Figure 5: Design of capping sheet to be reviewed againts top 'HAT' brakets spacing 750mm as specified in MAC drawing 500004

Document Ref: NRC-MAC-XX-XX-CA-X-0005 - P01


59319-MAC-XX-CA-S-DN08_P01
S3-Fit for Internal Review and Comment Job No. 59319
Project: National Rehabilitation Centre – North and South Pavilions

Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 1 /P01


Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

CONTENTS

INTRODUCTION ............................................................................................................................................................................ 2
1 MODEL PARAMETERS AND SET-UP ....................................................................................................................................... 2
2 BRACKET FIXINGS CAPACITY CHECK .................................................................................................................................... 3
3 TOP HAT BRACKET CHECK ..................................................................................................................................................... 7
3.1 STRESS ............................................................................................................................................................................... 8

3.2 STRAIN................................................................................................................................................................................. 8

3.3 DEFLECTION ..................................................................................................................................................................... 10

3.4 BUCKLING CHECK ............................................................................................................................................................ 10

4 CAPPING SHEET CHECK ........................................................................................................................................................ 11


4.1 STRESS ............................................................................................................................................................................. 12

4.2 STRAIN............................................................................................................................................................................... 12

4.3 DEFLECTION ..................................................................................................................................................................... 13

5 VHB TAPE AT CONTACT FACES ............................................................................................................................................ 14


CONCLUSION ............................................................................................................................................................................. 15

APPENDIX…………………………………………………………………………………………………………………………….…16
59291-MAC-XX-SK-S-0007_P01…………………………………………………………………..…………………………...…...17
TAPCON_ xtrem LT HFL min. anchorage 8x70/25-5…….…………….………………………………………………………..…18
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 2 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

INTRODUCTION
This design note aims to provide a calculation for the parapet capping sheet, capping support bracket, and associated
fixings. It is recommended to read this report in conjunction with the following documents:

 59319-MAC-XX-CA-S-DN02_P01 Where is this document?


 59291-MAC-XX-SK-S-0007_P01
 TAPCON_ xtrem LT HFL min. anchorage 8x70/25-5

The capping and the bracket will be analysed using RFEM analysis software, using non-linear finite element analysis and
the relevant Eurocodes.
The fixing loads will be calculated using a Robot stick model and iExpert Spit software to account for eccentrically applied
loadings and checked in accordance with relevant Eurocodes and associated National Annexes and manufacturers
published data.

1 MODEL PARAMETERS AND SET-UP


The site dynamic pressure qp was determined in the wind load calculations using METSPEC14 software and shown to be
qp= 0.886 kN/m2 (59319-MAC-XX-CA-S-DN02)

The worst-case wind Cpe value for the parapets was found to be 2.1. The highest wind load on the parapets will be:
W = cpe x qp
W = 2.1 x 0.886kN/m2 = 1.86 kN/m2

The dead load of the MAC aluminum capping will be 0.065kN/m2


The worst case capping size was found to be 821mm.

The outline of the parapet, capping and fixings can be seen in the diagram below:
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 3 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

Brackets spacing 750mm shown


in MAC 500004 drg.
Is plywood weight
included in calculation?

Figure 1 – Parapet and Capping Layout

2 BRACKET FIXINGS CAPACITY CHECK

TAPCON xtrem LT HFL min. anchorage 8x70/25-5, 1.5mm DX51D Galv Steel top hat bracket at 600cc to concrete.

The fixings reactions were calculated using a stick model in ROBOT to account for eccentricity.

