Download as pdf or txt
Download as pdf or txt
You are on page 1of 119

R410A

Commercial Air Conditioners

Engineering Data
Mini TVR Individual

Model:

3 phase, 380-415V, 60Hz


4TVH0068BK000AA
4TVH0076BK000AA
4TVH0089BK000AA
4TVH0136BK000AA
4TVH0153BK000AA
Mini TVR Individual 60Hz

CONTENTS

Part 1 General Information ............................................................................ 3

Part 2 Outdoor Unit Engineering Data ....................................................... 17

Part 3 System Design and Installation ........................................................ 75

CONTENTS

1
Mini TVR Individual Series Engineering Data Book

2
Mini TVR Individual 60Hz
Mini TVR Individual 60Hz

Part 1
General Information
1 Indoor and Outdoor Unit Capacities ........................................................ 4

2 External Appearance ............................................................................... 6

3 Nomenclature ......................................................................................... 8

4 Combination Ratio ................................................................................ 11

5 Selection Procedure .............................................................................. 12

Part 1 – General Information

3
Mini TVR Individual 60Hz
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
Table 1-1.1: Indoor unit abbreviation codes
Abbreviation Abbreviation
Type Type
code code
Q1 One-way Cassette T1 High Static Pressure Duct
Q2 Two-way Cassette G Wall-mounted
Q4C Compact Four-way Cassette DL Ceiling & Floor
Q4 Four-way Cassette F Floor Standing
T2 Medium Static Pressure Duct Z Console

Table 1-1.2: Indoor unit capacity range


Capacity Capacity
Q1 Q2 Q4C Q4 T2 T1 G DL F
Mini TVR Individual Series Engineering Data Book

kW kBtu/h HP index
1.8 5 0.6 18 18 — — — — — — — —
2.2 7 0.8 22 22 22 22 — 22 — 22 — 22
2.8 9 1 28 28 28 28 28 28 — 28 — 28
3.6 12 1.25 36 36 36 36 36 36 — 36 36 36
4.5 15 1.6 45 45 45 45 45 45 — 45 45 45
5.6 19 2 56 56 56 — 56 56 — 56 56 56
7.1 24 2.5 71 71 71 — 71 71 71 71 71 71
8.0 27 3 80 — — — 80 80 80 80 80 80
9.0 30 3.2 90 — — — 90 90 90 90 90 —
10.0 34 3.6 100 — — — 100 — — — — —
11.2 38 4 112 — — — 112 112 112 — 112 —
14.0 48 5 140 — — — 140 140 140 — 140 —
16.0 55 6 160 — — — — — 160 — 160 —
20.0 68 7 200 — — — — — 200 — — —
25.0 85 9 250 — — — — — 250 — — —
28.0 96 10 280 — — — — — 280 — — —
40.0 136 14 400 — — — — — 400 — — —
45.0 154 16 450 — — — — — 450 — — —
56.0 191 20 560 — — — — — 560 — — —

1.2 Heat recovery ventilator


Table 1-1.4: Heat recovery ventilator capacity range
3
m /h 200 300 400 500 800 1000 1500 2000
Capacity
CFM 120 180 240 300 470 590 880 1180

4
Mini TVR Individual 60Hz
1.3 Outdoor Units
Table 1-1.5: Outdoor unit capacity range
Capacity Model Name
7HP 4TVH0068BK000AA
8HP 4TVH0076BK000AA
9HP 4TVH0089BK000AA
14HP 4TVH0136BK000AA
16HP 4TVH0153BK000AA
Notes:
1. Individual Series (Mini TVR Individual) outdoor units could not be combined.

Part 1 – General Information

5
Mini TVR Individual 60Hz
2 External Appearance
2.1 Indoor Units
Table 1-2.1: Indoor unit appearance

One-way Cassette Two-way Cassette

Q1 Q2

Compact Four-way Cassette Four-way Cassette

Q4C Q4
Mini TVR Individual Series Engineering Data Book

Medium Static Pressure Duct High Static Pressure Duct

T2 T1

Wall-mounted Ceiling & Floor

G DL

Floor Standing

6
Mini TVR Individual 60Hz
2.2 Heat Recovery Ventilator
Table 1-2.3: Heat recovery ventilator appearance
Heat Recovery Ventilator

2.3 Outdoor Units


Table 1-2.4: Outdoor unit appearance
7/8/9HP 14/16HP

Part 1 – General Information

7
Mini TVR Individual 60Hz
3 Nomenclature
3.1 Indoor Units
AC Series
MDV - D 28 Q4 / N1 - E

1 ○
2 ○3 ○4 ○5 ○
6

Legend
No. Code Remarks
1 MDV Midea VRF
2 D VRF indoor unit
3 28 Capacity index (the capacity in kW multiplied by 10)
Indoor unit type
Q1: One-way Cassette
Mini TVR Individual Series Engineering Data Book

Q2: Two-way Cassette


Q4C: Compact Four-way Cassette
Q4: Four-way Cassette
4 Q4 T2: Medium Static Pressure Duct
T1: High Static Pressure Duct
G: Wall-mounted
DL: Ceiling & Floor
F: Floor Standing
Z: Console
5 N1 Refrigerant type (N1: R410A)
6 E Design code

8
Mini TVR Individual 60Hz
DC series
M I 2 - 22 Q1 D H N1
1 ○
○ 2 ○
3 ○4 ○5 ○
6 ○
7 ○8

Legend
No. Code Remarks
1 M Midea
2 I VRF indoor unit
3 2 The 2nd generation VRF DC indoor unit
4 22 Capacity index (the capacity in kW multiplied by 10)
Indoor unit type
Q1: One-way Cassette
Q2: Two-way Cassette
Q4C: Compact Four-way Cassette
Q4: Four-way Cassette
5 Q1 T2: Medium Static Pressure Duct
T1: High Static Pressure Duct
G: Wall-mounted

Part 1 – General Information


DL: Ceiling & Floor
F: Floor Standing
Z: Console
6 D Series category (D: DC series)
Power supply
7 H Omit: 1 phase, 220-240V, 50Hz
H: 1 phase, 220-240V, 50/60Hz
8 N1 Refrigerant type (N1: R410A)

9
Mini TVR Individual 60Hz
3.2 Heat recovery ventilator
AC Series
HRV - 200

1 ○
2

Legend
No. Code Remarks
1 HRV Heat recovery ventilator
3
2 200 Airflow in m /h

DC Series
HRV - D 200

1 ○
2 ○
3

Legend
Mini TVR Individual Series Engineering Data Book

No. Code Remarks


1 HRV Heat recovery ventilator
2 D Series category (D: DC series)
3
3 200 Airflow in m /h

3.3 Outdoor Units


MDV - V 200 W / D R N1

1 ○
2 ○
3 ○
4 ⑤ ⑥ ⑦
Legend
No. Code Remarks
1 MDV Midea VRF
2 V All DC inverter
3 200 Capacity index (the capacity in kW multiplied by 10)
4 W VRF outdoor unit
5 D DC inverter compressor
6 R Power supply (R: 3 phase, 380-415V, 50Hz)
7 N1 Refrigerant type (N1: R410A)

10
Mini TVR Individual 60Hz
4 Combination Ratio

Sum of capacity indexes of the indoor units


Combination ratio =
Capacity index of the outdoor unit

Table 1-4.1: Indoor and outdoor unit combination ratio limitations

Type Minimum combination ratio Maximum combination ratio


Mini TVR Individual
50% 130%
outdoor units

Table 1-4.2: Combinations of Indoor and outdoor units


Outdoor unit capacity Sum of capacity indexes of Sum of capacity indexes of connected indoor Maximum number of
Capacity connected indoor units (standard units (fresh air processing units and standard connected indoor
kW HP
index indoor units only) indoor units together) units
20 7 200 100 to 260 100 to 200 10
22.4 8 224 112 to 291.2 112 to 224 11
26 9 260 130 to 338 130 to 260 12
40 14 400 200 to 520 200 to 400 14
45 16 450 225 to 585 225 to 450 15

Part 1 – General Information

11
Mini TVR Individual 60Hz
5 Selection Procedure
5.1 Procedure
Step 1: Establish design conditions

Design temperature and humidity (indoor and outdoor)


Required heat load of each room
System peak load
Piping length, level differences
Indoor unit specifications (type and quantity)
Step 2: Select indoor units

Decide indoor unit safety factor


Mini TVR Individual Series Engineering Data Book

Select indoor unit models ensuring that:


Indoor unit capacity corrected for indoor air temperature WB1 ≥ Required heat load × Indoor unit safety factor

Step 3: Select outdoor unit

Determine required total heat load on the outdoor unit

Use the sum of the peak load of each Use the system peak
room load

Provisionally select outdoor unit capacity based on combination ratio


limitations

Confirm that the number of indoor units connected to the outdoor unit is within
limitation

Correct cooling and heating capacities of the outdoor unit for the following items:
Outdoor air temperature / Indoor air temperature WB / Combination ratio / Piping length, level
difference / Piping heat loss / Frost accumulation (for heating capacity only)

No
Is corrected outdoor unit capacity ≥ Required total heat load on outdoor
unit?
Yes

VRF system selection is complete


Notes:
1. If the indoor design temperature falls between two temperatures listed in the indoor unit's capacity table, calculate the corrected capacity by
interpolation. If the indoor unit selection is to be based on total heat load and sensible heat load, select indoor units which satisfy not only the total
heat load requirements of each room but also the sensible heat load requirements of each room. As with total heat capacity, the sensible heat capacity
of indoor units should be corrected for indoor temperature, interpolating where necessary. For the indoor unit capacity tables, refer to the indoor unit
technical manuals.

12
Mini TVR Individual 60Hz
5.2 Example
The following is a selection example based on total heat load for cooling.

Figure 1-5.1: Room plan


Room D Room E

Room A

Room B Room C

Step 1: Establish design conditions


 Indoor air temperature 25°C DB, 18°C WB; outdoor air temperature 33°C DB.
 Determine peak load of each room and system peak load. As shown in Table 1-5.1, the system peak load is 19.3kW.

Table 1-5.1: Required heat load of each room (kW)


Time Room A Room C Room D Room E Room F Total
9:00 4.5 2.7 2.7 1.9 1.9 13.7
12:00 5.2 3.6 3.6 2.8 2.8 18
14:00 5.7 3.8 3.8 3.0 3.0 19.3
16:00 5.4 3.4 3.4 2.6 2.6 17.4

Part 1 – General Information


 The maximum piping lengths and level differences in this example are as given in Figure 1-5.2.
Figure 1-5.2: System diagram

Outdoor
Unit

Level Equivalent length of piping 60m


difference
40m
Indoor Indoor Indoor Indoor Indoor
Unit Unit Unit Unit Unit

 Indoor unit type for all rooms: Medium Static Pressure Duct (T2).

Step 2: Select indoor units


 In this example, a safety factor is not used (i.e. the safety factor is 1).
 Select indoor unit models using the medium static pressure duct cooling capacity table. Each indoor unit's corrected
capacity needs to be greater than or equal to the peak load of the relevant room. The selected indoor units are
shown in Table 1-5.3.

13
Mini TVR Individual 60Hz
Table 1-5.2: Extract from medium static pressure duct (T2) cooling capacity table
Indoor air temperature
Capacity 14°C WB 16°C WB 18°C WB 19°C WB 20°C WB 22°C WB 24°C WB
Model
index 20°C DB 23°C DB 26°C DB 27°C DB 28°C DB 30°C DB 32°C DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
22 1.5 1.4 1.8 1.5 2.1 1.6 2.2 1.6 2.3 1.7 2.4 1.5 2.4 1.5
28 1.9 1.7 2.3 1.9 2.6 2.1 2.8 2.1 3.0 2.1 3.1 2.0 3.1 1.9
36 2.5 2.1 2.9 2.3 3.4 2.5 3.6 2.6 3.8 2.7 4.2 2.8 3.9 2.3
45 3.1 2.6 3.7 2.8 4.2 3.1 4.5 3.2 4.8 3.2 4.9 3.1 5.1 2.9
56 3.9 3.0 4.6 3.3 5.3 3.6 5.6 3.7 5.9 3.8 6.2 3.7 6.2 3.4
T2
71 4.9 3.9 5.8 4.3 6.7 4.7 7.1 4.9 7.5 4.8 7.8 4.6 7.8 4.3
80 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.5 8.8 5.2 8.8 4.8
90 6.2 5.3 7.3 5.8 8.4 6.3 9.0 6.4 9.6 6.5 9.9 6.1 9.9 5.7
Mini TVR Individual Series Engineering Data Book

112 7.7 6.4 9.1 7.1 10.5 7.7 11.2 7.8 11.9 8.1 12.5 7.8 12.5 7.4
140 9.7 7.8 11.3 8.6 13.2 9.6 14.0 9.8 14.8 9.8 15.7 9.7 15.4 8.8
Abbreviations:
TC: Total capacity (kW); SHC: Sensible heat capacity (kW)

Table 1-5.3: Selected indoor units


Room A Room B Room C Room D Room E
Peak heat load (kW) 9.3 5.1 5.1 4.2 4.2
Selected indoor unit 4TVD0038EF000AA 4TVD0018EF000AA 4TVD0018EF000AA 4TVD0015EF000AA 4TVD0015EF000AA
Corrected TC (kW) 10.5 5.3 5.3 4.2 4.2

Step 3: Select outdoor unit


 Determine the required total heat load from the indoor units to the outdoor unit based on either the sum of the
peak loads of each room or the system peak load. In this example, it is determined based on the system peak load.
Therefore, the required heat load is 19.3kW.
 Provisionally select an outdoor unit using the sum of the capacity indexes (CIs) of the selected indoor units (as
shown in Table 1-5.4), ensuring that the combination ratio is between 50% and 130%. Refer to Table 1-5.5. As the
sum of CIs of the indoor units is 233, all outdoor units are potentially suitable. Start from the smaller, which is the
7HP unit.

Table 1-5.4: Sum of indoor unit capacity indexes


Model Capacity Index No. of units
4TVD0024EF000AA 71 1
4TVD0015EF000AA 45 2
4TVD0012EF000AA 36 2

Sum of CIs 233

Table 1-5.5: Combinations of Indoor and outdoor units


Outdoor unit capacity Sum of capacity indexes of Sum of capacity indexes of connected
Capacity connected indoor units indoor units (fresh air processing units
kW HP
index (standard indoor units only) and standard indoor units together)
20 7 200 100 to 260 100 to 200
22.4 8 224 112 to 291.2 112 to 224
26 9 260 130 to 338 130 to 260
40 14 400 200 to 520 200 to 400
45 16 450 225 to 585 225 to 450
14
Mini TVR Individual 60Hz
 The number of connected indoor units is 5 and the maximum number of connected indoor units on the 7HP
outdoor unit is 10, so the number of connected indoor units is within the limitation.
 Calculate the corrected capacity of the outdoor unit:
a) The sum of the indoor unit CIs is 233 and the CI of the 7HP outdoor unit (4TVH0068BK000AA) is 200, so the
combination ratio is 233 / 200 = 116.5%.
b) Using the outdoor unit’s cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor
air temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.6 and 1-5.7.

Table 1-5.6: Extract from Table 2-7.1 4TVH0068BK000AA Table 1-5.7: Cooling capacity calculated by
cooling capacity interpolation
Indoor air temp. Indoor air temp.
Outdoor (°C DB / °C WB) Outdoor (°C DB / °C WB)
air 25.8 / 18.0 air 25.8 / 18.0
CR CR
temp. temp.
(°C DB) TC PI (°C DB) TC PI
kW kW kW kW
31 21.1 5.72
120% 33 20.8 5.94 120% 33 20.8 5.94
35 20.4 6.15 1
B = 20.66
31 20.6 5.59
110% 33 20.4 5.89 110% 33 20.4 5.89
35 20.1 6.11

Part 1 – General Information


Notes:
1. 20.4 + (20.8 – 20.4) × (116.5 – 110) / (120 – 110) =
20.66

c) Find the correction factor for piping length and level difference (“K1”)

Figure 1-5.3: V4+i rate of change in cooling capacity


0.90

H(m)
0.87

0.84
0.85

0.81
0.92

50
40
0.95

K1 = 0.898
30
0.97

20
1.0

10
0
10 20 30 40 50 60 70 80 90 100 110 120
L(m)
0
-10
1.0

-20
0.97

-30
0.95

-40
0.87
0.92
0.90

0.85
0.84

d) Calculate the corrected capacity of 4TVH0068BK000AA (“C”) by using K1:

C = B × K1 = 20.66 × 0.898 =18.55kW

 The corrected capacity 18.55 kW is lower than required total heat load 19.3kW, so selection is not complete. Step 3
should be repeated from the point where the outdoor unit capacity is provisionally selected.

Repeat Step 3: Select outdoor unit


 Determine the required total heat load from the indoor units to the outdoor unit based on either the sum of the
peak loads of each room or the system peak load. In this example, it is determined based on the system peak load.
Therefore, the required heat load is 19.3kW.
 Provisionally select an outdoor unit using the sum of the capacity indexes (CIs) of the selected indoor units (as
15
Mini TVR Individual 60Hz
shown in Table 1-5.4), ensuring that the combination ratio is between 50% and 130%. Refer to Table 1-5.5. As the
sum of CIs of the indoor units is 23. For the 7HP unit is not suitable, try to select 8Hp unit.
 The number of connected indoor units is 5 and the maximum number of connected indoor units on the 8HP
outdoor unit is 11, so the number of connected indoor units is within the limitation.
 Calculate the corrected capacity of the outdoor unit:
a) The sum of the indoor unit CIs is 233 and the CI of the 8HP outdoor unit (4TVH0076BK000AA) is 224, so the
combination ratio is 233 / 224 = 104%.
b) Using the outdoor unit’s cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor
air temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.10 and 1-5.11.

Table 1-5.8: Extract from Table 2-7.2 4TVH0076BK000AA Table 1-5.8: Cooling capacity calculated by
cooling capacity interpolation
Indoor air temp. Indoor air temp.
Outdoor (°C DB / °C WB) Outdoor (°C DB / °C WB)
air 25.8 / 18.0 air 25.8 / 18.0
CR CR
temp. temp.
(°C DB) TC PI (°C DB) TC PI
Mini TVR Individual Series Engineering Data Book

kW kW kW kW
31 23.0 6.23
110% 33 22.9 6.57 110% 33 22.9 6.57
35 22.5 6.81 1
B = 21.76
31 21.0 5.41
100% 33 21.0 5.76 100% 33 21.0 5.76
35 21.0 6.15
Notes:
1. 21 + (22.9 – 21.0) × (104 – 100) / (110 – 100) = 21.76
c) Find the correction factor for piping length and level difference (“K1”)

Figure 1-5.4: V4+i rate of change in cooling capacity


0.90

H(m)
0.87

0.84
0.85

0.81
0.92

50
40
0.95

K1 = 0.898
30
0.97

20
1.0

10
0
10 20 30 40 50 60 70 80 90 100 110 120
L(m)
0
-10
1.0

-20
0.97

-30
0.95

-40
0.87
0.92
0.90

0.85
0.84

d) Calculate the corrected capacity of 4TVH0076BK000AA (“C”) by using K1:

C = B × K1 = 21.76 × 0.898 =19.5kW

 The corrected capacity 19.5 kW is larger than required total heat load 19.3kW, so selection is complete.

16
Mini TVR Individual 60Hz

Part 2
Outdoor Unit
Engineering Data
1 Specifications ........................................................................................ 18

2 Dimensions ........................................................................................... 20

Part 2 - Outdoor Unit Engineering Data


3 Installation Space Requirements ........................................................... 21

4 Piping Diagrams .................................................................................... 23

5 Wiring Diagrams .................................................................................... 25

6 Electrical Characteristics ........................................................................ 27

7 Capacity Tables...................................................................................... 28

8 Operating Limits .................................................................................... 70

9 Sound Levels ......................................................................................... 71

10 Accessories.......................................................................................... 73

17
Mini TVR Individual 60Hz
1 Specifications
Table 2-1.1: 7/8/9HP specifications
Model 4TVH0068BD000AA 4TVH0076BD000AA 4TVH0089BD000AA
Power supply V-Ph-Hz 380-415/3/60
Capacity kW 20 22.4 26
Cooling Power input kW 6.1 6.8 7.6
EER 3.28 3.29 3.42
Capacity kW 22 24.5 28.5
Heating Power input kW 6.1 5.9 6.8
COP 3.61 4.15 4.19
Model LNB42FSAMC LNB53FCAMC
Type Rotary
Brand MITSUBISHI
Quantity 1
Mini TVR Individual Series Engineering Data Book

Compressor
Capacity kW 13.98 16.86 16.86
Input kW 4.27 5.2 5.2
Crankcase heater W 25
Refrigerant oil type FV50S
Model WZDK170-38G-1
Type DC motor
Quantity 2
Brand Panasonic
Outdoor fan
Insulation class E
motor
Safe class IP×4
Input W 260(up)/200(down) 250(up)/185(down) 250(up)/185(down)
Output W 210(up)/160(down) 200(up)/150(down) 200(up)/150(down)
Rated current A 2.1(up)/1.7(down) 1.7(up)/1.4(down) 1.7(up)/1.4(down)
3
Outdoor air flow m /h 10999 10494 10494
Sound pressure level dB(A) 59 59 60
Connectable Total capacity % 50-130
indoor unit Max. quantity 10 11 12
Net dimension
mm 1120×1558×528
(W×H×D)
Outdoor uint Packing
mm 1270×1720×565
(W×H×D)
Net/Gross weight mm 137/153 146.5/162.5 147/163
Type R410A
Refrigerant
Factory charged kg 4.8 6.2 6.2
Throttle type Electronic expansion valve
Design pressure (Hi/Lo) MPa 4.4/2.6
Refrigerant Liquid pipe mm Ф9.53 Ф9.53 Ф9.53
piping Gas pipe mm Ф19.1 Ф19.1 Ф22.2
o
Ambient temp. Cooling C -15~46
range Heating
o
C -15~24
Notes:
Capacities are based on the following conditions:
o o o o
1. Cooling: Indoor temperature 27 C DB/19 C WB; Outdoor temperature 35 C DB/24 C WB;
o o o o
2. Heating: Indoor temperature 20 C DB/15 C WB; Outdoor temperature 7 C DB/6 C WB;
3. Piping length: Interconnecting piping length 7.5m, level difference of zero;
4. Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor;
5. The above data may be changed without notice for future improvement on quality and performance.

18
Mini TVR Individual 60Hz
Table 2-1.2: 14/16HP specifications
Model 4TVH0136BD000AA 4TVH0153BD000AA
Power supply V-Ph-Hz 380-415/3/60
Capacity kW 40.0 45.0
Cooling Power input kW 11.9 13.6
EER 3.35 3.32
Capacity kW 45.0 50.0
Heating Power input kW 11.1 12.7
COP 4.05 3.93
Model LNB42FSAMC LNB53FCAMC
Type Rotary
Brand MITSUBISHI
Quantity 2
Compressor
Capacity kW 13.98×2 16.86×2
Input kW 4.27×2 5.2×2
Crankcase heater W 25×2

Part 2 - Outdoor Unit Engineering Data


Refrigerant oil type FV50S
Model WZDK560-38G(B)+YDK320-6A
Type DC+AC
Quantity 2
Brand Nidec,panasonic,welling/welling,matchwell
Outdoor fan
Insulation class DC: E/AC: F
motor
Safe class IP44
Input W 580/422
Output W 560/320
Rated current A 3.84+2.65
3
Outdoor air flow m /h 16575 16575
Sound pressure level dB(A) 62 62
Connectable Total capacity % 50-130
indoor unit Max. quantity 14 15
Net dimension (W×H×D) mm 1360×1650×540 1460×1650×540
Outdoor uint Packing (W×H×D) mm 1450×1785×560 1550×1785×560
Net/Gross weight mm 240/260 275/290
Type R410A
Refrigerant
Factory charged kg 9 12
Throttle type Electronic expansion valve
Design pressure (Hi/Lo) MPa 4.4/2.6
Liquid pipe mm Ф12.7 Ф12.7
Refrigerant piping
Gas pipe mm Ф22.2 Ф25.4
o
Ambient temp. Cooling C -5~48
o
range Heating C -15~24
Notes:
Capacities are based on the following conditions:
o o o o
1. Cooling: Indoor temperature 27 C DB/19 C WB; Outdoor temperature 35 C DB/24 C WB.
o o o o
2. Heating: Indoor temperature 20 C DB/15 C WB; Outdoor temperature 7 C DB/6 C WB.
3. Piping length: Interconnecting piping length 7.5m, level difference of zero.
4. Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor.
5. The above data may be changed without notice for future improvement on quality and performance.

19
Mini TVR Individual 60Hz
2 Dimensions
Figure 2-2.1: 7/8/9HP dimensions (unit: mm)

1558

1120
Mini TVR Individual Series Engineering Data Book

668 205.8

494
528
414
400

Figure 2-2.2: 14/16HP dimensions (unit: mm)


1650

A B 505
540
500
475
450

Model A(mm) B(mm) C(mm)


40kW 175 505 1360
45kW 225 555 1460

20
Mini TVR Individual 60Hz
3 Installation Space Requirements
Figure 2-3.1: 7/8/9HPSingle
single unitunit installation
installation (unit: mm)
(Wall or obstacle)

Air inlet

> 300
>300
Maintain the electric
wire and pipeline
Air inlet
>3000 >600

Air outlet

Figure 2-3.2: 7/8/9HP multiple unit installation


Parallel connect(unit:
the mm)
two units or above

Part 2 - Outdoor Unit Engineering Data


>300
>600

>3000

Parallel connect the front with rear sides

>3000 >1000 >6000 >4000 >300

21
Mini TVR Individual 60Hz
Figure 2-3.3: 14/16HP single unit installation (unit: mm)

> 600
(Wall or obstacle)

Air inlet

> 400
>400 Maintain
channel
Air inlet >600

> 4000
Air outlet

Figure 2-3.4: 14/16HP multiple unit installation (unit: mm)


Mini TVR Individual Series Engineering Data Book

>400
>600

>4000
> 600

>4000 >1000 >8000 >6000 >400

22
Mini TVR Individual 60Hz
4 Piping Diagrams
Figure 2-4.1: 7/8/9HP piping diagram

High pressure
gas-liquid
separator

Low pressure
gas-liquid
separator

Part 2 - Outdoor Unit Engineering Data


Notes:
20Kw doesn’t have SV6

Figure 2-4.2: 14/16HP piping diagram


SV6

EXVA High pressure valve

EXVB
T3 T4

ST1 Low pressure valve

High
pressure
switch SV7
Low
pressure
separator

separator

switch
Oil

Oil

SV2
Gas-liquid
separator
Inverter

Inverter
comp.

comp.

SV41 SV42

Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation
efficiency is up to 99%.
2. Gas-liquid separator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.

23
Mini TVR Individual 60Hz
3. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Four-way valve(ST1):
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the heat
exchanger functions as a condenser; when open, the heat exchanger functions as an evaporator.
5. Solenoid valve SV2:
Protects the compressor. If compressor discharge temperature rises above 98°C, SV2 opens and sprays a small
amount of liquid refrigerant to cool the compressor. SV2 closes again once the discharge temperature has fallen
below 85°C.
6. Solenoid valve SV4:
Returns oil to the compressor. Opens once the compressor has run for 200 seconds and closes 600 seconds later and
then opens for 3 minutes every 20 minutes.
7. Solenoid valve SV6
By-pass the refrigerant. It will be closed in heating and standby mode. It will be open in forced cooling and oil return
Mini TVR Individual Series Engineering Data Book

mode. In cooling mode, it will be open or closed according to discharge pressure.


8. Solenoid valve SV7:
Allows refrigerant return to the compressor directly. Opens when indoor air temperature is close to the set
temperature to avoid frequent compressor on/off.
9. High and low pressure switches:
Regulate system pressure. When system pressure rises above the upper limit or falls below the lower limit, the high or
low pressure switches turn off, stopping the compressor. After 5 minutes, the compressor restarts.

24
RED 3

BLACK
B LU E P N +15V CN205
CN2 (CN3)
C N5 IC20 1
5 Wiring Diagrams

IPMMODULE Code Name


E N C3 S6 S5
10 Inverter compressor
ON Dial-up function definition COMP.
CN201
P N V W FAN- UP,FAN-DOWN Fan Motor
RED U 1 2 1 2 3
CN1 STF1 4-way valve
2 S5 f unc tio n de fin itio n
CN48 STF1
Figure 2-5.1: 7/8/9HP wiring diagram

S5 SV(2,4,5,6,7 ) Solenoid valve


ON He a ti n g p ri o ri ty
2 CN47 EE V Electric expansion valve
S V4 C N250 mo d e ( se tte d by
1 2 3 fa cto ry d e fau l t) HEAT1 Crankcaseheating
2 CN46 S V7 DSP2 S5
IC201 ON
L-PRO Pipelinelow-pressure switch
2 Co o l i n g p ri o ri ty
CN45 SV2 H-PRO Pipeline high-pressure switch
m o de

CN4
2
T5 1 2 3
CN44 POWER-C K1 Dischargetemperatureswitch
I+ S 5
V ON In i ti al -s ta rt XS1-XS2,XP1-XP2 Middle terminal
2
V U CN42 S V6
p ri o ri ty m o d e T3 Piping temperature sensor
12 3

CN7
U W W C N119/ CN121
CN27 S5 T4 Outdoor environment temperature sensor
CN120/ CN122
CO MP . ON Inverter compressor discharge
K1 He a ti n g o n l y m o de T5 temperature sensor
Y/G CN13 H_PRO
1 2 3 KM(B) Contactor
CN 14 C T1 S5

CN24
L-PRO E1,E2 Filter capacitor
CN20 CN9 ON
CN41 Co o l i n g o n l y m od e R1,R2 Cement resistor
1 2 3 PTC Thermal resistor
RED BLACK 2
R1 R2 XT2 Big 4-phase terminal
EEV. T3
STF1 S V4 SV7 SV2 SV6 H EA T1 L-3 Reactor
T4 S 6 f unc tio n de fin itio n:
CT1,IC201 Currentinstrument transformer
S6
Y /G Y/ G ON
BD-1 Bridge rectifier
RED Au t o ma t i c
CN101 ZR10 Varistor
1 2 a d d re ss i n g
C1,C2 Ferrite core
BLAC K S 6
L3’ L3 No n a u tom a ti c
YELLO W RED BLU E ON
CN202

CN103
5 FA N C N206 a dd re s s in g (s e tte d
CAP2 UP YELLO W L2’ L2 1 2 Contentsdisplayed by DSP2

CN107
CAP3 WHI T E b y fa c tor y d e fau l t)
CN205 CN201 S6 H0 COMM. Fault between Ir341and main chip
5 YELLO W L1’ L1 ON
FAN

CN104
CN204 RED Clear indoor unit H1 COMM.Fault betweencommunicationchip and mainchip
DOWN C N200 address

C N109
BL UE
FIL TER BOARD 1 2 H4 3 times of P6 p rotection in 30 minu tes
CN209 N BL ACK H5 3 times of P2 p rotection in 30 minu tes
CN203
CN212 H7 The number of i ndoor units decreases.

CN150 CN207 H8 Reserved


F AN-UP FAN-DOWN 3 CN211
Y/G Y/G HF M-HOME for the indoor and outdoor units
does not match.
E1 Reserved
ORANGE
PTC2 PTC1 E2 Communicati onf ault between the out door
E NC2 f un ctio n d efin itio n: and i ndoor units.
T T 4 T3 & T4 temperature sensor fault.
( Di a l -u p c a nn o t b e c h an g e d .) E4
Volt age protection fault or a lack of
D1 C T1 E5 Phase B 、Phase N.
RED
10 In d o o ru n i t E6 DCfan motor fault .
RED E NC 2 c a p a ci ty d i a l -u p Discharge temperature sensor faul t.

4
B ROWN BROWN E7
YELLO W BLA CK 0 : 8HP( 25.2KW/26KW) Afan in theA region run for more
RED BLUE EA
1 :10HP(28KW) than 5 minutes in Heat mode
KM1 YELLO W F: 7HP( 22.4KW) Eb 2 time s of E6 pro tection in 10 minu tes
2 1 Middle connecti on CN4
panel c om ponents Invert er compressor top high
Z XT2 P0 temperat ureprot ection
4 3 A B C N High pressure protection
Z R1 YELLO W P1

~ 3 ~ 2 ~1
O RA NGE 5 E NC3 f un ctio n d efin itio n: P2 Low pressure protection
6 K1 K2 E O A E X Y E P Q E

5
P3 Outdoor Inputcurrent protection
21 22 BLACK E N C3 Compressor discharge high protection
Ou td o o ru n i t n etw o rk P4
A2 A1 a dd re s s d i a l -u p P5 Outdoor condenser high temperature protection
L-3 BLUE RED
0 -F i n d ic a te s 0 -1 5 . P6 Inverter module protection
P8 Typhoon protection
POWER SUPPLY PE Evaporator high temperature protection
Note: Us e a three-c ore s hiel ding wire and
ensure the s hielding lay er i s grounded.
Mini TVR Individual 60Hz

25
Part 2 - Outdoor Unit Engineering Data
Mini TVR Individual Series Engineering Data Book

26
CODE NAME
2 2 COMP(INV1)、
COMP(INV2) Inverter compressor
2
B LA CK R ED 2
W HI TE BROWN FAN_A DC fan
FAN_B AC fan
ST1 Main 4-way valve
N P N P (THE SETTING OF ENC2 IS NOT ALLOWED TO ALTER DISCRETIONARILY.) 2 2
KM(A、B) Contactor
2 2 B LA C K
ENC2 0 1 2 3 4 5 6 R ED XT2
BROWN W HI TE 4-phase terminal
CAPACITY SETTING 6P 8P 10P 12P 14P 16P 18P L-PRO Low pressure ON/OFF switch
DC FILTER BOARD B DC FILTER BOARD A
P H-PRO High pressure ON/OFF switch
BROWN
3
B LU E FAN CONTROL PANEL FAN_A E XVA、EXVB Elctronic expansion valve

CN3
RED
N PTC-IN P N PTC-IN P B LA CK
N XS4-XS6 Middle terminal
BROW N
T3A T4 T5 H_PRO HGS_1 HGS_2 B LU E
CN4 T3B XP4-XP6 Middle terminal
CN1 W HI TE
3 IC16 IC17 T3A、T3B Condenser pipe Temp.sensor
Figure 2-5.2: 14/16HP wiring diagram

R ED R ED BROWN BR OW N
L_PRO

BLUE
RED
T3A T3B T4 Outdoor Temp.sensor

BLUE
I+
I+

BROWN

XP 6 X S6
( WH IT E)
RED GAS_1 GAS_2 Temp.sensor of Inverter

(BLACK)
BR OWN T4 T5
5L3
module radiator
1L1 A1 1L1 5L3 A1 N1 P1 N1 P1
Mini TVR Individual 60Hz

GAS_2 CN3 CN3 GAS_1、GAS_2 Discharge Temp.sensor


P N P N

X P5 X S5
5 B LA CK of inverter compressor
GAS_1 R ED Y EL LO W +15V

YELLO WX P4 X S4
KM( A) +15V Discharge Temp.switch
HGS_1、HGS_2
2T1 6T3 A2 2T1 6T3 A2 CN21 CN20 CN10 CN11 CN27 CN2 CN25 CN17 CN18 10 of inverter compressor
INVERTER MODULE CN1 INVERTER MODULE

CN1
B A W HI TE H-YL1 L-YL1 Low pressure sensor
KM(B )

BLUE
CN7
10

ORANGE
ORANGE
BLA CK H-YL1 High pressure sensor
W HI TE L-YL1
CN2

L-1 ENC2

BLU E
BLU E
BLU E
BLU E
ZR L-2 ZR SW1 COOL U V W U V W

CN6
S11 5 L-1、L-2 Reactor
O RA NG E A O RA NG E ON EXVA CT1、CT2、

CN36 CN14 CN13


B Current inductor

CN54
1 2 3 4 SW2 CHECK 5 IC16、IC1 7
5 4 5 4 POWER
EXVB

CN35
BD-B BD-A TRANS1、TRANS2 Power transformer
3

CN55
3 2 1 3 2 1 BD-A、BD-B 3-phase bridge rectifier

CN19
MAIN CONTROL BOARD
2 ZR Varistor
DSP2 DSP1

CN43
R ED R ED R ED BRO W N BROWN BROWN SV1-SV7 Solenoid valve
RED
BLUE

BLACK
BLACK

BLUE

CN12
R ED

CN15 TRANS2
CN41 CN211 V V HEAT、
U W U W HEAT1 Crankcase heater

CN29

CN16
CN59

CN57

YELLOW/GREEN
L1’ L2’ L3’ L1’ L2’ L3’ TRANS1

CN51 SV4
CN49 SV2

CN61 HEAT1
CN47 ST2
CN50 SV4
CN48 SV1
CN56 SV7
GND_2

CN60 HEAT
CN46 ST1
CN53 SV6
CN52 SV4_2

BROWN
COMP(INV1) COMP(INV2) DSP1 and DSP2 display content

CN30

CN58
CN1
YELLOW/GREEN

GND_2
Y ELL OW/ GREEN

CN212
B LU E E1 Phase protection
E2 COMM.Error with indoor unit

N
FILTER BOARD B FILTER BOARD A COMP B

RED
COMP A

F AN_H
FAN_L

BLACK
WHITE
BLUE
GND_1 GND_1 E4 Outdoor Temp.sensor error

YELLOW/GREEN
N N E5 Voltage protecation
2
L1 L2 L3 xH0 COMM.Error between IR341 and main chip

CN150
L1 L2 L3 GAS_1 for COMP A,GAS_2 for COMP B。

YELLOW/GREEN YELLOW/GREEN
H1 COMM.Error between 0537 and main chip

RED
BLUE
YELLOW
(THE SETTING OF S11 IS NOT ALLOWED H4 3 times of P6 protection in 60 minutes
TO ALTER DISCRETIONARILY.)
R ED W HI TE B LU E B LA CK RED WHITE B LU E B LA CK FAN_B H5 3 times of P2 protection in 60 minutes
W HI TE S1 1

Y ELL OW/ GR EEN


CT1 CT2 ON 6、8 、10 H P H6 3 times of P4 protection in 100 minutes

BLUE
WHITE
H7 QTY.Of indoor units decreases error
B LU E Outdoor unit setting
1 2 3 4 P0 Inverter compressor top Temp.Protection
S1 1
P1 High pressure protection
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE

BLUE

ON 12-18HP
FAN CAPACITOR P2 Low pressure protection
BROWN
Outdoor unit setting
BROWN

1 2 3 4
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE
BLUE

BLUE

R ED W HI TE B LU E BLACK xP3 Compressor current protection


S 8 Re se rve P4 Discharge Temp.Protection
BROWN

BROWN
P5 High condenser Temp.Protection

ON
1 2
CN4 CN5
xP6 Inverter module protection
A B C N ST2 ST1 SV6 SV4_2 SV4 SV4 SV2 SV1 SV7 P9 DC fan protection
HEAT HEAT1
K1 K2 E O A E X Y E P Q E PL The Temp.protection of inverter module
COMP B COMP A HEAT1 for COMP A,HEAT for COMP B。
XT2 C7 3 times of PL protection in 60 minutes
If had SV4_2,SV4 for COMP A, dF Defrosting
SV4_2 for COMP B。 d0 Oil returning
Heat Sink A Case Heat Sink B Case
T o o ut do or To ki lo - T o in do or To indoor
u ni ts c en tr al wa tt h ou r un it s unit s X display in DSP1,other display in DSP2;
THREE-PHASE POWER m on it or me te r c en tr al commun ica
m on it or -tion bus X reprsents for a system,1-A system,2-B system。
Mini TVR Individual 60Hz
6 Electrical Characteristics
Table 2-6.1: Outdoor unit electrical characteristics
Power Supply1 Compressor OFM
Capacity Model Min. Max.
Hz Volts MCA2 TOCA3 MFA4 MSC5 RLA6 kW FLA
volts volts
7 4TVH0068BD000AA 50 380-415 342 456 18.75 18 25 / 12 2×0.17 2.1+1.7
8 4TVH0076BD000AA 50 380-415 342 456 25 23 25 / 15.4 2×0.17 2.1+1.7
9 4TVH0089BD000AA 50 380-415 342 456 26.25 23 32 / 15.4 2×0.17 2.1+1.7
14 4TVH0136BD000AA 50 380-415 342 456 42.5 39.84 60 / 12×2 0.56+0.32 2.65+3.84
16 4TVH0153BD000AA 50 380-415 342 456 52.5 49.84 60 / 15.4×2 0.56+0.32 2.65+3.84

Abbreviations:
MCA: Minimum Circuit Amps; TOCA: Total Over-current Amps; MFA: Maximum Fuse Amps; MSC: Maximum Starting Current (A); RLA: Rated Load Amps; FLA: Full
Load Amps

Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable
voltage variation between phases is 2%.
2. Select wire size based on the value of MCA.

Part 2 - Outdoor Unit Engineering Data


3. TOCA indicates the total overcurrent amps value of each OC set.
4. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
5. MSC indicates the maximum current on compressor start-up in amps.
6. RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB.

27
Mini TVR Individual 60Hz
7 Capacity Tables
7.1 Cooling Capacity Tables
Table 2-7.1: 4TVH0068BD000AA cooling capacity
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 16.7 2.44 19.8 2.98 23.0 3.20 23.9 3.35 25.2 3.46 25.6 3.75 26.2 3.75
-13 16.7 2.45 19.8 2.98 23.0 3.22 23.9 3.36 25.2 3.46 25.6 3.75 26.2 3.78
-11 16.7 2.45 19.8 3.00 23.0 3.22 23.9 3.37 25.2 3.47 25.6 3.76 26.2 3.78
-9 17.2 2.47 20.5 3.02 23.8 3.24 24.5 3.39 26.0 3.48 26.3 3.78 26.9 3.81
-7 17.2 2.49 20.5 3.02 23.8 3.24 24.5 3.40 26.0 3.48 26.3 3.78 26.9 3.82
-5 17.6 2.49 20.9 3.04 24.3 3.26 25.2 3.40 26.4 3.49 27.1 3.80 27.8 3.82
-2 17.6 2.49 20.9 3.10 24.3 3.26 25.2 3.42 26.4 3.49 27.1 3.85 27.8 3.86
0 17.6 2.54 20.9 3.16 24.3 3.38 25.2 3.60 26.4 3.69 27.1 3.89 27.8 3.91
2 17.6 2.58 20.9 3.16 24.3 3.50 25.2 3.81 26.4 3.74 27.1 3.92 27.8 3.97
4 17.6 2.64 20.9 3.22 24.3 3.62 25.2 3.82 26.4 3.79 27.1 3.98 27.8 4.04
6 17.6 2.69 20.9 3.29 24.3 3.75 25.2 3.85 26.1 3.90 26.7 4.04 27.4 4.07
8 17.6 2.75 20.9 3.36 24.3 3.94 25.2 4.04 25.8 4.03 26.4 4.05 27.1 4.11
Mini TVR Individual Series Engineering Data Book

10 17.6 2.81 20.9 3.44 24.3 4.09 25.2 4.18 25.5 4.11 26.1 4.12 26.8 4.23
12 17.6 2.86 20.9 3.50 24.3 4.17 24.9 4.24 25.2 4.17 25.8 4.18 26.4 4.26
14 17.6 2.92 20.9 3.57 24.2 4.23 24.6 4.30 24.9 4.23 25.5 4.24 26.1 4.36
130% 16 17.6 2.97 20.9 3.64 23.9 4.29 24.2 4.36 24.5 4.35 25.1 4.30 25.8 4.42
18 17.6 3.03 20.9 3.72 23.6 4.36 23.9 4.38 24.2 4.41 24.9 4.45 25.5 4.49
20 17.6 3.09 20.9 3.95 23.2 4.57 23.6 4.60 23.9 4.62 24.5 4.66 25.1 4.71
21 17.6 3.17 20.9 4.09 23.1 4.68 23.4 4.70 23.7 4.73 24.4 4.78 25.0 4.82
23 17.6 3.40 20.9 4.39 22.8 4.89 23.1 4.92 23.4 4.94 24.0 4.99 24.6 5.04
25 17.6 3.63 20.9 4.70 22.4 5.11 22.7 5.13 23.1 5.16 23.7 5.21 24.4 5.26
27 17.6 3.88 20.9 5.03 22.1 5.32 22.4 5.35 22.7 5.38 23.4 5.43 24.0 5.49
29 17.6 4.14 20.9 5.38 21.8 5.53 22.1 5.57 22.4 5.60 23.1 5.66 23.7 5.71
31 17.6 4.42 20.9 5.69 21.4 5.76 21.8 5.79 22.1 5.81 22.7 5.88 23.4 5.94
33 17.6 4.71 20.5 5.90 21.1 5.97 21.4 6.00 21.8 6.03 22.4 6.10 23.0 6.17
35 17.6 5.02 20.1 6.12 20.8 6.19 21.1 6.22 21.4 6.26 22.1 6.33 22.7 6.40
37 17.6 5.34 19.9 6.34 20.5 6.41 20.8 6.45 21.1 6.49 21.7 6.56 22.4 6.64
39 17.6 5.69 19.5 6.40 20.1 6.63 20.5 6.67 20.8 6.71 21.4 6.78 22.1 6.86
41 17.6 5.99 19.3 6.47 19.9 6.69 20.3 6.73 20.6 6.77 21.2 6.80 21.2 6.93
43 17.6 6.14 19.2 6.50 19.8 6.71 20.2 6.76 20.4 6.78 20.8 6.81 21.0 6.94
45 17.6 6.45 19.0 6.56 19.6 6.77 20.0 6.80 20.1 6.81 20.3 6.83 20.6 7.07
-15 15.3 2.36 18.2 2.86 21.2 3.38 22.7 3.71 24.0 3.89 24.2 3.99 24.7 4.09
-13 15.3 2.37 18.2 2.86 21.2 3.40 22.7 3.72 24.0 3.89 24.2 4.00 24.7 4.11
-11 15.3 2.37 18.2 2.88 21.2 3.40 22.7 3.73 24.0 3.90 24.2 4.01 24.7 4.11
-9 15.9 2.39 18.9 2.89 22.0 3.43 23.3 3.75 24.7 3.91 24.9 4.03 25.4 4.13
-7 15.9 2.41 18.9 2.89 22.0 3.43 23.3 3.75 24.7 3.91 24.9 4.03 25.4 4.14
-5 16.2 2.41 19.3 2.92 22.4 3.45 24.0 3.76 25.1 3.92 25.7 4.05 26.3 4.15
-2 16.2 2.43 19.3 2.95 22.4 3.48 24.0 3.78 25.1 3.97 25.7 4.08 26.3 4.17
0 16.2 2.45 19.3 2.97 22.4 3.52 24.0 3.79 25.1 4.00 25.7 4.11 26.3 4.18
2 16.2 2.46 19.3 3.00 22.4 3.55 24.0 3.83 25.1 4.02 25.7 4.14 26.3 4.19
4 16.2 2.49 19.3 3.04 22.4 3.60 24.0 3.86 25.1 4.07 25.7 4.14 26.3 4.20
6 16.2 2.51 19.3 3.06 22.4 3.64 24.0 3.91 25.1 4.12 25.7 4.18 26.3 4.21
8 16.2 2.53 19.3 3.09 22.4 3.69 24.0 3.96 25.1 4.16 25.7 4.19 26.3 4.23
10 16.2 2.57 19.3 3.13 22.4 3.72 24.0 4.03 25.1 4.16 25.7 4.20 26.3 4.25
12 16.2 2.61 19.3 3.19 22.4 3.80 24.0 4.10 24.8 4.18 25.4 4.18 25.9 4.28
14 16.2 2.66 19.3 3.26 22.4 3.87 24.0 4.18 24.4 4.20 25.1 4.24 25.6 4.33
120% 16 16.2 2.71 19.3 3.32 22.4 3.95 23.9 4.10 24.1 4.27 24.7 4.32 25.3 4.39
18 16.2 2.76 19.3 3.39 22.4 4.08 23.5 4.36 23.8 4.37 24.4 4.41 25.0 4.46
20 16.2 2.82 19.3 3.52 22.4 4.39 23.2 4.57 23.5 4.59 24.1 4.63 24.6 4.67
21 16.2 2.84 19.3 3.64 22.4 4.55 23.0 4.68 23.3 4.69 23.9 4.74 24.5 4.78
23 16.2 3.04 19.3 3.90 22.4 4.87 22.7 4.88 23.0 4.91 23.6 4.96 24.1 5.00
25 16.2 3.25 19.3 4.18 22.1 5.08 22.4 5.10 22.6 5.12 23.3 5.17 23.9 5.22
27 16.2 3.47 19.3 4.46 21.8 5.29 22.1 5.32 22.4 5.34 22.9 5.39 23.5 5.44
29 16.2 3.70 19.3 4.77 21.4 5.50 21.7 5.53 22.0 5.56 22.6 5.61 23.2 5.66
31 16.2 3.95 19.3 5.09 21.1 5.72 21.4 5.75 21.7 5.78 22.3 5.84 22.9 5.89
33 16.2 4.20 19.3 5.43 20.8 5.94 21.1 5.97 21.4 5.99 21.9 6.06 22.5 6.12
35 16.2 4.47 19.3 5.79 20.4 6.15 20.7 6.18 21.1 6.22 21.6 6.28 22.2 6.35
37 16.2 4.76 19.3 6.17 20.1 6.37 20.4 6.40 20.7 6.44 21.3 6.50 21.9 6.58
39 16.2 5.06 19.2 6.51 19.8 6.59 20.1 6.63 20.4 6.66 21.0 6.73 21.6 6.80
41 16.2 5.20 19.1 6.56 19.6 6.63 19.9 6.67 20.2 6.71 20.8 6.75 21.0 6.85
43 16.2 5.28 19.0 6.60 19.5 6.67 19.8 6.70 20.0 6.73 20.5 6.77 20.6 6.99
45 16.2 5.34 18.9 6.67 19.3 6.73 19.6 6.76 19.9 6.78 20.1 6.79 20.4 7.14

