 V USD 924 040/041/045/046 239
without data cable 25-pole 924 060/061 237
Plug-in adapter D-Sub 9-, 9 100 A 15 V FS 924 018 235
25-pole 924 019 233
VG-AnyLAN Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
in enclosure RJ45 8x8 300 A 6V NET-Protector 929 035/036 201
EG NET PRO 19” LSA 100 A 30 V 929 037 201
flush-mounted Cat. 5 RJ45, LSA 8 300 A 6V DSM 924 263 242
socket outlet
socket outlet adapter RJ45 8 300 A 6V DATA-Protector 909 955 284
Voice over IP Plug-in patch cord 3 m RJ45 8 2.5 kA 48 V DEHNpatch 929 100 206
(VOIP) Plug-in patch cord 5 m RJ45 8 2.5 kA 48 V DEHNpatch 929 110 206
140 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Easy Choice upon Interface
AMPS, NADAC coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
(824 – 894 MHz) for dc supply
coax plug-in adapter, BNC 1 20 kA DC – 1 GHz DEHNgate 929 043 228
for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
coax plug-in adapter, 7/16-Connector 1 20 kA DC, DEHNgate 929 046 229
for dc supply, low 806 – 2200 MHz
intermodulation
coax plug-in adapter 7/16-Connector 1 40 kA 890 – 2200 MHz DEHNgate 929 048 230
coax plug-in adapter N-Connector 1 25 kA 890 – 2200 MHz DEHNgate 929 049 230
DCS 1800 B162 coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
(1710 – 1880 MHz) for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
coax plug-in adapter, 7/16-Connector 1 20 kA DC, DEHNgate 929 046 229
for dc supply, low 806 – 2200 MHz
intermodulation
coax plug-in adapter 7/16-Connector 1 40 kA 890 – 2200 MHz DEHNgate 929 048 230
coax plug-in adapter N-Connector 1 25 kA 890 – 2200 MHz DEHNgate 929 049 230
DCF 77 coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
for dc supply
coax plug-in adapter, BNC 1 20 kA DC – 1 GHz DEHNgate 929 043 228
for dc supply
Radio systems coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
for dc supply
coax plug-in adapter, BNC 1 20 kA DC – 1 GHz DEHNgate 929 043 228
for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 3 GHz DEHNgate 929 058 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
coax plug-in adapter, 7/16-Connector 1 20 kA DC, DEHNgate 929 046 229
for dc supply, low 806 – 2200 MHz
intermodulation
coax plug-in adapter, U-Connector 1 20 kA DC – 300 MHz DEHNgate 929 057 228
for dc supply
coax plug-in adapter 7/16-Connector 1 25 kA 380 – 512 MHz DEHNgate 929 047 230
coax plug-in adapter 7/16-Connector 1 40 kA 890 – 2200 MHz DEHNgate 929 048 230
coax plug-in adapter N-Connector 1 25 kA 890 – 2200 MHz DEHNgate 929 049 230
GPS coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
(1565 – 1585 MHz) for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
GPS coax plug-in adapter, 7/16-Connector 1 20 kA DC, DEHNgate 929 046 229
(1565 – 1585 MHz) for dc supply, low 806 – 2300 MHz
intermodulation
coax plug-in adapter 7/16-Connector 1 40 kA 890 – 2200 MHz DEHNgate 929 048 230
coax plug-in adapter N-Connector 1 25 kA 890 – 2200 MHz DEHNgate 929 049 230
www.dehn.de 141
Easy Choice upon Interface INFORMATION TECHNOLOGY SYSTEMS
GSM 900, GSMR coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
(876 – 960 MHz) for dc supply
coax plug-in adapter, BNC 1 20 kA DC – 1 GHz DEHNgate 929 043 228
for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
coax plug-in adapter, 7/16-Connector 1 20 kA DC, DEHNgate 929 046 229
for dc supply, low 806 – 2200 MHz
intermodulation
coax plug-in adapter 7/16-Connector 1 40 kA 890 – 2200 MHz DEHNgate 929 048 230
coax plug-in adapter N-Connector 1 25 kA 890 – 2200 MHz DEHNgate 929 049 230
PCS 1900 coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
(1850 – 1990 MHz) for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
coax plug-in adapter, 7/16-Connector 1 20 kA DC, DEHNgate 929 046 229
for dc supply, low 806 – 2200 MHz
intermodulation
coax plug-in adapter 7/16-Connector 1 40 kA 890 – 2200 MHz DEHNgate 929 048 230
coax plug-in adapter N-Connector 1 25 kA 890 – 2200 MHz DEHNgate 929 049 230
TETRA, NMT 450 coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
(380 – 512 MHz) for dc supply
coax plug-in adapter, BNC 1 20 kA DC – 1 GHz DEHNgate 929 043 228
for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
coax plug-in adapter 7/16-Connector 1 25 kA 380 – 512 MHz DEHNgate 929 047 230
UMTS coax plug-in adapter, BNC 1 5 kA DC – 4GHz DEHNgate 929 042 227
for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
coax plug-in adapter, N-Connector 1 20 kA DC – 2.5 GHz DEHNgate 929 045 228
for dc supply
coax plug-in adapter, 7/16-Connector 1 20 kA DC, DEHNgate 929 046 229
for dc supply, low 806 – 2200 MHz
intermodulation
coax plug-in adapter 7/16-Connector 1 40 kA 890 – 2200 MHz DEHNgate 929 048 230
coax plug-in adapter N-Connector 1 25 kA 890 – 2200 MHz DEHNgate 929 049 230
WLAN (2.4 GHz band) coax plug-in adapter, BNC 1 5 kA DC – 4 GHz DEHNgate 929 042 227
for dc supply
coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
WLAN (5 GHz band) coax plug-in adapter, N-Connector 1 5 kA DC – 5.8 GHz DEHNgate 929 044 227
for dc supply
Video (2-Draht) DIN rail, pluggable screw terminals 2 20 kA 2.5 kA 100 MHz BLITZDUCTOR CT 919 670 154
+919 506 147
DIN rail, pluggable screw terminals 2 10 kA 100 MHz BLITZDUCTOR CT 919 570 161
+919 506 147
Video (coax) coax plug-in adapter BNC 1 2.5 kA 300 MHz UGKF 929 010 220
142 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS SPDs for
Information Technology Systems
The surge protective circuits of the SPDs contain no radio-active isotopes and Test standard for the SPDs:
generally consist of at least one voltage-limiting component. In some cases they DIN EN 61643-21 / VDE 0845 3-1:2001
also provide additional overcurrent-limiting components. SPDs consisting of seve- Low voltage surge protective devices – Part 21: Surge protective devices connec-
ral stages, must be designed to have no blind spot, i.e. it has to be ensured that ted to telecommunications and signalling networks – Performance requirements
the different protective stages are coordinated with each other. Otherwise the and testing methods
protective stages will only response in part which would lead to failures within
the SPD. Discharge capacity
According to the standard DIN EN 61643-21 / VDE 0845 3-1, SPDs must be tested
Choosing the right SPDs with at least one voltage and current impulse as stated in the table shown with
When choosing SPDs, especially the following aspects have to be taken into con- the quantity of impulses as mentioned in the table. Further tests can be perfor-
sideration: med – even with different pulse amplitudes or numbers of pulses. Voltage protec-
– Protective effect (discharge capacity, voltage protection level and coordinati- tion level Up is the max. voltage protection level measured at the output of the
on characteristics) device occurred during the test or tests performed.
– System parameters (system voltage, nominal current, transmission parame- Category C represents especially disturbing pulses with a steep rising edge and
ters) lower energy, opposite to the disturbing pulses of Category D, which is supposed
– Installation environment (design, conditions for connection and approvals / to simulate high-energy loads caused by coupled partial lightning currents. The
certifications) technical data of the SPD provide the category – both in the description of the
discharge capacity (In, Iimp) and the voltage protection level (Up).
The selection aid on pages 128 to 142 assigns suitable SPDs to common
interfaces
C3 ≥ 1 kV, 10 A, 25 A 300
1 kV µs or 100 A,
10/1000 µs
www.dehn.de 143
Coordination Characteristics (CC) INFORMATION TECHNOLOGY SYSTEMS
The voltage protection level Up of a surge protective device should be rated Generally, the test level can be taken from the documentation on the device or
below the destruction limit of the downstream IT terminal unit. obtained from the manufacturer of the device.
However, often neither the destruction limit of the terminal unit is known, nor is Consequently, a surge protective device must limit conducted interferences to
the energy load taken into consideration, which leads to the most frequent values below the test level of the terminal unit.
destructions. Therefore it is necessary here to orientate to another criterion for For simplifying the choice of surge protective devices the different devices are
comparison. marked with coordination characteristics (CC).
Within the scope of the test on electromagnetic compatibility (EMC), electric and Coordination characteristics describe the discharge capacity of the surge protecti-
electronic equipment must have a predefined immunity against conducted impul- ve device as well as the discharge capacity or the test level of the device to be
sive interferences (surges). The requirements on the immunity and the test proce- protected. In order to ensure a faultless operation, the test level of a terminal
dure are described in IEC 61000-4-5. unit (e.g. 3) must be greater or equal to the test level (e.g. 1, 2, or 3) indicated on
As equipment is used in different electromagnetic environmental conditions, it the coordination characteristics of the surge protective device.
must also come up to different immunities. The immunity is indicated by a test
level (1 – 4), where level 1 represents the lowest and level 4 the highest immuni-
ty requirement on the terminal unit.
XX Lightning current load (2.5 kA, 10/350 µs per line – Category D1)
X Max. impulse load (2.5 kA, 8/20 µs per line – Category D2)
terminal unit
terminal unit
144 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT
PLUGGABLE SPDs FOR DIN RAIL MOUNTING Lightning Current / Surge Arrester
BLITZDUCTOR® CT is a pluggable, universal two-pole lightning current/ They provide a permanently high impulse current discharge capacity (min.
surge arrester in a modular terminal block system for max. requirements 10x test impulse) and protect the terminal equipment with extremely low
on the availability of measuring and control circuits, bus systems, alarm protection levels that are supported by the low-impendance structure of
systems and telecommunication systems. The coordinated arresters of the the device. The protective circuit is integrated in the arrester module only
Yellow/Line family can be used as and not in the base part. This allows to disconnect and remove all rele-
– lightning current arresters vant components of the cable run for testing. Corresponding arrester test
units can also be provided.
– combined (i.e. lightning current/surge) arresters
A wide range of accessories makes the use of BLITZDUCTOR® CT very
– surge arresters comfortable. Components for easy marking, for earthing shields or reser-
ved cables or for easy testing of the cables complete the arrester pro-
gramme.
BLITZDUCTOR® CT mounted completely. Universal base part for all arrester modu-
Two-part construction with universal les. Optimises storage, allows prewirings
base part and application-specific arres- and facilitates service. No signal inter-
ter module in space-saving design for ruption when exchanging the modules
DIN rail mounting. thanks to capacitive and inductive con-
tacts in the base part.
www.dehn.de 145
BLITZDUCTOR® CT INFORMATION TECHNOLOGY SYSTEMS
Lightning Current / Surge Arrester PLUGGABLE SPDs FOR DIN RAIL MOUNTING
Shield connection
Blitzductor CT
tube GDT 90 prevents upcoming protected and unpro-
1 compensating currents. Transient 1 IN 2 1 IN 2
tected cables have to
impulse currents on the shield, be laid separately.
however, are discharged via the IN IN
3 indirect shield earthing.
For direct earthing Part No. 919 505 In case of a stranded cable,
of both wires reserved wires should be
contacted and earthed. If the
reserved wires are connected
with the base parts, earth
terminal sets (Part No. 919
505) should be used. This
No. ..
Ø min 6 mm2
146 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT Base Part
19 506 BCT BAS
BCT BAS
BCT MOD...
Line (IN) 1 3 Line (OUT)
2 4
BCT BAS
Dimension drawing BCT BAS Basic circuit diagram with and without plugged-in • Universal unit for all types of arrester
module modules
Base part for use as universal feed-through terminal for supporting the arrester module without • Plug-in and removal without signal
signal interruption. The arrester module is safely earthed via the supporting foot of the DIN rail interruption
by means of a snap-on device. Allows direct or indirect shield earthing • Patent insert for indirect shield
earthing
BCT BAS
Max. continuous dc voltage UC 350 V
Max. continuous ac voltage UC 250 V
Nominal current IL 10 A
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Mounting on 35 mm DIN rail according to EN 60715
Connection input / output screw/screw
Cross-sectional area, solid 0.08 - 4 mm2 (shield)
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.5 Nm / 0.8 Nm (shield)
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material polyamide PA 6.6
Colour yellow
Approvals, Certifications CSA
Ordering information
Type BCT BAS
Part No. 919 506
Packing unit 1 pc(s)
Accessory Part for BLITZDUCTOR® CT Base Part Accessory Part for BLITZDUCTOR® CT Base Part
Test/Disconnection Plug 919 504
PTS
BCT MOD
Plugged in once, the module interrupts the run of the connected BCT MOD PTS
The earth terminal set consists of a prewired flexible cable with a EKS BCT Earth
cables and leads them to 5 test sockets to the front side of the plug and two connector sleeves. Its function is direct earthing of cable
Test/Disconnection Plug for BCT 919 504 Terminal Set for BCT 919 505
test/disconnection plug. This allows to carry out measurements in the wires not been used before but already connected with the base part
installation without removing the lines from the base part Type EKS BCT
Type BCT MOD PTS Design approx. 125 mm long
Design like arrester module PU Part
Accessories 2 measuring circuits, 1 m long (plug Ø1 mm, socket Ø4 mm) Type pc(s) No.
PU Part EKS BCT 1 919 505
Type pc(s) No.
BCT MOD PTS 1 919 504
ting into the base part and establishing an indirect shield earthing. GDT 90
Discharge Tube 90 V
Gas
919 502
the shield terminals in the base part. Provides a permanent shield
The SPD can be retrofitted or exchanged any time and is mostly used contact especially for bus cables at min. installation work EFK BCT
Spring Terminal for BCT
EMC
919 508
www.dehn.de 147
BLITZDUCTOR® CT INFORMATION TECHNOLOGY SYSTEMS
919 510 BCT MOD
B 110
1 3
2 4
Ordering information
Type BCT MOD B 110
Part No. 919 510
Packing unit 1 pc(s)
148 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT
19 620 BCT MOD
BE 5
BCT MOD BE 5 – BE 60
19 621 BCT MOD
2 4
• Optimal protection
Dimension drawing BCT MOD BE 5 – BE 60 2 upstream protective stages of the gas discharge
tube minimise the decoupling impedance to the • Minimal series impedance
diodes • For use according to the lightning
Combined lightning current and surge arrester module for protection of 2 single wires with protection zones concept at bounda-
common reference potential as well as unbalanced interfaces. ries 0A – 2 and higher
Ordering information
Type BCT MOD BE 5 BCT MOD BE 12 BCT MOD BE 15 BCT MOD BE 24 BCT MOD BE 30 BCT MOD BE 48 BCT MOD BE 60
Part No. 919 620 919 621 919 622 919 623 919 624 919 625 919 626
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
www.dehn.de 149
BLITZDUCTOR® CT INFORMATION TECHNOLOGY SYSTEMS 919 627
BCT MOD BE 110
1 3
2 4
• Optimal protection Using powerful varistors minimises the decoup- Dimension drawing BCT MOD BE 110
ling impedance to the gas discharge tube.
• Minimal series impedance
• For use according to the lightning
protection zones concept at bounda- Combined lightning current and surge arrester module for protecting 2 single wires with com-
ries 0A – 2 and higher mon reference potential as well as unbalanced interfaces.
Ordering information
Type BCT MOD BE 110
Part No. 919 627
Packing unit 1 pc(s)
919 506 BCT BAS
BCT BAS Line (IN) Line (OUT)
1 3
Base part for use as universal feed-through terminal for supporting 2 4
BCT BAS
Part
BCT-Base
919 506
the arrester module without signal interruption. The arrester module
is safely earthed via the supporting foot of the DIN rail by means of
a snap-on device. Allows direct or indirect shield earthing BCT BAS
BCT MOD BE C 5 – BE C 30
19 661 BCT MOD
2 4
Ordering information
Type BCT MOD BE C 5 BCT MOD BE C 12 BCT MOD BE C 24 BCT MOD BE C 30
Part No. 919 660 919 661 919 662 919 663
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
*) measured in a 100 Ω system Line (IN) Line (OUT) BCT BAS
919 506 BCT BAS
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
BCT MOD BD 5 – BD 60
919 641 BCT MOD
2 4
• Optimal protection 2 upstream protective stages of the gas discharge Dimension drawing BCT MOD BD 5 – BD 60
tube minimise the decoupling impedance to the
• Minimal series impedance diodes
• For use according to the lightning
protection zones concept at bounda- Combined lightning current and surge arrester module for protection of balanced interfaces with
ries 0A – 2 and higher electrical isolation.
Ordering information
Type BCT MOD BD 5 BCT MOD BD 12 BCT MOD BD 15 BCT MOD BD 24 BCT MOD BD 30 BCT MOD BD 48 BCT MOD BD 60
Part No. 919 640 919 641 919 642 919 643 919 644 919 645 919 646
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
919 506 BCT BAS
BCT BAS Line (IN) Line (OUT)
1 3
Base part for use as universal feed-through terminal for supporting 2 4
BCT BAS
Part
BCT-Base
919 506
the arrester module without signal interruption. The arrester module
is safely earthed via the supporting foot of the DIN rail by means of
a snap-on device. Allows direct or indirect shield earthing BCT BAS
1 3
2 4
Dimension drawing BCT MOD BD 110/BD 250 Using the powerful varistor minimises the • Optimal protection
decoupling impedance to the gas discharge tube.
• Minimal series impedance
• For use according to the lightning
Combined lightning current and surge arrester module for protection of balanced interfaces with protection zones concept at bounda-
electrical isolation, telecommunication. ries 0A – 2 and higher
Ordering information
Type BCT MOD BD 110 BCT MOD BD 250
Part No. 919 647 919 649
Packing unit 1 pc(s) 1 pc(s)
Line (IN) Line (OUT) BCT BAS 919 506 BCT BAS
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
1 3
2 4
• Optimal protection Combining several diodes to one matrix minimi- Dimension drawing BCT MOD BD HF
ses the capacity of the protective circuit.
• Minimal self-capacitance
• For use according to the lightning
protection zones concept at bounda- Combined lightning current and surge arrester module for protection of high-frequency bus
ries 0A – 2 and higher systems or video transmissions.
BCT MOD BD HF 5
Nominal voltage UN 5V
Max. continuous dc voltage Uc 6.0 V
Max. continuous ac voltage Uc 4.2 V
Nominal current IL 0.1 A
D1 Total impulse current (10/350) Iimp 5 kA
D1 Lightning impulse current (10/350) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20) In 20 kA
C2 Nominal discharge current (8/20) per line In 20 kA
Voltage protection level line-line at Iimp D1 Up ≤ 11 V
Voltage protection level line-PG at Iimp D1 Up ≤ 20 V
Voltage protection level at 1 kV/µs C3 Up ≤ 10 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 10 V
Coordination characteristics KK XX/1
Series impedance per line 1.4 Ohm
Bandwidth line-line fG 100 MHz
Capacitance line-line C ≤ 20 pF
Capacitance line-PG C ≤ 40 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection (plugged) IP 20
Pluggable into base part
Earthing via base part
Enclosure material polyamide PA 6.6
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications CSA
Ordering information
Type BCT MOD BD HF 5
Part No. 919 670
Packing unit 1 pc(s)
919 506 BCT BAS
BCT BAS Line (IN) Line (OUT)
1 3
Base part for use as universal feed-through terminal for supporting 2 4
BCT BAS
Part
BCT-Base
919 506
the arrester module without signal interruption. The arrester module
is safely earthed via the supporting foot of the DIN rail by means of
a snap-on device. Allows direct or indirect shield earthing BCT BAS
1 3
2 4
Dimension drawing BCT MOD BD HFD Combining several diodes to one matrix mini- • Optimal protection
mises the capacity of the protective circuit.
• Minimal self-capacitance
• For use according to the lightning
Combined lightning current and surge arrester module for protection of electrically isolated protection zones concept at bounda-
high-frequency bus systems or telecommunication transmissions. ries 0A – 2 and higher
Ordering information
Type BCT MOD BD HFD 5 BCT MOD BD HFD 24
Part No. 919 671 919 675
Packing unit 1 pc(s) 1 pc(s)
Line (IN) Line (OUT) BCT BAS 919 506 BCT BAS
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
BCT MOD ME 5 – ME 60
919 521 BCT MOD
2 4
• Powerful standard protection Energy-coordinated gas discharge tubes and Dimension drawing BCT MOD ME 5 – ME 60
diodes connected to earth.
• Minimal series impedance
• For use according to the lightning
protection zones concept at bounda- Surge arrester module for protection of 2 single wires with common reference potential as well
ries 0B – 2 and higher as unbalanced interfaces.
Ordering information
Type BCT MOD ME 5 BCT MOD ME 12 BCT MOD ME 15 BCT MOD ME 24 BCT MOD ME 30 BCT MOD ME 48 BCT MOD ME 60
Part No. 919 520 919 521 919 522 919 523 919 524 919 525 919 526
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
919 506 BCT BAS
BCT BAS Line (IN) Line (OUT)
1 3
Base part for use as universal feed-through terminal for supporting 2 4
BCT BAS
Part
BCT-Base
919 506
the arrester module without signal interruption. The arrester module
is safely earthed via the supporting foot of the DIN rail by means of
a snap-on device. Allows direct or indirect shield earthing BCT BAS
156 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT
19 527 BCT MOD
ME 110
1 3
2 4
Dimension drawing BCT MOD ME 110 Using powerful varistors no longer requires the • Powerful standard protection
decoupling to the gas discharge tube.
• Minimal series impedance
• For use according to the lightning
Surge arrester module for protection of 2 single wires with common reference potential as well protection zones concept at bounda-
as unbalanced interfaces. ries 0B – 2 and higher
Ordering information
Type BCT MOD ME 110
Part No. 919 527
Packing unit 1 pc(s)
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
www.dehn.de 157
BLITZDUCTOR® CT INFORMATION TECHNOLOGY SYSTEMS
919 560 BCT MOD
ME C 5
BCT MOD ME C 5 – ME C 30
919 561 BCT MOD
2 4
Ordering information
Type BCT MOD ME C 5 BCT MOD ME C 12 BCT MOD ME C 24 BCT MOD ME C 30
Part No. 919 560 919 561 919 562 919 563
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
919 506 BCT BAS
BCT BAS Line (IN) Line (OUT) *) measured in a 100 Ω system
1 3
Base part for use as universal feed-through terminal for supporting 2 4
BCT BAS
Part
BCT-Base
919 506
the arrester module without signal interruption. The arrester module
is safely earthed via the supporting foot of the DIN rail by means of
a snap-on device. Allows direct or indirect shield earthing BCT BAS
158 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT
19 540 BCT MOD
MD 5
BCT MOD MD 5 – MD 60
19 541 BCT MOD
2 4
Dimension drawing BCT MOD MD 5 – MD 60 Protective circuit, free of leakage currents to • Powerful standard protection
earth, energy-coordinated.
• Minimal series impedance
• For use according to the lightning
Surge arrester module for protection of balanced interfaces with electrical isolation. protection zones concept at bounda-
ries 0B – 2 and higher
Ordering information
Type BCT MOD MD 5 BCT MOD MD 12 BCT MOD MD 15 BCT MOD MD 24 BCT MOD MD 30 BCT MOD MD 48 BCT MOD MD 60
Part No. 919 540 919 541 919 542 919 543 919 544 919 545 919 546
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
www.dehn.de 159
BLITZDUCTOR® CT INFORMATION TECHNOLOGY SYSTEMS
919 547 BCT MOD
MD 110
1 3
2 4
• Powerful standard protection Using a powerful varistor no longer requires the Dimension drawing BCT MOD MD 110/MD 250
decoupling to the gas discharge tube.
• No series impedance
• For use according to the lightning
protection zones concept at bounda- Surge arrester module for protection of balanced interfaces with electrical isolation,
ries at 0B – 2 and higher telecommunication.
Ordering information
Type BCT MOD MD 110 BCT MOD MD 250
Part No. 919 547 919 549
Packing unit 1 pc(s) 1 pc(s)
160 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT
19 570 BCT MOD
MD HF 5
1 3
2 4
Dimension drawing BCT MOD MD HF Combining several diodes to one matrix mini- • Minimal self-capacitance
mises the capacity of the protective circuit.
• Best transmission performance
• For use according to the lightning
Surge arrester module for protection of high-frequency bus systems or video transmissions. protection zones concept at bounda-
ries 0B – 2 and higher
BCT MOD MD HF 5
Nominal voltage UN 5V
Max. continuous dc voltage Uc 6.0 V
Max. continuous ac voltage Uc 4.2 V
Nominal current IL 0.1 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 10 kA
Voltage protection level line-line at In C2 Up ≤ 50 V
Voltage protection level line-PG at In C2 Up ≤ 70 V
Voltage protection level at 1 kV/µs C3 Up ≤ 10 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 10 V
Coordination characteristics KK X/1
Series impedance per line 1.0 Ohm
Bandwidth line-line fG 100 MHz
Capacitance line-line C ≤ 20 pF
Capacitance line-PG C ≤ 40 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection (plugged) IP 20
Pluggable into base part
Earthing via base part
Enclosure material polyamide PA 6.6
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications CSA
Ordering information
Type BCT MOD MD HF 5
Part No. 919 570
Packing unit 1 pc(s)
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
www.dehn.de 161
BLITZDUCTOR® CT INFORMATION TECHNOLOGY SYSTEMS
919 571 BCT MOD
MD HFD 5
1 3
2 4
• Minimal self-capacitance Combining several diodes to one matrix minimi- Dimension drawing BCT MOD MD HFD
ses the capacity of the protective circuit.
• Best transmission performance
• For use according to the lightning
protection zones concept at bounda- Surge arrester module for protection of electrically isolated high-frequency bus systems or
ries 0B – 2 and higher telecommunication transmissions.
Ordering information
Type BCT MOD MD HFD 5 BCT MOD MD HFD 24
Part No. 919 571 919 575
Packing unit 1 pc(s) 1 pc(s)
162 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT
19 552 BCT MOD
MD TC N
1 3
2 4
Dimension drawing BCT MOD MD TC N A series connection of gas discharge tubes in- • Powerful standard protection
creases the insulation resistance to earth.
• High insulation resistance to earth
• For use according to the lightning
Surge arrester module for protection of telecommunication interfaces. Unit specified for use in protection zones concept at bounda-
Norway. ries 0B – 2 and higher
BCT MOD MD TC N
Max. continuous dc voltage Uc 280 V
Max. continuous ac voltage Uc 190 V
Nominal current IL 1A
C2 Total nominal discharge current (8/20) In 20 kA
C2 Nominal discharge current (8/20) per line In 10 kA
Voltage protection level line-line at In C2 Up ≤ 750 V
Voltage protection level line-PG at In C2 Up ≤ 950 V
Voltage protection level at 1 kV/µs C3 Up ≤ 490 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 800 V
Coordination characteristics KK X/2
Bandwidth line-line fG 18 MHz
Capacitance line-line C ≤ 400 pF
Capacitance line-PG C ≤ 20 pF
Response time line-line ta ≤ 25 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection (plugged) IP 20
Pluggable into base part
Earthing via base part
Enclosure material polyamide PA 6.6
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications CSA
Ordering information
Type BCT MOD MD TC N
Part No. 919 552
Packing unit 1 pc(s)
1 3
2 4 Base part for use as universal feed-through terminal for supporting
the arrester module without signal interruption. The arrester module
BCT BAS
Part
BCT-Base
919 506
is safely earthed via the supporting foot of the DIN rail by means of
BCT BAS a snap-on device. Allows direct or indirect shield earthing
Type BCT BAS
BCT MOD...
Line (IN) Line (OUT) Cross-sectional area, solid 0.08 - 4 mm2 (shield)
1 3
Cross-sectional area, flexible 0.08 - 2.5 mm2
2 4 Enclosure material polyamide PA 6.6
PU Part
BCT BAS Type pc(s) No.
