INSTALL INSTRUCTIONS DC6-48-60-0-1B-01(-SS)

Installation Instructions:

DC6-48-60-0-1B-01
(CEQ. 10279)

Installation Instructions:

DC6-48-60-0-1B-01-SS
(ANT. 14706)

DC6-48-60-0-1B-01 with
Myers Hub Kit installed (included with each unit)

www.raycap.com
INSTALL INSTRUCTIONS DC6-48-60-0-1B-01(-SS)

Contents

Section Description Page

1 Copyright 2

1.1 Disclaimer 2

1.2 Warnings 2

2 Introduction 3

3 OVP Package Contents 3

3.1 Prerequisites 3

3.2 Tools 3

4.1 Definitions / Callouts 4

5 Opening Cover 5

6.1 Removing Touch Guards 5

7 Installing Ground Cable 6

8 Installing DC Cables -48V Connection Hardware 6

9.1 Installing DC Input Trunk Cables (8/6AWG) 7

10.1 Installing DC Output (Trunk or Jumper) Cables 7

11. Installing Touch Guards 8

12. Installing Alarm Cable 9

13.1 Closing and Securing Unit 9

Addendum 1: 4AWG Cable Trunk 10

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 1 of 14
DC6-48-60-0-1B-01(-SS) INSTALL INSTRUCTIONS

1.0 Copyright © Raycap, Inc. 2018 - All Rights Reserved

1.1 Disclaimer
The information in this document is subject to change without notice and describes only the
product defined in the introduction of this documentation. This documentation is intended for the
use of Raycap customers only for the purposes of the agreement under which the document is
submitted, and no part may be used, reproduced, modified or transmitted in any form or means
without the prior written permission of Raycap. The documentation has been prepared to be used
by professional and properly trained personnel, and the customer assumes full responsibility when
using it. Raycap welcomes customer comments as part of the process of continuous development
and improvement of the documentation.
Raycap has made all reasonable efforts to ensure that the instructions contained in this document
are adequate and free of material errors and omissions. Raycap will, if deemed necessary, explain
issues which may not be covered by this document.
The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Raycap shall have no liability for any error damage of any
kind resulting from the use of this document.

1.2 Warnings
Please read this manual prior to use to become familiar with the product’s numerous features and
operating procedures. To maintain the maximum degree of safety, follow the sequences as outlined.
Before using the product, read all instructions and cautionary markings on the product and on any
equipment connected to the product.

CAUTION:
Unless otherwise noted, product usage that is not recommended or sold by the product
manufacturer can result in risk of fire, electric shock, or injury to persons.
Do not operate the product if it has been damaged in any way. Return damaged products to
their manufacturer for repair or replacement.
Do not disassemble the product as incorrect reassembling can risk electrical shock or fire.
Do not bend fiber-optic cables beyond their minimum bend radius. Bending the cables beyond
their minimum bend radius can damage the cables and cause problems that are difficult to
diagnose.
Do not let fiber-optic cables hang free from the connector. Do not allow fastened loops of
cables to dangle, which stresses the cables at the fastening point.

WARNING:
Do not look directly into a fiber-optic transceiver or into the ends of fiber-optic cables. Fiber-
optic transceivers and fiber-optic cables connected to transceivers emit laser light that can
damage your eyes.
Do not stare into the laser beam or view it directly with optical instruments even if the interface
has been disabled.
Secure the cables so that they are not supporting their own weight. Place excess cable out of
the way in a neatly coiled loop. Placing fasteners on a loop helps cables maintain their shape.
Disconnect or disable the DC power source to the product prior to beginning its installation.
Ensure that the DC power source to the product remains de-energized until the completion of
the installation and after all connections have been verified to be correctly configured.
Electrostatic sensitive devices. ESD mitigative procedures, such as wearing wriststraps are to
be used during installation and maintenance.

For conditions other than those described above, please contact a Raycap Account Representative
at (208) 777-1166, (800) 890-2569 or www.raycap.com
Thank you for choosing quality products from Raycap.

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 2 of 14
INSTALL INSTRUCTIONS DC6-48-60-0-1B-01(-SS)

2.0 Introduction
In a split Radio Base Station (RBS) architecture the typical RBS consists of a Base Band Unit
(BBU) and Remote Radio Heads (RRH) connected by cabling. Power to the RRH is provided
through copper cables traveling from the DC power plant to the top of the tower or roof top.
This creates a conductive path, making the active equipment at the top and the base of the site
vulnerable to damage by direct lightning strikes. Protection systems must be able to withstand
direct lightning currents in order to protect the sensitive equipment. Raycap’s RRH solutions
featuring Strikesorb® SPD technology significantly enhance the reliability & availability of the
RRH site by providing superior electrical protection at the RRH and DC power plant.

