Regarding the calculation of wind load, we have some following comments :

1. Calculation report CA-X-0001 is for Wind load calculation.


2. Quite conservative to consider one height for different parts of main building. Suggest a seperate wind load
calculation for North Pavilion 5 where large span of Panel installed.
MAC Roofing

Calculations
CALCULATION
SUBMISSION
CONTRACT & SUBMISSION DETAILS:

Project Name: National Rehabilitaion Centre - Loughborough


Project Number: 59319
Building Reference: Linear Hub, Energy Centre, Refuse Compound & Utility Hub

Revision Number: P01

System Name: Calculations - Wind Loads

Client: SRM
From: Ken Basnett
Date: 05-Feb-24
Recipient: Lisa Sanders
Response Required By: 12-Feb-24

Name Organisation
Chris Cahill MAC
Copies:
Paul Webb MAC
Jennifer Heaton MAC

Document No.: NRC-MAC-XX-XX-CA-X-0001


Status: S3 – Fit for Internal Review & Comment
CALCULATION
SUBMISSION
WIND LOADS

CONTENTS:

1. Site Locations of Buildings

2. Calculations - Wind Loads


Calculation
Submission

Site Locations of Buildings


LOCATIONS
SUMMARY
Calculation
Submission

Calculations

Wind Load
Document Ref: 59319-MAC-XX-CA-S-DN01

Project: National Rehabilitation Centre Job No. 59319

Description: DESIGN NOTE 02 – Wall Wind Loads Page./rev: 1 /P01


Address: Unit 1, Tel: 0151 346 2670
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral,
CH62 3PT
email: admin@macroofing.com
Director: Terry Cavanagh
Calc. by: JB Date: 14/09/2023 Chk'd by: AC Date: 14/09/2023

20/01/2021
Wind Loads Brief

This Design Note aims to provide a summary of the wall wind loadings applicable to the National Rehabilitation
Centre.

Energy Centre

Building Data:
Address National Rehabilitation Centre, Stanford on Soar, Loughborough
Post Code LE12 5QW
N. G. Coordinates SK560240
Altitude 84.2m
Topology influence No
Height of the building 7.65m
Roof type Flat Roof With Parapets
Parapet Yes – 3m

Results
Peak Velocity Pressure qp: 0.742 kN/m²

Table 1 - Cpe and Wind Loads Table for Energy Centre Walls

Zone Cpe Cpi Max Load


kN/m2
Suction -1.200 -1.039
F
Pressure +0.703 +0.744
Suction -0.800 (-0.3 / 0.2) -0.742
G
Pressure +0.703 +0.744
Suction -0.500 -0.519
H
Pressure +0.703 +0.744
Document Ref: 59319-MAC-XX-CA-S-DN01

Project: National Rehabilitation Centre Job No. 59319

Description: DESIGN NOTE 02 – Wall Wind Loads Page./rev: 2 /P01


Address: Unit 1, Tel: 0151 346 2670
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral,
CH62 3PT
email: admin@macroofing.com
Director: Terry Cavanagh
Calc. by: JB Date: 14/09/2023 Chk'd by: AC Date: 14/09/2023

20/01/2021
Main Building

Building Data:
Address National Rehabilitation Centre, Stanford on Soar, Loughborough
Post Code LE12 5QW
N. G. Coordinates SK560240
Altitude 84m Quite conservative to consider one height for
Topography Influence No different parts of the main building. Suggest a
Height of the building 15.7m seperate wind load calculation for North Pavilion
Roof type Flat Roof With Parapets 5 where large span of Panel installed.
Parapet Yes – 200mm / 250mm / 1400mm

Results
Peak Velocity Pressure qp: 0.886

Zone Cpe Cpi Max Load


kN/m2
Suction -1.200 -1.240
F
Pressure +0.700 +0.886
Suction -0.800 (-0.3 / 0.2) -0.886
G
Pressure +0.700 +0.886
Suction -0.500 -0.620
H
Pressure +0.700 +0.886
Document Ref: 59319-MAC-XX-CA-S-DN01

Project: National Rehabilitation Centre Job No. 59319

Description: DESIGN NOTE 02 – Wall Wind Loads Page./rev: 3 /P01


Address: Unit 1, Tel: 0151 346 2670
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral,
CH62 3PT
email: admin@macroofing.com
Director: Terry Cavanagh
Calc. by: JB Date: 14/09/2023 Chk'd by: AC Date: 14/09/2023

20/01/2021
Refuse Compound

Building Data:
Address National Rehabilitation Centre, Stanford on Soar, Loughborough
Post Code LE12 5QW
N. G. Coordinates SK560240
Altitude 84m
Topography Influence No
Height of the building 3.46m
Roof type Flat Roof
Parapet Yes – 400mm

Results
Peak Velocity Pressure qp: 0.575 kN/m²

Table 2 - Cpe and Wind Loads Table for Refuse Compound Walls

Zone Cpe Cpi Max Load


kN/m2
Suction -1.200 -0.806
F
Pressure +0.610 +0.523
Suction -0.800 (-0.3 / 0.2) -0.575
G
Pressure +0.610 +0.523
Suction -0.500 -0.403
H
Pressure +0.610 +0.523
Document Ref: 59319-MAC-XX-CA-S-DN01