BCT BAS 1 919 506
www.dehn.de 163
BLITZDUCTOR® CT INFORMATION TECHNOLOGY SYSTEMS
919 589 BCT MOD
MY 250
1 3
2 4
Ordering information
Type BCT MOD MY 250
Part No. 919 589
Packing unit 1 pc(s)
164 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR CT Accessories
19 504 BCT MOD
TS
1 3
2 4
Dimension drawing BCT MOD PTS Basic circuit diagram BCT MOD PTS • For plugging into the base part of
BLITZDUCTOR® CT
• Makes maintenance and trouble
Plugged in once, the module interrupts the run of the connected cables and leads them to 5 test shooting easier
sockets to the front side of the test/disconnection plug. This allows to carry out measurements in
• Measuring cables included
the installation without removing the lines from the base part
Ordering information
Type BCT MOD PTS
Part No. 919 504
Packing unit 1 pc(s)
19 502 GDT 90
GDT 90 Gas
Discharge Tube 90 V 919 502
Gas discharge tube with lightning current carrying capability for inserting into the base part and • Device with lightning current carrying
establishing an indirect shield earthing. The SPD can be retrofitted or exchanged any time and is capability
mostly used at risks of leakage pickups • Low sparkover voltage
GDT 90
D1 Lightning impulse current carrying capability (10/350) 5 kA
Design h 8 x 6 mm
Mounting on BCT BAS
Ordering information
Type GDT 90
Part No. 919 502
Packing unit 1 pc(s)
www.dehn.de 165
BLITZDUCTOR CT Accessories INFORMATION TECHNOLOGY SYSTEMS 919 505 EKS BCT
• Easy handling The earth terminal set consists of a prewired flexible cable with a plug and two connector
• Quick exchange for retrofitting an sleeves. Its function is direct earthing of cable wires not been used before but already
arrester module connected with the base part
EKS BCT
Design approx. 125 mm long
Mounting on BCT BAS
Ordering information
Type EKS BCT
Part No. 919 505
Packing unit 1 pc(s)
• Min. space requirements EMC spring terminal, tested with lightning currents, for screwing into the shield terminals in the
• Compensates the yield of the base part. Provides a permanent shield contact especially for bus cables at min. installation work
conductor
• Especially easy handling with bus
cables
EFK BCT
D1 Lightning impulse current carrying capability (10/350) 5 kA
Clamping range Rd 2 - 10 mm
Mounting on BCT BAS
Ordering information
Type EFK BCT
Part No. 919 508
Packing unit 10 pc(s)
166 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
COMPACT SPDs FOR DIN RAIL MOUNTING Surge Protective Terminal Block
DEHNconnect RK is a 6 mm wide surge protective modular terminal block. even jumper bars can be plugged into the protected side of the arrester
With 5 cage clamp spring pressure connections, 2 lines can be protected and thus transmit signals. As the arresters are only enclosed on one side
and, additionally, the equipotential bonding to the terminal equipment for space-saving reasons, a covering plate should be used at the end of
can be established. Thanks to the snap-in fixing device at the supporting every SPD block.
foot, the device is safely earthed via the DIN rail. For reducing the wiring,
ok marking plates
www.dehn.de 167
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS 919 920 DCO
RK ME 12
919 921 DCO
DCO RK ME 12
DEHNconnect RK 12 V 919 920
DCO RK ME 24
DEHNconnect RK 24 V 919 921
DCO RK ME 48
1 3 DEHNconnect RK 48 V
DCO RK ME 110
DEHNconnect RK 110 V
919 922
919 923
2 4
IN OUT
• Standard protection in modular ter- Energy-coordinated gas discharge tubes and Dimension drawing DCO RK ME
minal blocks diodes to earth
Ordering information
Type DCO RK ME 12 DCO RK ME 24 DCO RK ME 48 DCO RK ME 110
Part No. 919 920 919 921 919 922 919 923
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
Enclosure PU Part
Type material Colour pc(s) No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979
168 www.dehn.de
40 DCO RK
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
41 DCO RK
1 3
2 4
IN OUT
Dimension drawing DCO RK MD 12 / MD 24 Protective circuit free of leakage currents to • Standard protection in modular
earth, energy-coordinated. terminal blocks
• Low series impedance
2-stage surge arrester for protection of a floating two-core conductor as well as balanced • For use according to the lightning
interfaces. protection zones concept at bounda-
ries 0B – 2 and higher
DCO RK MD 12 DCO RK MD 24
Nominal voltage UN 12 V 24 V
Max. continuous dc voltage Uc 14 V 33 V
Max. continuous ac voltage Uc 9.5 V 23 V
Nominal current IL 0.5 A 0.5 A
C2 Total nominal discharge current (8/20) In 10 kA 10 kA
C2 Nominal discharge current (8/20) per line In 5 kA 5 kA
Voltage protection level line-line at In C2 Up ≤ 25 V ≤ 50 V
Voltage protection level line-PG at In C2 Up ≤ 750 V ≤ 750 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 19 V ≤ 45 V
Voltage protection level line-PG at 1 kV/µs: line/PG Up ≤ 650 V ≤ 650 V
Coordination characteristics KK X/1 X/1
Series impedance per line 1.8 Ohm 1.8 Ohm
Bandwidth line-line fG 2.5 MHz 6 MHz
Parasitic capacitance line-line C ≤ 2.4 nF ≤ 1 nF
Parasitic capacitance line-PG C ≤ 5 pF ≤ 5 pF
Response time line-line ta ≤ 1 ns ≤ 1 ns
Response time line-PG ta ≤ 100 ns ≤ 100 ns
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection IP 00, with cover IP 20 IP 00, with cover IP 20
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2 0.08 - 2.5 mm2
Earthing via DIN rail / terminal DIN rail / terminal
Enclosure material polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow
Test standards IEC 61643-21 IEC 61643-21
Ordering information
Type DCO RK MD 12 DCO RK MD 24
Part No. 919 940 919 941
Packing unit 1 pc(s) 1 pc(s)
Enclosure PU Part
Type material Colour pc(s) No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979
www.dehn.de 169
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS 919 942 DCO
RK MD 48
1 3
2 4
IN OUT
• Standard protection in modular ter- Protective circuit, free of leakage currents to Dimension DCO RK MD 48
minal blocks earth, energy-coordinated
• Extremely low series impedance
• For use according to the lightning 2-stage surge arrester for protection of a floating two-core conductor as well as balanced
protection zones concept at bounda- interfaces up to 1.7 A.
ries 0B – 2 and higher
DCO RK MD 48
Nominal voltage UN 48 V
Max. continuous dc voltage Uc 55 V
Max. continuous ac voltage Uc 38.5 V
Nominal current IL 1.7 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 Up ≤ 100 V
Voltage protection level line-PG at In C2 Up ≤ 750 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 70 V
Voltage protection level line-PG at 1 kV/µs: line/PG Up ≤ 650 V
Coordination characteristics KK X/1
Series impedance per line 0.4 Ohm
Bandwidth line-line fG 10 MHz
Parasitic capacitance line-line C ≤ 0.6 nF
Parasitic capacitance line-PG C ≤ 10 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Ordering information
Type DCO RK MD 48
Part No. 919 942
Packing unit 1 pc(s)
Enclosure PU Part
Type material Colour pc(s) No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979
170 www.dehn.de
19 943
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
DCO RK MD 110
1 3
2 4
IN OUT
Dimension drawing DCO RK MD 110 Protection circuit, free of leakage currents to • Standard protection in modular ter-
earth, energy-coordinated. minal blocks
• Low series impedance
2-stage surge arrester for protection of a floating two-core conductor, telecommunication. • For use according to the lightning
protection zones concept at bounda-
ries 0B – 2 and higher
DCO RK MD 110
Nominal voltage UN 110 V
Max. continuous dc voltage Uc 170 V
Max. continuous ac voltage Uc 120 V
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 Up ≤ 260 V
Voltage protection level line-PG at In C2 Up ≤ 750 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 230 V
Voltage protection level line-PG at 1 kV/µs: line/PG Up ≤ 650 V
Coordination characteristics KK X/2
Series impedance per line 1.8 Ohm
Bandwidth line-line fG 16 MHz
Parasitic capacitance line-line C ≤ 0.4 nF
Parasitic capacitance line-PG C ≤ 5 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Ordering information
Type DCO RK MD 110
Part No. 919 943
Packing unit 1 pc(s)
Enclosure PU Part
Type material Colour pc(s) No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979
www.dehn.de 171
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS 919 970
DCO RK MD HF 5
1 3
2 4
IN OUT
• Low self-capacitance The capacity of the protective circuit can be mini- Dimension drawing DCO RK MD HF
mised by combining several diodes to one
• Very good transmission performance matrix.
• For use according to the lightning
protection zones concept at bounda- 2-stage surge arrester for protection of balanced and unbalanced interfaces with extra-low
ries 0B – 2 and higher voltages. Also suitable for high transmission rates. For shielded bus lines, SAK shield connection
systems should be used.
DCO RK MD HF 5
Nominal voltage UN 5V
Max. continuous dc voltage Uc 6.0 V
Max. continuous ac voltage Uc 4.2 V
Nominal current IL 0.1 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 Up ≤ 27 V
Voltage protection level line-PG at In C2 Up ≤ 50 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 14 V
Voltage protection level line-PG at 1 kV/µs: line/PG Up ≤ 14 V
Coordination characteristics KK X/1
Series impedance per line 1.0 Ohm
Bandwidth line-line fG 250 MHz
Bandwidth line-PG fG 180 MHz
Parasitic capacitance line-line C ≤ 19 pF
Parasitic capacitance line-PG C ≤ 16 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 00 with cover IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material thermoplastic PA 6.6
Colour yellow
Test standards IEC 61643-21
Ordering information
Type DCO RK MD HF 5
Part No. 919 970
Packing unit 1 pc(s)
Enclosure PU Part
Type material Colour pc(s) No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979
172 www.dehn.de
DCO RK E
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK
DCO RK E
DCO RK E
DCO RK E
COMPACT SPDs FOR DIN RAIL MOUNTING DCO RK E
RK E 12
Nconnect RK 12 V 919 987
RK E 24
Nconnect RK 24 V 919 988
RK E 48
Nconnect RK 48 V
RK E 60
919 989 1 3
Nconnect RK 60 V 919 990
2 4
IN OUT
Dimension drawing DCO RK E Powerful diodes limit surges to earth. • Protection in modular terminal blocks
• High nominal current
• For use according to the lightning
Finely limiting surge protection for 2 single wires with common reference potential as well as protection zones concept at bounda-
unbalanced interfaces. Suitable for energy coordination with upstream BLITZDUCTOR® VT GS ries 1 – 2 and higher
surge arrester.
Ordering information
Type DCO RK E 12 DCO RK E 24 DCO RK E 48 DCO RK E 60
Part No. 919 987 919 988 919 989 919 990
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
Enclosure PU Part
Type material Colour pc(s) No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979
www.dehn.de 173
DEHNconnect RK INFORMATION TECHNOLOGY SYSTEMS 919 986
DCO RK D 5 24
1 3
IN OUT
2 4
• EMC protection in modular terminal Powerful diodes limit surges among the signal Dimension drawing DCO RK D
blocks lines.
• High nominal current
• For use according to the lightning Surge protection for output digital modules by SIEMENS-SPS S7-300 (lab-tested). The terminal
protection zones concept at bounda- allows an increased EMC protection. No connection to PG.
ries 1 – 2 and higher
DCO RK D 5 24
Nominal voltage UN +24 V / -5 V
Max. continuous dc voltage Uc +30 V / -6 V
Nominal current IL 10 A
C1 Total nominal discharge current (8/20) In 0.3 kA
C1 Nominal discharge current (8/20) per line In 0.3 kA
Voltage protection level line-line at In C1 Up ≤ 70 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 45 V
Coordination characteristics KK 4/1
Bandwidth line-line fG 3.5 MHz
Parasitic capacitance line-line C ≤ 2 nF
Response time line-line ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Ordering information
Type DCO RK D 5 24
Part No. 919 986
Packing unit 1 pc(s)
Enclosure PU Part
Type material Colour pc(s) No.
AD DCO RK GE polyamide PA 6.6 yellow 1 919 979
174 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS
COMPACT SPDs FOR DIN RAIL MOUNTING
Accessory Part for DEHNconnect RK Accessory Part for DEHNconnect RK
Covering Plate 919 979
RK GE
AD DCO Jumper Bar 919 885
RK
KB 5 DCO
www.dehn.de 175
BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS
Surge Arrester COMPACT SPDs FOR DIN RAIL MOUNTING
BLITZDUCTOR® VT is a family of compact surge arresters in modular ter- ters protect 4-wire signal lines or special applications. The equipment is
minal blocks and includes different types of enclosures. Most of the arres- earthed via a screw terminal.
176 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
18 400 BVT TTY
4
2 2
3 3
IN OUT
4 4
Dimension drawing BVT TTY The resistances at the circuit output protect opto- • Simultaneous protection of two TTY
coupler and protective diodes in the terminal loops
equipment against overloads.
• Additional decoupling to the terminal
equipment
Because of the additional decoupling resistances at the output, only few loadable diodes in the • For use according to the lightning
terminal equipment are integrated into the energy coordination of the protection levels. This is protection zones concept at bounda-
especially important for optocoupler interfaces. ries 0B – 2 and higher
BVT TTY 24
Nominal voltage UN 24 V
Max. continuous dc voltage UC 26.8 V
Max. continuous ac voltage UC 18.9 V
Nominal current IL 0.1 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 10 kA
Voltage protection line-line at In C2 Up ≤ 65 V
Voltage protection level line-PG at In C2 Up ≤ 700 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 36 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 600 V
Coordination characteristics KK X/1
Series impedance per line (per pair) 17.2 Ohm
Bandwidth line-line fG 8 MHz
Parasitic capacitance line-line C ≤ 1 nF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminal) 0.5 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications CSA
Ordering information
Type BVT TTY 24
Part No. 918 400
Packing unit 1 pc(s)
www.dehn.de 177
BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS
918 407 BVT MTTY
24
3 3
2 2
IN OUT
1 1
• Economical compact protection Protection circuit, free of leakage currents to Dimension drawing BVT MTTY
earth, energy-coordinated with simple
• For use according to the lightning decoupling.
protection zones concept at bounda-
ries 0B – 1 and higher Surge arrester for two floating two-core conductors. Unbalanced use of the decoupling
impedance.
BVT MTTY 24
Nominal voltage UN 24 V
Max. continuous dc voltage UC 26.8 V
Max. continuous ac voltage UC 18.9 V
Nominal current IL 0.1 A
C2 Total nominal discharge current (8/20) In 20 kA
C2 Nominal discharge current (8/20) per line In 10 kA
Voltage protection line-line at In C2 Up ≤ 65 V
Voltage protection level line-PG at In C2 Up ≤ 700 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 36 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 600 V
Coordination characteristics KK X/1
Series impedance per line (per pair) 2.2 Ohm
Bandwidth line-line fG 10 MHz
Parasitic capacitance line-line C ≤ 1 nF
Response time line-line ta ≤ 100 ns
Response time line-PG ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminal) 0.5 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Ordering information
Type BVT MTTY 24
Part No. 918 407
Packing unit 1 pc(s)
178 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
18 403 BVT GS
10
3 3
2 2
IN OUT
1 1
Dimension drawing BVT GS The decoupling at the output allows the following • Quad protection with gas discharge
energy-coordinated use of protective diodes tubes
without considering the cable length.
• Decoupling integrated
Compact surge arrester for four lines with integrated decoupling resistors at the output of the • For use according to the lightning
equipment. This allows energy coordination with downstream diode arresters DCO RK E ... and FS. protection zones concept at bounda-
ries 0B – 1 and higher
BVT GS 110
Nominal voltage UN 110 V
Max. continuous dc voltage UC 170 V
Max. continuous ac voltage UC 130 V
Nominal current IL 0.25 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 10 kA
Voltage protection line-line at In C2 Up ≤ 800 V
Voltage protection level line-PG at In C2 Up ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 800 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 600 V
Coordination characteristics KK X/
Series impedance per line 10 Ohm
Bandwidth line-line fG 18 MHz
Parasitic capacitance line-line C ≤ 10 pF
Response time line-line ta ≤ 100 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminal) 0.5 Nm
Earthing via screw terminal
Enclosure material Thermoplastic UL 94 V-0
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications CSA
Ordering information
Type BVT GS 110
Part No. 918 403
Packing unit 1 pc(s)
www.dehn.de 179
BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS
918 401 BVT
RS485 5
7 7
4 4
3 3
IN OUT
6 6
5 5
1 1
2 2
• Connections for 4 bus lines and SG Circuiting diodes to a common reference point Dimension drawing BVT RS485
leads to a low protection level between the
• Direct and indirect shield earthing signal lines.
• For use according to the lightning
protection zones concept at bounda- Surge arrester for many applications, e.g. for balanced 4-wire interfaces RS 485/422 or tempera-
ries 0B – 2 and higher ture sensors. Optionally direct or indirect shield earthing and connection of a signal ground (SG).
BVT RS485 5
Nominal voltage UN 5V
Max. continuous dc voltage UC 6V
Max. continuous ac voltage UC 4.2 V
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 10 kA
Voltage protection line-line at In C2 Up ≤ 20 V
Voltage protection level line-PG at In C2 Up ≤ 700 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 8.5 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 600 V
Coordination characteristics KK X/1
Series impedance per line 1.8 Ohm
Bandwidth line-line fG 1.7 MHz
Parasitic capacitance line-line C ≤ 5 nF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminal) 0.5 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications CSA
Ordering information
Type BVT RS485 5
Part No. 918 401
Packing unit 1 pc(s)
180 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
18 402 BVT AD
4
BVT AD 24 BLITZ-
DUCTOR VT 24 V 918 402
0V 0V
+24 V +24 V
Dimension drawing BVT AD As a unipolar diode is used, negative operating • EMC protection for PLC 24 V power
voltages are not permissible. supplies
• Especially low protection level
Quickly responding surge protection, for e.g. Siemens SPS S7-300 with dc power supply. • For use according to the lightning
Especially, if an electromagnetically rough environment has to be expected and conventional protection zones concept at bounda-
varistor-based arresters do not limit sharply enough. ries 1 – 2 and higher
BVT AD 24
Nominal voltage UN 24 V
Max. continuous dc voltage UC 35 V
Nominal current IL 10 A
C2 Total nominal discharge current (8/20) In 2 kA
C2 Nominal discharge current (8/20) per line In 1 kA
Voltage protection line-line at In C2 Up ≤ 70 V
Voltage protection level line-PG at In C2 Up ≤ 700 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 50 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 700 V
Parasitic capacitance line-line C ≤ 7 nF
Parasitic capacitancd line-PG C ≤ 10 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.5 - 4.0 mm2
Cross-sectional area, flexible 0.5 - 4.0 mm2
Tightening torque (terminal) 0.8 Nm
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications CSA
Ordering information
Type BVT AD 24
Part No. 918 402
Packing unit 1 pc(s)
www.dehn.de 181
BLITZDUCTOR® VT KKS INFORMATION TECHNOLOGY SYSTEMS
Combined Surge Arrester COMPACT SPDs FOR DIN RAIL MOUNTING
for Cathodic Protection Systems
K - K + M - M +
K- K+ M- M+
Application example
182 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT KKS
18 420 BVT KKS
ALD 75
K+ Kp+
ϑ ϑ FM
ϑ
Dimension drawing BVT KKS ALD Thermal fuses monitor the varistors. Capacitive • For protective circuits
control for a low impulse sparkover voltage.
• High nominal current
Energy-coordinated combined lightning current and surge arrester for protection of the inverter • For use according to the lightning
in the protective circuit (red colour). Plug-in remote signalling contact (break contact) for protection zones concpet at bounda-
indication of overloads. Installation into the steel plate enclosure recommended. ries 0A – 2 and higher
Ordering information
Type BVT KKS ALD 75
Part No. 918 420
Packing unit 1 pc(s)
www.dehn.de 183
BLITZDUCTOR® VT KKS INFORMATION TECHNOLOGY SYSTEMS
918 421 BVT KKS
APD 36
ϑ
M+ Mp+
ϑ FM
• For voltage measuring circuits Thermal fuses monitor the discharge circuits. Dimension drawing BVT KKS APD
Capacitive control for a low impulse sparkover
• Plug-in remote signalling contact voltage.
• For use according to the lightning
protection zones concept at bounda- Energy-coordinated combined lightning current and surge arrester for protection of voltage mea-
ries 0A – 2 and higher suring circuits (yellow colour). Plug-in remote signalling contact (break contact) for indication of
overloads. Installation into a steel-plate enclosure recommended.
Ordering information
Type BVT KKS APD 36
Part No. 918 421
Packing unit 1 pc(s)
184 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT KKS
18 404 BVT KKS
ALD SN
D Dp
ϑ ϑ FM
ϑ
Dimension drawing BVT KKS ALD SN Thermal fuses monitor the varistors. Capacitive • For protective circuits
control for a low impulse sparkover voltage.
• Unit in accordance with SNAM
Energy-coordinated combined lightning current and surge arrester for protection of the inverter specification
in the protective circuit (red colour). Plug-in remote signalling contact (break contact) for indica- • For use according to the lightning
tion of overloads. Installation into steel-plate enclosure recommended. Unit according to SNAM. protection zones concept at bounda-
ries 0A – 2 and higher
Ordering information
Type BVT KKS ALD SN
Part No. 918 404
Packing unit 1 pc(s)
www.dehn.de 185
BLITZDUCTOR® VT KKS INFORMATION TECHNOLOGY SYSTEMS
918 405 BVT KKS
APD SN
ϑ
M Mp
ϑ FM
• For protective circuits Thermal fuses monitor the varistors. Capacitive Dimension drawing BVT KKS APD SN
control for a low impulse sparkover voltage.
• Unit in accordance with SNAM
specification Energy-coordinated combined lightning current and surge arrester for protection of the inverter
• For use according to the lightning in the protective circuit (red colour). Plug-in remote signalling contact (break contact) for indica-
protection zones concept at bounda- tion of overloads. Installation into steel-plate enclosure recommended. Unit according to SNAM.
ries 0A – 2 and higher
Ordering information
Type BVT KKS APD SN
Part No. 918 405
Packing unit 1 pc(s)
186 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DPL
LSA-PLUS TECHNOLOGY Surge Arrester
Plug-in surge arresters for IT installations and devices to be connected via Units:
terminals or disconnection blocks with LSA-PLUS IDC termination (con- – DPL 1: Surge protective plug for 1 two-core conductor (TC). The plug
necting method without soldering, screwing and insulation). for 1 TC allows also partial furnishments of LSA-PLUS terminal blocks
Both the arresters for 1 TC and those for 10 TC can be installed easily and or using protective plugs with different circuits or nominal voltage on
removed for test purposes. The tense fit of the arresters provides a safe one LSA-PLUS block. For earthing, one ES 10DA earthing busbar has
contact even at slight vibrations. to be installed into each block.
– DPL 10: Surge protective terminal blocks for 10 two-core conductors
(TC) with the same signals. The earth contact with the mounting
frame is established automatically when plugging in the arrester.
DPL ... F (yellow colour) include a 2-stage DPL ... G (grey colour) include gas dis-
protective circuit and are designed for charge tubes only. They can be plugged
mounting on disconnection blocks. Apart into disconnection or terminal blocks.
from the 10 TC unit, also 1 TC arresters Mounting on terminal blocks, however, is
can be combined in any kind of series. the preferred connecting method, as they
Interfaces like ISDN S0, require 2 DPL 1 F provide a higher impulse current carrying
per interface. capability. After an overload, the pro-
tective elements of the 10 TC unit can be
DPL ... F family DPL ... G family exchanged individually. The 1 TC plug
has an additional fail-safe overload pro-
tection, which short circuits the arrester
in case of a fault.
DPL 1 F... DPL 10 F...
ES 10 DA
AL 2 10DA LSA or
TL 2 10 DA LSA TL 10 DA LSA
TL 2 10DA LSA
MB 2 10 LSA
MB 2 10 LSA
MB 2 10 LSA
Mounting DPL
www.dehn.de 187
DPL INFORMATION TECHNOLOGY SYSTEMS
907 220 DPL 1 G A
110
• Small dimension Protection with two gas discharge tubes and Dimension drawing DPL 1 G A
fail-safe spring contact.
• Gas discharge tube with fail-safe
performance
• For use according to the lightning Protective plug 1 TC for nearly all applications with integrated fail-safe performance.
protection zones concept at bounda- Earthing via ES 10 DA.
ries 0B – 1 and higher
DPL 1 G A 110
Nominal voltage UN 110 V
Max. continuous dc voltage Uc 180 V
Max. continuous ac voltage Uc 127 V
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level at 1 kV/µs line/PG Up ≤ 600 V
Bandwidth line-line fG 65 MHz
Parasitic capacitance line-PG C ≤ 5 pF
Response time line-line ta ≤ 100 ns
Response time line-PG ta ≤ 100 ns
fail-safe performance gas discharge tube with spring contacts
Operating temperature range -40°C...+80°C
Pluggable into LSA-PLUS disconnection and terminal blocks (type 2)
Earthing via earthing busbar
Enclosure material thermoplastic
Colour grey
Ordering information
Type DPL 1 G A 110
Part No. 907 220
Packing unit 5 pc(s)
PU Part
Type pc(s) No.
ES 10DA 1 907 998
188 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DPL
07 145 DPL 1 F
ARD 110
LSA-PLUS TECHNOLOGY
ARD 250
1 3
2 4
Dimension drawing DPL 1 F ARD 110 / ARD 250 Combination of gas discharge tubes, decoupling • Low protection level
resistors and varistor between the signal lines.
• Very good transmission performance
• For use according to the lightning
Protective plug 1 TC with 2-stage protective circuit for ADSL, ISDN Uk0 or a/b-lines. protection zones concept at bounda-
Earthing via ES 10 DA. For disconnection blocks only. ries 0B – 2 and higher
Ordering information
Type DPL 1 F ARD 110 DPL 1 F ARD 250
Part No. 907 145 907 146
Packing unit 10 pc(s) 1 pc(s)
PU Part
Type pc(s) No.
ES 10DA 1 907 998
www.dehn.de 189
DPL INFORMATION TECHNOLOGY SYSTEMS
907 144 DPL 1 F
ATP 5
1 3
2 4
• For max. transmission rates Combination of gas discharge tubes, decoupling Dimension drawing DPL 1 F ATP
resistors and low capacitance diode matrix.
• No leakage currents to earth
• For use according to the lightning
protection zones concept at bounda- Protective plug 1 TC with 2-stage protective circuit for high-frequency transmission such as
ries 0B – 2 and higher G.703 or ISDN U2m, S2m and S0. Earthing via ES 10 DA. For disconnection blocks only.
DPL 1 F ATP 5
Nominal voltage UN 5V
Max. continuous dc voltage Uc 7.5 V
Max. continuous ac voltage Uc 5.3 V
Nominal current IL 0.1 A
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 UP ≤ 35 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 13 V
Voltage protection level at 1 kV/µs line/PG Up < 600 V
Series impedance per line 1 Ohm
Bandwidth line-line fG 180 MHz
Parasitic capacitance line-line C ≤ 60 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Pluggable into LSA-PLUS disconnection blocks (type 2)
Earthing via earthing busbar
Enclosure material polyamide PA 6.6
Colour yellow
Ordering information
Type DPL 1 F ATP 5
Part No. 907 144
Packing unit 10 pc(s)
PU Part
Type pc(s) No.
ES 10DA 1 907 998
190 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DPL
07 120 DPL 1 F
ALE 5
LSA-PLUS TECHNOLOGY
ALE 12
07 122 DPL 1 F
ALE 15
07 123 DPL 1 F
ALE 24
2 4
Dimension drawing DPL 1 F ALE 5 – ALE 24 Combination of gas discharge tubes, decoupling • Increased nominal current
coils and diodes to PG.
• Low self-heating
• For use according to the lightning
Protective plug 1 TC with 2-stage protective circuit for load circuits with common reference protection zones concept at bounda-
potential. Earthing via ES 10 DA. For disconnection blocks only. ries 0B – 2 and higher
Ordering information
Type DPL 1 F ALE 5 DPL 1 F ALE 12 DPL 1 F ALE 15 DPL 1 F ALE 24
Part No. 907 120 907 121 907 122 907 123
Packing unit 10 pc(s) 10 pc(s) 10 pc(s) 10 pc(s)
PU Part
Type pc(s) No.
ES 10DA 1 907 998
www.dehn.de 191
DPL INFORMATION TECHNOLOGY SYSTEMS
907 124 DPL 1 F
ALE 48
LSA-PLUS TECHNOLOGY
ALE 60
907 126 DPL 1 F
ALE 110
1 3
2 4
• Increased nominal current Combination of gas discharge tubes, decoupling Dimension drawing DPL 1 F ALE 48 – ALE 110
coils and varistors to PG.
• Low self-heating
• For use according to the lightning
protection zones concept at bounda- Protective plug 1 TC with 2-stage protective circuit for load circuits with common reference
ries 0B – 2 and higher potential. Earthing via ES 10 DA. For disconnection blocks only.
Ordering information
Type DPL 1 F ALE 48 DPL 1 F ALE 60 DPL 1 F ALE 110
Part No. 907 124 907 125 907 126
Packing unit 10 pc(s) 10 pc(s) 10 pc(s)
PU Part
Type pc(s) No.
ES 10DA 1 907 998
192 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DPL
07 127 DPL 1 F
ARE 5
LSA-PLUS TECHNOLOGY
ARE 12
07 129 DPL 1 F
ARE 15
07 130 DPL 1 F
ARE 24
2 4
Dimension drawing DPL 1 F ARE 5 – ARE 24 Combination of gas discharge tubes, decoupling • Good transmission performance
resistors and diodes to PG.
• Decoupling resistance integrated
• For use according to the lightning
Protective plug 1 TC with 2-stage protective circuit for signal circuits with common reference protection zones concept at bounda-
potential. Earthing via ES 10 DA. For disconnection blocks only. ries 0B – 2 and higher
Ordering information
Type DPL 1 F ARE 5 DPL 1 F ARE 12 DPL 1 F ARE 15 DPL 1 F ARE 24
Part No. 907 127 907 128 907 129 907 130
Packing unit 10 pc(s) 10 pc(s) 10 pc(s) 10 pc(s)
PU Part
Type pc(s) No.
ES 10DA 1 907 998
www.dehn.de 193
DPL INFORMATION TECHNOLOGY SYSTEMS
907 112 DPL 10 F
ARE 12
DPL 10 F ARE
907 110 DPL 10 F
LSA-PLUS TECHNOLOGY
ARE 24
907 111 DPL 10 F
ARE 110
IN
1 2 3 4 5 6 7 8 9 10
DPL 10 F ARE 12 Surge
Protective Block DPL 10 F, 12 V 907 112
DPL 10 F ARE 24 Surge
Protective Block DPL 10 F, 24 V 907 110
DPL 10 F ARE 110 Surge
Protective Block DPL 10 F, 110 V 907 111
OUT
• Simultaneous protection for Combination of gas discharge tubes, decoupling Dimension drawing DPL 10 F ARE
20 wires / 10 TC resistors and diodes to PG for 20 single wires.
• Quick installation
• For use according to the lightning Protective plug 10 TC, with 2-stage protective circuit for signal circuits with common potential.
protection zones concept at bounda- Type 110 for use in telecommunications. For disconnection blocks only.
ries 0B – 2 and higher
Ordering information
Type DPL 10 F ARE 12 DPL 10 F ARE 24 DPL 10 F ARE 110
Part No. 907 112 907 110 907 111
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
194 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DPL
07 210 DPL 10
G2 110
DPL 10 G
07 214 DPL 10
LSA-PLUS TECHNOLOGY
G3 110
07 215 DPL 10
G3 110 FS
DPL 10 G2 110
echnology, 10 TC -SET-
LSA-Plus
907 210
IN
DPL 10 G3 110 LSA-Plus
echnology, 10 TC
DPL 10 G3 110 FS
907 214
LSA-Plus 1 2 3 4 5 6 7 8 9 10
echnology, 10 TC FS 907 215
OUT
Dimension drawing DPL 10 G Mounting rails connected with 2- or 3-pole gas • Block mounting rail for powerful
discharge tubes – according to type. surge arresters with or without fail-
safe function
Protective plug 10 TC with gas discharge tubes for nearly all kinds of applications. DPL 10 G2 is a • Max. discharge capacity if used in
set of 1x block mounting rail (907 212) with transparent cover (907 213) and 20x gas discharge terminal blocks
tubes (907 211). DPL 10 G3 is a mounting rail already equipped with surge arresters. • For use according to the lightning
Amendment FS stands for fail-safe function. protection zones concept at bounda-
ries 0A – 1 and higher
Ordering information
Type DPL 10 G2 110 DPL 10 G3 110 DPL 10 G3 110 FS
Part No. 907 210 907 214 907 215
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 195
INFORMATION TECHNOLOGY SYSTEMS
LSA-PLUS TECHNOLOGY
PU Part PU Part
Type pc(s) No. Type pc(s) No.
ES 10DA 1 907 998 AD BM 10DA 1 907 213
907 212 BM 10DA Block for gas discharge tubes 907 211 GDT 230
196 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Accessories for LSA-PLUS Technology
LSA-PLUS TECHNOLOGY
• Approved quality
• 45° angled IDC contacts
• Further accessories available on request
The IDC termination method is used for installing many lines quickly and Having used wires with a diameter of 0.65 mm, a re-wiring to smaller
economically. This method is especially common in telecommunications diameters is no longer possible.
(e.g. DTAG).
The blocks are suitable for connection of plastic-insulated wires with
copper conductor material:
Conductor diameter: 0.4-0.8 mm
Outer diameter: 0.7-1.5 mm
MB2 10 LSA
Ordering information
Type MB2 10 LSA
Part No. 907 995
Packing unit 1 pc(s)
Insertion tool with sensor for LSA-PLUS connections for connecting the wires and simultaneous Insertion Tool
07 994 AW2 LSA
cutting of residual lengths. With extractor hook and blade.
