Installation 2.

29
AC/DC Control Connection Diagrams

A B C

P1
33kV CTs
P1

VN E04
VB E02

VC E03
VA E01
P1

Z01
IAW1
52-1 Z02
Z03
IBW1
Z04
B (H2) P1
H1 H2 H3 Z05
A (H1)

SEL-787 Relay
ICW1
C (H3) Z06
30 MVA
a (X1) b (X2) Z07

IAW2
c (X3) Z08
X1 X2 X3 Z09

IBW2
Z10
Z11
52-2
ICW2
Z12

IN
P1
E09
E10

P1
11KV CTs
P1
a b c

Note: The CT secondary circuit must be grounded in the relay


Installing the optional 1 ACI/3 AVI voltage/current card in Slot E of the SEL-787 provides neutral current and REF
protection, as well as three-phase voltage inputs. These voltage inputs provide the relay with 20.0 to 70.0 Hz frequency
tracking, over-/undervoltage elements, frequency elements, power elements, and volts-per-hertz protection of the
transformer.
Refer to Figure 2.24, which illustrates tripping control of the two-power circuit breakers.

Figure 2.22 SEL-787 Provides Two-Winding Transformer Differential Protection With REF and Voltage-Based
Protection

Date Code 20230601 Instruction Manual SEL-787 Relay