SPECTRA - Moulded case circuit breakers
Seal
For extra safety, access to connection terminals and to controls can be
locked off while at the same time retaining visibility.
Degree of protection
Use In front, in accordance with the NF C 20-010 standard:
- basic circuit-breaker: IP 2X (E 160)
Spectra circuit-breakers provide a solution for three performance levels: IP 3X (E 250 to E 1250)
- normal breaking capacity, type EN - fixed or withdrawable circuit-breaker, with terminal covers:
- High breaking capacity, type EH IP 3X
- Limiter circuit-breaker, type EL
By adding or replacing elements, it is possible to perform the following Note: the addition of electrical control units, rotary control handle, earth-
functions: leakage units or the use of withdrawable devices does not affect the
- earth leakage protection, protection offered by the circuit-breaker
- visible breaking isolation.
Temperature derating
The maximum normal current for a circuit-breaker depends on the ambient
Breaking capacity (according to IEC 947-2 at 415V) temperature in which it is placed.
Icu (kA) This is concerned with the temperature around the circuit-breaker:
- either the ambient temperature when the circuit-breaker is installed in the
open air
100 - or the air inside the box or casing which the circuit-breaker is encased.
The reference (test) temperature for all Spectra circuit-breakers is 400C.
EL EL EL EL Derating is not automatic, the rating plug must be selected according to the
160 250 400 630 ambient temperature around the circuit-breaker.
I
Installation
DOWNLINE
UPLINE
O
Spectra circuit-breakers can be mounted on all boards for industrial and
tertiary use. B
I
In particular, adapter accessories (plates, racks, ...) have been designed for DOWNLINE
integration within our Modula 400 boxes and Modula 4000 switchboards. 3
Circuit breaker models
Fixture Fixed
160 / 1250 • •
Spectra circuit-breakers, in the fixed or withdrawable versions, can be fixed
Withdrawable
on panels, girders or stanchions. • •
125 / 630
Mounting behind or against a door or panel requires no special effort. The
cut-out in the door or panel enables the control handle alone or all the Withdrawable type V
160 /1250 • •
displays and controls to be visible, as required.
Safety perimeter
Power source During breaking, all circuit breakers produce external agents (fragments,
gases, . . . ); in order to guarantee security during this phase, it is necessary
The power source can be connected either upline or downline of the Spectra to respect the safety distances indicated below.
circuit-breaker, and up to the maximum voltage for use (690V).
UPLINE
⇒
100
25
70
0 0 (1)
Note: forward
facing
safety distance = 0
I I
(1) 10 mm for:
O O - E 160 types H, L, EM
⇒
- E 400/630/800/1250 with
extensions or PAR
Accreditation/certification
IEC 947-2, EN 60 947.2, NF C 63 120,
UL 489, JIS, CSA, Bureau Véritas, Germanischer Lloyd,
Lloyd's Register of Shipping, RINA
SPECTRA - Moulded case circuit breakers
Spectra electronics
Spectra's secret in finding the correct protection lies in the combination of a
High performance electronic protection. very sensitive current sensor, a fast AD Converter unit and a
microprocessor specially designed for protection.
N L1 L2 L3
Activator
AD Converter
Processing
Sampler
4
unit
Curve 1: "over-protection" The Spectra electronic circuit breaker may receive two types of instructions:
- The rating plug, adjustable from 0.8 to 1 enables the adjustment of
protection againt overcurrent according to the maximum current
supported by the cable (Iz) and the operating current(Ie).
Curve 1 shows a current with a - Short-term (ST) and instantaneous (I) trip setting enables protection of
distortion of 10% due to cables against overloads and the protection of people against indirect
harmonic 5: contact, while taking into account the nature of the source.
- peak value: Ic = 110 A The same circuit breaker enables protection of lower power sources from
- deducted RMS value: short-circuits (alternator) or the protection of a load from a high inrush
I eff. = 110/√2= 78 A current (transformer).
- true RMS value Irms = 71 A One version, without the LT function, is intended for the protection of motors
A traditional circuit breaker (EM circuit-breaker).
would trip prematurely, resulting The fine tuning and precision of the ST setting enables discrimination
in a disruption of operations. between circuit breakers with LT settings close to each other.
In order to guarantee total protection of the installation, the two settings of
Curve 2: "under-protection" the circuit breaker are linked. Selection of LT protection automatically
defines the ST and instantaneous (I) setting ranges. This link precludes all
risk of "under-protection" in ST mode.
Curve 2 shows a current with a
20% distortion due to harmonic 3:
- peak value Ic = 85 A
- deducted RMS value:
I eff. = 85/√2= 60 A
- true RMS value: Irms = 71 A
A traditional electronic circuit
breaker would not trip for this
overload condition, resulting in
the risk of the cable or the load
being destroyed.