28
Mini TVR Individual 60Hz
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
Table 2-7.1: 4TVH0068BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 14.0 2.06 16.8 2.56 19.5 3.06 20.9 3.31 22.3 3.58 23.8 3.69 24.3 3.80
-13 14.0 2.07 16.8 2.56 19.5 3.08 20.9 3.32 22.3 3.58 23.8 3.70 24.3 3.82
-11 14.0 2.07 16.8 2.58 19.5 3.08 20.9 3.33 22.3 3.59 23.8 3.71 24.3 3.82
-9 14.5 2.08 17.4 2.60 20.2 3.10 21.4 3.34 23.1 3.60 24.4 3.73 24.9 3.84
-7 14.5 2.10 17.4 2.60 20.2 3.10 21.4 3.34 23.1 3.60 24.4 3.73 24.9 3.85
-5 14.9 2.10 17.7 2.62 20.6 3.12 22.0 3.35 23.4 3.61 25.2 3.75 25.8 3.86
-2 14.9 2.14 17.7 2.65 20.6 3.15 22.0 3.39 23.4 3.64 25.2 3.78 25.8 3.88
0 14.9 2.16 17.7 2.67 20.6 3.17 22.0 3.41 23.4 3.68 25.2 3.82 25.8 3.93
2 14.9 2.21 17.7 2.69 20.6 3.22 22.0 3.45 23.4 3.72 25.2 3.88 25.8 3.98
4 14.9 2.26 17.7 2.72 20.6 3.25 22.0 3.49 23.4 3.77 25.2 3.93 25.8 4.02
6 14.9 2.28 17.7 2.75 20.6 3.29 22.0 3.54 23.4 3.82 25.2 3.97 25.8 4.08
8 14.9 2.30 17.7 2.80 20.6 3.32 22.0 3.58 23.4 3.86 25.2 4.00 25.8 4.12
10 14.9 2.33 17.7 2.84 20.6 3.37 22.0 3.64 23.4 3.92 25.2 4.03 25.8 4.16
12 14.9 2.38 17.7 2.89 20.6 3.44 22.0 3.72 23.4 4.00 24.9 4.09 25.4 4.21

Part 2 - Outdoor Unit Engineering Data


14 14.9 2.42 17.7 2.94 20.6 3.50 22.0 3.78 23.4 4.07 24.6 4.12 25.1 4.24
110% 16 14.9 2.46 17.7 3.00 20.6 3.57 22.0 3.86 23.4 4.15 24.3 4.17 24.8 4.29
18 14.9 2.51 17.7 3.06 20.6 3.64 22.0 3.96 23.4 4.35 23.9 4.38 24.5 4.42
20 14.9 2.56 17.7 3.12 20.6 3.86 22.0 4.26 23.1 4.56 23.6 4.60 24.1 4.64
21 14.9 2.58 17.7 3.21 20.6 4.00 22.0 4.42 22.9 4.67 23.4 4.70 24.0 4.74
23 14.9 2.70 17.7 3.44 20.6 4.28 22.0 4.74 22.6 4.88 23.1 4.92 23.6 4.97
25 14.9 2.89 17.7 3.68 20.6 4.58 22.0 5.07 22.3 5.09 22.8 5.14 23.4 5.18
27 14.9 3.08 17.7 3.94 20.6 4.90 21.6 5.29 21.9 5.30 22.5 5.35 23.0 5.40
29 14.9 3.28 17.7 4.20 20.6 5.24 21.4 5.50 21.6 5.52 22.1 5.57 22.7 5.62
31 14.9 3.49 17.7 4.48 20.6 5.59 21.0 5.71 21.3 5.74 21.9 5.79 22.4 5.85
33 14.9 3.72 17.7 4.78 20.4 5.89 20.7 5.93 21.0 5.95 21.5 6.01 22.1 6.07
35 14.9 3.95 17.7 5.09 20.1 6.11 20.4 6.14 20.6 6.17 21.1 6.23 21.7 6.29
37 14.9 4.21 17.7 5.42 19.8 6.33 20.1 6.36 20.3 6.39 20.9 6.45 21.4 6.51
39 14.9 4.47 17.7 5.77 19.4 6.54 19.7 6.58 20.0 6.61 20.5 6.68 21.1 6.74
41 14.9 4.52 17.7 5.82 19.3 6.59 19.6 6.62 19.8 6.66 20.2 6.72 20.4 6.79
43 14.9 4.56 17.7 5.89 19.1 6.64 19.4 6.67 19.7 6.70 20.1 6.75 20.1 6.93
45 14.9 4.71 17.7 5.93 18.9 6.70 19.2 6.75 19.5 6.76 19.9 6.93 19.9 7.09
-15 12.8 1.87 15.2 2.26 17.7 2.69 19.0 2.90 20.3 3.16 22.5 3.58 23.8 3.73
-13 12.8 1.88 15.2 2.26 17.7 2.71 19.0 2.91 20.3 3.16 22.5 3.59 23.8 3.75
-11 12.8 1.88 15.2 2.27 17.7 2.71 19.0 2.92 20.3 3.17 22.5 3.60 23.8 3.75
-9 13.2 1.90 15.7 2.29 18.3 2.73 19.4 2.93 20.9 3.18 23.2 3.62 24.4 3.77
-7 13.2 1.91 15.7 2.29 18.3 2.73 19.4 2.93 20.9 3.18 23.2 3.62 24.4 3.78
-5 13.5 1.92 16.1 2.31 18.7 2.75 20.0 2.94 21.3 3.19 23.9 3.64 25.3 3.79
-2 13.5 1.94 16.1 2.34 18.7 2.78 20.0 3.00 21.3 3.23 23.9 3.68 25.3 3.82
0 13.5 1.96 16.1 2.36 18.7 2.81 20.0 3.03 21.3 3.26 23.9 3.74 25.3 3.86
2 13.5 2.00 16.1 2.39 18.7 2.84 20.0 3.07 21.3 3.30 23.9 3.79 25.3 3.92
4 13.5 2.01 16.1 2.42 18.7 2.88 20.0 3.12 21.3 3.34 23.9 3.83 25.3 3.97
6 13.5 2.04 16.1 2.46 18.7 2.92 20.0 3.17 21.3 3.39 23.9 3.89 25.3 4.03
8 13.5 2.08 16.1 2.50 18.7 2.97 20.0 3.21 21.3 3.45 23.9 3.95 25.3 4.09
10 13.5 2.10 16.1 2.55 18.7 3.02 20.0 3.26 21.3 3.51 23.9 4.01 25.3 4.15
12 13.5 2.14 16.1 2.60 18.7 3.07 20.0 3.32 21.3 3.58 23.9 4.09 24.9 4.18
14 13.5 2.18 16.1 2.65 18.7 3.13 20.0 3.39 21.3 3.64 23.9 4.17 24.6 4.23
100% 16 13.5 2.22 16.1 2.70 18.7 3.20 20.0 3.45 21.3 3.72 23.8 4.22 24.3 4.28
18 13.5 2.26 16.1 2.75 18.7 3.26 20.0 3.52 21.3 3.79 23.5 4.36 24.0 4.39
20 13.5 2.30 16.1 2.80 18.7 3.35 20.0 3.70 21.3 4.06 23.1 4.56 23.6 4.60
21 13.5 2.33 16.1 2.83 18.7 3.48 20.0 3.83 21.3 4.20 23.0 4.67 23.5 4.71
23 13.5 2.38 16.1 3.02 18.7 3.72 20.0 4.10 21.3 4.50 22.7 4.88 23.1 4.92
25 13.5 2.54 16.1 3.22 18.7 3.99 20.0 4.40 21.3 4.83 22.4 5.10 22.9 5.14
27 13.5 2.71 16.1 3.44 18.7 4.26 20.0 4.70 21.3 5.16 22.0 5.31 22.5 5.36
29 13.5 2.89 16.1 3.67 18.7 4.55 20.0 5.02 21.2 5.48 21.7 5.53 22.2 5.57
31 13.5 3.07 16.1 3.91 18.7 4.85 20.0 5.36 20.9 5.70 21.4 5.75 21.9 5.80
33 13.5 3.26 16.1 4.17 18.7 5.17 20.0 5.72 20.6 5.91 21.1 5.96 21.6 6.02
35 13.5 3.47 16.1 4.43 18.7 5.52 20.0 6.10 20.2 6.12 20.7 6.18 21.2 6.23
37 13.5 3.69 16.1 4.72 18.7 5.88 19.6 6.31 19.9 6.35 20.4 6.40 20.9 6.45
39 13.5 3.92 16.1 5.01 18.7 6.26 19.4 6.53 19.6 6.56 20.1 6.62 20.6 6.68
41 13.5 4.10 16.1 5.20 18.7 6.48 19.1 6.57 19.4 6.66 19.7 6.77 20.3 6.82
43 13.5 4.29 16.1 5.38 18.7 6.61 18.8 6.65 19.3 6.73 19.8 6.82 19.9 6.90
45 13.5 4.53 16.1 5.62 18.7 6.72 18.4 6.74 19.2 6.85 19.7 6.92 19.5 6.99
29
Mini TVR Individual 60Hz
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
Table 2-7.1: 4TVH0068BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.5 1.66 13.7 1.99 16.0 2.35 17.1 2.58 18.3 2.76 20.3 3.15 22.4 3.61
-13 11.5 1.66 13.7 1.99 16.0 2.37 17.1 2.59 18.3 2.76 20.3 3.16 22.4 3.63
-11 11.5 1.66 13.7 2.00 16.0 2.37 17.1 2.60 18.3 2.77 20.3 3.17 22.4 3.63
-9 11.9 1.68 14.2 2.02 16.5 2.38 17.5 2.60 18.8 2.77 20.8 3.19 23.0 3.64
-7 11.9 1.69 14.2 2.02 16.5 2.38 17.5 2.60 18.8 2.78 20.8 3.19 23.0 3.65
-5 12.1 1.69 14.5 2.03 16.9 2.40 18.0 2.62 19.1 2.78 21.5 3.20 23.9 3.66
-2 12.1 1.71 14.5 2.05 16.9 2.43 18.0 2.65 19.1 2.82 21.5 3.23 23.9 3.70
0 12.1 1.74 14.5 2.08 16.9 2.47 18.0 2.68 19.1 2.85 21.5 3.27 23.9 3.73
2 12.1 1.76 14.5 2.11 16.9 2.49 18.0 2.73 19.1 2.90 21.5 3.34 23.9 3.78
4 12.1 1.79 14.5 2.14 16.9 2.53 18.0 2.76 19.1 2.93 21.5 3.39 23.9 3.84
Mini TVR Individual Series Engineering Data Book

6 12.1 1.81 14.5 2.18 16.9 2.58 18.0 2.81 19.1 2.99 21.5 3.44 23.9 3.90
8 12.1 1.85 14.5 2.22 16.9 2.63 18.0 2.85 19.1 3.04 21.5 3.50 23.9 3.94
10 12.1 1.88 14.5 2.27 16.9 2.68 18.0 2.89 19.1 3.11 21.5 3.55 23.9 4.00
12 12.1 1.92 14.5 2.31 16.9 2.73 18.0 2.94 19.1 3.17 21.5 3.62 23.9 4.08
14 12.1 1.95 14.5 2.35 16.9 2.78 18.0 3.00 19.1 3.22 21.5 3.68 23.9 4.15
90% 16 12.1 1.98 14.5 2.39 16.9 2.84 18.0 3.06 19.1 3.29 21.5 3.76 23.8 4.23
18 12.1 2.01 14.5 2.44 16.9 2.89 18.0 3.12 19.1 3.35 21.5 3.83 23.5 4.36
20 12.1 2.06 14.5 2.50 16.9 2.94 18.0 3.18 19.1 3.48 21.5 4.12 23.1 4.56
21 12.1 2.07 14.5 2.52 16.9 2.99 18.0 3.29 19.1 3.60 21.5 4.27 23.0 4.67
23 12.1 2.11 14.5 2.61 16.9 3.21 18.0 3.53 19.1 3.86 21.5 4.58 22.6 4.88
25 12.1 2.23 14.5 2.80 16.9 3.43 18.0 3.77 19.1 4.13 21.5 4.90 22.4 5.10
27 12.1 2.37 14.5 2.98 16.9 3.66 18.0 4.03 19.1 4.41 21.5 5.24 22.0 5.31
29 12.1 2.52 14.5 3.17 16.9 3.90 18.0 4.30 19.1 4.72 21.3 5.48 21.7 5.52
31 12.1 2.68 14.5 3.38 16.9 4.16 18.0 4.59 19.1 5.03 20.9 5.70 21.4 5.75
33 12.1 2.84 14.5 3.59 16.9 4.44 18.0 4.89 19.1 5.37 20.6 5.92 21.1 5.96
35 12.1 3.02 14.5 3.82 16.9 4.73 18.0 5.21 19.1 5.72 20.3 6.13 20.7 6.18
37 12.1 3.21 14.5 4.06 16.9 5.03 18.0 5.55 19.1 6.10 19.9 6.35 20.4 6.40
39 12.1 3.40 14.5 4.32 16.9 5.35 18.0 5.91 19.1 6.49 19.6 6.57 20.1 6.62
41 12.1 3.52 14.5 4.52 16.9 5.55 18.0 6.07 19.1 6.53 19.5 6.74 19.9 6.77
43 12.1 3.69 14.5 4.72 16.9 5.74 18.0 6.22 19.1 6.67 19.4 6.82 19.8 6.88
45 12.1 3.92 14.5 4.95 16.9 5.98 18.0 6.43 19.1 6.86 19.3 6.89 19.5 6.97
-15 10.2 1.46 12.2 1.73 14.1 2.05 15.2 2.19 16.3 2.37 18.0 2.72 20.0 3.11
-13 10.2 1.47 12.2 1.73 14.1 2.06 15.2 2.20 16.3 2.37 18.0 2.73 20.0 3.12
-11 10.2 1.47 12.2 1.74 14.1 2.06 15.2 2.21 16.3 2.38 18.0 2.74 20.0 3.12
-9 10.6 1.48 12.6 1.75 14.6 2.08 15.5 2.21 16.8 2.38 18.5 2.75 20.5 3.14
-7 10.6 1.49 12.6 1.75 14.6 2.08 15.5 2.21 16.8 2.39 18.5 2.75 20.5 3.15
-5 10.8 1.49 12.9 1.76 14.9 2.09 16.0 2.22 17.1 2.39 19.1 2.77 21.2 3.16
-2 10.8 1.51 12.9 1.79 14.9 2.11 16.0 2.26 17.1 2.41 19.1 2.79 21.2 3.19
0 10.8 1.54 12.9 1.81 14.9 2.13 16.0 2.28 17.1 2.46 19.1 2.83 21.2 3.23
2 10.8 1.57 12.9 1.84 14.9 2.16 16.0 2.33 17.1 2.50 19.1 2.89 21.2 3.29
4 10.8 1.60 12.9 1.87 14.9 2.21 16.0 2.38 17.1 2.55 19.1 2.94 21.2 3.34
6 10.8 1.62 12.9 1.91 14.9 2.24 16.0 2.43 17.1 2.59 19.1 2.99 21.2 3.39
8 10.8 1.66 12.9 1.95 14.9 2.29 16.0 2.47 17.1 2.65 19.1 3.03 21.2 3.46
10 10.8 1.67 12.9 2.00 14.9 2.35 16.0 2.53 17.1 2.71 19.1 3.10 21.2 3.49
12 10.8 1.69 12.9 2.03 14.9 2.39 16.0 2.58 17.1 2.77 19.1 3.16 21.2 3.56
14 10.8 1.73 12.9 2.07 14.9 2.43 16.0 2.62 17.1 2.82 19.1 3.21 21.2 3.63
80% 16 10.8 1.75 12.9 2.10 14.9 2.48 16.0 2.67 17.1 2.87 19.1 3.28 21.2 3.69
18 10.8 1.78 12.9 2.15 14.9 2.53 16.0 2.73 17.1 2.93 19.1 3.35 21.2 3.77
20 10.8 1.82 12.9 2.19 14.9 2.58 16.0 2.78 17.1 2.98 19.1 3.47 21.2 4.03
21 10.8 1.83 12.9 2.20 14.9 2.61 16.0 2.81 17.1 3.05 19.1 3.59 21.2 4.18
23 10.8 1.87 12.9 2.25 14.9 2.73 16.0 2.99 17.1 3.26 19.1 3.85 21.2 4.48
25 10.8 1.92 12.9 2.39 14.9 2.92 16.0 3.20 17.1 3.49 19.1 4.12 21.2 4.79
27 10.8 2.05 12.9 2.55 14.9 3.11 16.0 3.41 17.1 3.72 19.1 4.40 21.2 5.13
29 10.8 2.18 12.9 2.71 14.9 3.31 16.0 3.63 17.1 3.98 19.1 4.69 21.2 5.48
31 10.8 2.31 12.9 2.89 14.9 3.53 16.0 3.87 17.1 4.24 19.1 5.01 20.9 5.70
33 10.8 2.46 12.9 3.07 14.9 3.76 16.0 4.13 17.1 4.51 19.1 5.34 20.6 5.91
35 10.8 2.61 12.9 3.26 14.9 4.00 16.0 4.39 17.1 4.81 19.1 5.70 20.2 6.12
37 10.8 2.76 12.9 3.46 14.9 4.25 16.0 4.68 17.1 5.12 19.1 6.08 19.9 6.34
39 10.8 2.93 12.9 3.69 14.9 4.52 16.0 4.97 17.1 5.45 19.1 6.47 19.6 6.56
41 10.8 2.99 12.9 3.72 14.9 4.59 16.0 5.11 17.1 5.55 19.1 6.63 19.5 6.68
43 10.8 3.08 12.9 3.76 14.9 4.65 16.0 5.19 17.1 5.63 19.1 6.71 19.3 6.75
45 10.8 3.17 12.9 3.80 14.9 4.74 16.0 5.30 17.1 5.72 19.1 6.79 19.1 6.86
30
Mini TVR Individual 60Hz
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
Table 2-7.1: 4TVH0068BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 8.9 1.30 10.7 1.53 12.4 1.74 13.3 1.87 14.2 2.01 15.7 2.28 17.5 2.62
-13 8.9 1.31 10.7 1.53 12.4 1.75 13.3 1.88 14.2 2.01 15.7 2.29 17.5 2.64
-11 8.9 1.31 10.7 1.54 12.4 1.75 13.3 1.88 14.2 2.01 15.7 2.30 17.5 2.64
-9 9.2 1.32 11.1 1.55 12.8 1.76 13.6 1.89 14.7 2.02 16.2 2.31 17.9 2.65
-7 9.2 1.33 11.1 1.55 12.8 1.76 13.6 1.89 14.7 2.02 16.2 2.31 17.9 2.66
-5 9.4 1.33 11.3 1.56 13.1 1.77 14.0 1.90 14.9 2.03 16.7 2.32 18.6 2.66
-2 9.4 1.34 11.3 1.57 13.1 1.78 14.0 1.93 14.9 2.06 16.7 2.35 18.6 2.70
0 9.4 1.35 11.3 1.59 13.1 1.82 14.0 1.97 14.9 2.10 16.7 2.40 18.6 2.74
2 9.4 1.36 11.3 1.60 13.1 1.85 14.0 2.01 14.9 2.14 16.7 2.45 18.6 2.78
4 9.4 1.38 11.3 1.64 13.1 1.89 14.0 2.04 14.9 2.18 16.7 2.49 18.6 2.85
6 9.4 1.40 11.3 1.67 13.1 1.93 14.0 2.11 14.9 2.23 16.7 2.54 18.6 2.90
8 9.4 1.42 11.3 1.72 13.1 1.98 14.0 2.14 14.9 2.28 16.7 2.61 18.6 2.96
10 9.4 1.45 11.3 1.74 13.1 2.03 14.0 2.19 14.9 2.34 16.7 2.66 18.6 2.99
12 9.4 1.49 11.3 1.77 13.1 2.07 14.0 2.23 14.9 2.38 16.7 2.71 18.6 3.05

Part 2 - Outdoor Unit Engineering Data


14 9.4 1.51 11.3 1.80 13.1 2.10 14.0 2.26 14.9 2.43 16.7 2.76 18.6 3.11
70% 16 9.4 1.54 11.3 1.83 13.1 2.15 14.0 2.31 14.9 2.47 16.7 2.81 18.6 3.17
18 9.4 1.56 11.3 1.87 13.1 2.19 14.0 2.35 14.9 2.52 16.7 2.87 18.6 3.23
20 9.4 1.59 11.3 1.90 13.1 2.23 14.0 2.39 14.9 2.57 16.7 2.93 18.6 3.32
21 9.4 1.60 11.3 1.92 13.1 2.24 14.0 2.42 14.9 2.59 16.7 2.97 18.6 3.44
23 9.4 1.63 11.3 1.95 13.1 2.29 14.0 2.50 14.9 2.72 16.7 3.18 18.6 3.68
25 9.4 1.66 11.3 2.03 13.1 2.44 14.0 2.67 14.9 2.90 16.7 3.40 18.6 3.94
27 9.4 1.76 11.3 2.16 13.1 2.61 14.0 2.84 14.9 3.10 16.7 3.63 18.6 4.21
29 9.4 1.87 11.3 2.29 13.1 2.77 14.0 3.03 14.9 3.30 16.7 3.87 18.6 4.50
31 9.4 1.97 11.3 2.43 13.1 2.95 14.0 3.22 14.9 3.51 16.7 4.13 18.6 4.79
33 9.4 2.10 11.3 2.59 13.1 3.14 14.0 3.43 14.9 3.74 16.7 4.40 18.6 5.11
35 9.4 2.22 11.3 2.75 13.1 3.33 14.0 3.65 14.9 3.98 16.7 4.69 18.6 5.45
37 9.4 2.34 11.3 2.91 13.1 3.54 14.0 3.87 14.9 4.23 16.7 4.99 18.6 5.80
39 9.4 2.48 11.3 3.08 13.1 3.76 14.0 4.12 14.9 4.50 16.7 5.30 18.6 6.18
41 9.4 2.59 11.3 3.19 13.1 3.87 14.0 4.26 14.9 4.63 16.7 5.52 18.6 6.46
43 9.4 2.80 11.3 3.41 13.1 4.03 14.0 4.48 14.9 4.77 16.7 5.72 18.6 6.66
45 9.4 2.87 11.3 3.48 13.1 4.11 14.0 4.56 14.9 5.01 16.7 6.03 18.6 6.91
-15 7.6 1.11 9.1 1.29 10.6 1.51 11.4 1.61 12.2 1.75 13.5 1.96 15.0 2.24
-13 7.6 1.12 9.1 1.29 10.6 1.52 11.4 1.62 12.2 1.75 13.5 1.96 15.0 2.25
-11 7.6 1.12 9.1 1.30 10.6 1.52 11.4 1.62 12.2 1.76 13.5 1.97 15.0 2.25
-9 7.9 1.13 9.4 1.31 11.0 1.53 11.7 1.63 12.6 1.76 13.9 1.98 15.4 2.26
-7 7.9 1.14 9.4 1.31 11.0 1.53 11.7 1.63 12.6 1.76 13.9 1.98 15.4 2.27
-5 8.1 1.14 9.6 1.32 11.2 1.54 12.0 1.64 12.8 1.77 14.4 1.98 15.9 2.28
-2 8.1 1.14 9.6 1.34 11.2 1.56 12.0 1.66 12.8 1.79 14.4 2.01 15.9 2.29
0 8.1 1.16 9.6 1.36 11.2 1.58 12.0 1.68 12.8 1.82 14.4 2.04 15.9 2.32
2 8.1 1.18 9.6 1.39 11.2 1.61 12.0 1.71 12.8 1.84 14.4 2.09 15.9 2.35
4 8.1 1.21 9.6 1.41 11.2 1.65 12.0 1.73 12.8 1.87 14.4 2.12 15.9 2.38
6 8.1 1.23 9.6 1.44 11.2 1.68 12.0 1.77 12.8 1.90 14.4 2.16 15.9 2.44
8 8.1 1.25 9.6 1.46 11.2 1.71 12.0 1.81 12.8 1.94 14.4 2.20 15.9 2.48
10 8.1 1.27 9.6 1.50 11.2 1.73 12.0 1.86 12.8 1.98 14.4 2.24 15.9 2.52
12 8.1 1.30 9.6 1.52 11.2 1.77 12.0 1.89 12.8 2.01 14.4 2.29 15.9 2.56
14 8.1 1.32 9.6 1.55 11.2 1.79 12.0 1.92 12.8 2.05 14.4 2.33 15.9 2.61
60% 16 8.1 1.33 9.6 1.57 11.2 1.82 12.0 1.96 12.8 2.09 14.4 2.37 15.9 2.66
18 8.1 1.36 9.6 1.59 11.2 1.86 12.0 1.99 12.8 2.13 14.4 2.41 15.9 2.70
20 8.1 1.37 9.6 1.63 11.2 1.89 12.0 2.03 12.8 2.17 14.4 2.46 15.9 2.76
21 8.1 1.39 9.6 1.64 11.2 1.91 12.0 2.05 12.8 2.19 14.4 2.48 15.9 2.79
23 8.1 1.41 9.6 1.67 11.2 1.94 12.0 2.09 12.8 2.23 14.4 2.58 15.9 2.97
25 8.1 1.43 9.6 1.69 11.2 2.01 12.0 2.19 12.8 2.37 14.4 2.75 15.9 3.16
27 8.1 1.49 9.6 1.80 11.2 2.15 12.0 2.33 12.8 2.52 14.4 2.93 15.9 3.38
29 8.1 1.57 9.6 1.91 11.2 2.29 12.0 2.48 12.8 2.69 14.4 3.13 15.9 3.61
31 8.1 1.67 9.6 2.02 11.2 2.42 12.0 2.64 12.8 2.86 14.4 3.33 15.9 3.84
33 8.1 1.76 9.6 2.15 11.2 2.57 12.0 2.80 12.8 3.04 14.4 3.54 15.9 4.09
35 8.1 1.87 9.6 2.28 11.2 2.73 12.0 2.98 12.8 3.23 14.4 3.77 15.9 4.36
37 8.1 1.97 9.6 2.41 11.2 2.89 12.0 3.16 12.8 3.43 14.4 4.01 15.9 4.64
39 8.1 2.08 9.6 2.55 11.2 3.07 12.0 3.35 12.8 3.64 14.4 4.26 15.9 4.93
41 8.1 2.15 9.6 2.66 11.2 3.18 12.0 3.48 12.8 3.78 14.4 4.46 15.9 5.16
43 8.1 2.21 9.6 2.77 11.2 3.29 12.0 3.58 12.8 3.91 14.4 4.65 15.9 5.38
45 8.1 2.32 9.6 2.91 11.2 3.42 12.0 3.72 12.8 4.10 14.4 4.86 15.9 5.68
31
Mini TVR Individual 60Hz
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
Table 2-7.1: 4TVH0068BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.4 0.97 7.6 1.12 8.9 1.29 9.5 1.35 10.1 1.44 11.2 1.62 12.5 1.75
-13 6.4 0.97 7.6 1.12 8.9 1.29 9.5 1.36 10.1 1.44 11.2 1.63 12.5 1.76
-11 6.4 0.97 7.6 1.13 8.9 1.29 9.5 1.36 10.1 1.44 11.2 1.63 12.5 1.76
-9 6.6 0.98 7.9 1.13 9.2 1.30 9.7 1.37 10.5 1.44 11.5 1.64 12.8 1.77
-7 6.6 0.99 7.9 1.13 9.2 1.30 9.7 1.37 10.5 1.45 11.5 1.64 12.8 1.77
-5 6.8 0.99 8.1 1.14 9.4 1.31 10.0 1.37 10.6 1.45 11.9 1.65 13.3 1.78
-2 6.8 0.99 8.1 1.16 9.4 1.33 10.0 1.39 10.6 1.47 11.9 1.67 13.3 1.80
0 6.8 1.01 8.1 1.18 9.4 1.35 10.0 1.41 10.6 1.49 11.9 1.70 13.3 1.83
2 6.8 1.03 8.1 1.20 9.4 1.37 10.0 1.43 10.6 1.52 11.9 1.70 13.3 1.87
4 6.8 1.04 8.1 1.22 9.4 1.39 10.0 1.45 10.6 1.55 11.9 1.75 13.3 1.91
Mini TVR Individual Series Engineering Data Book

6 6.8 1.05 8.1 1.24 9.4 1.41 10.0 1.48 10.6 1.58 11.9 1.77 13.3 1.97
8 6.8 1.08 8.1 1.26 9.4 1.43 10.0 1.52 10.6 1.60 11.9 1.80 13.3 2.03
10 6.8 1.10 8.1 1.27 9.4 1.46 10.0 1.54 10.6 1.64 11.9 1.85 13.3 2.06
12 6.8 1.11 8.1 1.29 9.4 1.48 10.0 1.57 10.6 1.68 11.9 1.88 13.3 2.10
14 6.8 1.13 8.1 1.31 9.4 1.50 10.0 1.60 10.6 1.70 11.9 1.92 13.3 2.14
50% 16 6.8 1.14 8.1 1.32 9.4 1.52 10.0 1.63 10.6 1.73 11.9 1.95 13.3 2.17
18 6.8 1.16 8.1 1.35 9.4 1.55 10.0 1.65 10.6 1.76 11.9 1.98 13.3 2.21
20 6.8 1.18 8.1 1.36 9.4 1.57 10.0 1.68 10.6 1.79 11.9 2.01 13.3 2.25
21 6.8 1.18 8.1 1.38 9.4 1.59 10.0 1.69 10.6 1.81 11.9 2.04 13.3 2.28
23 6.8 1.20 8.1 1.40 9.4 1.61 10.0 1.73 10.6 1.84 11.9 2.07 13.3 2.33
25 6.8 1.22 8.1 1.42 9.4 1.64 10.0 1.76 10.6 1.90 11.9 2.18 13.3 2.48
27 6.8 1.24 8.1 1.48 9.4 1.73 10.0 1.87 10.6 2.01 11.9 2.32 13.3 2.65
29 6.8 1.31 8.1 1.56 9.4 1.84 10.0 1.99 10.6 2.15 11.9 2.47 13.3 2.82
31 6.8 1.38 8.1 1.65 9.4 1.95 10.0 2.11 10.6 2.28 11.9 2.62 13.3 3.00
33 6.8 1.46 8.1 1.75 9.4 2.07 10.0 2.24 10.6 2.42 11.9 2.79 13.3 3.19
35 6.8 1.55 8.1 1.85 9.4 2.19 10.0 2.37 10.6 2.56 11.9 2.96 13.3 3.39
37 6.8 1.63 8.1 1.96 9.4 2.32 10.0 2.51 10.6 2.71 11.9 3.14 13.3 3.60
39 6.8 1.72 8.1 2.06 9.4 2.45 10.0 2.66 10.6 2.88 11.9 3.33 13.3 3.82
41 6.8 1.79 8.1 2.15 9.4 2.54 10.0 2.78 10.6 3.00 11.9 3.51 13.3 4.00
43 6.8 1.91 8.1 2.30 9.4 2.63 10.0 2.90 10.6 3.08 11.9 3.68 13.3 4.18
45 6.8 1.95 8.1 2.36 9.4 2.80 10.0 3.13 10.6 3.21 11.9 4.04 13.3 4.53
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

32
Mini TVR Individual 60Hz
Table 2-7.2: 4TVH0076BD000AA cooling capacity
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 18.7 2.72 22.1 3.32 25.8 3.57 26.8 3.73 28.2 3.86 28.7 4.18 29.4 4.18
-13 18.7 2.73 22.1 3.32 25.8 3.59 26.8 3.75 28.2 3.86 28.7 4.18 29.4 4.22
-11 18.7 2.73 22.1 3.34 25.8 3.59 26.8 3.76 28.2 3.86 28.7 4.19 29.4 4.22
-9 19.3 2.75 23.0 3.37 26.6 3.61 27.5 3.77 29.2 3.88 29.5 4.22 30.1 4.25
-7 19.3 2.78 23.0 3.37 26.6 3.61 27.5 3.78 29.2 3.88 29.5 4.22 30.1 4.25
-5 19.7 2.78 23.4 3.39 27.2 3.64 28.2 3.78 29.6 3.89 30.3 4.23 31.1 4.26
-2 19.7 2.78 23.4 3.46 27.2 3.64 28.2 3.81 29.6 3.89 30.3 4.29 31.1 4.30
0 19.7 2.83 23.4 3.52 27.2 3.77 28.2 4.02 29.6 4.12 30.3 4.34 31.1 4.36
2 19.7 2.88 23.4 3.53 27.2 3.90 28.2 4.24 29.6 4.17 30.3 4.37 31.1 4.42
4 19.7 2.94 23.4 3.59 27.2 4.03 28.2 4.26 29.6 4.22 30.3 4.44 31.1 4.51
6 19.7 3.00 23.4 3.67 27.2 4.18 28.2 4.30 29.3 4.35 29.9 4.51 30.7 4.54
8 19.7 3.07 23.4 3.75 27.2 4.39 28.2 4.51 28.9 4.49 29.6 4.52 30.3 4.59
10 19.7 3.13 23.4 3.83 27.2 4.55 28.2 4.66 28.6 4.58 29.3 4.59 30.0 4.72
12 19.7 3.19 23.4 3.90 27.2 4.65 27.8 4.73 28.2 4.65 28.9 4.66 29.6 4.75
14 19.7 3.25 23.4 3.98 27.1 4.72 27.5 4.79 27.8 4.72 28.6 4.73 29.3 4.86
130% 16 19.7 3.31 23.4 4.06 26.8 4.79 27.1 4.86 27.4 4.85 28.2 4.80 28.9 4.93
18 19.7 3.37 23.4 4.14 26.4 4.86 26.7 4.89 27.1 4.91 27.8 4.96 28.6 5.00
20 19.7 3.45 23.4 4.41 26.0 5.10 26.4 5.12 26.7 5.15 27.4 5.20 28.2 5.25
21 19.7 3.54 23.4 4.56 25.8 5.22 26.2 5.24 26.6 5.27 27.3 5.32 28.0 5.37

Part 2 - Outdoor Unit Engineering Data


23 19.7 3.79 23.4 4.89 25.5 5.45 25.8 5.48 26.2 5.51 26.9 5.56 27.6 5.62
25 19.7 4.05 23.4 5.24 25.1 5.69 25.4 5.72 25.8 5.76 26.6 5.81 27.3 5.87
27 19.7 4.33 23.4 5.61 24.8 5.93 25.1 5.97 25.4 5.99 26.2 6.06 26.9 6.12
29 19.7 4.62 23.4 5.99 24.4 6.17 24.7 6.20 25.1 6.24 25.8 6.31 26.6 6.37
31 19.7 4.93 23.4 6.34 24.0 6.42 24.4 6.45 24.7 6.48 25.4 6.55 26.2 6.63
33 19.7 5.25 23.0 6.58 23.7 6.65 24.0 6.69 24.4 6.73 25.1 6.80 25.8 6.87
35 19.7 5.60 22.6 6.82 23.3 6.90 23.7 6.94 24.0 6.97 24.7 7.06 25.4 7.13
37 19.7 5.96 22.2 7.07 23.0 7.15 23.3 7.19 23.7 7.23 24.3 7.31 25.0 7.40
39 19.7 6.34 21.8 7.14 22.6 7.39 23.0 7.43 23.3 7.48 24.0 7.56 24.7 7.65
41 19.7 6.68 21.6 7.21 22.3 7.46 22.7 7.50 23.0 7.55 23.8 7.58 23.8 7.72
43 19.7 6.84 21.5 7.24 22.2 7.48 22.6 7.54 22.8 7.56 23.3 7.59 23.5 7.74
45 19.7 7.18 21.3 7.31 22.0 7.55 22.4 7.59 22.5 7.59 22.7 7.62 23.0 7.89
-15 17.2 2.63 20.4 3.18 23.8 3.77 25.5 4.14 26.9 4.33 27.1 4.44 27.7 4.56
-13 17.2 2.64 20.4 3.18 23.8 3.80 25.5 4.15 26.9 4.33 27.1 4.46 27.7 4.58
-11 17.2 2.64 20.4 3.21 23.8 3.80 25.5 4.16 26.9 4.34 27.1 4.47 27.7 4.58
-9 17.8 2.66 21.2 3.23 24.6 3.82 26.1 4.18 27.7 4.36 27.9 4.49 28.4 4.61
-7 17.8 2.68 21.2 3.23 24.6 3.82 26.1 4.18 27.7 4.36 27.9 4.49 28.4 4.62
-5 18.2 2.69 21.6 3.25 25.1 3.85 26.9 4.19 28.2 4.37 28.8 4.51 29.4 4.63
-2 18.2 2.71 21.6 3.29 25.1 3.88 26.9 4.22 28.2 4.42 28.8 4.55 29.4 4.65
0 18.2 2.74 21.6 3.31 25.1 3.93 26.9 4.23 28.2 4.46 28.8 4.58 29.4 4.66
2 18.2 2.74 21.6 3.34 25.1 3.96 26.9 4.27 28.2 4.48 28.8 4.61 29.4 4.67
4 18.2 2.77 21.6 3.39 25.1 4.01 26.9 4.31 28.2 4.54 28.8 4.62 29.4 4.68
6 18.2 2.80 21.6 3.41 25.1 4.06 26.9 4.36 28.2 4.59 28.8 4.66 29.4 4.69
8 18.2 2.83 21.6 3.45 25.1 4.11 26.9 4.41 28.2 4.63 28.8 4.67 29.4 4.72
10 18.2 2.86 21.6 3.49 25.1 4.15 26.9 4.49 28.2 4.64 28.8 4.69 29.4 4.74
12 18.2 2.91 21.6 3.56 25.1 4.23 26.9 4.57 27.8 4.66 28.4 4.66 29.0 4.77
14 18.2 2.97 21.6 3.63 25.1 4.32 26.9 4.67 27.4 4.69 28.1 4.73 28.7 4.82
120% 16 18.2 3.02 21.6 3.70 25.1 4.40 26.7 4.10 27.0 4.76 27.7 4.81 28.3 4.90
18 18.2 3.08 21.6 3.78 25.1 4.55 26.3 4.86 26.6 4.88 27.3 4.92 28.0 4.97
20 18.2 3.14 21.6 3.92 25.1 4.89 26.0 5.10 26.3 5.11 27.0 5.16 27.6 5.21
21 18.2 3.17 21.6 4.06 25.1 5.07 25.8 5.21 26.1 5.23 26.8 5.28 27.4 5.33
23 18.2 3.39 21.6 4.35 25.1 5.43 25.4 5.44 25.8 5.47 26.4 5.53 27.0 5.57
25 18.2 3.62 21.6 4.66 24.7 5.66 25.0 5.68 25.4 5.71 26.1 5.76 26.7 5.82
27 18.2 3.87 21.6 4.98 24.4 5.89 24.7 5.93 25.0 5.96 25.7 6.01 26.3 6.07
29 18.2 4.12 21.6 5.32 24.0 6.13 24.3 6.17 24.6 6.20 25.3 6.26 26.0 6.31
31 18.2 4.40 21.6 5.67 23.6 6.38 24.0 6.41 24.3 6.44 25.0 6.51 25.6 6.57
33 18.2 4.68 21.6 6.05 23.3 6.62 23.6 6.65 23.9 6.68 24.6 6.75 25.2 6.82
35 18.2 4.99 21.6 6.45 22.9 6.85 23.2 6.89 23.6 6.93 24.2 7.00 24.9 7.08
37 18.2 5.31 21.6 6.87 22.6 7.10 22.9 7.14 23.2 7.18 23.8 7.25 24.5 7.33
39 18.2 5.65 21.5 7.26 22.2 7.34 22.5 7.39 22.8 7.42 23.5 7.51 24.2 7.58
41 18.2 5.80 21.3 7.31 22.0 7.39 22.3 7.44 22.6 7.48 23.3 7.53 23.5 7.64
43 18.2 5.89 21.2 7.36 21.8 7.44 22.1 7.47 22.5 7.50 22.9 7.55 23.1 7.79
45 18.2 5.96 21.1 7.43 21.6 7.51 21.9 7.54 22.3 7.56 22.5 7.57 22.9 7.96
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
33
Mini TVR Individual 60Hz
Table 2-7.2: 4TVH0076BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 15.7 2.29 18.8 2.86 21.8 3.42 23.4 3.69 25.0 3.99 26.6 4.12 27.2 4.24
-13 15.7 2.30 18.8 2.86 21.8 3.44 23.4 3.70 25.0 3.99 26.6 4.13 27.2 4.26
-11 15.7 2.30 18.8 2.88 21.8 3.44 23.4 3.71 25.0 4.00 26.6 4.14 27.2 4.26
-9 16.3 2.32 19.4 2.90 22.6 3.46 23.9 3.72 25.8 4.01 27.3 4.16 27.9 4.28
-7 16.3 2.34 19.4 2.90 22.6 3.46 23.9 3.72 25.8 4.01 27.3 4.16 27.9 4.29
-5 16.6 2.34 19.8 2.92 23.0 3.48 24.6 3.74 26.2 4.02 28.2 4.18 28.9 4.31
-2 16.6 2.39 19.8 2.96 23.0 3.51 24.6 3.78 26.2 4.05 28.2 4.22 28.9 4.33
0 16.6 2.41 19.8 2.97 23.0 3.54 24.6 3.80 26.2 4.10 28.2 4.26 28.9 4.38
2 16.6 2.47 19.8 3.00 23.0 3.59 24.6 3.84 26.2 4.14 28.2 4.32 28.9 4.44
4 16.6 2.52 19.8 3.04 23.0 3.63 24.6 3.89 26.2 4.21 28.2 4.38 28.9 4.48
6 16.6 2.54 19.8 3.07 23.0 3.66 24.6 3.95 26.2 4.25 28.2 4.43 28.9 4.55
8 16.6 2.56 19.8 3.12 23.0 3.71 24.6 3.99 26.2 4.30 28.2 4.46 28.9 4.59
10 16.6 2.59 19.8 3.16 23.0 3.76 24.6 4.06 26.2 4.37 28.2 4.49 28.9 4.63
12 16.6 2.65 19.8 3.23 23.0 3.83 24.6 4.14 26.2 4.45 27.9 4.55 28.5 4.69
14 16.6 2.69 19.8 3.28 23.0 3.90 24.6 4.22 26.2 4.54 27.5 4.59 28.2 4.73
110% 16 16.6 2.74 19.8 3.35 23.0 3.98 24.6 4.30 26.2 4.63 27.2 4.65 27.8 4.78
Mini TVR Individual Series Engineering Data Book

18 16.6 2.80 19.8 3.41 23.0 4.06 24.6 4.42 26.2 4.85 26.8 4.88 27.4 4.93
20 16.6 2.85 19.8 3.48 23.0 4.30 24.6 4.75 25.8 5.09 26.5 5.12 27.0 5.17
21 16.6 2.88 19.8 3.58 23.0 4.45 24.6 4.92 25.7 5.21 26.2 5.24 26.9 5.29
23 16.6 3.02 19.8 3.84 23.0 4.78 24.6 5.28 25.3 5.43 25.9 5.49 26.5 5.54
25 16.6 3.22 19.8 4.11 23.0 5.10 24.6 5.65 25.0 5.67 25.5 5.73 26.2 5.77
27 16.6 3.43 19.8 4.39 23.0 5.46 24.2 5.89 24.6 5.91 25.2 5.97 25.8 6.02
29 16.6 3.66 19.8 4.68 23.0 5.84 23.9 6.13 24.2 6.16 24.8 6.21 25.4 6.27
31 16.6 3.89 19.8 5.00 23.0 6.23 23.5 6.37 23.8 6.40 24.5 6.45 25.0 6.52
33 16.6 4.14 19.8 5.33 22.9 6.57 23.2 6.61 23.5 6.64 24.1 6.70 24.7 6.76
35 16.6 4.41 19.8 5.67 22.5 6.81 22.8 6.85 23.1 6.88 23.7 6.95 24.3 7.01
37 16.6 4.69 19.8 6.04 22.2 7.06 22.5 7.08 22.7 7.12 23.4 7.19 23.9 7.26
39 16.6 4.99 19.8 6.43 21.8 7.30 22.1 7.33 22.4 7.37 23.0 7.44 23.6 7.52
41 16.6 5.04 19.8 6.49 21.6 7.35 21.9 7.38 22.2 7.42 22.7 7.49 22.9 7.57
43 16.6 5.09 19.8 6.57 21.4 7.40 21.7 7.44 22.1 7.47 22.5 7.52 22.5 7.72
45 16.6 5.25 19.8 6.61 21.2 7.47 21.5 7.52 21.9 7.54 22.2 7.73 22.3 7.90
-15 14.3 2.09 17.0 2.52 19.9 3.00 21.2 3.23 22.7 3.52 25.2 3.99 26.6 4.16
-13 14.3 2.10 17.0 2.52 19.9 3.02 21.2 3.24 22.7 3.52 25.2 4.00 26.6 4.18
-11 14.3 2.10 17.0 2.53 19.9 3.02 21.2 3.25 22.7 3.53 25.2 4.01 26.6 4.18
-9 14.8 2.12 17.6 2.55 20.5 3.04 21.8 3.26 23.5 3.54 25.9 4.04 27.3 4.21
-7 14.8 2.13 17.6 2.55 20.5 3.04 21.8 3.26 23.5 3.55 25.9 4.04 27.3 4.22
-5 15.1 2.14 18.0 2.57 21.0 3.06 22.4 3.28 23.8 3.56 26.8 4.05 28.3 4.23
-2 15.1 2.16 18.0 2.60 21.0 3.09 22.4 3.34 23.8 3.60 26.8 4.10 28.3 4.26
0 15.1 2.18 18.0 2.63 21.0 3.13 22.4 3.38 23.8 3.64 26.8 4.17 28.3 4.30
2 15.1 2.23 18.0 2.67 21.0 3.16 22.4 3.42 23.8 3.68 26.8 4.23 28.3 4.37
4 15.1 2.24 18.0 2.69 21.0 3.21 22.4 3.47 23.8 3.73 26.8 4.27 28.3 4.42
6 15.1 2.27 18.0 2.75 21.0 3.25 22.4 3.54 23.8 3.78 26.8 4.33 28.3 4.49
8 15.1 2.32 18.0 2.79 21.0 3.31 22.4 3.58 23.8 3.84 26.8 4.40 28.3 4.56
10 15.1 2.35 18.0 2.84 21.0 3.36 22.4 3.64 23.8 3.91 26.8 4.47 28.3 4.63
12 15.1 2.38 18.0 2.90 21.0 3.43 22.4 3.70 23.8 3.99 26.8 4.55 27.9 4.66
14 15.1 2.43 18.0 2.95 21.0 3.49 22.4 3.78 23.8 4.06 26.8 4.65 27.6 4.72
100% 16 15.1 2.47 18.0 3.01 21.0 3.57 22.4 3.85 23.8 4.14 26.6 4.70 27.2 4.77
18 15.1 2.52 18.0 3.06 21.0 3.63 22.4 3.92 23.8 4.22 26.3 4.86 26.9 4.89
20 15.1 2.57 18.0 3.13 21.0 3.74 22.4 4.12 23.8 4.53 25.9 5.09 26.5 5.13
21 15.1 2.59 18.0 3.15 21.0 3.88 22.4 4.27 23.8 4.68 25.8 5.21 26.3 5.25
23 15.1 2.66 18.0 3.36 21.0 4.15 22.4 4.57 23.8 5.02 25.4 5.44 25.9 5.49
25 15.1 2.83 18.0 3.59 21.0 4.44 22.4 4.90 23.8 5.38 25.0 5.68 25.6 5.73
27 15.1 3.02 18.0 3.83 21.0 4.75 22.4 5.24 23.8 5.76 24.6 5.92 25.2 5.98
29 15.1 3.22 18.0 4.09 21.0 5.07 22.4 5.60 23.8 6.11 24.3 6.17 24.9 6.21
31 15.1 3.43 18.0 4.36 21.0 5.41 22.4 5.98 23.4 6.35 23.9 6.41 24.5 6.46
33 15.1 3.64 18.0 4.65 21.0 5.76 22.4 6.38 23.0 6.59 23.6 6.64 24.2 6.71
35 15.1 3.87 18.0 4.94 21.0 6.15 22.4 6.80 22.6 6.83 23.2 6.89 23.8 6.95
37 15.1 4.11 18.0 5.26 21.0 6.55 22.0 7.04 22.3 7.07 22.9 7.14 23.4 7.19
39 15.1 4.37 18.0 5.59 21.0 6.97 21.7 7.28 21.9 7.31 22.5 7.38 23.0 7.45
41 15.1 4.58 18.0 5.79 21.0 7.23 21.3 7.33 21.8 7.43 22.1 7.55 22.7 7.60
43 15.1 4.78 18.0 6.00 21.0 7.36 21.0 7.41 21.6 7.50 22.2 7.60 22.3 7.69
45 15.1 5.05 18.0 6.27 21.0 7.49 20.6 7.51 21.5 7.63 22.0 7.72 21.9 7.79
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
34
Mini TVR Individual 60Hz
Table 2-7.2: 4TVH0076BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 12.8 1.85 15.4 2.22 17.9 2.62 19.1 2.88 20.4 3.07 22.7 3.51 25.1 4.02
-13 12.8 1.86 15.4 2.22 17.9 2.64 19.1 2.89 20.4 3.07 22.7 3.52 25.1 4.04
-11 12.8 1.86 15.4 2.23 17.9 2.64 19.1 2.90 20.4 3.08 22.7 3.53 25.1 4.04
-9 13.3 1.87 15.9 2.25 18.5 2.65 19.6 2.90 21.1 3.09 23.3 3.55 25.8 4.06
-7 13.3 1.89 15.9 2.25 18.5 2.65 19.6 2.90 21.1 3.10 23.3 3.55 25.8 4.07
-5 13.6 1.89 16.2 2.27 18.9 2.67 20.2 2.92 21.4 3.10 24.1 3.57 26.7 4.08
-2 13.6 1.91 16.2 2.29 18.9 2.71 20.2 2.96 21.4 3.14 24.1 3.60 26.7 4.13
0 13.6 1.93 16.2 2.32 18.9 2.75 20.2 2.99 21.4 3.18 24.1 3.64 26.7 4.16
2 13.6 1.96 16.2 2.35 18.9 2.78 20.2 3.04 21.4 3.23 24.1 3.72 26.7 4.22
4 13.6 1.99 16.2 2.38 18.9 2.82 20.2 3.08 21.4 3.27 24.1 3.78 26.7 4.28
6 13.6 2.02 16.2 2.43 18.9 2.88 20.2 3.14 21.4 3.33 24.1 3.84 26.7 4.35
8 13.6 2.06 16.2 2.48 18.9 2.93 20.2 3.18 21.4 3.39 24.1 3.91 26.7 4.39
10 13.6 2.10 16.2 2.53 18.9 2.99 20.2 3.23 21.4 3.46 24.1 3.96 26.7 4.46
12 13.6 2.14 16.2 2.57 18.9 3.04 20.2 3.28 21.4 3.53 24.1 4.03 26.7 4.55
14 13.6 2.17 16.2 2.62 18.9 3.10 20.2 3.34 21.4 3.59 24.1 4.11 26.7 4.63
90% 16 13.6 2.21 16.2 2.67 18.9 3.16 20.2 3.41 21.4 3.67 24.1 4.19 26.6 4.71
18 13.6 2.24 16.2 2.72 18.9 3.22 20.2 3.47 21.4 3.74 24.1 4.27 26.3 4.86
20 13.6 2.29 16.2 2.78 18.9 3.28 20.2 3.55 21.4 3.88 24.1 4.59 25.9 5.09
21 13.6 2.31 16.2 2.80 18.9 3.34 20.2 3.67 21.4 4.01 24.1 4.76 25.8 5.21