AW2 LSA
Ordering information
Type AW2 LSA
Part No. 907 994
Packing unit 1 pc(s)
www.dehn.de 197
Accessories for LSA-PLUS Technology INFORMATION TECHNOLOGY SYSTEMS
LSA-PLUS TECHNOLOGY
Terminal Block Series 2 for LSA-PLUS connections for connecting 10 two-core conductors, each to a non-open
termination on the cable and routing side. DPL 1 G or DPL 10 G can be plugged in. Parallel
protective circuit only.
Ordering information
Type AL2 10DA LSA
Part No. 907 997
Packing unit 1 pc(s)
Disconnection Block Series 2 for LSA-PLUS connections for connecting 10 two-core conductors, each on the cable and 907 996 TL2 10DA
LSA
routing side. By plugging DPL ... F in, the protection is serially provided between the disconnec- TL2 10DA LSA
Disconnection Modules 10 TC LSA-PLUS 907 996
Ordering information
Type TL2 10DA LSA
Part No. 907 996
Packing unit 1 pc(s)
Earth Conductor Block Series 2 for LSA-PLUS connections for connecting 38 earth conductors or shields. 907 993 EL2 38EA
LSA
Ordering information
Type EL2 38EA LSA
Part No. 907 993
Packing unit 1 pc(s)
198 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS NET Protector
SPDs FOR 19” TECHNOLOGY Surge Arrester
19” enclosure, equippable with up to 3 surge protective boards for pro- NET Protector requires space of only 1 vertical module and is mostly
tection of active network components like HUBs, switches (class D) or installed into terminal boards. It is inserted as a patch panel with surge
telecommunication systems. Typical applications: Ethernet, Token Ring, E1 protection or as a retrofitted device for patching between the patch panel
and ISDN. and the device to be protected.
b
9
7
4
a
7
33
3
6
5
4
NET PRO TC
No. 929 2 LSA
072 Uc 170V
c 8
c
1
Installation drawing
GHTM Certificate
www.dehn.de 199
NET-Protector INFORMATION TECHNOLOGY SYSTEMS
Surge Arrester SPDs FOR 19” TECHNOLOGY
200 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS NET Protector
29 035 NET PRO
TP
1 1
NET PRO 4TP NET-
rotector 4TP 929 035 1 1
NET PRO LSA 4TP NET-
rotector/LSA-PLUS/4TP 929 036
NET PRO 4TP 30 NET-
rotector 4TP 30 929 037
2 2
2 3 3 2
3 3
6 6
4 4
6 6
4 4
5 5
7 7
5 5
7 7
8 8
8 8
Dimension drawing NET PRO 4TP Fine protection for all pairs thanks to low • GHMT certificate for class D channel
capacitance diode matrix for each pair. link
• Low protection level for all lines
Fine protection board with 8 shielded ports for universal cablings (class D). For universal use as • For use according to the lightning
protection for all 4 pairs (4 TP) is provided. To be installed into EG NET PRO 19“ and mounted protection zones concept at
into the distribution cabinet as a patch field or retrofitting unit boundaries 1 – 2 and higher
NET PRO 4TP NET PRO LSA 4TP NET PRO 4TP 30
Nominal voltage UN 5V 5V 24 V
Max. continuous dc voltage Uc 6V 6V 30 V
Max. continuous ac voltage Uc 4.2 V 4.2 V 21.1 V
Nominal current IL 100 mA 100 mA 100 mA
C2 Nominal discharge current (8/20) per port In 2.4 kA 2.4 kA 0.8 kA
C2 Nominal discharge current (8/20) per line In 0.3 kA 0.3 kA 0.1 kA
Voltage protection level line-line at In C2 Up ≤ 35 V ≤ 35 V ≤ 60 V
Voltage protection level line-PG at In C2 Up ≤ 35 V ≤ 35 V ≤ 60 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 13 V ≤ 13 V ≤ 40 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 13 V ≤ 13 V ≤ 40 V
Bandwidth line-line at 100 Ohm fG 165 MHz 170 MHz 300 MHz
Insertion loss at 100 MHz < 0.4 dB < 0.3 dB < 0.4 dB
Capacity line-line C ≤ 35 pF ≤ 35 pF ≤ 16 pF
Capacity line-PG C ≤ 50 pF ≤ 50 pF ≤ 20 pF
Response time line-line ta ≤ 1 ns ≤ 1 ns ≤ 1 ns
Response time line-PG ta ≤ 1 ns ≤ 1 ns ≤ 1 ns
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C
Degree of protection IP 00 IP 00 IP 00
Mounting in enclosure enclosure enclosure
Connection input/output RJ45 shielded / RJ45 shielded LSA-PLUS / RJ45 shielded RJ45 shielded / RJ45 shielded
Pinning 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8 1/2, 3/6, 4/5, 7/8
Earthing via enclosure enclosure enclosure
Dimension W x L 135 x 77 mm 135 x 107 mm 135 x 77 mm
Test standards VDE 0845-2, IEC 61643-21 VDE 0845-2, IEC 61643-21 VDE 0845-2, IEC 61643-21
Approvals, Certifications Class D — —
Ordering information
Type NET PRO 4TP NET PRO LSA 4TP NET PRO 4TP 30
Part No. 929 035 929 036 929 037
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 201
NET Protector INFORMATION TECHNOLOGY SYSTEMS
929 067 NET PRO
ISDN
5 5
6 6
3 3
• Patch panel or retrofitting unit Energy-coordinated ISDN 4-wire protective circuit Dimension drawing NET PRO ISDN
with additional protection of the remote power
• Protection integrated for the remote supply.
power supply
• For use according to the lightning Surge protective board with 8 unshielded ports for ISDN S0 systems. Installation into EG NET PRO
protection zones concept at 19“ and mounting in distribution boards upstream of the telecommunication system. Retrofitting
boundaries 0B – 2 and higher or patch panel unit (LSA)
Ordering information
Type NET PRO ISDN NET PRO ISDN LSA
Part No. 929 067 929 068
Packing unit 1 pc(s) 1 pc(s)
NET PRO TC
29 070 NET PRO
5 5
ϑ
Dimension drawing NET PRO TC PTC thermistors decouple the protective stages • Patch panel or retrofitting unit
and thus protect the terminal systems additionally
at “power crossings“. Please consider the reser- • Protection integrated against power
vation depending on the type. crossing
Protective board with 8 unshielded ports against surges and ac current influences on • For use according to the lightning
telecommunication systems with analogue or system transmission technology. For installation protection zones concept at
into EG NET PRO 19“ as retrofitting or patch panel unit (LSA) boundaries 0B – 2 and higher
NET PRO TC 1 NET PRO TC 1 LSA NET PRO TC 2 NET PRO TC 2 LSA
Nominal voltage UN 130 V 130 V 130 V 130 V
Max. continuous dc voltage Uc 170 V 170 V 170 V 170 V
Max. continuous ac voltage Uc 120 V 120 V 120 V 120 V
Nominal current IL 150 mA 150 mA 150 mA 150 mA
C2 Nominal discharge current (8/20) per port In 5 kA 10 kA 10 kA 20 kA
C2 Nominal discharge current (8/20) per line In 2.5 kA 5 kA 2.5 kA 5 kA
Voltage protection level line-line at In C2 Up ≤ 250 V ≤ 275 V ≤ 250 V ≤ 275 V
Voltage protection level line-PG at In C2 Up ≤ 600 V ≤ 600 V ≤ 600 V ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 230 V ≤ 230 V ≤ 230 V ≤ 230 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 600 V ≤ 600 V ≤ 600 V ≤ 600 V
Coordination characteristics KK X/2 X/2 X/2 X/2
Series impedance per line 10 Ohm 10 Ohm 10 Ohm 10 Ohm
Bandwidth line-line fG 10 MHz 10 MHz 10 MHz 10 MHz
Capacity line-line C ≤ 300 pF ≤ 300 pF ≤ 300 pF 300 pF
Capacity line-PG C ≤ 15 pF ≤ 15 pF ≤ 15 pF 15 pF
Response time line-line ta ≤ 1 ns ≤ 1 ns ≤ 1 ns ≤ 1 ns
Response time line-PG ta ≤ 100 ns ≤ 100 ns ≤ 100 ns ≤ 100 ns
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C
Degree of protection IP 00 IP 00 IP 00 IP 00
Mounting in enclosure enclosure enclosure enclosure
Connection input/output RJ45 / RJ45 LSA-PLUS / RJ45 RJ45 / RJ45 LSA-PLUS / RJ45
Pinning 4/5 4/5 4/5, 3/6 4/5, 3/6
Earthing via enclosure enclosure enclosure enclosure
Dimension W x L 135 x 77 mm 135 x 107 mm 135 x 77 mm 135 x 107 mm
Test standards VDE 0845-2, IEC 61643-21 VDE 0845-2, IEC 61643-21 VDE 0845-2, IEC 61643-21 VDE 0845-2, IEC 61643-21
Ordering information
Type NET PRO TC 1 NET PRO TC 1 LSA NET PRO TC 2 NET PRO TC 2 LSA
Part No. 929 069 929 070 929 071 929 072
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 203
NET Protector INFORMATION TECHNOLOGY SYSTEMS
929 074 NET PRO
E1 LSA
1/7
1
2
2/8 3
4
4/3 5
6
7
5/6 8
• Patch panel unit Energy-coordinated 2 TC protective circuit for Dimension drawing NET PRO E1 LSA
2 plug-in reservations at the protected port.
• Suitable for different RJ45 reser-
vations
• For use according to the lightning Surge protective board, patch panel unit, with 8 unshielded ports for E1 interfaces. Installations
protection zones concept at into EG NET PRO 19“ and mounting in distribution boards upstream of the telecommunication
boundaries 0B – 2 and higher system. Variable connection by reservation of several socket pins
Ordering information
Type NET PRO E1 LSA
Part No. 929 074
Packing unit 1 pc(s)
204 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpatch
RJ CONNECTION
DEHNpatch is the first patch cable with surge protection in Cat. 6 per-
formance that can be used universally acc. to EN 50173 up to 48 V dc.
The design of the new surge arrester DEHNpatch as a patch cable is revo- requirements of Cat. 6 and can be used universally for nominal voltages
lutionary. It allows not only to equip new installations very easily, but also up to 48 V. Both existing applications in offices and industry like Gigabit
any retrofittings at existing installations without great installation work. Ehernet, ATM or ISDN, and future systems like Voice of IP and Power Over
DEHNpatch is simply plugged in between the patch panel and the active Ethernet can be protected. Thanks to its fully shielded design DEHNpatch
component (e.g. switch) instead of a conventional patch cable. The DIN can be used in shielded and unshielded networks. The width corresponds
rail mountable supporting foot with snap-in device provides safe eart- approximately to a RJ45 socket. Thus up to 24 devices can be installed in
hing. For single application, a piece of DIN rail with fixing device is inclu- one series and be integrated into a 19” rack.
ded in delivery. For multiple application the DEHNpatch mounting set The standard total cable length of DEHNpatch is 3 m and 5 m (other
would be helpful. This can be provided as accessory. DEHNpatch fulfils the lengths available on request).
GHMT Certificate DPA M CAT6 RJ45S 48 GHMT Certificate DPA M CAT6 RJ45H 48
www.dehn.de 205
DEHNpatch INFORMATION TECHNOLOGY SYSTEMS
929 100 DPA M
CAT6 RJ45S 48
DPA M CAT 6
929 110 DPA M
RJ CONNECTION
CAT6 RJ45H 48
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
• Ideal for retrofitting with protection Protection of all pairs with heavy duty gas dis- Dimension drawing DPA M CAT 6 RJ45 S48
for all lines charge tubes and a low capacitance diode matrix
per pair.
• Cat. 6 acc. to ISO/IEC 118001
• Application according to the lightning Fully shielded universal surge arrester for use as patch cable for Ethernet and similar applications
protection zones concept at bounda- in universally structured cabling systems of Category 6 or class E.
ries 0B – 2 and higher
Ordering information
Type DPA M CAT6 RJ45S 48 DPA M CAT6 RJ45H 48
Part No. 929 100 929 110
Packing unit 1 pc(s) 1 pc(s)
206 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
RJ CONNECTION Surge Arrester
Surge arrester as DIN rail mountable device for terminal telecommunica- gateways (TK/EiB interface) or for protection of industrial modems for DIN
tion equipment and telephone systems with RJ plug-in connection for DIN rail mounting.
rail mounting. They are often used in installations upstream of residential
RJ sockets and screw terminals at the The SPD for DIN rail mounting was deve-
input and output of BVT TC 1 allow an loped for installation-friendly protection
especially universal use. For example for of the S0 input of residential gateways.
installation upstream of NTBA’s with The integrated distribution function at
screw wiring or screw/plug-in connection the protected output allows the wiring
upstream of modems and telecommuni- of two protected outgoing ISDN bus
cation systems. circuits.
www.dehn.de 207
BLITZDUCTOR® VT INFORMATION TECHNOLOGY SYSTEMS
918 410 BVT ISDN
3 3
BVT ISDN BLITZ-
DUCTOR VT 918 410
6 6
IN OUT
4 4
5 5
a2
a1
b1
b2
• RJ45 sockets Energy-coordinated ISDN 4-wire protective circuit Dimension drawing BVT ISDN
with additional protection of the remote power
• Additional screw terminals for the supply.
ISDN lines
• For use according to the lightning For ISDN S0 buses with RJ45 connections. The additional screw terminal connection at the
protection zones concept at bounda- protected output allows a double wiring of the S0 bus (distribution function).
ries 0B – 2 and higher
BVT ISDN
Nominal voltage UN 5V
Nominal voltage pa-pa UN 40 V
Max. continuous dc voltage UC 7.5 V
Max. continuous dc voltage pa-pa UC 60 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 2.5 kA
Voltage protection level line-line at In C2 Up ≤ 30 V
Voltage protection level line-PG at In C2 Up ≤ 600 V
Voltage protection level pa-pa at In C2 Up ≤ 130 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 17 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 600 V
Voltage protection level pa-pa at 1 kV/µs C3 Up ≤ 100 V
Coordination characteristics KK X/1
Series impedance per line 1.0 Ohm
Bandwidth line-line fG 1.7 MHz
Capacity line-line C ≤ 3.3 nF
Capacity line-PG C ≤ 15 pF
Capacity pa-pa C ≤ 600 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Response time pa-pa ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 10
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output RJ45/RJ45 or terminals
Pinning 3/6, 4/5
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via terminal
Enclosure material thermoplastic, UL 94- V-0
Colour yellow
Test standards IEC 61643-21
Ordering information
Type BVT ISDN
Part No. 918 410
Packing unit 1 pc(s)
208 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® VT
18 411 BVT TC 1
RJ CONNECTION BVT TC
BVT TC 1 BLITZ-
DUCTOR VT 918 411
4 4
IN OUT
5 5
a1 a1
b1 b1
Dimension drawing BVT TC Energy-coordinated protective circuit, free of • RJ sockets, compatible with RJ12 pins
leakage currents to earth.
• Additional screw terminals for the a/b
lines
For a/b lines, ISDN Uk0 or ADSL with RJ45 connections and additional screw terminal connections. • For use according to the lightning
The pinning of the RJ45 sockets is compatible with RJ11/12. The parallel screw terminals are protection zones concept at bounda-
more robust than the RJ45 sockets and increase In to 10 kA. ries 0B – 2 and higher
BVT TC 1
Nominal voltage UN 130 V
Max. continuous dc voltage UC 170 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20) In 5 kA
C2 Nominal discharge current (8/20) per line In 2.5 kA
Voltage protection level line-line at In C2 Up ≤ 275 V
Voltage protection level line-PG at In C2 Up ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 240 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 600 V
Coordination characteristics KK X/2
Series impedance per line 4.7 Ohm
Bandwidth line-line fG 17 MHz
Capacity line-line C ≤ 300 pF
Capacity line-PG C ≤ 15 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 10
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output RJ45 or terminals / RJ45 or terminals
Pinning 4/5
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via screw terminal
Enclosure material thermoplastic, UL 94 V-0
Colour yellow
Test standards IEC 61643-21
Ordering information
Type BVT TC 1
Part No. 918 411
Packing unit 1 pc(s)
www.dehn.de 209
DSM TM INFORMATION TECHNOLOGY SYSTEMS
Surge Arrester RJ CONNECTION
DSM TM is a surge arrester close to terminal equipment, designed for both ISDN S0 and Ethernet 10 BT (class C cabling). As screw terminals are
Touch Manager wave (Siemens). Usually the SPD is integrated into flush- available at the input, they can be connected with both rigid and flexible
mounted or small-sized distribution boards and connected with the local conductors or shields.
equipotential bonding of the terminal device. Because of the universal
reservation of the pluggable RJ45 output, it can be used for protection of
Delivery of DSM TM
210 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DSM TM
24 274 DSM TM
RJ CONNECTION DSM TM
1
2
a1 3
b1 4
5
a2 6
b2 7
8
SHL
Dimension drawing DSM TM Low-capacitance structure with high discharge • Indirect shield earthing
capacity and low voltage protection level
between the signal cores. • Installation accessories included
• For use according to the lightning
For IT installations, class C, or services like Ethernet 10 BT or ISDN S0 interfaces. Transition from protection zones concept at bounda-
screw terminal to RJ45 plug. No leakage pickups are generated thanks to the indirect shielding. ries 0B – 2 and higher
DSM TM
Nominal voltage UN 5V
Max. continuous dc voltage UC 6V
Max. continuous ac voltage Uc 4.2 V
Nominal current IL 200 mA
C1 Nominal discharge current (8/20) line-line In 500 A
C2 Nominal discharge current (8/20) line-PG In 5 kA
C2 Total nominal discharge current (8/20) line-PG In 10 kA
Voltage protection level line-line at In C1 Up ≤ 28 V
Voltage protection level line-PG at In C2 UP ≤ 600 V
Voltage protection level shield-PG at In C2 UP ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 UP ≤ 11 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 380 V
Voltage protection level shield-PG at 1 kV/µs C3 UP ≤ 600 V
Coordination characteristics KK X/1
Bandwidth fG 55 MHz
Capacity line-line C ≤ 75 pF
Capacity line-PG C ≤ 20 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Response time shield-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output screw terminal / RJ45 connecting lead
Pinning Ethernet 1/2, 3/6 or ISDN 4/5, 3/6
Cross-sectional area, solid 0 - 1.0 mm2
Cross-sectional area, flexible 0 - 1.0 mm2
Tightening torque (terminal) 0.3 Nm
Earthing via lead 1.0 mm2
Enclosure material polyamide PA 6.6, UL 94 V-2
Colour yellow
Test standards IEC 61643-21
Accessories adhesive pad, socket terminal
Ordering information
Type DSM TM
Part No. 924 274
Packing unit 1 pc(s)
www.dehn.de 211
DEHNlink INFORMATION TECHNOLOGY SYSTEMS
Surge Arrester RJ CONNECTION
Surge arrester for surface mounting in modern design. It protects Compared to conventional devices
especially modems and telephone systems with RJ plug-in connection. The ( ... ECO), the different SPD units with
plug-in connections allow an easy installation. type description ...I have an additional
LED indication of the supply voltage.
This helps to recognise interferences on
the installation immediately.
Furthermore, they provide a wide range
of accessories like connecting cables or
fixing material.
Unit with and without state
indication
With its integrated distribution function, DLI ISDN I can protect two
DEHNlink
terminal devices at the same time. The state indication is only illumina-
ISDN/I
ted, if the NTBA is also connected to the power supply and not at
UC 7,5 V
SPD X 2 isn 2,5 kA
Line protected
emergency operation (remote supply of telecommunication network
ISDN
operators).
ISDN
LED on ok
State
Faulty
212 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNlink
29 024 DLI ISDN I
6 6
protected
4 4
5 5
3
6
4
5
Dimension drawing DLI ISDN I Energy-coordinated ISDN 4-wire protective circuit • 2 protected outputs
with additional protection and indication of the
remote power supply. • Surge protection and LED indication
of the remote supply included
SPD with two protected ISDN S0 outputs (distribution function) and state indication (LED) of the • For use according to the lightning
remote supply voltage. No indication at emergency operation (supply from telephone system protection zones concept at bounda-
only). Connecting cable and mounting material included. ries 0B – 2 and higher
DLI ISDN I
Nominal voltage UN 5V
Nominal voltage pa-pa UN 40 V
Max. continuous dc voltage Uc 7.5 V
Max. continuous ac voltage Uc 5.2 V
Max. continuous dc voltage pa-pa UC 45 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 2.5 kA
Voltage protection level line-line at In C2 Up ≤ 30 V
Voltage protectino level line-PG at In C2 Up ≤ 600 V
Voltage protection level pa-pa at In C2 Up ≤ 180 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 17 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 600 V
Voltage protection level pa-pa at In C2 Up ≤ 100 V
Coordination characteristics KK X/1
Series impedance per line 1 Ohm
Bandwidth line-line 2 MHz
Parasitic capacitance line-line C ≤ 3 nF
Parasitic capacitance line-PG C ≤ 15 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Response time pa-pa ta ≤ 25 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection: input/output RJ45 / 2 x RJ45
Pinning 3/6, 4/5
Earthing via flat connector 6.3 mm
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Accessories connecting lead, mounting material
Ordering information
Type DLI ISDN I
Part No. 929 024
Packing unit 1 pc(s)
www.dehn.de 213
DEHNlink INFORMATION TECHNOLOGY SYSTEMS
929 027 DLI TC 1 I
929 028 DLI TC 2 I
DLI TC I RJ CONNECTION
3 3
DLI TC 1 I DEHNlink
ϑ TC 1
DLI TC 2 I
929 027
DEHNlink
TC 2 929 028
6 6
ϑ
protected
4 4
ϑ
5 5
ϑ
• LED indication of the supply voltage 2-stage protective circuit with overcurrent pro- Dimension drawing DLI TC I
tection and system voltage indication. Please
• Protection integrated against power note: The figure shows the 2 TC unit of DLI TC 2 I.
crossing
• For use according to the lightning Protective device for analogue or system telephony with operating state indication (LED).
protection zones concept at bounda- Protects also against ac current influences. TC protection for 1 or 2 two-core conductors (TC).
ries 0B – 2 and higher Compatible with pins of RJ11/12 plugs. Connecting cable and mounting material included.
DLI TC 1 I DLI TC 2 I
Nominal voltage UN 110 V 110 V
Max. continuous dc voltage Uc 170 V 170 V
Max. continuous ac voltage Uc 120 V 120 V
Nominal current IL 150 mA 150 mA
C2 Total nominal discharge current (8/20) In 5 kA 10 kA
C2 Nominal discharge current (8/20) per line In 2.5 kA 2.5 kA
Voltage protection level line-line at In C2 Up ≤ 250 V ≤ 250 V
Voltage protectino level line-PG at In C2 Up ≤ 600 V ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 230 V ≤ 230 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 600 V ≤ 600 V
Coordination characteristics KK X/2 X/2
Series impedance per line 10 Ohm 10 Ohm
Bandwidth line-line 10 MHz 10 MHz
Parasitic capacitance line-line C ≤ 300 pF ≤ 300 pF
Parasitic capacitance line-PG C ≤ 15 pF ≤ 15 pF
Response time line-line ta ≤ 1 ns ≤ 1 ns
Response time line-PG ta ≤ 100 ns ≤ 100 ns
Operating temperature range -40°C...+80°C -40°C...+80°C
Degree of protection IP 20 IP 20
Connection: input/output RJ45 / RJ45 (compatible with RJ12) RJ45 / RJ45
Pinning 4/5 (3/4 at RJ12) 3/6, 4/5
Earthing via flat connector 6.3 mm flat connector 6.3 mm
Enclosure material polyamide PA 6.6 polyamide PA 6.6
Colour yellow yellow
Test standards IEC 61643-21 IEC 61643-21
Accessories connecting lead, mounting material connecting lead, mounting material
Ordering information
Type DLI TC 1 I DLI TC 2 I
Part No. 929 027 929 028
Packing unit 1 pc(s) 1 pc(s)
214 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNlink
29 029 DLI TC DK
29 080 DLI TC
DLI TC
CO
RJ CONNECTION
29 081 DLI TC
CO RJ12
DLI TC DK DEHNlink-
Denmark 929 029
DLI TC ECO DEHNlink-
Denmark 929 080
DLI TC ECO RJ12 DEHNlink-
Denmark 929 081
4 4
protected
5 5
Dimension drawing DLI TC Using a high-capacity varistor, the decoupling to • Economical protection for 1 two-core
the gas discharge tube can be omitted. conductor
• Modern design
Protective device for analogue or system telephony, RJ45 or RJ12 unit. DK unit specified for use • For use according to the lightning
in Denmark. protection zones concept at bounda-
ries 0B – 2 and higher
Ordering information
Type DLI TC DK DLI TC ECO DLI TC ECO RJ12
Part No. 929 029 929 080 929 081
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 215
INFORMATION TECHNOLOGY SYSTEMS
216 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNlink TC BT
BT JACK CONNECTION Surge Arrester
www.dehn.de 217
DEHNlink TC BT INFORMATION TECHNOLOGY SYSTEMS
929 026 DLI TC BT
1 1 DLI TC BT
BT
DEHNlink
929 026
6 6
2 2
protected
5 5
3 3
4 4
• Unit according to British Telecom Energy-coordinated protective circuit for all pairs, Dimension drawing DLI TC BT
requirements free of leakage currents to earth.
DLI TC BT
Nominal voltage UN 130 V
Max. continuous dc voltage UC 145 V
Nominal current IL 125 mA
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 Up ≤ 210 V
Voltage protection at In C2 Up ≤ 550 V
Voltage protection level line-line at 1 kV/µs C3 UP ≤ 185 V
Voltage protection level line-PG at 1 kV/µs line/PG UP ≤ 450 V
Series impedance per line 4.7 Ohm
Coordination characteristics KK X/2
Bandwidth fG 13 MHz
Parasitic capacitance line-line C ≤ 400 pF
Parasitic capacitance line-PG C ≤ 10 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output BT jack / BT jack
Pinning 1/6, 2/5, 3/4
Earthing via flat connector 6.3 mm
Enclosure thermoplastic
Colour black
Test standards IEC 61643-21
Accessories connecting lead, mounting material
Ordering information
Type DLI TC BT
Part No. 929 026
Packing unit 1 pc(s)
218 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS UGKF
COAXIAL CONNECTION Surge Arrester
Surge arrester as cable adapter for coaxial systems like video systems
and computer networks.
UGKF are shielded surge arresters for plugging into coaxial terminal devices cable shield is earthed indirectly via a gas discharge tube. The arrester
or connections. Frequent applications are outdoor video surveillance entries are used as sockets and protected outputs as plugs.
systems or computer networks. In order to avoid leakage pickups, the
Application of UGKF B L
www.dehn.de 219
UGKF INFORMATION TECHNOLOGY SYSTEMS
929 010 UGKF
BNC
• Easily adaptable Low-capacitance, 2-stage protective circuit with Dimension drawing UGKF BNC
indirect shield earthing for avoiding leakage
• Avoids leakage pickups pickups.
• For use according to the lightning
protection zones concept at bounda- UGKF BNC is suitable for video cameras and Arcnet with BNC connection. Special units for video
ries 0B – 2 and higher cameras with higher nominal voltage can be provided on request.
UGKF BNC
Nominal voltage UN 5V
Max. continuous dc voltage UC 8V
C2 Nominal discharge current (8/20) per line In 2.5 kA
C2 Nominal discharge current (8/20) shield-PG In 10 kA
Voltage protection level line-shield at In C2 UP ≤ 25 V
Voltage protection level line-shield at 1 kV/µs C3 UP ≤ 13 V
Voltage protection level shield-PG at 1 kV/µs C3 Up ≤ 600 V
Series impedance per line 10 Ohm
Bandwidth fG 300 MHz
Return loss ≥ 20 dB to 40 MHz
Response time line-shield ta ≤ 1 ns
Response time shield-PG ta ≤ 100 ns
Connection input/output BNC socket / BNC plug
Earthing via outgoing earth conductor 0.75 mm2
Shield earthing indirectly via an integrated spark gap
Test standards VDE 0845-1, IEC 61643-21
Ordering information
Type UGKF BNC
Part No. 929 010
Packing unit 1 pc(s)
220 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS UGKF
29 017 UGKF B L
Dimension drawing UGKF B L Low-capacitance, 2-stage protective circuit with • Easily adaptable
indirect shield earthing for avoiding leakage
pickups. • Avoids leakage pickups
• For use according to the lightning
UGKF B L is suitable for Ethernet 10 Base 2 with BNC connection. The SPD can be used in protection zones concept at bounda-
segments in any quantity. It can also be connected with EAD sockets or tees. ries 0B – 2 and higher
UGKF B L
Nominal voltage UN -8 / +1 V
Max. continuous dc voltage UC -10 / +1.4 V
C2 Nominal discharge current (8/20) per line In 2.5 kA
C2 Nominal discharge current (8/20) shield-PG In 10 kA
Voltage protection level line-shield at In C2 UP 35 V
Voltage protection level line-shield at 1 kV/µs C3 UP 15 V
Voltage protection level shield-PG at 1 kV/µs C3 Up 600 V
Series impedance per line 1 Ohm
Bandwidth fG 300 MHz
Return loss ≥ 20 dB to 100 MHz
Response time line-shield ta ≤ 1 ns
Response time shield-PG ta ≤ 100 ns
Connection input/output BNC socket / BNC plug
Earthing via outgoing earth conductor 0.75 mm2
Shield earthing indirectly via an integrated spark gap
Test standards VDE 0845-2, IEC 61643-21
Ordering information
Type UGKF B L
Part No. 929 017
Packing unit 1 pc(s)
www.dehn.de 221
UGKF INFORMATION TECHNOLOGY SYSTEMS
929 012 UGKF N L
• Easily adaptable Low-capacitance, 2-stage protective circuit with Dimension drawing UGKF N L
indirect shield earthing for avoiding leakage
• Avoids leakage pickups pickups
• For use according to the lightning
UGKF N L is suitable for Ethernet 10 Base 5 with N connection. Max. 2 SPDs may be installed in
protection zones concept at bounda-
one segment. An insulating sleeve is included in delivery for isolating the enclosure from earth
ries 0B – 2 and higher
potential.
UGKF N L
Nominal voltage UN -8 / +1 V
Max. continuous dc voltage UC -10 / +1.4 V
C2 Nominal discharge current (8/20) per line In 2.5 kA
C2 Nominal discharge current (8/20) shield-PG In 10 kA
Voltage protection level line-shield at In C2 UP ≤ 20 V
Voltage protection level line-shield at 1 kV/µs C3 UP ≤ 15 V
Voltage protection level shield-PG at 1 kV/µs C3 Up ≤ 600 V
Series impedance per line 10 Ohm
Bandwidth fG 90 MHz
Return loss ≥ 20 dB to 20 MHz
Response time line-shield ta ≤ 1 ns
Response time shield-PG ta ≤ 100 ns
Connection input/output N socket / N plug
Earthing via outgoing earth conductor 0.75 mm2
Shield earthing indirectly via integrated spark gap
Test standards VDE 0845-1, IEC 61643-21
Accessories insulating sleeve
Ordering information
Type UGKF N L
Part No. 929 012
Packing unit 1 pc(s)
222 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
COAXIAL CONNECTION Lightning Current / Surge Arrester
DEHNgate is a family of lightning current / surge arresters in cable adap- According to application, different mechanical and electrical units are
ter design for coaxial systems like cell sites and antenna systems. available.