SPECTRA - Moulded case circuit breakers
Protection selection
In order to define the desired characteristics:
B
5
EN - EH - EL EN - EH - EL -EM
LT setting
defined by the rating pug Circuit breaker curve
EM type
Instantaneous setting
defined by I >
Ir 0.63 Iinst Iinst x Ir
B
6
Circuit breakers EN 160 EH 160 EL 160 EN 250 EH 250 EL 250 EN400 EH400 EL400
Rated current
Ith 400C (A) 160 160 160 250 250 250 400 400 400
Ith 500C (A) 160 160 160 235 235 235 400 400 400
Ith 600C (A) 160 160 160 215 215 215 400 400 400
Rated operating voltage Ue
AC 50/60Hz (V) 690 690 690 690 690 690 690 690 690
Rated insulation voltage Ui (V) 690 690 690 690 690 690 690 690 690
Ultimate short-circuit breaking capacity Icu
AC 50/60Hz 220/240V (kA) 65 130 200 65 130 200 65 130 200
380/415V (kA) 35 65 100 35 65 100 35 65 100
500V (kA) 25 40 50 25 40 50 25 40 50
660/690V (kA) 8 8 10 10 10 12 10 10 16
Service short-circuit breaking capacity Ics
AC 50/60Hz 220/240V (% Icu) 75 50 50 75 50 50 75 50 50
380/415V (% Icu) 75 50 50 75 50 50 75 50 50
500V (% Icu) 50 50 50 50 50 50 50 50 50
660/690V (% Icu) 50 50 50 50 75 75 50 50 50
Rated short-circuit making capacity Icm
220/240V (kA peak) 145 290 440 145 290 440 145 290 440
380/415V (kA peak) 75 145 220 75 145 220 75 145 220
Single pole IT system breaking capacity Ice
220/240V (% Icu) 50 50 50 50 50 50 50 50 50
380/415V (% Icu) 30 25 15 30 25 25 30 25 15
Rated impulse voltage Uimp (kV) 8 8 8 8 8 8 8 8 8
Operational category A A A A A A A A A
Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
Endurance
Mechanical ops. 15 000 15 000 15 000 15 000 15 000 15 000 10 000 10 000 10 000
Electrical ops. 4 000 4 000 4 000 4 000 4 000 4 000 3 000 3 000 3 000
Total fault elimination time (ms) 10 8 4 10 8 5 12 10 6
Degree of pollution 3 3 3 3 3 3 3 3 3
EM circuit breakers Motor protection
Rating plugs supplied with the appliance (non-
adjustable)
EM 160/32 to 630: Breaking capacities are
identical to those for the EL range EM 160/32 EM 160/63 EM 160/160 EM 250 EM 400
EM 800 to 1250: Breaking capacities are identical
to those for the EH range
Rating plugs Setting range: 0.8 to 1 x In
25A 80A 160A
32A 100A 200A
50A 125A 250A
63A 160A 320A
80A 200A 400A
100A 250A
125A
160A
SPECTRA - Moulded case circuit breakers
B
7
75 50 50 75 50 75 50
75 50 50 75 75 75 75
50 50 50 75 50 75 50
50 50 50 100 100 100 100
50 50 50 50 65 50 65
30 25 15 30 25 30 25
8 8 8 8 8 8 8
A A A A A A A
3-4 3-4 3-4 3-4 3-4 3-4 3-4
Functions
Circuit breakers EN 160 EH 160 EL 160 EN 250 EH 250 EL 250
Differential (adaptable casing) •(1) •(1) •(1) •(1) •(1) •(1)
According to selection of visible isolation(2) • • • • • •
(withdrawable & type V)
Motor protection (ST and I only) EM32/63/160 EM32/63/160 EM32/63/160 EM 250 EM 250 EM 250
Control accessories
Manual rotary • • • • • •
Electrical • • • • • •
Safety accessories
Terminal cover • • • • • •
Locking off by padlock • • • • • •
by lock • • • • • •
Installation /Connection
Fixed front connections FAV • • • • • •
appliance rear connections FAR • • • • • •
Withdrawable front connections DAV • • • • • •
appliance rear connections DAR • • • • • •
EN 400 EH 400 EL 400 EN 630 EH 630 EL 630 EN 800 EH 800 EN 1250 EH 1250
•(1) •(1) •(1) •(1) •(1) •(1) (1) (1) (1) (1)
EM 400 EM 400 EM 400 EM 630 EM 630 EM 630 EM 800 EM 800 EM 1250 EM 1250
• • • • • • • • • •
B
9
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
- - - - - - - - - -
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
SPECTRA - Moulded case circuit breakers
Operating curves
E 160 circuit breaker E 250 to E1250 circuit breakers
10000 10000
7 7
5 5
4 4
3 3
2 2
B 1000
7
1000
7
10 5 5
4 4
3 3
2 2
100 100
7 7
5 5
4 4
3 3
Operating time in seconds
10 10
7 7
5 5
4 4
3 3
MAX MAX
2 2
1 1
7 7
5 5
4 4
3 3
MIN MIN
2 2
0.1 MAX
0.1 MAX
7 7
5 5
4 4
3 3
2 2
0.01 0.01
1 2 3 4 5 6 7 8 910 2 3 1 2 3 4 5 6 7 8 910 2 3
110
E800/1250
B
0.2
H
11
ϕ=
100
The limiting capacity of a circuit
ude
breaker is the expression of the 90
plit
j
am
breaker's capacity, in the event of a 80
ed
short-circuit, to let no current
um
through that is greater than the 70
ass
assumed fault current.