Part 2 - Outdoor Unit Engineering Data


23 13.6 2.36 16.2 2.91 18.9 3.57 20.2 3.93 21.4 4.31 24.1 5.10 25.4 5.44
25 13.6 2.48 16.2 3.12 18.9 3.82 20.2 4.21 21.4 4.60 24.1 5.46 25.0 5.68
27 13.6 2.64 16.2 3.32 18.9 4.08 20.2 4.49 21.4 4.92 24.1 5.85 24.6 5.92
29 13.6 2.81 16.2 3.54 18.9 4.35 20.2 4.79 21.4 5.26 23.8 6.11 24.3 6.16
31 13.6 2.99 16.2 3.77 18.9 4.64 20.2 5.11 21.4 5.61 23.4 6.35 23.9 6.41
33 13.6 3.17 16.2 4.00 18.9 4.95 20.2 5.45 21.4 5.98 23.1 6.60 23.6 6.64
35 13.6 3.37 16.2 4.26 18.9 5.27 20.2 5.81 21.4 6.38 22.7 6.84 23.2 6.89
37 13.6 3.57 16.2 4.53 18.9 5.61 20.2 6.19 21.4 6.80 22.3 7.07 22.9 7.13
39 13.6 3.79 16.2 4.82 18.9 5.97 20.2 6.59 21.4 7.24 22.0 7.32 22.5 7.38
41 13.6 3.92 16.2 5.04 18.9 6.18 20.2 6.76 21.4 7.28 21.8 7.51 22.3 7.55
43 13.6 4.11 16.2 5.26 18.9 6.40 20.2 6.94 21.4 7.44 21.7 7.61 22.1 7.67
45 13.6 4.37 16.2 5.52 18.9 6.66 20.2 7.17 21.4 7.65 21.6 7.69 21.8 7.77
-15 11.4 1.63 13.6 1.93 15.8 2.28 17.0 2.44 18.2 2.64 20.2 3.04 22.3 3.46
-13 11.4 1.64 13.6 1.93 15.8 2.30 17.0 2.45 18.2 2.64 20.2 3.05 22.3 3.48
-11 11.4 1.64 13.6 1.94 15.8 2.30 17.0 2.46 18.2 2.65 20.2 3.05 22.3 3.48
-9 11.8 1.65 14.1 1.95 16.4 2.31 17.4 2.47 18.8 2.66 20.8 3.07 22.9 3.50
-7 11.8 1.66 14.1 1.95 16.4 2.31 17.4 2.47 18.8 2.66 20.8 3.07 22.9 3.51
-5 12.1 1.66 14.4 1.97 16.7 2.33 17.9 2.48 19.1 2.67 21.4 3.08 23.8 3.52
-2 12.1 1.69 14.4 1.99 16.7 2.35 17.9 2.52 19.1 2.69 21.4 3.11 23.8 3.55
0 12.1 1.72 14.4 2.02 16.7 2.38 17.9 2.54 19.1 2.74 21.4 3.16 23.8 3.60
2 12.1 1.75 14.4 2.05 16.7 2.41 17.9 2.59 19.1 2.79 21.4 3.22 23.8 3.67
4 12.1 1.78 14.4 2.08 16.7 2.46 17.9 2.65 19.1 2.84 21.4 3.28 23.8 3.72
6 12.1 1.81 14.4 2.13 16.7 2.50 17.9 2.71 19.1 2.89 21.4 3.33 23.8 3.78
8 12.1 1.85 14.4 2.18 16.7 2.55 17.9 2.76 19.1 2.96 21.4 3.38 23.8 3.86
10 12.1 1.86 14.4 2.23 16.7 2.62 17.9 2.82 19.1 3.02 21.4 3.46 23.8 3.90
12 12.1 1.89 14.4 2.26 16.7 2.67 17.9 2.88 19.1 3.09 21.4 3.52 23.8 3.97
14 12.1 1.92 14.4 2.31 16.7 2.71 17.9 2.92 19.1 3.14 21.4 3.58 23.8 4.04
80% 16 12.1 1.95 14.4 2.35 16.7 2.77 17.9 2.98 19.1 3.20 21.4 3.66 23.8 4.11
18 12.1 1.99 14.4 2.39 16.7 2.82 17.9 3.04 19.1 3.26 21.4 3.73 23.8 4.20
20 12.1 2.03 14.4 2.44 16.7 2.88 17.9 3.10 19.1 3.33 21.4 3.87 23.8 4.49
21 12.1 2.04 14.4 2.46 16.7 2.91 17.9 3.13 19.1 3.40 21.4 4.01 23.8 4.66
23 12.1 2.08 14.4 2.51 16.7 3.04 17.9 3.34 19.1 3.64 21.4 4.29 23.8 4.99
25 12.1 2.14 14.4 2.67 16.7 3.25 17.9 3.57 19.1 3.89 21.4 4.59 23.8 5.34
27 12.1 2.28 14.4 2.84 16.7 3.46 17.9 3.80 19.1 4.15 21.4 4.90 23.8 5.72
29 12.1 2.43 14.4 3.02 16.7 3.69 17.9 4.05 19.1 4.44 21.4 5.23 23.8 6.11
31 12.1 2.58 14.4 3.22 16.7 3.93 17.9 4.32 19.1 4.73 21.4 5.59 23.4 6.35
33 12.1 2.74 14.4 3.42 16.7 4.19 17.9 4.60 19.1 5.03 21.4 5.96 23.0 6.59
35 12.1 2.91 14.4 3.64 16.7 4.45 17.9 4.89 19.1 5.36 21.4 6.35 22.6 6.83
37 12.1 3.08 14.4 3.86 16.7 4.74 17.9 5.21 19.1 5.71 21.4 6.77 22.3 7.07
39 12.1 3.26 14.4 4.11 16.7 5.04 17.9 5.54 19.1 6.08 21.4 7.21 21.9 7.31
41 12.1 3.34 14.4 4.15 16.7 5.11 17.9 5.69 19.1 6.19 21.4 7.40 21.8 7.44
43 12.1 3.43 14.4 4.19 16.7 5.19 17.9 5.79 19.1 6.27 21.4 7.48 21.7 7.52
45 12.1 3.53 14.4 4.24 16.7 5.29 17.9 5.91 19.1 6.38 21.4 7.56 21.4 7.65
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
35
Mini TVR Individual 60Hz
Table 2-7.2: 4TVH0076BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 10.0 1.45 12.0 1.71 13.9 1.94 14.9 2.09 15.9 2.24 17.6 2.55 19.6 2.92
-13 10.0 1.46 12.0 1.71 13.9 1.95 14.9 2.09 15.9 2.24 17.6 2.55 19.6 2.94
-11 10.0 1.46 12.0 1.72 13.9 1.95 14.9 2.10 15.9 2.24 17.6 2.56 19.6 2.94
-9 10.3 1.47 12.4 1.73 14.3 1.96 15.2 2.11 16.5 2.25 18.1 2.57 20.1 2.95
-7 10.3 1.48 12.4 1.73 14.3 1.96 15.2 2.11 16.5 2.25 18.1 2.57 20.1 2.96
-5 10.6 1.49 12.6 1.74 14.6 1.97 15.7 2.12 16.7 2.26 18.7 2.58 20.8 2.97
-2 10.6 1.50 12.6 1.75 14.6 1.99 15.7 2.16 16.7 2.30 18.7 2.62 20.8 3.01
0 10.6 1.51 12.6 1.77 14.6 2.03 15.7 2.20 16.7 2.34 18.7 2.68 20.8 3.05
2 10.6 1.51 12.6 1.78 14.6 2.06 15.7 2.24 16.7 2.38 18.7 2.73 20.8 3.10
4 10.6 1.53 12.6 1.83 14.6 2.10 15.7 2.28 16.7 2.43 18.7 2.78 20.8 3.17
6 10.6 1.56 12.6 1.86 14.6 2.16 15.7 2.35 16.7 2.49 18.7 2.83 20.8 3.23
8 10.6 1.59 12.6 1.91 14.6 2.21 15.7 2.39 16.7 2.54 18.7 2.91 20.8 3.30
10 10.6 1.62 12.6 1.94 14.6 2.26 15.7 2.44 16.7 2.61 18.7 2.97 20.8 3.34
12 10.6 1.66 12.6 1.97 14.6 2.31 15.7 2.48 16.7 2.66 18.7 3.02 20.8 3.40
14 10.6 1.69 12.6 2.01 14.6 2.35 15.7 2.52 16.7 2.70 18.7 3.08 20.8 3.46
70% 16 10.6 1.71 12.6 2.04 14.6 2.39 15.7 2.58 16.7 2.76 18.7 3.13 20.8 3.53
Mini TVR Individual Series Engineering Data Book

18 10.6 1.74 12.6 2.08 14.6 2.44 15.7 2.62 16.7 2.80 18.7 3.20 20.8 3.60
20 10.6 1.77 12.6 2.12 14.6 2.48 15.7 2.67 16.7 2.86 18.7 3.26 20.8 3.70
21 10.6 1.79 12.6 2.14 14.6 2.50 15.7 2.69 16.7 2.89 18.7 3.31 20.8 3.83
23 10.6 1.81 12.6 2.17 14.6 2.56 15.7 2.79 16.7 3.03 18.7 3.55 20.8 4.11
25 10.6 1.85 12.6 2.26 14.6 2.72 15.7 2.98 16.7 3.23 18.7 3.79 20.8 4.39
27 10.6 1.96 12.6 2.41 14.6 2.91 15.7 3.17 16.7 3.46 18.7 4.05 20.8 4.69
29 10.6 2.08 12.6 2.56 14.6 3.09 15.7 3.38 16.7 3.68 18.7 4.32 20.8 5.01
31 10.6 2.20 12.6 2.71 14.6 3.29 15.7 3.59 16.7 3.91 18.7 4.60 20.8 5.34
33 10.6 2.34 12.6 2.89 14.6 3.50 15.7 3.82 16.7 4.17 18.7 4.90 20.8 5.70
35 10.6 2.47 12.6 3.06 14.6 3.71 15.7 4.07 16.7 4.44 18.7 5.22 20.8 6.08
37 10.6 2.61 12.6 3.24 14.6 3.95 15.7 4.32 16.7 4.72 18.7 5.56 20.8 6.47
39 10.6 2.77 12.6 3.44 14.6 4.19 15.7 4.59 16.7 5.01 18.7 5.91 20.8 6.89
41 10.6 2.89 12.6 3.56 14.6 4.31 15.7 4.74 16.7 5.17 18.7 6.16 20.8 7.20
43 10.6 3.13 12.6 3.80 14.6 4.49 15.7 5.00 16.7 5.32 18.7 6.38 20.8 7.42
45 10.6 3.19 12.6 3.88 14.6 4.58 15.7 5.08 16.7 5.58 18.7 6.73 20.8 7.71
-15 8.5 1.24 10.2 1.44 11.9 1.68 12.7 1.80 13.7 1.95 15.1 2.18 16.8 2.50
-13 8.5 1.25 10.2 1.44 11.9 1.69 12.7 1.81 13.7 1.95 15.1 2.19 16.8 2.51
-11 8.5 1.25 10.2 1.45 11.9 1.69 12.7 1.81 13.7 1.96 15.1 2.19 16.8 2.51
-9 8.8 1.26 10.6 1.46 12.3 1.70 13.1 1.82 14.1 1.96 15.6 2.20 17.2 2.52
-7 8.8 1.27 10.6 1.46 12.3 1.70 13.1 1.82 14.1 1.97 15.6 2.20 17.2 2.53
-5 9.0 1.27 10.8 1.47 12.6 1.71 13.4 1.82 14.3 1.97 16.1 2.21 17.8 2.54
-2 9.0 1.27 10.8 1.49 12.6 1.74 13.4 1.85 14.3 1.99 16.1 2.25 17.8 2.55
0 9.0 1.29 10.8 1.51 12.6 1.77 13.4 1.87 14.3 2.02 16.1 2.28 17.8 2.59
2 9.0 1.32 10.8 1.55 12.6 1.80 13.4 1.91 14.3 2.05 16.1 2.33 17.8 2.62
4 9.0 1.35 10.8 1.58 12.6 1.83 13.4 1.93 14.3 2.08 16.1 2.36 17.8 2.66
6 9.0 1.37 10.8 1.61 12.6 1.87 13.4 1.98 14.3 2.12 16.1 2.41 17.8 2.72
8 9.0 1.39 10.8 1.63 12.6 1.90 13.4 2.01 14.3 2.17 16.1 2.45 17.8 2.76
10 9.0 1.42 10.8 1.67 12.6 1.93 13.4 2.07 14.3 2.21 16.1 2.50 17.8 2.80
12 9.0 1.45 10.8 1.70 12.6 1.97 13.4 2.11 14.3 2.24 16.1 2.55 17.8 2.85
14 9.0 1.47 10.8 1.72 12.6 2.00 13.4 2.14 14.3 2.29 16.1 2.59 17.8 2.90
60% 16 9.0 1.48 10.8 1.75 12.6 2.03 13.4 2.18 14.3 2.33 16.1 2.64 17.8 2.96
18 9.0 1.51 10.8 1.78 12.6 2.07 13.4 2.22 14.3 2.37 16.1 2.68 17.8 3.01
20 9.0 1.53 10.8 1.81 12.6 2.11 13.4 2.26 14.3 2.42 16.1 2.74 17.8 3.08
21 9.0 1.55 10.8 1.82 12.6 2.13 13.4 2.28 14.3 2.44 16.1 2.77 17.8 3.11
23 9.0 1.57 10.8 1.86 12.6 2.16 13.4 2.33 14.3 2.48 16.1 2.88 17.8 3.31
25 9.0 1.59 10.8 1.89 12.6 2.24 13.4 2.44 14.3 2.64 16.1 3.07 17.8 3.53
27 9.0 1.66 10.8 2.01 12.6 2.39 13.4 2.60 14.3 2.81 16.1 3.27 17.8 3.77
29 9.0 1.75 10.8 2.13 12.6 2.55 13.4 2.77 14.3 3.00 16.1 3.49 17.8 4.02
31 9.0 1.86 10.8 2.25 12.6 2.70 13.4 2.94 14.3 3.19 16.1 3.71 17.8 4.28
33 9.0 1.96 10.8 2.39 12.6 2.87 13.4 3.12 14.3 3.39 16.1 3.95 17.8 4.56
35 9.0 2.08 10.8 2.54 12.6 3.04 13.4 3.32 14.3 3.60 16.1 4.21 17.8 4.86
37 9.0 2.20 10.8 2.68 12.6 3.23 13.4 3.52 14.3 3.82 16.1 4.47 17.8 5.17
39 9.0 2.32 10.8 2.84 12.6 3.42 13.4 3.73 14.3 4.06 16.1 4.75 17.8 5.50
41 9.0 2.39 10.8 2.96 12.6 3.54 13.4 3.88 14.3 4.21 16.1 4.97 17.8 5.75
43 9.0 2.47 10.8 3.09 12.6 3.67 13.4 3.99 14.3 4.36 16.1 5.18 17.8 6.00
45 9.0 2.58 10.8 3.24 12.6 3.82 13.4 4.14 14.3 4.57 16.1 5.41 17.8 6.33
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
36
Mini TVR Individual 60Hz
Table 2-7.2: 4TVH0076BD000AAcooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 7.1 1.08 8.6 1.25 9.9 1.43 10.6 1.51 11.4 1.60 12.6 1.81 14.0 1.95
-13 7.1 1.08 8.6 1.25 9.9 1.44 10.6 1.51 11.4 1.60 12.6 1.81 14.0 1.96
-11 7.1 1.08 8.6 1.25 9.9 1.44 10.6 1.52 11.4 1.61 12.6 1.82 14.0 1.96
-9 7.4 1.09 8.9 1.26 10.3 1.45 10.9 1.52 11.7 1.61 12.9 1.83 14.4 1.97
-7 7.4 1.10 8.9 1.26 10.3 1.45 10.9 1.52 11.7 1.61 12.9 1.83 14.4 1.97
-5 7.6 1.10 9.0 1.27 10.5 1.46 11.2 1.53 11.9 1.62 13.4 1.84 14.9 1.98
-2 7.6 1.11 9.0 1.30 10.5 1.48 11.2 1.55 11.9 1.64 13.4 1.86 14.9 2.01
0 7.6 1.13 9.0 1.32 10.5 1.50 11.2 1.57 11.9 1.66 13.4 1.89 14.9 2.04
2 7.6 1.14 9.0 1.34 10.5 1.53 11.2 1.60 11.9 1.69 13.4 1.90 14.9 2.08
4 7.6 1.15 9.0 1.36 10.5 1.55 11.2 1.62 11.9 1.73 13.4 1.95 14.9 2.13
6 7.6 1.18 9.0 1.38 10.5 1.57 11.2 1.65 11.9 1.76 13.4 1.98 14.9 2.20
8 7.6 1.20 9.0 1.40 10.5 1.60 11.2 1.69 11.9 1.78 13.4 2.01 14.9 2.27
10 7.6 1.23 9.0 1.42 10.5 1.62 11.2 1.72 11.9 1.83 13.4 2.06 14.9 2.30
12 7.6 1.24 9.0 1.44 10.5 1.65 11.2 1.75 11.9 1.87 13.4 2.10 14.9 2.34
14 7.6 1.26 9.0 1.46 10.5 1.67 11.2 1.79 11.9 1.90 13.4 2.14 14.9 2.38
50% 16 7.6 1.27 9.0 1.48 10.5 1.70 11.2 1.81 11.9 1.92 13.4 2.17 14.9 2.42
18 7.6 1.29 9.0 1.50 10.5 1.72 11.2 1.84 11.9 1.96 13.4 2.21 14.9 2.46
20 7.6 1.31 9.0 1.52 10.5 1.75 11.2 1.87 11.9 2.00 13.4 2.25 14.9 2.51
21 7.6 1.32 9.0 1.54 10.5 1.77 11.2 1.89 11.9 2.02 13.4 2.27 14.9 2.54

Part 2 - Outdoor Unit Engineering Data


23 7.6 1.34 9.0 1.56 10.5 1.80 11.2 1.92 11.9 2.05 13.4 2.31 14.9 2.59
25 7.6 1.36 9.0 1.59 10.5 1.83 11.2 1.96 11.9 2.12 13.4 2.43 14.9 2.77
27 7.6 1.38 9.0 1.65 10.5 1.93 11.2 2.09 11.9 2.25 13.4 2.58 14.9 2.95
29 7.6 1.46 9.0 1.74 10.5 2.05 11.2 2.22 11.9 2.39 13.4 2.75 14.9 3.14
31 7.6 1.54 9.0 1.84 10.5 2.17 11.2 2.36 11.9 2.54 13.4 2.92 14.9 3.34
33 7.6 1.63 9.0 1.95 10.5 2.31 11.2 2.49 11.9 2.69 13.4 3.11 14.9 3.56
35 7.6 1.72 9.0 2.06 10.5 2.44 11.2 2.64 11.9 2.85 13.4 3.30 14.9 3.78
37 7.6 1.81 9.0 2.18 10.5 2.58 11.2 2.79 11.9 3.02 13.4 3.50 14.9 4.01
39 7.6 1.92 9.0 2.30 10.5 2.73 11.2 2.96 11.9 3.21 13.4 3.71 14.9 4.26
41 7.6 1.99 9.0 2.40 10.5 2.83 11.2 3.10 11.9 3.35 13.4 3.91 14.9 4.46
43 7.6 2.13 9.0 2.56 10.5 2.93 11.2 3.24 11.9 3.43 13.4 4.11 14.9 4.66
45 7.6 2.17 9.0 2.63 10.5 3.13 11.2 3.49 11.9 3.58 13.4 4.50 14.9 5.05
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

37
Mini TVR Individual 60Hz
Table 2-7.3: 4TVH0089BD000AA cooling capacity
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 21.7 3.04 25.7 3.71 30.0 3.99 31.1 4.17 32.7 4.31 33.3 4.67 34.1 4.68
-13 21.7 3.06 25.7 3.71 30.0 4.02 31.1 4.19 32.7 4.31 33.3 4.68 34.1 4.71
-11 21.7 3.06 25.7 3.74 30.0 4.02 31.1 4.20 32.7 4.32 33.3 4.68 34.1 4.71
-9 22.4 3.08 26.7 3.77 30.9 4.03 31.9 4.22 33.9 4.33 34.2 4.71 34.9 4.75
-7 22.4 3.10 26.7 3.77 30.9 4.03 31.9 4.23 33.9 4.33 34.2 4.71 34.9 4.75
-5 22.8 3.11 27.2 3.79 31.6 4.06 32.8 4.23 34.4 4.35 35.2 4.73 36.1 4.76
-2 22.8 3.11 27.2 3.87 31.6 4.06 32.8 4.25 34.4 4.35 35.2 4.79 36.1 4.81
0 22.8 3.16 27.2 3.93 31.6 4.21 32.8 4.49 34.4 4.60 35.2 4.85 36.1 4.87
2 22.8 3.22 27.2 3.94 31.6 4.36 32.8 4.74 34.4 4.66 35.2 4.88 36.1 4.94
4 22.8 3.29 27.2 4.02 31.6 4.51 32.8 4.76 34.4 4.72 35.2 4.96 36.1 5.04
6 22.8 3.35 27.2 4.10 31.6 4.68 32.8 4.80 34.0 4.86 34.8 5.04 35.7 5.08
8 22.8 3.43 27.2 4.19 31.6 4.91 32.8 5.04 33.6 5.02 34.4 5.05 35.2 5.12
10 22.8 3.50 27.2 4.28 31.6 5.09 32.8 5.20 33.1 5.11 34.0 5.13 34.8 5.27
12 22.8 3.56 27.2 4.36 31.6 5.19 32.3 5.28 32.8 5.19 33.5 5.21 34.4 5.31
14 22.8 3.64 27.2 4.45 31.5 5.27 31.9 5.36 32.3 5.27 33.1 5.28 34.0 5.43
130% 16 22.8 3.70 27.2 4.54 31.1 5.35 31.5 5.43 31.8 5.42 32.7 5.36 33.5 5.51
Mini TVR Individual Series Engineering Data Book

18 22.8 3.77 27.2 4.63 30.6 5.43 31.0 5.46 31.5 5.49 32.3 5.54 33.1 5.59
20 22.8 3.85 27.2 4.93 30.2 5.70 30.6 5.73 31.0 5.76 31.8 5.81 32.7 5.87
21 22.8 3.95 27.2 5.10 30.0 5.83 30.5 5.86 30.8 5.89 31.7 5.95 32.5 6.00
23 22.8 4.24 27.2 5.47 29.6 6.09 30.0 6.13 30.4 6.16 31.2 6.22 32.0 6.28
25 22.8 4.53 27.2 5.86 29.2 6.36 29.5 6.39 30.0 6.43 30.8 6.49 31.7 6.56
27 22.8 4.83 27.2 6.27 28.8 6.63 29.2 6.67 29.5 6.70 30.4 6.77 31.2 6.84
29 22.8 5.16 27.2 6.70 28.3 6.89 28.7 6.93 29.2 6.98 30.0 7.05 30.8 7.12
31 22.8 5.51 27.1 7.09 27.9 7.17 28.3 7.21 28.7 7.24 29.5 7.32 30.4 7.41
33 22.8 5.87 26.6 7.35 27.5 7.44 27.9 7.48 28.3 7.52 29.2 7.60 29.9 7.68
35 22.8 6.26 26.2 7.62 27.0 7.71 27.5 7.75 27.9 7.80 28.7 7.89 29.5 7.97
37 22.8 6.66 25.8 7.90 26.6 7.99 27.0 8.03 27.5 8.08 28.2 8.17 29.1 8.27
39 22.8 7.09 25.3 7.98 26.2 8.26 26.6 8.31 27.0 8.36 27.9 8.45 28.7 8.55
41 22.8 7.46 25.1 8.06 25.9 8.33 26.4 8.38 26.7 8.44 27.6 8.47 27.6 8.63
43 22.8 7.65 24.9 8.10 25.8 8.36 26.2 8.42 26.5 8.45 27.1 8.48 27.3 8.65
45 22.8 8.03 24.7 8.17 25.5 8.43 26.0 8.48 26.1 8.49 26.3 8.51 26.7 8.81
-15 19.9 2.94 23.7 3.56 27.6 4.22 29.6 4.62 31.2 4.84 31.5 4.97 32.1 5.09
-13 19.9 2.95 23.7 3.56 27.6 4.24 29.6 4.64 31.2 4.84 31.5 4.98 32.1 5.12
-11 19.9 2.95 23.7 3.58 27.6 4.24 29.6 4.65 31.2 4.86 31.5 4.99 32.1 5.12
-9 20.6 2.97 24.6 3.61 28.6 4.27 30.3 4.67 32.2 4.87 32.4 5.02 33.0 5.15
-7 20.6 3.00 24.6 3.61 28.6 4.27 30.3 4.67 32.2 4.88 32.4 5.02 33.0 5.16
-5 21.1 3.00 25.1 3.63 29.2 4.30 31.2 4.69 32.7 4.89 33.4 5.04 34.2 5.18
-2 21.1 3.03 25.1 3.67 29.2 4.34 31.2 4.71 32.7 4.94 33.4 5.08 34.2 5.19
0 21.1 3.06 25.1 3.70 29.2 4.39 31.2 4.73 32.7 4.99 33.4 5.11 34.2 5.20
2 21.1 3.07 25.1 3.74 29.2 4.42 31.2 4.77 32.7 5.01 33.4 5.15 34.2 5.21
4 21.1 3.10 25.1 3.78 29.2 4.48 31.2 4.81 32.7 5.07 33.4 5.16 34.2 5.23
6 21.1 3.13 25.1 3.81 29.2 4.54 31.2 4.87 32.7 5.13 33.4 5.21 34.2 5.25
8 21.1 3.16 25.1 3.85 29.2 4.60 31.2 4.93 32.7 5.18 33.4 5.22 34.2 5.27
10 21.1 3.20 25.1 3.90 29.2 4.64 31.2 5.02 32.7 5.18 33.4 5.24 34.2 5.29
12 21.1 3.26 25.1 3.97 29.2 4.73 31.2 5.11 32.2 5.21 33.0 5.21 33.7 5.33
14 21.1 3.32 25.1 4.06 29.2 4.82 31.2 5.21 31.8 5.24 32.6 5.29 33.3 5.39
120% 16 21.1 3.38 25.1 4.14 29.2 4.92 31.0 4.10 31.4 5.31 32.1 5.38 32.9 5.47
18 21.1 3.44 25.1 4.22 29.2 5.08 30.6 5.43 30.9 5.45 31.7 5.50 32.5 5.55
20 21.1 3.51 25.1 4.38 29.2 5.47 30.2 5.70 30.6 5.72 31.3 5.77 32.0 5.82
21 21.1 3.54 25.1 4.54 29.2 5.66 29.9 5.83 30.3 5.85 31.1 5.90 31.9 5.96
23 21.1 3.79 25.1 4.86 29.2 6.06 29.5 6.08 29.9 6.12 30.6 6.18 31.4 6.23
25 21.1 4.05 25.1 5.20 28.7 6.33 29.1 6.35 29.4 6.38 30.3 6.44 31.0 6.50
27 21.1 4.32 25.1 5.56 28.3 6.59 28.7 6.63 29.1 6.66 29.8 6.72 30.6 6.78
29 21.1 4.61 25.1 5.94 27.9 6.85 28.2 6.89 28.6 6.92 29.3 7.00 30.2 7.06
31 21.1 4.92 25.1 6.34 27.4 7.13 27.9 7.16 28.2 7.20 29.0 7.27 29.7 7.34
33 21.1 5.23 25.1 6.76 27.0 7.40 27.4 7.44 27.8 7.47 28.5 7.55 29.2 7.62
35 21.1 5.57 25.1 7.21 26.6 7.66 26.9 7.70 27.4 7.74 28.1 7.83 28.9 7.91
37 21.1 5.93 25.1 7.68 26.2 7.94 26.6 7.98 26.9 8.02 27.7 8.10 28.4 8.19
39 21.1 6.31 25.0 8.11 25.7 8.20 26.1 8.26 26.5 8.30 27.3 8.39 28.0 8.47
41 21.1 6.48 24.8 8.17 25.5 8.26 25.9 8.31 26.3 8.35 27.1 8.41 27.2 8.53
43 21.1 6.58 24.6 8.23 25.3 8.31 25.7 8.34 26.1 8.38 26.6 8.44 26.8 8.71
45 21.1 6.66 24.5 8.30 25.1 8.39 25.4 8.42 25.8 8.45 26.1 8.46 26.5 8.89
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
38
Mini TVR Individual 60Hz
Table 2-7.3: 4TVH0089BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 18.2 2.56 21.8 3.19 25.3 3.82 27.1 4.12 29.0 4.45 30.9 4.60 31.5 4.74
-13 18.2 2.57 21.8 3.19 25.3 3.84 27.1 4.13 29.0 4.45 30.9 4.61 31.5 4.76
-11 18.2 2.57 21.8 3.22 25.3 3.84 27.1 4.15 29.0 4.47 30.9 4.62 31.5 4.76
-9 18.9 2.60 22.6 3.24 26.2 3.87 27.8 4.16 30.0 4.48 31.7 4.65 32.4 4.79
-7 18.9 2.62 22.6 3.24 26.2 3.87 27.8 4.16 30.0 4.49 31.7 4.65 32.4 4.80
-5 19.3 2.62 23.0 3.26 26.7 3.89 28.6 4.18 30.5 4.50 32.8 4.67 33.5 4.81
-2 19.3 2.67 23.0 3.30 26.7 3.93 28.6 4.22 30.5 4.53 32.8 4.71 33.5 4.84
0 19.3 2.70 23.0 3.32 26.7 3.96 28.6 4.25 30.5 4.58 32.8 4.76 33.5 4.90
2 19.3 2.76 23.0 3.35 26.7 4.02 28.6 4.29 30.5 4.63 32.8 4.83 33.5 4.96
4 19.3 2.81 23.0 3.39 26.7 4.06 28.6 4.35 30.5 4.70 32.8 4.90 33.5 5.00
6 19.3 2.84 23.0 3.43 26.7 4.09 28.6 4.42 30.5 4.75 32.8 4.95 33.5 5.08
8 19.3 2.86 23.0 3.49 26.7 4.14 28.6 4.46 30.5 4.81 32.8 4.98 33.5 5.13
10 19.3 2.90 23.0 3.53 26.7 4.20 28.6 4.54 30.5 4.89 32.8 5.02 33.5 5.18
12 19.3 2.96 23.0 3.61 26.7 4.28 28.6 4.63 30.5 4.98 32.4 5.09 33.1 5.25
14 19.3 3.01 23.0 3.67 26.7 4.36 28.6 4.71 30.5 5.07 31.9 5.13 32.7 5.28
110% 16 19.3 3.06 23.0 3.74 26.7 4.45 28.6 4.80 30.5 5.17 31.6 5.19 32.2 5.34
18 19.3 3.12 23.0 3.81 26.7 4.54 28.6 4.94 30.5 5.42 31.1 5.46 31.9 5.51
20 19.3 3.19 23.0 3.89 26.7 4.80 28.6 5.31 30.0 5.69 30.7 5.73 31.4 5.78
21 19.3 3.22 23.0 4.00 26.7 4.98 28.6 5.50 29.8 5.82 30.5 5.86 31.2 5.91

Part 2 - Outdoor Unit Engineering Data


23 19.3 3.37 23.0 4.29 26.7 5.34 28.6 5.90 29.3 6.07 30.1 6.13 30.7 6.19
25 19.3 3.60 23.0 4.59 26.7 5.71 28.6 6.32 29.0 6.34 29.6 6.40 30.4 6.45
27 19.3 3.83 23.0 4.91 26.7 6.11 28.1 6.59 28.5 6.61 29.3 6.67 29.9 6.73
29 19.3 4.09 23.0 5.23 26.7 6.52 27.8 6.85 28.1 6.88 28.8 6.94 29.5 7.01
31 19.3 4.35 23.0 5.58 26.7 6.97 27.3 7.12 27.7 7.15 28.4 7.21 29.1 7.28
33 19.3 4.63 23.0 5.95 26.6 7.34 26.9 7.39 27.3 7.42 28.0 7.49 28.7 7.56
35 19.3 4.93 23.0 6.34 26.1 7.61 26.5 7.65 26.8 7.69 27.5 7.76 28.2 7.84
37 19.3 5.24 23.0 6.75 25.7 7.89 26.1 7.92 26.4 7.96 27.1 8.04 27.8 8.11
39 19.3 5.57 23.0 7.19 25.3 8.15 25.6 8.19 26.0 8.24 26.7 8.32 27.4 8.40
41 19.3 5.63 23.0 7.25 25.1 8.21 25.4 8.25 25.8 8.29 26.3 8.37 26.6 8.46
43 19.3 5.69 23.0 7.34 24.9 8.27 25.2 8.31 25.6 8.35 26.1 8.41 26.2 8.63
45 19.3 5.87 23.0 7.38 24.6 8.34 25.0 8.41 25.4 8.43 25.8 8.63 25.9 8.83
-15 16.6 2.34 19.8 2.81 23.0 3.35 24.6 3.61 26.4 3.94 29.3 4.46 30.9 4.65
-13 16.6 2.34 19.8 2.81 23.0 3.38 24.6 3.63 26.4 3.94 29.3 4.47 30.9 4.68
-11 16.6 2.34 19.8 2.83 23.0 3.38 24.6 3.64 26.4 3.95 29.3 4.49 30.9 4.68
-9 17.2 2.36 20.5 2.85 23.8 3.40 25.3 3.65 27.2 3.96 30.1 4.51 31.7 4.70
-7 17.2 2.38 20.5 2.85 23.8 3.40 25.3 3.65 27.2 3.97 30.1 4.51 31.7 4.71
-5 17.6 2.39 20.9 2.87 24.3 3.42 26.0 3.66 27.7 3.97 31.1 4.53 32.9 4.73
-2 17.6 2.42 20.9 2.91 24.3 3.46 26.0 3.73 27.7 4.03 31.1 4.58 32.9 4.76
0 17.6 2.44 20.9 2.94 24.3 3.50 26.0 3.78 27.7 4.07 31.1 4.66 32.9 4.81
2 17.6 2.49 20.9 2.98 24.3 3.53 26.0 3.83 27.7 4.11 31.1 4.73 32.9 4.89
4 17.6 2.51 20.9 3.01 24.3 3.59 26.0 3.88 27.7 4.16 31.1 4.77 32.9 4.94
6 17.6 2.54 20.9 3.07 24.3 3.63 26.0 3.95 27.7 4.23 31.1 4.84 32.9 5.02
8 17.6 2.59 20.9 3.12 24.3 3.70 26.0 4.00 27.7 4.29 31.1 4.92 32.9 5.10
10 17.6 2.62 20.9 3.18 24.3 3.76 26.0 4.07 27.7 4.37 31.1 5.00 32.9 5.17
12 17.6 2.66 20.9 3.24 24.3 3.83 26.0 4.14 27.7 4.46 31.1 5.09 32.4 5.21
14 17.6 2.71 20.9 3.30 24.3 3.90 26.0 4.22 27.7 4.54 31.1 5.19 32.0 5.28
100% 16 17.6 2.77 20.9 3.36 24.3 3.98 26.0 4.30 27.7 4.63 30.9 5.25 31.6 5.34
18 17.6 2.82 20.9 3.42 24.3 4.06 26.0 4.38 27.7 4.72 30.6 5.43 31.2 5.47
20 17.6 2.87 20.9 3.49 24.3 4.18 26.0 4.61 27.7 5.06 30.1 5.68 30.7 5.74
21 17.6 2.90 20.9 3.52 24.3 4.33 26.0 4.77 27.7 5.23 29.9 5.82 30.6 5.87
23 17.6 2.97 20.9 3.76 24.3 4.64 26.0 5.11 27.7 5.61 29.5 6.08 30.1 6.14
25 17.6 3.16 20.9 4.02 24.3 4.97 26.0 5.48 27.7 6.01 29.1 6.35 29.7 6.40
27 17.6 3.38 20.9 4.28 24.3 5.31 26.0 5.86 27.7 6.43 28.6 6.62 29.3 6.68
29 17.6 3.59 20.9 4.57 24.3 5.66 26.0 6.26 27.6 6.83 28.2 6.89 28.9 6.94
31 17.6 3.83 20.9 4.88 24.3 6.04 26.0 6.68 27.2 7.10 27.8 7.16 28.4 7.22
33 17.6 4.07 20.9 5.19 24.3 6.44 26.0 7.13 26.7 7.36 27.4 7.43 28.0 7.50
35 17.6 4.32 20.9 5.52 24.3 6.87 26.0 7.60 26.3 7.63 26.9 7.70 27.6 7.76
37 17.6 4.60 20.9 5.88 24.3 7.32 25.5 7.87 25.9 7.91 26.6 7.98 27.1 8.04
39 17.6 4.89 20.9 6.25 24.3 7.79 25.2 8.13 25.4 8.17 26.1 8.25 26.7 8.33
41 17.6 5.11 20.9 6.48 24.3 8.08 24.8 8.19 25.2 8.30 25.6 8.44 26.4 8.50
43 17.6 5.34 20.9 6.70 24.3 8.23 24.4 8.28 25.1 8.38 25.8 8.49 25.9 8.59
45 17.6 5.65 20.9 7.01 24.3 8.37 23.9 8.40 24.9 8.53 25.6 8.63 25.4 8.71
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
39
Mini TVR Individual 60Hz
Table 2-7.3: 4TVH0089BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 14.9 2.07 17.8 2.48 20.8 2.93 22.2 3.22 23.7 3.44 26.3 3.93 29.2 4.49
-13 14.9 2.07 17.8 2.48 20.8 2.95 22.2 3.23 23.7 3.44 26.3 3.94 29.2 4.52
-11 14.9 2.07 17.8 2.50 20.8 2.95 22.2 3.24 23.7 3.45 26.3 3.95 29.2 4.52
-9 15.5 2.09 18.5 2.51 21.5 2.97 22.7 3.25 24.5 3.46 27.1 3.97 30.0 4.54
-7 15.5 2.11 18.5 2.51 21.5 2.97 22.7 3.25 24.5 3.46 27.1 3.97 30.0 4.55
-5 15.8 2.11 18.9 2.53 21.9 2.99 23.4 3.26 24.9 3.47 27.9 3.99 31.0 4.57
-2 15.8 2.13 18.9 2.56 21.9 3.03 23.4 3.31 24.9 3.51 27.9 4.03 31.0 4.61
0 15.8 2.16 18.9 2.59 21.9 3.07 23.4 3.34 24.9 3.55 27.9 4.07 31.0 4.65
2 15.8 2.19 18.9 2.62 21.9 3.10 23.4 3.40 24.9 3.61 27.9 4.16 31.0 4.71
4 15.8 2.23 18.9 2.66 21.9 3.16 23.4 3.44 24.9 3.66 27.9 4.22 31.0 4.78
6 15.8 2.26 18.9 2.71 21.9 3.21 23.4 3.51 24.9 3.72 27.9 4.29 31.0 4.86
8 15.8 2.30 18.9 2.77 21.9 3.28 23.4 3.55 24.9 3.79 27.9 4.37 31.0 4.91
10 15.8 2.35 18.9 2.83 21.9 3.34 23.4 3.61 24.9 3.87 27.9 4.42 31.0 4.99
12 15.8 2.39 18.9 2.88 21.9 3.40 23.4 3.67 24.9 3.94 27.9 4.51 31.0 5.08
14 15.8 2.43 18.9 2.93 21.9 3.46 23.4 3.74 24.9 4.01 27.9 4.59 31.0 5.17
90% 16 15.8 2.47 18.9 2.98 21.9 3.53 23.4 3.81 24.9 4.10 27.9 4.68 30.9 5.26
Mini TVR Individual Series Engineering Data Book

18 15.8 2.51 18.9 3.04 21.9 3.59 23.4 3.88 24.9 4.18 27.9 4.77 30.6 5.43
20 15.8 2.56 18.9 3.11 21.9 3.67 23.4 3.96 24.9 4.33 27.9 5.13 30.1 5.68
21 15.8 2.58 18.9 3.13 21.9 3.73 23.4 4.10 24.9 4.49 27.9 5.32 29.9 5.82
23 15.8 2.63 18.9 3.26 21.9 3.99 23.4 4.39 24.9 4.81 27.9 5.70 29.4 6.08
25 15.8 2.78 18.9 3.48 21.9 4.27 23.4 4.70 24.9 5.14 27.9 6.10 29.1 6.35
27 15.8 2.95 18.9 3.71 21.9 4.56 23.4 5.02 24.9 5.50 27.9 6.53 28.6 6.62
29 15.8 3.14 18.9 3.95 21.9 4.86 23.4 5.36 24.9 5.88 27.7 6.83 28.2 6.88
31 15.8 3.34 18.9 4.21 21.9 5.18 23.4 5.71 24.9 6.27 27.2 7.10 27.8 7.16
33 15.8 3.54 18.9 4.48 21.9 5.53 23.4 6.09 24.9 6.69 26.8 7.37 27.4 7.43
35 15.8 3.77 18.9 4.76 21.9 5.89 23.4 6.49 24.9 7.13 26.4 7.64 26.9 7.70
37 15.8 3.99 18.9 5.06 21.9 6.27 23.4 6.91 24.9 7.60 25.9 7.91 26.6 7.97
39 15.8 4.24 18.9 5.39 21.9 6.67 23.4 7.36 24.9 8.09 25.5 8.18 26.1 8.24
41 15.8 4.39 18.9 5.63 21.9 6.91 23.4 7.56 24.9 8.14 25.4 8.39 25.9 8.44
43 15.8 4.60 18.9 5.87 21.9 7.15 23.4 7.75 24.9 8.31 25.2 8.50 25.7 8.57
45 15.8 4.89 18.9 6.17 21.9 7.45 23.4 8.01 24.9 8.54 25.1 8.59 25.3 8.68
-15 13.2 1.82 15.8 2.15 18.4 2.55 19.7 2.73 21.2 2.95 23.4 3.39 25.9 3.87
-13 13.2 1.83 15.8 2.15 18.4 2.57 19.7 2.74 21.2 2.95 23.4 3.40 25.9 3.89
-11 13.2 1.83 15.8 2.17 18.4 2.57 19.7 2.75 21.2 2.96 23.4 3.41 25.9 3.89
-9 13.7 1.84 16.4 2.18 19.0 2.59 20.2 2.76 21.8 2.97 24.1 3.43 26.6 3.91
-7 13.7 1.86 16.4 2.18 19.0 2.59 20.2 2.76 21.8 2.98 24.1 3.43 26.6 3.92
-5 14.0 1.86 16.7 2.20 19.4 2.60 20.8 2.77 22.2 2.98 24.9 3.45 27.6 3.93
-2 14.0 1.89 16.7 2.23 19.4 2.63 20.8 2.81 22.2 3.01 24.9 3.48 27.6 3.97
0 14.0 1.92 16.7 2.25 19.4 2.66 20.8 2.84 22.2 3.06 24.9 3.53 27.6 4.03
2 14.0 1.96 16.7 2.29 19.4 2.70 20.8 2.90 22.2 3.12 24.9 3.60 27.6 4.10
4 14.0 1.99 16.7 2.32 19.4 2.75 20.8 2.96 22.2 3.17 24.9 3.66 27.6 4.16
6 14.0 2.02 16.7 2.38 19.4 2.79 20.8 3.03 22.2 3.23 24.9 3.72 27.6 4.23
8 14.0 2.06 16.7 2.43 19.4 2.86 20.8 3.08 22.2 3.30 24.9 3.77 27.6 4.31
10 14.0 2.08 16.7 2.49 19.4 2.93 20.8 3.15 22.2 3.38 24.9 3.86 27.6 4.35
12 14.0 2.11 16.7 2.53 19.4 2.98 20.8 3.22 22.2 3.45 24.9 3.93 27.6 4.44
14 14.0 2.15 16.7 2.58 19.4 3.03 20.8 3.27 22.2 3.51 24.9 4.00 27.6 4.52
80% 16 14.0 2.18 16.7 2.62 19.4 3.09 20.8 3.33 22.2 3.58 24.9 4.09 27.6 4.60
18 14.0 2.22 16.7 2.67 19.4 3.15 20.8 3.40 22.2 3.65 24.9 4.17 27.6 4.69
20 14.0 2.26 16.7 2.72 19.4 3.22 20.8 3.46 22.2 3.72 24.9 4.32 27.6 5.02
21 14.0 2.28 16.7 2.75 19.4 3.25 20.8 3.50 22.2 3.80 24.9 4.48 27.6 5.20
23 14.0 2.33 16.7 2.81 19.4 3.40 20.8 3.73 22.2 4.07 24.9 4.79 27.6 5.58
25 14.0 2.40 16.7 2.98 19.4 3.64 20.8 3.98 22.2 4.34 24.9 5.13 27.6 5.97
27 14.0 2.55 16.7 3.18 19.4 3.87 20.8 4.25 22.2 4.64 24.9 5.48 27.6 6.39
29 14.0 2.71 16.7 3.38 19.4 4.13 20.8 4.53 22.2 4.96 24.9 5.85 27.6 6.83
31 14.0 2.88 16.7 3.60 19.4 4.39 20.8 4.82 22.2 5.29 24.9 6.25 27.1 7.10
33 14.0 3.06 16.7 3.82 19.4 4.68 20.8 5.14 22.2 5.62 24.9 6.66 26.7 7.36
35 14.0 3.25 16.7 4.07 19.4 4.98 20.8 5.47 22.2 5.99 24.9 7.10 26.3 7.63
37 14.0 3.44 16.7 4.31 19.4 5.30 20.8 5.83 22.2 6.38 24.9 7.57 25.9 7.90
39 14.0 3.65 16.7 4.60 19.4 5.63 20.8 6.20 22.2 6.79 24.9 8.06 25.4 8.17
41 14.0 3.73 16.7 4.64 19.4 5.72 20.8 6.36 22.2 6.91 24.9 8.27 25.3 8.32
43 14.0 3.84 16.7 4.68 19.4 5.80 20.8 6.47 22.2 7.01 24.9 8.36 25.1 8.41
45 14.0 3.95 16.7 4.74 19.4 5.91 20.8 6.61 22.2 7.13 24.9 8.45 24.8 8.54
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
40
Mini TVR Individual 60Hz
Table 2-7.3: 4TVH0089BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.6 1.62 13.9 1.91 16.1 2.16 17.3 2.33 18.5 2.50 20.5 2.84 22.7 3.27
-13 11.6 1.63 13.9 1.91 16.1 2.18 17.3 2.34 18.5 2.50 20.5 2.85 22.7 3.28
-11 11.6 1.63 13.9 1.92 16.1 2.18 17.3 2.35 18.5 2.51 20.5 2.86 22.7 3.28
-9 12.0 1.64 14.4 1.93 16.7 2.19 17.7 2.35 19.1 2.52 21.0 2.88 23.3 3.30
-7 12.0 1.66 14.4 1.93 16.7 2.19 17.7 2.35 19.1 2.52 21.0 2.88 23.3 3.31
-5 12.3 1.66 14.7 1.95 17.0 2.21 18.2 2.36 19.4 2.52 21.7 2.89 24.1 3.32
-2 12.3 1.67 14.7 1.96 17.0 2.22 18.2 2.41 19.4 2.57 21.7 2.93 24.1 3.37
0 12.3 1.68 14.7 1.98 17.0 2.26 18.2 2.46 19.4 2.62 21.7 2.99 24.1 3.41
2 12.3 1.69 14.7 1.99 17.0 2.30 18.2 2.50 19.4 2.66 21.7 3.06 24.1 3.47
4 12.3 1.71 14.7 2.04 17.0 2.35 18.2 2.55 19.4 2.72 21.7 3.11 24.1 3.55
6 12.3 1.74 14.7 2.08 17.0 2.41 18.2 2.63 19.4 2.78 21.7 3.16 24.1 3.62
8 12.3 1.77 14.7 2.14 17.0 2.46 18.2 2.67 19.4 2.84 21.7 3.25 24.1 3.68
10 12.3 1.81 14.7 2.17 17.0 2.53 18.2 2.72 19.4 2.92 21.7 3.32 24.1 3.73
12 12.3 1.85 14.7 2.20 17.0 2.58 18.2 2.78 19.4 2.97 21.7 3.38 24.1 3.80
14 12.3 1.88 14.7 2.24 17.0 2.62 18.2 2.82 19.4 3.02 21.7 3.44 24.1 3.87
70% 16 12.3 1.92 14.7 2.28 17.0 2.67 18.2 2.88 19.4 3.08 21.7 3.50 24.1 3.94
18 12.3 1.95 14.7 2.33 17.0 2.72 18.2 2.93 19.4 3.13 21.7 3.57 24.1 4.03
20 12.3 1.98 14.7 2.37 17.0 2.78 18.2 2.98 19.4 3.20 21.7 3.65 24.1 4.14
21 12.3 2.00 14.7 2.39 17.0 2.80 18.2 3.01 19.4 3.23 21.7 3.70 24.1 4.28

