SPECTRA - Moulded case circuit breakers

Contents
B.2 General characteristics

B.6 Technical data

B.8 Functions

B.10 Operating curves


B
1
B.11 Limiter circuit breakers

B.12 Earth leakage protection circuit breakers

B.13 SHR Residual current earth


leakage devices
B.14 MTS Earth leakage protection units with separate
magnetic cores
B.15 Electrical auxiliaries AS, BA, ST, UV

B.18 Electrical control

B.20 Manual rotary control

B.22 Visible isolation circuit breakers

B.24 Catalogue numbers

B.48 Overall dimensions

B.68 Connections

B.74 Drilling diagrams

B.77 Weights
SPECTRA - Moulded case circuit breakers

General chracteristics Description


Spectra "Moulded case" circuit-breakers with electronic protection are
available in three and four pole versions, in fixed or withdrawable formats.
The Spectra circuit-breakers have individual rating plugs and enable
protected distribution of electricity within a current range of 20 and 1250 A.

Suitability for visible isolation


Spectra circuit-breakers are ideal for fully visible isolation selection:
With the handle free, the indication "open" (green display) is only possible
B when the main contacts are separated by a distance of > 20 mm.
Spectra circuit-breakers conform to standards: IEC 947-3,
2 NF C 79-130 and CNOMO recommendations (protection of machine tools).

Double, forward-facing insulation


Spectra circuit-breakers are provided with forward-facing sockets designed
for insertion of internal electrical auxilliaries in situ without the need to
interrupt the power supply.
The sockets are completely insulated from the power circuit.

Seal
For extra safety, access to connection terminals and to controls can be
locked off while at the same time retaining visibility.
Degree of protection
Use In front, in accordance with the NF C 20-010 standard:
- basic circuit-breaker: IP 2X (E 160)
Spectra circuit-breakers provide a solution for three performance levels: IP 3X (E 250 to E 1250)
- normal breaking capacity, type EN - fixed or withdrawable circuit-breaker, with terminal covers:
- High breaking capacity, type EH IP 3X
- Limiter circuit-breaker, type EL
By adding or replacing elements, it is possible to perform the following Note: the addition of electrical control units, rotary control handle, earth-
functions: leakage units or the use of withdrawable devices does not affect the
- earth leakage protection, protection offered by the circuit-breaker
- visible breaking isolation.
Temperature derating
The maximum normal current for a circuit-breaker depends on the ambient
Breaking capacity (according to IEC 947-2 at 415V) temperature in which it is placed.
Icu (kA) This is concerned with the temperature around the circuit-breaker:
- either the ambient temperature when the circuit-breaker is installed in the
open air
100 - or the air inside the box or casing which the circuit-breaker is encased.
The reference (test) temperature for all Spectra circuit-breakers is 400C.
EL EL EL EL Derating is not automatic, the rating plug must be selected according to the
160 250 400 630 ambient temperature around the circuit-breaker.

65 Fixed appliance Withdrawable appliance


0 0 0 0 0
40 C 50 C 60 C 70 C 40 C 500 C 600 C 700 C
EH EH EH EH E 160 160 A 160 A 160 A 145 A 160 A 160 A 160 A 145 A
EH EH
160 250 400 630 800 1250 E 250 250 A 235 A 215 A 185 A 230 A 210 A 195 A 170 A
E 400 400 A 400 A 400 A 400 A 400 A 400 A 400 A 400 A
35 E 630 630 A 630 A 590 A 550 A 580 A 570 A 530 A 500 A
E 800 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A
EN EN EN EN EN EN E 1250 1250 A 1250 A 1250 A 1110 A 1125 A 1125 A 1125 A 1000 A
160 250 400 630 800 1250
Resistance/pole
To enable calculation of the power dissipated by the fixed circuit-breaker
during normal operation.
0
160 250 400 630 800 1250 Ith (A) Breaker E 160 E 250 E 400 E 630 E 800 E 1250
Resistance(1) 0.25 0.20 0.10 0.10 0.03 0.03
(1) Value in milli-ohms.
SPECTRA - Moulded case circuit breakers

Internal electrical auxiliaries Orientation


A fixed circuit breaker can be mounted as follows:
The BA bell alarm, AS auxilliary "ON/OFF" switch, ST voltmetric shunt
release, and UV undervoltage releases are common to the whole Spectra vertical horizontal
range.
These are placed face up on the appliance installed, without the need to UPLINE
interrupt the power supply. 900 900

I
Installation

DOWNLINE

UPLINE
O
Spectra circuit-breakers can be mounted on all boards for industrial and
tertiary use. B

I
In particular, adapter accessories (plates, racks, ...) have been designed for DOWNLINE
integration within our Modula 400 boxes and Modula 4000 switchboards. 3
Circuit breaker models
Fixture Fixed
160 / 1250 • •
Spectra circuit-breakers, in the fixed or withdrawable versions, can be fixed
Withdrawable
on panels, girders or stanchions. • •
125 / 630
Mounting behind or against a door or panel requires no special effort. The
cut-out in the door or panel enables the control handle alone or all the Withdrawable type V
160 /1250 • •
displays and controls to be visible, as required.

Safety perimeter
Power source During breaking, all circuit breakers produce external agents (fragments,
gases, . . . ); in order to guarantee security during this phase, it is necessary
The power source can be connected either upline or downline of the Spectra to respect the safety distances indicated below.
circuit-breaker, and up to the maximum voltage for use (690V).

UPLINE

100
25
70
0 0 (1)
Note: forward
facing
safety distance = 0
I I
(1) 10 mm for:
O O - E 160 types H, L, EM

- E 400/630/800/1250 with
extensions or PAR

painted or insulated metal


DOWNLINE 0 10
metal

Accreditation/certification
IEC 947-2, EN 60 947.2, NF C 63 120,
UL 489, JIS, CSA, Bureau Véritas, Germanischer Lloyd,
Lloyd's Register of Shipping, RINA
SPECTRA - Moulded case circuit breakers

Spectra electronics
Spectra's secret in finding the correct protection lies in the combination of a
High performance electronic protection. very sensitive current sensor, a fast AD Converter unit and a
microprocessor specially designed for protection.

N L1 L2 L3

Activator

AD Converter
Processing

Sampler
4
unit

LT setting ST and I setting


Traditional electronic protection devices are based on the measurement of
the peak value of the current and the deduction of the RMS value.
This method is accurate on condition that: The current sensor output signal
- the power source is sinusoidal and alternating at a constant frequency, for each phase is sampled more
- the load is a passive one (R, L, C). than 30 times per cycle in order to
establish the true RMS value,
Modern electrical installations are no longer of this type. independent of the network, the
Modern installations without a static converter or other electronic equipment nature of the load and the
generating harmonics are rare, environment of the installation.
- power networks are subject to interference, both with respect to In this way Spectra guarantees
voltage and frequency, "correct protection".
- loads are increasingly active.
Under these conditions, traditional electronic breakers are completely
unsuitable. According to the network/load couple, it will create an "over-
protection" or an "underprotection". Spectra samples more than 30 times per cycle.

Spectra: multi-protector or multi-protection

Curve 1: "over-protection" The Spectra electronic circuit breaker may receive two types of instructions:
- The rating plug, adjustable from 0.8 to 1 enables the adjustment of
protection againt overcurrent according to the maximum current
supported by the cable (Iz) and the operating current(Ie).
Curve 1 shows a current with a - Short-term (ST) and instantaneous (I) trip setting enables protection of
distortion of 10% due to cables against overloads and the protection of people against indirect
harmonic 5: contact, while taking into account the nature of the source.
- peak value: Ic = 110 A The same circuit breaker enables protection of lower power sources from
- deducted RMS value: short-circuits (alternator) or the protection of a load from a high inrush
I eff. = 110/√2= 78 A current (transformer).
- true RMS value Irms = 71 A One version, without the LT function, is intended for the protection of motors
A traditional circuit breaker (EM circuit-breaker).
would trip prematurely, resulting The fine tuning and precision of the ST setting enables discrimination
in a disruption of operations. between circuit breakers with LT settings close to each other.
In order to guarantee total protection of the installation, the two settings of
Curve 2: "under-protection" the circuit breaker are linked. Selection of LT protection automatically
defines the ST and instantaneous (I) setting ranges. This link precludes all
risk of "under-protection" in ST mode.
Curve 2 shows a current with a
20% distortion due to harmonic 3:
- peak value Ic = 85 A
- deducted RMS value:
I eff. = 85/√2= 60 A
- true RMS value: Irms = 71 A
A traditional electronic circuit
breaker would not trip for this
overload condition, resulting in
the risk of the cable or the load
being destroyed.
SPECTRA - Moulded case circuit breakers

Protection selection
In order to define the desired characteristics:

B
5
EN - EH - EL EN - EH - EL -EM
LT setting
defined by the rating pug Circuit breaker curve
EM type

Zone that is automatically generated


as soon as the
Ir and Iinst. selection is made

Instantaneous setting
defined by I >
Ir 0.63 Iinst Iinst x Ir

3 or 4 pole Rating plug In (A) Instantaneous setting points


circuit (designation) in x Ir
breaker adj. 0.8 to 1
MIN. • • • • • MAX.
160/32 E 3A 160/32 25 2.9 3.7 4.7 5.9 7.7 10.1 13.3
E 4A 160/32 32 6.0 7.9 10.5 13.8
160/63 E 3A 160/63 50 3.0 3.7 4.7 5.9 7.7 10.0 12.8
E 4A 160/63 63 13.0
160/160 E 3A 160/160 80 2.9 3.7 4.7 5.9 7.7 9.9 12.5
E 4A 160/160 100 3.0 3.8 7.8 10.0 12.8
125 3.0 3.8 4.8 6.0 7.8 10.1 13.1
160 7.9 10.2 13.3
MIN. • • • • MAX.
250 E 3A 250 80 - 100 - 125 3.0 3.7 4.7 5.9 7.7 10
E 4A 250 160 - 200 - 250
400 E 3A 400 160 - 200 - 250 3.0 3.8 4.8 6.1 7.9 10.2
E 4A 400 320 - 400
630 E 3A 630 250 - 320 - 400 3.0 3.8 4.8 6.1 7.8 10.1
E 4A 630 500 - 630
800 E 3A 800 320 - 400 - 500 3.0 3.8 4.8 6.1 7.9 10.0
E 4A 800 630 10.3
800 8.0 10.8
1250 E 3A 1250 630 - 800 3.0 3.8 4.8 6.1 7.9 10.2
E 4A 1250 1000 - 1250

Without rating plug, the circuit breaker is auto-protected between 15 and 25 % Iu