Project: National Rehabilitation Centre Job No. 59319

Description: DESIGN NOTE 02 – Wall Wind Loads Page./rev: 4 /P01


Address: Unit 1, Tel: 0151 346 2670
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral,
CH62 3PT
email: admin@macroofing.com
Director: Terry Cavanagh
Calc. by: JB Date: 14/09/2023 Chk'd by: AC Date: 14/09/2023

20/01/2021
Utility Hub

Building Data:
Address National Rehabilitation Centre, Stanford on Soar, Loughborough
Post Code LE12 5QW
N. G. Coordinates SK560240
Altitude 85.685
Topology influence No
Height of the building 3.45m
Roof type Flat Roof
Parapet Yes – 400mm

Results
Peak Velocity Pressure qp: 0.576 kN/m²

Table 3 - Cpe and Wind Loads Table for Utility Hub Walls

Zone Cpe Cpi Max Load


kN/m2
Suction -1.200 -0.807
F
Pressure +0.714 +0.584
Suction -0.800 (-0.3 / 0.2) -0.575
G
Pressure +0.714 +0.584
Suction -0.500 -0.403
H
Pressure +0.714 +0.584

Figure 1 - General Cpe and Wind Load Zones for Walls


Document Ref: 59319-MAC-XX-CA-S-DN01

Project: National Rehabilitation Centre Job No. 59319

Description: DESIGN NOTE 02 – Wall Wind Loads Page./rev: 5 /P01


Address: Unit 1, Tel: 0151 346 2670
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral,
CH62 3PT
email: admin@macroofing.com
Director: Terry Cavanagh
Calc. by: JB Date: 14/09/2023 Chk'd by: AC Date: 14/09/2023

Parapet Loads 20/01/2021

All parapets are with return corners and have a solidity of 1 – From EN 1991-1-4:2005 Table 7.9

Energy Centre:

Peak Velocity Pressure qp: 0.742 kN/m²

Zone Cp,net Max Load


(kN/m2)
A 2.1 1.558
B 1.8 1.336
C 1.4 1.039
D 1.2 0.890

Main Building
Peak Velocity Pressure qp: 0.886
Zone Cp,net Max Load
(kN/m2)
A 2.1 1.861
Conservative value for lower B 1.8 1.595
C 1.4 1.240
levels of parapets at North/South D 1.2 1.063
Pavilion
Refuse Compound

Peak Velocity Pressure qp: 0.575 kN/m²

Zone Cp,net Max Load


(kN/m2)
A 2.1 1.208
B 1.8 1.035
C 1.4 0.805
D 1.2 0.690

Utility Hub

Peak Velocity Pressure qp: 0.576 kN/m²

Zone Cp,net Max Load


(kN/m2)
A 2.1 1.210
B 1.8 1.037
C 1.4 0.806
D 1.2 0.691
Document Ref: 59319-MAC-XX-CA-S-DN01

Project: National Rehabilitation Centre Job No. 59319

Description: DESIGN NOTE 02 – Wall Wind Loads Page./rev: 6 /P01


Address: Unit 1, Tel: 0151 346 2670
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral,
CH62 3PT
email: admin@macroofing.com
Director: Terry Cavanagh
Calc. by: JB Date: 14/09/2023 Chk'd by: AC Date: 14/09/2023

20/01/2021

Figure 2 - Dimensions of the zones are applicable to all parapet corners (h* parapet height)
Document Ref: 59319-MAC-XX-CA-S-DN01

Project: National Rehabilitation Centre Job No. 59319

Description: DESIGN NOTE 02 – Wall Wind Loads Page./rev: 7 /P01


Address: Unit 1, Tel: 0151 346 2670
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral,
CH62 3PT
email: admin@macroofing.com
Director: Terry Cavanagh
Calc. by: JB Date: 14/09/2023 Chk'd by: AC Date: 14/09/2023

Design Check 20/01/2021


This design check is to confirm the Energy Centre and Main Building are suitable for the Paroc AST S 300mm Panels. Due to
the large parapets on these buildings, where the panels will also be installed, parapet loads have been considered.

Energy Centre:

Largest Wall Span = 4.4m

Restance Rd for this span = 2.7kN/m2

−1.039kN/m2× 1.5 = −1.559kN/m2< 2.7kN/m2 ∴ 𝑃𝑎𝑠𝑠

Parapet Height = 3.25m

Resistance Rd for this span = 3.7kN/m2

1.558kN/m2× 1.5 = 2.337kN/m2< 3.7kN/m2∴ 𝑃𝑎𝑠𝑠


Suggest seperate calculations for Panel at different
Main Building: Blocks. Particular large span panel at North Pavilion 5
and Double span panel at Linear Hub above the level 02.
Largest Wall Span = 4.25m Temperature and deflection effect need to be verified.
De-lamination issue of the external skin due to the
Resistace Rd for this span = 2.8kN/m2 Cembrit Panel loading should be assessed.
−1.240 × 1.5 = −1.860kN/m2< 2.8kN/m2 ∴ 𝑃𝑎𝑠𝑠

As the parapet for this building is 1.4m, it can be conservatively assumed that the resistance Rd would be 5.5kN/m2

2.792kN/m2< 5.5kN/m2∴ 𝑃𝑎𝑠𝑠

As the support width is 50mm, the bottom line is used to attain values from the graph below:

Figure 3 - Paroc AST S 300mm Span/Resistance Graph

You might also like