Part 2 - Outdoor Unit Engineering Data


23 12.3 2.03 14.7 2.43 17.0 2.86 18.2 3.11 19.4 3.39 21.7 3.96 24.1 4.59
25 12.3 2.07 14.7 2.53 17.0 3.04 18.2 3.33 19.4 3.62 21.7 4.24 24.1 4.91
27 12.3 2.19 14.7 2.69 17.0 3.25 18.2 3.54 19.4 3.86 21.7 4.53 24.1 5.24
29 12.3 2.33 14.7 2.86 17.0 3.45 18.2 3.78 19.4 4.11 21.7 4.82 24.1 5.60
31 12.3 2.46 14.7 3.03 17.0 3.68 18.2 4.02 19.4 4.37 21.7 5.14 24.1 5.97
33 12.3 2.61 14.7 3.23 17.0 3.91 18.2 4.27 19.4 4.66 21.7 5.48 24.1 6.37
35 12.3 2.77 14.7 3.42 17.0 4.15 18.2 4.55 19.4 4.96 21.7 5.84 24.1 6.79
37 12.3 2.92 14.7 3.63 17.0 4.41 18.2 4.82 19.4 5.28 21.7 6.22 24.1 7.23
39 12.3 3.09 14.7 3.84 17.0 4.68 18.2 5.13 19.4 5.60 21.7 6.61 24.1 7.70
41 12.3 3.23 14.7 3.98 17.0 4.82 18.2 5.30 19.4 5.77 21.7 6.88 24.1 8.04
43 12.3 3.49 14.7 4.25 17.0 5.02 18.2 5.59 19.4 5.94 21.7 7.13 24.1 8.29
45 12.3 3.57 14.7 4.34 17.0 5.12 18.2 5.68 19.4 6.24 21.7 7.52 24.1 8.61
-15 9.9 1.39 11.9 1.61 13.8 1.88 14.8 2.01 15.9 2.18 17.6 2.44 19.5 2.79
-13 9.9 1.39 11.9 1.61 13.8 1.89 14.8 2.02 15.9 2.18 17.6 2.44 19.5 2.81
-11 9.9 1.39 11.9 1.62 13.8 1.89 14.8 2.02 15.9 2.19 17.6 2.45 19.5 2.81
-9 10.3 1.40 12.3 1.63 14.3 1.90 15.2 2.03 16.4 2.19 18.1 2.46 20.0 2.82
-7 10.3 1.41 12.3 1.63 14.3 1.90 15.2 2.03 16.4 2.20 18.1 2.46 20.0 2.83
-5 10.5 1.42 12.5 1.64 14.6 1.91 15.6 2.04 16.6 2.20 18.7 2.47 20.7 2.84
-2 10.5 1.42 12.5 1.67 14.6 1.95 15.6 2.07 16.6 2.22 18.7 2.51 20.7 2.85
0 10.5 1.45 12.5 1.69 14.6 1.97 15.6 2.09 16.6 2.26 18.7 2.55 20.7 2.89
2 10.5 1.47 12.5 1.73 14.6 2.01 15.6 2.14 16.6 2.29 18.7 2.60 20.7 2.93
4 10.5 1.51 12.5 1.76 14.6 2.05 15.6 2.16 16.6 2.33 18.7 2.64 20.7 2.97
6 10.5 1.53 12.5 1.79 14.6 2.09 15.6 2.21 16.6 2.37 18.7 2.69 20.7 3.04
8 10.5 1.56 12.5 1.82 14.6 2.13 15.6 2.25 16.6 2.42 18.7 2.74 20.7 3.09
10 10.5 1.59 12.5 1.86 14.6 2.16 15.6 2.31 16.6 2.47 18.7 2.80 20.7 3.13
12 10.5 1.62 12.5 1.89 14.6 2.20 15.6 2.36 16.6 2.51 18.7 2.85 20.7 3.18
14 10.5 1.64 12.5 1.93 14.6 2.23 15.6 2.40 16.6 2.56 18.7 2.90 20.7 3.25
60% 16 10.5 1.66 12.5 1.96 14.6 2.27 15.6 2.44 16.6 2.60 18.7 2.95 20.7 3.31
18 10.5 1.69 12.5 1.99 14.6 2.31 15.6 2.48 16.6 2.65 18.7 3.00 20.7 3.37
20 10.5 1.71 12.5 2.03 14.6 2.36 15.6 2.53 16.6 2.70 18.7 3.06 20.7 3.44
21 10.5 1.73 12.5 2.04 14.6 2.38 15.6 2.55 16.6 2.72 18.7 3.09 20.7 3.47
23 10.5 1.75 12.5 2.08 14.6 2.42 15.6 2.60 16.6 2.78 18.7 3.22 20.7 3.70
25 10.5 1.78 12.5 2.11 14.6 2.51 15.6 2.72 16.6 2.95 18.7 3.43 20.7 3.94
27 10.5 1.85 12.5 2.24 14.6 2.67 15.6 2.91 16.6 3.14 18.7 3.66 20.7 4.21
29 10.5 1.96 12.5 2.38 14.6 2.85 15.6 3.09 16.6 3.35 18.7 3.90 20.7 4.50
31 10.5 2.08 12.5 2.52 14.6 3.02 15.6 3.29 16.6 3.56 18.7 4.15 20.7 4.78
33 10.5 2.19 12.5 2.67 14.6 3.21 15.6 3.49 16.6 3.79 18.7 4.41 20.7 5.10
35 10.5 2.32 12.5 2.84 14.6 3.40 15.6 3.71 16.6 4.02 18.7 4.70 20.7 5.43
37 10.5 2.46 12.5 3.00 14.6 3.60 15.6 3.93 16.6 4.27 18.7 5.00 20.7 5.78
39 10.5 2.59 12.5 3.17 14.6 3.82 15.6 4.17 16.6 4.54 18.7 5.30 20.7 6.14
41 10.5 2.67 12.5 3.31 14.6 3.96 15.6 4.33 16.6 4.70 18.7 5.55 20.7 6.42
43 10.5 2.76 12.5 3.45 14.6 4.10 15.6 4.46 16.6 4.87 18.7 5.79 20.7 6.70
45 10.5 2.89 12.5 3.63 14.6 4.26 15.6 4.63 16.6 5.11 18.7 6.05 20.7 7.07
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.
41
Mini TVR Individual 60Hz
Table 2-7.3: 4TVH0089BD000AA cooling capacity (continued)
Indoor temperature(°C DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 8.3 1.20 9.9 1.39 11.5 1.60 12.3 1.69 13.2 1.79 14.6 2.02 16.2 2.18
-13 8.3 1.21 9.9 1.39 11.5 1.61 12.3 1.69 13.2 1.79 14.6 2.03 16.2 2.19
-11 8.3 1.21 9.9 1.40 11.5 1.61 12.3 1.70 13.2 1.79 14.6 2.03 16.2 2.19
-9 8.6 1.22 10.3 1.41 11.9 1.62 12.6 1.70 13.6 1.80 15.0 2.04 16.7 2.20
-7 8.6 1.23 10.3 1.41 11.9 1.62 12.6 1.70 13.6 1.80 15.0 2.04 16.7 2.21
-5 8.8 1.23 10.5 1.42 12.2 1.63 13.0 1.71 13.8 1.81 15.5 2.05 17.3 2.21
-2 8.8 1.24 10.5 1.45 12.2 1.65 13.0 1.73 13.8 1.84 15.5 2.08 17.3 2.24
0 8.8 1.26 10.5 1.47 12.2 1.68 13.0 1.76 13.8 1.86 15.5 2.11 17.3 2.28
2 8.8 1.28 10.5 1.49 12.2 1.71 13.0 1.78 13.8 1.89 15.5 2.12 17.3 2.32
4 8.8 1.29 10.5 1.52 12.2 1.73 13.0 1.81 13.8 1.93 15.5 2.18 17.3 2.38
6 8.8 1.31 10.5 1.54 12.2 1.75 13.0 1.85 13.8 1.96 15.5 2.21 17.3 2.45
8 8.8 1.34 10.5 1.57 12.2 1.78 13.0 1.89 13.8 1.99 15.5 2.25 17.3 2.53
10 8.8 1.37 10.5 1.59 12.2 1.81 13.0 1.92 13.8 2.05 15.5 2.30 17.3 2.57
12 8.8 1.38 10.5 1.61 12.2 1.84 13.0 1.96 13.8 2.09 15.5 2.35 17.3 2.61
14 8.8 1.40 10.5 1.63 12.2 1.86 13.0 2.00 13.8 2.12 15.5 2.39 17.3 2.66
50% 16 8.8 1.42 10.5 1.65 12.2 1.89 13.0 2.03 13.8 2.15 15.5 2.43 17.3 2.70
Mini TVR Individual Series Engineering Data Book

18 8.8 1.44 10.5 1.68 12.2 1.93 13.0 2.06 13.8 2.19 15.5 2.47 17.3 2.75
20 8.8 1.46 10.5 1.70 12.2 1.96 13.0 2.09 13.8 2.23 15.5 2.51 17.3 2.81
21 8.8 1.47 10.5 1.72 12.2 1.98 13.0 2.11 13.8 2.25 15.5 2.54 17.3 2.84
23 8.8 1.50 10.5 1.74 12.2 2.01 13.0 2.15 13.8 2.29 15.5 2.58 17.3 2.90
25 8.8 1.52 10.5 1.77 12.2 2.05 13.0 2.19 13.8 2.37 15.5 2.71 17.3 3.09
27 8.8 1.55 10.5 1.84 12.2 2.16 13.0 2.34 13.8 2.51 15.5 2.89 17.3 3.30
29 8.8 1.63 10.5 1.95 12.2 2.29 13.0 2.48 13.8 2.67 15.5 3.07 17.3 3.51
31 8.8 1.72 10.5 2.06 12.2 2.43 13.0 2.63 13.8 2.84 15.5 3.27 17.3 3.74
33 8.8 1.82 10.5 2.18 12.2 2.58 13.0 2.79 13.8 3.01 15.5 3.47 17.3 3.97
35 8.8 1.93 10.5 2.30 12.2 2.72 13.0 2.95 13.8 3.19 15.5 3.69 17.3 4.22
37 8.8 2.03 10.5 2.44 12.2 2.89 13.0 3.12 13.8 3.38 15.5 3.91 17.3 4.49
39 8.8 2.14 10.5 2.57 12.2 3.05 13.0 3.31 13.8 3.58 15.5 4.15 17.3 4.76
41 8.8 2.23 10.5 2.68 12.2 3.16 13.0 3.46 13.8 3.74 15.5 4.37 17.3 4.98
43 8.8 2.38 10.5 2.87 12.2 3.27 13.0 3.62 13.8 3.84 15.5 4.59 17.3 5.20
45 8.8 2.43 10.5 2.94 12.2 3.49 13.0 3.90 13.8 4.00 15.5 5.03 17.3 5.65
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

42
Mini TVR Individual 60Hz
Table 2-7.4: 4TVH0136BD000AA cooling capacity
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 35.1 4.86 41.9 5.94 48.6 6.36 50.4 6.62 52.9 6.81 54.1 7.41 55.5 7.45
-2 35.1 4.86 41.9 6.05 48.6 6.36 50.4 6.66 52.9 6.81 54.1 7.50 55.5 7.53
0 35.1 4.95 41.9 6.16 48.6 6.60 50.4 7.03 52.9 7.21 54.1 7.59 55.5 7.63
2 35.1 5.04 41.9 6.17 48.6 6.82 50.4 7.42 52.9 7.29 54.1 7.65 55.5 7.74
4 35.1 5.15 41.9 6.29 48.6 7.06 50.4 7.45 52.9 7.38 54.1 7.64 55.5 7.89
6 35.1 5.25 41.9 6.42 48.6 7.32 50.4 7.52 52.3 7.61 53.5 7.64 54.9 7.95
8 35.1 5.37 41.9 6.56 48.6 7.69 50.4 7.88 51.6 7.86 52.9 3.90 54.2 8.02
10 35.1 5.49 41.9 6.70 48.6 7.97 50.4 8.15 51.0 4.04 52.3 4.06 53.6 8.26
12 35.1 5.58 41.9 6.83 48.6 8.13 49.7 4.03 50.4 4.06 51.6 4.07 52.9 8.31
14 35.1 5.69 41.9 6.96 48.4 4.05 49.1 4.06 49.7 4.08 51.0 4.09 52.3 8.50
16 35.1 5.79 41.9 7.11 47.9 4.06 48.4 4.08 49.0 4.10 50.3 4.12 51.6 8.63
18 35.1 5.90 41.9 7.25 47.1 8.50 47.7 8.55 48.4 8.60 49.7 8.68 51.0 8.76
20 35.1 6.03 41.9 7.71 46.4 8.92 47.1 8.97 47.7 9.01 49.0 9.09 50.3 9.19
130% 21 35.1 6.19 41.9 7.99 46.1 9.13 46.9 9.17 47.4 9.22 48.7 9.32 50.0 9.40
23 35.1 6.64 41.9 8.56 45.6 9.54 46.1 9.59 46.7 9.64 48.0 9.74 49.3 9.83
25 35.1 7.09 41.9 9.17 44.9 9.96 45.4 10.01 46.1 10.07 47.4 10.17 48.7 10.26
27 35.1 7.57 41.9 9.82 44.3 10.38 44.9 10.44 45.4 10.49 46.7 10.60 48.0 10.71

Part 2 - Outdoor Unit Engineering Data


29 35.1 8.08 41.9 10.49 43.6 10.79 44.1 10.86 44.9 10.92 46.1 11.04 47.4 11.15
31 35.1 8.63 41.7 11.10 42.9 11.23 43.6 11.29 44.1 11.34 45.4 11.47 46.7 11.60
33 35.1 9.19 41.0 11.52 42.3 11.64 42.9 11.71 43.6 11.77 44.9 11.90 46.0 12.03
35 35.1 9.80 40.3 11.93 41.6 12.08 42.3 12.14 42.9 12.21 44.1 12.35 45.4 12.48
37 35.1 10.43 39.7 12.37 41.0 12.51 41.6 12.58 42.3 12.66 43.4 12.80 44.7 12.94
39 35.1 11.10 39.0 12.49 40.3 12.93 41.0 13.01 41.6 13.09 42.9 13.23 44.1 13.39
41 35.1 11.68 38.6 12.62 39.9 13.05 40.6 13.13 41.1 13.21 42.4 13.26 42.4 13.51
43 35.1 11.98 38.3 12.68 39.6 13.08 40.4 13.19 40.7 13.23 41.7 13.28 41.9 13.54
45 35.1 12.57 38.1 12.80 39.2 13.21 39.9 13.27 40.1 13.29 40.5 13.33 41.1 13.80
48 35.1 13.02 38.0 13.21 38.6 13.33 39.3 13.39 39.6 13.44 39.5 13.56 40.2 13.84
-5 32.4 4.70 38.6 5.69 44.9 6.73 48.0 7.34 50.3 7.65 51.4 7.89 52.6 8.10
-2 32.4 4.74 38.6 5.75 44.9 6.80 48.0 7.38 50.3 7.74 51.4 7.96 52.6 8.13
0 32.4 4.79 38.6 5.79 44.9 6.87 48.0 7.40 50.3 7.81 51.4 8.01 52.6 8.15
2 32.4 4.80 38.6 5.85 44.9 6.92 48.0 7.47 50.3 7.84 51.4 8.07 52.6 8.17
4 32.4 4.85 38.6 5.92 44.9 7.02 48.0 7.54 50.3 7.94 51.4 8.08 52.6 8.19
6 32.4 4.90 38.6 5.97 44.9 7.10 48.0 7.62 50.3 8.03 51.4 8.15 52.6 8.21
8 32.4 4.94 38.6 6.03 44.9 7.20 48.0 7.72 50.3 8.11 51.4 8.18 52.6 8.25
10 32.4 5.00 38.6 6.11 44.9 7.27 48.0 7.86 50.3 8.12 51.4 8.20 52.6 8.29
12 32.4 5.10 38.6 6.22 44.9 7.41 48.0 8.00 49.6 8.15 50.7 8.16 51.9 8.34
14 32.4 5.20 38.6 6.35 44.9 7.55 48.0 8.16 48.9 8.20 50.1 8.28 51.3 8.44
16 32.4 5.29 38.6 6.48 44.9 7.70 47.7 4.10 48.3 8.32 49.4 8.42 50.6 8.57
18 32.4 5.39 38.6 6.61 44.9 7.96 47.0 8.50 47.6 8.53 48.7 8.61 50.0 8.69
20 32.4 5.50 38.6 6.86 44.9 8.56 46.4 8.92 47.0 8.95 48.1 9.03 49.3 9.11
120% 21 32.4 5.55 38.6 7.10 44.9 8.87 46.0 9.13 46.6 9.16 47.9 9.24 49.0 9.33
23 32.4 5.93 38.6 7.62 44.9 9.49 45.4 9.53 46.0 9.57 47.1 9.67 48.3 9.75
25 32.4 6.34 38.6 8.15 44.1 9.91 44.7 9.94 45.3 9.99 46.6 10.09 47.7 10.18
27 32.4 6.77 38.6 8.71 43.6 10.31 44.1 10.38 44.7 10.43 45.9 10.52 47.0 10.62
29 32.4 7.22 38.6 9.30 42.9 10.73 43.4 10.79 44.0 10.84 45.1 10.95 46.4 11.05
31 32.4 7.70 38.6 9.93 42.1 11.16 42.9 11.21 43.4 11.27 44.6 11.39 45.7 11.50
33 32.4 8.20 38.6 10.59 41.6 11.58 42.1 11.64 42.7 11.69 43.9 11.82 45.0 11.93
35 32.4 8.72 38.6 11.29 40.9 11.99 41.4 12.06 42.1 12.12 43.3 12.25 44.4 12.38
37 32.4 9.29 38.6 12.03 40.3 12.43 40.9 12.49 41.4 12.56 42.6 12.69 43.7 12.83
39 32.4 9.88 38.4 12.70 39.6 12.85 40.1 12.93 40.7 12.99 42.0 13.14 43.1 13.26
41 32.4 10.15 38.1 12.79 39.3 12.94 39.8 13.02 40.4 13.08 41.7 13.17 41.9 13.36
43 32.4 10.30 37.9 12.88 39.0 13.02 39.5 13.07 40.1 13.13 41.0 13.21 41.3 13.63
45 32.4 10.42 37.7 13.00 38.6 13.14 39.1 13.19 39.7 13.23 40.1 13.25 40.8 13.93
48 32.4 10.51 37.4 13.15 38.1 13.25 38.5 13.29 39.3 13.34 39.5 13.30 40.3 14.10
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

43
Mini TVR Individual 60Hz
Table 2-7.4: 4TVH0136BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 29.7 4.10 35.4 5.11 41.1 6.09 44.0 6.54 46.9 7.04 50.4 7.31 51.6 7.54
-2 29.7 4.18 35.4 5.17 41.1 6.15 44.0 6.61 46.9 7.09 50.4 7.38 51.6 7.58
0 29.7 4.22 35.4 5.20 41.1 6.19 44.0 6.65 46.9 7.17 50.4 7.46 51.6 7.67
2 29.7 4.32 35.4 5.25 41.1 6.29 44.0 6.72 46.9 7.25 50.4 7.56 51.6 7.76
4 29.7 4.40 35.4 5.31 41.1 6.35 44.0 6.81 46.9 7.36 50.4 7.67 51.6 7.84
6 29.7 4.44 35.4 5.37 41.1 6.41 44.0 6.91 46.9 7.44 50.4 7.75 51.6 7.96
8 29.7 4.49 35.4 5.46 41.1 6.48 44.0 6.98 46.9 7.53 50.4 7.80 51.6 8.04
10 29.7 4.54 35.4 5.53 41.1 6.58 44.0 7.10 46.9 7.65 50.4 7.86 51.6 8.11
12 29.7 4.64 35.4 5.65 41.1 6.70 44.0 7.25 46.9 7.79 49.9 7.97 50.9 8.21
14 29.7 4.72 35.4 5.74 41.1 6.83 44.0 7.38 46.9 7.94 49.1 8.04 50.3 8.27
16 29.7 4.80 35.4 5.85 41.1 6.96 44.0 7.52 46.9 8.10 48.6 8.13 49.6 8.36
18 29.7 4.89 35.4 5.97 41.1 7.10 44.0 7.73 46.9 8.48 47.9 8.55 49.0 8.63
20 29.7 4.99 35.4 6.09 41.1 7.52 44.0 8.31 46.1 8.90 47.3 8.97 48.3 9.05
110% 21 29.7 5.04 35.4 6.27 41.1 7.79 44.0 8.61 45.9 9.11 46.9 9.17 48.0 9.25
Mini TVR Individual Series Engineering Data Book

23 29.7 5.28 35.4 6.72 41.1 8.36 44.0 9.24 45.1 9.51 46.3 9.61 47.3 9.69
25 29.7 5.63 35.4 7.18 41.1 8.93 44.0 9.90 44.6 9.93 45.6 10.02 46.7 10.10
27 29.7 6.00 35.4 7.68 41.1 9.56 43.3 10.31 43.9 10.35 45.0 10.44 46.0 10.54
29 29.7 6.40 35.4 8.20 41.1 10.22 42.7 10.73 43.3 10.78 44.3 10.87 45.4 10.97
31 29.7 6.82 35.4 8.74 41.1 10.91 42.0 11.15 42.6 11.19 43.7 11.29 44.7 11.40
33 29.7 7.25 35.4 9.32 40.9 11.50 41.4 11.56 42.0 11.61 43.0 11.72 44.1 11.84
35 29.7 7.71 35.4 9.93 40.1 11.92 40.7 11.98 41.3 12.05 42.3 12.16 43.4 12.27
37 29.7 8.21 35.4 10.57 39.6 12.35 40.1 12.40 40.6 12.46 41.7 12.59 42.7 12.70
39 29.7 8.72 35.4 11.26 38.9 12.77 39.4 12.83 40.0 12.90 41.0 13.02 42.1 13.15
41 29.7 8.81 35.4 11.35 38.6 12.86 39.1 12.92 39.7 12.98 40.5 13.11 40.9 13.24
43 29.7 8.90 35.4 11.50 38.2 12.95 38.8 13.01 39.4 13.07 40.1 13.16 40.2 13.51
45 29.7 9.19 35.4 11.56 37.9 13.07 38.4 13.17 39.0 13.19 39.7 13.52 39.9 13.82
48 29.7 9.52 35.4 12.54 37.3 13.15 37.8 13.26 38.6 13.33 39.1 13.57 39.4 13.97
-5 27.0 3.74 32.1 4.50 37.4 5.36 40.0 5.74 42.6 6.22 47.9 7.09 50.6 7.40
-2 27.0 3.78 32.1 4.56 37.4 5.41 40.0 5.84 42.6 6.31 47.9 7.18 50.6 7.45
0 27.0 3.82 32.1 4.61 37.4 5.47 40.0 5.91 42.6 6.37 47.9 7.29 50.6 7.53
2 27.0 3.90 32.1 4.67 37.4 5.53 40.0 5.99 42.6 6.44 47.9 7.40 50.6 7.65
4 27.0 3.92 32.1 4.71 37.4 5.62 40.0 6.08 42.6 6.52 47.9 7.47 50.6 7.74
6 27.0 3.98 32.1 4.81 37.4 5.69 40.0 6.19 42.6 6.62 47.9 7.58 50.6 7.85
8 27.0 4.06 32.1 4.88 37.4 5.79 40.0 6.26 42.6 6.72 47.9 7.70 50.6 7.98
10 27.0 4.11 32.1 4.97 37.4 5.89 40.0 6.37 42.6 6.85 47.9 7.83 50.6 8.10
12 27.0 4.17 32.1 5.07 37.4 6.00 40.0 6.48 42.6 6.98 47.9 7.97 49.9 8.16
14 27.0 4.25 32.1 5.16 37.4 6.11 40.0 6.61 42.6 7.10 47.9 8.13 49.3 8.26
16 27.0 4.33 32.1 5.26 37.4 6.24 40.0 6.74 42.6 7.25 47.6 8.23 48.6 8.36
18 27.0 4.41 32.1 5.36 37.4 6.35 40.0 6.86 42.6 7.39 47.0 8.50 48.0 8.56
20 27.0 4.49 32.1 5.47 37.4 6.54 40.0 7.22 42.6 7.92 46.3 8.90 47.3 8.98
100% 21 27.0 4.54 32.1 5.52 37.4 6.78 40.0 7.47 42.6 8.20 46.0 9.11 47.0 9.19
23 27.0 4.65 32.1 5.89 37.4 7.26 40.0 8.00 42.6 8.79 45.4 9.53 46.3 9.61
25 27.0 4.96 32.1 6.29 37.4 7.78 40.0 8.58 42.6 9.41 44.7 9.94 45.7 10.02
27 27.0 5.29 32.1 6.70 37.4 8.31 40.0 9.17 42.6 10.07 44.0 10.36 45.0 10.46
29 27.0 5.63 32.1 7.15 37.4 8.87 40.0 9.80 42.4 10.70 43.4 10.79 44.4 10.87
31 27.0 6.00 32.1 7.63 37.4 9.46 40.0 10.46 41.9 11.11 42.7 11.21 43.7 11.31
33 27.0 6.37 32.1 8.13 37.4 10.09 40.0 11.16 41.1 11.53 42.1 11.63 43.1 11.74
35 27.0 6.77 32.1 8.64 37.4 10.76 40.0 11.90 40.4 11.95 41.4 12.06 42.4 12.16
37 27.0 7.20 32.1 9.21 37.4 11.47 39.3 12.32 39.9 12.38 40.9 12.49 41.7 12.59
39 27.0 7.65 32.1 9.78 37.4 12.20 38.7 12.73 39.1 12.80 40.1 12.91 41.1 13.04
41 27.0 8.01 32.1 10.14 37.4 12.65 38.1 12.82 38.8 13.00 39.4 13.21 40.5 13.31
43 27.0 8.36 32.1 10.50 37.4 12.89 37.5 12.97 38.6 13.12 39.7 13.30 39.8 13.46
45 27.0 8.84 32.1 10.97 37.4 13.11 36.7 13.15 38.4 13.36 39.3 13.51 39.0 13.63
48 27.0 9.23 32.1 11.36 37.4 13.13 35.2 13.30 38.3 13.60 36.9 13.65 38.2 13.76
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

44
Mini TVR Individual 60Hz
Table 2-7.4: 4TVH0136BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 24.3 3.30 29.0 3.97 33.7 4.68 36.0 5.10 38.3 5.43 43.0 6.24 47.7 7.15
-2 24.3 3.33 29.0 4.01 33.7 4.74 36.0 5.18 38.3 5.50 43.0 6.30 47.7 7.22
0 24.3 3.39 29.0 4.06 33.7 4.81 36.0 5.24 38.3 5.57 43.0 6.37 47.7 7.27
2 24.3 3.44 29.0 4.11 33.7 4.86 36.0 5.32 38.3 5.65 43.0 6.51 47.7 7.38
4 24.3 3.49 29.0 4.17 33.7 4.94 36.0 5.39 38.3 5.72 43.0 6.61 47.7 7.49
6 24.3 3.54 29.0 4.25 33.7 5.03 36.0 5.49 38.3 5.82 43.0 6.71 47.7 7.62
8 24.3 3.60 29.0 4.33 33.7 5.14 36.0 5.56 38.3 5.93 43.0 6.84 47.7 7.69
10 24.3 3.67 29.0 4.43 33.7 5.23 36.0 5.64 38.3 6.06 43.0 6.92 47.7 7.81
12 24.3 3.74 29.0 4.51 33.7 5.32 36.0 5.74 38.3 6.17 43.0 7.06 47.7 7.95
14 24.3 3.80 29.0 4.59 33.7 5.42 36.0 5.85 38.3 6.29 43.0 7.18 47.7 8.10
16 24.3 3.86 29.0 4.67 33.7 5.53 36.0 5.97 38.3 6.41 43.0 7.33 47.6 8.24
18 24.3 3.93 29.0 4.76 33.7 5.63 36.0 6.08 38.3 6.54 43.0 7.47 47.0 8.50
20 24.3 4.01 29.0 4.87 33.7 5.74 36.0 6.21 38.3 6.78 43.0 8.03 46.3 8.90
90% 21 24.3 4.04 29.0 4.91 33.7 5.84 36.0 6.41 38.3 7.02 43.0 8.32 46.0 9.11
23 24.3 4.12 29.0 5.10 33.7 6.25 36.0 6.88 38.3 7.54 43.0 8.93 45.3 9.53
25 24.3 4.35 29.0 5.45 33.7 6.69 36.0 7.36 38.3 8.05 43.0 9.56 44.7 9.94
27 24.3 4.62 29.0 5.81 33.7 7.14 36.0 7.86 38.3 8.61 43.0 10.23 44.0 10.36

Part 2 - Outdoor Unit Engineering Data


29 24.3 4.92 29.0 6.19 33.7 7.62 36.0 8.39 38.3 9.21 42.6 10.70 43.4 10.78
31 24.3 5.23 29.0 6.59 33.7 8.11 36.0 8.95 38.3 9.81 41.9 11.11 42.7 11.21
33 24.3 5.55 29.0 7.01 33.7 8.66 36.0 9.54 38.3 10.47 41.3 11.55 42.1 11.63
35 24.3 5.90 29.0 7.46 33.7 9.22 36.0 10.17 38.3 11.16 40.6 11.96 41.4 12.06
37 24.3 6.25 29.0 7.92 33.7 9.81 36.0 10.83 38.3 11.90 39.9 12.38 40.9 12.48
39 24.3 6.64 29.0 8.44 33.7 10.44 36.0 11.53 38.3 12.67 39.3 12.81 40.1 12.91
41 24.3 6.87 29.0 8.82 33.7 10.82 36.0 11.84 38.3 12.75 39.0 13.14 39.9 13.21
43 24.3 7.20 29.0 9.20 33.7 11.20 36.0 12.14 38.3 13.02 38.8 13.31 39.5 13.42
45 24.3 7.66 29.0 9.66 33.7 11.66 36.0 12.55 38.3 13.38 38.6 13.45 38.9 13.60
48 24.3 8.08 29.0 10.10 33.7 12.10 36.0 12.71 38.3 13.49 38.3 13.64 37.9 13.78
-5 21.6 2.91 25.7 3.44 29.9 4.08 32.0 4.33 34.1 4.67 38.3 5.40 42.4 6.16
-2 21.6 2.95 25.7 3.49 29.9 4.11 32.0 4.40 34.1 4.71 38.3 5.45 42.4 6.22
0 21.6 3.01 25.7 3.53 29.9 4.16 32.0 4.45 34.1 4.80 38.3 5.52 42.4 6.30
2 21.6 3.07 25.7 3.58 29.9 4.22 32.0 4.54 34.1 4.88 38.3 5.64 42.4 6.42
4 21.6 3.12 25.7 3.64 29.9 4.30 32.0 4.64 34.1 4.97 38.3 5.74 42.4 6.51
6 21.6 3.17 25.7 3.73 29.9 4.37 32.0 4.74 34.1 5.06 38.3 5.82 42.4 6.62
8 21.6 3.23 25.7 3.81 29.9 4.47 32.0 4.82 34.1 5.17 38.3 5.91 42.4 6.75
10 21.6 3.26 25.7 3.90 29.9 4.59 32.0 4.94 34.1 5.29 38.3 6.05 42.4 6.82
12 21.6 3.30 25.7 3.96 29.9 4.67 32.0 5.04 34.1 5.41 38.3 6.16 42.4 6.94
14 21.6 3.37 25.7 4.04 29.9 4.75 32.0 5.12 34.1 5.50 38.3 6.27 42.4 7.07
16 21.6 3.42 25.7 4.11 29.9 4.84 32.0 5.21 34.1 5.60 38.3 6.40 42.4 7.20
18 21.6 3.48 25.7 4.19 29.9 4.94 32.0 5.32 34.1 5.71 38.3 6.53 42.4 7.35
20 21.6 3.54 25.7 4.27 29.9 5.04 32.0 5.42 34.1 5.82 38.3 6.77 42.4 7.86
80% 21 21.6 3.58 25.7 4.30 29.9 5.08 32.0 5.48 34.1 5.95 38.3 7.01 42.4 8.15
23 21.6 3.64 25.7 4.39 29.9 5.32 32.0 5.84 34.1 6.37 38.3 7.51 42.4 8.74
25 21.6 3.75 25.7 4.67 29.9 5.69 32.0 6.24 34.1 6.80 38.3 8.04 42.4 9.35
27 21.6 3.99 25.7 4.97 29.9 6.06 32.0 6.66 34.1 7.27 38.3 8.58 42.4 10.01
29 21.6 4.25 25.7 5.29 29.9 6.46 32.0 7.09 34.1 7.76 38.3 9.16 42.4 10.70
31 21.6 4.51 25.7 5.63 29.9 6.88 32.0 7.55 34.1 8.28 38.3 9.78 41.7 11.11
33 21.6 4.80 25.7 5.98 29.9 7.33 32.0 8.05 34.1 8.81 38.3 10.42 41.1 11.53
35 21.6 5.08 25.7 6.37 29.9 7.79 32.0 8.56 34.1 9.38 38.3 11.11 40.4 11.95
37 21.6 5.39 25.7 6.75 29.9 8.29 32.0 9.13 34.1 9.99 38.3 11.85 39.9 12.37
39 21.6 5.71 25.7 7.20 29.9 8.82 32.0 9.70 34.1 10.63 38.3 12.62 39.1 12.80
41 21.6 5.84 25.7 7.27 29.9 8.95 32.0 9.96 34.1 10.83 38.3 12.94 38.9 13.02
43 21.6 6.01 25.7 7.33 29.9 9.08 32.0 10.13 34.1 10.98 38.3 13.09 38.7 13.16
45 21.6 6.18 25.7 7.42 29.9 9.25 32.0 10.35 34.1 11.17 38.3 13.24 38.2 13.38
48 21.6 6.38 25.7 7.47 29.9 9.40 32.0 10.49 34.1 11.26 38.3 13.37 37.9 13.56
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

45
Mini TVR Individual 60Hz
Table 2-7.4: 4TVH0136BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 18.9 2.60 22.6 3.05 26.1 3.45 28.0 3.70 29.9 3.95 33.4 4.52 37.1 5.20
-2 18.9 2.62 22.6 3.06 26.1 3.48 28.0 3.77 29.9 4.02 33.4 4.59 37.1 5.27
0 18.9 2.63 22.6 3.10 26.1 3.55 28.0 3.85 29.9 4.09 33.4 4.69 37.1 5.34
2 18.9 2.65 22.6 3.12 26.1 3.60 28.0 3.92 29.9 4.17 33.4 4.79 37.1 5.43
4 18.9 2.68 22.6 3.20 26.1 3.68 28.0 3.99 29.9 4.26 33.4 4.86 37.1 5.55
6 18.9 2.73 22.6 3.25 26.1 3.77 28.0 4.12 29.9 4.36 33.4 4.95 37.1 5.66
8 18.9 2.78 22.6 3.35 26.1 3.86 28.0 4.18 29.9 4.45 33.4 5.09 37.1 5.77
10 18.9 2.83 22.6 3.40 26.1 3.96 28.0 4.27 29.9 4.57 33.4 5.20 37.1 5.84
12 18.9 2.90 22.6 3.45 26.1 4.04 28.0 4.35 29.9 4.65 33.4 5.29 37.1 5.95
14 18.9 2.95 22.6 3.51 26.1 4.11 28.0 4.41 29.9 4.73 33.4 5.39 37.1 6.06
16 18.9 3.00 22.6 3.58 26.1 4.19 28.0 4.51 29.9 4.83 33.4 5.49 37.1 6.17
18 18.9 3.05 22.6 3.64 26.1 4.27 28.0 4.59 29.9 4.91 33.4 5.60 37.1 6.30
20 18.9 3.10 22.6 3.71 26.1 4.35 28.0 4.67 29.9 5.00 33.4 5.71 37.1 6.48
70% 21 18.9 3.13 22.6 3.74 26.1 4.38 28.0 4.72 29.9 5.05 33.4 5.79 37.1 6.70
Mini TVR Individual Series Engineering Data Book

23 18.9 3.18 22.6 3.80 26.1 4.47 28.0 4.88 29.9 5.31 33.4 6.21 37.1 7.19
25 18.9 3.24 22.6 3.96 26.1 4.76 28.0 5.21 29.9 5.66 33.4 6.64 37.1 7.68
27 18.9 3.43 22.6 4.22 26.1 5.08 28.0 5.55 29.9 6.05 33.4 7.09 37.1 8.21
29 18.9 3.64 22.6 4.47 26.1 5.40 28.0 5.92 29.9 6.43 33.4 7.55 37.1 8.77
31 18.9 3.85 22.6 4.75 26.1 5.76 28.0 6.29 29.9 6.85 33.4 8.05 37.1 9.35
33 18.9 4.09 22.6 5.05 26.1 6.13 28.0 6.69 29.9 7.30 33.4 8.58 37.1 9.98
35 18.9 4.33 22.6 5.36 26.1 6.50 28.0 7.12 29.9 7.76 33.4 9.14 37.1 10.63
37 18.9 4.57 22.6 5.68 26.1 6.91 28.0 7.55 29.9 8.26 33.4 9.74 37.1 11.32
39 18.9 4.84 22.6 6.01 26.1 7.33 28.0 8.04 29.9 8.77 33.4 10.34 37.1 12.06
41 18.9 5.06 22.6 6.23 26.1 7.54 28.0 8.30 29.9 9.04 33.4 10.77 37.1 12.59
43 18.9 5.47 22.6 6.66 26.1 7.85 28.0 8.75 29.9 9.31 33.4 11.16 37.1 12.99
45 18.9 5.59 22.6 6.80 26.1 8.02 28.0 8.89 29.9 9.77 33.4 11.77 37.1 13.48
48 18.9 5.73 22.6 6.86 26.1 8.10 28.0 9.03 29.9 10.04 33.4 12.30 37.1 13.80
-5 16.1 2.22 19.3 2.57 22.4 3.00 24.0 3.19 25.6 3.45 28.7 3.87 31.9 4.44
-2 16.1 2.23 19.3 2.61 22.4 3.05 24.0 3.24 25.6 3.48 28.7 3.93 31.9 4.47
0 16.1 2.26 19.3 2.64 22.4 3.09 24.0 3.28 25.6 3.54 28.7 3.99 31.9 4.53
2 16.1 2.30 19.3 2.71 22.4 3.15 24.0 3.34 25.6 3.59 28.7 4.07 31.9 4.59
4 16.1 2.37 19.3 2.76 22.4 3.21 24.0 3.38 25.6 3.64 28.7 4.13 31.9 4.65
6 16.1 2.39 19.3 2.81 22.4 3.27 24.0 3.46 25.6 3.72 28.7 4.22 31.9 4.76
8 16.1 2.44 19.3 2.86 22.4 3.33 24.0 3.52 25.6 3.79 28.7 4.30 31.9 4.84
10 16.1 2.49 19.3 2.92 22.4 3.38 24.0 3.62 25.6 3.86 28.7 4.38 31.9 4.91
12 16.1 2.53 19.3 2.97 22.4 3.45 24.0 3.69 25.6 3.93 28.7 4.46 31.9 4.99
14 16.1 2.57 19.3 3.01 22.4 3.50 24.0 3.75 25.6 4.01 28.7 4.54 31.9 5.08
16 16.1 2.60 19.3 3.06 22.4 3.56 24.0 3.82 25.6 4.07 28.7 4.62 31.9 5.18
18 16.1 2.65 19.3 3.11 22.4 3.62 24.0 3.88 25.6 4.15 28.7 4.70 31.9 5.28
20 16.1 2.68 19.3 3.18 22.4 3.69 24.0 3.96 25.6 4.23 28.7 4.79 31.9 5.39
60% 21 16.1 2.71 19.3 3.19 22.4 3.72 24.0 3.99 25.6 4.27 28.7 4.84 31.9 5.44
23 16.1 2.74 19.3 3.26 22.4 3.78 24.0 4.07 25.6 4.35 28.7 5.04 31.9 5.79
25 16.1 2.79 19.3 3.30 22.4 3.93 24.0 4.27 25.6 4.62 28.7 5.37 31.9 6.17
27 16.1 2.90 19.3 3.51 22.4 4.19 24.0 4.55 25.6 4.92 28.7 5.72 31.9 6.59
29 16.1 3.06 19.3 3.72 22.4 4.46 24.0 4.84 25.6 5.24 28.7 6.11 31.9 7.04
31 16.1 3.26 19.3 3.94 22.4 4.73 24.0 5.15 25.6 5.58 28.7 6.49 31.9 7.49
33 16.1 3.43 19.3 4.19 22.4 5.02 24.0 5.47 25.6 5.93 28.7 6.91 31.9 7.99
35 16.1 3.64 19.3 4.44 22.4 5.32 24.0 5.80 25.6 6.30 28.7 7.36 31.9 8.50
37 16.1 3.85 19.3 4.70 22.4 5.64 24.0 6.16 25.6 6.69 28.7 7.83 31.9 9.04
39 16.1 4.06 19.3 4.97 22.4 5.98 24.0 6.53 25.6 7.10 28.7 8.31 31.9 9.62
41 16.1 4.19 19.3 5.19 22.4 6.20 24.0 6.79 25.6 7.37 28.7 8.70 31.9 10.06
43 16.1 4.32 19.3 5.40 22.4 6.42 24.0 6.99 25.6 7.62 28.7 9.07 31.9 10.49
45 16.1 4.52 19.3 5.68 22.4 6.68 24.0 7.25 25.6 8.00 28.7 9.47 31.9 11.07
48 16.1 4.69 19.3 5.93 22.4 6.90 24.0 7.44 25.6 8.31 28.7 9.82 31.9 11.60
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

46
Mini TVR Individual 60Hz
Table 2-7.4: 4TVH0136BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 13.5 1.93 16.1 2.23 18.7 2.56 20.0 2.68 21.3 2.83 23.9 3.21 26.6 3.46
-2 13.5 1.94 16.1 2.27 18.7 2.59 20.0 2.72 21.3 2.88 23.9 3.26 26.6 3.51
0 13.5 1.97 16.1 2.31 18.7 2.63 20.0 2.75 21.3 2.91 23.9 3.31 26.6 3.57
2 13.5 2.00 16.1 2.34 18.7 2.68 20.0 2.79 21.3 2.96 23.9 3.33 26.6 3.64
4 13.5 2.02 16.1 2.38 18.7 2.71 20.0 2.83 21.3 3.02 23.9 3.41 26.6 3.73
6 13.5 2.06 16.1 2.42 18.7 2.75 20.0 2.89 21.3 3.08 23.9 3.46 26.6 3.84
8 13.5 2.11 16.1 2.46 18.7 2.79 20.0 2.96 21.3 3.12 23.9 3.52 26.6 3.97
10 13.5 2.15 16.1 2.49 18.7 2.84 20.0 3.00 21.3 3.21 23.9 3.61 26.6 4.02
12 13.5 2.17 16.1 2.52 18.7 2.89 20.0 3.06 21.3 3.27 23.9 3.67 26.6 4.09
14 13.5 2.20 16.1 2.55 18.7 2.92 20.0 3.13 21.3 3.32 23.9 3.74 26.6 4.17
16 13.5 2.23 16.1 2.58 18.7 2.97 20.0 3.18 21.3 3.37 23.9 3.80 26.6 4.23
18 13.5 2.26 16.1 2.63 18.7 3.01 20.0 3.22 21.3 3.43 23.9 3.86 26.6 4.31
20 13.5 2.29 16.1 2.66 18.7 3.06 20.0 3.27 21.3 3.50 23.9 3.93 26.6 4.39
50% 21 13.5 2.31 16.1 2.69 18.7 3.09 20.0 3.30 21.3 3.53 23.9 3.98 26.6 4.44
23 13.5 2.34 16.1 2.73 18.7 3.14 20.0 3.37 21.3 3.59 23.9 4.04 26.6 4.54
25 13.5 2.37 16.1 2.77 18.7 3.21 20.0 3.43 21.3 3.70 23.9 4.25 26.6 4.84
27 13.5 2.42 16.1 2.89 18.7 3.38 20.0 3.66 21.3 3.93 23.9 4.52 26.6 5.16

Part 2 - Outdoor Unit Engineering Data


29 13.5 2.55 16.1 3.05 18.7 3.59 20.0 3.88 21.3 4.19 23.9 4.81 26.6 5.50
31 13.5 2.69 16.1 3.22 18.7 3.80 20.0 4.12 21.3 4.44 23.9 5.12 26.6 5.85
33 13.5 2.85 16.1 3.42 18.7 4.04 20.0 4.36 21.3 4.71 23.9 5.44 26.6 6.22
35 13.5 3.01 16.1 3.61 18.7 4.27 20.0 4.62 21.3 4.99 23.9 5.77 26.6 6.61
37 13.5 3.18 16.1 3.82 18.7 4.52 20.0 4.89 21.3 5.29 23.9 6.13 26.6 7.02
39 13.5 3.35 16.1 4.02 18.7 4.78 20.0 5.18 21.3 5.61 23.9 6.49 26.6 7.46
41 13.5 3.49 16.1 4.20 18.7 4.95 20.0 5.42 21.3 5.86 23.9 6.84 26.6 7.80
43 13.5 3.72 16.1 4.49 18.7 5.13 20.0 5.66 21.3 6.01 23.9 7.19 26.6 8.15
45 13.5 3.81 16.1 4.60 18.7 5.47 20.0 6.10 21.3 6.26 23.9 7.88 26.6 8.84
48 13.5 3.90 16.1 4.73 18.7 5.79 20.0 6.49 21.3 6.54 23.9 8.51 26.6 9.52
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

47
Mini TVR Individual 60Hz
Table 2-7.5: 4TVH0153BD000AA cooling capacity
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 39.5 5.56 47.1 6.79 54.6 7.27 56.7 7.57 59.5 7.78 60.9 8.46 62.4 8.52
-2 39.5 5.56 47.1 6.92 54.6 7.27 56.7 7.61 59.5 7.78 60.9 8.57 62.4 8.60
0 39.5 5.65 47.1 7.04 54.6 7.54 56.7 8.03 59.5 8.24 60.9 8.68 62.4 8.72
2 39.5 5.76 47.1 7.05 54.6 7.80 56.7 8.48 59.5 8.33 60.9 8.74 62.4 8.85
4 39.5 5.88 47.1 7.19 54.6 8.07 56.7 8.52 59.5 8.44 60.9 8.73 62.4 9.02
6 39.5 6.00 47.1 7.33 54.6 8.37 56.7 8.59 58.8 8.70 60.2 8.73 61.8 9.08
8 39.5 6.14 47.1 7.50 54.6 8.78 56.7 9.01 58.1 8.99 59.5 3.90 61.0 9.17
10 39.5 6.27 47.1 7.66 54.6 9.11 56.7 9.31 57.4 4.04 58.8 4.06 60.3 9.44
12 39.5 6.38 47.1 7.81 54.6 9.29 55.9 4.03 56.7 4.06 58.0 4.07 59.5 9.50
14 39.5 6.51 47.1 7.96 54.5 4.05 55.3 4.06 55.9 4.08 57.4 4.09 58.8 9.71
16 39.5 6.62 47.1 8.12 53.8 4.06 54.5 4.08 55.1 4.10 56.6 4.12 58.0 9.86
18 39.5 6.75 47.1 8.29 53.0 9.71 53.7 9.77 54.5 9.83 55.9 9.92 57.4 10.01
20 39.5 6.89 47.1 8.82 52.2 10.19 53.0 10.25 53.7 10.30 55.1 10.39 56.6 10.50
130% 21 39.5 7.08 47.1 9.13 51.9 10.43 52.7 10.48 53.4 10.54 54.8 10.65 56.2 10.74
Mini TVR Individual Series Engineering Data Book