um
N
60 E400/630
xim
Ma
H L
1 50
40 N
E250
This characteristic is expressed by H L
limiting curves. 30 N
E160
H
20 N
2 10
kA eff.
1: Icc unlimited peak 0 10 20 30 40 50 60 70 80 90 100
2: Icc limited peak (actual)
The great limiting capacity of Spectra circuit berakers is a result of the
optimal combination of: Thermal constraints limited as a function of the actual intensity of the
- a light moving part, reducing inertia, short-circuit
- a strong current loop, to generate maximum force of repulsion,
- a slot motor with strong electro-magnetic field to accelerate the opening of A² s
the contacts E800/1250
- contact materials combining good conductivity and high durability, H
- an arc chamber combining a high energy absorbtion capacity, speed of the
breaking of the arc and the cooling of the gasses. N E400/630
107 L
This combination has enabled an exceptional breaking capacity /volume H
ratio.
N
The use of Spectra limiter circuit-breakers enables a great reduction in
E250
stresses that normally develop during a short-circuit: H L
- Reduction in thermal constraints in conductors, increasing their life. N E160
106 H
- Reduction in mechanical constraints due to the reduction of the N
electrodynamic forces of repulsion between conductors, which reduces
the risk of deformation or rupture of the wiring
- Reduction in electro-magnetic effects.
The electro-magnetic field reduces and causes less damage to 105
neighbouring devices and sensors.
Rationalisation
Spectra limiter circuit breakers offer multiple advantages:
- reduction in the volume of boxes and cabinets, kA eff.
- reduction in logistic costs because of the smaller volume, 104
- possibility of connecting circuit breakers with smaller capacity downline. 1 10 30 50 70 100
SPECTRA - Moulded case circuit breakers
Rear:
- two terminals for remote control
Diagram
The protection of people and property provided by differential circuit
breakers with residual intensity measurement, is obtained by combining a The electronic board is powered from three phases: protection is
Spectra circuit breaker equipped with an ST voltmetric shunt release and a ensured even if one phase is lost .
differential block (MIR).
The MIR block can be adapted in situ, to the E 160, E 250, E 400 and 630
circuit breakers.
N L1 L2 L3
Presentation Characteristics
–
–
Modular box 4 modules - DIN 43880
Mounting on symmetrical rail (surface or flush)
Controlled network
alternative L.V.
AC
< 1000V
B
– Screw terminals for 2.5 mm2 wires 13
frequency 40 to 70Hz - 400Hz N.C.
– Front face setting
– Sealable transparent cover Detection principle measurement residual
current
core ratio 600/1 (optional 470/1)
Functions maximum current 500A - 1 s.