SPECTRA - Moulded case circuit breakers

Technical data E 160 E 250 E400

B
6

Circuit breakers EN 160 EH 160 EL 160 EN 250 EH 250 EL 250 EN400 EH400 EL400
Rated current
Ith 400C (A) 160 160 160 250 250 250 400 400 400
Ith 500C (A) 160 160 160 235 235 235 400 400 400
Ith 600C (A) 160 160 160 215 215 215 400 400 400
Rated operating voltage Ue
AC 50/60Hz (V) 690 690 690 690 690 690 690 690 690
Rated insulation voltage Ui (V) 690 690 690 690 690 690 690 690 690
Ultimate short-circuit breaking capacity Icu
AC 50/60Hz 220/240V (kA) 65 130 200 65 130 200 65 130 200
380/415V (kA) 35 65 100 35 65 100 35 65 100
500V (kA) 25 40 50 25 40 50 25 40 50
660/690V (kA) 8 8 10 10 10 12 10 10 16
Service short-circuit breaking capacity Ics
AC 50/60Hz 220/240V (% Icu) 75 50 50 75 50 50 75 50 50
380/415V (% Icu) 75 50 50 75 50 50 75 50 50
500V (% Icu) 50 50 50 50 50 50 50 50 50
660/690V (% Icu) 50 50 50 50 75 75 50 50 50
Rated short-circuit making capacity Icm
220/240V (kA peak) 145 290 440 145 290 440 145 290 440
380/415V (kA peak) 75 145 220 75 145 220 75 145 220
Single pole IT system breaking capacity Ice
220/240V (% Icu) 50 50 50 50 50 50 50 50 50
380/415V (% Icu) 30 25 15 30 25 25 30 25 15
Rated impulse voltage Uimp (kV) 8 8 8 8 8 8 8 8 8
Operational category A A A A A A A A A
Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
Endurance
Mechanical ops. 15 000 15 000 15 000 15 000 15 000 15 000 10 000 10 000 10 000
Electrical ops. 4 000 4 000 4 000 4 000 4 000 4 000 3 000 3 000 3 000
Total fault elimination time (ms) 10 8 4 10 8 5 12 10 6
Degree of pollution 3 3 3 3 3 3 3 3 3
EM circuit breakers Motor protection
Rating plugs supplied with the appliance (non-
adjustable)
EM 160/32 to 630: Breaking capacities are
identical to those for the EL range EM 160/32 EM 160/63 EM 160/160 EM 250 EM 400
EM 800 to 1250: Breaking capacities are identical
to those for the EH range
Rating plugs Setting range: 0.8 to 1 x In
25A 80A 160A
32A 100A 200A
50A 125A 250A
63A 160A 320A
80A 200A 400A
100A 250A
125A
160A
SPECTRA - Moulded case circuit breakers

E 630 E 800 E 1250

B
7

EN 630 EH 630 EL 630 EN 800 EH 800 EN 1250 EH 1250

630 630 630 800 800 1250 1250


630 630 630 800 800 1250 1250
630 630 630 800 800 1250 1250

690 690 690 690 690 690 690


690 690 690 690 690 690 690

65 130 200 65 100 65 100


35 65 100 35 65 35 65
25 40 50 25 50 25 50
10 16 18 10 18 10 18

75 50 50 75 50 75 50
75 50 50 75 75 75 75
50 50 50 75 50 75 50
50 50 50 100 100 100 100

145 290 440 145 220 145 220


75 145 220 75 145 75 145

50 50 50 50 65 50 65
30 25 15 30 25 30 25
8 8 8 8 8 8 8
A A A A A A A
3-4 3-4 3-4 3-4 3-4 3-4 3-4

10 000 10 000 10 000 5 000 5 000 5 000 5 000


3 000 3 000 3 000 1 000 1 000 1 000 1 000
12 10 6 20 12 20 12
3 3 3 3 3 3 3

EM 630 EM 800 EM 1250

250A 320A 630A


320A 400A 800A
400A 500A 1000A
500A 630A 1250A
630A 800A
SPECTRA - Moulded case circuit breakers

Functions
Circuit breakers EN 160 EH 160 EL 160 EN 250 EH 250 EL 250
Differential (adaptable casing) •(1) •(1) •(1) •(1) •(1) •(1)
According to selection of visible isolation(2) • • • • • •
(withdrawable & type V)
Motor protection (ST and I only) EM32/63/160 EM32/63/160 EM32/63/160 EM 250 EM 250 EM 250

B Internal electrical auxiliaries


BA bell alarm • • • • • •
8
AS auxiliary "ON/OFF" switch • • • • • •
ST voltmetric shunt release • • • • • •
UV undervoltage release • • • • • •

Control accessories
Manual rotary • • • • • •
Electrical • • • • • •

Safety accessories
Terminal cover • • • • • •
Locking off by padlock • • • • • •
by lock • • • • • •

Installation /Connection
Fixed front connections FAV • • • • • •
appliance rear connections FAR • • • • • •
Withdrawable front connections DAV • • • • • •
appliance rear connections DAR • • • • • •

(1) Separate core unit


(2) All Spectra circuit breakers meet the
selection function standard (IEC 947-3)
SPECTRA - Moulded case circuit breakers

EN 400 EH 400 EL 400 EN 630 EH 630 EL 630 EN 800 EH 800 EN 1250 EH 1250
•(1) •(1) •(1) •(1) •(1) •(1) (1) (1) (1) (1)

• • • • • • •(type V) •(type V) •(type V) •(type V)

EM 400 EM 400 EM 400 EM 630 EM 630 EM 630 EM 800 EM 800 EM 1250 EM 1250

• • • • • • • • • •
B
9
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •

• • • • • • • • • •
• • • • • • • • • •

- - - - - - - - - -
• • • • • • • • • •
• • • • • • • • • •

• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
SPECTRA - Moulded case circuit breakers

Operating curves
E 160 circuit breaker E 250 to E1250 circuit breakers

10000 10000
7 7
5 5
4 4
3 3
2 2
B 1000
7
1000
7
10 5 5
4 4
3 3
2 2

100 100
7 7
5 5
4 4
3 3
Operating time in seconds

Operating time in seconds


MIN MIN
2 2

10 10
7 7
5 5
4 4
3 3
MAX MAX
2 2
1 1
7 7
5 5
4 4
3 3
MIN MIN
2 2
0.1 MAX
0.1 MAX
7 7
5 5
4 4
3 3
2 2
0.01 0.01

1 2 3 4 5 6 7 8 910 2 3 1 2 3 4 5 6 7 8 910 2 3

multiples of the setting current multiples of the setting current


SPECTRA - Moulded case circuit breakers

Limiter circuit breakers


General Curves
(derived from tests according to IEC 947-2)
Network voltage 380/415 V

Limited peak intensity as a function of the actual intensity of the


short-circuit current.
KA peak
120

110
E800/1250
B

0.2
H
11

ϕ=
100
The limiting capacity of a circuit

ude
breaker is the expression of the 90

plit
j

am
breaker's capacity, in the event of a 80

ed
short-circuit, to let no current

um
through that is greater than the 70

ass
assumed fault current.

um
N
60 E400/630

xim
Ma
H L
1 50

40 N
E250
This characteristic is expressed by H L
limiting curves. 30 N
E160
H
20 N

2 10
kA eff.
1: Icc unlimited peak 0 10 20 30 40 50 60 70 80 90 100
2: Icc limited peak (actual)
The great limiting capacity of Spectra circuit berakers is a result of the
optimal combination of: Thermal constraints limited as a function of the actual intensity of the
- a light moving part, reducing inertia, short-circuit
- a strong current loop, to generate maximum force of repulsion,
- a slot motor with strong electro-magnetic field to accelerate the opening of A² s
the contacts E800/1250
- contact materials combining good conductivity and high durability, H
- an arc chamber combining a high energy absorbtion capacity, speed of the
breaking of the arc and the cooling of the gasses. N E400/630
107 L
This combination has enabled an exceptional breaking capacity /volume H
ratio.
N
The use of Spectra limiter circuit-breakers enables a great reduction in
E250
stresses that normally develop during a short-circuit: H L
- Reduction in thermal constraints in conductors, increasing their life. N E160
106 H
- Reduction in mechanical constraints due to the reduction of the N
electrodynamic forces of repulsion between conductors, which reduces
the risk of deformation or rupture of the wiring
- Reduction in electro-magnetic effects.
The electro-magnetic field reduces and causes less damage to 105
neighbouring devices and sensors.
Rationalisation
Spectra limiter circuit breakers offer multiple advantages:
- reduction in the volume of boxes and cabinets, kA eff.
- reduction in logistic costs because of the smaller volume, 104
- possibility of connecting circuit breakers with smaller capacity downline. 1 10 30 50 70 100
SPECTRA - Moulded case circuit breakers

Earth leakage protection circuit breakers


Differential protection Remote control
It is possible to control the opening of the circuit breaker using two isolated
terminals, at the rear of the earth leakage protection unit.
Operating voltage: 220 to 415 V AC or DC: no defined polarity.
Test circuit
The "test" button enables simulation of a 30 mA insulation fault;
The circuit simultaneously tests:
- the sensor (core)
- the processing circuit
B - the warning light (V)
- the voltmetric shunt release (ST)
12
Presentation
Front facing:
- "test" button.
- fault indicator light
- the RZ reset button
- adjusting switch ∆ I
- adjusting switch ∆ t
- ST terminals (under the shutter)

Rear:
- two terminals for remote control

Diagram
The protection of people and property provided by differential circuit
breakers with residual intensity measurement, is obtained by combining a The electronic board is powered from three phases: protection is
Spectra circuit breaker equipped with an ST voltmetric shunt release and a ensured even if one phase is lost .
differential block (MIR).
The MIR block can be adapted in situ, to the E 160, E 250, E 400 and 630
circuit breakers.
N L1 L2 L3

The MIR differential units are:


- protected against untimely tripping (no tripping by the 250A
ST
8/20 micro-second wave, defined by IEC 947.2 app.. B)
- adapted to continual bi-directional and uni-directional pulsed
components (class A).
V
Differential protection devices ensure the following functions: C RZ
- protection of people against direct contact in TT systems +
F T I
- additional protection for people against contact in IT or TNS systems -
- protection of property against destruction or fire in the event of faulty
insulation.
Differential protection is also achievable on all Spectra circuit breakers RC
through the combination of a circuit breaker fitted with voltmetric release and
a differential unit with separate magnetic core (SHR, MTS). RS TEST RT

RS: adjusting switch ∆ I RZ: reset button


Functioning RT: adjusting switch ∆ t RC: terminals for remote control

Measuring the fault


The sensor consists of a detection magnetic core. The core is made from a Characteristics
high permability magnetic alloy meeting the requirements of IEC 947.2,
app. B Operating voltage (V) 220 to 415
50/60 Hz
Processing the measurement Switchable version
The processing circuit comprises: instantaneous fixed threshold (A) 0.03
- a filter F threshold: Mult. position (A) 0.3 - 1-3
- a comparator C
time delay (ms) 0 - 100 - 300 - 500
- a timer T
In the event of a fault, the contact I closes.
The rectifier simultaneously powers the voltmetric release ST and the Standards
warning light V: The differential MIR units comply with:
- the warning light changes - IEC 947-2
- the voltmetric shunt release opens the circuit breaker (the open command - NF C 60-130
can be made permanent). - NF C 61-141 (additional clause)
The warning light V cannot be reset (using the RZ button) until the fault has - NF C 62-411
been rectified and the circuit breaker closed.
SPECTRA - Moulded case circuit breakers

SHR 1100 and SHR 1110


Residual current earth leakage devices
Residual current earth leakage protection devices
with separate core, which, via a Spectra circuit
breaker provide circuit opening in the event of an
isolation fault.
Specially designed for industrial networks.

Presentation Characteristics


Modular box 4 modules - DIN 43880
Mounting on symmetrical rail (surface or flush)
Controlled network
alternative L.V.
AC
< 1000V
B
– Screw terminals for 2.5 mm2 wires 13
frequency 40 to 70Hz - 400Hz N.C.
– Front face setting
– Sealable transparent cover Detection principle measurement residual
current
core ratio 600/1 (optional 470/1)
Functions maximum current 500A - 1 s.
Isolation fault LED indication nominal impedance 100Ω
two changeover switches Current measurement
Pre-alarm 50% LED indication threshold 30mA at 3.4A
positive security one changeover switch pre-alarm 50% of the threshold
relay (not adjustable)
Fault reset by push-button threshold adjustm. 64 steps
(optional bistable relay) indicators 4 LEDs
System failure manual integrated test Power supply
external test frequency 40 to 400Hz
Core failure signal 'error' and tripping standard voltage 24 to 480V~ in 3 ranges
consumption 4VA
Performances Operating time adjustable on SHR 1110
Supply voltage V1 V2 adjustments 0.1 to 1.5 s. in 16 steps
version 1 24V~ 48V~ instantaneous 15 ms
version 2 110/127V~ 440/480V~ bypass if 30mA threshold
version 3 220/240V~ 380/415V~
Connection diagram
Contacts dry contacts Cores CITO - CITF
output 2 changeover + 1 NO Alarm 50%
– Ratio: 600/1 Core failure
breaking capacity 6A 250V, 1500VA max. – Connection by box type terminals for wires of Tripping
System failure
insulation 4kV eff. 2.5 mm2
Protection degree IP20 surface – Connection to earth leakage protection relays
IP42 flush using armoured cable with two insulated
conductors and the shortest possible cabling
Remarks (resistance < 30Ω)
1. Ensure cover conductors are centered
2. If the neutral is not out, enclose the 3 phases
3. Never allow the core to enclose the protection CT
conductor V1
4. Armoured cable obligatory for cable lengths V2
(SHR / core) ⊕ 5 m or for sensitive
TEST
settings ⊕ 1A
SPECTRA - Moulded case circuit breakers

MTS earth leakage protection units with separate magnetic


core
Function and use
Maximum current earth leakage protection relay with separate magnetic core which uses a circuit breaker
Spectra release to open a circuit in the event of an isolation fault.
Specially designed for industrial networks.