23 39.5 7.59 47.1 9.79 51.3 10.91 51.9 10.96 52.6 11.02 54.0 11.13 55.4 11.24
25 39.5 8.10 47.1 10.48 50.5 11.38 51.1 11.44 51.9 11.51 53.4 11.62 54.8 11.73
27 39.5 8.65 47.1 11.22 49.8 11.86 50.5 11.93 51.1 11.99 52.6 12.12 54.0 12.24
29 39.5 9.24 47.1 11.99 49.0 12.34 49.7 12.41 50.5 12.48 51.9 12.61 53.4 12.74
31 39.5 9.86 46.9 12.68 48.2 12.83 49.0 12.90 49.7 12.96 51.1 13.11 52.6 13.25
33 39.5 10.50 46.1 13.16 47.6 13.31 48.2 13.38 49.0 13.45 50.5 13.60 51.7 13.75
35 39.5 11.20 45.3 13.64 46.8 13.80 47.6 13.88 48.2 13.95 49.7 14.11 51.1 14.26
37 39.5 11.92 44.7 14.13 46.1 14.30 46.8 14.37 47.6 14.46 48.9 14.63 50.3 14.79
39 39.5 12.68 43.9 14.28 45.3 14.77 46.1 14.87 46.8 14.96 48.2 15.12 49.7 15.31
41 39.5 13.35 43.4 14.42 44.8 14.91 45.6 15.00 46.3 15.10 47.7 15.15 47.8 15.44
43 39.5 13.69 43.1 14.49 44.6 14.95 45.4 15.07 45.8 15.12 46.9 15.18 47.2 15.48
45 39.5 14.37 42.8 14.63 44.1 15.09 44.9 15.17 45.1 15.19 45.6 15.24 46.3 15.77
48 39.5 14.88 42.7 15.10 43.4 15.23 44.2 15.31 44.6 15.36 44.4 15.50 45.2 15.82
-5 36.5 5.37 43.4 6.50 50.5 7.69 54.0 8.39 56.6 8.74 57.9 9.02 59.1 9.26
-2 36.5 5.42 43.4 6.57 50.5 7.77 54.0 8.44 56.6 8.85 57.9 9.10 59.1 9.29
0 36.5 5.47 43.4 6.62 50.5 7.86 54.0 8.46 56.6 8.92 57.9 9.15 59.1 9.31
2 36.5 5.49 43.4 6.69 50.5 7.91 54.0 8.54 56.6 8.96 57.9 9.22 59.1 9.33
4 36.5 5.54 43.4 6.77 50.5 8.02 54.0 8.61 56.6 9.08 57.9 9.24 59.1 9.36
6 36.5 5.60 43.4 6.82 50.5 8.12 54.0 8.71 56.6 9.18 57.9 9.31 59.1 9.39
8 36.5 5.65 43.4 6.89 50.5 8.23 54.0 8.82 56.6 9.27 57.9 9.35 59.1 9.43
10 36.5 5.72 43.4 6.98 50.5 8.30 54.0 8.98 56.6 9.28 57.9 9.37 59.1 9.47
12 36.5 5.83 43.4 7.11 50.5 8.47 54.0 9.15 55.8 9.31 57.1 9.32 58.3 9.53
14 36.5 5.94 43.4 7.26 50.5 8.63 54.0 9.33 55.0 9.37 56.4 9.46 57.7 9.65
16 36.5 6.05 43.4 7.40 50.5 8.80 53.7 4.10 54.3 9.51 55.6 9.62 56.9 9.79
18 36.5 6.16 43.4 7.55 50.5 9.09 52.9 9.71 53.5 9.75 54.8 9.84 56.2 9.93
20 36.5 6.29 43.4 7.84 50.5 9.79 52.2 10.19 52.9 10.23 54.2 10.32 55.4 10.41
120% 21 36.5 6.34 43.4 8.12 50.5 10.14 51.7 10.43 52.4 10.47 53.8 10.56 55.1 10.67
23 36.5 6.78 43.4 8.71 50.5 10.85 51.1 10.89 51.7 10.94 53.0 11.05 54.3 11.14
25 36.5 7.24 43.4 9.31 49.7 11.33 50.3 11.36 50.9 11.42 52.4 11.53 53.7 11.64
27 36.5 7.74 43.4 9.95 49.0 11.79 49.7 11.86 50.3 11.91 51.6 12.02 52.9 12.13
29 36.5 8.25 43.4 10.63 48.2 12.26 48.9 12.33 49.5 12.39 50.8 12.52 52.2 12.63
31 36.5 8.80 43.4 11.35 47.4 12.76 48.2 12.81 48.9 12.88 50.1 13.01 51.4 13.14
33 36.5 9.37 43.4 12.10 46.8 13.23 47.4 13.31 48.1 13.36 49.3 13.51 50.6 13.64
35 36.5 9.97 43.4 12.90 46.0 13.71 46.6 13.78 47.4 13.86 48.7 14.00 50.0 14.15
37 36.5 10.61 43.4 13.75 45.3 14.21 46.0 14.28 46.6 14.35 47.9 14.50 49.2 14.66
39 36.5 11.29 43.2 14.52 44.5 14.68 45.2 14.77 45.8 14.85 47.2 15.01 48.5 15.16
41 36.5 11.60 42.9 14.62 44.2 14.79 44.8 14.88 45.5 14.95 46.9 15.05 47.1 15.27
43 36.5 11.77 42.7 14.72 43.8 14.88 44.5 14.93 45.1 15.00 46.1 15.09 46.4 15.58
45 36.5 11.91 42.4 14.86 43.4 15.01 44.0 15.07 44.7 15.12 45.2 15.14 45.9 15.92
48 36.5 12.01 42.1 15.02 42.8 15.15 43.3 15.19 44.2 15.24 44.5 15.20 45.3 16.12
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

48
Mini TVR Individual 60Hz
Table 2-7.5: 4TVH0153BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 33.4 4.69 39.9 5.84 46.3 6.97 49.5 7.48 52.7 8.04 56.7 8.36 58.0 8.61
-2 33.4 4.78 39.9 5.91 46.3 7.02 49.5 7.55 52.7 8.11 56.7 8.44 58.0 8.66
0 33.4 4.83 39.9 5.95 46.3 7.08 49.5 7.60 52.7 8.20 56.7 8.52 58.0 8.76
2 33.4 4.93 39.9 6.00 46.3 7.19 49.5 7.68 52.7 8.29 56.7 8.64 58.0 8.87
4 33.4 5.03 39.9 6.07 46.3 7.26 49.5 7.78 52.7 8.41 56.7 8.76 58.0 8.95
6 33.4 5.08 39.9 6.14 46.3 7.33 49.5 7.90 52.7 8.51 56.7 8.85 58.0 9.09
8 33.4 5.13 39.9 6.24 46.3 7.41 49.5 7.98 52.7 8.60 56.7 8.92 58.0 9.19
10 33.4 5.19 39.9 6.32 46.3 7.52 49.5 8.12 52.7 8.74 56.7 8.98 58.0 9.27
12 33.4 5.30 39.9 6.45 46.3 7.66 49.5 8.29 52.7 8.91 56.1 9.11 57.2 9.39
14 33.4 5.39 39.9 6.56 46.3 7.81 49.5 8.43 52.7 9.07 55.3 9.18 56.6 9.45
16 33.4 5.48 39.9 6.69 46.3 7.96 49.5 8.60 52.7 9.26 54.6 9.29 55.8 9.56
18 33.4 5.59 39.9 6.82 46.3 8.12 49.5 8.83 52.7 9.70 53.8 9.77 55.1 9.86
20 33.4 5.70 39.9 6.97 46.3 8.60 49.5 9.49 51.9 10.17 53.2 10.25 54.3 10.34
110% 21 33.4 5.75 39.9 7.17 46.3 8.91 49.5 9.84 51.6 10.41 52.7 10.48 54.0 10.58
23 33.4 6.03 39.9 7.68 46.3 9.55 49.5 10.56 50.8 10.87 52.1 10.98 53.2 11.07
25 33.4 6.43 39.9 8.21 46.3 10.21 49.5 11.31 50.1 11.35 51.3 11.46 52.6 11.55
27 33.4 6.86 39.9 8.78 46.3 10.93 48.7 11.79 49.3 11.82 50.6 11.93 51.8 12.04

Part 2 - Outdoor Unit Engineering Data


29 33.4 7.31 39.9 9.37 46.3 11.68 48.1 12.26 48.7 12.32 49.8 12.43 51.1 12.54
31 33.4 7.79 39.9 9.99 46.3 12.46 47.3 12.74 47.9 12.79 49.2 12.90 50.3 13.03
33 33.4 8.29 39.9 10.65 46.0 13.14 46.6 13.22 47.3 13.27 48.4 13.40 49.7 13.53
35 33.4 8.82 39.9 11.35 45.2 13.62 45.8 13.69 46.4 13.77 47.6 13.89 48.9 14.02
37 33.4 9.38 39.9 12.08 44.5 14.11 45.2 14.17 45.6 14.24 46.9 14.39 48.1 14.52
39 33.4 9.97 39.9 12.87 43.7 14.59 44.4 14.66 45.0 14.74 46.1 14.88 47.4 15.03
41 33.4 10.07 39.9 12.97 43.4 14.69 44.0 14.77 44.7 14.84 45.5 14.99 46.0 15.13
43 33.4 10.18 39.9 13.14 43.0 14.80 43.7 14.87 44.3 14.94 45.1 15.04 45.3 15.44
45 33.4 10.51 39.9 13.21 42.6 14.93 43.2 15.05 43.9 15.08 44.7 15.45 44.9 15.80
48 33.4 10.88 39.9 14.33 42.0 15.03 42.5 15.15 43.4 15.24 43.9 15.51 44.3 15.97
-5 30.4 4.27 36.2 5.14 42.1 6.12 45.0 6.56 47.9 7.11 53.8 8.11 56.9 8.46
-2 30.4 4.32 36.2 5.21 42.1 6.19 45.0 6.68 47.9 7.21 53.8 8.20 56.9 8.51
0 30.4 4.37 36.2 5.26 42.1 6.26 45.0 6.76 47.9 7.28 53.8 8.34 56.9 8.61
2 30.4 4.45 36.2 5.34 42.1 6.32 45.0 6.85 47.9 7.36 53.8 8.46 56.9 8.74
4 30.4 4.49 36.2 5.39 42.1 6.42 45.0 6.95 47.9 7.45 53.8 8.54 56.9 8.84
6 30.4 4.55 36.2 5.49 42.1 6.50 45.0 7.07 47.9 7.56 53.8 8.66 56.9 8.98
8 30.4 4.64 36.2 5.58 42.1 6.62 45.0 7.15 47.9 7.68 53.8 8.80 56.9 9.13
10 30.4 4.69 36.2 5.68 42.1 6.73 45.0 7.28 47.9 7.83 53.8 8.94 56.9 9.26
12 30.4 4.77 36.2 5.79 42.1 6.85 45.0 7.41 47.9 7.97 53.8 9.11 56.1 9.33
14 30.4 4.86 36.2 5.90 42.1 6.98 45.0 7.55 47.9 8.12 53.8 9.29 55.4 9.44
16 30.4 4.95 36.2 6.01 42.1 7.13 45.0 7.70 47.9 8.29 53.5 9.40 54.6 9.55
18 30.4 5.04 36.2 6.12 42.1 7.26 45.0 7.84 47.9 8.45 52.9 9.71 54.0 9.79
20 30.4 5.13 36.2 6.25 42.1 7.48 45.0 8.25 47.9 9.05 52.1 10.17 53.2 10.26
100% 21 30.4 5.19 36.2 6.30 42.1 7.75 45.0 8.54 47.9 9.37 51.8 10.41 52.9 10.50
23 30.4 5.31 36.2 6.73 42.1 8.30 45.0 9.15 47.9 10.04 51.1 10.89 52.1 10.98
25 30.4 5.66 36.2 7.18 42.1 8.89 45.0 9.81 47.9 10.76 50.3 11.36 51.4 11.46
27 30.4 6.05 36.2 7.66 42.1 9.49 45.0 10.48 47.9 11.51 49.5 11.84 50.6 11.95
29 30.4 6.43 36.2 8.17 42.1 10.14 45.0 11.20 47.7 12.23 48.9 12.34 50.0 12.43
31 30.4 6.85 36.2 8.72 42.1 10.81 45.0 11.95 47.1 12.70 48.1 12.81 49.2 12.92
33 30.4 7.28 36.2 9.29 42.1 11.53 45.0 12.76 46.3 13.18 47.4 13.29 48.5 13.42
35 30.4 7.73 36.2 9.88 42.1 12.30 45.0 13.60 45.5 13.65 46.6 13.78 47.7 13.89
37 30.4 8.23 36.2 10.52 42.1 13.10 44.2 14.08 44.8 14.15 46.0 14.28 46.9 14.39
39 30.4 8.74 36.2 11.18 42.1 13.95 43.6 14.55 44.0 14.63 45.2 14.75 46.3 14.90
41 30.4 9.15 36.2 11.59 42.1 14.46 42.9 14.66 43.7 14.85 44.4 15.10 45.6 15.21
43 30.4 9.56 36.2 12.00 42.1 14.73 42.2 14.83 43.4 14.99 44.6 15.20 44.8 15.38
45 30.4 10.10 36.2 12.54 42.1 14.98 41.3 15.03 43.2 15.27 44.3 15.43 43.9 15.58
48 30.4 10.55 36.2 12.98 42.1 15.00 39.6 15.20 43.1 15.54 41.6 15.59 42.9 15.73
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

49
Mini TVR Individual 60Hz
Table 2-7.5: 4TVH0153BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 27.3 3.78 32.6 4.53 37.9 5.35 40.5 5.83 43.1 6.20 48.4 7.13 53.7 8.17
-2 27.3 3.81 32.6 4.58 37.9 5.41 40.5 5.91 43.1 6.28 48.4 7.20 53.7 8.25
0 27.3 3.87 32.6 4.64 37.9 5.50 40.5 5.98 43.1 6.36 48.4 7.29 53.7 8.31
2 27.3 3.93 32.6 4.69 37.9 5.55 40.5 6.08 43.1 6.46 48.4 7.44 53.7 8.44
4 27.3 3.99 32.6 4.76 37.9 5.65 40.5 6.16 43.1 6.54 48.4 7.55 53.7 8.56
6 27.3 4.04 32.6 4.86 37.9 5.75 40.5 6.27 43.1 6.66 48.4 7.67 53.7 8.70
8 27.3 4.12 32.6 4.95 37.9 5.87 40.5 6.36 43.1 6.77 48.4 7.81 53.7 8.78
10 27.3 4.20 32.6 5.06 37.9 5.97 40.5 6.45 43.1 6.93 48.4 7.91 53.7 8.93
12 27.3 4.27 32.6 5.15 37.9 6.09 40.5 6.56 43.1 7.06 48.4 8.06 53.7 9.09
14 27.3 4.34 32.6 5.24 37.9 6.19 40.5 6.69 43.1 7.18 48.4 8.21 53.7 9.26
16 27.3 4.42 32.6 5.33 37.9 6.32 40.5 6.82 43.1 7.33 48.4 8.38 53.5 9.42
18 27.3 4.49 32.6 5.44 37.9 6.43 40.5 6.95 43.1 7.48 48.4 8.54 52.9 9.71
20 27.3 4.58 32.6 5.57 37.9 6.56 40.5 7.09 43.1 7.75 48.4 9.18 52.1 10.17
90% 21 27.3 4.62 32.6 5.61 37.9 6.67 40.5 7.33 43.1 8.03 48.4 9.51 51.8 10.41
Mini TVR Individual Series Engineering Data Book

23 27.3 4.71 32.6 5.83 37.9 7.15 40.5 7.86 43.1 8.61 48.4 10.21 50.9 10.89
25 27.3 4.97 32.6 6.23 37.9 7.64 40.5 8.41 43.1 9.20 48.4 10.92 50.3 11.36
27 27.3 5.28 32.6 6.63 37.9 8.16 40.5 8.98 43.1 9.84 48.4 11.69 49.5 11.84
29 27.3 5.63 32.6 7.07 37.9 8.71 40.5 9.59 43.1 10.52 47.9 12.23 48.9 12.32
31 27.3 5.97 32.6 7.53 37.9 9.27 40.5 10.23 43.1 11.22 47.1 12.70 48.1 12.81
33 27.3 6.34 32.6 8.01 37.9 9.90 40.5 10.90 43.1 11.97 46.4 13.20 47.4 13.29
35 27.3 6.74 32.6 8.52 37.9 10.54 40.5 11.62 43.1 12.76 45.6 13.67 46.6 13.78
37 27.3 7.15 32.6 9.05 37.9 11.22 40.5 12.37 43.1 13.60 44.8 14.15 46.0 14.26
39 27.3 7.59 32.6 9.64 37.9 11.93 40.5 13.18 43.1 14.48 44.2 14.64 45.2 14.75
41 27.3 7.85 32.6 10.08 37.9 12.37 40.5 13.53 43.1 14.57 43.9 15.02 44.9 15.10
43 27.3 8.23 32.6 10.51 37.9 12.80 40.5 13.88 43.1 14.88 43.7 15.21 44.5 15.34
45 27.3 8.75 32.6 11.04 37.9 13.33 40.5 14.34 43.1 15.29 43.4 15.37 43.8 15.54
48 27.3 9.24 32.6 11.55 37.9 13.83 40.5 14.52 43.1 15.42 43.1 15.59 42.6 15.75
-5 24.3 3.33 28.9 3.93 33.6 4.66 36.0 4.95 38.4 5.33 43.1 6.17 47.7 7.04
-2 24.3 3.38 28.9 3.98 33.6 4.70 36.0 5.03 38.4 5.38 43.1 6.23 47.7 7.11
0 24.3 3.44 28.9 4.03 33.6 4.76 36.0 5.09 38.4 5.48 43.1 6.31 47.7 7.20
2 24.3 3.50 28.9 4.09 33.6 4.83 36.0 5.19 38.4 5.58 43.1 6.44 47.7 7.34
4 24.3 3.56 28.9 4.16 33.6 4.92 36.0 5.31 38.4 5.68 43.1 6.56 47.7 7.44
6 24.3 3.62 28.9 4.26 33.6 4.99 36.0 5.42 38.4 5.78 43.1 6.66 47.7 7.57
8 24.3 3.69 28.9 4.36 33.6 5.11 36.0 5.51 38.4 5.91 43.1 6.75 47.7 7.71
10 24.3 3.72 28.9 4.45 33.6 5.24 36.0 5.65 38.4 6.05 43.1 6.91 47.7 7.79
12 24.3 3.78 28.9 4.53 33.6 5.33 36.0 5.76 38.4 6.18 43.1 7.04 47.7 7.94
14 24.3 3.85 28.9 4.62 33.6 5.43 36.0 5.85 38.4 6.29 43.1 7.17 47.7 8.08
16 24.3 3.90 28.9 4.69 33.6 5.54 36.0 5.96 38.4 6.40 43.1 7.31 47.7 8.23
18 24.3 3.98 28.9 4.78 33.6 5.65 36.0 6.09 38.4 6.53 43.1 7.46 47.7 8.40
20 24.3 4.05 28.9 4.88 33.6 5.76 36.0 6.20 38.4 6.65 43.1 7.74 47.7 8.98
80% 21 24.3 4.09 28.9 4.91 33.6 5.81 36.0 6.27 38.4 6.80 43.1 8.01 47.7 9.31
23 24.3 4.16 28.9 5.02 33.6 6.09 36.0 6.67 38.4 7.28 43.1 8.58 47.7 9.99
25 24.3 4.29 28.9 5.33 33.6 6.51 36.0 7.13 38.4 7.77 43.1 9.18 47.7 10.69
27 24.3 4.56 28.9 5.68 33.6 6.93 36.0 7.61 38.4 8.30 43.1 9.81 47.7 11.44
29 24.3 4.86 28.9 6.05 33.6 7.39 36.0 8.10 38.4 8.87 43.1 10.47 47.7 12.23
31 24.3 5.15 28.9 6.43 33.6 7.86 36.0 8.63 38.4 9.46 43.1 11.18 46.9 12.70
33 24.3 5.48 28.9 6.84 33.6 8.38 36.0 9.20 38.4 10.06 43.1 11.91 46.3 13.18
35 24.3 5.81 28.9 7.28 33.6 8.91 36.0 9.79 38.4 10.72 43.1 12.70 45.5 13.66
37 24.3 6.16 28.9 7.72 33.6 9.48 36.0 10.43 38.4 11.42 43.1 13.55 44.8 14.13
39 24.3 6.53 28.9 8.23 33.6 10.08 36.0 11.09 38.4 12.15 43.1 14.43 44.0 14.63
41 24.3 6.67 28.9 8.30 33.6 10.23 36.0 11.38 38.4 12.37 43.1 14.79 43.8 14.88
43 24.3 6.87 28.9 8.38 33.6 10.38 36.0 11.58 38.4 12.54 43.1 14.96 43.5 15.04
45 24.3 7.06 28.9 8.47 33.6 10.58 36.0 11.82 38.4 12.76 43.1 15.13 43.0 15.29
48 24.3 7.30 28.9 8.53 33.6 10.74 36.0 11.98 38.4 12.87 43.1 15.28 42.6 15.50
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

50
Mini TVR Individual 60Hz
Table 2-7.5: 4TVH0153BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 21.2 2.97 25.4 3.48 29.4 3.95 31.5 4.23 33.6 4.52 37.6 5.17 41.8 5.94
-2 21.2 2.99 25.4 3.50 29.4 3.97 31.5 4.31 33.6 4.60 37.6 5.25 41.8 6.02
0 21.2 3.01 25.4 3.55 29.4 4.05 31.5 4.39 33.6 4.68 37.6 5.35 41.8 6.10
2 21.2 3.03 25.4 3.56 29.4 4.12 31.5 4.48 33.6 4.76 37.6 5.47 41.8 6.20
4 21.2 3.07 25.4 3.65 29.4 4.21 31.5 4.56 33.6 4.87 37.6 5.56 41.8 6.35
6 21.2 3.12 25.4 3.72 29.4 4.31 31.5 4.70 33.6 4.98 37.6 5.66 41.8 6.47
8 21.2 3.17 25.4 3.82 29.4 4.41 31.5 4.78 33.6 5.09 37.6 5.82 41.8 6.59
10 21.2 3.24 25.4 3.89 29.4 4.53 31.5 4.88 33.6 5.22 37.6 5.94 41.8 6.67
12 21.2 3.32 25.4 3.94 29.4 4.62 31.5 4.97 33.6 5.32 37.6 6.05 41.8 6.80
14 21.2 3.37 25.4 4.01 29.4 4.69 31.5 5.04 33.6 5.41 37.6 6.16 41.8 6.93
16 21.2 3.43 25.4 4.09 29.4 4.78 31.5 5.15 33.6 5.52 37.6 6.27 41.8 7.06
18 21.2 3.48 25.4 4.16 29.4 4.88 31.5 5.24 33.6 5.61 37.6 6.40 41.8 7.20
20 21.2 3.54 25.4 4.23 29.4 4.97 31.5 5.33 33.6 5.72 37.6 6.53 41.8 7.40
70% 21 21.2 3.57 25.4 4.27 29.4 5.00 31.5 5.39 33.6 5.77 37.6 6.62 41.8 7.66
23 21.2 3.63 25.4 4.34 29.4 5.11 31.5 5.57 33.6 6.07 37.6 7.09 41.8 8.21
25 21.2 3.70 25.4 4.53 29.4 5.44 31.5 5.96 33.6 6.47 37.6 7.59 41.8 8.78
27 21.2 3.92 25.4 4.82 29.4 5.81 31.5 6.34 33.6 6.91 37.6 8.10 41.8 9.39

Part 2 - Outdoor Unit Engineering Data


29 21.2 4.16 25.4 5.11 29.4 6.18 31.5 6.76 33.6 7.35 37.6 8.63 41.8 10.03
31 21.2 4.40 25.4 5.43 29.4 6.58 31.5 7.19 33.6 7.83 37.6 9.20 41.8 10.69
33 21.2 4.67 25.4 5.77 29.4 7.00 31.5 7.64 33.6 8.34 37.6 9.81 41.8 11.40
35 21.2 4.95 25.4 6.12 29.4 7.42 31.5 8.14 33.6 8.87 37.6 10.45 41.8 12.15
37 21.2 5.22 25.4 6.49 29.4 7.90 31.5 8.63 33.6 9.44 37.6 11.13 41.8 12.94
39 21.2 5.54 25.4 6.87 29.4 8.38 31.5 9.18 33.6 10.03 37.6 11.82 41.8 13.78
41 21.2 5.78 25.4 7.12 29.4 8.62 31.5 9.49 33.6 10.33 37.6 12.31 41.8 14.39
43 21.2 6.25 25.4 7.61 29.4 8.98 31.5 10.00 33.6 10.64 37.6 12.76 41.8 14.84
45 21.2 6.39 25.4 7.77 29.4 9.16 31.5 10.16 33.6 11.17 37.6 13.45 41.8 15.41
48 21.2 6.55 25.4 7.84 29.4 9.26 31.5 10.32 33.6 11.47 37.6 14.05 41.8 15.77
-5 18.2 2.53 21.7 2.94 25.2 3.43 27.0 3.65 28.8 3.94 32.3 4.42 35.8 5.08
-2 18.2 2.55 21.7 2.99 25.2 3.49 27.0 3.70 28.8 3.98 32.3 4.49 35.8 5.11
0 18.2 2.59 21.7 3.02 25.2 3.53 27.0 3.75 28.8 4.05 32.3 4.56 35.8 5.17
2 18.2 2.63 21.7 3.09 25.2 3.60 27.0 3.82 28.8 4.10 32.3 4.65 35.8 5.24
4 18.2 2.71 21.7 3.15 25.2 3.67 27.0 3.87 28.8 4.16 32.3 4.72 35.8 5.31
6 18.2 2.73 21.7 3.21 25.2 3.74 27.0 3.95 28.8 4.25 32.3 4.82 35.8 5.44
8 18.2 2.79 21.7 3.26 25.2 3.81 27.0 4.03 28.8 4.33 32.3 4.91 35.8 5.53
10 18.2 2.84 21.7 3.34 25.2 3.87 27.0 4.14 28.8 4.42 32.3 5.00 35.8 5.61
12 18.2 2.90 21.7 3.39 25.2 3.94 27.0 4.22 28.8 4.49 32.3 5.09 35.8 5.70
14 18.2 2.93 21.7 3.45 25.2 4.00 27.0 4.29 28.8 4.58 32.3 5.19 35.8 5.81
16 18.2 2.97 21.7 3.50 25.2 4.07 27.0 4.36 28.8 4.66 32.3 5.28 35.8 5.92
18 18.2 3.02 21.7 3.56 25.2 4.14 27.0 4.43 28.8 4.75 32.3 5.37 35.8 6.03
20 18.2 3.06 21.7 3.63 25.2 4.22 27.0 4.53 28.8 4.84 32.3 5.48 35.8 6.16
60% 21 18.2 3.10 21.7 3.65 25.2 4.25 27.0 4.56 28.8 4.87 32.3 5.53 35.8 6.21
23 18.2 3.13 21.7 3.72 25.2 4.32 27.0 4.66 28.8 4.97 32.3 5.75 35.8 6.62
25 18.2 3.19 21.7 3.78 25.2 4.49 27.0 4.87 28.8 5.28 32.3 6.14 35.8 7.06
27 18.2 3.32 21.7 4.01 25.2 4.78 27.0 5.20 28.8 5.63 32.3 6.54 35.8 7.53
29 18.2 3.50 21.7 4.25 25.2 5.09 27.0 5.53 28.8 5.99 32.3 6.98 35.8 8.05
31 18.2 3.72 21.7 4.51 25.2 5.41 27.0 5.88 28.8 6.38 32.3 7.42 35.8 8.56
33 18.2 3.92 21.7 4.78 25.2 5.74 27.0 6.25 28.8 6.78 32.3 7.90 35.8 9.13
35 18.2 4.16 21.7 5.08 25.2 6.08 27.0 6.63 28.8 7.20 32.3 8.41 35.8 9.71
37 18.2 4.40 21.7 5.37 25.2 6.45 27.0 7.04 28.8 7.64 32.3 8.94 35.8 10.34
39 18.2 4.64 21.7 5.68 25.2 6.84 27.0 7.46 28.8 8.12 32.3 9.49 35.8 11.00
41 18.2 4.79 21.7 5.93 25.2 7.08 27.0 7.76 28.8 8.42 32.3 9.94 35.8 11.49
43 18.2 4.94 21.7 6.18 25.2 7.33 27.0 7.99 28.8 8.71 32.3 10.36 35.8 11.99
45 18.2 5.17 21.7 6.49 25.2 7.63 27.0 8.29 28.8 9.14 32.3 10.83 35.8 12.65
48 18.2 5.36 21.7 6.78 25.2 7.89 27.0 8.50 28.8 9.50 32.3 11.22 35.8 13.25
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

51
Mini TVR Individual 60Hz
Table 2-7.5: 4TVH0153BD000AA cooling capacity (continued)
Indoor temperature(oC DB/WD)
Outdoor
Combination 20.8/14 23.3/16 25.8/18 27/19 28.2/20 30.7/22 32/24
temp.
(%) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
(oC)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 15.2 2.20 18.2 2.55 21.1 2.92 22.5 3.06 23.9 3.23 26.8 3.67 29.9 3.96
-2 15.2 2.22 18.2 2.60 21.1 2.96 22.5 3.10 23.9 3.29 26.8 3.72 29.9 4.01
0 15.2 2.25 18.2 2.64 21.1 3.01 22.5 3.15 23.9 3.33 26.8 3.78 29.9 4.08
2 15.2 2.29 18.2 2.67 21.1 3.06 22.5 3.19 23.9 3.38 26.8 3.80 29.9 4.16
4 15.2 2.31 18.2 2.72 21.1 3.09 22.5 3.23 23.9 3.45 26.8 3.90 29.9 4.27
6 15.2 2.35 18.2 2.76 21.1 3.14 22.5 3.30 23.9 3.52 26.8 3.95 29.9 4.39
8 15.2 2.41 18.2 2.81 21.1 3.19 22.5 3.38 23.9 3.56 26.8 4.02 29.9 4.53
10 15.2 2.46 18.2 2.84 21.1 3.24 22.5 3.43 23.9 3.67 26.8 4.12 29.9 4.60
12 15.2 2.47 18.2 2.88 21.1 3.30 22.5 3.50 23.9 3.74 26.8 4.20 29.9 4.67
14 15.2 2.51 18.2 2.91 21.1 3.34 22.5 3.57 23.9 3.79 26.8 4.27 29.9 4.77
16 15.2 2.55 18.2 2.95 21.1 3.39 22.5 3.63 23.9 3.85 26.8 4.34 29.9 4.84
18 15.2 2.58 18.2 3.01 21.1 3.45 22.5 3.68 23.9 3.92 26.8 4.42 29.9 4.93
20 15.2 2.62 18.2 3.04 21.1 3.50 22.5 3.74 23.9 4.00 26.8 4.49 29.9 5.02
50% 21 15.2 2.64 18.2 3.08 21.1 3.54 22.5 3.78 23.9 4.03 26.8 4.55 29.9 5.08
Mini TVR Individual Series Engineering Data Book

23 15.2 2.68 18.2 3.12 21.1 3.59 22.5 3.85 23.9 4.11 26.8 4.62 29.9 5.19
25 15.2 2.71 18.2 3.17 21.1 3.67 22.5 3.92 23.9 4.23 26.8 4.86 29.9 5.53
27 15.2 2.77 18.2 3.30 21.1 3.87 22.5 4.18 23.9 4.49 26.8 5.17 29.9 5.90
29 15.2 2.91 18.2 3.48 21.1 4.11 22.5 4.44 23.9 4.78 26.8 5.50 29.9 6.29
31 15.2 3.08 18.2 3.68 21.1 4.34 22.5 4.71 23.9 5.08 26.8 5.85 29.9 6.69
33 15.2 3.26 18.2 3.90 21.1 4.62 22.5 4.98 23.9 5.39 26.8 6.21 29.9 7.11
35 15.2 3.45 18.2 4.12 21.1 4.87 22.5 5.28 23.9 5.70 26.8 6.60 29.9 7.55
37 15.2 3.63 18.2 4.36 21.1 5.17 22.5 5.59 23.9 6.05 26.8 7.00 29.9 8.03
39 15.2 3.83 18.2 4.60 21.1 5.46 22.5 5.92 23.9 6.41 26.8 7.42 29.9 8.52
41 15.2 3.99 18.2 4.80 21.1 5.66 22.5 6.20 23.9 6.69 26.8 7.82 29.9 8.92
43 15.2 4.25 18.2 5.13 21.1 5.86 22.5 6.47 23.9 6.86 26.8 8.21 29.9 9.31
45 15.2 4.35 18.2 5.26 21.1 6.25 22.5 6.98 23.9 7.15 26.8 9.01 29.9 10.11
48 15.2 4.45 18.2 5.41 21.1 6.62 22.5 7.42 23.9 7.47 26.8 9.73 29.9 10.87
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

52
Mini TVR Individual 60Hz
7.2 Heating Capacity Tables
Table 2-7.6: 4TVH0068BD000AA heating capacity
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 15.6 4.82 15.6 5.10 15.5 5.38 15.5 5.51 15.4 5.66 15.4 5.93
-11.8 -13 16.3 5.04 16.3 5.31 16.2 5.57 16.1 5.70 16.1 5.84 16.1 6.10
-9.8 -11 17.0 5.26 17.0 5.51 16.9 5.77 16.9 5.89 16.9 6.02 16.8 6.27
-9.5 -10 17.5 5.37 17.4 5.62 17.3 5.86 17.3 5.99 17.3 6.11 17.3 6.35
-8.5 -9.1 17.8 5.47 17.7 5.70 17.7 5.95 17.7 6.07 17.7 6.19 17.6 6.43
-7 -7.6 18.4 5.62 18.4 5.86 18.4 6.09 18.4 6.21 18.3 6.32 18.2 6.56
-5 -5.6 19.4 5.84 19.3 6.06 19.3 6.28 19.3 6.39 19.2 6.50 19.2 6.72
-3 -3.7 20.3 6.03 20.3 6.24 20.3 6.45 20.2 6.56 20.2 6.66 20.1 6.87
130%
0 -0.7 21.9 6.32 21.9 6.52 21.9 6.71 21.9 6.78 21.8 6.91 21.8 7.10
3 2.2 23.7 6.58 23.6 6.77 23.5 6.95 23.5 7.03 23.5 7.13 23.5 7.30
5 4.1 24.9 6.75 24.8 6.92 24.8 7.09 24.7 7.18 24.7 7.26 24.7 7.43
7 6 26.1 6.91 26.1 7.07 26.1 7.23 26.0 7.31 26.0 7.39 24.9 7.10
9 7.9 27.4 7.05 27.4 7.21 27.4 7.36 27.3 7.44 26.7 7.28 24.9 6.67
11 9.8 28.8 7.19 28.8 7.34 28.6 7.43 27.7 7.14 26.7 6.84 24.9 6.28

Part 2 - Outdoor Unit Engineering Data


13 11.8 30.4 7.33 30.3 7.47 28.6 6.96 27.7 6.69 26.7 6.42 24.9 5.89
15 13.7 31.8 7.45 30.5 7.07 28.6 6.56 27.7 6.31 26.7 6.05 24.9 5.56
-13.7 -15 15.6 5.20 15.5 5.45 15.4 5.70 15.4 5.84 15.4 5.97 15.4 6.22
-11.8 -13 16.2 5.40 16.2 5.64 16.1 5.89 16.1 6.01 16.1 6.13 16.1 6.38
-9.8 -11 17.0 5.60 16.9 5.83 16.9 6.07 16.8 6.19 16.8 6.30 16.8 6.54
-9.5 -10 17.4 5.70 17.3 5.93 17.3 6.16 17.3 6.27 17.3 6.39 17.2 6.61
-8.5 -9.1 17.7 5.79 17.7 6.01 17.7 6.23 17.6 6.35 17.6 6.46 17.5 6.69
-7 -7.6 18.4 5.94 18.4 6.16 18.3 6.37 18.3 6.48 18.2 6.58 18.2 6.80
-5 -5.6 19.3 6.13 19.3 6.34 19.2 6.54 19.2 6.65 19.2 6.75 19.1 6.95
-3 -3.7 20.3 6.31 20.3 6.51 20.2 6.70 20.2 6.80 20.1 6.90 20.1 7.09
120%
0 -0.7 21.9 6.58 21.9 6.77 21.8 6.94 21.8 7.04 21.7 7.12 21.7 7.30
3 2.2 23.6 6.83 23.5 7.00 23.5 7.16 23.5 7.25 23.5 7.33 23.0 7.29
5 4.1 24.8 6.98 24.7 7.14 24.7 7.30 24.7 7.38 24.7 7.46 23.0 6.84
7 6 26.1 7.12 26.1 7.27 26.0 7.42 25.6 7.32 24.7 7.02 23.0 6.44
9 7.9 27.4 7.26 27.3 7.41 26.4 7.16 25.6 6.88 24.7 6.60 23.0 6.06
11 9.8 28.8 7.39 28.1 7.26 26.4 6.73 25.6 6.47 24.7 6.21 23.0 5.71
13 11.8 29.8 7.32 28.1 6.81 26.4 6.31 25.6 6.08 24.7 5.84 23.0 5.37
15 13.7 29.8 6.89 28.1 6.42 26.4 5.96 25.6 5.73 24.7 5.51 23.0 5.07
-13.7 -15 15.5 5.57 15.4 5.81 15.4 6.04 15.4 6.16 15.4 6.27 15.3 6.50
-11.8 -13 16.1 5.76 16.1 5.98 16.1 6.20 16.1 6.31 16.0 6.43 16.0 6.65
-9.8 -11 16.9 5.94 16.8 6.16 16.8 6.37 16.8 6.48 16.8 6.58 16.8 6.80
-9.5 -10 17.3 6.04 17.3 6.24 17.2 6.46 17.2 6.56 17.2 6.66 17.1 6.87
-8.5 -9.1 17.7 6.12 17.6 6.32 17.6 6.53 17.5 6.63 17.5 6.73 17.5 6.14
-7 -7.6 18.3 6.26 18.3 6.45 18.2 6.65 18.2 6.75 18.2 6.84 18.2 7.04
-5 -5.6 19.3 6.43 19.2 6.62 19.1 6.81 19.1 6.90 19.1 7.00 19.1 7.19
-3 -3.7 20.2 6.60 20.2 6.77 20.1 6.96 20.1 7.04 20.0 7.13 20.0 7.31
110%
0 -0.7 21.8 6.84 21.8 7.01 21.7 7.18 21.7 7.26 21.7 7.34 21.1 7.20
3 2.2 23.5 7.07 23.5 7.23 23.5 7.38 23.4 7.45 22.6 7.15 21.1 6.55
5 4.1 24.7 7.21 24.7 7.36 24.2 7.29 23.4 7.00 22.6 6.72 21.1 6.16
7 6 26.0 7.34 25.8 7.39 24.2 6.84 23.4 6.58 22.6 6.31 21.1 5.80
9 7.9 27.3 7.46 25.8 6.95 24.2 6.44 23.4 6.19 22.6 5.94 21.1 5.47
11 9.8 27.3 7.02 25.8 6.54 24.2 6.06 23.4 5.83 22.6 5.60 21.1 5.16
13 11.8 27.3 6.58 25.8 6.13 24.2 5.70 23.4 5.48 22.6 5.27 21.1 4.86
15 13.7 27.3 5.85 25.8 5.78 24.2 5.38 23.4 5.17 22.6 4.98 21.1 4.59
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

53
Mini TVR Individual 60Hz
Table 2-7.6: 4TVH0068BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 15.4 5.94 15.4 6.16 15.3 6.37 15.3 6.48 15.3 6.58 15.2 6.80
-11.8 -13 16.1 6.12 16.1 6.31 16.0 6.52 16.0 6.62 16.0 6.73 15.9 6.93
-9.8 -11 16.8 6.28 16.8 6.48 16.8 6.67 16.8 6.77 16.7 6.87 16.7 7.06
-9.5 -10 17.3 6.37 17.2 6.56 17.2 6.75 17.1 6.84 17.1 6.94 17.0 7.13
-8.5 -9.1 17.6 6.44 17.5 6.63 17.5 6.81 17.5 6.91 17.5 7.00 17.5 7.19
-7 -7.6 18.2 6.57 18.2 6.75 18.2 6.92 18.2 7.02 18.2 7.11 18.1 7.29
-5 -5.6 19.2 6.73 19.1 6.90 19.1 7.07 19.1 7.15 19.1 7.24 19.0 7.42
-3 -3.7 20.1 6.88 20.1 6.25 20.0 7.21 20.0 7.29 20.0 7.37 19.2 7.06
100%
0 -0.7 21.7 7.11 21.7 7.26 21.7 7.41 21.3 7.29 20.6 6.99 19.2 6.41
3 2.2 23.5 7.31 23.4 7.45 22.0 6.89 21.3 6.62 20.6 6.36 19.2 5.84
5 4.1 24.7 7.45 23.4 7.00 22.0 6.48 21.3 6.23 20.6 5.99 19.2 5.51
7 6 24.8 7.07 23.4 6.58 22.0 6.10 21.3 5.87 20.6 5.64 19.2 5.19
9 7.9 24.8 6.64 23.4 6.19 22.0 5.74 21.3 5.46 20.6 5.32 19.2 4.90
Mini TVR Individual Series Engineering Data Book

11 9.8 24.8 6.25 23.4 5.83 22.0 5.42 21.3 5.21 20.6 5.01 19.2 4.63
13 11.8 24.8 5.87 23.4 5.48 22.0 5.10 21.3 4.91 20.6 4.73 19.2 4.37
15 13.7 24.8 5.54 23.4 5.17 22.0 4.82 21.3 4.64 20.6 4.47 19.2 4.14
-13.7 -15 15.3 6.32 15.3 6.51 15.3 6.70 15.2 6.80 15.2 6.89 15.2 7.08
-11.8 -13 16.0 6.47 16.0 6.65 15.9 6.84 15.9 6.93 15.9 7.02 15.8 7.20
-9.8 -11 16.7 6.62 16.7 6.80 16.7 6.97 16.7 7.06 16.7 7.15 16.6 7.33
-9.5 -10 17.2 6.70 17.1 6.88 17.1 7.04 17.0 7.13 17.0 7.22 17.0 7.38
-8.5 -9.1 17.5 6.77 17.5 6.94 17.4 7.11 17.4 7.19 17.4 7.27 17.2 7.34
-7 -7.6 18.1 6.88 18.1 7.04 18.1 7.21 18.1 7.29 18.1 7.37 17.2 7.01
-5 -5.6 19.1 7.03 19.0 7.19 19.0 7.34 19.0 7.42 18.5 7.19 17.2 6.59
-3 -3.7 20.0 7.17 20.0 7.31 19.8 7.34 19.1 7.05 18.5 6.77 17.2 6.21
90%
0 -0.7 21.7 7.38 21.1 7.19 19.8 6.66 19.1 6.40 18.5 6.15 17.2 5.65
3 2.2 22.3 7.03 21.1 6.54 19.8 6.07 19.1 5.84 18.5 5.61 17.2 5.16
5 4.1 22.3 6.61 21.1 6.16 19.8 5.72 19.1 5.50 18.5 5.29 17.2 4.87
7 6 22.3 6.21 21.1 5.80 19.8 5.39 19.1 5.19 18.5 4.99 17.2 4.60
9 7.9 22.3 5.85 21.1 5.46 19.8 5.08 19.1 4.90 18.5 4.71 17.2 4.35
11 9.8 22.3 5.51 21.1 5.15 19.8 4.80 19.1 4.63 18.5 4.45 17.2 4.12
13 11.8 22.3 5.19 21.1 4.86 19.8 4.52 19.1 4.37 18.5 4.21 17.2 3.89
15 13.7 22.3 4.90 21.1 4.59 19.8 4.29 19.1 4.13 18.5 3.98 17.2 3.69
-13.7 -15 15.3 6.69 15.2 6.86 15.2 7.03 15.2 7.11 15.2 7.20 15.2 7.37
-11.8 -13 15.9 6.83 15.9 6.99 15.9 7.15 15.9 7.23 15.9 7.32 15.4 7.12
-9.8 -11 16.7 6.96 16.7 7.12 16.6 7.28 16.6 7.35 16.5 7.34 15.4 6.73
-9.5 -10 17.1 7.03 17.0 7.18 17.0 7.34 17.0 7.41 16.5 7.12 15.4 6.53
-8.5 -9.1 17.5 7.10 16.2 7.25 17.4 7.39 17.0 7.22 16.5 6.93 15.4 6.35
-7 -7.6 18.1 7.20 18.1 7.34 17.6 7.18 17.0 6.90 16.5 6.62 15.4 6.08
-5 -5.6 19.1 7.33 18.7 7.29 17.6 6.75 17.0 6.49 16.5 6.23 15.4 5.72
-3 -3.7 19.8 7.37 18.7 6.86 17.6 6.35 17.0 6.12 16.5 5.87 15.4 5.40
80%
0 -0.7 19.8 6.69 18.7 6.23 17.6 5.78 17.0 5.57 16.5 5.35 15.4 4.93
3 2.2 19.8 6.09 18.7 5.68 17.6 5.28 17.0 5.09 16.5 4.90 15.4 4.52
5 4.1 19.8 5.74 18.7 5.35 17.6 4.98 17.0 4.80 16.5 4.63 15.4 4.27
7 6 19.8 5.40 18.7 5.05 17.6 4.71 17.0 4.54 16.5 4.37 15.4 4.04
9 7.9 19.8 5.10 18.7 4.77 17.6 4.44 17.0 4.29 16.5 4.14 15.4 3.83
11 9.8 19.8 4.82 18.7 4.51 17.6 4.21 17.0 4.06 16.5 3.91 15.4 3.63
13 11.8 19.8 4.54 18.7 4.25 17.6 3.98 17.0 3.83 16.5 3.70 15.4 3.43
15 13.7 19.8 4.29 18.7 4.03 17.6 3.77 17.0 3.64 16.5 3.51 15.4 3.26
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

54
Mini TVR Individual 60Hz
Table 2-7.6: 4TVH0068BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 15.2 7.07 15.1 7.22 15.1 7.37 14.8 7.26 14.4 6.96 13.4 6.38
-11.8 -13 15.8 7.19 15.8 7.33 15.4 7.15 14.8 6.88 14.4 6.60 13.4 6.05
-9.8 -11 16.6 7.30 16.4 7.30 15.4 6.76 14.8 6.50 14.4 6.23 13.4 5.73
-9.5 -10 17.0 7.37 16.4 7.08 15.4 6.56 14.8 6.31 14.4 6.06 13.4 5.57
-8.5 -9.1 17.4 7.41 16.4 6.89 15.4 6.38 14.8 6.14 14.4 5.90 13.4 5.43
-7 -7.6 17.4 7.07 16.4 6.58 15.4 6.11 14.8 5.88 14.4 5.65 13.4 5.20
-5 -5.6 17.4 6.65 16.4 6.19 15.4 5.75 14.8 5.53 14.4 6.53 13.4 4.90
-3 -3.7 17.4 6.26 16.4 5.84 15.4 5.43 14.8 5.22 14.4 5.02 13.4 4.63
70%
0 -0.7 17.4 5.70 16.4 5.32 15.4 4.95 14.8 4.77 14.4 4.59 13.4 4.25
3 2.2 17.4 5.20 16.4 4.87 15.4 4.54 14.8 4.37 14.4 4.21 13.4 3.90
5 4.1 17.4 4.91 16.4 4.59 15.4 4.29 14.8 4.13 14.4 3.98 13.4 3.69
7 6 17.4 4.64 16.4 4.35 15.4 4.06 14.8 3.91 14.4 3.78 13.4 3.50
9 7.9 17.4 4.39 16.4 4.11 15.4 3.84 14.8 3.71 14.4 3.58 13.4 3.32
11 9.8 17.4 4.15 16.4 3.89 15.4 3.64 14.8 3.52 14.4 3.40 13.4 3.15
13 11.8 17.4 3.92 16.4 3.68 15.4 3.45 14.8 3.34 14.4 3.22 13.4 2.99