Isolation fault LED indication nominal impedance 100Ω
two changeover switches Current measurement
Pre-alarm 50% LED indication threshold 30mA at 3.4A
positive security one changeover switch pre-alarm 50% of the threshold
relay (not adjustable)
Fault reset by push-button threshold adjustm. 64 steps
(optional bistable relay) indicators 4 LEDs
System failure manual integrated test Power supply
external test frequency 40 to 400Hz
Core failure signal 'error' and tripping standard voltage 24 to 480V~ in 3 ranges
consumption 4VA
Performances Operating time adjustable on SHR 1110
Supply voltage V1 V2 adjustments 0.1 to 1.5 s. in 16 steps
version 1 24V~ 48V~ instantaneous 15 ms
version 2 110/127V~ 440/480V~ bypass if 30mA threshold
version 3 220/240V~ 380/415V~
Connection diagram
Contacts dry contacts Cores CITO - CITF
output 2 changeover + 1 NO Alarm 50%
– Ratio: 600/1 Core failure
breaking capacity 6A 250V, 1500VA max. – Connection by box type terminals for wires of Tripping
System failure
insulation 4kV eff. 2.5 mm2
Protection degree IP20 surface – Connection to earth leakage protection relays
IP42 flush using armoured cable with two insulated
conductors and the shortest possible cabling
Remarks (resistance < 30Ω)
1. Ensure cover conductors are centered
2. If the neutral is not out, enclose the 3 phases
3. Never allow the core to enclose the protection CT
conductor V1
4. Armoured cable obligatory for cable lengths V2
(SHR / core) ⊕ 5 m or for sensitive
TEST
settings ⊕ 1A
SPECTRA - Moulded case circuit breakers
Characteristics
MTS
B Alternating earth neutral network protected
Frequency
•
50 to 175Hz
14 Setting values fixed 0.03A Detection core mounting
adjustable 0.1 to 1A
On armoured cable
Time delay 0 to 500 ms (for 0.1 to 1A)
Out-going contacts 2 changeover contacts End box electrically
(2A/250V cos ϕ 0.3) isolated from its support
sensors
Display •
Test button •
Reset button •
Power Detection core
Frequency 50/60 Hz Passing diameter: 34, 55, 70, 100 mm
Flexible connection
AC 220/240V or 380/415V (shipped with MTS) common to cable's ring and
detection core ratio: fuse at the cable end box
Mounting - signal:
recessible into the bottom of the housing 34: 230/1
55: 200/1
For junction boxes
70: 200/1 Junction box
100: 280/1 electrically isolated
from its support
- test: input
34, 55, 70, 100: 200/1 output 2
sensor
Connection diagram sensors
output 1
220/240V 50/60Hz
380/415V 50/60Hz
3 4 6
Notes
0.5/1.5 mm2 1. Ensure conductors are centred in the core.
2. If the neutral is not out, enclose the 3 phases.
3. Never allow the protection conductor to be
enclosed by the core.
1
~ 2 12 11 14 22 21 24 3 4 5 6
SPECTRA - Moulded case circuit breakers
Electrical auxiliaries
General
BA bell alarms, AS auxiliary "ON/OFF" switches, ST voltmetric shunt
releases and UV undervoltage releases are common to all Spectra circuit
breakers,
e.g.: an AS auxiliary "ON/OFF" switch can be installed equally well on an E
160 or E 1250 circuit breaker.
Thus it is not necessary to specify the type of circuit-breaker. Only the
release voltage and the type of contact (standard or low level) has to be
indicated with the order.
Assembly
B
15
On each circuit breaker, ducts for the wiring are provided enabling the
passage of the cables to the right, left, or to the rear side of the device,
without increasing its original dimensions.
Electrical auxiliaries
Auxiliary AS "ON/OFF" switches BA bell alarm contacts
B
16
Description Description
Indicates the "open" or "closed" position of the circuit breaker to other Changeover contacts signalling the "tripped" status of the circuit breaker
auxiliaries such as logic circuits, relays, diplays, etc. ... for control, locking, or caused by a fault or opening by voltmetric ST or UV trip devices, or by an
remote indicator functions... earth leakage.
The contact returns to the "normal" position following resetting of the circuit
Low level AS contacts breaker.
For communications between the circuit breaker and automatic or logic
circuits. The BA contact is not activated with a normal closing or opening of the
These (gold plated) contacts are suitable for voltages of circuit breaker.
5 to 30 V AC/DC.
Diagrams show switches in the "OFF" position Low level BA contacts
For communications between the circuit breaker and automatic or logic
open closed open closed Wiring colour code circuits.
12: BNWH (brown & white) These (gold plated) contacts are suitable for voltages of
22 24
12 14 12 14 14: RD (red) 5 to 30 V AC/DC.