DL1 = 0.065kN/m2 x 0.6m = 0.039 kN/m


W1 = 1.86 kN/m2 x 0.6m = 1.12 kN/m
W2 = 1.86 kN/m2 x 0.6m = 1.12 kN/m
LL1 = 0.6kN/m2 x 0.6m = 0.36 kN/m Is plywood weight included in
LL2 = 0.9 kN calculation?

should be 0.75m as shown in


MAC drg. 500004
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 4 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

Figure 2 - Application of loads

Multiple load cases were taken into account, however, it was found that the reaction forces for 1.35DL + 0.75W2 + 1.5LL2
was governing for pull out forces on the fixing, which can be seen below:
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 5 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

Figure 3 - Maximum support reactions

Reactions obtained from the Robot software were applied to iExpert software. Results for the TAPCON xtrem LT HFL min.
anchorage 8x70/25-5 are shown in the diagram below:

Should Nz be positive?

Figure 4 - Fixings and top hat layout iExpert


Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 6 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

Table 1 - Loads on anchors (iExpert)

Figure 5 - iExpert Spit Fixing Layout and Utilisation for TAPCON xtrem LT HFL min. anchorage 8x70/25-5

Pull through resistance:


For screws subject to static and wind loads:
Fp,Rd = 0.5 x dw x t x fu x ym2
Fp,Rd = 0.5 x 16* x 1.5 x 270** / 1.25 = 2592N or 2.592kN
*Assuming 16mm head diameter
**DX51D Fu = 270

Table 2 - Fixing Utilisation Table

Max Applied Top Layer Base Layer Max Tension Utilisation


Tension Fixing Thickness Thickness Capacity (%)
(kN) (mm) (mm) (kN)
2.01 TAPCON xtrem LT HFL 1.5 Concrete 2.592 90.0%*
min. anchorage 8x70/25-
5

*Highest utilisaton from IExpert software.


Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 7 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

3 TOP HAT BRACKET CHECK


For non-linear finite element analysis a bilinear material model of DX51D steel was used. According to the
recommendations given EN 1993-1-5:2006, clause C.6 2(b), we assumed an elastoplastic material model with a nominal
plateau slope.
The material properties used in the model are shown in the figure below.

Figure 6 – Bilinear material model parameters

The following load combinations were created:

Figure 7 - List of load combinations


Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 8 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

Figure 8 – Application of wind load

3.1 STRESS
Althougth there is a slight upward slope to the stress-strain curve for the material after the elastic yield point, in reality the
governing criteria after this are always limited to the strain limit, therefore no stress evaluation against the Von-Misses
failure criterion is necessary.

3.2 STRAIN
Since we are using non-linear material properties, we need to check the maximum strain is within the requirements of BS
EN 1993-1-5:2006, Clause C.8(1) recommended maximum strain for non-linear FE analysis is 5%
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 9 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

Figure 9 – Worst-case overall strain results in the entire model (RFEM)

As shown above, the equivalent total strain is 19.6‰ or 1.96% which is less than the allowable 5% strain limit, hence OK.
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 10 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

3.3 DEFLECTION
The worst-case deflection at the serviceability limit state is given below:

540mm

Figure 10 - Worst case deflection (RFEM)

The allowable deflection limit may be taken as span/200 (span/100 for cantilervers) = 540/100 = 5.4mm which is greater
than 3.05mm, hence OK.

3.4 BUCKLING CHECK


A review of the buckling capacity of the bracket was also undertaken. The results of which are presented below:

Figure 11 - Critical load factors

As can be seen from the above figure, the lowest [+ve] critical coefficient is 6.66 meaning that the applied can can be
multiplied by 7.057 times before reaching the critical buckling load, hence OK
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 11 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

4 CAPPING SHEET CHECK


For non-linear finite element analysis, a bilinear material model of 1050-H14 aluminium was used. The material properties
used in the model are shown in the figure below.

Figure 12 - Bilinear material model parameters

Figure 13 - Application of wind load (pressure)


Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 12 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

=0.9kN over
200x200mm square

Figure 14 - Application of live point load

4.1 STRESS
Althougth there is a slight upward slope to the stress-strain curve for the material after the elastic yield point, in reality the
governing criteria after this are always limited to the strain limit, therefore no stress evaluation against the Von-misses
failure criterion is necessary.