Part 2 - Outdoor Unit Engineering Data


15 13.7 17.4 3.72 16.4 3.49 15.4 3.27 14.8 3.17 14.4 3.06 13.4 2.85
-13.7 -15 14.9 7.26 14.0 6.75 13.2 6.26 12.8 6.02 12.4 5.78 11.5 5.32
-11.8 -13 14.9 6.87 14.0 6.39 13.2 5.93 12.8 5.71 12.4 5.49 11.5 5.08
-9.8 -11 14.9 6.49 14.0 6.04 13.2 5.62 12.8 5.40 12.4 5.20 11.5 4.79
-9.5 -10 14.9 6.31 14.0 5.88 13.2 5.46 12.8 5.26 12.4 5.05 11.5 4.66
-8.5 -9.1 14.9 6.14 14.0 5.73 13.2 5.32 12.8 5.13 12.4 4.93 11.5 4.55
-7 -7.6 14.9 5.87 14.0 5.48 13.2 5.09 12.8 4.91 12.4 4.72 11.5 4.36
-5 -5.6 14.9 5.53 14.0 5.16 13.2 4.81 12.8 4.63 12.4 4.46 11.5 4.13
-3 -3.7 14.9 5.22 14.0 4.88 13.2 4.55 12.8 4.39 12.4 4.22 11.5 3.91
60%
0 -0.7 14.9 4.77 14.0 4.47 13.2 4.17 12.8 4.02 12.4 3.87 11.5 3.59
3 2.2 14.9 4.37 14.0 4.10 13.2 3.83 12.8 3.70 12.4 3.57 11.5 3.31
5 4.1 14.9 4.14 14.0 3.88 13.2 3.63 12.8 3.51 12.4 3.38 11.5 3.14
7 6 14.9 3.91 14.0 3.68 13.2 3.44 12.8 3.33 12.4 3.22 11.5 2.99
9 7.9 14.9 3.71 14.0 3.49 13.2 3.26 12.8 3.16 12.4 3.05 11.5 2.84
11 9.8 14.9 3.52 14.0 3.31 13.2 3.11 12.8 3.00 12.4 2.90 11.5 2.71
13 11.8 14.9 3.33 14.0 3.14 13.2 2.95 12.8 2.85 12.4 2.76 11.5 2.57
15 13.7 14.9 3.17 14.0 2.98 13.2 2.80 12.8 2.72 12.4 2.63 11.5 2.46
-13.7 -15 12.4 5.81 11.7 5.43 11.0 5.05 10.6 4.86 10.2 4.68 9.5 4.33
-11.8 -13 12.4 5.52 11.7 5.16 11.0 4.80 10.6 4.63 10.2 4.45 9.5 4.12
-9.8 -11 12.4 5.23 11.7 4.89 11.0 4.55 10.6 4.39 10.2 4.23 9.5 3.91
-9.5 -10 12.4 5.09 11.7 4.75 11.0 4.44 10.6 4.28 10.2 4.12 9.5 3.81
-8.5 -9.1 12.4 4.96 11.7 4.64 11.0 4.33 10.6 4.17 10.2 4.02 9.5 3.72
-7 -7.6 12.4 4.75 11.7 4.45 11.0 4.15 10.6 4.01 10.2 3.87 9.5 3.58
-5 -5.6 12.4 4.48 11.7 4.21 11.0 3.93 10.6 3.79 10.2 3.66 9.5 3.39
-3 -3.7 12.4 4.25 11.7 3.98 11.0 3.72 10.6 3.60 10.2 3.47 9.5 3.22
50%
0 -0.7 12.4 3.90 11.7 3.66 11.0 3.43 10.6 3.31 10.2 3.20 9.5 2.98
3 2.2 12.4 3.59 11.7 3.37 11.0 3.16 10.6 3.06 10.2 2.95 9.5 2.76
5 4.1 12.4 3.41 11.7 3.20 11.0 3.00 10.6 2.91 10.2 2.81 9.5 2.62
7 6 12.4 3.23 11.7 3.04 11.0 2.86 10.6 2.76 10.2 2.68 9.5 2.50
9 7.9 12.4 3.07 11.7 2.89 11.0 2.72 10.6 2.64 10.2 2.55 9.5 2.38
11 9.8 12.4 2.92 11.7 2.75 11.0 2.59 10.6 2.51 10.2 2.43 9.5 2.27
13 11.8 12.4 2.77 11.7 2.61 11.0 2.46 10.6 2.39 10.2 2.31 9.5 2.17
15 13.7 12.4 2.64 11.7 2.50 11.0 2.35 10.6 2.28 10.2 2.21 9.5 2.08
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

55
Mini TVR Individual 60Hz
Table 2-7.7: 4TVH0076BD000AA heating capacity
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 17.4 4.67 17.3 4.93 17.3 5.20 17.3 5.33 17.2 5.47 17.2 5.74
-11.8 -13 18.1 4.87 18.1 5.13 18.0 5.39 18.0 5.52 18.0 5.65 17.9 5.90
-9.8 -11 19.0 5.09 18.9 5.33 18.8 5.58 18.8 5.70 18.8 5.82 18.7 6.07
-9.5 -10 19.4 5.19 19.4 5.43 19.3 5.67 19.3 5.79 19.2 5.91 19.2 6.14
-8.5 -9.1 19.8 5.29 19.8 5.52 19.8 5.75 19.7 5.87 19.7 5.98 19.6 6.22
-7 -7.6 20.5 5.44 20.5 5.67 20.5 5.89 20.5 6.01 20.4 6.11 20.3 6.34
-5 -5.6 21.6 5.65 21.5 5.86 21.5 6.08 21.5 6.18 21.4 6.28 21.4 6.50
-3 -3.7 22.6 5.83 22.6 6.04 22.6 6.24 22.5 6.34 22.5 6.44 22.4 6.64
130%
0 -0.7 24.4 6.11 24.4 6.31 24.3 6.49 24.3 6.56 24.3 6.68 24.3 6.87
3 2.2 26.4 6.37 26.3 6.54 26.2 6.72 26.2 6.80 26.2 6.90 26.1 7.06
5 4.1 27.7 6.53 27.6 6.70 27.6 6.86 27.5 6.94 27.5 7.03 27.5 7.19
7 6 29.1 6.68 29.0 6.83 29.0 7.00 28.9 7.07 28.9 7.15 27.8 6.87
9 7.9 30.6 6.82 30.5 6.97 30.5 7.12 30.4 7.20 29.8 7.04 27.8 6.45
Mini TVR Individual Series Engineering Data Book

11 9.8 32.1 6.96 32.0 7.09 31.9 7.19 30.8 6.90 29.8 6.62 27.8 6.08
13 11.8 33.8 7.09 33.8 7.23 31.9 6.74 30.8 6.47 29.8 6.21 27.8 5.70
15 13.7 35.5 7.21 33.9 6.84 31.9 6.34 30.8 6.10 29.8 5.85 27.8 5.38
-13.7 -15 17.3 5.03 17.3 5.27 17.2 5.52 17.2 5.65 17.2 5.77 17.1 6.02
-11.8 -13 18.0 5.22 18.0 5.46 18.0 5.69 18.0 5.82 17.9 5.93 17.9 6.17
-9.8 -11 18.9 5.42 18.8 5.64 18.8 5.87 18.7 5.98 18.7 6.09 18.7 6.32
-9.5 -10 19.4 5.52 19.3 5.74 19.2 5.95 19.2 6.07 19.2 6.18 19.1 6.40
-8.5 -9.1 19.8 5.60 19.7 5.82 19.7 6.03 19.6 6.14 19.6 6.25 19.5 6.47
-7 -7.6 20.5 5.75 20.5 5.95 20.4 6.16 20.4 6.27 20.3 6.37 20.3 6.57
-5 -5.6 21.5 5.93 21.5 6.13 21.4 6.33 21.4 6.43 21.4 6.53 21.3 6.72
-3 -3.7 22.6 6.11 22.6 6.30 22.5 6.48 22.5 6.57 22.4 6.67 22.4 6.86
120%
0 -0.7 24.3 6.37 24.3 6.54 24.3 6.71 24.3 6.80 24.2 6.89 24.2 7.06
3 2.2 26.3 6.61 26.2 6.77 26.2 6.93 26.1 7.01 26.1 7.09 25.6 7.05
5 4.1 27.6 6.75 27.5 6.90 27.5 7.06 27.5 7.13 27.5 7.21 25.6 6.62
7 6 29.0 6.89 29.0 7.03 28.9 7.18 28.5 7.08 27.5 6.79 25.6 6.23
9 7.9 30.5 7.03 30.4 7.16 29.4 6.93 28.5 6.65 27.5 6.38 25.6 5.86
11 9.8 32.0 7.15 31.3 7.03 29.4 6.51 28.5 6.26 27.5 6.01 25.6 5.52
13 11.8 33.2 7.08 31.3 6.59 29.4 6.11 28.5 5.88 27.5 5.65 25.6 5.20
15 13.7 33.2 6.67 31.3 6.21 29.4 5.76 28.5 5.54 27.5 5.33 25.6 4.90
-13.7 -15 17.3 5.39 17.2 5.62 17.1 5.84 17.1 5.95 17.1 6.07 17.0 6.29
-11.8 -13 18.0 5.57 18.0 5.78 17.9 6.00 17.9 6.11 17.8 6.21 17.8 6.44
-9.8 -11 18.8 5.75 18.7 5.95 18.7 6.16 18.7 6.27 18.7 6.37 18.7 6.57
-9.5 -10 19.3 5.84 19.2 6.04 19.1 6.25 19.1 6.34 19.1 6.44 19.1 6.64
-8.5 -9.1 19.7 5.92 19.6 6.11 19.6 6.31 19.5 6.41 19.5 6.51 19.5 5.94
-7 -7.6 20.4 6.05 20.4 6.24 20.3 6.43 20.3 6.53 20.3 6.62 20.2 6.81
-5 -5.6 21.5 6.22 21.4 6.41 21.3 6.58 21.3 6.67 21.3 6.77 21.2 6.95
-3 -3.7 22.5 6.38 22.5 6.55 22.4 6.73 22.4 6.81 22.3 6.90 22.3 7.07
110%
0 -0.7 24.3 6.62 24.3 6.78 24.2 6.94 24.2 7.02 24.2 7.10 23.5 6.96
3 2.2 26.2 6.84 26.1 6.99 26.1 7.13 26.1 7.20 25.2 6.91 23.5 6.34
5 4.1 27.5 6.97 27.5 7.12 27.0 7.05 26.1 6.77 25.2 6.50 23.5 5.96
7 6 28.9 7.10 28.7 7.15 27.0 6.62 26.1 6.36 25.2 6.11 23.5 5.61
9 7.9 30.4 7.22 28.7 6.72 27.0 6.23 26.1 5.98 25.2 5.75 23.5 5.29
11 9.8 30.4 6.79 28.7 6.32 27.0 5.86 26.1 5.64 25.2 5.42 23.5 4.99
13 11.8 30.4 6.37 28.7 5.93 27.0 5.51 26.1 5.30 25.2 5.10 23.5 4.70
15 13.7 30.4 5.66 28.7 5.59 27.0 5.20 26.1 5.00 25.2 4.82 23.5 4.44
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

56
Mini TVR Individual 60Hz
Table 2-7.7: 4TVH0076BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 17.2 5.75 17.1 5.95 17.0 6.16 17.0 6.27 17.0 6.37 17.0 6.57
-11.8 -13 17.9 5.92 17.9 6.11 17.8 6.31 17.8 6.41 17.8 6.51 17.7 6.70
-9.8 -11 18.7 6.08 18.7 6.27 18.7 6.45 18.7 6.55 18.6 6.64 18.6 6.83
-9.5 -10 19.2 6.16 19.1 6.34 19.1 6.53 19.1 6.62 19.1 6.71 19.0 6.90
-8.5 -9.1 19.6 6.23 19.5 6.41 19.5 6.59 19.5 6.68 19.4 6.77 19.4 6.95
-7 -7.6 20.3 6.35 20.3 6.53 20.2 6.70 20.2 6.79 20.2 6.87 20.1 7.05
-5 -5.6 21.4 6.51 21.3 6.67 21.3 6.84 21.2 6.92 21.2 7.00 21.2 7.17
-3 -3.7 22.4 6.66 22.4 6.05 22.3 6.97 22.3 7.05 22.3 7.13 21.4 6.83
100%
0 -0.7 24.2 6.87 24.2 7.02 24.1 7.16 23.7 7.05 22.9 6.76 21.4 6.20
3 2.2 26.1 7.07 26.1 7.20 24.5 6.67 23.7 6.41 22.9 6.15 21.4 5.65
5 4.1 27.5 7.20 26.1 6.77 24.5 6.27 23.7 6.03 22.9 5.79 21.4 5.33
7 6 27.6 6.83 26.1 6.36 24.5 5.90 23.7 5.68 22.9 5.46 21.4 5.02
9 7.9 27.6 6.42 26.1 5.98 24.5 5.56 23.7 5.28 22.9 5.14 21.4 4.74
11 9.8 27.6 6.05 26.1 5.64 24.5 5.24 23.7 5.04 22.9 4.85 21.4 4.47
13 11.8 27.6 5.68 26.1 5.30 24.5 4.93 23.7 4.75 22.9 4.57 21.4 4.22

Part 2 - Outdoor Unit Engineering Data


15 13.7 27.6 5.36 26.1 5.00 24.5 4.66 23.7 4.49 22.9 4.32 21.4 4.00
-13.7 -15 17.1 6.11 17.0 6.30 17.0 6.48 16.9 6.57 16.9 6.67 16.9 6.85
-11.8 -13 17.8 6.26 17.8 6.44 17.7 6.61 17.7 6.70 17.7 6.79 17.6 6.97
-9.8 -11 18.6 6.41 18.6 6.57 18.6 6.74 18.6 6.83 18.6 6.92 18.5 7.09
-9.5 -10 19.1 6.48 19.0 6.65 19.0 6.81 18.9 6.90 18.9 6.98 18.9 7.14
-8.5 -9.1 19.5 6.55 19.5 6.71 19.4 6.87 19.4 6.95 19.4 7.03 19.2 7.10
-7 -7.6 20.2 6.66 20.2 6.81 20.1 6.97 20.1 7.05 20.1 7.13 19.2 6.78
-5 -5.6 21.3 6.80 21.2 6.95 21.2 7.10 21.1 7.17 20.6 6.95 19.2 6.37
-3 -3.7 22.3 6.93 22.3 7.07 22.1 7.10 21.3 6.82 20.6 6.54 19.2 6.01
90%
0 -0.7 24.1 7.13 23.4 6.96 22.1 6.44 21.3 6.19 20.6 5.95 19.2 5.46
3 2.2 24.8 6.80 23.4 6.33 22.1 5.87 21.3 5.65 20.6 5.42 19.2 5.00
5 4.1 24.8 6.39 23.4 5.95 22.1 5.53 21.3 5.32 20.6 5.12 19.2 4.71
7 6 24.8 6.01 23.4 5.61 22.1 5.21 21.3 5.02 20.6 4.83 19.2 4.45
9 7.9 24.8 5.66 23.4 5.28 22.1 4.91 21.3 4.74 20.6 4.56 19.2 4.21
11 9.8 24.8 5.33 23.4 4.98 22.1 4.64 21.3 4.47 20.6 4.31 19.2 3.98
13 11.8 24.8 5.02 23.4 4.70 22.1 4.38 21.3 4.22 20.6 4.07 19.2 3.76
15 13.7 24.8 4.74 23.4 4.44 22.1 4.15 21.3 4.00 20.6 3.85 19.2 3.57
-13.7 -15 17.0 6.47 17.0 6.64 17.0 6.80 17.0 6.88 16.9 6.96 16.9 7.13
-11.8 -13 17.7 6.60 17.7 6.77 17.7 6.92 17.7 7.00 17.7 7.08 17.1 6.89
-9.8 -11 18.6 6.73 18.6 6.89 18.5 7.04 18.5 7.11 18.4 7.09 17.1 6.51
-9.5 -10 19.1 6.80 19.0 6.95 19.0 7.09 19.0 7.17 18.4 6.89 17.1 6.31
-8.5 -9.1 19.4 6.87 18.1 7.01 19.4 7.15 19.0 6.99 18.4 6.70 17.1 6.15
-7 -7.6 20.1 6.96 20.1 7.10 19.6 6.95 19.0 6.67 18.4 6.41 17.1 5.88
-5 -5.6 21.2 7.09 20.8 7.05 19.6 6.53 19.0 6.28 18.4 6.02 17.1 5.53
-3 -3.7 22.1 7.13 20.8 6.64 19.6 6.15 19.0 5.92 18.4 5.68 17.1 5.23
80%
0 -0.7 22.1 6.47 20.8 6.02 19.6 5.59 19.0 5.39 18.4 5.17 17.1 4.77
3 2.2 22.1 5.89 20.8 5.49 19.6 5.11 19.0 4.92 18.4 4.74 17.1 4.37
5 4.1 22.1 5.55 20.8 5.18 19.6 4.82 19.0 4.64 18.4 4.47 17.1 4.13
7 6 22.1 5.23 20.8 4.89 19.6 4.55 19.0 4.39 18.4 4.23 17.1 3.91
9 7.9 22.1 4.93 20.8 4.61 19.6 4.30 19.0 4.15 18.4 4.00 17.1 3.70
11 9.8 22.1 4.66 20.8 4.36 19.6 4.07 19.0 3.92 18.4 3.78 17.1 3.51
13 11.8 22.1 4.39 20.8 4.11 19.6 3.85 19.0 3.71 18.4 3.58 17.1 3.32
15 13.7 22.1 4.15 20.8 3.90 19.6 3.65 19.0 3.52 18.4 3.39 17.1 3.16
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

57
Mini TVR Individual 60Hz
Table 2-7.7: 4TVH0076BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 16.9 6.83 16.8 6.98 16.8 7.13 16.5 7.02 16.0 6.73 14.9 6.18
-11.8 -13 17.6 6.95 17.6 7.09 17.2 6.92 16.5 6.65 16.0 6.38 14.9 5.85
-9.8 -11 18.5 7.06 18.2 7.06 17.2 6.54 16.5 6.28 16.0 6.03 14.9 5.54
-9.5 -10 18.9 7.13 18.2 6.85 17.2 6.34 16.5 6.10 16.0 5.86 14.9 5.39
-8.5 -9.1 19.3 7.16 18.2 6.67 17.2 6.18 16.5 5.94 16.0 5.71 14.9 5.25
-7 -7.6 19.3 6.84 18.2 6.37 17.2 5.91 16.5 5.69 16.0 5.46 14.9 5.03
-5 -5.6 19.3 6.43 18.2 5.99 17.2 5.56 16.5 5.35 16.0 6.32 14.9 4.74
-3 -3.7 19.3 6.05 18.2 5.65 17.2 5.25 16.5 5.05 16.0 4.86 14.9 4.48
70%
0 -0.7 19.3 5.51 18.2 5.15 17.2 4.79 16.5 4.61 16.0 4.44 14.9 4.11
3 2.2 19.3 5.03 18.2 4.71 17.2 4.39 16.5 4.23 16.0 4.08 14.9 3.77
5 4.1 19.3 4.75 18.2 4.44 17.2 4.15 16.5 4.00 16.0 3.85 14.9 3.57
7 6 19.3 4.49 18.2 4.21 17.2 3.92 16.5 3.78 16.0 3.65 14.9 3.39
9 7.9 19.3 4.24 18.2 3.98 17.2 3.72 16.5 3.59 16.0 3.46 14.9 3.21
Mini TVR Individual Series Engineering Data Book

11 9.8 19.3 4.01 18.2 3.76 17.2 3.52 16.5 3.40 16.0 3.29 14.9 3.05
13 11.8 19.3 3.79 18.2 3.56 17.2 3.33 16.5 3.23 16.0 3.11 14.9 2.90
15 13.7 19.3 3.59 18.2 3.38 17.2 3.16 16.5 3.06 16.0 2.96 14.9 2.76
-13.7 -15 16.6 7.02 15.6 6.53 14.7 6.05 14.2 5.82 13.8 5.59 12.8 5.14
-11.8 -13 16.6 6.64 15.6 6.18 14.7 5.74 14.2 5.52 13.8 5.31 12.8 4.91
-9.8 -11 16.6 6.28 15.6 5.85 14.7 5.43 14.2 5.23 13.8 5.03 12.8 4.64
-9.5 -10 16.6 6.10 15.6 5.69 14.7 5.28 14.2 5.09 13.8 4.89 12.8 4.51
-8.5 -9.1 16.6 5.94 15.6 5.54 14.7 5.15 14.2 4.96 13.8 4.77 12.8 4.40
-7 -7.6 16.6 5.68 15.6 5.30 14.7 4.93 14.2 4.75 13.8 4.57 12.8 4.22
-5 -5.6 16.6 5.35 15.6 5.00 14.7 4.65 14.2 4.48 13.8 4.31 12.8 3.99
-3 -3.7 16.6 5.05 15.6 4.72 14.7 4.40 14.2 4.24 13.8 4.08 12.8 3.78
60%
0 -0.7 16.6 4.61 15.6 4.32 14.7 4.03 14.2 3.89 13.8 3.75 12.8 3.47
3 2.2 16.6 4.23 15.6 3.97 14.7 3.71 14.2 3.58 13.8 3.46 12.8 3.20
5 4.1 16.6 4.00 15.6 3.75 14.7 3.51 14.2 3.39 13.8 3.27 12.8 3.04
7 6 16.6 3.78 15.6 3.56 14.7 3.33 14.2 3.22 13.8 3.11 12.8 2.89
9 7.9 16.6 3.59 15.6 3.37 14.7 3.16 14.2 3.06 13.8 2.95 12.8 2.75
11 9.8 16.6 3.40 15.6 3.20 14.7 3.00 14.2 2.90 13.8 2.80 12.8 2.62
13 11.8 16.6 3.22 15.6 3.03 14.7 2.85 14.2 2.76 13.8 2.67 12.8 2.49
15 13.7 16.6 3.06 15.6 2.88 14.7 2.71 14.2 2.63 13.8 2.54 12.8 2.38
-13.7 -15 13.8 5.62 13.0 5.25 12.3 4.88 11.8 4.70 11.4 4.53 10.6 4.18
-11.8 -13 13.8 5.34 13.0 4.99 12.3 4.64 11.8 4.47 11.4 4.31 10.6 3.98
-9.8 -11 13.8 5.06 13.0 4.73 12.3 4.41 11.8 4.24 11.4 4.09 10.6 3.78
-9.5 -10 13.8 4.92 13.0 4.60 12.3 4.29 11.8 4.14 11.4 3.98 10.6 3.69
-8.5 -9.1 13.8 4.80 13.0 4.49 12.3 4.18 11.8 4.04 11.4 3.89 10.6 3.60
-7 -7.6 13.8 4.60 13.0 4.31 12.3 4.01 11.8 3.88 11.4 3.74 10.6 3.46
-5 -5.6 13.8 4.34 13.0 4.07 12.3 3.80 11.8 3.67 11.4 3.54 10.6 3.28
-3 -3.7 13.8 4.11 13.0 3.85 12.3 3.60 11.8 3.48 11.4 3.36 10.6 3.12
50%
0 -0.7 13.8 3.77 13.0 3.54 12.3 3.32 11.8 3.20 11.4 3.10 10.6 2.88
3 2.2 13.8 3.47 13.0 3.26 12.3 3.06 11.8 2.96 11.4 2.86 10.6 2.67
5 4.1 13.8 3.29 13.0 3.10 12.3 2.90 11.8 2.81 11.4 2.72 10.6 2.54
7 6 13.8 3.13 13.0 2.94 12.3 2.77 11.8 2.67 11.4 2.59 10.6 2.42
9 7.9 13.8 2.97 13.0 2.80 12.3 2.63 11.8 2.55 11.4 2.47 10.6 2.31
11 9.8 13.8 2.82 13.0 2.66 12.3 2.51 11.8 2.43 11.4 2.35 10.6 2.20
13 11.8 13.8 2.68 13.0 2.53 12.3 2.38 11.8 2.31 11.4 2.24 10.6 2.10
15 13.7 13.8 2.55 13.0 2.41 12.3 2.28 11.8 2.21 11.4 2.14 10.6 2.01
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

58
Mini TVR Individual 60Hz
Table 2-7.8: 4TVH0089BD000AA heating capacity
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 20.3 5.38 20.2 5.69 20.1 6.00 20.1 6.15 20.0 6.31 20.0 6.61
-11.8 -13 21.1 5.62 21.1 5.92 21.0 6.21 20.9 6.36 20.9 6.51 20.8 6.80
-9.8 -11 22.1 5.86 22.0 6.15 21.9 6.43 21.9 6.57 21.9 6.71 21.8 6.99
-9.5 -10 22.6 5.99 22.5 6.26 22.4 6.53 22.4 6.68 22.3 6.81 22.3 7.08
-8.5 -9.1 23.1 6.09 23.0 6.36 23.0 6.63 22.9 6.76 22.9 6.90 22.8 7.17
-7 -7.6 23.9 6.27 23.9 6.53 23.8 6.79 23.8 6.92 23.7 7.05 23.6 7.31
-5 -5.6 25.2 6.51 25.1 6.76 25.0 7.00 25.0 7.13 24.9 7.24 24.9 7.49
-3 -3.7 26.3 6.72 26.2 6.96 26.2 7.19 26.1 7.31 26.1 7.43 26.1 7.66
130%
0 -0.7 28.4 7.05 28.4 7.27 28.3 7.48 28.3 7.56 28.2 7.70 28.2 7.91
3 2.2 30.7 7.34 30.6 7.54 30.5 7.75 30.5 7.84 30.5 7.95 30.4 8.14
5 4.1 32.2 7.52 32.1 7.72 32.1 7.90 32.0 8.00 32.0 8.10 31.9 8.28
7 6 33.8 7.70 33.7 7.88 33.7 8.06 33.7 8.15 33.7 8.24 32.3 7.91
9 7.9 35.6 7.86 35.5 8.04 35.5 8.20 35.4 8.29 34.7 8.12 32.3 7.44
11 9.8 37.4 8.02 37.3 8.18 37.1 8.28 35.8 7.96 34.7 7.63 32.3 7.00
13 11.8 39.4 8.17 39.3 8.33 37.1 7.76 35.8 7.45 34.7 7.16 32.3 6.57

Part 2 - Outdoor Unit Engineering Data


15 13.7 41.3 8.31 39.4 7.89 37.1 7.31 35.8 7.03 34.7 6.75 32.3 6.20
-13.7 -15 20.2 5.79 20.1 6.08 20.0 6.36 20.0 6.51 20.0 6.65 19.9 6.93
-11.8 -13 21.0 6.01 21.0 6.29 20.9 6.56 20.9 6.70 20.8 6.84 20.8 7.11
-9.8 -11 22.0 6.24 21.9 6.50 21.9 6.76 21.8 6.90 21.8 7.02 21.7 7.29
-9.5 -10 22.5 6.36 22.4 6.61 22.3 6.86 22.3 6.99 22.3 7.12 22.3 7.37
-8.5 -9.1 23.0 6.46 22.9 6.70 22.9 6.95 22.8 7.07 22.8 7.21 22.7 7.45
-7 -7.6 23.8 6.62 23.8 6.86 23.7 7.10 23.7 7.22 23.6 7.34 23.6 7.58
-5 -5.6 25.1 6.84 25.0 7.07 24.9 7.29 24.9 7.41 24.9 7.52 24.8 7.75
-3 -3.7 26.2 7.04 26.2 7.26 26.1 7.47 26.1 7.58 26.1 7.69 26.1 7.90
120%
0 -0.7 28.3 7.34 28.3 7.54 28.2 7.74 28.2 7.84 28.1 7.94 28.1 8.14
3 2.2 30.6 7.61 30.5 7.80 30.5 7.98 30.4 8.08 30.4 8.17 29.8 8.13
5 4.1 32.1 7.78 32.0 7.96 32.0 8.13 31.9 8.22 31.9 8.31 29.8 7.63
7 6 33.7 7.94 33.7 8.11 33.7 8.27 33.1 8.16 32.0 7.82 29.8 7.18
9 7.9 35.5 8.10 35.4 8.26 34.2 7.98 33.1 7.67 32.0 7.36 29.8 6.76
11 9.8 37.3 8.24 36.4 8.10 34.2 7.51 33.1 7.21 32.0 6.92 29.8 6.37
13 11.8 38.6 8.16 36.4 7.59 34.2 7.04 33.1 6.77 32.0 6.51 29.8 5.99
15 13.7 38.6 7.68 36.4 7.15 34.2 6.64 33.1 6.38 32.0 6.14 29.8 5.65
-13.7 -15 20.1 6.21 20.0 6.47 19.9 6.73 19.9 6.86 19.9 6.99 19.8 7.25
-11.8 -13 20.9 6.42 20.9 6.67 20.8 6.92 20.8 7.04 20.7 7.16 20.7 7.42
-9.8 -11 21.9 6.62 21.8 6.86 21.8 7.10 21.7 7.22 21.7 7.34 21.7 7.58
-9.5 -10 22.4 6.73 22.3 6.96 22.3 7.20 22.3 7.31 22.3 7.43 22.2 7.66
-8.5 -9.1 22.9 6.82 22.8 7.05 22.8 7.28 22.7 7.39 22.7 7.51 22.7 6.84
-7 -7.6 23.7 6.98 23.7 7.19 23.6 7.41 23.6 7.52 23.6 7.63 23.5 7.85
-5 -5.6 25.0 7.17 24.9 7.38 24.8 7.59 24.8 7.69 24.8 7.80 24.7 8.01
-3 -3.7 26.1 7.36 26.1 7.55 26.1 7.75 26.1 7.85 26.0 7.95 26.0 8.15
110%
0 -0.7 28.2 7.63 28.2 7.82 28.1 8.00 28.1 8.09 28.1 8.19 27.3 8.03
3 2.2 30.5 7.89 30.4 8.05 30.4 8.22 30.3 8.30 29.3 7.97 27.3 7.30
5 4.1 32.0 8.04 32.0 8.20 31.4 8.12 30.3 7.80 29.3 7.49 27.3 6.87
7 6 33.7 8.19 33.4 8.24 31.4 7.63 30.3 7.33 29.3 7.04 27.3 6.46
9 7.9 35.4 8.32 33.4 7.74 31.4 7.18 30.3 6.90 29.3 6.62 27.3 6.09
11 9.8 35.4 7.82 33.4 7.29 31.4 6.76 30.3 6.50 29.3 6.24 27.3 5.75
13 11.8 35.4 7.34 33.4 6.84 31.4 6.35 30.3 6.11 29.3 5.87 27.3 5.41
15 13.7 35.4 6.52 33.4 6.45 31.4 6.00 30.3 5.77 29.3 5.55 27.3 5.12
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

59
Mini TVR Individual 60Hz
Table 2-7.8: 4TVH0089BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 20.0 6.62 19.9 6.86 19.8 7.10 19.8 7.22 19.8 7.34 19.7 7.58
-11.8 -13 20.8 6.82 20.8 7.04 20.7 7.27 20.7 7.38 20.7 7.50 20.6 7.73
-9.8 -11 21.8 7.00 21.7 7.22 21.7 7.44 21.7 7.55 21.6 7.66 21.6 7.87
-9.5 -10 22.3 7.10 22.3 7.31 22.3 7.52 22.2 7.63 22.2 7.74 22.1 7.95
-8.5 -9.1 22.8 7.18 22.7 7.39 22.7 7.59 22.7 7.70 22.6 7.81 22.6 8.01
-7 -7.6 23.6 7.32 23.6 7.52 23.5 7.72 23.5 7.82 23.5 7.92 23.4 8.12
-5 -5.6 24.9 7.51 24.8 7.69 24.8 7.89 24.7 7.97 24.7 8.07 24.6 8.27
-3 -3.7 26.1 7.67 26.1 6.97 26.0 8.04 26.0 8.12 26.0 8.21 24.9 7.87
100%
0 -0.7 28.1 7.92 28.1 8.09 28.0 8.26 27.6 8.12 26.7 7.79 24.9 7.14
3 2.2 30.4 8.15 30.3 8.30 28.5 7.68 27.6 7.38 26.7 7.09 24.9 6.51
5 4.1 31.9 8.30 30.3 7.80 28.5 7.22 27.6 6.95 26.7 6.68 24.9 6.14
7 6 32.1 7.88 30.3 7.33 28.5 6.80 27.6 6.54 26.7 6.29 24.9 5.78
9 7.9 32.1 7.40 30.3 6.90 28.5 6.40 27.6 6.08 26.7 5.93 24.9 5.46
Mini TVR Individual Series Engineering Data Book

11 9.8 32.1 6.97 30.3 6.50 28.5 6.04 27.6 5.81 26.7 5.59 24.9 5.16
13 11.8 32.1 6.54 30.3 6.11 28.5 5.69 27.6 5.48 26.7 5.27 24.9 4.87
15 13.7 32.1 6.17 30.3 5.77 28.5 5.37 27.6 5.17 26.7 4.98 24.9 4.61
-13.7 -15 19.9 7.05 19.8 7.26 19.8 7.47 19.7 7.58 19.7 7.68 19.7 7.89
-11.8 -13 20.7 7.22 20.7 7.42 20.6 7.62 20.6 7.73 20.6 7.82 20.5 8.03
-9.8 -11 21.7 7.38 21.7 7.58 21.6 7.77 21.6 7.87 21.6 7.97 21.5 8.17
-9.5 -10 22.2 7.47 22.1 7.67 22.1 7.85 22.0 7.95 22.0 8.05 22.0 8.23
-8.5 -9.1 22.7 7.55 22.7 7.74 22.6 7.92 22.6 8.01 22.6 8.11 22.3 8.19
-7 -7.6 23.5 7.67 23.5 7.85 23.4 8.04 23.4 8.12 23.4 8.21 22.3 7.82
-5 -5.6 24.7 7.84 24.7 8.01 24.7 8.18 24.6 8.27 23.9 8.01 22.3 7.35
-3 -3.7 25.9 7.99 25.9 8.15 25.7 8.19 24.7 7.86 23.9 7.54 22.3 6.92
90%
0 -0.7 28.1 8.22 27.3 8.02 25.7 7.43 24.7 7.14 23.9 6.85 22.3 6.30
3 2.2 28.9 7.83 27.3 7.29 25.7 6.76 24.7 6.51 23.9 6.25 22.3 5.76
5 4.1 28.9 7.37 27.3 6.86 25.7 6.38 24.7 6.13 23.9 5.90 22.3 5.43
7 6 28.9 6.92 27.3 6.46 25.7 6.01 24.7 5.78 23.9 5.56 22.3 5.13
9 7.9 28.9 6.53 27.3 6.08 25.7 5.66 24.7 5.46 23.9 5.25 22.3 4.85
11 9.8 28.9 6.15 27.3 5.74 25.7 5.35 24.7 5.16 23.9 4.96 22.3 4.59
13 11.8 28.9 5.78 27.3 5.41 25.7 5.04 24.7 4.87 23.9 4.69 22.3 4.34
15 13.7 28.9 5.47 27.3 5.11 25.7 4.78 24.7 4.61 23.9 4.44 22.3 4.12
-13.7 -15 19.8 7.46 19.7 7.65 19.7 7.84 19.7 7.93 19.6 8.03 19.6 8.22
-11.8 -13 20.6 7.61 20.6 7.80 20.5 7.97 20.5 8.06 20.5 8.16 19.9 7.94
-9.8 -11 21.6 7.76 21.6 7.94 21.5 8.12 21.5 8.20 21.4 8.18 19.9 7.50
-9.5 -10 22.2 7.84 22.1 8.01 22.1 8.18 22.1 8.27 21.4 7.94 19.9 7.28
-8.5 -9.1 22.6 7.91 21.0 8.08 22.5 8.24 22.1 8.05 21.4 7.73 19.9 7.08
-7 -7.6 23.4 8.03 23.4 8.19 22.8 8.01 22.1 7.69 21.4 7.38 19.9 6.77
-5 -5.6 24.7 8.17 24.2 8.12 22.8 7.52 22.1 7.23 21.4 6.94 19.9 6.38
-3 -3.7 25.7 8.21 24.2 7.65 22.8 7.08 22.1 6.82 21.4 6.54 19.9 6.02
80%
0 -0.7 25.7 7.45 24.2 6.94 22.8 6.45 22.1 6.21 21.4 5.96 19.9 5.49
3 2.2 25.7 6.79 24.2 6.33 22.8 5.89 22.1 5.67 21.4 5.46 19.9 5.03
5 4.1 25.7 6.39 24.2 5.97 22.8 5.55 22.1 5.35 21.4 5.16 19.9 4.76
7 6 25.7 6.02 24.2 5.63 22.8 5.25 22.1 5.06 21.4 4.87 19.9 4.50
9 7.9 25.7 5.69 24.2 5.32 22.8 4.95 22.1 4.78 21.4 4.61 19.9 4.27
11 9.8 25.7 5.37 24.2 5.02 22.8 4.69 22.1 4.52 21.4 4.36 19.9 4.04
13 11.8 25.7 5.06 24.2 4.74 22.8 4.43 22.1 4.27 21.4 4.12 19.9 3.82
15 13.7 25.7 4.79 24.2 4.49 22.8 4.20 22.1 4.05 21.4 3.91 19.9 3.64
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

60
Mini TVR Individual 60Hz
Table 2-7.8: 4TVH0089BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 19.7 7.88 19.6 8.04 19.6 8.21 19.2 8.09 18.6 7.76 17.3 7.12
-11.8 -13 20.5 8.01 20.5 8.17 20.0 7.97 19.2 7.66 18.6 7.36 17.3 6.75
-9.8 -11 21.5 8.14 21.2 8.13 20.0 7.53 19.2 7.24 18.6 6.95 17.3 6.38
-9.5 -10 22.0 8.21 21.2 7.89 20.0 7.31 19.2 7.03 18.6 6.76 17.3 6.21
-8.5 -9.1 22.5 8.26 21.2 7.68 20.0 7.12 19.2 6.84 18.6 6.58 17.3 6.05
-7 -7.6 22.5 7.89 21.2 7.34 20.0 6.81 19.2 6.55 18.6 6.30 17.3 5.79
-5 -5.6 22.5 7.41 21.2 6.91 20.0 6.41 19.2 6.16 18.6 7.28 17.3 5.47
-3 -3.7 22.5 6.98 21.2 6.51 20.0 6.05 19.2 5.82 18.6 5.60 17.3 5.17
70%
0 -0.7 22.5 6.35 21.2 5.93 20.0 5.52 19.2 5.32 18.6 5.12 17.3 4.73
3 2.2 22.5 5.80 21.2 5.43 20.0 5.06 19.2 4.87 18.6 4.70 17.3 4.34
5 4.1 22.5 5.47 21.2 5.12 20.0 4.79 19.2 4.61 18.6 4.44 17.3 4.12
7 6 22.5 5.17 21.2 4.85 20.0 4.52 19.2 4.36 18.6 4.21 17.3 3.90
9 7.9 22.5 4.89 21.2 4.58 20.0 4.28 19.2 4.13 18.6 3.99 17.3 3.70
11 9.8 22.5 4.63 21.2 4.34 20.0 4.06 19.2 3.92 18.6 3.79 17.3 3.51
13 11.8 22.5 4.37 21.2 4.11 20.0 3.84 19.2 3.72 18.6 3.59 17.3 3.34

Part 2 - Outdoor Unit Engineering Data


15 13.7 22.5 4.14 21.2 3.89 20.0 3.65 19.2 3.53 18.6 3.41 17.3 3.18
-13.7 -15 19.3 8.09 18.2 7.52 17.1 6.98 16.6 6.71 16.0 6.45 14.9 5.93
-11.8 -13 19.3 7.66 18.2 7.13 17.1 6.61 16.6 6.37 16.0 6.12 14.9 5.66
-9.8 -11 19.3 7.23 18.2 6.74 17.1 6.26 16.6 6.02 16.0 5.79 14.9 5.34
-9.5 -10 19.3 7.03 18.2 6.55 17.1 6.08 16.6 5.86 16.0 5.63 14.9 5.19
-8.5 -9.1 19.3 6.84 18.2 6.38 17.1 5.93 16.6 5.71 16.0 5.49 14.9 5.07
-7 -7.6 19.3 6.54 18.2 6.11 17.1 5.68 16.6 5.48 16.0 5.26 14.9 4.87
-5 -5.6 19.3 6.16 18.2 5.76 17.1 5.36 16.6 5.17 16.0 4.97 14.9 4.60
-3 -3.7 19.3 5.82 18.2 5.44 17.1 5.07 16.6 4.89 16.0 4.71 14.9 4.35
60%
0 -0.7 19.3 5.32 18.2 4.98 17.1 4.64 16.6 4.49 16.0 4.32 14.9 4.00
3 2.2 19.3 4.87 18.2 4.57 17.1 4.27 16.6 4.12 16.0 3.98 14.9 3.69
5 4.1 19.3 4.61 18.2 4.33 17.1 4.04 16.6 3.91 16.0 3.77 14.9 3.51
7 6 19.3 4.36 18.2 4.10 17.1 3.83 16.6 3.71 16.0 3.59 14.9 3.33
9 7.9 19.3 4.13 18.2 3.89 17.1 3.64 16.6 3.52 16.0 3.40 14.9 3.17
11 9.8 19.3 3.92 18.2 3.69 17.1 3.46 16.6 3.35 16.0 3.23 14.9 3.02
13 11.8 19.3 3.71 18.2 3.50 17.1 3.28 16.6 3.18 16.0 3.07 14.9 2.87
15 13.7 19.3 3.53 18.2 3.32 17.1 3.13 16.6 3.03 16.0 2.93 14.9 2.74
-13.7 -15 16.1 6.48 15.2 6.05 14.3 5.62 13.7 5.42 13.3 5.22 12.4 4.82
-11.8 -13 16.1 6.15 15.2 5.75 14.3 5.35 13.7 5.16 13.3 4.96 12.4 4.59
-9.8 -11 16.1 5.83 15.2 5.45 14.3 5.08 13.7 4.89 13.3 4.72 12.4 4.36
-9.5 -10 16.1 5.67 15.2 5.30 14.3 4.94 13.7 4.77 13.3 4.59 12.4 4.25
-8.5 -9.1 16.1 5.53 15.2 5.17 14.3 4.82 13.7 4.65 13.3 4.49 12.4 4.15
-7 -7.6 16.1 5.30 15.2 4.96 14.3 4.63 13.7 4.47 13.3 4.31 12.4 3.99
-5 -5.6 16.1 5.00 15.2 4.69 14.3 4.38 13.7 4.23 13.3 4.08 12.4 3.78
-3 -3.7 16.1 4.73 15.2 4.44 14.3 4.15 13.7 4.01 13.3 3.87 12.4 3.59
50%
0 -0.7 16.1 4.34 15.2 4.08 14.3 3.82 13.7 3.69 13.3 3.57 12.4 3.32
3 2.2 16.1 4.00 15.2 3.76 14.3 3.52 13.7 3.41 13.3 3.29 12.4 3.07
5 4.1 16.1 3.80 15.2 3.57 14.3 3.35 13.7 3.24 13.3 3.13 12.4 2.92
7 6 16.1 3.60 15.2 3.39 14.3 3.19 13.7 3.08 13.3 2.98 12.4 2.79
9 7.9 16.1 3.42 15.2 3.22 14.3 3.03 13.7 2.94 13.3 2.84 12.4 2.66
11 9.8 16.1 3.25 15.2 3.06 14.3 2.89 13.7 2.80 13.3 2.71 12.4 2.53
13 11.8 16.1 3.09 15.2 2.91 14.3 2.75 13.7 2.67 13.3 2.58 12.4 2.42
15 13.7 16.1 2.94 15.2 2.78 14.3 2.62 13.7 2.54 13.3 2.46 12.4 2.31
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

61
Mini TVR Individual 60Hz
Table 2-7.9: 4TVH0136BD000AA heating capacity
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 32.0 8.78 31.9 9.28 31.7 9.79 31.7 10.03 31.6 10.29 31.6 10.80
-11.8 -13 33.3 9.17 33.3 9.66 33.1 10.13 33.0 10.38 33.0 10.62 32.9 11.10
-9.8 -11 34.9 9.57 34.7 10.03 34.6 10.49 34.6 10.73 34.6 10.96 34.4 11.42
-9.5 -10 35.7 9.77 35.6 10.22 35.4 10.67 35.4 10.90 35.3 11.11 35.3 11.56
-8.5 -9.1 36.4 9.95 36.3 10.38 36.3 10.83 36.1 11.04 36.1 11.26 36.0 11.71
-7 -7.6 37.7 10.24 37.7 10.67 37.6 11.09 37.6 11.30 37.4 11.50 37.3 11.94
-5 -5.6 39.7 10.62 39.6 11.03 39.4 11.43 39.4 11.63 39.3 11.82 39.3 12.22
-3 -3.7 41.6 10.97 41.4 11.36 41.4 11.73 41.3 11.94 41.3 12.12 41.1 12.50
130%
0 -0.7 44.9 11.50 44.9 11.86 44.7 12.21 44.7 12.34 44.6 12.57 44.6 12.92
3 2.2 48.4 11.98 48.3 12.31 48.1 12.64 48.1 12.80 48.1 12.97 48.0 13.29
5 4.1 50.9 12.28 50.7 12.60 50.7 12.90 50.6 13.06 50.6 13.22 50.4 13.52
7 6 53.4 12.57 53.3 12.86 53.3 13.16 53.1 13.31 53.1 13.45 51.0 12.92
9 7.9 56.1 12.83 56.0 13.12 56.0 13.39 55.9 13.54 54.7 13.25 51.0 12.14
Mini TVR Individual Series Engineering Data Book

11 9.8 59.0 13.09 58.9 13.35 58.6 13.52 56.6 12.99 54.7 12.45 51.0 11.43
13 11.8 62.1 13.33 62.0 13.59 58.6 12.67 56.6 12.17 54.7 11.69 51.0 10.73
15 13.7 65.1 13.57 62.3 12.87 58.6 11.94 56.6 11.48 54.7 11.01 51.0 10.12
-13.7 -15 31.9 9.46 31.7 9.92 31.6 10.38 31.6 10.63 31.6 10.85 31.4 11.32
-11.8 -13 33.1 9.82 33.1 10.26 33.0 10.71 33.0 10.94 32.9 11.16 32.9 11.60
-9.8 -11 34.7 10.19 34.6 10.61 34.6 11.04 34.4 11.26 34.4 11.46 34.3 11.89
-9.5 -10 35.6 10.38 35.4 10.80 35.3 11.20 35.3 11.42 35.3 11.62 35.1 12.04
-8.5 -9.1 36.3 10.54 36.1 10.94 36.1 11.35 36.0 11.55 36.0 11.76 35.9 12.17
-7 -7.6 37.6 10.81 37.6 11.20 37.4 11.59 37.4 11.79 37.3 11.98 37.3 12.37
-5 -5.6 39.6 11.16 39.4 11.53 39.3 11.91 39.3 12.09 39.3 12.28 39.1 12.64
-3 -3.7 41.4 11.49 41.4 11.85 41.3 12.20 41.3 12.37 41.1 12.56 41.1 12.90
120%
0 -0.7 44.7 11.98 44.7 12.31 44.6 12.63 44.6 12.80 44.4 12.96 44.4 13.29
3 2.2 48.3 12.43 48.1 12.73 48.1 13.03 48.0 13.19 48.0 13.33 47.0 13.26
5 4.1 50.7 12.70 50.6 12.99 50.6 13.28 50.4 13.42 50.4 13.57 47.0 12.46
7 6 53.3 12.96 53.3 13.23 53.1 13.51 52.3 13.32 50.6 12.77 47.0 11.72
9 7.9 56.0 13.22 55.9 13.48 54.0 13.03 52.3 12.52 50.6 12.01 47.0 11.03
11 9.8 58.9 13.45 57.4 13.22 54.0 12.25 52.3 11.78 50.6 11.30 47.0 10.39
13 11.8 61.0 13.32 57.4 12.40 54.0 11.49 52.3 11.06 50.6 10.63 47.0 9.77
15 13.7 61.0 12.54 57.4 11.68 54.0 10.84 52.3 10.42 50.6 10.02 47.0 9.23
-13.7 -15 31.7 10.13 31.6 10.57 31.4 10.98 31.4 11.20 31.4 11.42 31.3 11.84
-11.8 -13 33.0 10.48 33.0 10.88 32.9 11.29 32.9 11.49 32.7 11.69 32.7 12.11
-9.8 -11 34.6 10.81 34.4 11.20 34.4 11.59 34.3 11.79 34.3 11.98 34.3 12.37
-9.5 -10 35.4 10.98 35.3 11.36 35.1 11.75 35.1 11.94 35.1 12.12 35.0 12.50
-8.5 -9.1 36.1 11.13 36.0 11.50 36.0 11.88 35.9 12.07 35.9 12.25 35.9 11.17
-7 -7.6 37.4 11.39 37.4 11.73 37.3 12.10 37.3 12.28 37.3 12.46 37.1 12.82
-5 -5.6 39.4 11.71 39.3 12.05 39.1 12.38 39.1 12.56 39.1 12.73 39.0 13.08
-3 -3.7 41.3 12.01 41.3 12.33 41.1 12.66 41.1 12.82 41.0 12.97 41.0 13.31
110%
0 -0.7 44.6 12.46 44.6 12.76 44.4 13.06 44.4 13.21 44.4 13.36 43.1 13.10
3 2.2 48.1 12.87 48.0 13.15 48.0 13.42 47.9 13.55 46.3 13.00 43.1 11.92
5 4.1 50.6 13.12 50.6 13.39 49.6 13.26 47.9 12.73 46.3 12.22 43.1 11.22
7 6 53.1 13.36 52.7 13.45 49.6 12.46 47.9 11.96 46.3 11.49 43.1 10.55
9 7.9 55.9 13.58 52.7 12.64 49.6 11.72 47.9 11.26 46.3 10.81 43.1 9.95
11 9.8 55.9 12.77 52.7 11.89 49.6 11.03 47.9 10.61 46.3 10.19 43.1 9.39
13 11.8 55.9 11.98 52.7 11.16 49.6 10.37 47.9 9.98 46.3 9.59 43.1 8.84
15 13.7 55.9 10.64 52.7 10.52 49.6 9.79 47.9 9.41 46.3 9.07 43.1 8.36
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