Characteristics
MTS
B Alternating earth neutral network protected
Frequency

50 to 175Hz
14 Setting values fixed 0.03A Detection core mounting
adjustable 0.1 to 1A
On armoured cable
Time delay 0 to 500 ms (for 0.1 to 1A)
Out-going contacts 2 changeover contacts End box electrically
(2A/250V cos ϕ 0.3) isolated from its support
sensors
Display •
Test button •
Reset button •
Power Detection core
Frequency 50/60 Hz Passing diameter: 34, 55, 70, 100 mm
Flexible connection
AC 220/240V or 380/415V (shipped with MTS) common to cable's ring and
detection core ratio: fuse at the cable end box

Mounting - signal:
recessible into the bottom of the housing 34: 230/1
55: 200/1
For junction boxes
70: 200/1 Junction box
100: 280/1 electrically isolated
from its support
- test: input
34, 55, 70, 100: 200/1 output 2

sensor
Connection diagram sensors

output 1
220/240V 50/60Hz
380/415V 50/60Hz
3 4 6
Notes
0.5/1.5 mm2 1. Ensure conductors are centred in the core.
2. If the neutral is not out, enclose the 3 phases.
3. Never allow the protection conductor to be
enclosed by the core.

1
~ 2 12 11 14 22 21 24 3 4 5 6
SPECTRA - Moulded case circuit breakers

Electrical auxiliaries
General
BA bell alarms, AS auxiliary "ON/OFF" switches, ST voltmetric shunt
releases and UV undervoltage releases are common to all Spectra circuit
breakers,
e.g.: an AS auxiliary "ON/OFF" switch can be installed equally well on an E
160 or E 1250 circuit breaker.
Thus it is not necessary to specify the type of circuit-breaker. Only the
release voltage and the type of contact (standard or low level) has to be
indicated with the order.
Assembly
B
15

Left-hand compartment Right-hand compartment


Option of connecting UV or ST Option of connecting 1 or 2 AS
releases plus 3-pole BA . auxilliary switches.
1 or 2 additional AS contacts can be
connected to the 4-pole E 400 to
E 1250 circuit breakers (an extra
socket is provided for this).

On each circuit breaker, ducts for the wiring are provided enabling the
passage of the cables to the right, left, or to the rear side of the device,
without increasing its original dimensions.

Maximum possibilities for auxilliaries


circuit breaker 3P 4P
160 160 400
to 1250 to 250 to 1250
AS 2 2 2+2
BA 1 1 1
ST or UV 1 1 1

Withdrawable circuit breakers


- option of connecting 8 wires to one 8-contact block
- option of connecting 16 wires to two 8-contact blocks (max.)
As this is intended for installation in compartments that are accesssible from
the front, it is not necessary to take off the cover of the circuit breaker.
SPECTRA - Moulded case circuit breakers

Electrical auxiliaries
Auxiliary AS "ON/OFF" switches BA bell alarm contacts

B
16

Description Description
Indicates the "open" or "closed" position of the circuit breaker to other Changeover contacts signalling the "tripped" status of the circuit breaker
auxiliaries such as logic circuits, relays, diplays, etc. ... for control, locking, or caused by a fault or opening by voltmetric ST or UV trip devices, or by an
remote indicator functions... earth leakage.
The contact returns to the "normal" position following resetting of the circuit
Low level AS contacts breaker.
For communications between the circuit breaker and automatic or logic
circuits. The BA contact is not activated with a normal closing or opening of the
These (gold plated) contacts are suitable for voltages of circuit breaker.
5 to 30 V AC/DC.
Diagrams show switches in the "OFF" position Low level BA contacts
For communications between the circuit breaker and automatic or logic
open closed open closed Wiring colour code circuits.
12: BNWH (brown & white) These (gold plated) contacts are suitable for voltages of
22 24
12 14 12 14 14: RD (red) 5 to 30 V AC/DC.
11: WH (white) normal default
22: OGWH (orange-white) Wiring colour code
96 98
24: OG (orange) 96: GN (green)
21
11 11 21: GY (grey) 98: BN (brown)
common common 95: YE (yellow)

Characteristics 95
Changeover contacts activated at the same time as main poles. common
2 versions: 1 NO/NC or 2 NO/NC (in the same volume)

Characteristics
Standard contacts
Standard contacts
E 160 to E 1250
Operating voltage (V) AC 50-60 Hz DC E 160 to E 1250
120 to 240 48 to 125 Operating voltage (V) AC 50-60 Hz DC
Load - resistive inductive 120 to 240 48 to 125
Uninterrupted current (A) 5 0.5 0.25 Load - resistive inductive
Breaking capacity (A) 5 0.5 0.25 Uninterrupted current (A) 5 0.5 0.25
Closing capacity (A) 5 0.5 0.25 Breaking capacity (A) 5 0.5 0.25
Closing capacity (A) 5 0.5 0.25
Low level contacts
Low level contacts
E 160 to E 1250
Operating voltage (V) AC 50-60 Hz DC E 160 to E 1250
5 to 30 5 to 30 Operating voltage (V) AC 50-60 Hz DC
Load - resistive inductive 5 to 30 5 to 30
Uninterrupted current (A) 1 1 0.5 Load - resistive inductive
Breaking capacity (A) 1 1 0.5 Uninterrupted current (A) 1 1 0.5
Closing capacity (A) 1 1 0.5 Breaking capacity (A) 1 1 0.5
Closing capacity (A) 1 1 0.5
SPECTRA - Moulded case circuit breakers

Shunt release ST Undervoltage release UV

B
17

Description Description
Causes the remote opening of the circuit breaker as Causes opening of the circuit breaker in the event of a
soon as it receives power (power can be permanent). drop in voltage (35% to 70 % of Un)
C1 D1 Guaranteed closure of the circuit breaker if
Operation is guaranteed from 55% of Un with
alternating current and from 70% of Un with direct Un > 85%.
U> current U< Operating range:
0.85 < Uc < 1.1 Un.
D2
C2
Wiring colour code: Wiring colour code
C1 - C2: Black(BK) D1 - D2: Blue (BL)

When the release does not receive power, or voltage is too low, the circuit
Characteristics breaker cannot be reclosed; the contacts do not touch.
E 160 to E 1250
Operating voltage (V) AC 50-60 Hz AC Characteristics
DC 50-60Hz
24 48 110/127 220/250 380/415 E 160 to E 1250
Max. ringing current (mA) 300 300 500 400 400 Operating voltage (V) AC 50-60 Hz/DC
Average current (mA) 10 10 6 5 6 24 48 110/127 220/250(2)
Release breaking time (ms) Max. calling current (mA) 100 100 200 200
min. (100 % Un) 15 12 10 15 15 Average current (mA) 80 45 45 45
max.* 45 30 35 50 50 Release breaking time (ms)
* 55 % of Un for AC - 70 % of Un for DC mini (100 % Un) 3 45 75 75
maxi (1) 85 120 250 250

(1) 55 % of Un for AC - 70 % of Un for DC.


(2) Time release MVR retarder (250, 500, 800, 1000 ms.)
at 220V AC 50 Hz.
Avoids untimely tripping with sudden loss of voltage.
SPECTRA - Moulded case circuit breakers

Electrical control for Characteristics


E 160 - E 250 circuit breakers Nominal voltages:
- alternating current 50/60Hz: 24 - 48 - 110/127 - 220/240 - 380/415V
- direct current: 24 - 48 - 110/125 - 220/250V
Operating voltage: 0.85 to 1.1 Un.
Apparent consumption:
- alternating current (average) 450VA/(max.) 500VA
- direct current: (average) 550W/(max.) 600W
Response time:
- opening/closing: 0.1 s.
B Maximum rate of operation:
- 5 cycles /mn.
18 Interval between two successive operations:
- 0.5 seconds

cycle

closing

rest 0.6 0.7 rest t (s)


0 0.1 1.2

opening

Description
Diagram
The electrical control is attached to the front of the breaker. It enables the
opening and closing of the circuit breaker by either remote or local control.

Opening and closing by means of a universal motor with two rotational


directions with automatic stop at the end of operation. BPM BPA
Local emergency level control.
Display showing:
1 4 3 2 5
- red: circuit breaker "closed"
- white: circuit breaker "open" due to a fault or voltmetric release tripping
- green: circuit breaker "open " and "reset" YE GNYE BL
Opening through ST, UV release, overload, short-circuit or "TEST" button GN IND OG
with resetting required by depressing the "BPA" button or locally by the
emergency control.
Any release of the reset circuit breaker requires resetting of the electrical
control. FC

Connection of wiring by means of connecting terminals.


Locking in the"open" position:
- using 3 padlocks → 8 (not supplied) CS
IND
- using Ronis locks (supplied), type 1104, opening to the right.
RD

1 : GN (green) BPM : "ON" push-button


2 : BL (blue) FC : limit switch
3 : GNYE (green/yellow) CS : safety contact on lever
4 : YE (yellow) IND : coil/induced
5 : OG (orange) R : resistor for U > 240V
6 : RD (red) : connection terminals
BPA : "reset/stop"
push-button
SPECTRA - Moulded case circuit breakers

Electrical control for Operation


E 400 - E 630 - E 800 - E 1250 circuit breakers The accumulation of energy (compression of the spring), requires rapid
closure of the circuit breaker, and is performed automatically with the
opening of the electrical control unit.
- closing: depressing the "ON" button (BPM) powers the closing electronics
EF, releasing the spring and closing the circuit breaker.
- opening: depressing the stop/reset (BPA) button powers the motor which
opens the circuit breaker and resets the spring.
Power is cut at the limit of the movement by the limit swicth (FC) contact ;
the circuit breaker is thus ready for a new closure.
- opening by an ST or UV release, overload or short-circuit or
"TEST" button with resetting required by depressing the BPA button or if
B
necessary by means of local emergency controls. 19
Any tripping of a circuit breaker requires closing or resetting of the electrical
control.
- use of a specific system for automation: call us.
Insertion of a BA fault contact in the "rearming" circuit makes local manual
resetting obligatory.
If closing is permanent (relay or selector switch), do not connect terminal 2
to avoid hunting.