3.0 OVP Package Contents


1 OVP Enclosure
1 Ground Lug - #6, Dual ¼" Stud, 1" P, Long, with window
2 M75 Inserts, for 6AWG Trunks and 8AWG Trunks
2 M75 Inserts, for 4AWG Trunks (See addendum 1 on page 10 for 4AWG)
3 M75 Inserts, for 8, 10 and 12AWG Jumpers

2 2½" Conduit fittings


2 ½" to 2" Conduit fitting adapters
Sil Bronze hardware for power connections

3.1 Prerequisites

This Document describes how to install the DC6-48-60-0-1B-01 / DC6-48-60-0-1B-01-SS


on site.

Installers of Raycap’s RRH surge protective and fiber/power management solutions must
be industry professionals who have attended training on the proper handling, installation
and cleaning of fiber-optic cable, and attended training on the installation of the equipment
by Raycap and/or the mobile operator. Installers are required to read this installation guide
thoroughly prior to installation of the Raycap RRH protection equipment.

3.2 Tools

#1 Flat blade screwdriver

#1 Philips screw driver

7/16" Nut Driver (for ground lug)

3/8" Nut Driver (for DC connections)

Torque Wrench/Tool

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 3 of 14
DC6-48-60-0-1B-01(-SS) INSTALL INSTRUCTIONS

Procedure
Definitions / Callouts

4.1 See illustration to identify Base Port Assembly Definitions

DC Jumpers DC DC Ground
Alarm (Out) Trunk Trunk
(In) (In)

Jumper Inserts: Trunk Inserts:


8, 10 and 12AWG 8/6AWG and 4AWG

-48V

Return

Main
Ground

Jumper ground and Trunk ground and


drain wire terminations drain wire terminations

4.2 See picture to identify


DC Power Port Cap
Assembly Definitions Cap

Gaskets may vary in


size and shape. Gasket

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 4 of 14
INSTALL INSTRUCTIONS DC6-48-60-0-1B-01(-SS)

Opening Cover

5. Open cover loosening the two screws


on the front of unit.

Removing the Touch Guard

6.1 There is (1) one touch guard covering


the DC connection lugs. Simply press
in on tab on white stand-off and
separate from touch guard. Repeat for
second stand-off.

Stand-Off (x2)

Touch Guard

6.2 Set touch


guards aside.

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 5 of 14
DC6-48-60-0-1B-01(-SS) INSTALL INSTRUCTIONS

Installing Ground Cable

7. Feed ground cable through ground


port and connect to ground lug.

This product is to be grounded to a


Common Bonding Network.

Only copper conductors shall be used


for grounding purposes.

Attach ground cable to Ground


Lug - #6, Dual ¼" Stud, 1" P, Long,
with window as shown. Tighten
nuts using a 7/16" nutdriver.

Torque: Using a torque wrench,


torque to 65 in-lbs.

Installing DC Cables
-48V Connection Hardware
Ground Lug - #6,
8. Each cable lug must be secured using Dual ¼" Stud, 1" P,
a nut, star washer, and a flat washer Long, with window
as pictured.
Nut

Star washer

Flat washer
*All lugs 5/8 pitch with #10 stud size
#8 Power Trunk RRH QTY Double Lugs for Power Double Lugs for Ground

6 12 Lugs (8AWG) 1 Lug (10-14AWG)

Burndy P/N # YA8CL-2TC10 YAV10-2TC10

Panduit P/N # LCD8-10A-L LCD10-10A-L

#6 Power Trunk

6 12 Lugs (6AWG) 1 Lug (8AWG)

Burndy P/N # YA6CL-2TC10 YA8CL-2TC10

Panduit P/N # LCD6-10A-L LCD8-10A-L

#4 Power Trunk

6 12 Lugs (4AWG) 1 Lug (8AWG)

Burndy P/N # YA4CL-2TC10 YA8CL-2TC10

Panduit P/N # LCD4-10A-L LCD8-10A-L

#12 Power Jumper

1 2 Lugs (12AWG) Jumper ground and drains


Burndy P/N # YAV10-2TC10 use mechanical lug terminal strip
4-14AWG
Panduit P/N # LCD10-10A-L

#10 Power Jumper

1 2 Lugs (10AWG) Jumper ground and drains


Burndy P/N # YAV10-2TC10 use mechanical lug terminal strip
4-14AWG
Panduit P/N # LCD10-10A-L

#8 Power Jumper

1 2 Lugs (8AWG) Jumper ground and drains


use mechanical lug terminal strip
Burndy P/N # YA8CL-2TC10
4-14AWG
Panduit P/N # LCD8-10A-L

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 6 of 14
INSTALL INSTRUCTIONS DC6-48-60-0-1B-01(-SS)

Installing DC Input Trunk Cables (8/6AWG)


*For 4AWG Trunk Installation see Addendum 1 on page 10

9.1 Feed DC trunk cable


through DC trunk port hole.