62
Mini TVR Individual 60Hz
Table 2-7.9: 4TVH0136BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 31.6 10.81 31.4 11.20 31.3 11.59 31.3 11.79 31.3 11.98 31.1 12.37
-11.8 -13 32.9 11.13 32.9 11.49 32.7 11.86 32.7 12.05 32.7 12.24 32.6 12.61
-9.8 -11 34.4 11.43 34.3 11.79 34.3 12.14 34.3 12.33 34.1 12.50 34.1 12.84
-9.5 -10 35.3 11.59 35.1 11.94 35.1 12.28 35.0 12.46 35.0 12.63 34.9 12.97
-8.5 -9.1 36.0 11.72 35.9 12.07 35.9 12.40 35.9 12.57 35.7 12.74 35.7 13.07
-7 -7.6 37.3 11.95 37.3 12.28 37.1 12.60 37.1 12.77 37.1 12.93 37.0 13.26
-5 -5.6 39.3 12.25 39.1 12.56 39.1 12.87 39.0 13.02 39.0 13.18 38.9 13.49
-3 -3.7 41.1 12.53 41.1 11.37 41.0 13.12 41.0 13.26 41.0 13.41 39.3 12.84
100%
0 -0.7 44.4 12.93 44.4 13.20 44.3 13.48 43.6 13.26 42.1 12.72 39.3 11.66
3 2.2 48.0 13.31 47.9 13.55 45.0 12.54 43.6 12.05 42.1 11.58 39.3 10.62
5 4.1 50.4 13.55 47.9 12.73 45.0 11.79 43.6 11.34 42.1 10.90 39.3 10.02
7 6 50.7 12.86 47.9 11.96 45.0 11.10 43.6 10.68 42.1 10.26 39.3 9.44
9 7.9 50.7 12.08 47.9 11.26 45.0 10.45 43.6 9.93 42.1 9.67 39.3 8.91
11 9.8 50.7 11.37 47.9 10.61 45.0 9.86 43.6 9.48 42.1 9.13 39.3 8.42
13 11.8 50.7 10.68 47.9 9.98 45.0 9.28 43.6 8.94 42.1 8.61 39.3 7.94

Part 2 - Outdoor Unit Engineering Data


15 13.7 50.7 10.08 47.9 9.41 45.0 8.76 43.6 8.45 42.1 8.13 39.3 7.52
-13.7 -15 31.4 11.50 31.2 11.85 31.2 12.20 31.1 12.37 31.1 12.54 31.1 12.89
-11.8 -13 32.7 11.78 32.7 12.11 32.5 12.44 32.5 12.61 32.5 12.77 32.4 13.10
-9.8 -11 34.2 12.05 34.2 12.37 34.1 12.69 34.1 12.84 34.1 13.02 33.9 13.33
-9.5 -10 35.1 12.20 34.9 12.51 34.9 12.82 34.8 12.97 34.8 13.13 34.8 13.44
-8.5 -9.1 35.8 12.33 35.8 12.63 35.7 12.93 35.7 13.07 35.7 13.23 35.2 13.36
-7 -7.6 37.1 12.53 37.1 12.82 36.9 13.12 36.9 13.26 36.9 13.41 35.2 12.76
-5 -5.6 39.1 12.80 38.9 13.07 38.9 13.35 38.8 13.49 37.8 13.07 35.2 11.99
-3 -3.7 40.9 13.05 40.9 13.31 40.5 13.36 39.1 12.83 37.8 12.31 35.2 11.30
90%
0 -0.7 44.4 13.42 43.1 13.09 40.5 12.12 39.1 11.65 37.8 11.19 35.2 10.28
3 2.2 45.6 12.79 43.1 11.91 40.5 11.04 39.1 10.62 37.8 10.21 35.2 9.40
5 4.1 45.6 12.02 43.1 11.20 40.5 10.41 39.1 10.00 37.8 9.63 35.2 8.87
7 6 45.6 11.30 43.1 10.55 40.5 9.80 39.1 9.44 37.8 9.08 35.2 8.38
9 7.9 45.6 10.65 43.1 9.93 40.5 9.24 39.1 8.91 37.8 8.58 35.2 7.91
11 9.8 45.6 10.03 43.1 9.37 40.5 8.74 39.1 8.42 37.8 8.10 35.2 7.50
13 11.8 45.6 9.44 43.1 8.84 40.5 8.23 39.1 7.94 37.8 7.65 35.2 7.08
15 13.7 45.6 8.92 43.1 8.35 40.5 7.80 39.1 7.52 37.8 7.25 35.2 6.72
-13.7 -15 31.3 12.18 31.1 12.48 31.1 12.80 31.1 12.94 31.0 13.10 31.0 13.42
-11.8 -13 32.6 12.43 32.6 12.73 32.4 13.02 32.4 13.16 32.4 13.32 31.4 12.96
-9.8 -11 34.1 12.67 34.1 12.96 34.0 13.25 34.0 13.38 33.7 13.35 31.4 12.24
-9.5 -10 35.0 12.80 34.9 13.07 34.9 13.35 34.9 13.49 33.7 12.96 31.4 11.88
-8.5 -9.1 35.7 12.92 33.2 13.19 35.6 13.45 34.9 13.15 33.7 12.61 31.4 11.56
-7 -7.6 37.0 13.10 37.0 13.36 36.0 13.07 34.9 12.56 33.7 12.05 31.4 11.06
-5 -5.6 39.0 13.33 38.3 13.26 36.0 12.28 34.9 11.81 33.7 11.33 31.4 10.41
-3 -3.7 40.6 13.41 38.3 12.48 36.0 11.56 34.9 11.13 33.7 10.68 31.4 9.83
80%
0 -0.7 40.6 12.17 38.3 11.33 36.0 10.52 34.9 10.13 33.7 9.73 31.4 8.97
3 2.2 40.6 11.09 38.3 10.34 36.0 9.61 34.9 9.25 33.7 8.91 31.4 8.22
5 4.1 40.6 10.44 38.3 9.74 36.0 9.07 34.9 8.74 33.7 8.42 31.4 7.77
7 6 40.6 9.83 38.3 9.20 36.0 8.56 34.9 8.26 33.7 7.96 31.4 7.35
9 7.9 40.6 9.28 38.3 8.68 36.0 8.09 34.9 7.80 33.7 7.52 31.4 6.96
11 9.8 40.6 8.76 38.3 8.20 36.0 7.65 34.9 7.38 33.7 7.12 31.4 6.60
13 11.8 40.6 8.26 38.3 7.74 36.0 7.24 34.9 6.98 33.7 6.73 31.4 6.24
15 13.7 40.6 7.81 38.3 7.34 36.0 6.86 34.9 6.62 33.7 6.39 31.4 5.94
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

63
Mini TVR Individual 60Hz
Table 2-7.9: 4TVH0136BD000AA heating capacity (continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 31.1 12.86 30.9 13.13 30.9 13.41 30.4 13.20 29.4 12.67 27.4 11.62
-11.8 -13 32.4 13.07 32.4 13.33 31.5 13.02 30.4 12.51 29.4 12.01 27.4 11.01
-9.8 -11 33.9 13.29 33.5 13.28 31.5 12.30 30.4 11.82 29.4 11.34 27.4 10.42
-9.5 -10 34.8 13.41 33.5 12.89 31.5 11.94 30.4 11.47 29.4 11.03 27.4 10.13
-8.5 -9.1 35.5 13.48 33.5 12.54 31.5 11.62 30.4 11.17 29.4 10.74 27.4 9.87
-7 -7.6 35.5 12.87 33.5 11.98 31.5 11.11 30.4 10.70 29.4 10.28 27.4 9.46
-5 -5.6 35.5 12.09 33.5 11.27 31.5 10.47 30.4 10.06 29.4 11.89 27.4 8.92
-3 -3.7 35.5 11.39 33.5 10.62 31.5 9.87 30.4 9.50 29.4 9.14 27.4 8.43
70%
0 -0.7 35.5 10.36 33.5 9.69 31.5 9.01 30.4 8.68 29.4 8.36 27.4 7.73
3 2.2 35.5 9.47 33.5 8.87 31.5 8.26 30.4 7.96 29.4 7.67 27.4 7.09
5 4.1 35.5 8.94 33.5 8.36 31.5 7.81 30.4 7.52 29.4 7.25 27.4 6.72
7 6 35.5 8.45 33.5 7.91 31.5 7.38 30.4 7.12 29.4 6.88 27.4 6.37
9 7.9 35.5 7.99 33.5 7.48 31.5 6.99 30.4 6.75 29.4 6.52 27.4 6.04
Mini TVR Individual Series Engineering Data Book

11 9.8 35.5 7.55 33.5 7.08 31.5 6.63 30.4 6.40 29.4 6.18 27.4 5.74
13 11.8 35.5 7.14 33.5 6.70 31.5 6.27 30.4 6.07 29.4 5.85 27.4 5.45
15 13.7 35.5 6.76 33.5 6.36 31.5 5.95 30.4 5.77 29.4 5.56 27.4 5.19
-13.7 -15 30.4 13.20 28.7 12.28 27.0 11.39 26.1 10.96 25.3 10.52 23.6 9.67
-11.8 -13 30.4 12.50 28.7 11.63 27.0 10.80 26.1 10.39 25.3 9.99 23.6 9.24
-9.8 -11 30.4 11.81 28.7 11.00 27.0 10.22 26.1 9.83 25.3 9.46 23.6 8.72
-9.5 -10 30.4 11.47 28.7 10.70 27.0 9.93 26.1 9.57 25.3 9.20 23.6 8.48
-8.5 -9.1 30.4 11.17 28.7 10.42 27.0 9.69 26.1 9.33 25.3 8.97 23.6 8.27
-7 -7.6 30.4 10.68 28.7 9.98 27.0 9.27 26.1 8.94 25.3 8.59 23.6 7.94
-5 -5.6 30.4 10.06 28.7 9.40 27.0 8.75 26.1 8.43 25.3 8.12 23.6 7.51
-3 -3.7 30.4 9.50 28.7 8.88 27.0 8.27 26.1 7.99 25.3 7.68 23.6 7.11
60%
0 -0.7 30.4 8.68 28.7 8.13 27.0 7.58 26.1 7.32 25.3 7.05 23.6 6.53
3 2.2 30.4 7.96 28.7 7.47 27.0 6.98 26.1 6.73 25.3 6.50 23.6 6.03
5 4.1 30.4 7.52 28.7 7.06 27.0 6.60 26.1 6.39 25.3 6.16 23.6 5.72
7 6 30.4 7.12 28.7 6.69 27.0 6.26 26.1 6.05 25.3 5.85 23.6 5.43
9 7.9 30.4 6.75 28.7 6.34 27.0 5.94 26.1 5.75 25.3 5.55 23.6 5.17
11 9.8 30.4 6.40 28.7 6.03 27.0 5.65 26.1 5.46 25.3 5.28 23.6 4.93
13 11.8 30.4 6.05 28.7 5.71 27.0 5.36 26.1 5.19 25.3 5.02 23.6 4.68
15 13.7 30.4 5.77 28.7 5.42 27.0 5.10 26.1 4.94 25.3 4.79 23.6 4.47
-13.7 -15 25.3 10.58 23.9 9.87 22.5 9.18 21.6 8.85 20.9 8.52 19.5 7.87
-11.8 -13 25.3 10.05 23.9 9.38 22.5 8.74 21.6 8.42 20.9 8.10 19.5 7.50
-9.8 -11 25.3 9.51 23.9 8.89 22.5 8.29 21.6 7.99 20.9 7.70 19.5 7.12
-9.5 -10 25.3 9.25 23.9 8.65 22.5 8.07 21.6 7.78 20.9 7.50 19.5 6.93
-8.5 -9.1 25.3 9.02 23.9 8.45 22.5 7.87 21.6 7.60 20.9 7.32 19.5 6.77
-7 -7.6 25.3 8.65 23.9 8.10 22.5 7.55 21.6 7.29 20.9 7.03 19.5 6.52
-5 -5.6 25.3 8.16 23.9 7.65 22.5 7.15 21.6 6.90 20.9 6.66 19.5 6.17
-3 -3.7 25.3 7.73 23.9 7.25 22.5 6.77 21.6 6.54 20.9 6.31 19.5 5.87
50%
0 -0.7 25.3 7.09 23.9 6.66 22.5 6.24 21.6 6.03 20.9 5.82 19.5 5.42
3 2.2 25.3 6.53 23.9 6.14 22.5 5.75 21.6 5.56 20.9 5.38 19.5 5.02
5 4.1 25.3 6.20 23.9 5.82 22.5 5.46 21.6 5.29 20.9 5.12 19.5 4.77
7 6 25.3 5.88 23.9 5.54 22.5 5.20 21.6 5.03 20.9 4.87 19.5 4.55
9 7.9 25.3 5.58 23.9 5.26 22.5 4.94 21.6 4.80 20.9 4.64 19.5 4.34
11 9.8 25.3 5.30 23.9 5.00 22.5 4.71 21.6 4.57 20.9 4.43 19.5 4.14
13 11.8 25.3 5.04 23.9 4.76 22.5 4.48 21.6 4.35 20.9 4.21 19.5 3.95
15 13.7 25.3 4.80 23.9 4.54 22.5 4.28 21.6 4.15 20.9 4.02 19.5 3.78
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

64
Mini TVR Individual 60Hz
Table 2-7.10: 4TVH0153BD000AA heating capacity
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 35.6 10.04 35.4 10.62 35.2 11.20 35.2 11.48 35.1 11.78 35.1 12.35
-11.8 -13 37.0 10.49 37.0 11.05 36.8 11.59 36.7 11.88 36.7 12.16 36.5 12.70
-9.8 -11 38.7 10.95 38.6 11.48 38.4 12.01 38.4 12.27 38.4 12.53 38.3 13.06
-9.5 -10 39.7 11.18 39.5 11.69 39.4 12.20 39.4 12.47 39.2 12.72 39.2 13.23
-8.5 -9.1 40.5 11.38 40.3 11.88 40.3 12.39 40.2 12.63 40.2 12.88 40.0 13.39
-7 -7.6 41.9 11.71 41.9 12.20 41.7 12.68 41.7 12.93 41.6 13.16 41.4 13.66
-5 -5.6 44.1 12.16 44.0 12.62 43.8 13.08 43.8 13.31 43.7 13.52 43.7 13.99
-3 -3.7 46.2 12.55 46.0 13.00 46.0 13.43 45.9 13.66 45.9 13.87 45.7 14.30
130%
0 -0.7 49.8 13.16 49.8 13.57 49.7 13.97 49.7 14.12 49.5 14.38 49.5 14.78
3 2.2 53.8 13.71 53.7 14.09 53.5 14.47 53.5 14.65 53.5 14.84 53.3 15.21
5 4.1 56.5 14.05 56.3 14.42 56.3 14.76 56.2 14.94 56.2 15.12 56.0 15.47
7 6 59.4 14.38 59.2 14.71 59.2 15.06 59.0 15.22 59.0 15.39 56.7 14.78
9 7.9 62.4 14.68 62.2 15.01 62.2 15.32 62.1 15.49 60.8 15.16 56.7 13.89
11 9.8 65.6 14.98 65.4 15.27 65.1 15.47 62.9 14.86 60.8 14.25 56.7 13.08
13 11.8 69.0 15.26 68.9 15.55 65.1 14.50 62.9 13.92 60.8 13.38 56.7 12.27

Part 2 - Outdoor Unit Engineering Data


15 13.7 72.4 15.52 69.2 14.73 65.1 13.66 62.9 13.13 60.8 12.60 56.7 11.58
-13.7 -15 35.4 10.82 35.2 11.35 35.1 11.88 35.1 12.16 35.1 12.42 34.9 12.95
-11.8 -13 36.8 11.23 36.8 11.74 36.7 12.26 36.7 12.52 36.5 12.77 36.5 13.28
-9.8 -11 38.6 11.66 38.4 12.14 38.4 12.63 38.3 12.88 38.3 13.11 38.1 13.61
-9.5 -10 39.5 11.88 39.4 12.35 39.2 12.81 39.2 13.06 39.2 13.29 39.0 13.77
-8.5 -9.1 40.3 12.06 40.2 12.52 40.2 12.98 40.0 13.21 40.0 13.46 39.8 13.92
-7 -7.6 41.7 12.37 41.7 12.81 41.6 13.26 41.6 13.49 41.4 13.71 41.4 14.15
-5 -5.6 44.0 12.77 43.8 13.20 43.6 13.62 43.6 13.84 43.6 14.05 43.5 14.47
-3 -3.7 46.0 13.15 46.0 13.56 45.9 13.95 45.9 14.15 45.7 14.37 45.7 14.76
120%
0 -0.7 49.7 13.71 49.7 14.09 49.5 14.45 49.5 14.65 49.4 14.83 49.4 15.21
3 2.2 53.7 14.22 53.5 14.56 53.5 14.91 53.3 15.09 53.3 15.26 52.2 15.17
5 4.1 56.4 14.53 56.2 14.86 56.2 15.19 56.0 15.36 56.0 15.52 52.2 14.25
7 6 59.2 14.83 59.2 15.14 59.1 15.45 58.1 15.24 56.2 14.61 52.2 13.41
9 7.9 62.2 15.13 62.1 15.42 60.0 14.91 58.1 14.32 56.2 13.74 52.2 12.62
11 9.8 65.4 15.39 63.8 15.13 60.0 14.02 58.1 13.47 56.2 12.93 52.2 11.89
13 11.8 67.8 15.24 63.8 14.18 60.0 13.15 58.1 12.65 56.2 12.16 52.2 11.18
15 13.7 67.8 14.35 63.8 13.36 60.0 12.40 58.1 11.92 56.2 11.46 52.2 10.56
-13.7 -15 35.2 11.60 35.1 12.09 34.9 12.57 34.9 12.82 34.9 13.06 34.8 13.54
-11.8 -13 36.7 11.99 36.7 12.45 36.5 12.92 36.5 13.15 36.3 13.38 36.3 13.85
-9.8 -11 38.4 12.37 38.3 12.82 38.3 13.26 38.1 13.49 38.1 13.71 38.1 14.15
-9.5 -10 39.4 12.57 39.2 13.00 39.0 13.44 39.0 13.66 39.0 13.87 38.9 14.30
-8.5 -9.1 40.2 12.73 40.0 13.16 40.0 13.59 39.8 13.81 39.8 14.02 39.8 12.78
-7 -7.6 41.6 13.03 41.6 13.43 41.4 13.84 41.4 14.05 41.4 14.25 41.3 14.66
-5 -5.6 43.8 13.39 43.7 13.79 43.5 14.17 43.5 14.37 43.5 14.56 43.3 14.96
-3 -3.7 45.9 13.74 45.9 14.10 45.7 14.48 45.7 14.66 45.6 14.84 45.6 15.22
110%
0 -0.7 49.5 14.25 49.5 14.60 49.4 14.94 49.4 15.11 49.4 15.29 47.9 14.99
3 2.2 53.5 14.73 53.3 15.04 53.3 15.36 53.2 15.50 51.4 14.88 47.9 13.64
5 4.1 56.2 15.01 56.2 15.32 55.1 15.17 53.2 14.56 51.4 13.99 47.9 12.83
7 6 59.0 15.29 58.6 15.39 55.1 14.25 53.2 13.69 51.4 13.15 47.9 12.07
9 7.9 62.1 15.54 58.6 14.46 55.1 13.41 53.2 12.88 51.4 12.37 47.9 11.38
11 9.8 62.1 14.61 58.6 13.61 55.1 12.62 53.2 12.14 51.4 11.66 47.9 10.74
13 11.8 62.1 13.71 58.6 12.77 55.1 11.86 53.2 11.41 51.4 10.97 47.9 10.11
15 13.7 62.1 12.17 58.6 12.04 55.1 11.20 53.2 10.77 51.4 10.37 47.9 9.57
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

65
Mini TVR Individual 60Hz
Table 2-7.10: 4TVH0153BD000AA heating capacity(continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 35.1 12.37 34.9 12.82 34.8 13.26 34.8 13.49 34.8 13.71 34.6 14.15
-11.8 -13 36.5 12.73 36.5 13.15 36.4 13.57 36.4 13.79 36.4 14.00 36.2 14.43
-9.8 -11 38.3 13.08 38.1 13.49 38.1 13.89 38.1 14.10 37.9 14.30 37.9 14.70
-9.5 -10 39.2 13.26 39.1 13.66 39.1 14.05 38.9 14.25 38.9 14.45 38.7 14.84
-8.5 -9.1 40.0 13.41 39.8 13.80 39.8 14.18 39.8 14.38 39.7 14.58 39.7 14.96
-7 -7.6 41.4 13.67 41.4 14.05 41.3 14.42 41.3 14.61 41.3 14.79 41.1 15.17
-5 -5.6 43.7 14.02 43.5 14.37 43.5 14.73 43.3 14.89 43.3 15.07 43.2 15.44
-3 -3.7 45.7 14.33 45.7 13.01 45.6 15.01 45.6 15.17 45.6 15.34 43.7 14.70
100%
0 -0.7 49.4 14.79 49.4 15.11 49.2 15.42 48.4 15.17 46.8 14.55 43.7 13.34
3 2.2 53.3 15.22 53.2 15.50 50.0 14.35 48.4 13.79 46.8 13.24 43.7 12.16
5 4.1 56.0 15.50 53.2 14.56 50.0 13.49 48.4 12.98 46.8 12.47 43.7 11.46
7 6 56.4 14.71 53.2 13.69 50.0 12.70 48.4 12.22 46.8 11.74 43.7 10.80
9 7.9 56.4 13.82 53.2 12.88 50.0 11.96 48.4 11.36 46.8 11.07 43.7 10.19
Mini TVR Individual Series Engineering Data Book

11 9.8 56.4 13.01 53.2 12.14 50.0 11.28 48.4 10.85 46.8 10.44 43.7 9.63
13 11.8 56.4 12.22 53.2 11.41 50.0 10.62 48.4 10.23 46.8 9.85 43.7 9.09
15 13.7 56.4 11.53 53.2 10.77 50.0 10.03 48.4 9.66 46.8 9.30 43.7 8.61
-13.7 -15 34.9 13.16 34.7 13.56 34.7 13.95 34.5 14.15 34.5 14.35 34.5 14.74
-11.8 -13 36.3 13.48 36.3 13.85 36.1 14.23 36.1 14.43 36.1 14.61 36.0 14.99
-9.8 -11 38.0 13.79 38.0 14.15 37.9 14.51 37.9 14.70 37.9 14.89 37.7 15.26
-9.5 -10 39.0 13.95 38.8 14.32 38.8 14.66 38.7 14.84 38.7 15.03 38.7 15.37
-8.5 -9.1 39.8 14.10 39.8 14.45 39.6 14.79 39.6 14.96 39.6 15.14 39.1 15.29
-7 -7.6 41.2 14.33 41.2 14.66 41.0 15.01 41.0 15.17 41.0 15.34 39.1 14.60
-5 -5.6 43.4 14.65 43.3 14.96 43.3 15.27 43.1 15.44 42.0 14.96 39.1 13.72
-3 -3.7 45.5 14.93 45.5 15.22 45.0 15.29 43.4 14.68 42.0 14.09 39.1 12.93
90%
0 -0.7 49.3 15.35 47.9 14.98 45.0 13.87 43.4 13.33 42.0 12.80 39.1 11.76
3 2.2 50.7 14.63 47.9 13.62 45.0 12.63 43.4 12.16 42.0 11.68 39.1 10.75
5 4.1 50.7 13.76 47.9 12.81 45.0 11.91 43.4 11.45 42.0 11.02 39.1 10.14
7 6 50.7 12.93 47.9 12.07 45.0 11.22 43.4 10.80 42.0 10.39 39.1 9.58
9 7.9 50.7 12.19 47.9 11.36 45.0 10.57 43.4 10.19 42.0 9.81 39.1 9.06
11 9.8 50.7 11.48 47.9 10.72 45.0 10.00 43.4 9.63 42.0 9.27 39.1 8.58
13 11.8 50.7 10.80 47.9 10.11 45.0 9.42 43.4 9.09 42.0 8.76 39.1 8.10
15 13.7 50.7 10.21 47.9 9.55 45.0 8.92 43.4 8.61 42.0 8.30 39.1 7.69
-13.7 -15 34.8 13.94 34.6 14.28 34.6 14.65 34.6 14.81 34.4 14.99 34.4 15.35
-11.8 -13 36.2 14.22 36.2 14.56 36.0 14.89 36.0 15.06 36.0 15.24 34.9 14.83
-9.8 -11 37.9 14.50 37.9 14.83 37.8 15.16 37.8 15.31 37.5 15.27 34.9 14.00
-9.5 -10 38.9 14.65 38.7 14.96 38.7 15.27 38.7 15.44 37.5 14.83 34.9 13.59
-8.5 -9.1 39.7 14.78 36.9 15.09 39.5 15.39 38.7 15.04 37.5 14.43 34.9 13.23
-7 -7.6 41.1 14.99 41.1 15.29 40.0 14.96 38.7 14.37 37.5 13.79 34.9 12.65
-5 -5.6 43.3 15.26 42.5 15.17 40.0 14.05 38.7 13.51 37.5 12.96 34.9 11.91
-3 -3.7 45.1 15.34 42.5 14.28 40.0 13.23 38.7 12.73 37.5 12.22 34.9 11.25
80%
0 -0.7 45.1 13.92 42.5 12.96 40.0 12.04 38.7 11.59 37.5 11.13 34.9 10.26
3 2.2 45.1 12.68 42.5 11.83 40.0 11.00 38.7 10.59 37.5 10.19 34.9 9.40
5 4.1 45.1 11.94 42.5 11.15 40.0 10.37 38.7 9.99 37.5 9.63 34.9 8.89
7 6 45.1 11.25 42.5 10.52 40.0 9.80 38.7 9.45 37.5 9.10 34.9 8.41
9 7.9 45.1 10.62 42.5 9.93 40.0 9.25 38.7 8.92 37.5 8.61 34.9 7.97
11 9.8 45.1 10.03 42.5 9.38 40.0 8.76 38.7 8.44 37.5 8.15 34.9 7.55
13 11.8 45.1 9.45 42.5 8.86 40.0 8.28 38.7 7.98 37.5 7.70 34.9 7.14
15 13.7 45.1 8.94 42.5 8.39 40.0 7.85 38.7 7.57 37.5 7.31 34.9 6.80
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

66
Mini TVR Individual 60Hz
Table 2-7.10: 4TVH0153BD000AA heating capacity(continued)
Indoor temperature(°C WB)
Outdoor Air
Combination 16 18 20 21 22 24
temperature
(%) TC PI TC PI TC PI TC PI TC PI TC PI
°C DB °C WB kW kW kW kW kW kW kW kW kW kW kW kW
-13.7 -15 34.5 14.71 34.4 15.02 34.4 15.34 33.7 15.11 32.6 14.50 30.4 13.29
-11.8 -13 35.9 14.96 35.9 15.26 35.0 14.89 33.7 14.32 32.6 13.74 30.4 12.60
-9.8 -11 37.7 15.21 37.2 15.19 35.0 14.07 33.7 13.52 32.6 12.98 30.4 11.92
-9.5 -10 38.6 15.34 37.2 14.74 35.0 13.66 33.7 13.13 32.6 12.62 30.4 11.59
-8.5 -9.1 39.4 15.42 37.2 14.35 35.0 13.29 33.7 12.78 32.6 12.29 30.4 11.30
-7 -7.6 39.4 14.73 37.2 13.70 35.0 12.72 33.7 12.24 32.6 11.76 30.4 10.82
-5 -5.6 39.4 13.84 37.2 12.90 35.0 11.97 33.7 11.51 32.6 13.60 30.4 10.21
-3 -3.7 39.4 13.03 37.2 12.16 35.0 11.30 33.7 10.87 32.6 10.46 30.4 9.65
70%
0 -0.7 39.4 11.86 37.2 11.08 35.0 10.31 33.7 9.93 32.6 9.57 30.4 8.84
3 2.2 39.4 10.84 37.2 10.14 35.0 9.45 33.7 9.10 32.6 8.77 30.4 8.11
5 4.1 39.4 10.23 37.2 9.57 35.0 8.94 33.7 8.61 32.6 8.30 30.4 7.69
7 6 39.4 9.66 37.2 9.05 35.0 8.44 33.7 8.15 32.6 7.87 30.4 7.29
9 7.9 39.4 9.14 37.2 8.56 35.0 8.00 33.7 7.72 32.6 7.45 30.4 6.91
11 9.8 39.4 8.64 37.2 8.10 35.0 7.59 33.7 7.32 32.6 7.08 30.4 6.56
13 11.8 39.4 8.16 37.2 7.67 35.0 7.17 33.7 6.94 32.6 6.70 30.4 6.23

Part 2 - Outdoor Unit Engineering Data


15 13.7 39.4 7.73 37.2 7.27 35.0 6.81 33.7 6.60 32.6 6.37 30.4 5.94
-13.7 -15 33.8 15.11 31.9 14.05 30.0 13.03 29.0 12.53 28.1 12.04 26.2 11.07
-11.8 -13 33.8 14.30 31.9 13.31 30.0 12.35 29.0 11.89 28.1 11.43 26.2 10.57
-9.8 -11 33.8 13.51 31.9 12.58 30.0 11.69 29.0 11.25 28.1 10.82 26.2 9.98
-9.5 -10 33.8 13.13 31.9 12.24 30.0 11.36 29.0 10.95 28.1 10.52 26.2 9.70
-8.5 -9.1 33.8 12.78 31.9 11.92 30.0 11.08 29.0 10.67 28.1 10.26 26.2 9.47
-7 -7.6 33.8 12.22 31.9 11.41 30.0 10.60 29.0 10.23 28.1 9.83 26.2 9.09
-5 -5.6 33.8 11.51 31.9 10.75 30.0 10.01 29.0 9.65 28.1 9.28 26.2 8.59
-3 -3.7 33.8 10.87 31.9 10.16 30.0 9.47 29.0 9.14 28.1 8.79 26.2 8.13
60%
0 -0.7 33.8 9.93 31.9 9.30 30.0 8.68 29.0 8.38 28.1 8.06 26.2 7.47
3 2.2 33.8 9.10 31.9 8.54 30.0 7.98 29.0 7.70 28.1 7.44 26.2 6.89
5 4.1 33.8 8.61 31.9 8.08 30.0 7.55 29.0 7.31 28.1 7.04 26.2 6.55
7 6 33.8 8.15 31.9 7.65 30.0 7.16 29.0 6.93 28.1 6.70 26.2 6.22
9 7.9 33.8 7.72 31.9 7.26 30.0 6.79 29.0 6.58 28.1 6.35 26.2 5.92
11 9.8 33.8 7.32 31.9 6.89 30.0 6.46 29.0 6.25 28.1 6.04 26.2 5.64
13 11.8 33.8 6.93 31.9 6.53 30.0 6.13 29.0 5.94 28.1 5.74 26.2 5.36
15 13.7 33.8 6.60 31.9 6.20 30.0 5.84 29.0 5.66 28.1 5.48 26.2 5.11
-13.7 -15 28.2 12.11 26.6 11.30 25.0 10.51 24.1 10.13 23.3 9.75 21.7 9.01
-11.8 -13 28.2 11.49 26.6 10.74 25.0 9.99 24.1 9.63 23.3 9.27 21.7 8.58
-9.8 -11 28.2 10.89 26.6 10.18 25.0 9.48 24.1 9.14 23.3 8.81 21.7 8.15
-9.5 -10 28.2 10.59 26.6 9.90 25.0 9.24 24.1 8.91 23.3 8.58 21.7 7.93
-8.5 -9.1 28.2 10.32 26.6 9.66 25.0 9.01 24.1 8.69 23.3 8.38 21.7 7.75
-7 -7.6 28.2 9.90 26.6 9.27 25.0 8.64 24.1 8.35 23.3 8.05 21.7 7.45
-5 -5.6 28.2 9.33 26.6 8.76 25.0 8.18 24.1 7.90 23.3 7.62 21.7 7.06
-3 -3.7 28.2 8.84 26.6 8.30 25.0 7.75 24.1 7.49 23.3 7.22 21.7 6.71
50%
0 -0.7 28.2 8.11 26.6 7.62 25.0 7.14 24.1 6.89 23.3 6.66 21.7 6.20
3 2.2 28.2 7.47 26.6 7.03 25.0 6.58 24.1 6.37 23.3 6.15 21.7 5.74
5 4.1 28.2 7.09 26.6 6.66 25.0 6.25 24.1 6.05 23.3 5.85 21.7 5.46
7 6 28.2 6.73 26.6 6.33 25.0 5.95 24.1 5.76 23.3 5.57 21.7 5.21
9 7.9 28.2 6.38 26.6 6.02 25.0 5.66 24.1 5.49 23.3 5.31 21.7 4.96
11 9.8 28.2 6.07 26.6 5.72 25.0 5.39 24.1 5.23 23.3 5.06 21.7 4.73
13 11.8 28.2 5.77 26.6 5.44 25.0 5.13 24.1 4.98 23.3 4.82 21.7 4.52
15 13.7 28.2 5.49 26.6 5.20 25.0 4.90 24.1 4.75 23.3 4.60 21.7 4.32
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (compressor + outdoor fan motor) (kW)
Notes:
1. Shaded cells indicate rating condition.

67
Mini TVR Individual 60Hz
7.3 Capacity Correction Factors for Piping Length and Level Difference
Figure 2-7.1: Rate of change in cooling capacity Figure 2-7.2: Rate of change in heating capacity

0.90
H(m) H(m)

0.87
0.85
0.84

0.81

0.97

0.96
1.0
0.92
50
50
40
0.95

40
30
0.97

30
20
1.0

20

1.0
10
0 10
10 20 30 40 50 60 70 80 90 100 110 120 0
L(m)
10 20 30 40 50 60 70 80 90 100 110 120 L(m)
0
-10 0
1.0

-20 -10
0.97

1.0
-30 -20
0.95

-40 -30
0.87
0.92
0.90

0.85
0.84

-40

0.96
1.0

0.97
Mini TVR Individual Series Engineering Data Book

Notes:
1. The horizontal axis shows equivalent length of piping between farthest indoor unit and first outdoor branch joint; the vertical axis shows the largest level
difference between indoor unit and outdoor unit. For level differences, positive values indicate that the outdoor unit is above the indoor unit, negative
values indicate that the outdoor unit is below the indoor unit.
2. These figures illustrate the rate of change in capacity of a system with only standard indoor units at maximum load (with the thermostat set to maximum)
under standard conditions. Under partial load conditions there is only a minor deviation from the rate of change in capacity shown in these figures.
3. The capacity of the system is either the total capacity of the indoor units obtained from indoor unit capacity tables or the corrected capacity of the
outdoor units as per the calculations below, whichever is smaller.

Corrected capacity of Capacity of outdoor units obtained from outdoor unit Capacity
= x
outdoor units capacity tables at the combination ratio correction factor

68
Mini TVR Individual 60Hz
7.4 Capacity Correction Factors for Frost Accumulation
The heating capacity tables do not take account of the reduction in capacity when frost has accumulated or while the
defrosting operation is in progress. If snow has accumulated against the outside surface of the outdoor unit heat
exchanger heating capacity is reduced. The reduction in heating capacity is dependent on a number of factors including
the outdoor temperature, the relative humidity and the amount of frosting which has occurred.

Corrected heating capacity values, which take these factors into account, can be calculated as follows, using the correction
factors for frost accumulation given in Table 2-7.11:

Corrected heating capacity = Value given in outdoor heating capacity table × Correction factor for frost accumulation

Table 2-7.11: Correction factor for frost accumulation


Heat exchanger inlet port temperature (°C / RH 85%) -7 -5 -2 0 2 5 7
Correction factor for frost accumulation 0.94 0.93 0.89 0.84 0.83 0.91 1.00

Corrected heating capacities express the heating capacity over the heating/defrosting cycle shown in Figure 2-7.3.
Figure 2-7.3: Defrosting cycle

Part 2 - Outdoor Unit Engineering Data


Defrosting operation Defrosting operation
Heating capacity

0 time
1 cycle

69
Mini TVR Individual 60Hz
8 Operating Limits
Table 2-8.1: 7/8/9HP operating limits
Outdoor Room
Mode
temperature temperature
Cooling operation -15℃~46℃ 21℃~32℃
Heating operating -15℃~24℃ 0℃~28℃

Table 2-8.2: 14/16HP operating limits


Outdoor Room
Mode
temperature temperature
Cooling operation -5℃~48℃ 21℃~32℃
Heating operating -15℃~24℃ 0℃~28℃

Notes:
Mini TVR Individual Series Engineering Data Book

1. If air conditioner is used outside the above conditions, it may cause the unit to function abnormally;
2. The phenomenon is normal that the surface of air conditioning may condense water when the relative larger humidity in room, please close the door and
window;
3. Optimum performance will be achieved within these operating temperature range.

70
Mini TVR Individual 60Hz
9 Sound Levels
9.1 Overall
Table 2-9.1: Sound pressure level
Model dB(A)
4TVH0068BD000AA 59
4TVH0076BD000AA 59
4TVH0089BD000AA 60
4TVH0136BD000AA 62
4TVH0153BD000AA 62
Notes:
1. Sound pressure level is measured at a position 1000mm in front of the unit and (H+1000)/2mm above the floor in a semi-anechoic chamber. During in-situ
operation, sound pressure levels may be higher as a result of ambient noise.

Figure 2-9.1: Sound pressure level measurement (unit: mm)

Front
1000

Part 2 - Outdoor Unit Engineering Data


(H+1000)
2

9.2 Octave Band Levels

Figure 2-9.2 7/8HP octave band level Figure 2-9.3 9HP octave band level

70 70

60 60

50 50

40 40

30 30

20 20
Audibility limits of Audibility limits of
continuous white sound continuous white sound

63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)

71
Mini TVR Individual 60Hz
Figure 2-9.4 14/16HP octave band level
70

60

50

40

30

20
Audibility limits of
continuous white sound

63 125 250 500 1000 2000 4000 8000


Octave band center frequency (Hz)
Mini TVR Individual Series Engineering Data Book

72
Mini TVR Individual 60Hz
10 Accessories
10.1 Standard Accessories
Table 2-10.1: 7/8/9HP standard accessories
Name Shape Quantity
Installation manual of outdoor unit 1
Operation manual of outdoor unit 1
Operation manual of indoor unit 1
Installation manual of branch pipes 1

Water outlet connection pipe 1

Straight screwdriver 1

Sealing ring 1

Waterproof chassis cover 2

Part 2 - Outdoor Unit Engineering Data


Connection pipe (26kW) 1

Connection pipe (26kW) 1

Table 2-10.2: 14/16HP standard accessories


Name Shape Quantity
Installation manual of outdoor unit 1
Operation manual of outdoor unit 1
Operation manual of indoor unit 1
Installation manual of branch pipes 1
Straight screwdriver 1
Connection pipe 1

Connection pipe 1

10.2 Optional Accessories


Table 2-10.3: Optional accessories
Gross/net
Optional accessories Model name Packing Size (mm) Function
Weight (kg)
TODK002HP 255×150×185 1.5/1.2
Branch Joint of outdoor
TODK003HP 345×160×285 3.4/2.4
unit
TODK004HP 475×165×300 4.8/3.6 Distribute the refrigerant to
TRDK056HP 290×105×100 0.4/0.3 Indoor Units and balance the
TRDK112HP 290×105×100 0.6/0.4 resistance between each
Branch Joint of indoor
TRDK225HP 310×130×125 0.9/0.6 outdoor unit.
unit
TRDK314HP 350×170×180 1.5/1.1
TRDK768HP 365×195×215 1.9/1.4

73
Mini TVR Individual 60Hz
Table 2-10.4: Other optional accessories
Optional accessories Model name Function
DPA51CM44 To stop the air-conditioner running in case of bad power supply such
Three phase electricity power
or as Phase Error, Over-voltage, Under-voltage lose, phase lost and
protector
HWUA/DPB71CM48 phase sequence inverse. Thus to protect the equipment.
Digital ammeter (WHM) DTS634/DT636 Electricity Charge monitor
Max. 4 groups indoor units can be connected to one branch box. It is
One to four branch box FQT4-01
only available for 20/22.4/26kW models.
Mini TVR Individual Series Engineering Data Book

74
-I Mini TVR Individual 60Hz

Part 3
System Design and
Installation
1 Preface to Part 3 ................................................................................... 76

2 Unit Placement and Installation ............................................................ 77

Part 3 - System Design and Installation


3 Refrigerant Piping Design ...................................................................... 81

4 Refrigerant Piping Installation ............................................................... 89

5 Drain Piping ........................................................................................ 100

6 Insulation ............................................................................................ 104

7 Charging Refrigerant ........................................................................... 106

8 Electrical Wiring .................................................................................. 108

9 Installation in Areas of High Salinity .................................................... 111

10 Commissioning.................................................................................. 112

11 Appendix to Part 3 – System Commissioning Report ......................... 114

75
Mini TVR Individual 60Hz
1 Preface to Part 3
1.1 Notes for Installers Boxes
The information contained in this Engineering Data Book may primarily be of use during the system design stage of a Trane
Mini TVR Individual Series VRF project. Additional important information which may primarily be of use during field
installation has been placed in boxes, such as the example below, titled “Notes for installers”.

Notes for installers 


 Notes for installers boxes contain important information which may primarily be of use during field installation,
rather than during desk-based system design.

1.2 Definitions
In this Engineering Data Book, the term “applicable legislation” refers to all national, local and other laws, standards, codes,
Mini TVR Individual Series Engineering Data Book

rules, regulations and other legislation that apply in a given situation.

1.3 Precautions
All system installation including installation of piping and electrical works must only be carried out by competent and
suitably qualified, certified and accredited professionals and in accordance with all applicable legislation.

76
-I Mini TVR Individual 60Hz
2 Unit Placement and Installation
2.1 Outdoor Units
2.1.1 Placement considerations
Placement of outdoor units should take account of the following considerations:
 Air conditioners should not be exposed to direct radiation from a high-temperature heat source.
 Air conditioners should not be installed in positions where dust or dirt may affect heat exchangers.
 Air conditioners should not be installed in locations where exposure to oil or to corrosive or harmful gases, such as
acidic or alkaline gases, may occur.
 Air conditioners should not be installed in locations where exposure to salinity may occur unless the anti-corrosion
treatment for high-salinity areas customization option has been added and the precautions described in Part 3, 9
“Installation in Areas of High Salinity” are taken.
 Outdoor units should be installed in well-drained, well-ventilated positions that are as close as possible to the indoor
units.

2.1.2 Spacing
Outdoor units must be spaced such that sufficient air may flow through each unit. Sufficient airflow across heat

Part 3 - System Design and Installation


exchangers is essential for outdoor units to function properly. Figures 3-2.1 to 3-2.6 show spacing requirements in three
different scenarios.
Figure 3-2.1: 7/8/9HP single unit installation (unit: mm)
(Wall or obstacle)

>600
Air inlet
> 300

>300
Maintain the electric
wire and pipeline
Air inlet
>600
>3000

Air outlet

Figure 3-2.2: 7/8/9HP parallel connect the two units or above (unit: mm)

>300
>600 >600

>3000

Figure 3-2.3: 7/8/9HP parallel connect the front with rear sides (unit: mm)
>600

>3000 >1000 >6000 >4000 >300

77
Mini TVR Individual 60Hz
Figure 3-2.4: 14/16HP single unit installation (unit: mm)

> 600
(Wall or obstacle)

Air inlet

> 400
>400 Maintain
channel
Air inlet >600

> 4000

Air outlet

Figure 3-2.5: 14/16HP parallel connect the two units or above (unit: mm)
Mini TVR Individual Series Engineering Data Book

>400
>600

>4000

Figure 3-2.6: 14/16HP parallel connect the front with rear sides (unit: mm)

> 600

>4000 >1000 >8000 >6000 >400

2.1.3 Base structures


Outdoor unit base structure design should take account of the following considerations:
 A solid base prevents excess vibration and noise. Outdoor unit bases should be constructed on solid ground or on
structures of sufficient strength to support the units’ weight.
 Bases should be at least 200mm high to provide sufficient access for installation of piping.
 Either steel or concrete bases may be suitable.
 A typical concrete base design is shown in Figure 3-2.7. A typical concrete specification is 1 part cement, 2 parts sand
and 6 parts crushed stone with Φ10mm steel reinforcing bar. The edges of the base should be chamfered.
 To ensure that all contact points are equally secure, bases should be completely level. Base design should ensure that
the points on the units’ bases designed for weight-bearing support are fully supported.
 A drainage ditch should be provided to allow drainage of condensate that may form on the heat exchangers when
the units are running in heating mode. The drainage should ensure that condensate is directed away from roadways
78
-I Mini TVR Individual 60Hz
and footpaths, especially in locations where the climate is such that condensate may freeze.

Figure 3-2.7: Outdoor unit typical concrete base structure design (unit: mm)
Outdoor unit

Φ10 Expansion bolt

Rubber anti-vibration pads

Solid ground or roof


Concrete base h≥200mm

≥ 200mm

≥150mm

Part 3 - System Design and Installation


2.1.4 Centralized drainage
When centralized drainage is required, install two waterproof covers for the chassis, as shown in Figure 3-2.8. Install the
water outlet union pipe and sealing ring on the chassis, and then connect the drainage pipe to complete centralized
drainage installation.

Figure 3-2.8: Centralized drainage


Sealing ring for the
Waterproof chassis cover water outlet union pipe

2.1.5 Acceptance and unpacking

Notes for installers 


 When units are delivered check whether any damage occurred during shipment. If there is damage to the
surface or outside of a unit, submit a written report to the shipping company.
 Check that the model, specifications and quantity of the units delivered are as ordered.
 Check that all accessories ordered have been included. Retain the Owner's Manual for future reference.

2.1.6 Hoisting

Notes for installers 


 Do not remove any packaging before hoisting. If units are not packaged or if the packaging is damaged, use
suitable boards or packing material to protect the units.
 Hoist one unit at a time, using two ropes to ensure stability.
 Keep units upright during hoisting, ensuring that the angle to the vertical does not exceed 30°.

79
Mini TVR Individual 60Hz
2.2 Indoor Units
2.2.1 Placement considerations
Placement of indoor units should take account of the following considerations:
 Sufficient space for drain piping and for access during servicing and maintenance should be allowed.
 To ensure a good cooling/heating effect, short-circuit ventilation (where outlet air returns quickly to a unit’s air inlet)
should be avoided.
 To prevent excessive noise or vibration during operation, suspension rods or other weight-bearing fixings should
typically be able to bear twice the unit’s weight.

Notes for installers 


 Before installing an indoor unit, check that the model to be installed is as specified in the construction drawings
and confirm the correct orientation of the unit.
 Ensure that units are installed at the correct height.
Mini TVR Individual Series Engineering Data Book

 To allow smooth condensate drainage and to ensure unit stability (to prevent excessive noise or vibration),
ensure that units are level to within 1° of the horizontal. If a unit is not level to within 1° of the horizontal, water
leakage or abnormal vibration/noise may occur.

80
-I Mini TVR Individual 60Hz
3 Refrigerant Piping Design
3.1 Design Considerations
Refrigerant piping design should take account of the following considerations:
 The amount of brazing required should be kept to a minimum.
 On the two inside sides of the first indoor branch joint (“A” in Figures 3-3.4 and Figure 3-3.5) the system should, as far
as possible, be equal in terms of number of units, total capacities and total piping lengths.

3.2 Material Specification


Only seamless phosphorus-deoxidized copper piping that complies with all applicable legislation should be used. Temper
grades and minimum thicknesses for different diameters of piping are specified in Table 3-3.1.

Table 3-3.1: Piping temper and thickness


Piping outer diameter 1 Minimum thickness
Temper
(mm) (mm)
Ф6.35 0.8
Ф9.53 0.8
O
Ф12.7 0.8
(annealed)

Part 3 - System Design and Installation


Ф15.9 1.0
Ф19.1 1.0
Ф22.2 1.2
Ф25.4 1.2
Ф28.6 1.3
Ф31.8 1/2H 1.5
Ф38.1 (half hard) 1.5
Ф41.3 1.5
Ф44.5 1.5
Ф54.0 1.8
Notes:
1. O: coiled piping;
2. 1/2H: straight piping.

3.3 Valve instruction


A multi-direction space is available for connecting pipes and wiring in various installation sites.