Diagram

installation of a
Description selector fault contact
relay switch (local reset
The electrical control is attached to the front of the breaker without removing push-button control control* control* obligatory)
the cover. It enables the opening and closing of the circuit breaker by either
remote or local control.
Energy accumulation type: a universal motor "arms" a spring in which the BPA BPM
potential energy needed for its closing is stored. BP LD
1 2 3
Local control via a push-button.
Indicator showing: GN 1 3 1 3
- red: "closed" or "open" due to a fault or voltmetric release (electrical control OG EF *do not connect 2
not reset)
- green: "open" and "reset". BN
Wiring connection by means of connecting terminals. FC
Locking in "open" position:
M
- using three Ø 8 padlocks (not supplied) GNYE RD
- using Ronis locks (supplied), type 1104, opening to the right. 5 4 96 98
4 BA
95
Characteristics
R R

Nominal voltage:
- alternating current 50/60 Hz: 24 - 48 - 110/127 - 220/240 - 380/415 V
- direct current: 24 - 48 - 110/125 - 220/250 V
Operating voltage: 0.85 to 1.1 Un.
Apparent consumption: 1 : BN (brown) BPM : "ON" push-button
- alternating current: (average) 250 VA/(max.) 650 VA 2 : OG (orange) EF : electrical closing
- direct current: (average)175 W/(max.) 600 W 3 : GN (green) M : motor
Response time: 4 : RD (red) FC : Limit switch
- opening: 2.5 s./ closing: 0.05 s. 5 : GNYE (green/yellow) : manual emergency
• with pulse control: R : resistance > 240V opening control
- minimum interval between pulse of 1 second with opening LD : fault display : connection terminals
• maximum rate of operation: 2 cycles/mn BA : Bell alarm : manual closing button
BPA : "stop/reset"
push-button

cycle

closing

rest 0.50 3.0 rest t (s)


0 0.05 8.05

opening
SPECTRA - Moulded case circuit breakers

Manual rotary control Basic elements for all installations


Handle
Colour:
- grey as standard
- red for safety circuit breakers in accordance with the standard VDE 0113

Locking in the "open" position:


1 - the handle is fitted with a retractable flap giving access to three
→ 8 padlocks only when the unit is in the "open" position.
2 - lock is easily snapped into place, and locking and removal of the key are
B only possible in the "open" position.
20
CACR display contacts (optional)
Two max. NO/NC contacts.
These are integrated into the converters to indicate the opening and/or
General pre-closing of the circuit breaker.
The rotary control is attached to the front of the circuit breaker
it is equally suited to the following applications: Basic converter
- fixed
- withdrawable
or installed: Can be fitted to the front of the circuit
- direct on breaker breaker to transform the sideways
- behind a screwed-on panel or a hinged door. movement of the control handle into
a rotary movement.
The handle can be snap-on mounted
on the converter.
Description The handle can be removed in the
The handle precisely indicates the main contact positions: "tripped" position by a by-pass.
- red: device "closed"
- white: device "tripped" by voltmetric release or "test" button
- green: device "open"
The rotary control guarantees opening or isolation function being clearly
visible (IEC 947-3):
the handle comes into the position facing the green indicator when the main Locking converter for direct mounting through a door or
contacts are separated by a distance greater than 20 mm. panel
Locking off is not possible unless main contacts are fully open.
A seal is available providing enhanced protection in the event of direct
installation on a door. Offers the same functions as the
basic converter, plus:
1 - locking, preventing opening of the
door or panel if the circuit breaker
is not "open".
2 - memorises the opening position
and preventing movement of the
handle if the door is open.
3 - by-pass allowing opening of the
door or panel with the circuit
breaker "closed".
SPECTRA - Moulded case circuit breakers

Types

Direct on unit Direct through door or panel Behind door or panel


(IP30) (IP55)

B
21

Components
Handle
Grey or red Grey or red Grey or red
+ + +
(lock: optional) (lock: optional) (lock: optional)

Converter
Basic converter Converter with lock Basic converter
+ + +
(1 or 2 CACR, optional) (1 or 2 CACR, optional) (1 or 2 CACR, optional)

External operator
Door-mounted operator:
- prevents opening of the door if
the circuit breaker is not "open"
- memorises the opening position
- prevents handle movement with
door open.

Funnel (optional)
This part eliminates the
problem of tolerances and
facilitates the coupling
between the external operator
and the extension bar.
SPECTRA - Moulded case circuit breakers

Visible isolation circuit breakers


General Withdrawable circuit breakers (plug-in IEC 947-2 type)
Spectra visible isolation circuit breakers can be used: For E 160 to E 630 circuit
- in general low voltage protection of low voltage metering, high/low voltage breakers
subscriber stations. - three sizes of plug-in units:
- wherever personnel safety implies the visually clear and physical 160 - 250 - 400/630,
separation of the source from the loads. - two positions:
They meet the standards: NF C 13-100 and NF C 15-100, and the decree of - plugged in,
14/11/1988. - removed.
They are constructed based on the standard withdrawable circuit breakers - connection:
B and may be fitted with the auxiliaries and accessories intended for these
devices.
front or rear.
- level of protection:
22 In additon the Spectra circuit breakers with visible isolation were designed to - plugged in: IP3x
enable: - removed: IP2x
- rapid removal,
- easy replacement without any risk of contact with live parts, Optional extras
- provision of reserve bases for future extensions. - wiring isolation:
- one 8-contact block
(2 blocks max.).
Structure
Withdrawable and type V circuit breakers comprise a standard circuit
breaker(N, H or L) and a withdrawable unit.
The withdrawable unit comprises: Visible isolation circuit breakers, type V
- a fixed three- or four-pole part equipped with front or rear connection (can be isolated according to IEC 947-2)
terminals,
- a moving part that fits onto the circuit breaker,
- a withdrawable safety device, that trips the circuit breaker as soon as
withdrawal starts,
- optional: isolation of the wiring of the internal electrical auxiliaries and the
control accessories.

For E 160 to E 1250 circuit breakers


- four sizes of withdrawable units, type V:
160 - 250 - 400/630 - 800/1250
- two stable positions indicated by front-facing display:
- red: plugged in,
- green: withdrawn.
- connection:
front or rear.
- padlocking:
three → 8 padlocks(not supplied)

Optional extras
- wiring isolation:
one 8-contact block (2 blocks max.).
- locking in withdrawn position by:
Ronis 1104 lock, supplied with adapter kit
- status display contacts (2 contacts: NO + NC):
- plugged in,
- withdrawn.
SPECTRA - Moulded case circuit breakers

Notes

B
23
SPECTRA - Catalogue numbers

Circuit breakers Rating plugs

B
24 In Nº of EN EH EL
poles 35kA 25 32 50 63 80 100
65kA 100kA
160/32 3 763032 763035 763038 PPP 763117 763116
763083(1) PPPP 763127 763126
4 763042 763045 763048 N 0% PPP 763137 763136
763084(1) N 50% PPP - -
160/63 3 763031 763034 763037 PPP 763115 763114
763073(1) PPPP 763125 763124
4 763041 763044 763047 N 0% PPP 763135 763134
763074(1) N 50% PPP - 763144
PPP N 0% - 763154

160/100 3 763013 763014 763015 PPP 763081 763080


763063(1) PPPP 763091 763090
4 763016 763017 763018 N 0% PPP 763093 763092
763064(1) N 50% PPP - 763094
160/160 3 763030 763033 763036 PPP 763113 763112
763053(1) PPPP 763123 763122
4 763040 763043 763046 N 0% PPP 763133 763132
763054(1) N 50% PPP - 763142
PPP N 0% - -
PPP N 50% - -
250 3 764053 764031 764032 PPP 764115 764114
764030(1) PPPP 764125 764124
4 764054 764041 764042 N 0% PPP 764135 764134
764040(1) N 50% PPP - -
PPP N 0% - -
400 3 765030 765031 765032 PPP
4 765040 765041 765042 PPPP
N 0% PPP
N 50% PPP
PPP N 0%

630 3 766030 766031 766032 PPP


4 766040 766041 766042 PPPP
N 0% PPP
N 50% PPP
PPP N 0%
800 3 767030 767031 - PPP
4 767040 767041 - PPPP
N 0% PPP
N 50% PPP
PPP N 0%
1250 3 768030 768031 - PPP
4 768040 768041 - PPPP
N 0% PPP
N 50% PPP
PPP N 0%
(1) Connection by non-isolated copper bars.
SPECTRA - Catalogue numbers

Circuit breaker features: page B.6


Rating plug features: page B.5
Auxiliary features: page B.11
Dimensions: page B.48
Connections: page B.68
B
25
125 160 200 250 320 400 500 630 800 1000 1250

763111 763110
763121 763120
763131 763130
763141 763140
763151 763150
- 763160
764113 764112 764111 764110
764123 764122 764121 764120
764133 764132 764131 764130
- - 764141 764140
- 764152 764151 764150
765114 765113 765112 765111 765110
765124 765123 765122 765121 765120
765134 765133 765132 765131 765130
- - - 765141 765140
- - 765152 765151 765150

766114 766113 766112 766111 766110


766124 766123 766122 766121 766120
766134 766133 766132 766131 766130
- - - 766141 766140
- - 766152 766151 766150
767114 767113 767112 767111 767110
767124 767123 767122 767121 767120
767134 767133 767132 767131 767130
- - - 767141 767140
- - - 767151 767150
768113 768112 768111 768110
768123 768122 768121 768120
768133 768132 768131 768130
- - 768141 768140
768153 768152 768151 768150
SPECTRA - E160 to E1250

EM "motor protection" circuit breakers MIR - Personnel protection


(including rating plug) (ST supplied)

3P 4P

763026 - EM 32

763023 - EM 63

763003 763004 EM 160


B
26 764003 764004 EM 250

765003 765004 EM 400

766003 766004 EM 630


E 160
767003 767004 EM 800 769323 MIR E 160 3P
769324 MIR E 160 4P
768003 768004 EM 1250
E 250
769423 MIR E 250 3P
769424 MIR E 250 4P

E 400/630
769524 MIR E 400/630 3P
769525 MIR E 400/630 4P

Circuit breaker features: page B.6


Auxiliary features: page B.11
Dimensions: page B.48
Connections: page B.68
SPECTRA - E160

Plug-in circuit breakers, front connections Plug in circuit breakers - type V, front connections
Complete plug-in unit (without circuit breaker) Complete plug in unit (without circuit breaker)

769353
769333 EDAV 3P E 160
769334 EDAV 4P E 160 EDVAV 3P E 160

769354
EDVAV 4P E 160
Plug in sub-assembly
(without circuit breaker) Plug in sub-assembly B
a) moving part (without circuit 27
769340 PMED 3P E 160 breaker)
769341 PMED 4P E 160 a) moving part

769363
b) fixed part
PMEDV 3P E 160
769343 PFEDAV 3P E 160
769344 PFEDAV 4P E 160 769364
PMEDV 4P E 160

b) fixed part
Plug in circuit breaker, rear connections 769365 PFEDVAV 3P E 160
Complete plug in unit (without circuit breaker) 769366 PFEDVAV 4P E 160

769336 EDAR 3P E 160


769337 EDAR 4P E 160 Removable circuit breakers - type V,
rear connections
Complete plug in unit (without circuit breaker)
Plug-in sub-assembly
(without circuit breaker) 769356
a) moving part EDVAR 3P E 160

769340 PMED 3P E 160 769357


769341 PMED 4P E 160
EDVAR 4P E 160
b) fixed part
Plug in sub-assembly
769346 PFEDAR 3P E 160 (without circuit breaker)
769347 PFEDAR 4P E 160 a) moving part

769363
Wiring isolation
PMEDV 3P E 160
8-contact block (2 blocks max.).
769085 SECT FIL E 160 769364 PMEDV 4P E 160

b) fixed part

769367 PFEDVAR 3P E 160

769368 PFEDVAR 4P E 160

Wiring isolation 8-contact block (2 blocks max.).


