Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 20

Water Fixture Unit Values and Branch Sizing

Level: Ground Floor


Room Name: Typical Toilet

Fixture No. WFUV Total


Lav-h (Private) 1 0.7 0.7
WC-h (Private Flush Tank) 1 2.2 2.2
Hand spray 1 1.5 1.5
Shower head (Private) 1 1 1
Total WFUV 5.4

Required Flow = 10 GPM


= 0.63 L/s
= 0.0006 M3/s

Pipe Material = PEX-AL-PEX


Roughness Factor (C) = 150

Selected Pipe Nominal diameter = 32 mm


Actual Pipe Inner Diameter = 26 mm

Flow Velocity = 1.19 m/s


= 3.90 fps

Friction Loss / meter = 0.0063 bar/meter


= 633.00 Pa/meter
Water Fixture Unit Values and Branch Sizing

Level: Ground Floor


Room Name: Typical Buffet.

Fixture No. WFUV Total


Kitchn Sink 1 4 4
Total WFUV 4

Required Flow = 8 GPM


= 0.50 L/s
= 0.0005 M3/s

Pipe Material = PEX-AL-PEX


Roughness Factor (C) = 150

Selected Pipe Nominal diameter = 32 mm


Actual Pipe Inner Diameter = 26 mm

Flow Velocity = 0.95 m/s


= 3.12 fps

Friction Loss / meter = 0.0042 bar/meter


= 418.91 Pa/meter
Water Fixture Unit Values and Branch Sizing

Level: Ground Floor


Room Name: Typical Laundry

Fixture No. WFUV Total


Washing Machine (15 lb). 3 4 12
Total WFUV 12

Required Flow = 15.75 GPM


= 0.99 L/s
= 0.0010 M3/s

Pipe Material = PEX-AL-PEX


Roughness Factor (C) = 150

Selected Pipe Nominal diameter = 50 mm


Actual Pipe Inner Diameter = 41 mm

Flow Velocity = 0.75 m/s


= 2.47 fps

Friction Loss / meter = 0.0016 bar/meter


= 159.60 Pa/meter
Potable Water Requirements

1.) Required connection Discharge :-

Total Water Fixture Unit Value:

Area WFUV WFUV TOT.


Typical Toilet 5.4 270
Typical Buffet. 4 16
Typical Laundry 12 48
Total 334

Supply System Predominatly For Flush Tank

Estimsted Flow for WFUV = 91.93 GPM


= 5.80 L/s
= 0.0058 M3/s

2.) Required connection pressure. :-

Static Head = 11.60 PSI 0.80 Bar

Friction Losses = 8.81 PSI 0.61 Bar

Residual Pressure = 20 PSI 1.38 Bar


Total = 40.42 PSI 2.79 Bar

Chosen = 40.61 PSI 2.80 Bar

3.) Main Potable Water Pipe Sizing. :-

Required Flow = 91.93 GPM


= 5.80 L/s
= 0.0058 M3/s

Pipe Material = UPVC - Class 5


Roughness Factor (C) = 150

Selected Pipe Nominal diameter = 90 mm


Actual Pipe Inner Diameter = 73 mm

Flow Velocity = 1.39 m/s


= 4.54 fps

Friction Loss / meter = 0.0025 bar/meter


= 251.38 Pa/meter

Chosen Pipe Diameter = 90 mm


PLUMBING DESIGN CALCULATIONS

ELECTRIC WATER HEATER SIZING

1.) DESIGN DATA :-

TYPE OF OCCUPANCY = Apartment House.


DEMAND FACTOR = 0.3
STORAGE FACTOR = 1.25

EWH No. EWH-4A


Location Ground Floor
Room Name Typical Toilet.

2.) CALCULATIONS :-

HOT WATER TOTAL HOT


FIXTURE SERVED NUMBER
DEMAND (LPH) WATER REQUIRED
Lav - Private 1 7.6 7.6
Shower 1 114 114
121.6

Hot water rating = 121.6 x 0.3 = 36.48 LPH

Storage capacity = 36.48 x 1.25 = 45.6 LITERS

3.) RECOMMENDED STANDARD SIZE :-

Actual Power Rating = 2.12 Kw

Chosen Power Rating = 3 Kw

No of units = 1 unit

H.W.R.T = 51.67 LPH

Selected Storage = 50 LITERS

WILL BE TAKEN EWH HAS CAPACITY OF 50 L and 3 KW


PLUMBING DESIGN CALCULATIONS

ELECTRIC WATER HEATER SIZING

1.) DESIGN DATA :-

TYPE OF OCCUPANCY = Club.


DEMAND FACTOR = 0.3
STORAGE FACTOR = 0.9

EWH No. EWH-2A


Location Ground Floor
Room Name Typical Buffet.