4.2 STRAIN
Since we are using non-linear material properties, we need to check what the maximum strain is within the requirements.
According to BS EN 1999-1-5 Section 6.1.4 For design purposes, an ultimate plastic strain value equal to 10(fo/E) can be
assumed.
For aluminium 1050-H14:
X elimit = 10 x (105/70000) = 0.015 or 1.5%
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 13 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

Figure 15 - Worst-case strain results in the entire model (RFEM)

As shown above, the equivalent total strain is 1.30 ‰ or 0.13% which is below the allowable 1.5% strain limit, hence OK.

4.3 DEFLECTION
The worst case deflection at the serviceability state is given below:

Figure 16 – Worst-case deflection

The allowable deflection limit may be taken as span/90 = 600mm / 90 = 6.6mm which is greater than 4.79 mm, hence OK.
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 14 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

5 VHB TAPE AT CONTACT FACES


To assist the design, VHB tape is used inbetween the coping and the bracket faces. The tape provides a way for the uplift
loads to be transferred between the coping panel and bracket.

The strength of 3M’s VHB tape from the 4910 range is 690kN/m2 for tension and 480kN/m2 for shear, under dynamic loads
(See 3M’s data sheet). The tapes are typically dispensed in 25mm wide rolls.

Hence the maximum allowable dynamic resistance per bracket will be:

Tension: Force x Area = 690kN/m2 x (0.025m x 0.821m) = 14.16kN


Shear: Force x Area = 480kN/m2 x (0.025m x 0.821m) = 9.85kN

Hence the maximum allowable dynamic resistance per bracket will be:

Tension (Factored): 1.5 x 1.86kN/m2 x 0.821m x 0.6m = 1.37kN < 14.16kN, Hence OK
Shear (Factored): 1.5 x 1.86kN/m2 x 0.1m x 0.6m = 0.17kN < 9.85kN, Hence OK
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 15 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

CONCLUSION
Parapet Bracket
Strain: applied strain / allowable strain = 1.96 / 5 x 100 = 39.2% < 100%, Hence OK
Deflection: applied deflection / allowable deflection = 3.05mm / 5.4mm x 100 = 56.5% <100%, Hence OK
The overall utilisation against buckling was:
Allowable critical coefficient / Applied critical coefficient = 1 / 6.66 x 100 = 15.0% < 100% hence OK

Capping Sheet
Strain: applied strain / allowable strain = 0.13 / 1.5 x 100 = 8.7% < 100%, hence OK
Deflection: applied deflection / allowable deflection = 4.79mm / 6.6mm x 100 = 72.6% < 100%, hence OK

Fixings
The overall utilisation of the TAPCON HFL min. anchorage 6x50/15 fixings is 90.0% < 100%, hence OK

VHB Tape
Tension: 1.37 / 14.16 x 100 = 9.7% < 100%, Hence OK
Shear: 0.17 / 9.85 x 100 = 1.7% < 100%, Hence OK
Document Ref: 59319-MAC-XX-CA-S-DN08_P01

Project: National Rehabilitation Centre – North and South Job No. 59319
Pavilions
Description: DESIGN NOTE 08 – Parapet Capping Page./rev: 16 /P01
Address: Unit 1, Tel: 0151 346 2670 Calculations
Lumina Business Park, Fax: 0151 334 0796
Bromborough, Wirral, email: admin@macroofing.com
CH62 3PT Director: Terry Cavanagh Calc. by: AC Date: 27/03/2024 Chk'd by: JB Date: 27/03/2024

APPENDIX
30x50x80x1.5mm
1 continuous length of 3M VHB DX51D galv. steel
4910 25mm wide tape between top hat bracket
capping sheet and bracket 30x50x80x1.5mm DX51D
galv. steel top hat bracket
A at 600cc