Coaxial DGA surge arresters can be pro- DGA FF TV can be mounted on DIN rails
vided with different kinds of plugs. Units in a space-saving way for protection of
for protection of video systems with a satellite systems with several outputs.
higher supply voltage or with a bilateral For single applications like cable TV con-
socket connection are also available on nections, the wall mounting adapter is of
request. help, which the device can be clicked
into. 2 F-cable connectors are also inclu-
ded.
DGA Arrester Family
Spark gap based surge arresters have an internal gas-filled surge arrester and can be
defined as low pass. This allows also a dc transmission (antenna supply). Peak voltages
exceeding the treshold voltage of the gas discharge tube are discharged. These arres- Application of quarterwave
ters provide extensive contact surfaces from the inner conductor to the gas discharge arrester
tube. This minimises the burn-off of the material during the discharge and ensures a
constant transmission performance.
Principle of a spark gap based
SPD
www.dehn.de 223
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
Lightning Current / Surge Arrester COAXIAL CONNECTION
1 Signal Test
HF test signal
te
SPD FF TV
DEHNga
IN 703
24 V
UC 2A
No. 909
DGA
5-2400 MHz
TP
-20 dB
ok
5-3000 MHz protected
meter
DEHNgate
DGA FF TV
SPD
No. 909 703
IN 2A
TP = test point
2
UC 24 V
A
KLASSE
CLASS
HF test signal
check
system
te
SPD FF TV
DEHNga
IN 703
24 V
UC 2A
No. 909
DGA
5-2400 MHz
TP
-20 dB
meter
5-3000 MHz protected
DEHNgate
DGA FF TV
SPD
No. 909 703
IN 2A
input UC 24 V
A
protected output
KLASSE
CLASS
SPD FF TV
DEHNga
IN 703
24 V
UC 2A
No. 909
DGA
TP
5-2400 MHz -20 dB
DEHNgate
DGA FF TV
SPD
No. 909 703
IN 2A
UC 24 V
A
KLASSE
CLASS
EB
cable length
max. 0.5 m
AWG 6/16 mm2
EB
224 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
09 703 DGA FF
V
DGA FF TV DEHNgate
09 703
TP
protected
Dimension drawing DGA FF Simplified schematic diagram of the protective • Frequency range up to 3 GHz, suit-
circuit. able for reverse LAN channels
Surge arrester suitable for remote supply for 75 Ohm satellite and TV cable systems with inte- • Integrated measuring output
grated measuring output for checking the system. Suitable for all common TV and satellite • For use according to the lightning
applications. For space-saving DIN rail or wall mounting. protection zones concept at bounda-
ries 0 – 1 and higher
DGA FF TV
Max. continuous dc voltage UC 24 V
Nominal current IL 2A
D1 Lightning impulse current (10/350) Iimp 0.2 kA
C2 Nominal discharge current (8/20) In 1.5 kA
Voltage protection level at Iimp D1 UP ≤ 230 V
Voltage protection level at 1 kV/µs C3 UP ≤ 60 V
Frequency range dc, 5-3000 MHz
Insertion loss 5-862 MHz 1.2 dB (±0.7 dB)
Insertion loss 862-2400 MHz 1.4 dB (± 0.7 dB)
Insertion loss 2400-3000 MHz 2 dB (± 1 dB)
Return loss input (5-47 MHz) ≥ 14 dB
Return loss output (5-47 MHz) ≥ 14 dB
Return loss test socket (5-47 MHz) ≥ 18 dB
Return loss (47-3000 MHz) ≥ 18 dB (-1.5 dB/octave)
Test socket connection loss 20 dB (± 1 dB)
Shield attenuation 5-300 MHz ≥ 85 dB
Shield attenuation 300-470 MHz ≥ 80 dB
Shield attenuation 470-1000 MHz ≥ 75 dB
Shield attenuation 1000-3000 MHz ≥ 55 dB
Surge impedance Z 75 Ohm
Response time line-shield ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 30
Mounting on 35 mm DIN rail acc. to EN 60715 or wall mounting
Connection input/output F socket / F socket
Earthing via DIN rail or screw connection
Enclosure material metal
Colour bare
Test standards IEC 61643-21
Ordering information
Type DGA FF TV
Part No. 909 703
Packing unit 1 pc(s)
www.dehn.de 225
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
929 040 DGA F 1.6
5.6
• For easy retrofitting Low-capacitance diode matrix for optimised Dimension drawing DGA F
transmission performance. Decoupling cable
• For high transmission rates length > 6 m to SPD, Part No. 929 041, required.
• For use according to the lightning
Surge arrester with integrated fine protection for G.703 interfaces. Earthing via enclosure. 1.6/5.6
protection zones concept at bounda-
connection. Optional energy coordination with DGA G 1.6 5.6, if the cable length in between is
ries 1 – 2 and higher
min. 6 m.
Ordering information
Type DGA F 1.6 5.6
Part No. 929 040
Packing unit 1 pc(s)
226 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
29 041 DGA G
.6 5.6
DGA G
29 042 DGA G
COAXIAL CONNECTION
BNC
29 044 DGA G N
29 058 DGA G N
Dimension drawings DGA G Fixed coaxial gas discharge tube • Min. dimension
• Extremely wide transmission range
• For use according to the lightning
Surge arrester suitable for remote supply, with integrated gas discharge tube. Especially adapted
protection zones concept at bounda-
to Wireless LAN and Wireless Local Loop applications in BNC, N or 1.5/5.6 connections for bulk-
ries 0B – 1 and higher
head mounting.
Ordering information
Type DGA G 1.6 5.6 DGA G BNC DGA G N DGA G N 3
Part No. 929 041 929 042 929 044 929 058
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 227
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
929 043 DGA AG
BNC
DGA AG
929 045 DGA AG
COAXIAL CONNECTION
N
929 057 DGA AG
U
• Support with great surface for con- Exchangeable gas discharge tube Dimension drawings DGA AG
nection of gas discharge tubes
• Long endurance due to min. contact
burn-off at the inner conductor
• For use according to the lightning Surge arrester suitable for remote supply with exchangeable gas discharge tube. Excellent RF
protection zones concept at bounda- endurance performance due to min. contact burn-off and great contact surface of the gas
ries 0A – 1 and higher discharge tube in a special cage.
Ordering information
Type DGA AG BNC DGA AG N DGA AG U
Part No. 929 043 929 045 929 057
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
228 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNgate
29 046 DGA LG 7
6
DGA LG 7 16 DEHNgate
29 046
/4
Dimension drawing DGA LG Quarterwave arrester combined with • For multi-frequency applications with
gas discharge tube dc supply
• Best transmission and PIM perfor-
mance
Surge arrester suitable for remote supply with combined spark gap based quarterwave techno- • For use according to the lightning
logy for multi-frequency applications (multi-carrier systems) because of minimum passive inter- protection zones concept at bounda-
modulation. Broad-band unit especially for all 4+3G services. ries 0A – 1 and higher
DGA LG 7 16
Max. continuous dc voltage UC 65 V
Nominal current IL 13 A
Max. transmission capacity 500 W
D1 Lightning impulse current (10/350) Iimp 5 kA
C2 Nominal discharge current (8/20) In 20 kA
Voltage protection level at 4 kV UOC Up ≤ 850 V
Frequency range dc, 806 MHz - 2.2 GHz
Insertion loss < 0.15 dB
Return loss ≥ 20 dB
Surge impedance Z 50 Ohm
Intermodulation typical -150 dB @ 2*43 dBm
Degree of protection IP 65
Connection input/output 7/16 socket / 7/16 plug
Earthing via earthing screw
Enclosure material brass, refined surface with trimetal plating
Colour bare
Exchangeable gas discharge tube yes
Test standards IEC 61643-21
Ordering information
Type DGA LG 7 16
Part No. 929 046
Packing unit 1 pc(s)
www.dehn.de 229
DEHNgate INFORMATION TECHNOLOGY SYSTEMS
929 047 DGA L4 7
16 S
DGA L4
929 048 DGA L4 7
COAXIAL CONNECTION
16 B
929 049 DGA L4 N
B
DGA L4 7 16 S DEHNgate
929 047
DGA L4 7 16 B DEHNgate
929 048
DGA L4 N B DEHNgate
929 049
/4
Ordering information
Type DGA L4 7 16 S DGA L4 7 16 B DGA L4 N B
Part No. 929 047 929 048 929 049
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
230 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS FS
D-SUB CONNECTION Surge Arrester
Surge protective adapter in metallised plastic enclosure with D-SUB plug- the application. Special versions with a different pinning or circuit are also
in terminal as socket – pin unit. The UNC screws can be exchanged in any available.
way so that either the pin or the socket is the threaded unit according to
www.dehn.de 231
FS INFORMATION TECHNOLOGY SYSTEMS
924 017 FS 9E PB
6
FS 9E PB D-SUB CONNECTION
6 6 FS 9E PB 6 Fine
Surge Protection Adapter FS 6 V 924 017
3 3
8 8
5 5
1 1
• Designed for Profibus-DP Diode protective circuit with very low capacity. Dimension drawing FS 9E PB
Pins 5 and 6 without protection for programming
• Transmission possible up to 12 MBit/s interface.
• For use according to the lightning
protection zones concept at bounda-
ries 1 – 2 and higher D-SUB, 9-pole device. Unit for Profibus-DP.
FS 9E PB 6
Nominal voltage UN 6V
Max. continuous dc voltage Uc 7V
C2 Nominal discharge current (8/20) line-line In 0.2 kA
C2 Nominal discharge current (8/20) line-SG In 0.2 kA
C2 Nominal discharge current (8/20) SG-PG In 0.4 kA
Voltage protection level line-line at In C2 UP ≤ 25 V
Voltage protection level line-SG at In C2 Up ≤ 25 V
Voltage protection level SG-PG at In C2 Up ≤ 25 V
Voltage protection level line-line at 1 kV/µs C3 UC ≤ 18 V
Voltage protection level line-SG at 1 kV/µs C3 Up ≤ 18 V
Voltage protection level SG-PG at 1 kV/µs C3 Up ≤ 18 V
Bandwidth fG 90 MHz
Parasitic capacitance line-line C 25 pF
Capacitance line-SG C 35 pF
Response time line-line ta ≤ 1 ns
Response time line-SG ta ≤ 1 ns
Response time SG-PG ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 40
Mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 9 plug / D-Sub 9 socket
Pinning Line: 3/8, SG: 5, PG: 1, 6: unprotected
Earthing via via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards VDE 0845-2, IEC 61643-21
Ordering information
Type FS 9E PB 6
Part No. 924 017
Packing unit 1 pc(s)
232 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS FS
24 019 FS 9E HS
2
D-SUB CONNECTION FS 9E HS
1 1
S 9E HS 12 Fine
urge Protection Adapter FS 12 V 924 019
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
Dimension drawing FS 9E HS 8-pole fine protection against common SG. • All pins protected
• Low voltage protection level
• For use according to the lightning
protection zones concept at bounda-
D-SUB, 9-pole device. V-24 unit with handshake function. ries 1 – 2 and higher
FS 9E HS 12
Nominal voltage UN 12 V
Max. continuous dc voltage Uc 15 V
C2 Nominal discharge current (8/20) line-SG In 0.1 kA
C2 Nominal discharge current (8/20) SG-PG In 0.1 kA
Voltage protection level line-SG at In C2 Up ≤ 24 V
Voltage protection level SG-PG at In C2 Up ≤ 200 V
Voltage protection level line-SG at 1 kV/µs C3 Up ≤ 21 V
Voltage protection level SG-PG at 1 kV/µs C3 Up ≤ 90 V
Bandwidth fG 10 MHz
Capacitance line-SG C 300 pF
Capacitance SG-PG C 700 pF
Response time line-SG ta ≤ 1 ns
Response time SG-PG ta ≤ 25 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 40
Mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 9 plug / D-Sub 9 socket
Pinning line: 1/2/3/4/6/7/8/9, SG: 5
Earthing via via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards VDE 0845-2, IEC 61643-21
Ordering information
Type FS 9E HS 12
Part No. 924 019
Packing unit 1 pc(s)
www.dehn.de 233
FS INFORMATION TECHNOLOGY SYSTEMS
924 016 FS 15E 5
9 9
4 4
11 11
8 8
1 1
• For 4-wire interfaces Fine protection for 2 TC to common SG. Dimension drawing FS 15E
• Low voltage protection level
• For use according to the lightning D-SUB, 15-pole device. RS-422, V.11 unit.
protection zones concept at bounda-
ries 1 – 2 and higher
FS 15E 5
Nominal voltage UN 5V
Max. continuous dc voltage Uc 8V
C2 Nominal discharge current (8/20) line-SG In 0.2 kA
C2 Nominal discharge current (8/20) SG-PG In 0.8 kA
Voltage protection level line-line at In C2 UP ≤ 16 V
Voltage protection level line-SG at In C2 Up ≤ 16 V
Voltage protection level SG-PG at In C2 Up ≤ 16 V
Voltage protection level line-line at 1 kV/µs C3 UC ≤ 11 V
Voltage protection level line-SG at 1 kV/µs C3 Up ≤ 11 V
Voltage protection level SG-PG at 1 kV/µs C3 Up ≤ 11 V
Bandwidth fG 4 MHz
Parasitic capacitance line-line C 1500 pF
Capacitance line-SG C 1500 pF
Capacitance line-PG C 800 pF
Response time line-line ta ≤ 1 ns
Response time line-SG ta ≤ 1 ns
Response time SG-PG ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 40
Mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 15 plug / D-Sub 15 socket
Pinning line: 2/9, 4/11, SG: 8, PG: 1
Earthing via via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards VDE 0845-2, IEC 61643-21
Ordering information
Type FS 15E 5
Part No. 924 016
Packing unit 1 pc(s)
234 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS FS
24 018 FS 25E HS
2
S 25E HS 12 Fine
urge Protection Adapter FS 12 V 924 018
2 2
3 3
4 4
5 5
6 6
8 8
20 20
7 7
1 1
Dimension drawing FS 25E HS 8-pole fine protection to common SG. • All lines interconnected
• Low voltage protection level
D-SUB, 25-pole device. V.24 unit with handshake function. • For use according to the lightning
protection zones concept at bounda-
ries 1 – 2 and higher
FS 25E HS 12
Nominal voltage UN 12 V
Max. continuous dc voltage Uc 15 V
C2 Nominal discharge current (8/20) line-SG In 0.1 kA
C2 Nominal discharge current (8/20) SG-PG In 0.1 kA
Voltage protection level line-SG at In C2 Up ≤ 24 V
Voltage protection level SG-PG at In C2 Up ≤ 200 V
Voltage protection level line-SG at 1 kV/µs C3 Up ≤ 21 V
Voltage protection level SG-PG at 1 kV/µs C3 Up ≤ 90 V
Bandwidth fG 10 MHz
Capacitance line-SG C 300 pF
Capacitance SG-PG C 700 pF
Response time line-SG ta ≤ 1 ns
Response time SG-PG ta ≤ 25 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 40
Mounting on D-Sub (2 threaded screws 4/40 UNC)
Connection input/output D-Sub 25 plug / D-Sub 25 socket
Pinning line: 2/3/4/5/6/8/20, SG: 7, other lines are unprotected
Earthing via via outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
Enclosure material plastic, metallised
Colour silver
Test standards VDE 0845-2, IEC 61643-21
Ordering information
Type FS 25E HS 12
Part No. 924 018
Packing unit 1 pc(s)
www.dehn.de 235
USD INFORMATION TECHNOLOGY SYSTEMS
Surge Arrester D-SUB CONNECTION
Surge protective adapter in metal enclosure with D-SUB plug-in terminal in switchgear cabinets the arrester can be snapped onto DIN rails. Special
as socket – pin unit. Type KB provides an additional 1.4 m data cable at units with different pinning or circuits can also be provided.
the side of the terminal equipment for easier connection. For application
236 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS USD
24 060 USD 9
V24 S KB
USD 9 V24
24 061 USD 9
D-SUB CONNECTION
V24 S B
USD 9 V24 S KB
Adapter
Cable
924 060 2 2
USD 9 V24 S B Cable
Adapter 924 061
3 3
5 5
Dimension drawing USD 9 V24 Combination of gas discharge tubes, decoupling • Plug-in surge arrester with 2-stage
resistances and diodes to PG. protective circuit
• For use according to the lightning
protection zones concept at bounda-
D-SUB 9-pole device. V.24 unit. ries 0B – 2 and higher
Ordering information
Type USD 9 V24 S KB USD 9 V24 S B
Part No. 924 060 924 061
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 237
USD INFORMATION TECHNOLOGY SYSTEMS
924 050 USD 15
V11 S KB
USD 15 V11
924 051 USD 15
D-SUB CONNECTION
V11 S B
11 11
USD 15 V11 S KB Cable
Adapter 924 050
USD 15 V11 S B Cable
Adapter 924 051
4 4
9 9
2 2
8 8
1 1
• Plug-in surge arrester with 2-stage The resistors at the output of the circuit protect Dimension drawing USD 15 V11
protective circuit optocoupler and protective diodes in the terminal
equipment against overloads.
• Integrated decoupling of the protec-
tive circuit to the terminal equipment
• For use according to the lightning D-SUB 15-pole device. RS 422, V.11 unit.
protection zones concept at bounda-
ries 0B – 2 and higher
Ordering information
Type USD 15 V11 S KB USD 15 V11 S B
Part No. 924 050 924 051
Packing unit 1 pc(s) 1 pc(s)
238 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS USD
24 040 USD 25
V24 S KB
USD 25 V24
24 041 USD 25
D-SUB CONNECTION
V24 S B
24 045 USD 25
V24 HS S KB
24 046 USD 25
V24 HS S B
7 7
1 1
Dimension drawing USD 25 V24 Basic circuit diagram of Part No. 929 045/046. • Plug-in surge arrester with 2-stage
Part No. 929 040/041 provide a different reser- protective circuit
vation of the lines to be protected.
• For use according to the lightning
protection zones concept at bounda-
D-SUB 25-pole device. V.24 unit, type HS with handshake function. ries 0B – 2 and higher
Ordering information
Type USD 25 V24 S KB USD 25 V24 S B USD 25 V24 HS S KB USD 25 V24 HS S B
Part No. 924 040 924 041 924 045 924 046
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 239
USD INFORMATION TECHNOLOGY SYSTEMS
924 047 USD 25
TTY B KS
USD 25 TTY
924 048 USD 25
D-SUB CONNECTION
TTY B S
9 9
USD 25 TTY B KS Cable
Adapter 924 047
USD 25 TTY B S Cable
Adapter 924 048
10 10
24 24
25 25
1 1
• Plug-in surge arrester with 2-stage The resistors at the circuit output protect Dimension drawing USD 25 TTY
protective circuit optocoupler and protective diodes in the
terminal equipment against overloads.
• Integrated decoupling of the protec-
tive circuit to the terminal equipment
• For use according to the lightning D-SUB 25-pole device. TTY unit.
protection zones concept at bounda-
ries 0B – 2 and higher
Ordering information
Type USD 25 TTY B KS USD 25 TTY B S
Part No. 924 047 924 048
Packing unit 1 pc(s) 1 pc(s)
240 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DSM (RJ45)
SOCKET OUTLET Surge Arrester
Shielded data socket outlet (Category 5) with integrated surge protection protective elements and is safe against opening. The data socket outlet is
for one port (outlet on the right). The cover of the other port hides the suitable for both the floor tank and the cable duct.
BR
W-BR
G
W-G
8 2 2 1
PG
4 5 6 3
Delivery
W-O
O
W-BL
BL
Pinning
www.dehn.de 241
DSM (RJ45) INFORMATION TECHNOLOGY SYSTEMS
924 263 DSM RJ45
4TP
2 2
3 3
6 6
4 4
IN OUT
5 5
7 7
8 8
• Shielded floor tank socket outlet Fine protection of all pairs by low-capacitance Dimension drawing DSM RJ45
diode matrix for each pair.
• All lines protected
• For use according to the lightning One protected port. Indirect shield earthing for universal use.
protection zones concept at bounda-
ries 1 – 2 and higher
Ordering information
Type DSM RJ45 4TP
Part No. 924 263
Packing unit 1 pc(s)
AMD DSM
AMD DSM Surface-
Socket outlet for surface mounting for supplementary installation of
DSM
type Mounting Box for DSM 924 298
242 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DSM
SPDs FOR TERMINAL CONNECTIONS Surge Arrester
A
k
IS D 270
V
5
M S
,5
4
n
E
D DN
B H
is
UC
Y
9
W
K
.
D
o
N
R
P
d
S
S
cte
te
ro
p
S 0 PD
4
S
3
2
2
1
N
b
a2
D
1
IS
b
a1
U C 7,5 V
BK
RD
isn
ISDN S 0 -> protected
DSM
SPD
SPD
4
3
2
1
b2
a2
b1
a1
1 2
3 4
1 2
3 4
www.dehn.de 243
DSM INFORMATION TECHNOLOGY SYSTEMS
924 270 DSM ISDN
SK
2 BK
protected
3 WH
4 YE
• Optional further wiring of the ISDN Energy-coordinated ISDN 4-wire protective circuit Dimension drawing DSM ISDN
bus via plug-in terminals with additional protection of the remote supply.
DSM ISDN SK
Nominal voltage UN 5V
Nominal voltage Pa-Pa UN 40 V
Max. continuous dc voltage UC 7.5 V
Max. continuous dc voltage pa-pa UC 45 V
Nominal current IL 200 mA
C2 Total nominal discharge current (8/20) In 20 kA
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 UP ≤ 30 V
Voltage protection level line-PG at In line/PG UP ≤ 600 V
Voltage protection level pa-pa at In C2 UP ≤ 180 V
Voltage protection level line-line at 1 kV/µs C3 UP ≤ 17 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 600 V
Voltage protection level pa-pa at 1 kV/µs C3 UP ≤ 100 V
Coordination characteristics KK X/1
Series impedance per line 4.7 Ohm
Bandwidth fG 4 MHz
Capacitance line-line C ≤ 1.5 nF
Capacitance line-PG C ≤ 15 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Response time pa-pa ta ≤ 25 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input/output quad pillar terminals / stranded conductors 0.25 mm2
Pinning 2 two-core conductors
Cross-sectional area, solid 0.5 - 1.0 mm
Earthing via flat connector 2.8 mm
Enclosure material polyamide PA 6.6
Colour yellow
Test standards IEC 61643-21
Accessories flat connector, earth conductor 500 mm
Ordering information
Type DSM ISDN SK
Part No. 924 270
Packing unit 1 pc(s)
244 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DSM
24 271 DSM TC 1
K
DSM TC
24 272 DSM TC 2
2 BK
protected
3 WH
4 YE
Dimension drawing DSM TC Energy-coordinated protective circuit, free of • Very good transmission performance
leakage currents to earth. The figure shows the
TC 2 unit for 2 two-core conductors. The other • Also suitable for installation into
types provide different reservations. distribution boards
• For use according to the lightning
For (system) telephony, Uk0, ADSL. TC protection for 1 or 2 two-core conductors. DK unit designed protection zones concept at bounda-
for applications in Denmark. ries 0B – 2 and higher
Ordering information
Type DSM TC 1 SK DSM TC 2 SK DSM TC DK SK
Part No. 924 271 924 272 924 273
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
www.dehn.de 245
BUStector INFORMATION TECHNOLOGY SYSTEMS
Surge Arrester SPDs FOR TERMINAL CONNECTIONS
BUStector is a surge arrester with a discharge capacity, protective effect a terminal device and be wired by means of the existing connecting
and mechanics adapted to the installation environment of EIB / KNX cables. It protects especially cable and area couplers as well as gateways
buses. Like a bus terminal it can be plugged onto the bus terminal pins of and sensors at external building walls.
246 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BUStector
25 001 BT 24
BT 24 BUStector
25 001
Dimension drawing BT High-capacity gas discharge tube, coordinated • Minimum space requirements
with the withstand of the equipment of KNX
systems. • For use according to the lightning
protection zones concept at bounda-
SPD with design of a bus terminal. Approved by EIBA. ries 0B – 1 and higher
BT 24
Nominal voltage Un 24 V
Max. continuous dc UC 45
Nominal current IL 6A
C2 Nominal discharge current per line In 5 kA
Voltage protection level at In C2 ≤ 1200 V
Voltage protection level line-PG at In C2 ≤ 650 V
Voltage protection level line-line at 1 kV/µs C3 ≤ 750 V
Voltage protection level line-PG at 1 kV/µs C3 ≤ 500 V
Bandwidth line-line 70 MHz
Capacity line-line ≤ 10 pF
Capacity line-PG ≤ 10 pF
Response time ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Connection input / output spring contacts Ø1 mm / connecting leads Ø0.8 mm
Earthing via lead 0.75 mm2, length 200 mm
Enclosure material thermoplastic
Colour blue
Test standards VDE 0845-1, IEC 61643-21
Approvals, Certifications EIBA certification No. Z 32/1399/95
Ordering information
Type BT 24
Part No. 925 001
Packing unit 1 pc(s)
www.dehn.de 247
AS-i Surge Protection Module INFORMATION TECHNOLOGY SYSTEMS
Surge Arrester SPDs FOR TERMINAL CONNECTIONS
Surge arrester for devices with AS interface connection according to AS-i device is passive and requires no bus address. Two LEDs inform about the
standard. The arrester is integrated into a water-proof module. For proper operation of the protection for the AS-i data line and the AUX-
connection it is screwed onto an FK-E or PG-E coupling module. The POWER power supply line.
248 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS AS-i Surge Protection Module
25 010 AS I MOD
AS I MOD
rotection Module
AS-i Surge
925 010
1
Dimension drawing AS-i Low-capacitance protective circuit between the • Fixed earth conductor, IP 67
lines and high isolation resistance to PG.
• Requires no bus address
• For use according to the lightning
protection zones concept at bounda-
Module with indication, protects data and AUX-Power. AS-i-approved. ries 0B – 2 and higher
AS I MOD
C2 Nominal discharge current (8/20) line-line In 0.5 kA
C2 Nominal discharge current (8/20) line-PG In 10 kA
Voltage protection level line-line at In C2 UP AS-i ≤ 100 V, AUX POWER ≤ 70 V
Voltage protection level line-PG at In C2 UP AS-i ≤ 1800 V, AUX POWER ≤ 1800 V
Voltage protection level line-line at 1 kV/µs C3 UP AS-i ≤ 50 V, AUX POWER ≤ 7 V
Voltage protection level line-PG at 1 kV/µs C3 UP AS-i ≤ 100 V, AUX POWER ≤ 70 V
Capacitance line-line C < 60 pF
Capacitance line-PG C < 5 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Total current input AS-i < 3 mA
Total current input AUX POWER < 3 mA
Degree of protection on coupling module IP 67
Mounting on coupling module FK, FK-E, PG, PG-E
Connection input/output via coupling module
Earthing via outgoing earth conductor AWG 16, 1 m long, oil-resistant
Test standards VDE 0845-1, IEC 61643-21
Approvals, Certifications AS-i certification
Ordering information
Type AS I MOD
Part No. 925 010
Packing unit 1 pc(s)
www.dehn.de 249
INFORMATION TECHNOLOGY SYSTEMS
250 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe
SCREWABLE SPDs Surge Arrester
Surge arrester for outdoor areas for screwing into 2-conductor process
field devices. Stainless steel, IP 67.
DEHNpipe is made of corrosion-resistant stainless steel and is screwed tration below). The arrester protects the inside of the process field device
into process field devices instead of conventional cable glands. Its fixed consequently against surges, as the interfering impulses are discharged
conductors are then connected with the terminals of the process field via the metal enclosure only and not via the inside of the device. For plas-
device. Thus, the protective components are installed directly into the tic field enclosures, earthing accessories are available.
cable run. This allows an energy-coordinated surge protection (see illus-
mounting
1 2 3 4
BK cable (black)
tauten transmitter
the cable RD cable (red)
max. 10 Nm
+
receiver −
GNYE
GNYE cable
removal (green/yellow)
4 3 2 1
Because of the 2-part structure of the protective device, the field cable The type of device for installation into pipes provides 2 npt male threads
can be connected, as usually, in the same way like the connection with and fixed conductors. The device is installed according to the figure.
a measuring sensor.
The cable gland provides a proofness of IP 67. DEHNpipe supports the
common earthing concepts for cable shield treatment of field cables.
According to the used cable gland, the cable shield is earthed directly or
indirectly or not earthed. The indirect earthing integrates the shield into
the protective concept – without leakage pickups.
www.dehn.de 251
DEHNpipe INFORMATION TECHNOLOGY SYSTEMS
929 941 DPI MD
24 M 2S
DPI MD 24 M 2S DEHNpipe
929 941
RD
SHL protected
BK
• Easy installation due to 2-part Energy-coordinated protective circuit, free of lea- Dimension drawing DPI MD
structure, Patent has been applied for kage currents, with gas discharge tube for indirect
shield earthing.
• Suitable for 3 shield concepts
• For use according to the lightning For 4-20 mA interfaces with thread M20 x 1.5 (inside/outside). Option of direct, indirect or no
protection zones concept at bounda- shield earthing. Cable gland has to be ordered separately.
ries 0B – 2 and higher
DPI MD 24 M 2S
Nominal voltage UN 24 V
Max. continuous dc voltage UC 34.8 V
Max. continuous ac voltage UC 24.5 V
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 10 kA
C2 Nominal discharge current (8/20) shield-PG In 20 kA
Voltage protection level line-line at In C2 UP ≤ 65 V
Voltage protection level line-PG at In C2 UP ≤ 650 V
Voltage protection level line-PG at In C2 UP ≤ 650 V
Voltage protection level line-line at 1 kV/µs C3 UP ≤ 50 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 500 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 600 V
Coordination characteristics KK X/1
Series impedance per line 2.2 Ohm
Bandwidth line-line fG 14 MHz
Capacitance line-line C ≤ 400 pF
Capacitance line-PG C ≤ 20 pF
Capacitance shield-PG C ≤ 15 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Response time shield-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 67
Mounting on the side of process field/device M20 x 1.5 female thread / M20 x 1.5 male thread
Connection input/output screw/connecting leads 1.5 mm2, length 200 mm
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 1.5 mm2
Earthing via enclosure or earthing ring (accessories)
Enclosure material stainless steel V2A
Colour bare
Test standards IEC 61643-21
Ordering information
Type DPI MD 24 M 2S
Part No. 929 941
Packing unit 1 pc(s)
252 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe
29 921 DPI ME
4 N A2G
RD BU
BK BK
protected
GNYE GNYE
Dimension drawing DPI ME Gas discharge tube and diodes, energy- • Robust structure
coordinated to earth.