769085 SECT FIL E 160

"Plugged in - removed" display contacts


769298 E 160 (2 blocks)

Locking off with Ronis 1104 lock


Dimensions: page B.48
Connections: page B.68 769309 VERED E 160
SPECTRA - E160

Electrical auxiliaries Electrical controls


AS auxiliary contacts DC
Standard contacts 769311 24 V
769312 48 V
769060 1 NO/NC 769313 110/125 V
769061 2 NO/NC 769314 220/250 V
Low level contacts AC 50, 60 Hz
769070 1 NO/NC 769316 24V
B 769071 2 NO/NC 769317
769318
48V
110/127V
28 769319 220/240V
769315 380/415 V
BA bell alarm
Sandard contacts
769068 1 NO/NC Locking off in "OFF" position with Ronis 1104 lock
opening to the right (supplied)
Low level contacts
769078 1 NO/NC 769350 VERCE E160

ST voltmetric shunt release


AC 50, 60 Hz - DC
769001 24 V
769002 48 V
769003 110/127 V
769004 220/250 V

AC 50, 60 Hz
769005 380/415 V

UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V

UV + time delay AC 50 Hz
769054 220 V

Auxiliary features page B.15


SPECTRA - E160

Rotary controls Accessories for rotary controls


Direct on the unit Lock Ronis 1104
Handle
769080 Opening to the right
769300 CRDG grey
769301 CRDR red

Funnel

769090
B
29

Direct through a door or panel Display switches


Handle 769299 CACR E 160/250
769302 CRAPG grey 12 14
769303 CRAPR red

11

Door joint
769308 E 160/250

Behind door or panel Replacement part for rotary control for


direct installation through door or panel.
Handle
769384 CRDPG grey
769385 CRDPR red
SPECTRA - E160

Safety accessories
Seals for control settings
769310
PLREG 3/4P E160

B Sealable terminal covers


1 SET
30 769377 3P E160
769378 4P E160

1 set includes 2 pieces


(up- and downline)

Padlocking the control handle in the "OFF" position

769306 VER MAN E160

Connections
Box type terminals for bare cable
1 SET *
769371 3RCFAV E160
769372 4RCFAV E160

* replacement part

Rear connections for bar or cable with crimp lug


+ and terminal covers
1 SET
769375 3RBFAR + CB E160
769376 4RBFAR + CB E160

Extender
769451 1 set of 4 pieces
SPECTRA - E250

Plug in circuit breakers, front connections Plug in circuit breakers- type V, front connections
complete withdrawable unit (without circuit breaker) Complete withdrawable unit (without circuit breaker)

769449
769433 EDAV 3P E250
769434 EDAV 4P E250 EDVAV 3P E250

769450
EDVAV 4P E250
Withdrawable sub-
assembly (without circuit
B
Withdrawable sub-assembly 31
breaker)
(without circuit breaker) a) moving part
a) moving part
769456

769440 PMED 3P E250 PMEDV 3P E250


769441 PMED 4P E250
769457
b) fixed part PMEDV 4P E250
b) fixed part
769443 PFEDAV 3P E250
769444 PFEDAV 4P E250 769458 PFEDVAV 3P E250

769459 PFEDVAV 4P E250

Withdrawable circuit breaker, front connections Withdrawable circuit breakers - type V,


Complete withdrawable unit (without circuit breaker)
rear connections
Complete withdrawable unit (without circuit breaker)
769436 EDAR 3P E250
769437 EDAR 4P E250 769452
EDVAR 3P E250

769453
EDVAR 4P E250
Withdrawable sub-
Withdrawable sub-assembly assembly (without
(without circuit breaker) circuit breaker)
a) moving part a) moving part

769456
769440 PMED 3P E250
769441 PMED 4P E250 PMEDV 3P E250

b) fixed part 769457


PMEDV 4P E250
769446 PFEDAR 3P E250 b) fixed part
769447 PFEDAR 4P E250
769460 PFEDVAR 3P E250

769461 PFEDVAR 4P E250

Wiring isoloation Wiring isolation


8-contact block (2 blocks max.). 8-contact block (2 blocks max.)

769085 SECT FIL E250 769085 SECT FIL E250

Display contacts "plugged in - removed"


769298 E250 (2 blocks)

Locking off using a Ronis 1104 lock


Dimensions: page B.49
Connections: page B.69 769309 VERED E250
SPECTRA - E250

Electrical auxiliaries Electrical controls


AS auxiliary contacts DC
Standard contacts 769311 24 V
769312 48 V
769060 1 NO/NC 769313 110/125 V
769061 2 NO/NC 769314 220/250 V
Low level contacts AC 50, 60 Hz
769070 1 NO/NC 769316 24 V
B 769071 2 NO/NC 769317
769318
48 V
110/127 V
32 769319 220/240 V
BA bell alarm 769315 380/415 V
Standard contact
769068 1 NO/NC Locking of the electrical control in the "OFF" position
Low level contact with a Ronis 1104 lock opening to the right (supplied)
769078 1 NO/NC 769350 VERCE E250

Voltmetric ST shunt release


AC 50, 60 Hz - DC
769001 24 V
769002 48 V
769003 110/127 V
769004 220/250 V

AC 50, 60 Hz
769005 380/415 V

UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V

UV + time delay unit AC 50 Hz


769054 220 V

Auxiliary features: page B.15


Dimensions: page B.49
Connections: page B.69
SPECTRA - E250

Rotary controls Accessories for rotary controls


Direct on the unit Lock (Ronis 1104)
Handle 769080
769300 CRDG grey
769301 CRDR red

Funnel

769090
B
33

Direct through a door or panel Display contacts


Handle 769299 CACR E250
769302 CRAPG grey 12 14
769303 CRAPR red

11

Door joint
769308

Behind door or panel Replacement part for rotary control


mounted direct through door or panel.
Handle
769384 CRDPG grey
769385 CRDPR red
SPECTRA - E250

Safety accessories
Lead seals for control settings
769310
PLREG 3/4P E250

B Sealable terminal covers


34 1 SET
769468 3P E250
769469 4P E250

One set includes 2 pieces


(up- and downline)

Padlocking the control handle in the "OFF" position

769306 VER MAN E250

Connections
Box type terminals for bare cables
1 SET*
769462 3RCFAV E250
769463 4RCFAV E250

* replacement for EH/EL 250

Rear connection for bar or cable with crimp lug + terminal


covers
1 SET
769466 3RBFAR + CB E250
769467 4RBFAR + CB E250
SPECTRA - E400

Withdrawable circuit breakers, front connections Withdrawable circuit breakers-type V, front


Complete withdrawable unit (without circuit breaker) connections
Complete withdrawable unit (without circuit breaker)
769533 EDAV 3P E400
769553
769534 EDAV 4P E400
EDVAV 3P E400
Withdrawable sub-assembly 769554
(without circuit breaker)
a) moving part EDVAV 4P E400

769540 PMED 3P E400


Withdrawable B
sub-assembly 35
769541 PMED 4P E400 (without circuit breaker)
a) moving part
b) fixed part
769563
769543 PFEDAV 3P E400
PMEDV 3P E400
769544 PFEDAV 4P E400
769564
PMEDV 4P E400
b) fixed part
Withdrawable circuit breakers, rear connections 769565 PFEDVAV 3P E400
Complete withdrawable unit (without circuit breaker)
769566 PFEDVAV 4P E400
769536 EDAR 3P E400
Withdrawable circuit breakers - type V,
769537 EDAR 4P E400
rear connections
Withdrawable sub-assembly Complete withdrawable unit (without circuit breaker)
(without circuit breaker) 769556
a) moving part
EDVAR 3P E400
769540 PMED 3P E400
769557
769541 PMED 4P E400
EDVAR 4P E400
b) fixed part Withdrawable
769546 PFEDAR 3P E400 sub-assembly
(without circuit breaker)
769547 PFEDAR 4P E400 a) moving part

769563
Wiring isolation PMEDV 3P E400
8-contact block (2 blocks max.).
769564 PMEDV 4P E400
769085 SECT FIL E400
b) fixed part

769567 PFEDVAR 3P E400

769568 PFEDVAR 4P E400

Wiring isolation
8-contact block (2 blocks max.)
769085 SECT FIL E400

Display contacts: "plugged in - removed"


769298 (2 blocks)

Locking off with a Ronis 1104 lock


Dimensions: page B.50
Connections: page B.70 769509 VERED E400
SPECTRA - E400

Electrical auxiliaries Electrical controls


AS auxiliary switches DC
Standard contacts 769517 24 V
769518 48 V
769060 1 NO/NC 769519 110 V
769061 2 NO/NC 769520 220 V
Low level contacts AC 50, 60 Hz
769070 1 NO/NC 769511 24 V

B 769071 2 NO/NC 769512


769513
48 V
110/127 V
36 769514 220/250 V
BA bell alarm 769515 380 V
769516 415 V
Standard contact
769068 1 NO/NC
Locking off the electrical control in the "OFF" position
Low level contact
using Ronis 1104 lock opening to the right (supplied)
769078 1 NO/NC

769521 VERCE E400


ST voltmetric shunt release
AC 50, 60 Hz - DC
769001 24 V
769002 48 V
769003 110/127 V
769004 220/250 V

AC 50, 60 Hz
769005 380/415 V

UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V

UV + time delay unit AC 50 Hz


769054 220 V

Auxiliary characteristics: page B.15


SPECTRA - E400

Rotary controls Accessories for rotary controls


Direct on the unit Lock (Ronis 1104)
Handle 769080
769500 CRDG grey
769501 CRDR red

Funnel

769090 B
37

Direct through door or panel


Display contacts
Handle
769502 CRAPG grey 769499 CACR E400
769503 CRAPR red
12 14

11

Door joint
769508
Behind door or panel
Replacement part for rotary control
Handle
mounted direct through door or panel.
769584 CRDPG grey
769585 CRDPR red
Connections
Box type terminals for bare cables
769571 3RCFAV E400
769572 4RCFAV E400

Safety accessories
Lead seals for settings controls
Rear connection for bar or cables with crimp lug
769510 + terminal covers
PLREG 3/4P E400 1 SET
769575 3RBFAR + CB E400
769576 4RBFAR + CB E400

Padlocking the control arm in


the "OFF" position Extension arms for bar or cable with crimp lug
769506 1 SET
769573 3RPBFAV E400
VER MAN E400 769574 4RPBFAV E400

One set includes 3 or 4 pieces


(up- or downline)
SPECTRA - E630

Withdrawable circuit breakers, front connections Withdrawable circuit breakers-type V, front connections
Complete withdrawable unit (without circuit breaker) Complete withdrawable unit (without circuit breaker)

769533 EDAV 3P E630 769553


769534 EDAV 4P E630
EDVAV 3P E630
Withdrawable sub-assembly 769554
(without circuit breaker)
EDVAV 4P E630
a) moving part
B 769540 PMED 3P E630
Withdrawable
sub-assembly
38 769541 PMED 4P E630
(without circuit breaker)
a) moving part
b) fixed part
769563
769543 PFEDAV 3P E630
PMEDV 3P E630
769544 PFEDAV 4P E630
769564
PMEDV 4P E630
b) fixed part
Withdrawable circuit breakers, rear connections 769565 PFEDVAV 3P E630
Complete withdrawable unit (without circuit breaker)
769566 PFEDVAV 4P E630
769536 EDAR 3P E630
769537 EDAR 4P E630
Withdrawable circuit breakers - type V,
Withdrawable sub-assembly rear connections
(without circuit breaker)
a) moving part
Complete withdrawable unit (without circuit breaker)
769556
769540 PMED 3P E630
769541 PMED 4P E630 EDVAR 3P E630

b) fixed part 769557


EDVAR 4P E630
769546 PFEDAR 3P E630
769547 PFEDAR 4P E630
Withdrawable
sub-assembly
(without circuit breaker)
a) moving part
Wiring isolation
8-contact block (2 blocks max.) 769563 PMEDV 3P E630
769085 SECT FIL E630 769564 PMEDV 4P E630

b) fixed part

769567 PFEDVAR 3P E630


769568 PFEDVAR 4P E630

Wiring isolation
8-contact block (2 blocks max.)
769085 SECT FIL E630

Display contacts: "plugged in - removed"


769298 (2 blocks)