11: WH (white) normal default
22: OGWH (orange-white) Wiring colour code
96 98
24: OG (orange) 96: GN (green)
21
11 11 21: GY (grey) 98: BN (brown)
common common 95: YE (yellow)
Characteristics 95
Changeover contacts activated at the same time as main poles. common
2 versions: 1 NO/NC or 2 NO/NC (in the same volume)
Characteristics
Standard contacts
Standard contacts
E 160 to E 1250
Operating voltage (V) AC 50-60 Hz DC E 160 to E 1250
120 to 240 48 to 125 Operating voltage (V) AC 50-60 Hz DC
Load - resistive inductive 120 to 240 48 to 125
Uninterrupted current (A) 5 0.5 0.25 Load - resistive inductive
Breaking capacity (A) 5 0.5 0.25 Uninterrupted current (A) 5 0.5 0.25
Closing capacity (A) 5 0.5 0.25 Breaking capacity (A) 5 0.5 0.25
Closing capacity (A) 5 0.5 0.25
Low level contacts
Low level contacts
E 160 to E 1250
Operating voltage (V) AC 50-60 Hz DC E 160 to E 1250
5 to 30 5 to 30 Operating voltage (V) AC 50-60 Hz DC
Load - resistive inductive 5 to 30 5 to 30
Uninterrupted current (A) 1 1 0.5 Load - resistive inductive
Breaking capacity (A) 1 1 0.5 Uninterrupted current (A) 1 1 0.5
Closing capacity (A) 1 1 0.5 Breaking capacity (A) 1 1 0.5
Closing capacity (A) 1 1 0.5
SPECTRA - Moulded case circuit breakers
B
17
Description Description
Causes the remote opening of the circuit breaker as Causes opening of the circuit breaker in the event of a
soon as it receives power (power can be permanent). drop in voltage (35% to 70 % of Un)
C1 D1 Guaranteed closure of the circuit breaker if
Operation is guaranteed from 55% of Un with
alternating current and from 70% of Un with direct Un > 85%.
U> current U< Operating range:
0.85 < Uc < 1.1 Un.
D2
C2
Wiring colour code: Wiring colour code
C1 - C2: Black(BK) D1 - D2: Blue (BL)
When the release does not receive power, or voltage is too low, the circuit
Characteristics breaker cannot be reclosed; the contacts do not touch.
E 160 to E 1250
Operating voltage (V) AC 50-60 Hz AC Characteristics
DC 50-60Hz
24 48 110/127 220/250 380/415 E 160 to E 1250
Max. ringing current (mA) 300 300 500 400 400 Operating voltage (V) AC 50-60 Hz/DC
Average current (mA) 10 10 6 5 6 24 48 110/127 220/250(2)
Release breaking time (ms) Max. calling current (mA) 100 100 200 200
min. (100 % Un) 15 12 10 15 15 Average current (mA) 80 45 45 45
max.* 45 30 35 50 50 Release breaking time (ms)
* 55 % of Un for AC - 70 % of Un for DC mini (100 % Un) 3 45 75 75
maxi (1) 85 120 250 250
cycle
closing
opening
Description
Diagram
The electrical control is attached to the front of the breaker. It enables the
opening and closing of the circuit breaker by either remote or local control.
Diagram
installation of a
Description selector fault contact
relay switch (local reset
The electrical control is attached to the front of the breaker without removing push-button control control* control* obligatory)
the cover. It enables the opening and closing of the circuit breaker by either
remote or local control.
Energy accumulation type: a universal motor "arms" a spring in which the BPA BPM
potential energy needed for its closing is stored. BP LD
1 2 3
Local control via a push-button.
Indicator showing: GN 1 3 1 3
- red: "closed" or "open" due to a fault or voltmetric release (electrical control OG EF *do not connect 2
not reset)
- green: "open" and "reset". BN
Wiring connection by means of connecting terminals. FC
Locking in "open" position:
M
- using three Ø 8 padlocks (not supplied) GNYE RD
- using Ronis locks (supplied), type 1104, opening to the right. 5 4 96 98
4 BA
95
Characteristics
R R
Nominal voltage:
- alternating current 50/60 Hz: 24 - 48 - 110/127 - 220/240 - 380/415 V
- direct current: 24 - 48 - 110/125 - 220/250 V
Operating voltage: 0.85 to 1.1 Un.
Apparent consumption: 1 : BN (brown) BPM : "ON" push-button
- alternating current: (average) 250 VA/(max.) 650 VA 2 : OG (orange) EF : electrical closing
- direct current: (average)175 W/(max.) 600 W 3 : GN (green) M : motor
Response time: 4 : RD (red) FC : Limit switch
- opening: 2.5 s./ closing: 0.05 s. 5 : GNYE (green/yellow) : manual emergency
• with pulse control: R : resistance > 240V opening control
- minimum interval between pulse of 1 second with opening LD : fault display : connection terminals
• maximum rate of operation: 2 cycles/mn BA : Bell alarm : manual closing button
BPA : "stop/reset"
push-button
cycle
closing
opening
SPECTRA - Moulded case circuit breakers
Types
B
21
Components
Handle
Grey or red Grey or red Grey or red
+ + +
(lock: optional) (lock: optional) (lock: optional)
Converter
Basic converter Converter with lock Basic converter
+ + +
(1 or 2 CACR, optional) (1 or 2 CACR, optional) (1 or 2 CACR, optional)
External operator
Door-mounted operator:
- prevents opening of the door if
the circuit breaker is not "open"
- memorises the opening position
- prevents handle movement with
door open.