• Encapsulated protective circuit
• Single ended version available on
request
For unbalanced interfaces with thread npt …” (outside/outside). Earth conductor led through. • For use according to the lightning
protection zones concept at bounda-
ries 0B – 2 and higher
DPI ME 24 N A2G
Nominal voltage UN 24 V
Max. continuous dc voltage UC 34.8 V
Max. continuous ac voltage UC 24.5 V
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 10 kA
Voltage protection level line-line at In C2 UP ≤ 120 V
Voltage protection level line-PG at In C2 UP ≤ 65 V
Voltage protection level line-line at 1 kV/µs C3 UP ≤ 98 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 49 V
Coordination characteristics KK X/1
Series impedance per line 4.7 Ohm
Capacitance line-line C ≤ 250 pF
Capacitance line-PG C ≤ 450 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 1 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 67
Mounting on the side of process field/device …’’ 14 npt male thread / …’’ 14 npt male thread
Connection input/output connecting leads AWG 16, length 500 mm
Earthing via enclosure and connecting lead
Enclosure material stainless steel V2A
Colour bare
Test standards IEC 61643-21
Ordering information
Type DPI ME 24 N A2G
Part No. 929 921
Packing unit 1 pc(s)
www.dehn.de 253
INFORMATION TECHNOLOGY SYSTEMS
ACCESSORIES FOR SCREWABLE SPDs
MS Eearthing Ring
Brass gland with shield connection Earthing ring of nickel-plated brass, for external earthing of DPI
KV S M20 MS 13 EMC ER DPI M20 Set of
Cable Gland
KV S M20 MS 9.5
Cable Gland
929 981
EMC
929 982
Type KV S M20 MS 13 KV S M20 MS 9.5 Earthing Rings for DEHNpipe 929 996
Type ER DPI M20
Sealing range 9.0 - 13.0 mm 6.5 - 9.5 mm Mounting on DPI M20 x 1.5
Shield diameter 6.7 - 10.5 mm 3.2 - 6.5 mm PU Part
Mounting on M20 x 1.5 M20 x 1.5 Type pc(s) No.
Degree of protection IP 68 IP 68 ER DPI M20 1 929 996
PU Part
Type pc(s) No.
KV S M20 MS 13 1 929 981
KV S M20 MS 9.5 1 929 982
929 984
MS 10.5
929 985
MS 8
KV M20
254 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT EX (i)
SPDs FOR HAZARDOUS AREAS
BLITZDUCTOR® CT EX is a separable, universal 2-pole surge arrester for high discharge capacity (min. 10x) and the low protection level. The pro-
DIN rail mounting for maximum requirements on availability of intrinsical- tective circuit is integrated into the arrester module only. This allows to
ly safe circuits and bus systems. Regarding intrinsical safety, the SPD can remove all relevant components from the cable run for testing purposes.
be considered earth-free and the self-inductance and self-capacitance are Corresponding test devices are available.
negligibly small. The low-impedance structure of the device supports the
BLITZDUCTOR® CT – Complete assem- Universal base part for all types of arrester
bly. Two-part unit with universal base modules. It optimises storage and benefits
part and specific arrester module, space- prewirings and service. Furthermore, the
saving design for DIN rail mounting. capacitive and inductive contacts in the
base part prevent signal interruptions
when arrester modules are changed.
www.dehn.de 255
BLITZDUCTOR® CT EX (i) INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR HAZARDOUS AREAS
256 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR CT Base Part Ex (i)
19 507 BCT BAS
X
BCT BAS
BCT MOD...
Line (IN) 1 3 Line (OUT)
2 4
BCT BAS
Dimension drawing BCT BAS EX Basic circuit diagram with and without plugged-in • Universal unit for all types of intrinsi-
module cally safe arrester modules
• Plug-in and removal without signal
Base part as universal feed-through terminal for instrinsically safe circuits for supporting the interruption
arrester module without signal interruption. The arrester module is safely earthed via the suppor- • Patent insert for indirect shield
ting foot of the DIN rail by means of a snap-on device. Allows direct and indirect shield earthing. earthing
BCT BAS EX
Max. continuous dc voltage UC 350 V
Max. continuous ac voltage UC 250 V
Nominal current IL 10 A
Operating temperature range -40°C...+80°C
Degree of protection IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output screw / screw
Cross-sectional area, solid 0.08 - 4 mm2 (shield)
Cross-sectional area, flexible 0.08 - 2.5 mm2
Tightening torque (terminals) 0.5 Nm/0.8 Nm (shield)
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material polyamide PA 6.6
Colour blue
Approvals, Certifications ATEX, CSA
Ordering information
Type BCT BAS EX
Part No. 919 507
Packing unit 1 pc(s)
www.dehn.de 257
BLITZDUCTOR® CT EX (i) INFORMATION TECHNOLOGY SYSTEMS
919 580 BCT MOD
MD EX 24
BCT MOD EX
919 581 BCT MOD
1 3
2 4
• For universal use Low-capacitance energy-coordinated protective Dimension drawing BCT MOD EX
circuit with insulation resistance > 500 V to earth
• Self-capacitance and inductance
negligibly small
• For use according to the lightning
protection zones concept at bounda- Surge arrester module for protection of intrinsically safe circuits and bus systems.
ries 0B – 2 and higher PTB 99 ATEX 2092 II 2 (1) G EEx ia IIC T4/T5/T6, fulfils FISCO requirements.
Ordering information
Type BCT MOD MD EX 24 BCT MOD MD EX 30
Part No. 919 580 919 581
Packing unit 1 pc(s) 1 pc(s)
919 507
EX
BCT BAS
258 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR® CT EX (i)
19 583 BCT MOD
MD HFD EX 6
1 3
2 4
Dimension drawing BCT MOD MD HFD EX Combining several diodes to one matrix, the • For RS 485 bus systems
capacity of the protective circuit can be mini-
mised. Insulation resistance > 500 V to earth. • Self-capacitance and -inductance
negligibly small
• For use according to the lightning
Surge arrester module for protection of intrinsically safe RS 485 bus systems. protection zones concept at bounda-
PTB 02 ATEX 2162 II 2 G EEx ib IIC T5/T6, fulfils FISCO requirements. ries 0B – 2 and higher
Ordering information
Type BCT MOD MD HFD EX 6
Part No. 919 583
Packing unit 1 pc(s)
1 3
2 4 Base part as universal feed-through terminal for instrinsically safe
circuits for supporting the arrester module without signal interruption.
BCT BAS EX
Part (Ex)
BCT-Base
919 507
The arrester module is safely earthed via the supporting foot of the
BCT BAS DIN rail by means of a snap-on device. Allows direct and indirect
shield earthing.
BCT MOD... Type BCT BAS EX
Line (IN) 1 3 Line (OUT)
Cross-sectional area, solid 0.08 - 4 mm2 (shield)
2 4 Cross-sectional area, flexible 0.08 - 2.5 mm2
Enclosure material polyamide PA 6.6
www.dehn.de 259
ITAK Ex (i) INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR HAZARDOUS AREAS
• Prewired unit
• With integrated SPD, tested according
to ATEX and FISCO
• Further customer-specific units
available on request
ITAK stands for the German description “Informationstechnik- tions. For example, our standard product range offers ITAK EXI 30, a com-
Anschaltkasten“ (english: switchbox for information technology systems). bination of ALGA 5 X enclosure and BCT MD EX 30 for protecting intrin-
Generally, ITAKs combine enclosure, SPD and terminals or shield termi- sically safe circuits in outdoor systems.
nals. These switchboxes can be produced according to customer specifica-
260 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS ITAK Ex (i)
89 406 ITAK EXI
0
TAK EXI 30 IT
Connection Box 989 406
1 3
2 4
SHL SHL
ITAK EXI 30
Nominal voltage UN 30 V
Max. continuous dc voltage Uc 34.8 V
Max. input voltage acc. to EN 50020 Ui 34.8 V
Max. input current acc. EN 50020 Ii 0.5 A
Total nominal discharge current (8/20) isn 10 kA
Nominal discharge current (8/20) per line isn 10 kA
Voltage protection level line-line at In C2 Up ≤ 60 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 1000 V
Coordination characteristics KK X/1
Series impedance per line 1.8 Ohm
Bandwidth line-line fG 6.0 MHz
Parasitic capacitance line-line C 1.1 nF
Operating temperature range -40°C...+80°C
Degree of protection IP 65
Mounting on wall in Ex zones 1, 2
Connection input/output cable gland M20 x 1.5
Cross-sectional area, solid 0.08 - 4 mm2 (shield)
Cross-sectional area, flexible 0.08 - 2.5 mm2
Cross-sectional area of equipotential bonding 4 mm2
Tightening torque (terminal) 0.5 Nm (line) / 0.8 Nm (shield)
Earthing via screw terminal
Enclosure material grey aluminium
Test standards VDE 0845-2, IEC 61643-21
Approvals, Certifications ATEX
Ordering information
Type ITAK EXI 30
Part No. 989 406
Packing unit 1 pc(s)
www.dehn.de 261
DEHNconnect RK Ex (i) INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR HAZARDOUS AREAS
DEHNconnect RK MD EX is a 6 mm wide surge protective terminal block ting foot ensures a safe earthing. As the SPDs are not enclosed on one
for intrinsically safe circuits. Each of the 5 cage clamp tension spring side in order to save space, a sealing cover at the end of each terminal
terminals protects 2 lines and establishes an additional equipotential block would provide further protection.
bonding to the terminal equipment. A self-locking device at the suppor-
application
Zones 1, 2
DEHNconnect RK EX 24
EB
262 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNconnect RK Ex (i)
SPDs FOR HAZARDOUS AREAS
www.dehn.de 263
DEHNconnect RK Ex (i) INFORMATION TECHNOLOGY SYSTEMS
919 960 DCO RK
MD EX 24
DCO RK MD EX 24
DEHNconnect RK 24 V EX 919 960
1 3
2 4
IN OUT
DCO RK MD EX 24
Nominal voltage UN 24 V
Max. continuous dc voltage Uc 33 V
Max. continuous ac voltage Uc 23 V
Max. input voltage acc. to EN 50020 Ui 30 V
Max. input current acc. to EN 50020 Ii 0.5 A
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 Up ≤ 50 V
Voltage protection level line-PG at In C2 Up ≤ 1500 V
Voltage protection level line-line at 1 kV/µs: line/line Up ≤ 45 V
Voltage protection level line-PG at 1 kV/µs C3 Up ≤ 1400 V
Coordination characteristics KK X/1
Series impedance per line 1.8 Ohm
Bandwidth line-line fG 6 MHz
Parasitic capacitance line-line C ≤ 1 nF
Parasitic capacitance line-PG C ≤ 6 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 00, with cover IP 20
Mounting on 35 mm DIN rail acc. to EN 60715
Connection input/output spring / spring
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 2.5 mm2
Earthing via DIN rail / terminal
Enclosure material polyamide PA 6.6
Colour blue
Test standards IEC 61643-21
Approvals, Certifications ATEX
Ordering information
Type DCO RK MD EX 24
Part No. 919 960
Packing unit 1 pc(s)
Accessory Part for DEHNconnect RK Ex (i) Accessory Part for DEHNconnect RK Ex (i)
919 978
RK BL
AD DCO
264 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe Ex (i)
SPDs FOR HAZARDOUS AREAS
Surge arrester for outdoor areas for screwing into 2-conductor process
field devices. Stainless steel. Allows mounting up to IP 67.
DEHNpipe is made of corrosion-resistant stainless steel and is screwed ter protects the inside of the process field device consequently against
into process field devices instead of conventional cable glands. Its fixed surges, as the interfering impulses are discharged via the metal enclosure
conductors are then connected with the terminals of the process field only, not via the inside of the device. For installation in Ex zone 1 or 2.
device. Thus, the protective components are installed directly into the
cable run. This allows an energy-coordinated surge protection. The arres-
Because of the 2-part design of the protective device, the field cable can
mounting be connected, as usually, in the same way like being connected with a
1 2 3 4 measuring sensor.
The cable gland provides a proofness of IP 67. DEHNpipe supports the
common earthing concepts for cable shield treatment at field cables.
According to the cable gland used, the cable shield is earthed directly
max. 10 Nm or not earthed.
removal
4 3 2 1
Installation of DPI MD EX
www.dehn.de 265
DEHNpipe Ex (i) INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR HAZARDOUS AREAS
266 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe Ex (i)
29 960 DPI MD
X 24 M 2
DPI MD EX 24 M 2 DEHNpipe
29 960
RD
protected
BK
Dimension drawing DPI MD EX Low-capacitance, energy-coordinated protective • Easy installation due to 2-part design,
circuit with insulation resistance > 500 V to earth. Patent has been applied for
• Self-capacitance and -inductance
negligibly small
Surge arrester for protecting measuring circuits and bus systems. PTB 03 ATEX 2088 II 2 (1) G • For use according to the lightning
EEx ia IIC T4/T5/T6, fulfils FISCO requirements. Cable gland has to be ordered separately. protection zones concept at bounda-
ries 0B – 2 and higher
DPI MD EX 24 M 2
Nominal voltage UN 24 V
Max. continuous dc voltage Uc 34.8 V
Max. continuous ac voltage UC 24.5 V
Max. input voltage acc. to EN 50020 Ui 30 V
Max. input current acc. to EN 50020 Ui 0.5 A
Nominal current IL 0.5 A
C2 Total nominal discharge current (8/20) In 10 kA
C2 Nominal discharge current (8/20) per line In 5 kA
Voltage protection level line-line at In C2 UP ≤ 55 V
Voltage protection level line-PG at In C2 UP ≤ 1100 V
Voltage protection level line-line at 1 kV/µs C3 UP ≤ 49 V
Voltage protection level line-PG at 1 kV/µs C3 UP ≤ 1000 V
Coordination characteristics KK X/1
Series impedance per line 1.8 Ohm
Bandwidth line-line fG 7 MHz
Capacity line-line C ≤ 850 pF
Capacity line-PG C ≤ 15 pF
Response time line-line ta ≤ 1 ns
Response time line-PG ta ≤ 100 ns
Operating temperature range -40°C...+80°C
Degree of protection IP 67
Mounting field/device side M20 x 1.5 female thread / M20 x 1.5 male thread
Connection input/output screw / connecting leads 1.5 mm2, length 200 mm
Cross-sectional area, solid 0.08 - 2.5 mm2
Cross-sectional area, flexible 0.08 - 1.5 mm2
Earthing via enclosure
Enclosure material stainless steel V2A
Colour bare
Test standards IEC 61643-21
Approvals, Certifications ATEX
Ordering information
Type DPI MD EX 24 M 2
Part No. 929 960
Packing unit 1 pc(s)
www.dehn.de 267
DEHNpipe Ex (i) INFORMATION TECHNOLOGY SYSTEMS
929 963 DPI CD
EXI 24 N
DPI CD EXI
929 961 DPI CD
RD
BK
GNYE
• Easy installation at process field devi- Low-capacitance protective circuit with insulation Dimension drawing DPI CD EXI
ces with unused cable gland resistance > 500 V to earth
Ordering information
Type DPI CD EXI 24 N DPI CD EXI 24 M
Part No. 929 963 929 961
Packing unit 1 pc(s) 1 pc(s)
268 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS
ACCESSORIES
Accessory Part for DEHNpipe Ex (i) Accessory Part for DEHNpipe Ex (i)
EMC Cable Gland Cable Gland
929 981 KV S M20 929 984 KV M20
MS 13 MS 10.5
929 982 KV S M20 929 985 KV M20
MS 9.5 MS 8
Brass gland with shield connection Brass gland without shield connection.
KV M20 MS 10.5 EMC
Cable Gland 929 984
KV M20 MS 8 EMC
KV S M20 MS 13 EMC Cable Gland 929 985
Type
Cable Gland
KV S M20 MS 9.5
Cable Gland
929 981
EMC
929 982
KV S M20 MS 13 KV S M20 MS 9.5 Type KV M20 MS 10.5 KV M20 MS 8
Sealing range 9.0 - 13.0 mm 6.5 - 9.5 mm Sealing range 7.0 - 10.5 mm 5.0 - 8.0 mm
Shield diameter 6.7 - 10.5 mm 3.2 - 6.5 mm Mounting on M20 x 1.5 M20 x 1.5
Mounting on M20 x 1.5 M20 x 1.5 Degree of protection IP 68 IP 68
Degree of protection IP 68 IP 68 PU Part
PU Part Type pc(s) No.
Type pc(s) No. KV M20 MS 10.5 1 929 984
KV S M20 MS 13 1 929 981 KV M20 MS 8 1 929 985
KV S M20 MS 9.5 1 929 982
www.dehn.de 269
DEHNpipe Ex (d) INFORMATION TECHNOLOGY SYSTEMS
SPDs FOR HAZARDOUS AREAS
Surge arrester for outdoor use for screwing into transmitters with 2-wire
interface. Stainless steel. Allows installation up to IP 67.
Flameproof DEHNpipe C is made of stainless steel and is designed to be nected with an earth terminal for process field devices. The arrester is
screwed directly into the process field device. Its fixed leads are connected designed in IP 67. Typical applications for these flameproof arresters are
to the terminals of the process field devices like those of the field cable. the protection of 4-20 mA signals or bus systems up to 30 V. Depending
Thus, the protection components are installed in parallel to the leads of on the type, DEHNpipe C is designed for measuring sensors with a M20 x
the field cable. The device can be easily installed at metal or synthetic 1.5 or …” cable gland connection. Its flameproof design is suitable for
enclosures as the earth conductor of the protective device can be con- installation in Ex zone 1 or 2.
270 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS DEHNpipe Ex (d)
964 DPI CD
24 N
DPI CD EXD
962 DPI CD
CD EXD 24 N DEHNpipe
964
CD EXD 24 M DEHNpipe
962
RD
BK
GNYE
Dimension drawing DPI CD EXD Protection circuit with low capacitance and • Easy installation at process field
insulation resistance > 500 V to earth. devices with unused conduit entries
• Type Ex(d) for universal use
Flameproof surge arrester for installation in hazardous areas for protection of intrinsically safe • For use according to the lightning
circuits and bus systems. ATEX certification KEMA 04 ATEX 1189X II 2 G EEx d IIC T5...T6, FISCO protection zones concept at bounda-
surge protector. ries 0B – 2 and higher
Ordering information
Type DPI CD EXD 24 N DPI CD EXD 24 M
Part No. 929 964 929 962
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 271
INFORMATION TECHNOLOGY SYSTEMS
272 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Components for Shield Terminals
ACCESSORIES
Shield terminal systems for anchor bars, DIN rails and constant force
springs. The yield of the used cable materials is compensated by a slip-
ping spring element.
Shield terminal systems for different installation environments. The aimed ductor materials become subject to a yield, this is compensated by a
use on anchor bars and DIN rails is possible as well as the use of constant slipping spring element. The shield terminal can be installed to be isola-
force springs in case of lacking space. As, in the course of time, the con- ted from the local potential by using corresponding insulating elements.
www.dehn.de 273
Components for Shield Terminals INFORMATION TECHNOLOGY SYSTEMS
308 403 SAK 10
AS V4A
ACCESSORIES
AS V4A
308 405 SAK 18
AS V4A
308 406 SAK 21
AS V4A
308 407 SAK 26
AS V4A
308 408 SAK 33
AS V4A
SAK 10 AS V4A SAK 14 AS V4A SAK 18 AS V4A SAK 21 AS V4A SAK 26 AS V4A SAK 33 AS V4A
Lightning impulse current carrying capability (10/350) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
Clamping range Rd 5 - 10 mm 8 - 14 mm 13 - 18 mm 17 - 21 mm 19 - 26 mm 25 - 33 mm
Material StSt StSt StSt StSt StSt StSt
Spring pressure 21 - 27 N 30 - 76 N 34 - 73 N 30 - 63 N 90 - 124 N 76 - 137 N
Mounting on anchor bar anchor bar anchor bar anchor bar anchor bar anchor bar
Dimension B x L x H 16 x 40 x 48 mm 19.5 x 40 x 50 mm 24 x 40 x 56 mm 29 x 40 x 59 mm 36.5 x 40 x 74 mm 45 x 40 x 82 mm
Approvals, Certifications ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97 ETL 10/PB 301/97
Ordering information
Type SAK 10 AS V4A SAK 14 AS V4A SAK 18 AS V4A SAK 21 AS V4A SAK 26 AS V4A SAK 33 AS V4A
Part No. 308 403 308 404 308 405 308 406 308 407 308 408
Packing unit 10 pc(s) 10 pc(s) 10 pc(s) 10 pc(s) 10 pc(s) 10 pc(s)
• Allows cutting to length as required Supporting bar for earthing and fixing the shield terminals.
Ordering information
Type AS SAK 1000 V2A
Part No. 308 421
Packing unit 10 pc(s)
274 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Components for Shield Terminals
08 425 ST AS
AK K
Bar support for insulated fixing of the anchor bar AS SAK 1000 V2A, with threaded socket M4. • Non-conductive connection of moun-
ting plate and anchor bar
• Equipotential bonding via terminal
AK 16 AS SAK MS
ST AS SAK K
Material plastic
Approvals, Certifications ETL 10/PB 301/97
Ordering information
Type ST AS SAK K
Part No. 308 425
Packing unit 10 pc(s)
08 411 AK 16 AS
AK MS
AK 16 AS SAK MS Protective
Conductor Terminal, -16 mm√ 308 411
For connection of equipotential bonding conductors with anchor bar AS SAK 1000 V2A. • Space-saving unit
• 2 fixing screws included for con-
ductor
AK 16 AS SAK MS
Cross-sectional area, solid 16 mm2
Mounting on anchor bar
Approvals, Certifications ETL 10/PB 301/97
Ordering information
Type AK 16 AS SAK MS
Part No. 308 411
Packing unit 5 pc(s)
www.dehn.de 275
Components for Shield Terminals INFORMATION TECHNOLOGY SYSTEMS
919 010 SAK 6,5
SN MS
Shield Terminal
919 011 SAK 11
ACCESSORIES
SN MS
Ordering information
Type SAK 6,5 SN MS SAK 11 SN MS
Part No. 919 010 919 011
Packing unit 10 pc(s) 10 pc(s)
Bar for supporting the shield terminals. Suitable for mounting on the bar supports.
SN 18X3 CU 1000
Material tin-plated copper
Mounting on bar holder
Dimension B x L x H 18 x 1000 x 3 mm
Ordering information
Type SN 18X3 CU 1000
Part No. 919 016
Packing unit 1 pc(s)
276 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Components for Shield Terminals
19 012 SH1 18X3
T
ACCESSORIES
T
H1 18X3 ST Bar
Holder, steel 919 012
H2 18X3 ST Bar
Holder ISO 919 013
Busbar support for earthed structures, suitable for mounting on DIN rails. Low-impedance
connection of the shield terminals to the DIN rail via the busbar
Ordering information
Type SH1 18X3 ST SH2 18X3 ST
Part No. 919 012 919 013
Packing unit 1 pc(s) 1 pc(s)
19 014 SH 18X3
K
H 18X3 K Bar
• Non-conductive connection of busbar and DIN rail
Holder, plastic 919 014
Busbar support for insulated structures, suitable for mounting on DIN rails or screw terminals.
SH 18X3 K
Material plastic
Colour black
Mounting on DIN rail or mounting plate
Ordering information
Type SH 18X3 K
Part No. 919 014
Packing unit 10 pc(s)
19 015 AK 35 SN
8X3 GG
Especially suitable for insulating busbar constructions, e.g. indirect shield earthing
AK 35 SN 18X3 GG
Cross-sectional area, solid 35 mm2
Mounting on busbar
Ordering information
Type AK 35 SN 18X3 GG
Part No. 919 015
Packing unit 1 pc(s)
www.dehn.de 277
Components for Shield Terminals INFORMATION TECHNOLOGY SYSTEMS
919 031 SA KRF
10 V2A
ACCESSORIES
15 V2A
919 033 SA KRF
22 V2A
919 034 SA KRF
29 V2A
919 035 SA KRF
37 V2A
919 036 SA KRF
50 V2A
919 037 SA KRF
70 V2A
919 038 SA KRF
94 V2A
• For solderfree connection of a Constant force springs allow solderfree shield connections for equipotential bonding or lightning
conductor with the shield equipotential bonding. They can be employed subsequentially without interrupting the conductor
• Usable for all plastic and lead- shield or requiring tools for installation. Approved for nuclear installations acc. to TÜV Certificate
sheathed cables No. T12-04-ETL003 (TÜV = German Technical Inspectorate).
• Also usable for steel-reinforced
lead-sheathed cables
SA KRF ... 10 V2A 15 V2A 22 V2A 29 V2A 37 V2A 50 V2A 70 V2A 94 V2A
Lightning impulse current
carrying capability (10/350) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
Clamping range Rd 4 - 10 mm 9 - 15 mm 14 - 22 mm 18.5 - 29 mm 23.5 - 37 mm 31 - 50 mm 44 - 70 mm 58 - 94 mm
Material StSt StSt StSt StSt StSt StSt StSt StSt
Colour bare bare bare bare bare bare bare bare
Mounting on cable shield cable shield cable shield cable shield cable shield cable shield cable shield cable shield
Approvals, Certifications T12-04-ETL 003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003 T12-04-ETL003
Ordering information
Type SA KRF 10 V2A SA KRF 15 V2A SA KRF 22 V2A SA KRF 29 V2A SA KRF 37 V2A SA KRF 50 V2A SA KRF 70 V2A SA KRF 94 V2A
Part No. 919 031 919 032 919 033 919 034 919 035 919 036 919 037 919 038
Packing unit 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
SKB 19 9M SW
Selfbonding Rubber Tape 919 030
• Selfbonding Reel with 9 m selfbonding rubber tape for wrapping round constant force springs for permanent
• Flexible protection against corrosion.
SKB 19 9M SW
Colour black
Dimension B x L x H tape measure 9 m x 19 mm mm
Ordering information
Type SKB 19 9M SW
Part No. 919 030
Packing unit 1 pc(s)
278 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Enclosure and PE Terminal
06 055 ALGA 5
ALGA 5
Aluminium Enclosure IP65 906 055
ALGA 5
Degree of protection IP 65
Mounting on wall
Dimension B x H x T 100 x 200 x 81 mm
Enclosure material aluminium
Ordering information
Type ALGA 5
Part No. 906 055
Packing unit 1 pc(s)
06 058 ALGA 5 X
ALGA 5 X
Aluminium Enclosure IP65 for BCT 906 058
ALGA 5 X
Degree of protection IP 65
Mounting on wall
Dimension B x H x T 160 x 100 x 85 mm
Enclosure material aluminium
Ordering information
Type ALGA 5 X
Part No. 906 058
Packing unit 1 pc(s)
www.dehn.de 279
Enclosure and PE Terminal INFORMATION TECHNOLOGY SYSTEMS
906 059 MS ALGA
5X
MS ALGA 5 X Mounting
Set for Enclosures 906 059
MS ALGA 5 X
Mounting on mast, pipe
Enclosure material StSt
Ordering information
Type MS ALGA 5 X
Part No. 906 059
Packing unit 1 pc(s)
PE Terminal
SLK 16 PE
Terminal 910 099
SLK 16
Cross-sectional area, flexible 6 - 16 mm2
Cross-sectional area, solid 6 - 25 mm2
Mounting on DIN rail acc. to EN 60715
Enclosure material green-yellow polyamide 6.6
Ordering information
Type SLK 16
Part No. 910 099
Packing unit 1 pc(s)
280 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Combined Protectors
COMBINED ADAPTERS
Combined surge protective adapter for plugging into socket outlets with
earth contact, with visual operation and fault indicator.
The SPDs of the Protector family for plugging into socket outlets with installation makes retrofittings of SPDs easier. The surge protection of the
earth contact protect consumers with additional data interfaces. The power side is furnished with a visual operation and fault indicator. This
surges are discharged via the PE pin of the socket outlet. The plug-in emphasises the easy maintenance.
NT-PROTECTOR
interfaces ISDN-PROTECTOR
230V~ Defect
ISDN - S0
230V~ Defect
NTBA
TAE/F
OUT 1 OUT 1
UK0-Interface
3m cable length
3m
DATA-PROTECTOR
TV-PROTECTOR
230V~ Defect
230V~ Defect
IN OUT
TV R
www.dehn.de 281
Combined Protectors INFORMATION TECHNOLOGY SYSTEMS
909 958 NT PRO
Ordering information
Type NT PRO
Part No. 909 958
Packing unit 1 pc(s)
282 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Combined Protectors
09 954 ISDN PRO
SDN PRO
rotector
ISDN-
909 954
Protection of the data side ISDN PRO
Nominal voltage line-line UN 5V
Nominal voltage pair/pair UN 40 V
Max. continuous dc voltage UC 7.5 V
Max. continuous dc voltage pa-pa UC 45 V
C2 Nominal discharge current (8/20) per line C2 In 2.5 kA
Voltage protection level line-line at In C2 UP ≤ 35 V
Voltage protection level line-PE at In C2 UP ≤ 600 V
Voltage protection level pa-pa at In C2 UP ≤ 220 V
Voltage protection level line-line at 1 kV/µs C3 Up ≤ 15 V
Voltage protection level line-PE at 1 kV/µs C3 Up ≤ 600 V
Voltage protection level pa/pa at 1 kV/µs C3 UP ≤ 100 V
Series impedance per line 1 Ohm
• 2 protected ISDN outputs
Bandwidth line-line fG 100 MHz
Capacitance line-line C ≤ 300 pF • No accessories required
Capacitance line-PE C ≤ 15 pF • For use according to the lightning
Capacitance pa-pa C ≤ 350 pF protection zones concept at bounda-
Response time line-line ta < 1 ns
ries 2 – 3 and higher
Response time line-PE ta < 100 ns
Combined surge protection for power and
Response time pa-pa ta < 25 ns ISDN S0 side of ISDN systems and devices.
Operating temperature range -25°C...+40°C With visual operation and fault indicator,
Degree of protection IP 20 two protected ISDN outputs.