Locking off with the Ronis 1104 lock


Dimensions: page B.50
Connections: page B.71 769509 VERED E630
SPECTRA - E630

Electrical auxiliaries Electrical controls


AS auxiliary switches DC
Standard contacts 769517 24 V
769518 48 V
769060 1 NO/NC 769519 110 V
769061 2 NO/NC 769520 220 V
Low level contacts AC 50, 60 Hz
769070 1 NO/NC 769511 24 V
769071 2 NO/NC 769512
769513
48 V
110/127 V B
769514 220/250 V 39
BA bell alarm 769515 380 V
769516 415 V
Standard contact
769068 1 NO/NC
Locking off the electrical control in the
Low level contact
"OFF" position with a Ronis lock (supplied)
769078 1 NO/NC

769521 VERCE E630


ST voltmetric shunt release
AC 50, 60 Hz - DC
769001 24 V
769002 48 V
769003 110/127 V
769004 220/250 V

AC 50, 60 Hz
769005 380/415 V

UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V

UV + time delay unit AC 50 Hz


769054 220 V

Auxiliary characteristics: page B.15


SPECTRA - E630

Rotary controls Rotary controls accessories


Direct on the unit Lock (Ronis 1104)
Handle 769080
769500 CRDG grey
769501 CRDR red

Funnel
B 769090
40

Direct through door or panel


Display contacts
Handle
769502 CRAPG grey 769499 CACR E630
769503 CRAPR red 12 14

11

Door joint
769508
Behind door or panel
Replacement part for rotary control
Handle mounted direct through door or panel.
769584 CRDPG grey
769585 CRDPR red Connections
Box type terminals for bare cables
1 SET
769571 3RCFAV E630
769572 4RCFAV E630

Safety accessories
Lead seals for control settings Rear connection bar or cable with crimp lug
769510 + terminal covers
PLREG 3/4P E630 1 SET
769575 3RBFAR + CB E630
769576 4RBFAR + CB E630

Locking off the control handle in the "OFF" position

Extension arms for bar or cable with crimp lug


769506
1 SET
VER MAN E630
769573 3RPBFAV E630
769574 4RPBFAV E630

One set includes 3 or 4 pieces


(up- or downline)
SPECTRA - E800

Withdrawable circuit breakers - type V, Withdrawable circuit breakers - type V,


front connections rear connections
Complete withdrawable unit (without circuit breaker) Complete withdrawable unit (without circuit breaker)

769733 769736

EDVAV 3P E800 EDVAR 3P E800

769734 769737

EDVAV 4P E800 EDVAR 4P E800


B
Withdrawable Withdrawable 41
sub-assembly (without sub-assembly
circuit breaker) (without circuit breaker)
a) moving part a) moving part

769740 769740

PMEDV 3P E800 PMEDV 3P E800

769741 769741

PMEDV 4P E800 PMEDV 4P E800

b) fixed part b) fixed part

769746 PFEDVAR 3P E800


769743 PFEDVAV 3P E800 769747 PFEDVAR 4P E800
769744 PFEDVAV 4P E800

Wiring isolation Wiring isolation


8-contact block (2 blocks max.) 8-contact block (2 blocks max.)

769085 SECT FIL E800 769085 SECT FIL E800

Display contacts: "plugged in - removed" Display contacts: "plugged in - removed"


769698 (2 blocks) 769698 (2 blocks)

Locking off with a Ronis 1104 lock Locking off with a Ronis 1104 lock
769509 VERED E800 769509 VERED E800

Dimensions: page B.56


Connections: page B.72
SPECTRA - E800

Electrical auxiliaries Electrical controls


AS auxiliary switches DC
Standard contacts 769717 24 V
769718 48 V
769060 1 NO/NC 769719 110 V
769061 2 NO/NC 769720 220 V
Low level contacts AC 50, 60 Hz
769070 1 NO/NC 769711 24 V
B 769071 2 NO/NC 769712
769713
48 V
110/127 V
42 769714 220/250 V
BA bell alarm 769715 380 V
769716 415 V
Standard contact
769068 1 NO/NC
Locking off of the electrical control
Low level contact
in the "OFF" position using Ronis lock (supplied)
769078 1 NO/NC

769521 VERCE E800


ST voltmetric shunt release
AC 50, 60 Hz - DC
769001 24 V
769002 48 V
769003 110/127 V
769004 220/250 V

AC 50, 60 Hz
769005 380/415 V

UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V

UV + time delay unit AC 50 Hz


769054 220 V

Auxiliary characteristics: page B.15


SPECTRA - E800

Rotary controls Accessories for rotary controls


Direct on the unit Lock (Ronis 1104)
Handle 769080
769700 CRDG grey
769701 CRDR red

Funnel

769090 B
43

Direct through door or panel


Display contacts
Handle
769702 CRAPG grey 769499 CACR E800
769703 CRAPR red
12 14

11

Door joint
769708
Behind door or panel
Replacement part for rotary control
Handle mounted direct through door or panel.
769784 CRDPG grey
769785 CRDPR red
Connections
Box type terminals for bare cables
1 SET
769771 3RCFAV E800
769772 4RCFAV E800

Safety accessories
Lead seals for controls settings
Rear connection for bar or cable with crimp lug
769510 + terminal covers
PLREG 3/4P E800
1 SET
769728 3RBFAR + CB E800
769729 4RBFAR + CB E800

Padlocking the control handle in the "OFF" position

769706 Extension arms for bar or cable with crimp lug


VER MAN E800
1 SET
769724 3RPBFAV E800
769725 4RPBFAV E800

One set includes 3 or 4 pieces


(up- or downline)
SPECTRA - E1250

Withdrawable circuit breakers - type V, Withdrawable circuit breakers - type V,


front connections rear connections
Complete withdrawable unit (without circuit breaker) Complete withdrawable unit (without circuit breaker)
769733 769736
EDVAV 3P E1250 EDVAR 3P E1250

769734 769737

B EDVAV 4P E1250 EDVAR 4P E1250

44 Withdrawable Withdrawable
sub-assembly sub-assembly
(without circuit breaker) (without circuit breaker)
a) moving part a) moving part

769740 769740
PMEDV 3P E1250 PMEDV 3P E1250

769741 769741
PMEDV 4P E1250 PMEDV 4P E1250
b) fixed part b) fixed part

769743 PFEDVAV 3P E1250 769746 PFEDVAR 3P E1250


769744 PFEDVAV 4P E1250 769747 PFEDVAR 4P E1250

Wiring isolation Wiring isolation


8-contact block (2 blocks max.) 8-contact block (2 blocks max.)
769085 SECT FIL E1250 769085 SECT FIL E1250

Contacts of signalisation Contacts of signalisation


769698 (2 blocks) 769698 (2 blocks)

Locking with Ronis 1104 lock Locking with Ronis 1104 lock
769509 VERED E1250 769509 VERED E1250

Dimensions: page B.56


Connections: page B.73
SPECTRA - E1250

Electrical auxiliaries Electrical controls


AS auxiliary switches DC
Standard contacts 769717 24 V
769718 48 V
769060 1 NO/NC 769719 110 V
769061 2 NO/NC 769720 220 V
Low level contacts AC 50, 60 Hz
769070 1 NO/NC 769711 24 V
769071 2 NO/NC 769712
769713
48 V
110/127 V B
769714 220/250 V 45
BA bell alarm 769715 380 V
769716 415 V
Standard contact
769068 1 NO/NC
Locking off the electrical control in the
Low level contact
"OFF" position using a Ronis lock (supplied)
769078 1 NO/NC

769521 VERCE E1250


ST voltmetric shunt release
AC 50, 60 Hz - DC
769001 24 V
769002 48 V
769003 110/127 V
769004 220/250 V

AC 50, 60 Hz
769005 380/415 V

UV undervoltage release
AC 50, 60 Hz - DC
769031 24 V
769032 48 V
769033 110/127 V
769034 220/250 V

UV + time delay unit AC 50 Hz


769054 220 V

Auxiliary characteristics: page B.15


SPECTRA - E1250

Rotary controls Accessories for rotary controls


Direct on the unit Lock (Ronis 1104)
Handle 769080
769700 CRDG grey
769701 CRDR red

Funnel

769090
B
46

Direct through door or panel Display contacts

Handle 769499 CACR E1250


769702 CRAPG grey 12 14
769703 CRAPR red

11

Door joint
769708

Replacement part for rotary control


Behind door or panel mounted direct through door or panel.
Handle
769784 CRDPG grey Connections
769785 CRDPR red
Box type terminals for bare cable
1 SET
769871 3RCFAV E1250
769872 4RCFAV E1250

Safety accessories
Rear connections for bar or cable with crimp lug
Lead seals for control settings + terminal covers
769510 1 SET
PLREG 3/4P E1250 769728 3RBFAR + CB E1250
769729 4RBFAR + CB E1250

Locking off the control handle in the "OFF" position


Extension arms for bar or cable with crimp lug
769706
1 SET
VER MAN E1250
769724 3RPBFAV E1250
769725 4RPBFAV E1250

One set includes 3 or 4 pieces


(up- or downline)
SPECTRA - Earth leakage protection

Residual current earth leakage devices MTS earth leakage protection unit with separate
SHR 1100 - SHR 1110 core

B
47

220/240V 380/415V Inner core diameter


742010 742110 34Ø
742011 742111 55Ø
742012 742112 70Ø
SHR 1100 (instantaneous) 742013 742113 100Ø

797070 24-48V AC
797071 110-480V AC
797072 220/415V AC

SHR 1110 (time delayed)


797073 24-48V AC
797074 110-480V AC
797075 220/415V AC

Installation kit
797106

Detection cores
Closed core CITF
797060 CITF Ø 35
797061 CITF Ø 80
797062 CITF Ø 110
797063 CITF Ø 140
797064 CITF Ø 210

Open core CITO


797065 CITO Ø 65
797066 CITO Ø 104

Characteristics: pages B.13-14


Connecting diagram: pages B.13-14
Dimensions: page B.144
SPECTRA - Overall dimensions

Circuit breakers E160

3 poles 4 poles

B
48

Circuit breakers E160 + MIR

3 poles 4 poles

fixation points

connection centres
SPECTRA - Overall dimensions

Circuit breakers E250

3 poles 4 poles

B
49

Circuit breakers E250 + MIR

3 poles 4 poles

fixation points

connection centres
SPECTRA - Overall dimensions

Circuit breakers E400/630

3 poles 4 poles

B
50

Circuit breakers E400/630 + MIR

3 poles 4 poles

A B C D E fixation points
front connections 346 482.5 63.5 74.5 83
connection centres
rear connections 267 403.5 24 35 43.5
SPECTRA - Overall dimensions

Circuit breakers E800/1250 (front connections)

3 poles 4 poles

B
51

Circuit breakers E800/1250 (rear connections)

3 poles 4 poles

fixation points

connection centres
SPECTRA - Overall dimensions

Three-pole plug-in circuit breakers E160 to E630,


front connections.

B
52

E 160 E 250 E 400/630 E 160 E 250 E 400/630


A 28.75 31.5 - M 66 66 108
A1 28.75 26 - N 23.5 23.5 18.5
B 360.5 399 510 P 29.6 29.6 46
C 37.5 51 60 P1 72.3 72.3 96.8
C1 37.5 48 60 P2 38.15 40.15 48.9
D 66.75 85.75 104.5 R 32 32 43
E 116.25 135.5 172.5 S 35 35 57.5
G 7 7 - T 70 70 115
H 6 6 5 V 35 35 46
J 81 97 97 W 105 105 140
J1 126.5 144 180 X 105 105 150
J2 138 157 202 Y 112 112 158
K 150 169 222

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Four-pole plug-in circuit breakers E160 to E630,


front connections.

B
53

E 160 E 250 E 400/630 E 160 E 250 E 400/630


A 28.75 31.5 - M 66 66 108
A1 28.75 26 - N 23.5 23.5 18.5
B 360.5 399 510 P 29.6 29.6 46
C 37.5 51 60 P1 72.3 72.3 96.8
C1 37.5 48 60 P2 38.15 40.15 48.9
D 66.75 85.75 104.5 R 32 32 43
E 116.25 135.5 172.5 S 35 35 57
G 7 7 - T 105 105 160
H 6 6 5 V 35 35 46
J 81 97 97 W 140 140 186
J1 126.5 144 180 X 140 140 196
J2 138 157 202 Y 147 147 204
K 150 169 222

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Three-pole plug-in circuit breakers E160 to E630,


rear connections.