2.) CALCULATIONS :-

HOT WATER TOTAL HOT


FIXTURE SERVED NUMBER
DEMAND (LPH) WATER REQUIRED
Kitchen Sink 1 76 76
76

Hot water rating = 76 x 0.3 = 22.8 LPH

Storage capacity = 22.8 x 0.9 = 20.52 LITERS

3.) RECOMMENDED STANDARD SIZE :-

Actual Power Rating = 1.32 Kw

Chosen Power Rating = 1.5 Kw

No of units = 1 unit

H.W.R.T = 25.84 LPH

Selected Storage = 30 LITERS

WILL BE TAKEN EWH HAS CAPACITY OF 30 L and 1.5 KW


PLUMBING DESIGN CALCULATIONS

ELECTRIC WATER HEATER SIZING

1.) DESIGN DATA :-

TYPE OF OCCUPANCY = Apartment House.


DEMAND FACTOR = 0.3
STORAGE FACTOR = 1.25

EWH No. EWH-2A


Location Ground Floor
Room Name Typical Janitor.

2.) CALCULATIONS :-

HOT WATER TOTAL HOT


FIXTURE SERVED NUMBER
DEMAND (LPH) WATER REQUIRED
Janitor Sink 1 76 76
76

Hot water rating = 76 x 0.3 = 22.8 LPH

Storage capacity = 22.8 x 1.25 = 28.5 LITERS

3.) RECOMMENDED STANDARD SIZE :-

Actual Power Rating = 1.32 Kw

Chosen Power Rating = 1.5 Kw

No of units = 1 unit

H.W.R.T = 25.84 LPH

Selected Storage = 30 LITERS

WILL BE TAKEN EWH HAS CAPACITY OF 30 L and 1.5 KW


PLUMBING DESIGN CALCULATIONS

ELECTRIC WATER HEATER SIZING

1.) DESIGN DATA :-

TYPE OF OCCUPANCY = Apartment House.


DEMAND FACTOR = 0.3
STORAGE FACTOR = 1.25

EWH No. EWH-1A


Location Ground Floor
Room Name Staff Toilet.

2.) CALCULATIONS :-

HOT WATER TOTAL HOT


FIXTURE SERVED NUMBER
DEMAND (LPH) WATER REQUIRED
Public Lavatory. 1 15 15
15

Hot water rating = 15 x 0.3 = 4.5 LPH

Storage capacity = 4.5 x 1.25 = 5.625 LITERS

3.) RECOMMENDED STANDARD SIZE :-

Actual Power Rating = 0.26 Kw

Chosen Power Rating = 1.2 Kw

No of units = 1 unit

H.W.R.T = 20.67 LPH

Selected Storage = 30 LITERS

WILL BE TAKEN EWH HAS CAPACITY OF 30 L and 1.2 KW


PLUMBING DESIGN CALCULATIONS

STORM DRAINAGE STACKS SIZING

1.) DESIGN DATA :-

City = Jeddah

Rain Fall Intensity = 100 mm/hr

Sizing Reference SBC 701 table. 6.6.2

Served Areas:

Area Name m2
Area 1 165
Area 10 140

2.) CALCULATION :-

Area Served Inner Diameter


Leader
Name m2 mm
RS-1 Area 1 82 75
RS-2 Area 2 114 75
PLUMBING DESIGN CALCULATIONS

3.) REFERENCE :-
Drainage Fixture Unit Values & PIPES Sizing

ZONE # 2
Typical 24 NOS.

WasteFixture No. DFUV Total


Lav (Private) 2 1 2
Lav (Public) 0 1 0
Kitchen Sink 0 2 0
Janitor Sink 0 2 0
Floor drain 2 2 4
WC (Private Flush Tank) 2 3 6
Shower 2 2 4
Total DFUV 16

Sizing refernce : international plumbing code table 710.1(2)


size of SOIL PIPE = 110 mm

size of vent stack


Sizing refernce : international plumbing code table 916.1
size of vent stack = 50 mm
2- ZONE # 3

WasteFixture No. DFUV Total


Lav (Private) 2 1 2
Lav (Public) 0 1 0
Kitchen Sink (Public) 1 4 4
Janitor Sink 0 2 0
WC (Private Flush Tank) 2 3 6
Shower 2 2 4
Floor drain 3 2 6
Total DFUV 22

Sizing refernce : international plumbing code table 710.1(2)


size of waste PIPE = 110 mm
3- ZONE # 4
Typical 4 NOS.
CALCULATION FOR LAUNDRY AREA.
WasteFixture No. DFUV Total
Lav (Private) 0 1 0
Lav (Public) 0 1 0
Washing Machine 3 2 6
Janitor Sink 1 2 2
Floor drain 2 2 4
Total DFUV 12

Sizing refernce : international plumbing code table 710.1(2)


size of waste PIPE = 75 mm
3- ZONE # 5
Typical 4 NOS.
CALCULATION FOR KITCHEN AREA.
WasteFixture No. DFUV Total
Lav (Private) 0 1 0
Lav (Public) 0 1 0
Washing Machine 0 2 0
Kitchen Sink (Public) 1 4 4
Floor drain 1 2 2
Total DFUV 6

Sizing refernce : international plumbing code table 710.1(2)


size of waste PIPE = 75 mm

Total DFU.= 478 DFU.