Connection input/output 3 m connecting cable with RJ45 plug / 2 x RJ45 socket
Pinning 3/6, 4/5
Earthing via protective conductor connection
Enclosure material thermoplastic, UL 94 V-2 L (N) L (N)
PE PE
Colour pure white N (L) N (L)
Nominal current IL 16 A
3 4
Nominal discharge current (8/20) L-N In 3 kA 5
OUT 2
3
Nominal discharge current (8/20) L/N-PE In 5 kA [(L+N)-PE] 6 6
Ordering information
Type ISDN PRO
Part No. 909 954
Packing unit 1 pc(s)
Dimension drawing ISDN Protector
www.dehn.de 283
Combined Protectors INFORMATION TECHNOLOGY SYSTEMS
909 955 DATA
PRO 4TP
Protection of the data side DATA PRO 4TP DATA PRO 4TP
Protector RJ45-4TP
DATA-
909 955
5 5
Combined impulse (1.2/50 - 8/20) L/N-PE Uoc 10 kV [(L+N)-PE]
7 7
Voltage protection level L-N Up ≤ 1.25 kV
8 8 Voltage protection level L/N-PE Up ≤ 1.5 kV
Response time L-N tA ≤ 25 ns
Response time L/N-PE tA ≤ 100 ns
Protection for the data side: Protection of all pairs Max. mains-side overcurrent protection 16 A gL/gG
by low-capacitance diode matrix for each pair. Short-circuit withstand capability
at max. mains-side overcurrent protection 6 kArms ac
TOV voltage L-N UT 335 V/5 sec
TOV voltage L/N-PE (1) UT 400 V/5 sec
TOV voltage L/N-PE (2) UT 1200 V+U0 /200 ms
Indication of the disconnection device red light
Mounting plug-in system with earth contact DIN 49440/DIN 49441
Test standards EN 61643-11 (VDE 0675-6-11):2002-12
Ordering information
Type DATA PRO 4TP
Part No. 909 955
Packing unit 1 pc(s)
284 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Combined Protectors
09 957 FAX PRO
AE FN
Ordering information
Type FAX PRO TAE FN
Part No. 909 957
Packing unit 1 pc(s)
www.dehn.de 285
Combined Protectors INFORMATION TECHNOLOGY SYSTEMS
909 950 FAX PRO
RJ11
Ordering information
Type FAX PRO RJ11
Part No. 909 950
Packing unit 1 pc(s)
286 www.dehn.de
INFORMATION TECHNOLOGY SYSTEMS Combined Protectors
09 956 FAX PRO
RJ45
Ordering information
Type FAX PRO RJ45
Part No. 909 956
Packing unit 1 pc(s)
www.dehn.de 287
Combined Protectors INFORMATION TECHNOLOGY SYSTEMS
909 921 TV PRO
288 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING Isolating Spark Gaps
ISOLATING SPARK GAPS For Lightning Equipotential Bonding
For lightning equipotential bonding according to IEC 61024-1 as well as TFS: High-capacity isolating spark gap
for use in IT systems according to IEC 60364-5-54. KFSU: Isolating spark gap
23 023 TFS
23 021 KFSU
TFS / KFSU
FS Isolating
park Gap 923 023
KFSU Ex-
solating Spark Gap 923 021
TFS / KFSU: Isolating spark gaps with synthetic coating and 2 connections Rd 10 mm made of
stainless steel
TFS KFSU
Ligthning impulse current (10/350) Iimp 100 kA —
Nominal discharge current (8/20) In 100 kA 100 kA
100% Lightning impulse sparkover voltage Uas 100 ≤ 4 kV ≤ 4 kV
Power frequency sparkover voltage (50 Hz) Uaw ≤ 2.5 kV ≤ 2.5 kV
Degree of protection IP 65 IP 65
Length of enclosure L 160 mm 160 mm
Diameter of enclosure D 43 mm 43 mm
Enclosure material steel-synthetic coating steel-synthetic coating
Connection Rd 10 mm Rd 10 mm
Material (connection) stainless steel stainless steel
Ordering information
Type TFS KFSU
Part No. 923 023 923 021
Packing unit 1 pc(s) 1 pc(s)
www.dehn.de 289
EXFS L / EXFS KU LIGHTNING EQUIPOTENTIAL BONDING
for explosive Areas ISOLATING SPARK GAPS
EXFS L ...: Isolating spark gap for explosive zones with flexible connecting cable
EXFS KU: Isolating spark gap for explosive zones with 1.5 m long connecting cables for underground installation
The Ex isolating spark gaps of the product family EXFS L / EXFS KU are
used for conductive system parts that cannot be interconnected directly in
hazardous zones. This affects, for example, pipe sections furnished with a
cathodic corrosion protection system.
The spark gaps EXFS L and EXFS KU certified by ATEX provide approved
and tested safety according to harmonised European standards.
The arc-resistant tungsten-copper electrodes provide the Ex spark gaps
with a long service life.
The approved type EXFS L with flexible conductor connection adjusts itself
quickly to every application environment. The prewired spark gaps inclu-
de connecting cables with different lengths with cable lug, M10 screw
and nut. The flat and/or angled connecting clips (IF) available as accesso-
ries allow an easy connection of the spark gap at pipeline flanges.
The EXFS KU unit is enclosed by a damp-proof PVC housing and thus
ideally suitable for underground installation at insulating couplings.
290 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING EXFS L / EXFS KU
23 060 EXFS
100
EXFS L ...
23 061 EXFS
lmax = 300 mm
(avoid loops)
Ordering information
Type EXFS L100 EXFS L200 EXFS L300
Part No. 923 060 923 061 923 062
Packing unit 1 pc(s) 1 pc(s) 1 pc(s)
Accessory Part for EXFS L / EXFS KU Accessory Part for EXFS L / EXFS KU
Angled Connection Bracket – IF 1 – 923 011
Angled connection bracket for EXFS ...; diameter corresponds to bolt Connection Bracket Type IF -SET- 923 011
Flat connection bracket for EXFS...; diameter corresponds to bolt dia-
diameter of the flange screw joint (d1 possible up to max. 60 mm) meter of the flange screw joint (d1 possible up to max. 60 mm) Connection Bracket Type IF -SET- 923 016
PU Part PU Part
Type Material pc(s) No. Type Material pc(s) No.
IF 1 St/tZn 1 923 011 IF 3 St/tZn 1 923 016
www.dehn.de 291
EXFS L / EXFS KU LIGHTNING EQUIPOTENTIAL BONDING
923 019 EXFS KU
EXFS KU Ex-
Isolating Spark Gap 923 019
EXFS KU: Ex Isolating spark gap with connecting cables for above- and
underground installation
EXFS KU
Lightning impulse current (10/350) Iimp 50 kA
Nominal discharge current (8/20) In 100 kA
100% lightning impulse sparkover voltage Uas100 ≤ 2.5 kV
Power frequency sparkover voltage (50 Hz) Uaw ≤ 1.2 kV
Type of protection according to EN 50014, EN 50021 II 3 G EEx nC II T4
Approvals, Certifications ZELM 03 ATEX 3192X
Enclosure length L 90 mm
Diameter of enclosure D 63 mm
Enclosure material zinc die casting, plastic
Connecting cable NYY-J-1x25 mm2
Cable length 2 x approx. 1500 mm
Ordering information
Type EXFS KU
Part No. 923 019
Packing unit 1 pc(s)
292 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING EXFS C1 / EXFS C1 KU
ISOLATING SPARK GAPS For explosive Areas
EXFS C1: Isolating spark gap for explosive zones with threaded M10 bolt and nut
EXFS C1 KU: Isolating spark gap for explosive zones with 2 m long connecting cables for underground installation
The Ex isolating spark gaps of the EXFS C1 / EXFS C1 KU family are used
when electrically conductive installation parts in explosive areas cannot
be connected directly.
The low sparkover voltages of the spark gaps have proved themselves for
protection, when the separate installation parts had only a low insulation
resistance against each other.
The ATEX-certified spark gaps EXFS C1 / EXFS C1 KU provide approved
safety according to harmonised European standards.
The powerful Ex isolating spark gaps are furnished with a fail-safe
device, which establishes a safe state (short circuit) even in case of over-
loads.
For connecting the EXFS C1 spark gaps, prewired connecting cables with
different lengths are available as accessories.
Flat and angled connection brackets (IF) make the connection of the spark
gaps at pipe flanges easier.
The variant EXFS C1 KU is enclosed by a damp-proof plastic coating.
Therefore, it is ideal for underground installation at insulating couplings.
www.dehn.de 293
EXFS C1 / EXFS C1 KU LIGHTNING EQUIPOTENTIAL BONDING
923 070 EXFS C1
EXFS C1: Ex Isolating spark gap made of stainless steel for aboveground installation
EXFS C1
Lightning impulse current (10/350) Iimp 75 kA
Nominal discharge current (8/20) In 100 kA
100 % Lightning impulse sparkover voltage Uas 100 ≤ 0.95 kV
Power-frequency sparkover voltage (50 Hz) Uaw ≤ 0.07 kV
Type of protection according to EN 50014, EN 50021 II 2 G EEx m II T3
Approvals, Certifications ZELM 02 ATEX 0096X
Enclosure length L 160 mm
Enclosure diameter D 50 mm
Enclosure material stainless steel / plastic
Connection of enclosure hexagon screw M10x16 mm and M10 nut
Ordering information
Type EXFS C1
Part No. 923 070
Packing unit 1 pc(s)
Accessory Part for EXFS C1 / EXFS C1 KU Accessory Part for EXFS C1 / EXFS C1 KU
923 026
L100
923 036
L200
923 046
AL EXFS
AL EXFS
AL EXFS
Connecting Cable Cu 25 mm2 923 011
Connecting cable for EXFS C1; with cable lug Ø10.5 mm, Connection Bracket Type IF -SET- 923 011
Angled connection bracket for EXFS ...; diameter corresponds to bolt
AL EXFS L100
Connecting Lead for EXFS C1
AL EXFS L200
923 026 M10 hexagon screw and nut, StSt (V2A) and spring washer diameter of the flange screw joint (d1 possible up to max. 60 mm)
Connecting Lead for EXFS C1 923 036
AL EXFS L300
Connecting Lead for EXFS C1 923 046
Cable lug Cross Cable PU Part PU Part
Type material section length pc(s) No. Type Material pc(s) No.
AL EXFS L100 Cu/gal Sn 25 mm2 100 mm 1 923 026 IF 1 St/tZn 1 923 011
AL EXFS L200 Cu/gal Sn 25 mm2 200 mm 1 923 036
AL EXFS L300 Cu/gal Sn 25 mm2 300 mm 1 923 046
923 016
294 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING EXFS C1 / EXFS C1 KU
23 071 EXFS C1
KU
XFS C1 KU Ex-
solating Spark Gap 923 071
EXFS C1 KU
Lightning impulse current (10/350) Iimp 75 kA
Nominal discharge current (8/20) In 100 kA
100 % Lightning impulse sparkover voltage Uas 100 ≤ 0.95 kV
Power-frequency sparkover voltage (50 Hz) Uaw ≥ 0.07 kV
Type of protection according to EN 50014, EN 50021 II 2 G EEx m II T3
Approvals, Certifications (EXFS C1) ZELM 02 ATEX 0096X
Enclosure length L 160 mm
Enclosure diameter D 50 mm
Enclosure material stainless steel / plastic
Connection of enclosure NYY-J-1x25 mm2, approx. 2 m long
Ordering information
Type EXFS C1 KU
Part No. 923 071
Packing unit 1 pc(s)
www.dehn.de 295
Protective Spark Gaps LIGHTNING EQUIPOTENTIAL BONDING
for use at roof supports for overhead lines ISOLATING SPARK GAPS
The function of the DSFS spark gap for roof supports is the indirect
connection of a roof support for overhead lines to the external lightning
protection system in accordance with DIN VDE 0211 as well as
IEC 61024-1
For indirect connection of a roof support for overhead lines with the
external lightning protection system in accordance with DIN VDE 0211
DSFS
920 000 DSFS
DSFS Protective
Spark Gap for roof supports 920 000
DSFS: Plastic-insulated protective spark gap for indirect connection of a roof support for
overhead lines to the external lightning protection system
DSFS
100% Lightning impulse sparkover voltage (1.2/50) Uas100 ~25 kV
Nominal discharge current (8/20) In 25 kA
Degree of protection IP 54
Power frequency sparkover voltage (50 Hz) Uaw ~10 kV
Material (connection) stainless steel (V2A)
Connection slot Ø13x11 mm
Coating material plastic
Ordering information
Type DSFS
Part No. 920 000
Packing unit 1 pc(s)
296 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING Equipotential Bonding
PU Part
Material St/gal Zn Type pc(s) No.
Reservation of contact studs 3
RK 95 PAS 100 563 013
PU Part
Type pc(s) No.
Flat conductor 30 mm 563 012
PAS
RK FL30
KS 398
C model:
13 terminal blocks for Rd 2.5 – 16 mm2
563 030 PAS 14RK
www.dehn.de 297
Equipotential Bonding LIGHTNING EQUIPOTENTIAL BONDING
Equipotential Bonding Bars Type PAS I 8AP M10 CU PAS I 8AP M10 V2A
with miniature terminal block system
PAS I 8AP M10 CU
472 227
PAS I 8AP M10 V2A
Material Cu StSt (V2A)
472 229
PU Part
Type pc(s) No. Type PAS I 12AP M10 CU PAS I 12AP M10 V2A
PAS 10AK ST 1 472 000
PAS I 12AP M10 CU
472 237
PAS I 12AP M10 V2A
Material Cu StSt (V2A)
472 239
472 257
8AP M10 CU
PAS BW
8 connections with connecting holes Ø13 mm, without insulators
Type PAS BW 8AP M10 CU
PAS BW 8AP M10 CU
Busbar
Earthing
472 257 Material Cu
Dimension (l x w x d) 500x40x5 mm
Cross section 200 mm2
PU Part
Type pc(s) No.
PAS BW 8AP M10 CU 1 472 257
472 210
M10
IS PAS
AD PAS
AD PAS
Accessories – Covers for EBs (Industry)
10AP V2A
472 299 AD PAS
Accessories – Fixing Set for EB (Industry) AD PAS 8AP V2A 1 472 269
Type BS M10 PAS AD PAS 10AP V2A 1 472 289
St/tZn
BS M10 PAS Fixing Set
for EB 472 201
Screw material AD PAS 12AP V2A 1 472 299
Screw 45 mm c M10x20 mm
Synthetic dowel Ø12x60 mm
PU Part
Type pc(s) No.
BS M10 PAS 1 472 201
298 www.dehn.de
LIGHTNING EQUIPOTENTIAL BONDING Equipotential Bonding
PAS 3AP
Straight unit
10 V2A 290 002 AH FE RF
PAS 4AP
PAS 6AP
www.dehn.de 299
Equipotential Bonding LIGHTNING EQUIPOTENTIAL BONDING
277 249
FBH 11 ST 25 277 240
308 030
F40 STBL
VK A R22
For T- and cross connections FBH 11 CU 25 277 247
Type VK A R22 F40 STBL FBH 11 V2A 25 277 249
VK A R22 F40 STBL
Connection Clamp St 308 030 Material St/bare
Clamping range Rd / Fl (+) 6-22 / 40 mm
PU Part
Type pc(s) No.
VK A R22 F40 STBL 25 308 030 Conductor Holder
Conductor holder incl. terminal (cross sectional area 2.5 - 95 mm2)
308 041
308 040
MAXI MV terminals for T-, cross and parallel connections Type LH R10 F40 AK 95 ST LH R10 F40 AK 95 CU
Type MMVK R16 R25 ST MMVK R16 R25 STBL Material St/tZn Cu
308 041 Material St/tZn St/bare 563 150 LH R10
CH Rd / Fl 8-10 / 40x10 mm 8-10 / 40x10 mm
F40 AK 95 ST
563 157 LH R10
308 040
308 120
R10 F30 ST
308 129
R10 F30 V2A
VK EH
VK EH For T-, cross and parallel connections, without threading the Terminals
conductors 563 169
300 www.dehn.de
MEASURING AND TEST DEVICES Arrester Test Unit
PM 10
Nominal dc voltage UN 8-12 V dc
M 10
Arrester Test Unit
PM 10
910 510
Power input 2W
Test parameter: Test voltage max. 1200 V dc
Test parameter: Test current 1 mA dc, constant
Measured value indication digital, LCD 3 …-digit in Volt
Test output sockets safety pole terminal (4 mm), positive pole: red colour, negative pole: black colour
Testing time approx. 1 sec.
Quantity of the individual tests during battery operation approx. 2000
Accessories included in delivery 2 test leads, each 1 m long, 2 safety tapping test clips, 1 plug-in power supply unit 230 V ac, 1 storage bag
Dimension of storage bag 295 x 110 x 110 mm
Ordering information
Type PM 10
Part No. 910 510
Packing unit 1 pc(s)
Test Adapter
PA KT Test
Adapter PA 910 504
PA DPL Test
Adapter PA 910 505
PA CT Test
Adapter PA 910 506
910 504 PA KT
910 505 PA DPL
910 506 PA CT
For connection with the PM 10 Arrester Test Unit for plugging in and testing
protection modules: BLITZDUCTOR KT, DPL and BLITZDUCTOR CT.
PA KT PA DPL PA CT
Ordering information
Type PA KT PA DPL PA CT
Part No. 910 504 910 505 910 506
Packing unit 1 ST 1 ST 1 ST
www.dehn.de 301
DEHNisola MEASURING AND TEST DEVICES
Control Device for Surge Arresters
DEHNisola: Measuring and evaluation unit with 3 hard-wired winding-type transformers and fixing material
DISO 3
910 600 DISO 3
la
iso
HN
DE 3
O
DIS
DISO 3
DEHNisola 910 600
DISO 3: Measuring and evaluation unit with 3 transformers Dimension drawing DISO 3
DISO 3
Indication-Limit value 1 IL 0.5 mArms (indication only at site, is reset when the value falls below)
Indication-Limit value 2 IL 5 mArms (indication at site and remote signalling, is reset only by applying the reset button at the device)
Measuring cycle every hour or acyclically after every discharge at the protective device under control
Self-test generation of fault currents in each sensor for testing the measuring unit.
Battery supply service life: approx. 10 years, LowBatt indication and remote signalling
Remote signalling contact: Max. ac switching voltage 125 V
Remote signalling contact: Max. dc switching voltage 110 V
Remote signalling contact: Max. switching capacity 30 W
Remote signalling contact: Max. switching current 1A
Remote signalling contact: Cross-sectional area 0.5 to 4 mm2
Operating temperature range -25°C...+60°C
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material: Measuring and evaluation unit red thermoplastic, UL 94 V-0
Degree of protection: Measuring and evaluation unit IP 20
Dimension: Measuring and evaluation unit 1.5 mods., DIN 43880
Dimension: Sensors inner Ø11 mm, outer Ø33 mm
Length of the sensor lines 300 mm each
Weight 0.23 kg
Ordering information
Type DISO 3
Part No. 910 600
Packing unit 1 pc(s)
302 www.dehn.de
MEASURING AND TEST DEVICES Impulse Meter
Registration of Discharges
L1
10 502 P2
Imp
uls
2 Impulse zäh
ler
Meter P2 910 502 P2
Dimension drawing P2
P2
Response wave for impulse currents (rise time ≥ 8 µs) > 1 kA
Sequence of impulses >1s
LCD indicator electronic meter 0...99
Supply Battery 9 V, IEC 6LR61 included in delivery, exchangeable, service life > 1 year
Battery load control button and LED situated at device
Setting device button at device for setting a meter reading (e.g. after exchanging a battery)
Resetting device button at device for resetting the meter reading to 0
Operating temperature range -10°C...+50°C
Mounting on 35 mm DIN rail acc. to EN 60715
Enclosure material: Meter red thermoplastic, UL 94-V0
Enclosure material: Sensor PA 6, grey colour
Degree of protection IP 20
Dimension: Meter 2 mods., DIN 43880
Dimension: Sensor inner Ø15 mm, outer Ø36 mm
Length of the connecting conductor (sensor to meter) max. 1 m, twisted
Weight (Meter, sensor and connecting conductor) 0.2 kg
Accessories included in delivery battery 9 V, IEC 6LR61; cable tie (fixing of sensors)
Ordering information
Type P2
Part No. 910 502
Packing unit 1 pc(s)
www.dehn.de 303
MEASURING AND TEST DEVICES
304 www.dehn.de
FURTHER INFORMATION AND DOCUMENTATION
Reprints Lightning Protection Guide Publications
32/E Lightning Protection for Fulfilling the Our Lightning Protection Guide is an indispens- DS 103 DEHN schützt Windenergieanlagen –
Principles of EMC able work equipment for lightning protection DEHN protects Wind Turbines
Reprinted from etz, Issue 1/1995 specialists.
DS 104 DEHN schützt Mobilfunkanlagen –
It includes procedure documentation, informa-
43/E Follow current limiting lightning current DEHN protects Cell Sites
tion and lists which the specialist needs for his
arrester for application in main distribu-
work. DS 107 E Safety for Sewage Plants
tion systems
The Lightning Protection Guide shall help to
Article from Elektropraktiker, DS 109 DEHN schützt Photovoltaikanlagen –
find solutions for lightning protection problems,
Issue 12/1997 DEHN protects Photovoltaic Systems
to design and install lightning protection sys-
tems, but also to measure and maintain the DS 122 DEHN schützt Anlagen der Öl- und
external and internal lightning protection sys- Gasindustrie –
tem. DEHN protects the Oil and Gas
Application Examples We shall be pleased to send it to you. Industry
Our application examples show examplarily
effected standard solutions. With basic common DS 125 E DEHN protects Medium Voltage
Contents:
characteristics combining individual installa- Systems
tions, they show which measures or protective 1. State of the art for installation of lightning
DS 509 DEHN protects – DEHN schützt
components to take in order to protect the protection systems
installation sufficiently. DS 614 E DEHN stops Surges
2. Characteristics of lightning current
By means of examples they show which light- DS 647 E Safety for your data networks
ning and surge protective equipment has been 3. Designing a lightning protection system
used for a building structure for principal pro- DS 663 E Safety for your measuring and
4. Lightning protection system
tection. Thus, it is no problem for designers to control system
transfer these solutions to present questions. 5. External lightning protection
DS 699 E DEHNventil Future starts here
The proposed solutions are so flexible to allow 6. Internal lightning protection
any variations, additions or individual adjust-
ments. 7. Protection of electrical and electronic
Further main catalogues
systems against LEMP
This means for the user: DS 427 E Main Catalogue EB –
8. Choice, installation and assembly of surge
The application example helps to design the Lightning Protection
protective devices (SPDs)
basic structure of the lightning and surge pro- DS 396 E Main Catalogue EK –
tection system; the standard performance index 9. Application proposals
Safety Equipment (pdf only)
describes the individual protective devices.
For further information please contact the DS 696 E Main Catalogue DELTEC –
responsible representatives of DEHN + SÖHNE Safety Equipment (pdf only)
in your country. They shall be pleased to give
you the requested information.
Like our catalogues and other publications,
our installation instructions can also be down-
loaded from our website
Seminars: www.dehn.de
We also provide seminars in the fields
The printed publications can be ordered from
– Lightning Protection our export department
– Surge Protection Fax: +49-(0)9181-906-444
– Safety Equipment
www.dehn.de 305
LITERATURE
DIN VDE Standards, VDE-Verlag, Berlin DIN V VDE V 0185 * VDE V 0185 Part 4 DIN VDE 0800 Part 2:1985-07
DIN VDE 0100:1973-05 Protection against lightning – Part 4: Electrical Telecommunications;
Erection of power installations with rated volta- and electronic systems within structures Earthing and equipotential bonding
ges below 1000 V
DIN EN 50164-1 DIN VDE 0800 Part 10:1991-03
DIN VDE 0100 Part 410:1997-01 DIN VDE 0185 Part 201:2000-04 Telecommunications;
Erection of power installations with nominal Lightning protection components (LPC) – Transitional requirements on erection and
voltages up to 1000 V – Part 4: Protection for Part 1: Requirements for connection compo- operation of installations
safety; Chapter 41: Protection against electric nents
shock (IEC 60364-4- 41:1992, modified); German version EN 50164-1:1999 DIN EN 50116
German version HD 384.4.41 S2:1996 DIN VDE 0805 Part 116:1997-06
DIN IEC 60060-1 Information technology equipment – Routine
DIN VDE 0100 Part 540:1991-11 DIN VDE 0432 Part 1:1994-06 electrical safety testing in production;
Erection of power installations with nominal High-voltage test techniques – Part 1: General German version EN 50116:1996
voltages up to 1000 V – Part 540: Selection and definitions and requirements (IEC 60060-1:
erection of equipment – earthing arrange- 1989+Corrigendum March 1990) DIN EN 41003
ments, protective conductors, equipotential German version HD 588.1 S1:1991 DIN VDE 0804 Part 100:1999-08
bonding conductors Particular safety requirements for equipment to
DIN VDE 0618 Part 1:1989-08 be connected to telecommunication networks;
DIN VDE 0100 Part 443:2002-01 Equipment for equipotential bonding; equipo- German version EN 41003:1998
Erection of low voltage installations – tential bonding busher for main equipotential
Part 4: Protection for safety; bonding DIN VDE 0845 Part 1:1987-10
Chapter 44: Protection against overvoltages; Protection of telecommunication systems
Section 443: Protection against overvoltages of DIN EN 60099-1 against lightning, electrostatic discharges and
atmospheric origin or due to switching DIN VDE 0675 Part 1:2000-08 overvoltages from electric power installations;
(IEC 60364-4-443:1995, modified); Surge arresters – Part 1: Non-linear resistor provisions against overvoltages
German version HD 384.4.443 S1:2000 type gapped surge arresters for a.c. systems
(IEC 60099-1:1991) E DIN VDE 0845 Part 2:1993-10
DIN V VDE V 0100 Part 534:1999-04 German version EN 60099-1:1994 + A1:1999 Protection of information technology and tele-
Electrical installations of buildings – communication against lightning, electrostatic
Part 534: Selection and erection of equipment – E DIN VDE 0675 Part 6:1989-11 discharges and overvoltages from electric
Devices for protection against overvoltage Surge arresters power installations; requirements and tests of
for use in a.c. supply systems with rated volta- overvoltage protection devices
DIN EN 60664-1:2003 ges ranging from 100 V to 1000 V
DIN VDE 0110 Part 1:2003-11 DIN EN 50083-1
Insulation coordination for equipment within E DIN VDE 0675 Part 6/A1:1996-03 DIN VDE 0855 Part 1:1994-03
low-voltage systems – Part 1: Principles, re- Surge arrester Cable networks for television signals, sound
quirements and tests for use in a.c. supply systems with rated volta- signals and interactive services – Part 1: Safety
ges ranging from 100 V to 1000 V requirements;
DIN VDE 0141:2000-01 German version EN 50083-1:1993
Earthing system for special power installations E DIN VDE 0675 Part 6/A2:1996-10
with nominal voltages above 1 kV Surge arresters DIN 18014:1994-02
for use in a.c. supply systems with rated volta- Foundation earth electrode
DIN EN 50178 ges ranging from 100 V to 1000 V
DIN VDE 0160:1998-04 IEC 60664-1:1992-10
Electronic equipment for use in power installa- DIN EN 61643-11 * VDE 0675 Part 6-11: Insulation coordination for equipment within
tions 2002-12-00 low-voltage systems; part 1: principles, require-
German version EN 50178:1997 Low-voltage surge protective devices – ments and tests
Part 11: Surge protective devices connected to
DIN V VDE V 0185-1 * VDE V 0185 Part 1 low-voltage power systems; Requirements and IEC 61024-1:1990-03
Protection against lightning – Part 1: General tests (IEC 61643-1:1998 + Corrigendum:1998, Protection of structures against lightning;
principles modified) Part 1: general principles
German version EN 61643-11:2002
DIN V VDE V 0185-2 * VDE V 0185 Part 2 IEC 61024-1-1:1993-08
DIN VDE 0800 Part 1:1989-05
Protection against lightning – Part 2: Risk Protection of structures against lightning;
management Telecommunications; Part 1: general principles; Section 1: guide A:
General concepts; requirements and tests for selection of protection levels for lightning pro-
DIN V VDE V 0185-3 * VDE V 0185 Part 3 the safety of facilities and apparatus tection systems
Protection against lightning – Part 3: Physical
damage to structures and live hazard
306 www.dehn.de
IEC 61024-1-2:1998-05 Books – Raab V.:
Protection of structures against lightning part – Hasse P., Wiesinger J.: "Überspannungsschutz in
1-2: general principles – guide B – design, Verbraucheranlagen – Auswahl, Errichtung,
installation, maintenance and inspection of "Handbuch für Blitzschutz und Erdung"
Prüfung", Huss-Medien GmbH Verlag
lightning protection systems Pflaum Verlag KG, München (ISBN 3-7905-
Technik, Berlin: (ISBN 3-341-01347-4), 2.
0657-5); VDE-Verlag GmbH, Berlin-Offen-
aktualisierte und erweiterte Auflage 2003.
IEC 61643-1:1998-02 bach (ISBN 3-8007-1882-0), 4., bearbeitete
Auflage 1993; 5. Auflage in Vorbereitung – Hasse P., Raab P.:
Surge protective devices connected to low-
voltage power distribution systems – – Hasse P.: In Vorbereitung Beitrag für:
Part 1: Performance requirements and testing "Loseblattsammlung VDE-Kompass
methods "Überspannungsschutz von Niederspan-
InfoPLUS-Paket 5 (7. Ergänzungslieferung)
nungsanlagen – Einsatz elektronischer
"Neue Blitzschutz-Normen in der Praxis",
IEC 61643-21:2000-09 Geräte auch bei direkten Blitzeinschlägen",
VDE Verlag, Berlin Offenbach
Verlag TÜV Rheinland, Köln (ISBN 3-8249-
Low voltage surge protective devices – 0474-8) 4., vollst. überarb. und erweiterte
Part 21: Surge protective devices connected to Auflage,1998; 5. Auflage in Vorbereitung
telecommunications and signalling networks –
Performance requirements and testing methods – Hasse P., Wiesinger J.:
"EMV Blitz-Schutzzonen-Konzept"
IEC 61312-1:1995-02 Pflaum-Verlag, München, Berlin-Offenbach:
Protection against lightning VDE-Verlag 1. Auflage 1994, (ISBN 3-7905-
electromagnetic impulse – 0670-2 bzw. 3-8007-1982-7)
Part 1: General principles
– Hasse P., Wiesinger J.:
"Blitzschutz der Elektronik – Risikoanalyse,
VG Standards, Beuth-Verlag GmbH Planen und Ausführen nach den neuen
VG 95 372:2000-06 Normen der Reihe DIN VDE 0185"
Elektromagnetische Verträglichkeit (EMV) ein- Pflaum-Verlag, München, Berlin-Offenbach:
schließlich Schutz gegen den Elektromagne- VDE-Verlag 1. Auflage 1999, 3-7905-0792-X
tischen Impuls (EMP) und Blitz (Übersicht) bzw. 3-8007-2345-X
– Hasse P.:
VG 95 371 Part 10:2003-08
"Überspannungsschutz von Niderspan-
Elektromagnetische Verträglichkeit (EMV) ein-
nungsanlagen – Einsatz elektronischer
schließlich Schutz gegen den Elektromagne-
Geräte auch bei direkten Blitzeinschlägen"
tischen Impuls (EMP) und Blitz. Allgemeine
TÜV Rheinland, Köln, 4. Auflage 1998, 3-
Grundlagen, Teil 10: Bedrohungsdaten für den
8249-0474-8
NEMP und Blitz.
Beiblatt 1:1993-09, Beiblatt 2:1993-08. – Hasse P.: (Mitautor des Gesamtwerkes)
"Blitz- und Überspannungsschutz für elektri-
VG 96 907 Part 1:2000-01
sche Verbraucheranlagen"
Schutz gegen Nuklear-Elektromagnetsichen Egyptien/Schliephacke (Gesamtwerk)
Impuls (NEMP) und Blitzschlag-Konstruktions- Buchtitel "Die Elektrofachkraft in der
maßnahmen und Schutzeinrichtungen. – Teil 1: betrieblichen Praxis"
Allgemeines WEKA Fachverlag für technische
Führungskräfte GmbH, 1999, Augsburg
3-8111-1161-0
Further Standards "Blitz- und Überspannungsschutz für elektri-
DVGW GW 309: Elektrische Überbrückung bei sche Verbraucheranlagen" Abschnitte 7.6.1
Rohrtrennungen. ZfGW-Verlag GmbH, Frankfurt. bis 7.6.6)
Ausgabe 2000
Arbeitsgemeinschaft DVGW/VDE für Korrosions- 3-8111-1161-0
fragen (AfK): AfK-Empfehlung Nr. 5/02.86, Ausgabe 2003
Kathodischer Korrosionsschutz in Verbindung 3-8111-1161-0
mit explosionsgefährdeten Bereichen. ZfGW- – Hasse P., Landers U., Wiesinger J.:
Verlag GmbH, Frankfurt.