B
54

E 160 E 250 E 400/630 E 160 E 250 E 400/630


A 28.75 31.5 - K 150 169 222
A1 28.75 26 - M 82 82 77
B 43 43 43 N 15 15 10
C 37.5 51 60 P 29.6 29.6 46
C1 37.5 48 60 P1 72.3 72.3 96.8
D 66.75 85.75 104.5 P2 38.15 40.15 48.9
E 219.5 257.5 295 R 32 32 43
F 203.5 241.5 324 S 35 35 57.5
G 7 7 - T 70 70 115
H 6 6 5 V 35 35 46
J 81 97 97 W 105 105 140
J1 126.5 144 180 X 105 105 150
J2 138 157 202 Y 112 112 158

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Four-pole plug-in circuit breakers E160 to E630,


rear connections.

B
55

E 160 E 250 E 400/630 E 160 E 250 E 400/630


A 28.75 31.5 - K 150 169 222
A1 28.75 26 - M 82 82 77
B 43 43 43 N 15 15 10
C 37.5 51 60 P 29.6 29.6 46
C1 37.5 48 60 P1 72.3 72.3 96.8
D 66.75 85.75 104.5 P2 38.15 40.15 48.9
E 219.5 257.5 295 R 32 32 43
F 203.5 241.5 324 S 35 35 57
G 7 7 - T 105 105 160
H 6 6 5 V 35 35 46
J 81 97 97 W 140 140 186
J1 126.5 144 180 X 140 140 196
J2 138 157 202 Y 147 147 204

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Three-pole withdrawable type V circuit breakers E160 to E1250,


front connections.

B
56

E 160 E 250 E 400/630 E 800/1250 E 160 E 250 E 400/630 E 800/1250


A 28.75 31.5 - - L 350 350 445 520
A1 28.75 26 - - M 66 66 108 166
B 360.5 399 510 674 N 23.5 23.5 18.5 18.5
C 37.5 51 60 80 P 29.6 29.6 46 84.5
C1 37.5 48 60 80 P1 72.3 72.3 96.8 158
D 66.75 85.75 104.5 147.5 P2 38.15 40.15 48.9 63.8
E 116.25 135.5 172.5 225.5 R 32 32 43 58.5
G 7 7 - - S 35 35 57.5 90
H 6 6 5 5 T 70 70 115 180
J 81 97 97 140 U 17 17 15.5 15
J1 126.5 144 180 268 V 35 35 46 70
J2 138 157 202 285 W 105 105 140 210
K 150 169 222 395 X 132 132 172 252
K1 178 197 250 425 Y 182 182 225 310

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Four-pole withdrawable type V circuit breakers E160 to E1250,


front connections.

B
57

E 160 E 250 E 400/630 E 800/1250 E 160 E 250 E 400/630 E 800/1250


A 28.75 31.5 - - L 350 350 445 520
A1 28.75 26 - - M 66 66 108 166
B 360.5 399 510 674 N 23.5 23.5 18.5 18.5
C 37.5 51 60 80 P 29.6 29.6 46 84.5
C1 37.5 48 60 80 P1 72.3 72.3 96.8 158
D 66.75 85.75 104.5 147.5 P2 38.15 40.15 48.9 63.8
E 116.25 135.5 172.5 225.5 R 32 32 43 58.5
G 7 7 - - S 35 35 57 90
H 6 6 5 5 T 105 105 160 250
J 81 97 97 140 U 17 17 15.5 15
J1 126.5 144 180 268 V 35 35 46 70
J2 138 157 202 285 W 140 140 186 280
K 150 169 222 395 X 167 167 218 322
K1 178 197 250 425 Y 217 217 270 380

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Three-pole withdrawable type V circuit breakers E160 to E1250,


rear connections.

B
58

E 160 E 250 E 400/630 E 800/1250 E 160 E 250 E 400/630 E 800/1250


A 28.75 31.5 - - L 350 350 445 520
A1 28.75 26 - - M 82 82 77 154.5
B 43 43 43 50 N 15 15 10 19.5
C 37.5 51 60 80 P 29.6 29.6 46 84.5
C1 37.5 48 60 80 P1 72.3 72.3 96.8 158
D 66.75 85.75 104.5 147.5 P2 38.15 40.15 48.9 63.8
E 219.5 257.5 295 395 R 32 32 43 58.5
F 203.5 241.5 324 394 S 35 35 57.5 90
G 7 7 - - T 70 70 115 180
H 6 6 5 5 U 17 17 15.5 15
J 81 97 97 140 V 35 35 46 70
J1 126.5 144 180 268 W 105 105 140 210
J2 138 157 202 285 X 132 132 172 252
K 150 169 222 395 Y 182 182 225 310
K1 178 197 250 425

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Four-pole withdrawable type V circuit breakers E160 to E1250,


rear connections.

B
59

E 160 E 250 E 400/630 E 800/1250 E 160 E 250 E 400/630 E 800/1250


A 28.75 31.5 - - L 350 350 445 520
A1 28.75 26 - - M 82 82 77 154.5
B 43 43 43 50 N 15 15 10 19.5
C 37.5 51 60 80 P 29.6 29.6 46 84.5
C1 37.5 48 60 80 P1 72.3 72.3 96.8 158
D 66.75 85.75 104.5 147.5 P2 38.15 40.15 48.9 63.8
E 219.5 257.5 295 395 R 32 32 43 58.5
F 203.5 241.5 324 394 S 35 35 57 90
G 7 7 - - T 105 105 160 250
H 6 6 5 5 U 17 17 15.5 15
J 81 97 97 140 V 35 35 46 70
J1 126.5 144 180 268 W 140 140 186 280
J2 138 157 202 285 X 167 167 218 322
K 150 169 222 395 Y 217 217 270 380
K1 178 197 250 425

Drilling diagrams: see B.73


fixation points for fixed part
SPECTRA - Overall dimensions

Electrical controls for circuit breakers E160 and E250

3 poles 81 E160 120.3 E160


97 E250 121.3 E250
105 37
35 23
17.5

B 1

60

circuit breaker
plug-in device
23.5 E160
12.5 E250

122

4 poles

105
126.5 E160
35
144 E250
17.5
1
12.5

122

fixation points for fixed part


fixation points
SPECTRA - Overall dimensions

Electrical controls for circuit breakers E400 to E1250

3 poles

RONIS
OPTIONAL

B
61

4 poles

(CIRCUIT BREAKER)

(WITHDRAWABLE)

E 400/630 E 800/1250
A 97 140 (1)
B 180 268
C 163.5 181.5
D 41 67.5
E 32 32
F 12.5 15
G 47 70
H 140 210
L 157 222
M 31.2 18
N 7.3 83
P 13 15

(1) PAR circuit breaker: 3P: 182 mm


4P: 184.5 mm

fixation points for fixed part


fixation points
SPECTRA - Overall dimensions

Rotary controls for circuit breakers E160 to E1250,


direct on unit

3 poles

RONIS
OPTIONAL

B
62

4 poles

(CIRCUIT BREAKER)

(WITHDRAWABLE)

E 160 E 250 E 400/630 E 800/1250 E 160 E 250 E 400/630 E 800/1250


A 81 97 97 140 (1) H (4P) 48.5 48.5 93 127
B 126.5 144 180 268 J 104.5 104.5 139 209
C 29 29 54.5 54.5 K 65.5 65.5 105.5 141.5
D 79 79 132 132 L 31.9 31.9 42.5 134.2
E 40 40 32 32 M 7.4 18.4 4 33.2
F 55 55 100 100 N 27 27 31 46
G 31 31 59 72 P 92.8 92.8 135.5 188.5
H (3P) 48.5 48.5 93.5 127
(1) PAR circuit breaker: 3P: 182 mm
4P: 184.5 mm
fixation points for fixed part
fixation points
SPECTRA - Overall dimensions

Rotary controls for E160 to E1250,


direct through door or panel.

3 poles 4 poles

B
63

(CIRCUIT BREAKER)

(WITHDRAWABLE)
RONIS
OPTIONAL

Drilling diagram

3 poles 4 poles

fixation points for fixed part


fixation points

E160 E250 E400/630 E800/1250 E160 E250 E400/630 E800/1250


A 81 97 97 140 (1) N 52.3 52.3 56.3 71.3
B 126.5 144 180 268 P 143 143 186 239
C 22.5 24.5 53 50 R 100 100 100 140
D 57 57 84 84 S 26.6 37.6 40.7 81.4
E 40 40 32 32 T 51.1 51.1 79.2 182.4
F 55 55 100 100 U 17.5 17.5 23 35
G 31 31 59 72 V (3P) 35 35 57.5 90
H (3P) 48.5 48.5 93,5 127 V (4P) 35 35 57 90
H (4P) 48.5 48.5 93 127 W 55.5 55.5 73.5 108.5
J 146 146 181 251 X 55.5 55.5 79.5 108.5
K 86.5 86.5 126.5 162.5 Y 8 8 2 8
L 31.9 31.9 42.5 134.2 Z 63.5 63.5 85 111.5
M 7.4 18.4 4 33.2
(1) Circuit breaker with rear horizontal terminal: 3P: 182 mm
4P: 184.5 mm
SPECTRA - Overall dimensions

Rotary controls for fixed or withdrawable circuit breakers E160 to E1250,


behind door or panel.

3 poles 4 poles
89.5 89.5

59.25 59.25
F F Max.5

B Min.80
G 30.25 G 30.25
64
89.5 89.5

E E

24.5

A B1 mini B2 maxi C D
circuit breaker Ronis
optional

Drilling diagram (installation at 90°)


3 poles 4 poles 3 poles 4 poles
F F
G

G
60° Ø28.5 G 60° Ø28.5 G

F
3xØ6 3xØ6
60° 60°
Ø39 Ø39 F

3 poles 4 poles

G G

F F

E 160 E 250 E 400/630 E 800/1250 fixation points for fixed part


A 81 97 97 140(1)
B1 90 90 120 120 fixation points
B2 350 350 378 370
C 67 67 97 97
D 40 40 32 32
E 55 55 100 100
F 31 31 59 72
G 7.4 18.4 4 33.2
(1) Circuit breaker with rear horizontal terminal: 3P: 182 mm
4P: 184.5 mm
SPECTRA - Overall dimensions

Padlocking the control handle


Circuit breakers E160/250

B
65

E 160 E 250
A 110 126

Circuit breakers E400/630

Circuit breakers E800/1250


SPECTRA - Overall dimensions

Sealable terminal covers mounted on circuit breakers E160/250

3 poles 4 poles

B
66

E 160 E 250
A 124 124
C 90 118
D 90 123
E 320 381
F 8 10.5
fixation points
H 86 103
SPECTRA - Overall dimensions

Sealable terminal covers mounted on circuit breakers + MIR (E160/250)

3 poles 4 poles

B
67

E 160 E 250
A 124 124
B 132 132
C 90 118
D 90 106
E 452 496
F 8 10.5
fixation points
H 86 103
SPECTRA - Connections

Fixed circuit breakers E160 Plug-in circuit breakers E160


Tunnel terminals (series) for cables without lug Front connections (series) for bar or cable with crimp lug
Screw CHC 27/64 : hex key # 5 Screw CHC M8-16 : hex key # 6
Torque : ≤ 6mm2 4 N.m ≥ 10 mm2 17 N.m Torque : 10 N.m
Note : if power is on the downline it is possible to connect bars or cables
with lugs (consult us) Connection
width: 20
thickness: 8.5 max.
UPLINE 0 min.