Funnel (optional)
This part eliminates the
problem of tolerances and
facilitates the coupling
between the external operator
and the extension bar.
SPECTRA - Moulded case circuit breakers
Optional extras
- wiring isolation:
one 8-contact block (2 blocks max.).
- locking in withdrawn position by:
Ronis 1104 lock, supplied with adapter kit
- status display contacts (2 contacts: NO + NC):
- plugged in,
- withdrawn.
SPECTRA - Moulded case circuit breakers
Notes
B
23
SPECTRA - Catalogue numbers
B
24 In Nº of EN EH EL
poles 35kA 25 32 50 63 80 100
65kA 100kA
160/32 3 763032 763035 763038 PPP 763117 763116
763083(1) PPPP 763127 763126
4 763042 763045 763048 N 0% PPP 763137 763136
763084(1) N 50% PPP - -
160/63 3 763031 763034 763037 PPP 763115 763114
763073(1) PPPP 763125 763124
4 763041 763044 763047 N 0% PPP 763135 763134
763074(1) N 50% PPP - 763144
PPP N 0% - 763154
763111 763110
763121 763120
763131 763130
763141 763140
763151 763150
- 763160
764113 764112 764111 764110
764123 764122 764121 764120
764133 764132 764131 764130
- - 764141 764140
- 764152 764151 764150
765114 765113 765112 765111 765110
765124 765123 765122 765121 765120
765134 765133 765132 765131 765130
- - - 765141 765140
- - 765152 765151 765150
3P 4P
763026 - EM 32
763023 - EM 63
E 400/630
769524 MIR E 400/630 3P
769525 MIR E 400/630 4P
Plug-in circuit breakers, front connections Plug in circuit breakers - type V, front connections
Complete plug-in unit (without circuit breaker) Complete plug in unit (without circuit breaker)
769353
769333 EDAV 3P E 160
769334 EDAV 4P E 160 EDVAV 3P E 160
769354
EDVAV 4P E 160
Plug in sub-assembly
(without circuit breaker) Plug in sub-assembly B
a) moving part (without circuit 27
769340 PMED 3P E 160 breaker)
769341 PMED 4P E 160 a) moving part
769363
b) fixed part
PMEDV 3P E 160
769343 PFEDAV 3P E 160
769344 PFEDAV 4P E 160 769364
PMEDV 4P E 160
b) fixed part
Plug in circuit breaker, rear connections 769365 PFEDVAV 3P E 160
Complete plug in unit (without circuit breaker) 769366 PFEDVAV 4P E 160
769363
Wiring isolation
PMEDV 3P E 160
8-contact block (2 blocks max.).
769085 SECT FIL E 160 769364 PMEDV 4P E 160
b) fixed part
AC 50, 60 Hz
769005 380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V
UV + time delay AC 50 Hz
769054 220 V
Funnel
769090
B
29
11
Door joint
769308 E 160/250
Safety accessories
Seals for control settings
769310
PLREG 3/4P E160
Connections
Box type terminals for bare cable
1 SET *
769371 3RCFAV E160
769372 4RCFAV E160
* replacement part
Extender
769451 1 set of 4 pieces
SPECTRA - E250
Plug in circuit breakers, front connections Plug in circuit breakers- type V, front connections
complete withdrawable unit (without circuit breaker) Complete withdrawable unit (without circuit breaker)
769449
769433 EDAV 3P E250
769434 EDAV 4P E250 EDVAV 3P E250
769450
EDVAV 4P E250
Withdrawable sub-
assembly (without circuit
B
Withdrawable sub-assembly 31
breaker)
(without circuit breaker) a) moving part
a) moving part
769456
769453
EDVAR 4P E250
Withdrawable sub-
Withdrawable sub-assembly assembly (without
(without circuit breaker) circuit breaker)
a) moving part a) moving part
769456
769440 PMED 3P E250
769441 PMED 4P E250 PMEDV 3P E250
AC 50, 60 Hz
769005 380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V
Funnel
769090
B
33
11
Door joint
769308
Safety accessories
Lead seals for control settings
769310
PLREG 3/4P E250
Connections
Box type terminals for bare cables
1 SET*
769462 3RCFAV E250
769463 4RCFAV E250
769563
Wiring isolation PMEDV 3P E400
8-contact block (2 blocks max.).
769564 PMEDV 4P E400
769085 SECT FIL E400
b) fixed part
Wiring isolation
8-contact block (2 blocks max.)
769085 SECT FIL E400
AC 50, 60 Hz
769005 380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V
Funnel
769090 B
37
11
Door joint
769508
Behind door or panel
Replacement part for rotary control
Handle
mounted direct through door or panel.