"Blitzschutz von elektrischen und elektroni-
KTA 2206/2000-06: Auslegung von Kernkraft- schen Systemen in baulichen Anlagen –
werken gegen Blitzeinwirkung. Risiko-Management, Planung und Ausführen
nach der neuen Vornormen der Reihe
0185".
VDE-Schriftenreihe Band 185, Berlin-
Offenbach: VDE Verlag GmbH, ISBN 3-8007-
2801-X, Erscheinungstermin. Sommer 2004.
www.dehn.de 307
KEY TO SYMBOLS USED IN BASIC CIRCUIT DIAGRAMS
EN 60617
Creepage discharge spark gap Capacitor Part 4
04-02-01
EN 60617
Varistor Part 4 Inductor
04-01-04
EN 60617
Thermal disconnector Part 7 Resistor,
07-09-03 temperature-controlled
EN 60617 EN 60617
Thermo Dynamic Control Parts 7 + 11 Socket and plug connector Part 3
07-09-03 03-03-05
111-07-02
EN 60617 EN 60617
Spark gap, general Part 7 Break contact Part 7
07-22-01 07-02-03
EN 60617 EN 60617
Fuse Part 7 Changeover contact Part 7
07-21-01 07-02-04
EN 60617
Temperature fuse Close contact Part 7
07-02-01
EN 60617 EN 60617
Filter, general Part 10 Enclosure with terminals Parts 2 + 3
10-16-03 02-01-07
03-02-02
EN 60617 EN 60617
LED, general Part 8 Horn Part 8
08-10-01 08-10-05
EN 60617
Suppressor diode, bipolar Part 5
05-03-07
EN 60617
Z-Diode, unipolar Part 5
05-03-06
308 www.dehn.de
LEGAL NOTES
Since we do not carry out the design of systems or system components, Trademarks
the suggested application of our products should be regarded as pro-
– "DEHNbloc" and our logo
duct information and for advisory purposes only. Our oral and written
advice on application is based on experience and given to the best of – "DEHNguard"
our knowledge. However, it must be also considered as not binding. This
– "DEHNport"
particularly applies to the different conditions of use which are beyond
our control. We recommend to check whether the respective DEHN pro- – "DEHNventil"
duct is suitable for the intended application.
– "BLITZDUCTOR"
Application, use and processing of our products take place beyond our
are registered trade marks of
control. Therefore, the product is completely subject to the user’s res- – ...MIT SICHERHEIT DEHN.
ponsibility. DEHN + SÖHNE GMBH + CO. KG.
www.dehn.de 309
INDEX OF PART NO.
Part No. Type Page Part No. Type Page Part No. Type Page
277 230 FBH 6 ST 300 472 289 AD PAS 10AP V2A 298 900 373 DV TNC 255 28
277 237 FBH 6 CU 300 472 299 AD PAS 12AP V2A 298 900 374 DV TNS 255 29
277 239 FBH 6 V2A 300 900 375 DV TT 255 30
277 240 FBH 11 ST 300 563 010 PAS 10RK 297 900 471 VC 280 2 113
277 247 FBH 11 CU 300 563 011 RK 16 PAS 297 900 506 DG TN 230 61
277 249 FBH 11 V2A 300 563 012 RK FL30 PAS 297 900 507 DG TN 230 FM 61
563 013 RK 95 PAS 297 900 508 DG TT 230 62
290 001 AH FE RF V G 299 563 014 SB PAS RK 297 900 509 DG TT 230 FM 62
290 002 AH FE RF 299 563 015 AH PAS RK 297 900 510 DG TNC 230 400 56
563 016 KS 198 PAS 297 900 540 DG TNC 230 400 FM 56
308 001 KV FE UNI 299 563 017 KS 398 PAS 297 900 516 DG IT 500 59
308 010 KV FE R10 299 563 018 KS 798 PAS 297 900 546 DG IT 500 FM 59
308 025 VK A UNI ST 300 563 019 RK FL40 PAS 297 900 517 DG Y PV 1000 70
308 026 VK A UNI V2 ST 300 563 020 PAS 9RK 297 900 520 DG TT 230 400 58
308 030 VK A R22 F40 STBL 300 563 030 PAS 14RK 297 900 550 DG TT 230 400 FM 58
308 040 MMVK R16 R25 ST 300 563 050 PAS 9AK 297 900 530 DG TNS 230 400 57
308 041 MMVK R16 R25 STBL 300 563 103 PAS 7RK UP 298 900 560 DG TNS 230 400 FM 57
308 120 VK EH R10 F30 ST 300 563 105 PAS 6RK OH 298 900 547 DG Y PV 1000 FM 70
308 129 VK EH R10 F30 V2A 300 563 150 LH R10 F40 AK 95 ST 300 900 595 MVS 3 6 126
308 403 SAK 10 AS V4A 274 563 157 LH R10 F40 AK 95 CU 300 900 600 DG 275 64
308 404 SAK 14 AS V4A 274 563 169 AK RPA V2A 300 900 601 DG 600 64
308 405 SAK 18 AS V4A 274 563 200 PAS 11AK 297 900 602 DG 385 64
308 406 SAK 21 AS V4A 274 563 222 AK FL40 PAS 297 900 603 DG 150 64
308 407 SAK 26 AS V4A 274 900 604 DG 75 64
308 408 SAK 33 AS V4A 274 900 025 DBM 1 255 40 900 605 DG 320 64
308 411 AK 16 AS SAK MS 275 900 026 DBM 1 255 L 40 900 607 DG 440 64
308 421 AS SAK 1000 V2A 274 900 055 DGPM 255 51 900 610 MVS 1 4 125
308 425 ST AS SAK K 275 900 100 DP 255 49 900 611 MVS 1 8 125
900 101 DP 440 49 900 612 MVS 1 57 125
472 000 PAS 10AK ST 298 900 104 DPM 255 47 900 613 MVS 3 57 126
472 021 PAS 6AP 10 ST 299 900 110 DB 3 255 44 900 614 MVS 4 56 126
472 022 PAS 3AP 10 ST 299 900 111 DB 1 255 43 900 616 MVS 2 7 16 125
472 023 PAS 2AP 10 ST 299 900 121 DBR 35 121 900 619 MVS 2 7 22 126
472 024 PAS 4AP 10 ST 299 900 122 DBR 63 121 900 620 DG 275 FM 65
472 109 PAS 2AP 10 V2A 299 900 130 DGP B 255 52 900 621 DG 600 FM 65
472 119 PAS 3AP 10 V2A 299 900 132 DGP BN 255 52 900 622 DG 385 FM 65
472 129 PAS 4AP 10 V2A 299 900 133 DGP C T 255 72 900 623 DG 150 FM 65
472 139 PAS 6AP 10 V2A 299 900 134 T C 255 77 900 624 DG 75 FM 65
472 201 BS M10 PAS 298 900 159 DB 1 440 43 900 625 DG 320 FM 65
472 207 PAS I 6AP M10 CU 298 900 222 DB 1 255 H 42 900 627 DG 440 FM 65
472 209 PAS I 6AP M10 V2A 298 900 260 DB NH00 255 45 900 641 DG T 385 67
472 210 IS PAS M10 298 900 261 V NH00 280 81 900 650 DG T 275 67
472 217 PAS I 10AP M10 CU 298 900 262 VA NH00 280 84 900 651 DG T 600 67
472 219 PAS I 10AP M10 V2A 298 900 263 V NH00 280 FM 82 900 652 DG T 320 67
472 227 PAS I 8AP M10 CU 298 900 264 VA NH00 280 FM 85 900 653 DG T 150 67
472 229 PAS I 8AP M10 V2A 298 900 265 V NH1 3 280 83 900 654 DG T 75 67
472 237 PAS I 12AP M10 CU 298 900 266 VA NH1 3 280 86 900 655 DG T 440 67
472 239 PAS I 12AP M10 V2A 298 900 269 DGP B NH00 N 255 53 900 659 DG T 275 VA 74
472 257 PAS BW 8AP M10 CU 298 900 309 IGA 10 IP54 123 900 667 DG T 75 VA 74
472 269 AD PAS 8AP V2A 298 900 370 DV 2P TT 255 33 900 674 T 75 77
472 279 AD PAS 6AP V2A 298 900 371 DV 2P TN 255 32 900 673 T 150 77
310 www.dehn.de
INDEX OF PART NO.
Part No. Type Page Part No. Type Page Part No. Type Page
900 670 T 275 77 901 102 DR 60 FML 98 907 998 ES 10DA 193
900 672 T 320 77 901 103 DR 48 FML 98 907 998 ES 10DA 190
900 679 T 385 77 901 104 DR 24 FML 98 907 998 ES 10DA 191
900 675 T 440 77 901 130 DR 230 3N FML 100 907 998 ES 10DA 188
900 671 T 600 77 907 998 ES 10DA 189
900 680 DG T 275 FM 68 902 375 VA NH00 280 3 IG FM 89
900 681 DG T 600 FM 68 902 376 VA NH00 280 4 IG FM 89 909 703 DGA FF TV 225
900 682 DG T 320 FM 68 902 385 VA NH00 280 3 IG 88 909 820 SF PRO 116
900 683 DG T 150 FM 68 902 386 VA NH00 280 4 IG 88 909 821 S PRO 115
900 684 DG T 75 FM 68 902 485 IGA 6 IP54 124 909 921 TV PRO 288
900 685 DG T 440 FM 68 902 486 IGA 11 IP54 124 909 950 FAX PRO RJ11 286
900 689 DG T 275 VA FM 75 902 492 NAK TAB 3 95 909 954 ISDN PRO 283
900 691 DG T 385 FM 68 902 493 NAK TAB 3+1 95 909 955 DATA PRO 4TP 284
900 692 DG T 75 VA FM 75 902 494 NAK TAB 4 95 909 956 FAX PRO RJ45 287
900 699 DK 35 122 909 957 FAX PRO TAE FN 285
900 813 MVS 3 6 8 126 906 055 ALGA 5 279 909 958 NT PRO 282
900 814 MVS 4 8 11 126 906 058 ALGA 5 X 279
900 964 NAK 63A 4 93 906 059 MS ALGA 5 X 280 910 099 SLK 16 280
900 965 NAK 63A 3 93 906 059 MS ALGA 5 X 261 910 502 P2 303
900 966 NAK 35A 4 92 910 504 PA KT 301
900 967 NAK 35A 3+1 92 907 110 DPL 10 F ARE 24 194 910 505 PA DPL 301
900 968 NAK 35A 3 92 907 111 DPL 10 F ARE 110 194 910 506 PA CT 301
900 969 NAK 63A 3+1 93 907 112 DPL 10 F ARE 12 194 910 510 PM 10 301
900 134 T C 255 72 907 120 DPL 1 F ALE 5 191 910 600 DISO 3 302
900 134 T C 255 62 907 121 DPL 1 F ALE 12 191 910 620 DSI DV 40
900 134 T C 255 58 907 122 DPL 1 F ALE 15 191 910 620 DSI DV 35
900 670 T 275 68 907 123 DPL 1 F ALE 24 191 910 620 DSI DV 30
900 670 T 275 67 907 124 DPL 1 F ALE 48 192 910 620 DSI DV 28
900 670 T 275 62 907 125 DPL 1 F ALE 60 192 910 620 DSI DV 29
900 670 T 275 61 907 126 DPL 1 F ALE 110 192 910 621 DSI DV 2P 36
900 670 T 275 58 907 127 DPL 1 F ARE 5 193 910 621 DSI DV 2P 32
900 670 T 275 56 907 128 DPL 1 F ARE 12 193 910 621 DSI DV 2P 33
900 670 T 275 57 907 129 DPL 1 F ARE 15 193 910 623 DSI DBM 40
900 671 T 600 68 907 130 DPL 1 F ARE 24 193 910 623 DSI DBM 37
900 671 T 600 67 907 144 DPL 1 F ATP 5 190 910 630 DSI E DV 38
900 671 T 600 59 907 145 DPL 1 F ARD 110 189 910 640 LWL DSI 38
900 672 T 320 68 907 146 DPL 1 F ARD 250 189 910 641 LWL ST DSI 38
900 672 T 320 67 907 210 DPL 10 G2 110 195
900 673 T 150 68 907 211 GDT 230 196 912 253 SPS PRO 103
900 673 T 150 67 907 212 BM 10DA 196 912 254 NF 10 101
900 674 T 75 68 907 213 AD BM 10DA 196 912 260 SFL PRO 118
900 674 T 75 67 907 214 DPL 10 G3 110 195
900 675 T 440 70 907 215 DPL 10 G3 110 FS 195 918 400 BVT TTY 24 177
900 675 T 440 68 907 220 DPL 1 G A 110 188 918 401 BVT RS485 5 180
900 675 T 440 67 907 993 EL2 38EA LSA 198 918 402 BVT AD 24 181
900 679 T 385 68 907 994 AW2 LSA 197 918 403 BVT GS 110 179
900 679 T 385 67 907 995 MB2 10 LSA 197 918 404 BVT KKS ALD SN 185
907 996 TL2 10DA LSA 198 918 405 BVT KKS APD SN 186
901 000 VAV 1000 79 907 997 AL2 10DA LSA 198 918 407 BVT MTTY 24 178
901 100 DR 230 FML 98 907 998 ES 10DA 196 918 410 BVT ISDN 208
901 101 DR 120 FML 98 907 998 ES 10DA 192 918 411 BVT TC 1 209
www.dehn.de 311
INDEX OF PART NO.
Part No. Type Page Part No. Type Page Part No. Type Page
918 420 BVT KKS ALD 75 183 919 522 BCT MOD ME 15 156 919 880 KB 10 DCO RK 175
918 421 BVT KKS APD 36 184 919 523 BCT MOD ME 24 156 919 885 KB 5 DCO RK 175
919 524 BCT MOD ME 30 156 919 888 KB 8 DCO RK 175
919 010 SAK 6,5 SN MS 276 919 525 BCT MOD ME 48 156 919 920 DCO RK ME 12 168
919 011 SAK 11 SN MS 276 919 526 BCT MOD ME 60 156 919 921 DCO RK ME 24 168
919 012 SH1 18X3 ST 277 919 527 BCT MOD ME 110 157 919 922 DCO RK ME 48 168
919 013 SH2 18X3 ST 277 919 540 BCT MOD MD 5 159 919 923 DCO RK ME 110 168
919 014 SH 18X3 K 277 919 541 BCT MOD MD 12 159 919 940 DCO RK MD 12 169
919 015 AK 35 SN 18X3 GG 277 919 542 BCT MOD MD 15 159 919 941 DCO RK MD 24 169
919 016 SN 18X3 CU 1000 276 919 543 BCT MOD MD 24 159 919 942 DCO RK MD 48 170
919 030 SKB 19 9M SW 278 919 544 BCT MOD MD 30 159 919 943 DCO RK MD 110 171
919 031 SA KRF 10 V2A 278 919 545 BCT MOD MD 48 159 919 960 DCO RK MD EX 24 264
919 032 SA KRF 15 V2A 278 919 546 BCT MOD MD 60 159 919 970 DCO RK MD HF 5 172
919 033 SA KRF 22 V2A 278 919 547 BCT MOD MD 110 160 919 977 BS 1 50 DCO RK 264
919 034 SA KRF 29 V2A 278 919 549 BCT MOD MD 250 160 919 977 BS 1 50 DCO RK 175
919 035 SA KRF 37 V2A 278 919 552 BCT MOD MD TC N 163 919 978 AD DCO RK BL 264
919 036 SA KRF 50 V2A 278 919 560 BCT MOD ME C 5 158 919 979 AD DCO RK GE 175
919 037 SA KRF 70 V2A 278 919 561 BCT MOD ME C 12 158 919 979 AD DCO RK GE 174
919 038 SA KRF 94 V2A 278 919 562 BCT MOD ME C 24 158 919 979 AD DCO RK GE 173
919 502 GDT 90 165 919 563 BCT MOD ME C 30 158 919 979 AD DCO RK GE 172
919 502 GDT 90 147 919 570 BCT MOD MD HF 5 161 919 979 AD DCO RK GE 171
919 504 BCT MOD PTS 165 919 571 BCT MOD MD HFD 5 162 919 979 AD DCO RK GE 170
919 504 BCT MOD PTS 147 919 575 BCT MOD MD HFD 24 162 919 979 AD DCO RK GE 169
919 505 EKS BCT 166 919 580 BCT MOD MD EX 24 258 919 979 AD DCO RK GE 168
919 505 EKS BCT 147 919 581 BCT MOD MD EX 30 258 919 986 DCO RK D 5 24 174
919 506 BCT BAS 164 919 583 BCT MOD MD HFD EX 6 259 919 987 DCO RK E 12 173
919 506 BCT BAS 162 919 589 BCT MOD MY 250 164 919 988 DCO RK E 24 173
919 506 BCT BAS 163 919 620 BCT MOD BE 5 149 919 989 DCO RK E 48 173
919 506 BCT BAS 160 919 621 BCT MOD BE 12 149 919 990 DCO RK E 60 173
919 506 BCT BAS 161 919 622 BCT MOD BE 15 149
919 506 BCT BAS 158 919 623 BCT MOD BE 24 149 920 000 DSFS 296
919 506 BCT BAS 159 919 624 BCT MOD BE 30 149
919 506 BCT BAS 156 919 625 BCT MOD BE 48 149 923 011 IF 1 294
919 506 BCT BAS 157 919 626 BCT MOD BE 60 149 923 011 IF 1 291
919 506 BCT BAS 154 919 627 BCT MOD BE 110 150 923 016 IF 3 294
919 506 BCT BAS 155 919 640 BCT MOD BD 5 152 923 016 IF 3 291
919 506 BCT BAS 152 919 641 BCT MOD BD 12 152 923 019 EXFS KU 292
919 506 BCT BAS 153 919 642 BCT MOD BD 15 152 923 021 KFSU 289
919 506 BCT BAS 150 919 643 BCT MOD BD 24 152 923 023 TFS 289
919 506 BCT BAS 151 919 644 BCT MOD BD 30 152 923 026 AL EXFS L100 294
919 506 BCT BAS 148 919 645 BCT MOD BD 48 152 923 036 AL EXFS L200 294
919 506 BCT BAS 149 919 646 BCT MOD BD 60 152 923 046 AL EXFS L300 294
919 506 BCT BAS 147 919 647 BCT MOD BD 110 153 923 060 EXFS L100 291
919 507 BCT BAS EX 258 919 649 BCT MOD BD 250 153 923 061 EXFS L200 291
919 507 BCT BAS EX 259 919 660 BCT MOD BE C 5 151 923 062 EXFS L300 291
919 507 BCT BAS EX 257 919 661 BCT MOD BE C 12 151 923 070 EXFS C1 294
919 508 EFK BCT 166 919 662 BCT MOD BE C 24 151 923 071 EXFS C1 KU 295
919 508 EFK BCT 147 919 663 BCT MOD BE C 30 151
919 510 BCT MOD B 110 148 919 670 BCT MOD BD HF 5 154 924 016 FS 15E 5 234
919 520 BCT MOD ME 5 156 919 671 BCT MOD BD HFD 5 155 924 017 FS 9E PB 6 232
919 521 BCT MOD ME 12 156 919 675 BCT MOD BD HFD 24 155 924 018 FS 25E HS 12 235
312 www.dehn.de
INDEX OF PART NO.
Part No. Type Page Part No. Type Page Part No. Type Page
924 019 FS 9E HS 12 233 924 396 DFL M 255 107 929 067 NET PRO ISDN 202
924 040 USD 25 V24 S KB 239 929 068 NET PRO ISDN LSA 202
924 041 USD 25 V24 S B 239 925 001 BT 24 247 929 069 NET PRO TC 1 203
924 045 USD 25 V24 HS S KB 239 925 010 AS I MOD 249 929 070 NET PRO TC 1 LSA 203
924 046 USD 25 V24 HS S B 239 929 071 NET PRO TC 2 203
924 047 USD 25 TTY B KS 240 929 010 UGKF BNC 220 929 072 NET PRO TC 2 LSA 203
924 048 USD 25 TTY B S 240 929 012 UGKF N L 222 929 074 NET PRO E1 LSA 204
924 050 USD 15 V11 S KB 238 929 017 UGKF B L 221 929 080 DLI TC ECO 215
924 051 USD 15 V11 S B 238 929 024 DLI ISDN I 213 929 081 DLI TC ECO RJ12 215
924 060 USD 9 V24 S KB 237 929 026 DLI TC BT 218 929 100 DPA M CAT6 RJ45S 48 206
924 061 USD 9 V24 S B 237 929 027 DLI TC 1 I 214 929 110 DPA M CAT6 RJ45H 48 206
924 263 DSM RJ45 4TP 242 929 028 DLI TC 2 I 214 929 199 MS DPA 206
924 270 DSM ISDN SK 244 929 029 DLI TC DK 215 929 921 DPI ME 24 N A2G 253
924 271 DSM TC 1 SK 245 929 034 EG NET PRO 19” 204 929 941 DPI MD 24 M 2S 252
924 272 DSM TC 2 SK 245 929 034 EG NET PRO 19” 202 929 960 DPI MD EX 24 M 2 267
924 273 DSM TC DK SK 245 929 034 EG NET PRO 19” 203 929 961 DPI CD EXI 24 M 268
924 274 DSM TM 211 929 034 EG NET PRO 19” 201 929 962 DPI CD EXD 24 M 271
924 298 AMD DSM 242 929 035 NET PRO 4TP 201 929 963 DPI CD EXI 24 N 268
924 328 AR1 STW 105 929 036 NET PRO LSA 4TP 201 929 964 DPI CD EXD 24 N 271
924 329 ZAP STW 105 929 037 NET PRO 4TP 30 201 929 981 KV S M20 MS 13 269
924 335 NSM PRO TW 120 929 040 DGA F 1.6 5.6 226 929 981 KV S M20 MS 13 254
924 336 AR1 TW 120 929 041 DGA G 1.6 5.6 227 929 982 KV S M20 MS 9.5 269
924 337 NSM PRO SI 120 929 042 DGA G BNC 227 929 982 KV S M20 MS 9.5 254
924 338 AR1 SI 120 929 043 DGA AG BNC 228 929 984 KV M20 MS 10.5 269
924 339 NSM PRO AZ 120 929 044 DGA G N 227 929 984 KV M20 MS 10.5 254
924 340 AR1 AZ 120 929 045 DGA AG N 228 929 985 KV M20 MS 8 269
924 342 NSM PRO EW 120 929 046 DGA LG 7 16 229 929 985 KV M20 MS 8 254
924 343 AR1 EW 120 929 047 DGA L4 7 16 S 230 929 996 ER DPI M20 254
924 350 STC 230 111 929 048 DGA L4 7 16 B 230
924 370 DSA 230 LA 105 929 049 DGA L4 N B 230 989 406 ITAK EXI 30 261
924 389 DFL A 255 108 929 057 DGA AG U 228
924 395 DFL D 255 109 929 058 DGA G N 3 227
www.dehn.de 313
TYPE / PRODUCT INDEX
Type Product Part No. Page Type Product Part No. Page
AD BM 10DA Surge Protective Block for DPL 10 G 907 213 196 BCT BAS BCT-Base Part 919 506 151
AD DCO RK BL Covering Plate for DCO, blue 919 978 264 BCT BAS BCT-Base Part 919 506 148
AD DCO RK GE Covering Plate for DCO, yellow 919 979 175 BCT BAS BCT-Base Part 919 506 149
AD DCO RK GE Covering Plate for DCO, yellow 919 979 174 BCT BAS BCT-Base Part 919 506 147
AD DCO RK GE Covering Plate for DCO, yellow 919 979 173 BCT BAS EX BCT-Base Part (Ex) 919 507 258
AD DCO RK GE Covering Plate for DCO, yellow 919 979 172 BCT BAS EX BCT-Base Part (Ex) 919 507 259
AD DCO RK GE Covering Plate for DCO, yellow 919 979 171 BCT BAS EX BCT-Base Part (Ex) 919 507 257
AD DCO RK GE Covering Plate for DCO, yellow 919 979 170 BCT MOD B 110 BCT-Protection Module B, 110 V 919 510 148
AD DCO RK GE Covering Plate for DCO, yellow 919 979 169 BCT MOD BD 110 BCT-Protection Module BD, 110 V 919 647 153
AD DCO RK GE Covering Plate for DCO, yellow 919 979 168 BCT MOD BD 12 BCT-Protection Module BD, 12 V 919 641 152
AD PAS 10AP V2A Cover NIRO, for 10-pole EB 472 289 298 BCT MOD BD 15 BCT-Protection Module BD, 15 V 919 642 152
AD PAS 12AP V2A Cover NIRO, for 12-pole EB 472 299 298 BCT MOD BD 24 BCT-Protection Module BD, 24 V 919 643 152
AD PAS 6AP V2A Cover NIRO, for 6-pole EB 472 279 298 BCT MOD BD 250 BCT-Protection Module BD, 250 V 919 649 153
AD PAS 8AP V2A Cover NIRO, for 8-pole EB 472 269 298 BCT MOD BD 30 BCT-Protection Module BD, 30 V 919 644 152
AH FE RF Distance Holder St/tZn, DIN 48833 A, 280 mm 290 002 299 BCT MOD BD 48 BCT-Protection Module BD, 48 V 919 645 152
AH FE RF V G Distance Holder St/tZn, reinf. version 300 mm 290 001 299 BCT MOD BD 5 BCT-Protection Module BD, 5 V 919 640 152
AH PAS RK Plastic cover, grey 563 015 297 BCT MOD BD 60 BCT-Protection Module BD, 60 V 919 646 152
AK 16 AS SAK MS Protective Conductor Terminal, -16 mm√ 308 411 275 BCT MOD BD HF 5 BCT-Protection Module BD HF, 5 V 919 670 154
AK 35 SN 18X3 GG Terminal for Busbar 919 015 277 BCT MOD BD HFD 24 BCT-Protection Module BD HFD, 24 V 919 675 155
AK FL40 PAS Terminal for Fl 40 563 222 297 BCT MOD BD HFD 5 BCT-Protection Module BD HFD, 5 V 919 671 155
AK RPA V2A Terminal St/tZn 563 169 300 BCT MOD BE 110 BCT-Protection Module BE, 110 V 919 627 150
AL EXFS L100 Connecting Lead for EXFS C1 923 026 294 BCT MOD BE 12 BCT-Protection Module BE, 12 V 919 621 149
AL EXFS L200 Connecting Lead for EXFS C1 923 036 294 BCT MOD BE 15 BCT-Protection Module BE, 15 V 919 622 149
AL EXFS L300 Connecting Lead for EXFS C1 923 046 294 BCT MOD BE 24 BCT-Protection Module BE, 24 V 919 623 149
AL2 10DA LSA Terminal Block 10TC LSA-PLUS 907 997 198 BCT MOD BE 30 BCT-Protection Module BE, 30 V 919 624 149
ALGA 5 Aluminium Enclosure IP65 906 055 279 BCT MOD BE 48 BCT-Protection Module BE, 48 V 919 625 149
ALGA 5 X Aluminium Enclosure IP65 for BCT 906 058 279 BCT MOD BE 5 BCT-Protection Module BE, 5 V 919 620 149
AMD DSM Surface-type Mounting Box for DSM 924 298 242 BCT MOD BE 60 BCT-Protection Module BE, 60 V 919 626 149
AR1 AZ Protector Cover, single piece, anthracite 924 340 120 BCT MOD BE C 12 BCT-Protection Module BE C, 12 V 919 661 151
AR1 EW Protector Cover, single piece, studio white 924 343 120 BCT MOD BE C 24 BCT-Protection Module BE C, 24 V 919 662 151
AR1 SI Protector Cover, single piece, silver 924 338 120 BCT MOD BE C 30 BCT-Protection Module BE C, 30 V 919 663 151
AR1 STW Covering Frame for DEHNsafe, studio white 924 328 105 BCT MOD BE C 5 BCT-Protection Module BE C, 5 V 919 660 151
AR1 TW Protector Cover, single-piece, titan white 924 336 120 BCT MOD MD 110 BCT-Protection Module MD, 110 V 919 547 160
AS I MOD AS-i Surge Protection Module 925 010 249 BCT MOD MD 12 BCT-Protection Module MD, 12 V 919 541 159
AS SAK 1000 V2A Anchor Bar, stainless steel, 1 m long 308 421 274 BCT MOD MD 15 BCT-Protection Module MD, 15 V 919 542 159
AW2 LSA Insertion Tool LSA-PLUS 907 994 197 BCT MOD MD 24 BCT-Protection Module MD, 24 V 919 543 159
BCT MOD MD 250 BCT-Protection Module MD, 250 V 919 549 160
BCT BAS BCT-Base Part 919 506 164 BCT MOD MD 30 BCT-Protection Module MD, 30 V 919 544 159
BCT BAS BCT-Base Part 919 506 162 BCT MOD MD 48 BCT-Protection Module MD, 48 V 919 545 159
BCT BAS BCT-Base Part 919 506 163 BCT MOD MD 5 BCT-Protection Module MD, 5 V 919 540 159
BCT BAS BCT-Base Part 919 506 160 BCT MOD MD 60 BCT-Protection Module MD, 60 V 919 546 159
BCT BAS BCT-Base Part 919 506 161 BCT MOD MD EX 24 BCT-Protection Module MD Ex, 24 V 919 580 258
BCT BAS BCT-Base Part 919 506 158 BCT MOD MD EX 30 BCT-Protection Module MD Ex, 30 V 919 581 258
BCT BAS BCT-Base Part 919 506 159 BCT MOD MD HF 5 BCT-Protection Module mD HF, 5 V 919 570 161
BCT BAS BCT-Base Part 919 506 156 BCT MOD MD HFD 24 BCT-Protection Module MD HFD, 24 V 919 575 162
BCT BAS BCT-Base Part 919 506 157 BCT MOD MD HFD 5 BCT-Protection Module MD HFD, 5 V 919 571 162
BCT BAS BCT-Base Part 919 506 154 BCT MOD MD HFD EX 6 BCT-Protection Module MD HFD EX, 6 V 919 583 259
BCT BAS BCT-Base Part 919 506 155 BCT MOD MD TC N BCT-Protection Module MD TC N, 250 V 919 552 163
BCT BAS BCT-Base Part 919 506 152 BCT MOD ME 110 BCT-Protection Module ME, 110 V 919 527 157
BCT BAS BCT-Base Part 919 506 153 BCT MOD ME 12 BCT-Protection Module ME, 12 V 919 521 156
BCT BAS BCT-Base Part 919 506 150 BCT MOD ME 15 BCT-Protection Module ME, 15 V 919 522 156
314 www.dehn.de
TYPE / PRODUCT INDEX
Type Product Part No. Page Type Product Part No. Page
BCT MOD ME 24 BCT-Protection Module ME, 24 V 919 523 156 DCO RK ME 12 DEHNconnect RK 12 V 919 920 168
BCT MOD ME 30 BCT-Protection Module ME, 30 V 919 524 156 DCO RK ME 24 DEHNconnect RK 24 V 919 921 168
BCT MOD ME 48 BCT-Protection Module ME, 48 V 919 525 156 DCO RK ME 48 DEHNconnect RK 48 V 919 922 168
BCT MOD ME 5 BCT-Protection Module ME, 5 V 919 520 156 DFL A 255 DEHNflex A 924 389 108