9.2 Cut wires to desired


length.

Insert cable into lug and


crimp to lug according to
AT&T color guide and lug
manufacturer’s
recommendations.

9.3 Tighten lugs using a 3/8"


nutdriver as shown.

Torque: Using a torque


wrench, torque
to 30 in-lbs.

Installing DC Output (Trunk or Jumper) Cables

10.1 Feed DC jumper cable


through DC jumper
port hole.

10.2 Cut wires to desired


length.

Insert cable into lug and


crimp to lug according to
AT&T color guide and lug
manufacturer’s
recommendations.

10.3 Tighten lugs using a 3/8"


nutdriver as shown.

Torque: Using a torque


wrench, torque
to 30 in-lbs.

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 7 of 14
DC6-48-60-0-1B-01(-SS) INSTALL INSTRUCTIONS

Install Touch Guard

11. Align touch guard over the two (2)


stand-offs and press down to secure.

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 8 of 14
INSTALL INSTRUCTIONS DC6-48-60-0-1B-01(-SS)

Installing Alarm Cable

12. Feed alarm cable through port cap


assembly.

Connect wires according to


your established color guide.

Note: If using a spade connector,


use #6 18-22AWG.

Connect alarm wires to


alarm lugs.

Closing and Securing Unit

13.1 Lock cover tightening the two


screws on the front of unit.

13.2 Installation complete.

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 9 of 14
DC6-48-60-0-1B-01(-SS) INSTALL INSTRUCTIONS

Addendum 1
4AWG Trunk Cable
See Page 6 for proper lug identification

Procedure
A1.1 Cut trunk cable to proper length so DC
conductors can reach furthest termination.

A1.2. Strip the outer jacket so 2" of outer jacket


remains inside unit.
(Make sure not to damage jacket of inner conductors or ground
and drain wires.)
-48V Return
A1.3. Strip A1 cable jacket 3.875" - 4.00". Supply
(Make sure not to damage the wire strands under jacket)

A1 A2 A3 B1 B2 B3

-48V Supply Red


Return Copper Wrap


Strip cable
jacket 3.875"- 4.00"


 
Cut trunk cable to
proper length so
DC conductors
can reach furthest
termination


Strip the outer jacket

2"
so 2" of outer jacket
remains inside unit.

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 10 of 14
INSTALL INSTRUCTIONS DC6-48-60-0-1B-01(-SS)

Procedure
A1.4. Unwrap Return-wires from A1 -48V
insulated cable, fan out Return wires then
twist into bundle.

A1.5. Strip 0.75" of insulation from the red


-48V wire and trim the exposed Return
wire to a length of 2.25".

A1.6. Slide boot on over cable.


Short end over -48V Supply, long end
over Return. On the return side, the
boot will need to be pulled back for
lug crimping. After crimping, roll boot
-48V over lug barrel.
Supply A1.7 Attach lugs to both -48V and Return
3.875" - 4.00"

cables and crimp.

Return A1.8 Attach cable lugs to unit. 


(Shown from right to left: A1, A2, A3...) Attach
cable lugs
A1.9. Repeat all 4AWG Trunk Cable instructions to unit
for additional cables.
 (A1, A2, A3, B1, B2, B3, C1, C2, C3, D1, D2 & D3).

A1.10. Attach ground and drain wires to unit per standard


installation instructions.

 
Attach and
Slide boot crimp lugs
 over cable
Strip 0.75"
of insulation Cut ground and
from the red drain wire to
-48V wire desired length as
and trim the shown.
exposed
Return wire Note: Different
to a length of NEMA enclosures
2.25" will need different
grounding wire
lengths.
.75"
Jumper ground Trunk ground
and drain wire and drain wire Main
terminations terminations Ground

2.
25
"

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 11 of 14
DC6-48-60-0-1B-01(-SS) INSTALL INSTRUCTIONS

Notes

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com
Page 12 of 14
DC6-48-60-0-1B-01(-SS) INSTALL INSTRUCTIONS

©Raycap • All rights reserved


(320-0832) Rev.C
www.raycap.com