769584 CRDPG grey
769585 CRDPR red
Connections
Box type terminals for bare cables
769571 3RCFAV E400
769572 4RCFAV E400
Safety accessories
Lead seals for settings controls
Rear connection for bar or cables with crimp lug
769510 + terminal covers
PLREG 3/4P E400 1 SET
769575 3RBFAR + CB E400
769576 4RBFAR + CB E400
Withdrawable circuit breakers, front connections Withdrawable circuit breakers-type V, front connections
Complete withdrawable unit (without circuit breaker) Complete withdrawable unit (without circuit breaker)
b) fixed part
Wiring isolation
8-contact block (2 blocks max.)
769085 SECT FIL E630
AC 50, 60 Hz
769005 380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V
Funnel
B 769090
40
11
Door joint
769508
Behind door or panel
Replacement part for rotary control
Handle mounted direct through door or panel.
769584 CRDPG grey
769585 CRDPR red Connections
Box type terminals for bare cables
1 SET
769571 3RCFAV E630
769572 4RCFAV E630
Safety accessories
Lead seals for control settings Rear connection bar or cable with crimp lug
769510 + terminal covers
PLREG 3/4P E630 1 SET
769575 3RBFAR + CB E630
769576 4RBFAR + CB E630
769733 769736
769734 769737
769740 769740
769741 769741
Locking off with a Ronis 1104 lock Locking off with a Ronis 1104 lock
769509 VERED E800 769509 VERED E800
AC 50, 60 Hz
769005 380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V
Funnel
769090 B
43
11
Door joint
769708
Behind door or panel
Replacement part for rotary control
Handle mounted direct through door or panel.
769784 CRDPG grey
769785 CRDPR red
Connections
Box type terminals for bare cables
1 SET
769771 3RCFAV E800
769772 4RCFAV E800
Safety accessories
Lead seals for controls settings
Rear connection for bar or cable with crimp lug
769510 + terminal covers
PLREG 3/4P E800
1 SET
769728 3RBFAR + CB E800
769729 4RBFAR + CB E800
769734 769737
44 Withdrawable Withdrawable
sub-assembly sub-assembly
(without circuit breaker) (without circuit breaker)
a) moving part a) moving part
769740 769740
PMEDV 3P E1250 PMEDV 3P E1250
769741 769741
PMEDV 4P E1250 PMEDV 4P E1250
b) fixed part b) fixed part
Locking with Ronis 1104 lock Locking with Ronis 1104 lock
769509 VERED E1250 769509 VERED E1250
AC 50, 60 Hz
769005 380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V
Funnel
769090
B
46
11
Door joint
769708
Safety accessories
Rear connections for bar or cable with crimp lug
Lead seals for control settings + terminal covers
769510 1 SET
PLREG 3/4P E1250 769728 3RBFAR + CB E1250
769729 4RBFAR + CB E1250
Residual current earth leakage devices MTS earth leakage protection unit with separate
SHR 1100 - SHR 1110 core
B
47
797070 24-48V AC
797071 110-480V AC
797072 220/415V AC
Installation kit
797106
Detection cores
Closed core CITF
797060 CITF Ø 35
797061 CITF Ø 80
797062 CITF Ø 110
797063 CITF Ø 140
797064 CITF Ø 210
3 poles 4 poles
B
48
3 poles 4 poles
fixation points
connection centres
SPECTRA - Overall dimensions
3 poles 4 poles
B
49
3 poles 4 poles
fixation points
connection centres
SPECTRA - Overall dimensions
3 poles 4 poles
B
50
3 poles 4 poles
A B C D E fixation points
front connections 346 482.5 63.5 74.5 83
connection centres
rear connections 267 403.5 24 35 43.5
SPECTRA - Overall dimensions
3 poles 4 poles
B
51
3 poles 4 poles
fixation points
connection centres
SPECTRA - Overall dimensions
B
52
B
53
B
54
B
55
B
56
B
57
B
58
B
59
B 1
60
circuit breaker
plug-in device
23.5 E160
12.5 E250
122
4 poles
105
126.5 E160
35
144 E250
17.5
1
12.5
122
3 poles
RONIS
OPTIONAL
B
61
4 poles
(CIRCUIT BREAKER)
(WITHDRAWABLE)
E 400/630 E 800/1250
A 97 140 (1)
B 180 268
C 163.5 181.5
D 41 67.5
E 32 32