2mm 1050 H14


alum. capping

Locator fixing A-A

A
TAPCON xtrem LT
HFL min. anchorage
8x70/25-5
Ref : 3/26/2024 - 1:26:51 PM / Version 2023.12.07
Date : 3/26/2024
Page : 1/4

CALCULATION SHEET FOR SPIT ANCHORS


Company : Phone number :
Carried out by : Mail address :
Company : Project name : NRC
Contact name : Location :
Phone number : Fastening point :
Mail address :

Comment :

Recommended anchors
TAPCON XTREM LT HFL-A4 min. anchorage 8x70/25-5 Product Code: 058655
Effective embedment : 32 mm
ETA-22/0364 issued 2022/11/28

Base material
Concrete resistance : C25/30 - fck,cyl = 25 N/mm²
Cracking of concrete : Cracked concrete
Thickness of concrete : 200 mm
Reinforcement type : Wide concrete reinforcement
Edge reinforcement : No edge reinforcement

Conditions
Installation conditions : Dry concrete
Short term temperature : 40 °C
Long term temperature : 24 °C

Anchor plate
Thickness of part to be fixed : 2 mm
Recommended plate thickness : The base plate thickness has not been checked

Clearance diameter : 12 mm
Profile :
Profile position : Ex = 0 mm ; Ey = 0 mm
Stand-off : None

Design method : EN 1992-4 for static, quasi-static loading


Design Actions :

Action [kN] / [kNm] Action type

Combination 1 standard -2.09 0 0.09 0 -0.99 0

Specifications :
Static
Sustained Load : False
Ref : 3/26/2024 - 1:26:51 PM / Version 2023.12.07
Date : 3/26/2024
Page : 2/4

Geometry :

Calculation Hypothesis :
- The anchoring plate is assumed to be sufficient to resist deformation imposed by the load actions.
- Connection between profile and base plate has not been checked
- The calculation is done acc. to expert judgement, based on EN 1992-4

- SPIT can only be held responsible if the calculation examples exactly reflect the application and if the installation is carried out
according to the instruction given in the SPIT specifications. The calculation is correct for SPIT anchors only. The
contractor or specifier should make sure that the base material is able to support the loads especially in the case of a group of
anchors. SPIT cannot be held responsible if this software package is modified without its written approval.
Ref : 3/26/2024 - 1:26:51 PM / Version 2023.12.07
Date : 3/26/2024
Page : 3/4

Resulting anchors forces

Loads on anchors

Anchor Tensile Shear[x] Shear[y]


1 2.01 kN 0 kN 0.02 kN
2 2.01 kN 0 kN 0.02 kN
3 0.11 kN 0 kN 0.02 kN

4 0.11 kN 0 kN 0.02 kN

4.25 2.01 0 67.2

0.09 0.02

Utilization

Tension load Tension force [kN] Strength [kN]


Pull out failure 2.01 2.16 93.1
Concrete cone failure 4.25 7.75 54.8

Splitting failure 4.25 5.73 74.0


Steel failure 2.01 18 11.2

Shear load Shear force [kN] Strength [kN]


Concrete Edge failure 0.09 5.42 1.66
Pryout failure 0.09 39.03 0.23
Steel failure 0.02 10.8 0.21

Combined tension and shear loads

THE APPLICATION IS SAFE


Ref : 3/26/2024 - 1:26:51 PM / Version 2023.12.07
Date : 3/26/2024
Page : 4/4

INSTALLATION DATA

TAPCON XTREM LT HFL-A4 min. anchorage 8x70/25-5 Product Code: 058655


Effective embedment : 32 mm
ETA-22/0364 issued 2022/11/28
Effective embedment : 32 mm
Minimum thickness of base material : 80 mm
Hole diameter in the base material : 8 mm
Hole depth in the base material : 78 mm
Installation torque : 20.00 Nm
Base plate thickness : 2 mm
Profile family (section type) :
Clearance diameter : 12 mm

INSTALLATION Method