Total discharge = 239 gpm.
HYDRAULIC CALCULATION FOR FIRE PROTECTION SYSTEMS:

1.) Required Flow from Fire Water Network:-

For Class 2 Stand Pipes System.


Required flow at the most remote Fire Hose Reel = 100 GPM
No Extra Flow shall be considered

Equivalent
Dia. Q Q Length P. Drop P. Drop
Segment C length.
(mm) GPM (m3/Sec) (meter) (bar/meter) (bar)
(meter)

(1-2) 75.00 100.00 0.01 120.00 20.00 30.00 0.0039 0.12

(2-3) 65.00 100.00 0.01 120.00 8.00 12.00 0.0078 0.09

(3-4) 65.00 100.00 0.01 120.00 63.00 94.50 0.0078 0.74

Total pressure Drop (Bar)


0.9486

3.) Required Pressure at Connection to Fire Water Network :-

Static Head = 9 PSI 0.60 Bar

Friction Losses = 6 PSI 0.40 Bar

Residual Pressure = 65 PSI 4.50 Bar


Total = 80 PSI 5.50 Bar

Chosen = 90 PSI 6.21 Bar


CALCULATION SHEET FOR: NOVEC 1230 FIRE FIGHTING SYSTEM

Building: AA08
Location: Majmaah
Altitude: 620 meters
Supression Agent: FK-1-5-12
Specific Voulme: 0.07189 m3/kg
(@ 20 °C)

Adjusted
Minimum Minimum Pressure Final
Minimum
Design Design Design Correction Design
Area Height Volume Hazard Safety Design Design
S/N Room Name Level Concentration Concentration Quantity Factor Quantity Number of Cylinders
Type Factor Factor Quantity
(MDC) (MDQ) (PCF) (FDQ)
(AMDQ)

m2 m m3 % KG Kg Kg Kg
Telecom Room
1 GR. 15.60 4.35 67.86 C 4.5 1.35 6.075 61.06 0 61.06 0.89 54.34 use 54.34 Kg Modular Type Cylinder
(01-69)

Telecom Room
2 GR. 13.40 4.35 58.29 C 4.5 1.35 6.075 52.45 0 52.45 0.89 46.68 use 46.68 Kg Modular Type Cylinder
(01-55)

Elec. Room
3 GR. 14.00 4.35 60.90 C 4.5 1.35 6.075 54.79 0 54.79 0.89 48.77 use 48.77 Kg Modular Type Cylinder
(01-59)
Elect. Room
4 GR. 13.00 4.35 56.55 C 4.5 1.35 6.075 50.88 0 50.88 0.89 45.28 use 45.28 Kg Modular Type Cylinder
(01-70)
Elec. Room
5 GR. 11.60 4.35 50.46 C 4.5 1.35 6.075 45.40 0 45.40 0.89 40.41 use 40.41 Kg Modular Type Cylinder
(01-83)
Elec. Room
6 GR. 13.40 4.35 58.29 C 4.5 1.35 6.075 52.45 0 52.45 0.89 46.68 use 46.68 Kg Modular Type Cylinder
(01-84)
Transformer
use 125.40 Kg Modular Type
7 Room GR. 36.00 4.35 156.60 C 4.5 1.35 6.075 140.90 0 140.90 0.89 125.40
Cylinder
(01-61)
Generator
8 GR. 18.60 4.35 80.91 C 4.5 1.35 6.075 72.80 0 72.80 0.89 64.79 use 64.79 Kg Modular Type Cylinder
(01-60)

Telecom Room
9 1ST 13.40 4.35 58.29 C 4.5 1.35 6.075 52.45 0 52.45 0.89 46.68 use 46.68 Kg Modular Type Cylinder
(02-44)

Elec Room
10 1ST 10.80 4.35 46.98 C 4.5 1.35 6.075 42.27 0 42.27 0.89 37.62 use 37.62 Kg Modular Type Cylinder
(02-47)
Elec Room
11 1ST 12.70 4.35 55.24 C 4.5 1.35 6.075 49.71 0 49.71 0.89 44.24 use 44.24 Kg Modular Type Cylinder
(02-63)
Control Room use 169.79 Kg Modular Type
12 3RD 46.60 4.55 212.03 C 4.5 1.35 6.075 190.77 0 190.77 0.89 169.79
(04-03) Cylinder
X1 228 Y1 70.52
X 334 Y 91.39149
X2 470 Y2 118.17
Second Floor
Second Floor
Second Floor

You might also like