F 12.5 15
G 47 70
H 140 210
L 157 222
M 31.2 18
N 7.3 83
P 13 15
3 poles
RONIS
OPTIONAL
B
62
4 poles
(CIRCUIT BREAKER)
(WITHDRAWABLE)
3 poles 4 poles
B
63
(CIRCUIT BREAKER)
(WITHDRAWABLE)
RONIS
OPTIONAL
Drilling diagram
3 poles 4 poles
3 poles 4 poles
89.5 89.5
59.25 59.25
F F Max.5
B Min.80
G 30.25 G 30.25
64
89.5 89.5
E E
24.5
A B1 mini B2 maxi C D
circuit breaker Ronis
optional
G
60° Ø28.5 G 60° Ø28.5 G
F
3xØ6 3xØ6
60° 60°
Ø39 Ø39 F
3 poles 4 poles
G G
F F
B
65
E 160 E 250
A 110 126
3 poles 4 poles
B
66
E 160 E 250
A 124 124
C 90 118
D 90 123
E 320 381
F 8 10.5
fixation points
H 86 103
SPECTRA - Overall dimensions
3 poles 4 poles
B
67
E 160 E 250
A 124 124
B 132 132
C 90 118
D 90 106
E 452 496
F 8 10.5
fixation points
H 86 103
SPECTRA - Connections
B
68
DOWNLINE
Tunnel terminals (can be mounted) for cables without lug
Screw CHC 27/64 : hex key # 5
Torque : ≤ 6 mm2 4 N.m ≥ 10 mm2 17 N.m
Rear connections (optional) for bar or cable with crimp lug
Nut H M6 : key 10 Screw CHC M5-10 : hex key # 4
Torque : 3 N.m Torque : 6 N.m
UPLINE
Connection
width: 20
thickness: 10 max. Terminal to be taken
from circuit breaker
DOWNLINE
Connection
width: 20
thickness: 8.5 max.
2 min.
SPECTRA - Connections
B
69
DOWNLINE
2) Tunnel terminals upline for cables without lug, and front connections
(remove terminals) for insulated bars or cables with insulated crimp lug.
Terminals : Screw CHC 5/8 : hex key # 8
Torque : ≤ 25 mm2 17 N.m ≥ 35 mm2 31 N.m
Sections : Screw CHC M8 + washer (not supplied) : hex key # 6
Torque : 10 N.m
Circuit breakers EN - EH - EL - EM
Rear connections (optional) for bar or cable with crimp lug
Nut H M8 : key 13 Screw CHC M6-16 : hex key # 5
Torque : 7 N.m Torque : 10 N.m UPLINE
DOWNLINE
SPECTRA - Connections
Connection
width: 25
thickness: 8.5 max.
0 min.
B
70
Connection
width: 32
thickness: 11.5 max.
1.5 min.
&
Connection
width: 40
Connection
thickness: 10 max.
width: 25
thickness: 8.5 max.
2 min.
3P : 2 x 76 mm + 1 x 124 mm
4P : 2 x 76 mm + 2 x 124 mm
Tunnel terminals (optional for EN and can be mounted for EH - EL - EM) for
cables without lug
Screw CHC 5/8 : hex key # 8
Torque : ≤ 25 mm2 17 N.m ≥ 35 mm2 31 N.m
For EH - EL - EM the
terminal to be taken from
the circuit breaker
SPECTRA - Connections
B
71
Front connection extension (optional) for bar or cable with crimp lug
Screw H M12 (not supplied) : key 19
Torque : 48 N.m
Screw CHC M12-25 : hex key # 10
Torque : 40 N.m
Extensions for front connections (optional) for bar or cable with crimp lug
Screw H M12 x 25 : key 19
Torque : 40 N.m
Screw H M12 (not supplied)
Torque : 48 N.m
Connection
width: 40
thickness: 10
3P : 2 A + 1 B
4P : 2 A + 2 B
Connection
width: 40
Plug-in circuit breakers E400/630, front connections thickness: 10
Connection
width: 40
thickness: 13 max.
3P : 2 A + 1 B
0 min. 4P : 2 A + 2 B
SPECTRA - Connections
B
Connection
72 width: 40
thickness: 13 max.
Connection
0 min.
width: 50
thickness: 16 max.
0 min.
Connection
width: 40
thickness: 13 max.
6 min.
Connection
width: 60
thickness: 16 max.
0 min.
SPECTRA - Connections
Plug-in circuit breakers E800/1250, front connections Plug-in circuit breakers E 800/1250, rear connections
Front connections (series) for bar or cable with crimp lug Rear connections (series) for bar or cable with crimp lug
Screw H M12-50 : key 19 Screw H M12-45 : key 19
Torque : 48 N.m Torque : 48 N.m
Vertical position
B
73
Circuit breakers E160 with rear connections Circuit breakers E250 with rear connections
B
74
Circuit breakers E400/630 with rear connections Circuit breakers E800/1250 with rear connections
B
75
4 poles
SPECTRA - Drilling diagrams
B
76
Weights(kg)
Aantekeningen