B
68

DOWNLINE
Tunnel terminals (can be mounted) for cables without lug
Screw CHC 27/64 : hex key # 5
Torque : ≤ 6 mm2 4 N.m ≥ 10 mm2 17 N.m
Rear connections (optional) for bar or cable with crimp lug
Nut H M6 : key 10 Screw CHC M5-10 : hex key # 4
Torque : 3 N.m Torque : 6 N.m

UPLINE

Connection
width: 20
thickness: 10 max. Terminal to be taken
from circuit breaker

DOWNLINE

Rear connections (series) for bar or cable with crimp lug


Screw H M10-20 : key 17
Torque : 28 N.m
Vertical position only.

Connection
width: 20
thickness: 8.5 max.
2 min.
SPECTRA - Connections

Fixed circuit breakers E250


Circuit breakers type EN Circuit breakers type EH - EL - EM (2 possibilités)
Front connections (series) for bar or cable with crimp lug 1) Tunnel terminals (series) for connection up- or downline with cables
Screw CHC M8-16 : hex key # 6 without lug
Torque : 10 N.m Screw CHC 5/8 : hex key # 8
Torque : ≤ 25 mm2 17 N.m ≥ 35 mm2 31 N.m
Connection
width: 20 UPLINE
thickness: 8.5 max.
0 min.

B
69

Tunnel terminals (optional) for cables without lug.


Screw CHC 5/8 : hex key # 8
Torque : ≤ 25 mm2 17 N.m ≥ 35 mm2 31 N.m

DOWNLINE

2) Tunnel terminals upline for cables without lug, and front connections
(remove terminals) for insulated bars or cables with insulated crimp lug.
Terminals : Screw CHC 5/8 : hex key # 8
Torque : ≤ 25 mm2 17 N.m ≥ 35 mm2 31 N.m
Sections : Screw CHC M8 + washer (not supplied) : hex key # 6
Torque : 10 N.m
Circuit breakers EN - EH - EL - EM
Rear connections (optional) for bar or cable with crimp lug
Nut H M8 : key 13 Screw CHC M6-16 : hex key # 5
Torque : 7 N.m Torque : 10 N.m UPLINE

Range and connection capacity


Connection identical to EN
width: 25
thickness: 10 max.

DOWNLINE
SPECTRA - Connections

Plug-in circuit breakers E250 Fixed circuit breakers E400/630


Front connections (series) for bar or cable with crimp lug Front connections (series) for bar or cable with crimp lug
Screw CHC M8-16 : hex key # 6 Screw CHC M12-25 : hex key # 10
Torque : 10 N.m Torque : 40 N.m

Connection
width: 25
thickness: 8.5 max.
0 min.

B
70

Connection
width: 32
thickness: 11.5 max.
1.5 min.

Rear connections (optional) for bar or cable with crimp lug


Nuts H M14 : key 22
Torque : 27 N.m
Screw CHC M10-25 : hex key # 8
Rear connections (series) for bar or cable with crimp lug Torque : 36 N.m
Screw H M10-20 : key 17
Torque : 28 N.m
&

&

Connection
width: 40
Connection
thickness: 10 max.
width: 25
thickness: 8.5 max.
2 min.
3P : 2 x 76 mm + 1 x 124 mm
4P : 2 x 76 mm + 2 x 124 mm

Tunnel terminals (optional for EN and can be mounted for EH - EL - EM) for
cables without lug
Screw CHC 5/8 : hex key # 8
Torque : ≤ 25 mm2 17 N.m ≥ 35 mm2 31 N.m

For EH - EL - EM the
terminal to be taken from
the circuit breaker
SPECTRA - Connections

Fixed circuit breakers E400/630


Tunnel terminals (optional) for cables without lug Tunnel terminals (optional) for cables without lug
Screw CHC M10-20 : hex key # 8 Screw CHC 11/16 : hex key # 8
Torque : ≤ 50 mm2 31 N.m ≥ 70 mm2 42 N.m Torque : ≤ 50 mm2 31 N.m ≥ 70 mm2 42 N.m
Screw CHC M12-25 : hex key # 10
Torque : 40 N.m

B
71

Screw and washer to


be taken from circuit
breaker

Front connection extension (optional) for bar or cable with crimp lug
Screw H M12 (not supplied) : key 19
Torque : 48 N.m
Screw CHC M12-25 : hex key # 10
Torque : 40 N.m

Extensions for front connections (optional) for bar or cable with crimp lug
Screw H M12 x 25 : key 19
Torque : 40 N.m
Screw H M12 (not supplied)
Torque : 48 N.m
Connection
width: 40
thickness: 10

3P : 2 A + 1 B
4P : 2 A + 2 B

Connection
width: 40
Plug-in circuit breakers E400/630, front connections thickness: 10

Front connections (series) for bar or cable with crimp lug


Screw H M12-25 : key 19
Torque : 40 N.m

Connection
width: 40
thickness: 13 max.
3P : 2 A + 1 B
0 min. 4P : 2 A + 2 B
SPECTRA - Connections

Plug-in circuit breakers E400/630, rear connections


Rear connections (series) for bar or cable with crimp lug 2) With extension for bar or cable with crimp lug
Screw H M12-25 : key 19 Screw CHC M5-16 : hex key # 4 Screw CHC M12-30 : hex key # 10
Torque : 40 N.m Torque : 6 N.m Torque : 48 N.m
Horizontal position Vertical position Screw H M12-40 : key 19
Torque : 48 N.m

B
Connection
72 width: 40
thickness: 13 max.
Connection
0 min.
width: 50
thickness: 16 max.
0 min.

Tunnel terminals (optional) for cables without lug


Screw CHC 11/16 : hex key # 8
Torque : ≤ 50 mm2 31 N.m ≥ 70 mm2 42 N.m Tunnel terminals (option) for cables without lug
Screw CHC M12-25 : hex key # 10 Screw CHC 3/4 : hex key # 10
Torque : 40 N.m Torque : 42 N.m
Rear connections in mandatory horizontal position Screw CHC 12-45 : hex key # 10
Torque : 45 N.m
Screw and washer to be taken from circuit breaker

Fixed circuit breakers E 800/1250

Front connections (series) 2 installation options


1) Without extension for bars
Screw CHC M12-30 : hex key # 10
Torque : 48 N.m

Rear connections (optional) for bar or cable with crimp lug


Screw H M12-40 : key 19
Torque : 48 N.m
Screw CHC M10-30 : hex key # 8
Torque : 36 N.m
Vertical position only

Connection
width: 40
thickness: 13 max.
6 min.

Connection
width: 60
thickness: 16 max.
0 min.
SPECTRA - Connections

Plug-in circuit breakers E800/1250, front connections Plug-in circuit breakers E 800/1250, rear connections
Front connections (series) for bar or cable with crimp lug Rear connections (series) for bar or cable with crimp lug
Screw H M12-50 : key 19 Screw H M12-45 : key 19
Torque : 48 N.m Torque : 48 N.m

Vertical position

B
73

Connection Horizontal position


width: 50
thickness: 20 max.
0 min.

Tunnel terminals (optional) for cables without lug.


Screw CHC 3/4 : hex key # 10 Connection
Torque : 42 N.m width: 50
thickness: 15 max.
Screw CHC M12-45 : hex key # 10 0 min.
Torque : 45 N.m

Tunnel terminals (optional) for cables without lug.


Screw CHC 3/4 : hex key # 10
Torque : 42 N.m
Screw H M12 (not supplied) : key 19
Torque : 48 N.m
Mandatory horizontal position

Screw H M12x60 nut supplied


SPECTRA - Drilling diagrams

Circuit breakers E160 with rear connections Circuit breakers E250 with rear connections

Basic unit Basic unit


3 poles 4 poles 3 poles 4 poles

B
74

Basic unit + MIR Basic unit + MIR


3 poles 4 poles 3 poles 4 poles
SPECTRA - Drilling diagrams

Circuit breakers E400/630 with rear connections Circuit breakers E800/1250 with rear connections

Basic unit Basic unit


3 poles 4 poles 3 poles

B
75

Basic unit + MIR


3 poles 4 poles

4 poles
SPECTRA - Drilling diagrams

Withdrawable circuit breakers E160/1250 and type V, front or rear connections.

B
76

fixing points for fixed part of withdrawable unit

E 160 E 250 E 400/630 E 800/1250


3 poles 4 poles 3 poles 4 poles 3 poles 4 poles 3 poles 4 poles
A 102 137 102 137 144 190 206 276
B 70 105 70 105 115 160 180 250
C 16 16 16 16 14.5 15 13 13
D 169 169 206 206 254 254 355 355
E 35 35 35 35 45 45 60 60
F 75 75 99 99 120 120 160 160
G 12 12 20 20 22 22 37.5 37.5
H 12 12 17 17 22 22 37.5 37.5
J 35 35 35 35 57.5 57 90 90
K 48.5 66 48.5 66 48.5 71.5 48.5 83.5
L 48.5 31 48.5 31 48.5 25.5 48.5 13.5
M 60 60 62 62 60 60 60 60
N 7.5 7.5 20 20 30 30 50 50
P 5.7 5.7 5.7 5.7 5.7 5.7 9 9
SPECTRASPECTRA
- Drilling diagrams
- Weights

Weights(kg)

E 160 E 250 E 400/630 E 800/1250


3 poles 4 poles 3 poles 4 poles 3 poles 4 poles 3 poles 4 poles
Basic unit
Fixed circuit breaker type EN 2.280 2.990 3.230 4.280 6.090 8.290 21.390 28.250
Fixed circuit breaker type EH 2.320 3.030 3.270 4.320 6.130 8.330 21.430 28.290
Fixed circuit breaker type EL 2.370 3.080 3.320 4.370 6.180 8.380 21.480 28.340
Fixed circuit breaker type EM 2.370 3.080 3.320 4.370 6.180 8.380 21.480 28.340
Rating plug B
All ratings 0.033 0.033 0.033 0.033 0.033 0.033 0.033 0.033 77
MIR Differential unit 1.410 1.510 1.540 1.630 3.230 3.320 - -
Internal electrical auxiliaries
AS auxiliary switch 0.122 0.122 0.122 0.122 0.122 0.122 0.122 0.122
BA Bell alarm 0.122 0.122 0.122 0.122 0.122 0.122 0.122 0.122
ST Voltmetric shunt release 0.103 0.103 0.103 0.103 0.103 0.103 0.103 0.103
UV Undervoltage release 0.102 0.102 0.102 0.102 0.102 0.102 0.102 0.102
Electrical controls 1.690 1.690 1.690 1.690 4.300 4.300 7.500 7.500
Locking of the electrical control 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012
Rotary controls
Direct on the unit 0.261 0.261 0.261 0.261 0.850 0.850 1.950 1.950
Direct through door or panel 0.283 0.283 0.283 0.283 1.000 1.000 2.200 2.200
Behind door or panel 0.904 0.904 0.904 0.904 1.500 1.500 2.650 2.650
Safety accessories
Lead sealing for circuit breaker control settings 0.017 0.017 0.017 0.017 0.017 0.017 0.017 0.017
Sealable terminal covers 0.370 0.370 0.476 0.476 - - - -
Connections
Box-type terminals for bare cable 0.062 0.076 0.132 0.168 0.540 0.710 0.985 1.324
Rear connections for bars or crimp lug cables 0.132 0.170 0.280 0.380 1.150 1.630 3.250 4.630
Extensions for bars or crimp lug cables - - - 1.145 1.571 1.413 1.875
Complete plug-in unit (without circuit breaker)
Front connection plug-in unit 2.380 3.030 2.500 3.240 9.110 11.450 - -
Rear- conection plug-in unit 2.210 2.860 2.390 3.080 8.350 10.750 - -
Complete type V withdrawable unit (without circuit breaker)
Front connection withdrawable unit type V 3.830 4.590 4.030 4.860 11.470 14.180 32.000 39.000
Rear connection withdrawable unit type V 3.900 4.450 3.930 4.570 10.000 12.750 29.660 36.800
SPECTRA - Drilling diagrams

Aantekeningen