BCT MOD ME 60 BCT-Protection Module ME, 60 V 919 526 156 DFL D 255 DEHNflex D 924 395 109
BCT MOD ME C 12 BCT-Protection Module ME C, 12 V 919 561 158 DFL M 255 DEHNflex M 924 396 107
BCT MOD ME C 24 BCT-Protection Module ME C, 24 V 919 562 158 DG 150 DEHNguard, 150 V 900 603 64
BCT MOD ME C 30 BCT-Protection Module ME C, 30 V 919 563 158 DG 150 FM DEHNguard FM, 150 V 900 623 65
BCT MOD ME C 5 BCT-Protection Module ME C, 5 V 919 560 158 DG 275 DEHNguard, 275 V 900 600 64
BCT MOD MY 250 BCT-Protection Module MY, 250 V 919 589 164 DG 275 FM DEHNguard FM, 275 V 900 620 65
BCT MOD PTS Test/Disconnection Plug for BCT 919 504 165 DG 320 DEHNguard, 320 V 900 605 64
BCT MOD PTS Test/Disconnection Plug for BCT 919 504 147 DG 320 FM DEHNguard FM, 320 V 900 625 65
BM 10DA Block Magazine 10 TC for DPL 10 G 907 212 196 DG 385 DEHNguard, 385 V 900 602 64
BS 1 50 DCO RK Quick Marking System for DCO RK 919 977 264 DG 385 FM DEHNguard FM, 385 V 900 622 65
BS 1 50 DCO RK Quick Marking System for DCO RK 919 977 175 DG 440 DEHNguard, 440 V 900 607 64
BS M10 PAS Fixing Set for EB 472 201 298 DG 440 FM DEHNguard FM, 440 V 900 627 65
BT 24 BUStector 925 001 247 DG 600 DEHNguard, 600 V 900 601 64
BVT AD 24 BLITZDUCTOR VT 24 V 918 402 181 DG 600 FM DEHNguard FM, 600 V 900 621 65
BVT GS 110 BLITZDUCTOR VT 110 V 918 403 179 DG 75 DEHNguard, 75 V 900 604 64
BVT ISDN BLITZDUCTOR VT 918 410 208 DG 75 FM DEHNguard FM, 75 V 900 624 65
BVT KKS ALD 75 BLITZDUCTOR VT 918 420 183 DG IT 500 DEHNguard IT, 500 V 900 516 59
BVT KKS ALD SN BLITZDUCTOR VT 918 404 185 DG IT 500 FM DEHNguard IT FM, 500 V 900 546 59
BVT KKS APD 36 BLITZDUCTOR VT 918 421 184 DG T 150 DEHNguard T, 150 V 900 653 67
BVT KKS APD SN BLITZDUCTOR VT 918 405 186 DG T 150 FM DEHNguard T FM, 150 V 900 683 68
BVT MTTY 24 BLITZDUCTOR VT 918 407 178 DG T 275 DEHNguard T, 275 V 900 650 67
BVT RS485 5 BLITZDUCTOR VT RS485 918 401 180 DG T 275 FM DEHNguard T FM, 275 V 900 680 68
BVT TC 1 BLITZDUCTOR VT 918 411 209 DG T 275 VA DEHNguard T 275 VA, 275 V 900 659 74
BVT TTY 24 BLITZDUCTOR VT TTY 918 400 177 DG T 275 VA FM DEHNguard T 275 VA FM, 275 V 900 689 75
DG T 320 DEHNguard T, 320 V 900 652 67
DATA PRO 4TP DATA-Protector RJ45-4TP 909 955 284 DG T 320 FM DEHNguard T FM, 320 V 900 682 68
DB 1 255 DEHNbloc/1 900 111 43 DG T 385 DEHNguard T, 385 V 900 641 67
DB 1 255 H DEHNbloc/1 900 222 42 DG T 385 FM DEHNguard T FM, 385 V 900 691 68
DB 1 440 DEHNbloc/1 900 159 43 DG T 440 DEHNguard T, 440 V 900 655 67
DB 3 255 DEHNbloc/3 900 110 44 DG T 440 FM DEHNguard T FM, 440 V 900 685 68
DB NH00 255 DEHNbloc NH 900 260 45 DG T 600 DEHNguard T, 600 V 900 651 67
DBM 1 255 DEHNbloc Maxi 1, 25 kA 900 025 40 DG T 600 FM DEHNguard T FM, 600 V 900 681 68
DBM 1 255 L DEHNbloc Maxi 1 with operation indicator, 25 kA 900 026 40 DG T 75 DEHNguard T, 75 V 900 654 67
DBR 35 DEHNbridge, 35 A 900 121 121 DG T 75 FM DEHNguard T FM, 75 V 900 684 68
DBR 63 DEHNbridge, 63 A 900 122 121 DG T 75 VA DEHNguard T VA, 75 V 900 667 74
DCO RK D 5 24 DEHNconnect RK 5/24 V 919 986 174 DG T 75 VA FM DEHNguard T VA FM, 75 V 900 692 75
DCO RK E 12 DEHNconnect RK 12 V 919 987 173 DG TN 230 DEHNguard TN, 2-pole, 230 V 900 506 61
DCO RK E 24 DEHNconnect RK 24 V 919 988 173 DG TN 230 FM DEHNguard TN FM, 2-pole, 230 V 900 507 61
DCO RK E 48 DEHNconnect RK 48 V 919 989 173 DG TNC 230 400 DEHNguard TNC, 3-pole 900 510 56
DCO RK E 60 DEHNconnect RK 60 V 919 990 173 DG TNC 230 400 FM DEHNguard TNC FM, 3-pole 900 540 56
DCO RK MD 110 DEHNconnect RK 110 V 919 943 171 DG TNS 230 400 DEHNguard TNS, 4-pole 900 530 57
DCO RK MD 12 DEHNconnect RK 12 V 919 940 169 DG TNS 230 400 FM DEHNguard TNS FM, 4-pole 900 560 57
DCO RK MD 24 DEHNconnect RK 24 V 919 941 169 DG TT 230 DEHNguard TT, 2-pole 900 508 62
DCO RK MD 48 DEHNconnect RK 48 V 919 942 170 DG TT 230 400 DEHNguard TT, 4-pole 900 520 58
DCO RK MD EX 24 DEHNconnect RK 24 V EX 919 960 264 DG TT 230 400 FM DEHNguard TT FM, 4-pole 900 550 58
DCO RK MD HF 5 DEHNconnect RK MD HF, 5 V 919 970 172 DG TT 230 FM DEHNguard TT FM, 2-pole 900 509 62
DCO RK ME 110 DEHNconnect RK 110 V 919 923 168 DG Y PV 1000 DEHNguard Y PV 900 517 70
www.dehn.de 315
TYPE / PRODUCT INDEX
Type Product Part No. Page Type Product Part No. Page
DG Y PV 1000 FM DEHNguard Y PV 900 547 70 DPL 1 F ARE 5 Surge Protective Plug DPL 1 F, 5 V 907 127 193
DGA AG BNC DEHNgate 929 043 228 DPL 1 F ATP 5 Surge Protective Plug DPL 1 F, 5 V 907 144 190
DGA AG N DEHNgate 929 045 228 DPL 1 G A 110 Surge Protective Plug DPL 1 G, 110 V 907 220 188
DGA AG U DEHNgate 929 057 228 DPL 10 F ARE 110 Surge Protective Block DPL 10 F, 110 V 907 111 194
DGA F 1.6 5.6 DEHNgate 929 040 226 DPL 10 F ARE 12 Surge Protective Block DPL 10 F, 12 V 907 112 194
DGA FF TV DEHNgate 909 703 225 DPL 10 F ARE 24 Surge Protective Block DPL 10 F, 24 V 907 110 194
DGA G 1.6 5.6 DEHNgate 929 041 227 DPL 10 G2 110 LSA-Plus Technology, 10 TC -SET- 907 210 195
DGA G BNC DEHNgate 929 042 227 DPL 10 G3 110 LSA-Plus Technology, 10 TC 907 214 195
DGA G N DEHNgate 929 044 227 DPL 10 G3 110 FS LSA-Plus Technology, 10 TC FS 907 215 195
DGA G N 3 DEHNgate 929 058 227 DPM 255 DEHNport Maxi 900 104 47
DGA L4 7 16 B DEHNgate 929 048 230 DR 120 FML DEHNrail 120 FML, 120 V 901 101 98
DGA L4 7 16 S DEHNgate 929 047 230 DR 230 3N FML DEHNrail 230/3N FML, 230 V 901 130 100
DGA L4 N B DEHNgate 929 049 230 DR 230 FML DEHNrail 230 FML, 230 V 901 100 98
DGA LG 7 16 DEHNgate 929 046 229 DR 24 FML DEHNrail 24 FML, 24 V 901 104 98
DGP B 255 DEHNgap B 900 130 52 DR 48 FML DEHNrail 48 FML, 48 V 901 103 98
DGP B NH00 N 255 DEHNgap B/NH/n 900 269 53 DR 60 FML DEHNrail 60 FML, 60 V 901 102 98
DGP BN 255 DEHNgap B/n 900 132 52 DSA 230 LA DEHNsafe 924 370 105
DGP C T 255 DEHNgap C/T 900 133 72 DSFS Protective Spark Gap for roof supports 920 000 296
DGPM 255 DEHNgap Maxi 900 055 51 DSI DBM DEHNsignal DB M Remote Signalling Module 910 623 40
DISO 3 DEHNisola 910 600 302 DSI DBM DEHNsignal DB M Remote Signalling Module 910 623 37
DK 35 Feed-through Terminal, 35 mm2 900 699 122 DSI DV DEHNsignal 910 620 40
DLI ISDN I DEHNlink ISDN/I 929 024 213 DSI DV DEHNsignal 910 620 35
DLI TC 1 I DEHNlink TC 1 929 027 214 DSI DV DEHNsignal 910 620 30
DLI TC 2 I DEHNlink TC 2 929 028 214 DSI DV DEHNsignal 910 620 28
DLI TC BT DEHNlink BT 929 026 218 DSI DV DEHNsignal 910 620 29
DLI TC DK DEHNlink-Denmark 929 029 215 DSI DV 2P DEHNsignal, 2-pole 910 621 36
DLI TC ECO DEHNlink-Denmark 929 080 215 DSI DV 2P DEHNsignal, 2-pole 910 621 32
DLI TC ECO RJ12 DEHNlink-Denmark 929 081 215 DSI DV 2P DEHNsignal, 2-pole 910 621 33
DP 255 DEHNport, 255 V 900 100 49 DSI E DV DEHNsignal Reception Module 910 630 38
DP 440 DEHNport, 440 V 900 101 49 DSM ISDN SK SPD for telecomm. terminal equipment 924 270 244
DPA M CAT6 RJ45H 48 Patch cable with surge protection 929 110 206 DSM RJ45 4TP Shielded Surge Protective Data Socket 924 263 242
DPA M CAT6 RJ45S 48 Patch cable with surge protection 929 100 206 DSM TC 1 SK SPD for telecomm. terminal equipment 924 271 245
DPI CD EXD 24 M DEHNpipe 929 962 271 DSM TC 2 SK SPD for telecomm. terminal equipment 924 272 245
DPI CD EXD 24 N DEHNpipe 929 964 271 DSM TC DK SK SPD for Terminal Telecom. Equipment, Denmark 924 273 245
DPI CD EXI 24 M DEHNpipe 929 961 268 DSM TM SPD for Data Sockets 924 274 211
DPI CD EXI 24 N DEHNpipe 929 963 268 DV 2P TN 255 DEHNventil TN, 2-pole 900 371 32
DPI MD 24 M 2S DEHNpipe 929 941 252 DV 2P TT 255 DEHNventil TT, 2-pole 900 370 33
DPI MD EX 24 M 2 DEHNpipe 929 960 267 DV TNC 255 DEHNventil TNC, 3-pole 900 373 28
DPI ME 24 N A2G DEHNpipe 929 921 253 DV TNS 255 DEHNventil TNC, 4-pole 900 374 29
DPL 1 F ALE 110 Surge Protective Plug DPL 1 F, 110 V 907 126 192 DV TT 255 DEHNventil TT, 4-pole 900 375 30
DPL 1 F ALE 12 Surge Protective Plug DPL 1 F, 12 V 907 121 191
DPL 1 F ALE 15 Surge Protective Plug DPL 1 F, 15 V 907 122 191 EFK BCT EMC Spring Terminal for BCT 919 508 166
DPL 1 F ALE 24 Surge Protective Plug DPL 1 F, 24 V 907 123 191 EFK BCT EMC Spring Terminal for BCT 919 508 147
DPL 1 F ALE 48 Surge Protective Plug DPL 1 F, 48 V 907 124 192 EG NET PRO 19” Enclosure for NET Protector 929 034 204
DPL 1 F ALE 5 Surge Protective Plug DPL 1 F, 5 V 907 120 191 EG NET PRO 19” Enclosure for NET Protector 929 034 202
DPL 1 F ALE 60 Surge Protective Plug DPL 1 F, 60 V 907 125 192 EG NET PRO 19” Enclosure for NET Protector 929 034 203
DPL 1 F ARD 110 Surge Protective Plug DPL 1 F, 110 V 907 145 189 EG NET PRO 19” Enclosure for NET Protector 929 034 201
DPL 1 F ARD 250 Surge Protective Plug DPL 1 F, 250 V 907 146 189 EKS BCT Earth Terminal Set for BCT 919 505 166
DPL 1 F ARE 12 Surge Protective Plug DPL 1 F, 12 V 907 128 193 EKS BCT Earth Terminal Set for BCT 919 505 147
DPL 1 F ARE 15 Surge Protective Plug DPL 1 F, 15 V 907 129 193 EL2 38EA LSA Earth Conductor Block, 38-pole LSA-PLUS 907 993 198
DPL 1 F ARE 24 Surge Protective Plug DPL 1 F, 24 V 907 130 193 ER DPI M20 Set of Earthing Rings for DEHNpipe 929 996 254
316 www.dehn.de
TYPE / PRODUCT INDEX
Type Product Part No. Page Type Product Part No. Page
ES 10DA Earthing Busbar for 10 TC 907 998 196 KV FE UNI Wedge Connector St/tZn, with grid position 308 001 299
ES 10DA Earthing Busbar for 10 TC 907 998 192 KV M20 MS 10.5 EMC Cable Gland 929 984 269
ES 10DA Earthing Busbar for 10 TC 907 998 193 KV M20 MS 10.5 EMC Cable Gland 929 984 254
ES 10DA Earthing Busbar for 10 TC 907 998 190 KV M20 MS 8 EMC Cable Gland 929 985 269
ES 10DA Earthing Busbar for 10 TC 907 998 191 KV M20 MS 8 EMC Cable Gland 929 985 254
ES 10DA Earthing Busbar for 10 TC 907 998 188 KV S M20 MS 13 EMC Cable Gland 929 981 269
ES 10DA Earthing Busbar for 10 TC 907 998 189 KV S M20 MS 13 EMC Cable Gland 929 981 254
EXFS C1 Ex-Isolating Spark Gap 923 070 294 KV S M20 MS 9.5 EMC Cable Gland 929 982 269
EXFS C1 KU Ex-Isolating Spark Gap 923 071 295 KV S M20 MS 9.5 EMC Cable Gland 929 982 254
EXFS KU Ex-Isolating Spark Gap 923 019 292
EXFS L100 Ex-Isolating Spark Gap 923 060 291 LH R10 F40 AK 95 CU Conductor Holder/Terminal Cu, for EB 563 157 300
EXFS L200 Ex-Isolating Spark Gap 923 061 291 LH R10 F40 AK 95 ST Conductor Holder/Terminal St/tZn, for EB 563 150 300
EXFS L300 Ex-Isolating Spark Gap 923 062 291 LWL DSI Optical fibre 910 640 38
LWL ST DSI Plug for Optical Fibre 910 641 38
FAX PRO RJ11 FAX-Protector RJ11/12 909 950 286
FAX PRO RJ45 FAX-Protector RJ45 909 956 287 MB2 10 LSA Mounting Frame 10 DA LSA-PLUS 907 995 197
FAX PRO TAE FN FAX-Protector TAE/F 909 957 285 MMVK R16 R25 ST MAXI MV terminal, St/tZn 308 040 300
FBH 6 ST Tape Conductors with Pressure Plate 277 230 300 MMVK R16 R25 STBL MAXI MV terminal, St/bare 308 041 300
FBH 6 CU Tape Conductors with Pressure Plate 277 237 300 MS ALGA 5 X Mounting Set for Enclosures 906 059 280
FBH 6 V2A Tape Conductors with Pressure Plate 277 239 300 MS ALGA 5 X Mounting Set for Enclosures 906 059 261
FBH 11 ST Tape Conductors with Pressure Plate 277 240 300 MS DPA Mounting Set for DEHNpatch 929 199 206
FBH 11 CU Tape Conductors with Pressure Plate 277 247 300 MVS 1 4 Busbar single-phase, 4-pole 900 610 125
FBH 11 V2A Tape Conductors with Pressure Plate 277 249 300 MVS 1 57 Busbar single-phase, 57-pole 900 612 125
FS 15E 5 Fine Surge Protection Adapter FS 5 V 924 016 234 MVS 1 8 Busbar single-phase, 8-pole 900 611 125
FS 25E HS 12 Fine Surge Protection Adapter FS 12 V 924 018 235 MVS 2 7 16 Busbar 2-phase, 16-pole 900 616 125
FS 9E HS 12 Fine Surge Protection Adapter FS 12 V 924 019 233 MVS 2 7 22 Busbar 2-phase, 22-pole 900 619 126
FS 9E PB 6 Fine Surge Protection Adapter FS 6 V 924 017 232 MVS 3 57 Busbar 3-phase, 57-pole 900 613 126
MVS 3 6 Busbar 3-phase, 6-pole 900 595 126
GDT 230 Gas Discharge Tube 230 907 211 196 MVS 3 6 8 Busbar 3-phase, 8-pole 900 813 126
GDT 90 Gas Discharge Tube 90 V 919 502 165 MVS 4 56 Busbar 4-phase, 56-pole 900 614 126
GDT 90 Gas Discharge Tube 90 V 919 502 147 MVS 4 8 11 Busbar 4-phase, 11-pole 900 814 126
IF 1 Connection Bracket Type IF -SET- 923 011 294 NAK 35A 3 Mains Connection Box 35 A, 3-pole 900 968 92
IF 1 Connection Bracket Type IF -SET- 923 011 291 NAK 35A 3+1 Mains Connection Box 35 A, 3+1-pole 900 967 92
IF 3 Connection Bracket Type IF -SET- 923 016 294 NAK 35A 4 Mains Connection Box 35 A, 4-pole 900 966 92
IF 3 Connection Bracket Type IF -SET- 923 016 291 NAK 63A 3 Mains Connection Box 63 A, 3-pole 900 965 93
IGA 10 IP54 Insulating Enclosure, 10 mods. 900 309 123 NAK 63A 3+1 Mains Connection Box 63 A, 3+1-pole 900 969 93
IGA 11 IP54 Insulating Enclosure 11 mods. 902 486 124 NAK 63A 4 Mains Connection Box 63 A, 4-pole 900 964 93
IGA 6 IP54 Insulating Enclosure 6 mods. 902 485 124 NAK TAB 3 Mains Connection Box TAB, 3-pole 902 492 95
IS PAS M10 Insulator for EB (Industry) 472 210 298 NAK TAB 3+1 Mains Connection Box TAB, 3+1-pole 902 493 95
ISDN PRO ISDN-Protector 909 954 283 NAK TAB 4 Mains Connection Box TAB, 4-pole 902 494 95
ITAK EXI 30 IT Connection Box 989 406 261 NET PRO 4TP NET-Protector 4TP 929 035 201
NET PRO 4TP 30 NET-Protector 4TP 30 929 037 201
KB 10 DCO RK Jumper Bar for DEHNconnect RK 919 880 175 NET PRO E1 LSA NET-Protector E1 LSA 929 074 204
KB 5 DCO RK Jumper Bar for DEHNconnect RK 919 885 175 NET PRO ISDN NET-Protector ISDN, 5 V 929 067 202
KB 8 DCO RK Jumper Bar for DEHNconnect RK 919 888 175 NET PRO ISDN LSA NET-Protector ISDN LSA, 5 V 929 068 202
KFSU Ex-Isolating Spark Gap 923 021 289 NET PRO LSA 4TP NET-Protector/LSA-PLUS/4TP 929 036 201
KS 198 PAS Terminal Bar, brass, 198 mm long 563 016 297 NET PRO TC 1 NET-Protector TC1, 110 V 929 069 203
KS 398 PAS Terminal bar, brass, 398 mm long 563 017 297 NET PRO TC 1 LSA NET-Protector TC 1 LSA, 110 V 929 070 203
KS 798 PAS Terminal bar, brass, 798 mm long 563 018 297 NET PRO TC 2 NET-Protector TC 2, 110 V 929 071 203
KV FE R10 Wedge Connector St/tZn, Rd 10 308 010 299 NET PRO TC 2 LSA NET-Protector TC 2 LSA,+B433 110 V 929 072 203
www.dehn.de 317
TYPE / PRODUCT INDEX
Type Product Part No. Page Type Product Part No. Page
NF 10 Mains Filter 10 A 912 254 101 SA KRF 94 V2A Contact Force Spring for shield connection 919 038 278
NSM PRO AZ NSM-Protector DELTA profile, anthracite 924 339 120 SAK 10 AS V4A Shielding Terminal, stainless steel, Rd 5-10 308 403 274
NSM PRO EW NSM-Protector DELTA profile, studio white 924 342 120 SAK 11 SN MS Shielding Terminal 5-B42211 919 011 276
NSM PRO SI NSM-Protector DELTA profile, silver 924 337 120 SAK 14 AS V4A Shielding Terminal, stainless steel, Rd 8-14 308 404 274
NSM PRO TW NSM-Protector DELTA profile, titan white 924 335 120 SAK 18 AS V4A Shielding Terminal, stainless steel, Rd 13-18 308 405 274
NT PRO NT-Protector 909 958 282 SAK 21 AS V4A Shielding Terminal, stainless steel, Rd 17-21 308 406 274
SAK 26 AS V4A Shielding Terminal, stainless steel, Rd 19-26 308 407 274
P2 Impulse Meter P2 910 502 303 SAK 33 AS V4A Shielding Terminal, stainless steel, Rd 25-33 308 408 274
PA CT Test Adapter PA 910 506 301 SAK 6,5 SN MS Shielding Terminal round wire 1,5-6,5 919 010 276
PA DPL Test Adapter PA 910 505 301 SB PAS RK Bar holder, plastic, grey 563 014 297
PA KT Test Adapter PA 910 504 301 SF PRO SF-Protector 909 820 116
PAS 10AK ST UNI Equipotential Bonding Bars 472 000 298 SFL PRO SFL-Protector 912 260 118
PAS 10RK Earthing Busbar 563 010 297 SH 18X3 K Bar Holder, plastic 919 014 277
PAS 11AK Earthing Busbar 563 200 297 SH1 18X3 ST Bar Holder, steel 919 012 277
PAS 14RK Earthing Busbar 563 030 297 SH2 18X3 ST Bar Holder ISO 919 013 277
PAS 2AP 10 ST Earthing Busbar 472 023 299 SKB 19 9M SW Selfbonding Rubber Tape 919 030 278
PAS 2AP 10 V2A Earthing Busbar 472 109 299 SLK 16 PE Terminal 910 099 280
PAS 3AP 10 ST Earthing Busbar 472 022 299 SN 18X3 CU 1000 Busbar, tinned 919 016 276
PAS 3AP 10 V2A Earthing Busbar 472 119 299 SPS PRO SPS-Protector 912 253 103
PAS 4AP 10 ST Earthing Busbar 472 024 299 ST AS SAK K Bar Support, plastic 308 425 275
PAS 4AP 10 V2A Earthing Busbar 472 129 299 STC 230 STC Surge Protection Module 924 350 111
PAS 6AP 10 ST Earthing Busbar 472 021 299 T 150 DGT Surge Protection Module, 150 V 900 673 68
PAS 6AP 10 V2A Earthing Busbar 472 139 299 T 150 DGT Surge Protection Module, 150 V 900 673 67
PAS 6RK OH Earthing Busbar 563 105 298 T 275 DGT Surge protection Module, 275 V 900 670 68
PAS 7RK UP Earthing Busbar 563 103 298 T 275 DGT Surge protection Module, 275 V 900 670 67
PAS 9AK Earthing Busbar 563 050 297 T 275 DGT Surge protection Module, 275 V 900 670 62
PAS 9RK Earthing Busbar 563 020 297 T 275 DGT Surge protection Module, 275 V 900 670 61
PAS BW 8AP M10 CU Earthing Busbar 472 257 298 T 275 DGT Surge protection Module, 275 V 900 670 58
PAS I 10AP M10 CU Earthing Busbar 472 217 298 T 275 DGT Surge protection Module, 275 V 900 670 56
PAS I 10AP M10 V2A Earthing Busbar 472 219 298 T 275 DGT Surge protection Module, 275 V 900 670 57
PAS I 12AP M10 CU Earthing Busbar 472 237 298 T 320 DGT Surge Protection Module, 320 V 900 672 68
PAS I 12AP M10 V2A Earthing Busbar 472 239 298 T 320 DGT Surge Protection Module, 320 V 900 672 67
PAS I 6AP M10 CU Earthing Busbar 472 207 298 T 385 DGT Surge Protection Module, 385 V 900 679 68
PAS I 6AP M10 V2A Earthing Busbar 472 209 298 T 385 DGT Surge Protection Module, 385 V 900 679 67
PAS I 8AP M10 CU Earthing Busbar 472 227 298 T 440 DGT Surge Protection Module, 440 V 900 675 70
PAS I 8AP M10 V2A Earthing Busbar 472 229 298 T 440 DGT Surge Protection Module, 440 V 900 675 68
PM 10 PM 10 Arrester Test Unit 910 510 301 T 440 DGT Surge Protection Module, 440 V 900 675 67
T 600 DGT Surge Protection Module, 600 V 900 671 68
RK 16 PAS Modular Terminal, -16 mm2 for EB 563 011 297 T 600 DGT Surge Protection Module, 600 V 900 671 67
RK 95 PAS Modular Terminal, 16-95 mm2 for EB 563 013 297 T 600 DGT Surge Protection Module, 600 V 900 671 59
RK FL30 PAS Modular Terminal, flat strip -30 mm for EB 563 012 297 T 75 DGT Surge Protection Module, 75 V 900 674 77
RK FL40 PAS Modular Terminal, flat strip -40 mm for EB 563 019 297 T 150 DGT Surge Protection Module, 150 V 900 673 77
T 275 DGT Surge protection Module, 275 V 900 670 77
S PRO S-Protector+B247 909 821 115 T 320 DGT Surge Protection Module, 320 V 900 672 77
SA KRF 10 V2A Contact Force Spring for shield connection 919 031 278 T 385 DGT Surge Protection Module, 385 V 900 679 77
SA KRF 15 V2A Contact Force Spring for shield connection 919 032 278 T 440 DGT Surge Protection Module, 440 V 900 675 77
SA KRF 22 V2A Contact Force Spring for shield connection 919 033 278 T 75 DGT Surge Protection Module, 75 V 900 674 68
SA KRF 29 V2A Contact Force Spring for shield connection 919 034 278 T 75 DGT Surge Protection Module, 75 V 900 674 67
SA KRF 37 V2A Contact Force Spring for shield connection 919 035 278 T C 255 TC Protection Module, 255 V 900 134 77
SA KRF 50 V2A Contact Force Spring for shield connection 919 036 278 T C 255 TC Protection Module, 255 V 900 134 72
SA KRF 70 V2A Contact Force Spring for shield connection 919 037 278 T C 255 TC Protection Module, 255 V 900 134 62
318 www.dehn.de
TYPE / PRODUCT INDEX
Type Product Part No. Page Type Product Part No. Page
T C 255 TC Protection Module, 255 V 900 134 58 V NH00 280 VNH Surge Arrester, Size 00 900 261 81
TFS Isolating Spark Gap 923 023 289 V NH00 280 FM VNH FM Surge Arrester, Size 00 900 263 82
TL2 10DA LSA Disconnection Modules 10 TC LSA-PLUS 907 996 198 V NH1 3 280 VNH Surge Arrester, Sizes 1-3 900 265 83
TV PRO TV-Protector 909 921 288 VA NH00 280 VANH Surge Arrester, Size 00 900 262 84
VA NH00 280 3 IG VANH Surge Arrester in Enclosure 902 385 88
UGKF B L SPD for Comupter Systems 929 017 221 VA NH00 280 3 IG FM VANH FM Surge Arrester in Enclosure 902 375 89
UGKF BNC SPD for Comupter Systems 929 010 220 VA NH00 280 4 IG VANH Surge Arrester in Enclosure 902 386 88
UGKF N L SPD for Comupter Systems 929 012 222 VA NH00 280 4 IG FM VANH FM Surge Arrester in Enclosure 902 376 89
USD 15 V11 S B Cable Adapter 924 051 238 VA NH00 280 FM VANH FM Surge Arrester, Size 00 900 264 85
USD 15 V11 S KB Cable Adapter 924 050 238 VA NH1 3 280 VANH 280, Sizes 1-3 900 266 86
USD 25 TTY B KS Cable Adapter 924 047 240 VAV 1000 VAV Surge Arrester 901 000 79
USD 25 TTY B S Cable Adapter 924 048 240 VC 280 2 Mains Surge Protection Module, 2-pole 900 471 113
USD 25 V24 HS S B Cable Adapter 924 046 239 VK A R22 F40 STBL Connection Clamp St/bare 308 030 300
USD 25 V24 HS S KB Cable Adapter 924 045 239 VK A UNI ST Connection Clamp St/tZn 308 025 300
USD 25 V24 S B Cable Adapter 924 041 239 VK A UNI V2 ST Connection Clamp St/tZn 308 026 300
USD 25 V24 S KB Cable Adapter 924 040 239 VK EH R10 F30 ST Connection Clamp St/tZn 308 120 300
USD 9 V24 S B Cable Adapter 924 061 237 VK EH R10 F30 V2A Connection Clamp StSt (V2A) 308 129 300
USD 9 V24 S KB Cable Adapter 924 060 237
ZAP STW Central Covering Plate for DEHNsafe 924 329 105
www.dehn.de 319
Lightning Protection
Surge Protection
Safety Equipment
DEHN + SÖHNE
Hans-Dehn-Str. 1
Postfach 1640
92306 Neumarkt
Germany