Figure 3-3.1: 7/8/9HP Valve instruction

81
Mini TVR Individual 60Hz
Figure 3-3.2: 14/16HP Valve instruction
Mini TVR Individual Series Engineering Data Book

Table 3-3.2: Pipe diameter of outdoor unit's connector


Capacity of indoor unit
Gas pipe (mm) Liquid pipe (mm)
(kW)
20/22.4kW Ф9.53 Ф19.1
26kW Ф9.53 Ф22.2
40kW Ф12.7 Ф22.2
45kW Ф12.7 Ф25.4
Notes:
1. Connecting pipe from right side: cut the side hole of the pipe-outlet plate selectively. It is suggested to cut a piece of metal plate below to avoid the mouse
come and destroy the machine wiring body.
2. Connecting pipe from front side: cut the frontal hole of the pipe-outlet plate selectively. It is suggested to cut a piece of metal plate right side to avoid the
mouse come and destroy the machine wiring body.
3. Connecting wiring cable: the strong and weak electrical wire should be out through the two plastic holes of the pipe-outlet plate, and binded with gas and
liquid pipe together.

3.4 The Permitted Piping Lengths and Level Differences


The piping length and level difference requirements that apply are summarized in Table 3-3.3 and are fully described as
follows (refer to Figure 3-3.4 and Figure 3-3.5):
1. Requirement 1: The total length of piping in one refrigerant system should not exceed 150m.
2. Requirement 2: The piping between the farthest indoor unit (N6) and the outdoor unit should not exceed 100m
(actual length) and 110m (equivalent length). (The equivalent length of each branch joint is 0.5m.)
3. Requirement 3: The piping between the farthest indoor unit (N6) and first indoor branch joint (A) should not exceed
40m in length.
4. Requirement 4: Indoor auxiliary pipes (a to f) should not exceed 15m in
Figure 3-3.3: Oil return bend (unit: mm)
length.
5. Requirement 5: The largest level difference between indoor unit and outdoor
unit should not exceed 50m (if the outdoor unit is above) or 40m (if the
outdoor unit is below). Additionally: If the outdoor unit is above and the level 300
difference is greater than 20m, it is recommended that an oil return bend with or more
dimensions as specified in Figure 3-3.3 is set every 10m in the gas pipe of the
300
main pipe; or more
6. Requirement 6: The largest level difference between indoor units should not
exceed 15m.
82
Part 3 - System Design and Installation

83
Mini TVR Individual 60Hz
-I
Mini TVR Individual 60Hz
Figure 3-3.4: The first connecting method

Outdoor unit

Drop HEIGHT between indoor unit and uutdoor unit

Pipe Length(from the nearest branch pipe equivalent length

a
L1
A

The first line Branch Pipe Maximum pipe equivalent length

Indoor Unit to Indoor


L2

Unit Drop Heihgt


(from the first line branch pipe) Maximum pipe equivalent length
L3 L4 L5
B C D E
b c d e f
Mini TVR Individual Series Engineering Data Book

Indoor Unit

Figure 3-3.5: The second connecting method

Outdoor unit
N1
Indoor auxiliary pipe
Level difference between indoor unit and outdoor unit

a N2
Piping between farthest indoor unit and
B

Level difference between indoor units


outdoor unit
b
L1 L2 Piping between farthest indoor unit and
A first indoor branch join

L3
L4 c N3
The first line Branch Pipe D N4
C d
Legend L5
L1 Main pipe
L2 to L5 Indoor main pipes E f
a to f Indoor auxiliary pipes e N5 N6
A to E Indoor branch joints

Indoor unit
Notes:
The distance between the first branch to the last indoor unit is more than 15m, choose the second connect method

Table 3-3.3: Summary of permitted refrigerant piping lengths and level differences
1 Permitted value
Total piping length Piping
20-26kW 40-45kW
Total Pipe Length(Actual) ≤120m ≤250m L1+L2+L3+L4+L5+a+b+c+d+e+f
Actual Length ≤60m ≤100m
2 L1+L2+L3+L4+L5+f(The first connecting method) or
Maximum Piping Equivalent
Pipe ≤70m ≤120m L1+L3+L5+f(The second connecting method)
Length
Length
Pipe Length (from the first branch to the L2+L3+L4+L5+f(The first connecting method) or
3 ≤20m ≤40m
furthest IDU) L3+L5+f(The second connecting method)
Pipe Length(IDU to the nearest branch) ≤15m ≤15m a,b,c,d,e,f
Level difference ODU up ≤30m ≤30m ----
Level 4
between IDU~ODU ODU down ≤20m ≤20m ----
difference 5
Level difference between IDU~IDU ≤8m ≤8m ----
Notes:
1. Refer to Requirement 1, above.
2. Refer to Requirement 2, above.
3. Refer to Requirement 3, above.
4. Refer to Requirement 5, above.
5. Refer to Requirement 6, above

84
-I Mini TVR Individual 60Hz
3.5 Selecting Piping Diameters
Tables 3-3.4 to 3-3.6 below, specify the required pipe diameters for the indoor and outdoor piping. The main pipe (L1) and
first indoor branch joint (A) should be sized according to whichever of Tables 3-3.4 and 3-3.5 indicates the larger size.

Figure 3-3.6: Selecting piping diameters

Outdoor Unit

N1
(56)
a
L2 intdoor Units
L1 B
A b N2
(56) N3
L3 (45)
L4 c
D N4
C d (45)
L5
f
E

Part 3 - System Design and Installation


Legend e
N5 N6
L1 Main pipe Figures in
(45) (56)
L2 to L5 Indoor main pipes parentheses indicate
a to f Indoor auxiliary pipes indoor unit capacity
A to E Indoor branch joints indexes.

1
Table 3-3.4: Main pipe (L1), indoor main pipes (L2 to L5) and indoor branch joint kits
Capacity of indoor unit (A×10) Gas pipe (mm) Liquid pipe (mm) Branch joint kit
A<166 Φ15.9 Φ9.53 TRDK056HP
166≤A<230 Φ19.1 Φ9.53 TRDK056HP
230≤A<330 Φ22.2 Φ9.53 TRDK112HP
330≤A Φ25.4 Φ12.7 TRDK112HP
Notes:
1. The main pipe (L1) and first indoor branch joint (A) should be sized according to whichever of Tables 3-3.4 and 3-3.5
indicates the larger size.

1
Table 3-3.5: Main pipe (L1) and first indoor branch joint (A)
Equivalent length of all liquid pipes and gas pipes < 90m Equivalent length of all liquid pipes and gas pipes ≥ 90m
Capacity of
outdoor unit Liquid pipe Liquid pipe
Gas pipe (mm) Branch joint kit Gas pipe (mm) Branch joint kit
(mm) (mm)
20/22.4kW Φ19.1 Φ9.53 TRDK056HP Φ22.2 Φ9.53 TRDK112HP
26kW Φ22.2 Φ9.53 TRDK112HP Φ25.4 Φ9.53 TRDK112HP
40kW Φ22.2 Φ12.7 TRDK112HP Φ25.4 Φ12.7 TRDK112HP
45kW Φ25.4 Φ12.7 TRDK112HP Φ28.6 Φ12.7 TRDK225HP
20/22.4kW Φ19.1 Φ9.53 TRDK056HP Φ22.2 Φ9.53 TRDK112HP
Notes:
1. The main pipe (L1) and first indoor branch joint (A) should be sized according to whichever of Tables 3-3.4 and 3-3.5 indicates the larger size.

Table 3-3.6: Indoor auxiliary pipes (a to f)


Capacity of indoor unit
Gas pipe (mm) Liquid pipe (mm)
(kW)
A≤4.5 Φ12.7 Φ6.35
A≥5.6 Φ15.9 Φ9.53

85
Mini TVR Individual 60Hz
3.6 Refrigerant Piping Selection Example
The example below illustrates the piping selection procedure for a system consisting of one outdoor unit (26kW) and 6
indoor units. The system's equivalent length of all liquid pipes and gas pipes is in excess of 90m.

Figure 3-3.7: Refrigerant piping selection example

Outdoor Unit

N1
(56)
a
L2 intdoor Units
L1 B
A b N2
Legend
(56) N3
L1 Main pipe
L2 to L5 Indoor main pipes L3 (45)
a to f Indoor auxiliary pipes L4 c
D N4
Mini TVR Individual Series Engineering Data Book

A to E Indoor branch joints C d (45)


Figures in parentheses indicate indoor unit L5
capacity indexes. f
E
e
N5 N6
(45) (56)

Step 1: Select indoor auxiliary pipes


 Indoor units N1, N2 and N6 are of capacity 5.6kW. Refer to Table 3-3.6. Indoor auxiliary pipe a, b and f is Φ15.9 /
Φ9.53.
 Indoor units N3 to N5 are of capacity 4.5kW. Refer to Table 3-3.6. Indoor auxiliary pipes c to e is Φ12.7 / Φ6.35.

Step 2: Select indoor main pipes and indoor branch joints B to E


 The indoor units (N1 and N2) downstream of indoor branch joint B have total capacity of 5.6+ 5.6 = 11.2kW. Refer to
Table 3-3.4. Indoor main pipe L2 is Φ15.9 / Φ9.53. Indoor branch joint B is TRDK056HP.
 The indoor units (N3 and N4) downstream of indoor branch joint D have total capacity of 4.5+ 4.5 = 9kW. Refer to Table
3-3.4. Indoor main pipe L4 is Φ15.9 / Φ9.53. Indoor branch joint D is TRDK056HP.
 The indoor units (N5 and N6) downstream of indoor branch joint E have total capacity of 4.5+ 5.6 = 10.1kW. Refer to
Table 3-3.4. Indoor main pipe L5 is Φ15.9 / Φ9.53. Indoor branch joint E is TRDK056HP.
 The indoor units (N3 to N6) downstream of indoor branch joint E have total capacity of 4.5 x 3+ 5.6 = 19.1kW. Refer to
Table 3-3.4. Indoor main pipe L3 is Φ19.1 / Φ9.53. Indoor branch joint E is TRDK056HP.

Step 3: Select main pipe and indoor branch joint A


 The indoor units (N1 to N6) downstream of indoor branch joint A have total capacity of 4.5 x 3+ 5.6 x 3 = 30.3kW. The
system's equivalent length of all liquid pipes and gas pipes is in excess of 90m. The capacity of the outdoor unit is
26kW. Refer to Tables 3-3.4 and 3-3.5. Main pipe L1 is the larger of Φ22.2 / Φ9.53 and Φ25.4 / Φ9.53, hence Φ25.4 /
Φ9.53 Indoor branch joint A is TRDK112HP.

3.7 Branch Joints


Branch joint design should take account of the following:
 U-shaped branch joints should be used – tee joints are not suitable. Branch joint dimensions are given in Tables 3-3.7.
 To ensure even distribution of refrigerant, branch joints should not be installed within 500mm of a 90° bend, another
branch joint or the straight section of piping leading to an indoor unit, with the minimum 500mm being measured
from the point where the branch joint is connected to the piping, as shown in Figure 3-3.8.

86
-I Mini TVR Individual 60Hz
Figure 3-3.8: Branch joint spacing and separation from bends (unit: mm)

500 or more 500 or more


500 or more

500 or more 500 or more

Indoor Indoor Indoor


unit unit unit

Table 3-3.7: Indoor branch joint dimensions (unit: mm)


Model (ID:15.9) Gas side joints Liquid side joints

OD:19.1

ID:19.1
ID:12.7

OD:9.5

ID:9.5
OD:19.1

ID:6.4

OD:12.7
ID:19.1

ID:15.9

ID:9.5
TRDK056HP

ID:6.4
ID:12.7

ID:9.5
OD:9.5
OD:19.1
(ID:15.9)

Part 3 - System Design and Installation


(ID:19.1)

OD:22.2

ID:22.2
ID:15.9

OD:12.7

ID:12.7
OD:22.2

ID:9.5
ID:6.4

OD:12.7
ID:22.2

ID:12.7
ID:25.4

ID:9.5
TRDK112HP

ID:6.4

ID:9.5

OD:12.7
ID:12.7

OD:22.2
(ID:19.1)
ID:15.9

OD:28.6

OD:15.9
(ID:12.7)
ID:28.6
ID:22.2
ID:19.1

ID:15.9
ID:9.5
OD:28.6

OD:15.9
ID:28.6
ID:31.8

ID:19.1
ID:15.9
TRDK225HP
ID:6.4

ID:9.5

(ID:12.7)
ID:15.9

OD:15.9
ID:19.1
ID:22.2

OD:28.6

3.8 Refrigerant Leakage Precautions


R410A refrigerant is not flammable in air at temperatures up to 100°C at atmospheric pressure and is generally considered
a safe substance to use in air conditioning systems. Nevertheless, precautions should be taken to avoid danger to life in
the unlikely event of a major refrigerant leakage. Precautions should be taken in accordance with all applicable legislation.
Where no applicable legislation exists, the following may be used as a guide:
 Air conditioned rooms should be large enough that if leakage of all the refrigerant in the system occurs, the
concentration of the refrigerant in the room does not reach a level dangerous to health.
 A critical concentration (at which point R410A becomes dangerous to human health) of 0.3 kg/m3 can be used.
 The potential concentration of refrigerant in a room following a leak can be calculated as follows:
 Calculate the total amount in of refrigerant in the system (“A”) as the nameplate charge (the charge in the system
when delivered from the factory) plus the additional charge added as per Part 3, 7.1 “Calculating Additional
Refrigerant Charge”.
 Calculate the total volume (“B”) of the smallest room into which refrigerant could potentially leak.
 Calculate the potential refrigerant concentration as A divided by B.
 If A/B is not less than 0.3 kg/m3, countermeasures such installing mechanical ventilators (either ventilating
regularly or controlled by refrigerant leakage detectors) should be taken.

87
Mini TVR Individual 60Hz
 Since R410A is heavier than air, particular consideration should be given to leak scenarios in basement rooms.

Figure 3-3.9: Potential refrigerant leak scenario

Outdoor unit

Indoor unit

Room full of leaking refrigerant


(All the refrigerant has leaked)
Mini TVR Individual Series Engineering Data Book

Figure 3-3.10: Mechanical ventilator controlled by refrigerant leak detector

Outside air Indoor unit

Leakage detector
connected to mechanical
ventilator

Air vent

88
-I Mini TVR Individual 60Hz
4 Refrigerant Piping Installation
4.1 Procedure and Principles
4.1.1 Installation procedure

Notes for installers 


Installation of the refrigerant piping system should proceed in the following order:

Pipe Pipe brazing Pipe Gastightness Joint


Vacuum drying
insulation and installation flushing test insulation

Note: Pipe flushing should be performed once the brazed connections have been completed with the exception of
the final connections to the indoor units. That is, flushing should be performed once the outdoor unit have been
connected but before the indoor units are connected.

Part 3 - System Design and Installation


4.1.2 Three principles for refrigerant piping

Reasons Measures

Particles such as oxide produced  Seal piping during storage1


CLEAN during brazing and/or building dust  Flow nitrogen during brazing2
can lead to compressor malfunction  Pipe flushing3

Moisture can lead to ice formation or


oxidization of internal components  Pipe flushing3
DRY leading to abnormal operation or  Vacuum drying4
compressor damage

 Pipe manipulation5 and brazing2


Imperfect seals can lead to refrigerant
SEALED leakage
techniques
 Gas tightness test6

Notes:
1. See Part 3, 4.2.1 “Pipe delivery, storage and sealing”.
2. See Part 3, 4.5 “Brazing”.
3. See Part 3, 4.7 “Pipe Flushing”.
4. See Part 3, 4.9 “Vacuum Drying”.
5. See Part 3, 4.3 “Manipulating Copper Piping”.
6. See Part 3, 4.8 “Gastightness Test”.

89
Mini TVR Individual 60Hz
4.2 Storing Copper Piping
4.2.1 Pipe delivery, storage and sealing

Notes for installers 


 Ensure that piping does not get bent or deformed during delivery or whilst stored.
 On construction sites store piping in a designated location.
 To prevent dust or moisture entering, piping should be kept sealed whilst in storage and until it is about to be
connected. If piping is to be used soon, seal the openings with plugs or adhesive tape. If piping is to be stored
for a long time, charge the piping with nitrogen at 0.2-0.5MPa and seal the openings by brazing.
 Storing piping directly on the ground risks dust or water ingress. Wooden supports can be used to raise piping
off the ground.
 During installation, ensure that piping to be inserted through a hole in a wall is sealed to ensure dust and/or
fragments of wall do not enter.
 Be sure to seal piping being installed outdoors (especially if being installed vertically) to prevent rain entering.
Mini TVR Individual Series Engineering Data Book

4.3 Manipulating Copper Piping


4.3.1 De-oiling

Notes for installers 


 Lubrication oil used during some copper pipe manufacturing processes can cause deposits to form in R410A
refrigerant systems, causing system errors. Oil-free copper piping should therefore be selected. If ordinary (oily)
copper piping is used, it must be cleaned with gauze dipped in tetrachloroethylene solution prior to installation.

Caution
 Never use carbon tetrachloride (CCl4) for pipe cleansing or flushing, as doing so will seriously damage the
system.

4.3.2 Cutting copper piping and removing burrs

Notes for installers 


 Use a pipe cutter rather than a saw or cutting machine to cut piping. Rotate the piping evenly and slowly,
applying even force to ensure that the piping does not become deformed during cutting. Using a saw or cutting
machine to cut piping runs the risk of copper shavings entering the piping. Copper shavings are difficult to
remove and pose a serious risk to the system if they enter the compressor or block the throttling unit.
 After cutting using a pipe cutter, use a reamer/scraper to remove any burrs that have formed at the opening,
keeping the opening of the piping downwards to avoid copper shavings from entering the piping.
 Remove burrs carefully to avoid scratches, which may prevent a proper seal being formed and lead to
refrigerant leakage.

90
-I Mini TVR Individual 60Hz
4.3.3 Expanding copper piping ends

Notes for installers 


 Ends of copper piping can be expanded so that another length of piping can be inserted and the joint brazed.
 Insert the expanding head of the pipe expander into the pipe. After completing pipe expansion, rotate the
copper pipe a few degrees to rectify the straight line mark left by the expanding head.

Caution
 Ensure that the expanded section of piping is smooth and even. Remove any burrs that remain after cutting.
Figure 3-4.1: Expanding copper piping ends

Part 3 - System Design and Installation


4.3.4 Flared joints
Flared joints should be used where a screw thread connection is required.

Notes for installers 


 Before flaring 1/2H (half hard) piping, anneal the end of the pipe to be flared.
 Remember to place the flare nut on the piping before flaring.
 Ensure the flared opening is not cracked, deformed or scratched, otherwise it will not form a good seal and
refrigerant leakage may occur.
 The diameter of the flared opening should be within the ranges specified in Table 3-4.1. Refer to Figure 3-4.2.

Table 3-4.1: Flared opening size ranges Figure 3-4.2: Flared opening
Pipe (mm) Flared opening diameter (A) (mm)
Ф6.35 8.7 - 9.1
Ф9.53 12.8 - 13.2
Ф12.7 16.2 - 16.6
Ф15.9 19.3 - 19.7

Ф19.1 23.6 - 24.0

 When connecting a flared joint, apply some compressor oil to the inner and outer surfaces of the flared opening
to facilitate the connection and rotation of the flare nut, ensure firm connection between the sealing surface
and the bearing surface, and avoid the pipe becoming deformed.

91
Mini TVR Individual 60Hz
4.3.5 Bending piping
Bending copper piping reduces the number of brazed joints required and can improve quality and save material.

Notes for installers 


Piping bending methods
 Hand bending is suitable for thin copper piping (Ф6. 35mm - Ф12. 7mm).
 Mechanical bending (using a bending spring, manual bending machine or powered bending machine) is suitable
for a wide range of diameters (Ф6. 35mm - Ф54.0mm).

Caution
 When using a spring bender, ensure that the bender is clean Figure 3-4.3: Pipe bending in excess of 90°
before inserting it in the piping.
 After bending a copper pipe, ensure that there are no wrinkles
or deformation on either side of the pipe.
Mini TVR Individual Series Engineering Data Book

 Ensure that bend angles do not exceed 90°, otherwise wrinkles


may appear on the inner side of the pipe, and the pipe may
buckle or crack. Refer to Figure 3-4.3.
 Do not use a pipe that has buckled during the bending process;
ensure that the cross section at the bend is greater than 2/3 of
the original area.

4.4 Refrigerant Piping Supports


Table 3-4.2: Refrigerant piping support spacings
When the air conditioner is running, the refrigerant piping will deform
(shrink, expand, droop). To avoid damage to piping, hangers or Interval between support points (m)
Pipe (mm)
supports should be spaced as per the criteria in the Table 3-4.2. In Horizontal Piping Vertical Piping

general, the gas and liquid pipes should be suspended in parallel and < Ф20 1 1.5

the interval between support points should be selected according to Ф20 – Ф40 1.5 2

the diameter of the gas pipe. > Ф40 2 2.5

Suitable insulation should be provided between the piping and the supports. If wooden dowels or blocks are to be used,
use wood that has undergone preservative treatment.

Changes in refrigerant flow direction and refrigerant temperature result in movement, expansion and shrinkage of the
refrigerant piping. Piping should therefore not be fixed too tightly, otherwise stress concentrations may occur in the piping,
with the potential for rupturing.

92
-I Mini TVR Individual 60Hz
4.5 Brazing
Care must be taken to prevent oxide forming on the inside of copper piping during brazing. The presence of oxide in a
refrigerant system adversely affects the operation of valves and compressors, potentially leading to low efficiency or even
compressor failure. To prevent oxidation, during brazing nitrogen should be flowed through the refrigerant piping.

Notes for installers 


Warning
 Never flow oxygen through piping as doing so aids oxidation and could easily lead to explosion and as such is
extremely dangerous.
 Take appropriate safety precautions such as having a fire extinguisher to hand whilst brazing.

Flowing nitrogen during brazing


 Use a pressure reducing valve to flow nitrogen through copper piping at 0.02-0.03MPa during brazing.
 Start the flow before brazing starts and ensure that the nitrogen continuously passes through the section being
brazed until the brazing is complete and the copper has cooled down completely.

Part 3 - System Design and Installation


Figure 3-4.4: Flowing nitrogen through piping during brazing

Legend
1 Copper piping
2 Section being brazed

3 Nitrogen connection

4 Hand valve
5 Pressure-reducing valve
6 Nitrogen

 When joining a shorter section of piping to a longer section, flow nitrogen from the shorter side to allow better
displacement of air with nitrogen.
 If the distance from the point where nitrogen enters the piping to the joint to be brazed is long, ensure that the
nitrogen is flowed for sufficient time to discharge all the air from the section to be brazed before commencing
brazing.

Figure 3-4.5: Flowing nitrogen from shorter side during brazing

Box continued on next page …

93
Mini TVR Individual 60Hz
… box continued from previous page

Piping orientation during brazing


Brazing should be conducted downwards or horizontally to avoid filler leakage.
Figure 3-4.6: Piping orientation during brazing

Brazing
Brazing

D
A
Brazing
Mini TVR Individual Series Engineering Data Book

Piping overlap during brazing


Table 3-4.3 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints
on piping of different diameters. Refer also to Figure 3-4.7.

Figure 3-4.7: Piping overlap and gap for brazed joints


B
Legend
A
D

A Inner diameter of larger pipe

D Outer diameter of smaller pipe


Brazing
B Inlaid depth (overlap)

1
Table 3-4.3: Piping overlap and gap for brazed joints
Minimum
Permissible A – D
D (mm) permissible B
(mm)
(mm)
5<D<8 6
0.05 - 0.21
8 < D < 12 7
12 < D < 16 8
0.05 - 0.27
16 < D < 25 10
25 < D < 35 12
0.05 - 0.35
35 < D < 45 14
Notes:
1. A, B, D refer to the dimensions shown in Figure 3-4.7.

Filler
 Use a copper/phosphorus brazing alloy (BCuP) filler that does not require flux.
 Do not use flux. Flux can cause corrosion of piping and can affect the performance of compressor oil.
 Do not use anti-oxidants when brazing. Residue can clog piping and damage components.

94
-I Mini TVR Individual 60Hz
4.6 Branch Joints

Notes for installers 


 Use U-shaped branch joints as specified on the Figure 3-4.8: Branch joint orientation
construction drawings – do not replace U-shaped branch
joints with tee joints.
 Indoor branch joints may be installed either horizontally or
vertically. Horizontal branch joints must be installed at an
angle to the horizontal not exceeding 10° in order to avoid
uneven distribution of refrigerant and possible
malfunction. Refer to Figure 3-4.8.
 To ensure even distribution of refrigerant, a limitation is
placed on how close branch joints may be installed to
bends, other branch joints and the straight sections of
piping leading to indoor units. Refer to Part 3, 3.7 “Branch
Joints”.

Part 3 - System Design and Installation


4.7 Pipe Flushing
4.7.1 Purpose
To remove dust, other particles and moisture, which could cause compressor malfunction if not flushed out before the
system is run, the refrigerant piping should be flushed using nitrogen. As described in Part 3, 4.1.1 “Installation procedure”,
pipe flushing should be performed once the piping connections have been completed with the exception of the final
connections to the indoor units. That is, flushing should be performed once the outdoor units have been connected but
before the indoor units are connected.

95
Mini TVR Individual 60Hz
4.7.2 Procedure

Notes for installers 


Warning
Only use nitrogen for flushing. Using carbon dioxide risks leaving condensation in the piping. Oxygen, air, refrigerant,
flammable gases and toxic gases must not be used for flushing. Use of such gases may result in fire or explosion.

Procedure
The liquid and gas sides can be flushed simultaneously; alternatively, one side can be flushed first and then Steps 1
to 8 repeated, for the other side. The flushing procedure is as follows:
1. Cover the inlets and outlets of the indoor units to prevent dirt getting blown in during pipe flushing. (Pipe
flushing should be carried out before connecting the indoor units to the piping system.)
2. Attach a pressure reducing valve to a nitrogen cylinder.
3. Connect the pressure reducing valve outlet to the inlet on the liquid (or gas) side of the outdoor unit.
Mini TVR Individual Series Engineering Data Book

4. Use blind plugs to block all liquid (gas) side openings, except for the opening at the indoor unit which is furthest
from the outdoor unit (“Indoor unit A” in Figure 3-4.9).
5. Start to open the nitrogen cylinder valve and gradually increase the pressure to 0.5MPa.
6. Allow time for nitrogen to flow as far as the opening at indoor unit A.
7. Flush the first opening:
a) Using suitable material, such as a bag or cloth, press firmly against the opening at indoor unit A.
b) When the pressure becomes too high to block with your hand, suddenly remove your hand allowing gas to
rush out.
c) Repeatedly flush in this manner until no further dirt or moisture is emitted from the piping. Use a clean
cloth to check for dirt or moisture being emitted. Seal the opening once it has been flushed.
8. Flush the other openings in the same manner, working in sequence from indoor unit A towards the outdoor
unit. Refer to Figure 3-4.10.
9. Once flushing is complete, seal all openings to prevent dust and moisture from entering.
Figure 3-4.9: Pipe flushing using nitrogen
nitrogen gas cylinder

liquid pipe
gas pipe
Outdoor
unit

Indoor Indoor
unit A unit B

1
Figure 3-4.10: Pipe flushing sequence

⑥ ⑤ ④ ③ ①
Notes:
1. 1-2-3-4-5-6 working towards the outdoor unit.

96
-I Mini TVR Individual 60Hz
4.8 Gastightness Test
4.8.1 Purpose
To prevent faults caused by refrigerant leakage, a gastightness test should be performed before system commissioning..

4.8.2 Procedure

Notes for installers 


Warning
Only dry nitrogen should be used for gastightness testing. Oxygen, air, flammable gases and toxic gases must not be
used for gastightness testing. Use of such gases may result in fire or explosion.

Procedure
The gastightness test procedure is as follows:
Step 1
 Once the piping system is complete and the indoor and outdoor units have been connected, vacuum the piping
to -0.1MPa.

Part 3 - System Design and Installation


Step 2
 Charge the indoor piping with nitrogen at 0.3MPa through the needle valves on the liquid and gas stop valves
and leave for at least 3 minutes (do not open the liquid or gas stop valves). Observe the pressure gauge to check
for large leakages. If there is a large leakage, the pressure gauge will drop quickly.
 If there are no large leakages, charge the piping with nitrogen at 1.5MPa and leave for at least 3 minutes.
Observe the pressure gauge to check for small leakages. If there is a small leakage, the pressure gauge will drop
distinctly.
 If there are no small leakages, charge the piping with nitrogen at 4.2MPa and leave for at least 24 hours to check
for micro leakages. Micro leakages are difficult to detect. To check for micro leakages, allow for any change in
ambient temperature over the test period by adjusting the reference pressure by 0.01MPa per 1°C of
temperature difference. Adjusted reference pressure = Pressure at pressurization + (temperature at observation
– temperature at pressurization) x 0.01MPa. Compare the observed pressure with the adjusted reference
pressure. If they are the same, the piping has passed the gastightness test. If the observed pressure is lower
than the adjusted reference pressure, the piping has a micro leakage.
 If the leakage is detected, refer to Part 3, 4.8.3 “Leak detection”. Once the leak has been found and fixed, the
gastightness test should be repeated.
Step 3
 If not continuing straight to vacuum drying (see Part 3, 4.9 “Vacuum Drying”) once the gastightness test is
complete, reduce the system pressure to 0.5-0.8MPa and leave the system pressurized until ready to carry out
the vacuum drying procedure.

Figure 3-4.11: Gastightness test

97
Mini TVR Individual 60Hz
4.8.3 Leak detection

Notes for installers 


The general methods for identifying the source of a leak are as follows:
1. Audio detection: relatively large leaks are audible.
2. Touch detection: place your hand at joints to feel for escaping gas.
3. Soapy water detection: small leaks can be detected by the formation of bubbles when soapy water is applied to
a joint.
4. Refrigerant leak detection: for leaks that are difficult to detect, refrigerant leak detection may be used as follows:
a) Pressurize the piping with nitrogen at 0.3MPa.
b) Add refrigerant into the piping until the pressure reaches 0.5MPa.
c) Use a halogen refrigerant detector to find the leak.
d) If the leak source cannot be found, continuing charging with refrigerant to a pressure of 4MPa and then
search again.
Mini TVR Individual Series Engineering Data Book

4.9 Vacuum Drying


4.9.1 Purpose
Vacuum drying should be performed in order to remove moisture and non-condensable gases from the system. Removing
moisture prevents ice formation and oxidization of copper piping or other internal components. The presence of ice
particles in the system would cause abnormal operation, whilst particles of oxidized copper can cause compressor damage.
The presence of non-condensable gases in the system would lead to pressure fluctuations and poor heat exchange
performance.

Vacuum drying also provides additional leak detection (in addition to the gas tightness test).

98
-I Mini TVR Individual 60Hz
4.9.2 Procedure

Notes for installers 


During vacuum drying, a vacuum pump is used to lower the pressure in the piping to the extent that any moisture
present evaporates. At 5mmHg (755mmHg below typical atmospheric pressure) the boiling point of water is 0°C.
Therefore a vacuum pump capable of maintaining a pressure of -756mmHg or lower should be used. Using a vacuum
pump with a discharge in excess of 4L/s and a precision level of 0.02mmHg is recommended.

Caution
 Before performing vacuum drying, make sure that all the outdoor unit stop valves are firmly closed.
 Once the vacuum drying is complete and the vacuum pump is stopped, the low pressure in the piping could
suck vacuum pump lubricant into the air conditioning system. The same could happen if the vacuum pump
stops unexpectedly during the vacuum drying procedure. Mixing of pump lubricant with compressor oil could
cause compressor malfunction and a one-way valve should therefore be used to prevent vacuum pump
lubricant seeping into the piping system.

Procedure

Part 3 - System Design and Installation


The vacuum drying procedure is as follows:
Step 1
 Connect the blue (low pressure side) hose of a pressure gauge to the outdoor unit gas pipe stop valve, the red
(high pressure side) hose to the outdoor unit liquid pipe stop valve and the yellow hose to the vacuum pump.
Step 2
 Start the vacuum pump and then open the pressure gauge valves to start vacuum the system.
 After 30 minutes, close the pressure gauge valves.
 After a further 5 to 10 minutes check the pressure gauge. If the gauge has returned to zero, check for leakages in
the refrigerant piping.
Step 3
 Re-open the pressure gauge valves and continue vacuum drying for at least 2 hours and until a pressure
difference of 756mmHg or more has been achieved. Once the pressure difference of at least 756mmHg has
been achieved, continue vacuum drying for 2 hours.
Step 4
 Close the pressure gauge valves and then stop the vacuum pump.
 After 1 hour, check the pressure gauge. If the pressure in the piping has not increased, the procedure is finished.
If the pressure has increased, check for leakages.
 After vacuum drying, keep the blue and red hoses connected to the pressure gauge and to the outdoor unit
stop valves, in preparation for refrigerant charging (see Part 3, 7 “Charging Refrigerant”).
Figure 3-4.12: Vacuum drying

Pressure
gauge

Yellow hose Outdoor unit


1
2

R410A
refrigerant tank
Pressure gauge
Weighing scale

Blue hose Red hose Field piping


1 Gas pipe stop valve
Stop valve
service port 2 Liquid pipe stop valve

99
Mini TVR Individual 60Hz
5 Drain Piping
5.1 Design Considerations
Drain piping design should take account of the following considerations:
 Indoor unit condensate drain piping needs to be of sufficient diameter to carry the volume of condensate produced
at the indoor units and installed at a slope sufficient to allow drainage. Discharge as close as possible to the indoor
units is usually preferable.
 To prevent the drain piping becoming excessively long, consideration should be given to installing multiple drain
piping systems, with each system having its own drainage point and providing drainage for a subset of the overall set
of indoor units.
 The routing of drain piping should take into consideration the need to maintain sufficient slope for drainage whilst
avoiding obstacles such as beams and ducting. The drain piping slope should be at least 1:100 away from indoor units.
Refer to Figure 3-5.1.
Figure 3-5.1: Drain piping minimum slope requirement
Mini TVR Individual Series Engineering Data Book

( 1cm/1m)
above 1/100

 To avoid backflow and other potential complications, two horizontal drain pipes should not meet at the same level.
Refer to the Figure 3-5.2 for suitable connection arrangements. Such arrangements also allow the slope of the two
horizontal pipes to be selected independently.
Figure 3-5.2: Drain piping joints – correct and incorrect configurations
Drain pipe
Drain pipe
Drain pipe Tee joint

Tee joint
Tee joint

 Branch drain piping should join main drain piping from the Figure 3-5.3: Branch drain piping joining main drain piping
top, as shown in Figure 3-5.3. 45°
 Recommended support/hanger spacing is 0.8 – 1.0m for
horizontal piping and 1.5 – 2.0m for vertical piping. Each
vertical section should be fitted with at least two supports.
For horizontal piping, spacing greater than those
recommended leads to sagging and deformation of the pipe
profile at the supports which impedes water flow and should
therefore be avoided.
 Air vents should be fitted at the highest point of each drain Figure 3-5.4: Effect of insufficient drain piping support
piping system to ensure that condensation is discharged
smoothly. U-bends or elbow joints should be used such that gap too big

the vents face downwards, to prevent dust entering the gas bag

piping. Refer to Figure 3-5.5. Air vents should not be


installed too close to indoor unit lift pumps.
100
-I Mini TVR Individual 60Hz
Figure 3-5.5: Drain piping air vents

 Air conditioner drain piping should be installed separately from waste, rainwater and other drain piping and should
not come into direct contact with the ground.
 Drain piping diameter should be not less than the indoor units’ drain piping connection.
 To allow inspection and maintenance, the piping clamps shipped with units should be used to attach drain piping to
indoor units – adhesive should not be used.
 Thermal insulation should be added to drain piping to prevent condensation forming. Thermal insulation should
extend all the way to the connection with the indoor unit.
 Units with drain pumps should have separate drain piping systems from systems that use natural drainage.

Part 3 - System Design and Installation


5.2 Water Traps
For indoor units with a high negative pressure differential at the outlet of the Figure 3-5.6: Drain piping water traps
drainage pan, a trap should be fitted to the drain piping to prevent poor
indoor unit
drainage and/or water being blown back into the drainage pan. Traps should
H
be arranged as in Figure 3-5.6. The vertical separation H should be in excess of plug
H/2
50mm. A plug may be fitted to allow cleaning or inspection.

5.3 Selecting Piping Diameters


Select branch drainage piping (the drain piping connection to each unit) diameters according to indoor unit flow volume
and select main drainage piping diameters according to the combined flow volume of the upstream indoor units. Use a
design assumption of 2 liters of condensate per horsepower per hour. For example, the combined flow volume of three
2HP units and two 1.5HP units would be calculated as follows:

Combined flow volume = 3 x 2 L/HP/h × 2HP = 18 L/h


+ 2 x 2 L/HP/h × 1.5HP

Tables 3-5.1 and 3-5.2 specify the required piping diameters for horizontal and vertical branch piping and for main piping.
Note that main piping should use PVC40 or larger.

Table 3-5.1: Horizontal drain piping diameters

Nominal Capacity (L/h)


PVC piping Remarks
diameter (mm) Slope 1:50 Slope 1:100
PVC25 25 39 27
Branch piping only
PVC32 32 70 50
PVC40 40 125 88
PVC50 50 247 175 Branch or main piping
PVC63 63 473 334

101
Mini TVR Individual 60Hz
Table 3-5.2: Vertical drain piping diameters
Nominal
PVC piping Capacity (L/h) Remarks
diameter (mm)
PVC25 25 220
Branch piping only
PVC32 32 410
PVC40 40 730
PVC50 50 1440
PVC63 63 2760 Branch or main piping
PVC75 75 5710
PVC90 90 8280

5.4 Drain Piping for Units with Lift Pumps


Drain piping for units with lift pumps should take account of the following additional considerations:
 A downward sloping section should immediately follow the vertically rising section adjacent to the unit, otherwise a
water pump error will occur. Refer to Figure 3-5.7.
 Air vents should not be installed on vertically rising sections of drain piping, otherwise water may be discharged
through the air vent or water flow may be impeded.
Mini TVR Individual Series Engineering Data Book

Figure 3-5.7: Downward sloping section of drain piping

5.5 Drain Piping Installation

Notes for installers 


Installation of the drain piping should proceed in the following order:
Drain piping Watertightness
Indoor unit installation Drain piping insulation
installation test

Caution
 Ensure that all joints are firm and once the drain piping is all connected conduct a watertightness test and
water flow test.
 Do not connect air conditioner drain piping to waste, rainwater or other drain piping and do not let air
conditioner drain piping come into direct contact with the ground.
 For units with drain pumps, test that the drain pump functions properly by adding water to the unit’s drainage
pan and running the unit. To allow inspection and maintenance, the pipe clamps shipped with units should be
used to attach drain piping to indoor units – adhesive should not be used.

102
-I Mini TVR Individual 60Hz
5.6 Watertightness Test and Water Flow Test
Once installation of a drainage piping system is compete, watertightness and water flow tests should be performed.

Notes for installers 


Watertightness test
 Fill the piping with water and test for leakages over a 24-hour period.

Water flow test (natural drainage test)


 Slowly fill the drainage pan of each indoor unit with at least 600ml of water through the inspection port and
check that the water is discharged through the outlet of the drain piping.

Caution
 The drain plug in the drainage pan is for removing accumulated water prior to performing indoor unit
maintenance. During normal operation, the drain should be plugged to prevent leakage.

Part 3 - System Design and Installation

103
Mini TVR Individual 60Hz
6 Insulation
6.1 Refrigerant Piping Insulation
6.1.1 Purpose
During operation, the temperature of the refrigerant piping varies. Insulation is required to ensure unit performance and
compressor lifespan. During cooling, the gas pipe temperature can be very low. Insulation prevents condensation forming
on the piping. During heating, the gas pipe temperature can rise to as high as 100°C. Insulation serves as necessary
protection from burns.

6.1.2 Selecting insulation materials


Refrigerant piping insulation should be closed-cell foam of B1 fire resistance rating that can withstand a constant
temperature of over 120°C and that complies with all applicable legislation.

6.1.3 Thickness of insulation


Minimum thicknesses for refrigerant piping insulation are specified in Table 3-6.1. In hot, humid environments, the
Mini TVR Individual Series Engineering Data Book

thickness of insulation should be increased over and above the specifications in Table 3-6.1.

Table 3-6.1: Refrigerant piping insulation thickness


Pipe outer diameter Minimum insulation thickness (mm) Minimum insulation thickness (mm)
(mm) Humidity < 80%RH Humidity ≥ 80%RH
Ф6.35
Ф9.53
Ф12.7
Ф15.9
Ф19.1
15 20
Ф22.2
Ф25.4
Ф28.6
Ф31.8
Ф38.1
Ф41.3
Ф44.5 20 25
Ф54.0

6.1.4 Installation of piping insulation


With the exception of joint insulation, insulation should be applied to piping before fixing the piping in place. Insulation at
joints in refrigerant piping should be applied after the gas tightness test has been completed.

Notes for installers 


 Installation of insulation should be carried out in a manner suited to the type of insulation material being used.
 Ensure there are no gaps at the joints between sections of insulation.
 Do not apply tape too tightly as doing so may shrink insulation, reducing its insulating properties leading to
condensation and loss of efficiency.
 Insulate gas and liquid pipes separately, otherwise heat exchange between the two sides will greatly impact
efficiency.
 Do not bind the separately insulated gas and liquid pipes together too tightly as doing so can damage the joints
between sections of insulation.

6.1.5 Installation of joint insulation


Insulation at joints in the refrigerant piping should be installed after the gas tightness test has been successfully
completed. The procedure at each joint is as follows:
1. Cut a section of insulation 50 to 100mm longer than the gap to be filled. Ensure that the cross-sectional and
104
-I Mini TVR Individual 60Hz
longitudinal openings are all cut evenly.
2. Embed the section into the gap ensuring that the ends abut tightly to the sections of insulation either side of the gap.
3. Glue the longitudinal cut and the joints with the sections of insulation either side of the gap.
4. Seal the seams with tape.

Figure 3-6.1: Installation of joint insulation (unit: mm)


straight-through joint
300

Copper pipe
Insulation
Insulation material
material
400

6.2 Drain Piping Insulation


 Use rubber/plastic insulating tube with a B1 fire resistance rating.

Part 3 - System Design and Installation


 The insulation should typically be in excess of 10mm thick.
 For drain piping installed inside a wall, insulation is not required.
 Use suitable adhesive to seal seams and joints in the insulation and then bind with cloth reinforced tape of width not
less than 50mm. Ensure tape is fixed firmly to avoid condensation.
 Ensure the drain piping insulation adjacent to the indoor unit drainage water outlet is fixed to the unit itself using
adhesive, to prevent condensation and dripping.

6.3 Ducting Insulation


 Suitable insulation should be added to ducting in according with all applicable legislation.

105
Mini TVR Individual 60Hz
7 Charging Refrigerant
7.1 Calculating Additional Refrigerant Charge
The additional refrigerant charge required depends on the lengths and diameters of the outdoor and indoor liquid pipes.
Table 3-7.1 shows the additional refrigerant charge required per meter of equivalent pipe length for different diameters of
pipe. The total additional refrigerant charge is obtained by summing the additional charge requirements for each of the
outdoor and indoor liquid pipes, as in the following formula, where L1 to L8 represent the equivalent lengths of the pipes of
different diameters. Assume 0.5m for the equivalent pipe length of each branch joint.

Additional refrigerant charge R (kg) = L1 (Φ6.35) × 0.022 Table 3-7.1: Additional refrigerant charge
+ L2 (Φ9.53) × 0.057 Additional refrigerant charge per
Liquid side
meter of equivalent length of
+ L3 (Φ12.7) × 0.110 piping (mm)
piping (kg)
+ L4 (Φ15.9) × 0.170 Φ6.35 0.022
Φ9.53 0.057
+ L5 (Φ19.1) × 0.260
Φ12.7 0.110
Mini TVR Individual Series Engineering Data Book

+ L6 (Φ22.2) × 0.360 Φ15.9 0.170


Φ19.1 0.260
Φ22.2 0.360

7.2 Adding Refrigerant

Notes for installers 


Caution
 Only charge refrigerant after performing a gas tightness test and vacuum drying.
 Never charge more refrigerant than required as doing so can lead to liquid hammering.
 Only use refrigerant R410A - charging with an unsuitable substance may cause explosions or accidents.
 Use tools and equipment designed for use with R410A to ensure required pressure resistance and to prevent
foreign materials from entering the system.
 Refrigerant must be treated in accordance with applicable legislation.
 Always use protective gloves and protect your eyes when charging refrigerant.
 Open refrigerant containers slowly.

Procedure
The procedure for adding refrigerant is as follows:
Step 1
 Calculate additional refrigerant charge R (kg) (see Part 3, 7.1 “Calculating Additional Refrigerant Charge”)

Step 2
 Place a tank of R410A refrigerant on a weighing scale. Turn the tank upside down to ensure refrigerant is
charged in a liquid state. (R410A is a blend of two different chemicals compounds. Charging gaseous R410A into
the system could mean that the refrigerant charged is not of the correct composition).
 After vacuum drying (see Part 3, 4.9 “Vacuum Drying”), the blue and red pressure gauge hoses should still be
connected to the pressure gauge and to the master unit stop valves.
 Connect the yellow hose from the pressure gauge to the R410A refrigerant tank.

Box continued on next page …

106
-I Mini TVR Individual 60Hz
… box continued from previous page

Step 3
· Open the valve where the yellow hose meets the pressure gauge, and open the refrigerant tank slightly to let the
refrigerant eliminate the air. Caution: open the tank slowly to avoid freezing your hand.
· Set the weighing scale to zero.

Step 4
· Open the three valves on the pressure gauge to begin charging refrigerant.
· When the amount charged reaches R (kg), close the three valves. If the amount charged has not reached R (kg)
but no additional refrigerant can be charged, close the three valves on the pressure gauge, run the outdoor unit
in cooling mode, and then open the yellow and blue valves. Continue charging until the full R (kg) of refrigerant
has been charged, then close the yellow and blue valves. Note: Before running the system, be sure to complete
all the pre-commissioning checks as listed in Part 3, 10.3 “Pre-commissioning Checks” and be sure to open all
stop valves as running the system with the stop valves closed would damage the compressor.

Figure 3-7.1: Charging refrigerant

Part 3 - System Design and Installation


Pressure
gauge

Yellow hose Outdoor unit


1
2

R410A
refrigerant tank

Weighing scale

Blue hose Red hose Field piping Pressure gauge


1 Gas pipe stop valve
Stop valve
service port 2 Liquid pipe stop valve

107
Mini TVR Individual 60Hz
8 Electrical Wiring
8.1 General

Notes for installers 


Caution
 All installation and wiring must be carried out by competent and suitably qualified, certified and accredited
professionals and in accordance with all applicable legislation.
 Electrical systems should be grounded in accordance with all applicable legislation.
 Overcurrent circuit breakers and residual-current circuit breakers (ground fault circuit interrupters) should be
used in accordance with all applicable legislation.
 Wiring patterns shown in this data book are general connection guides only and are not intended for, or to
include all details for, any specific installation.
 The refrigerant piping, power wiring and communication wiring are typically run in parallel. However the
Mini TVR Individual Series Engineering Data Book

communication wiring should not be bound together with the refrigerant piping or power wiring. To prevent
signal interference, the power wiring and communication wiring should not be run in the same conduit. If the
power supply is less than 10A, a separation of at least 300mm between power wiring and communication
wiring conduits should be maintained; if the power supply is in the range 10A to 50A then a separation of at
least 500mm should be maintained.

8.2 Power Supply Wiring


Power supply wiring design and installation should adhere to the following requirements:
 Separate power supplies should be provided for the indoor units and outdoor unit.
 Where five or more outdoor units are installed, additional residual current protection (leakage protection) should be
installed as shown in Figure 3-8.1.
 All the indoor units in a system (i.e. all the indoor units connected to the same outdoor unit) should be tied into the
same power circuit with the same power supply, overcurrent and residual current protection (leakage protection)
and manual switch, as shown in Figure 3-8.2. Do not install separate protectors or manual switches for each indoor
unit. Powering on and shutting down all indoor units in a system should be done simultaneously. The reason for this
is that if an indoor unit that is running were to suddenly power off whilst the other indoor units continued running,
the evaporator of the powered-off unit would freeze since refrigerant would continue flowing to that unit (its
expansion valve would still be open) but its fan would have stopped. The indoor units that remain running would not
get sufficient refrigerant so their performance would suffer. Additionally, liquid refrigerant returning directly to the
compressor from the powered-off unit would cause liquid hammering, potentially damaging the compressor.
 For outdoor unit power wire sizing and circuit breaker sizing, refer to Table 2-6.1 in Part 2, 6 “Electrical
Characteristics”.

108
-I Mini TVR Individual 60Hz
Figure 3-8.1: Outdoor unit power supply wiring

Figure 3-8.2: Indoor unit power supply wiring


Single-phase 220~ 50/60Hz
Leakage protector

Manual switch Branch box

1 2 3 4 5 6 7 8

Indoor unit

9 10 11 12 13 14 15 16

Part 3 - System Design and Installation


Notes for installers 
The 3-phase, 380-415V, 50 Hz power supply should be connected to the outdoor unit power supply terminals as
shown in Figure 3-8.3.
Figure 3-8.3: Outdoor unit 3-phase power supply terminals

8.3 Communication Wiring


Communication wiring design and installation should adhere to the following requirements:
2
 0.75mm three-core shielded cable should be used for communication wiring. Using other types of cable can lead to
interference and malfunction.
 Indoor communication wiring:
 The P Q E communication wires should be connected one unit after another in a daisy chain from the outdoor
unit to the final indoor unit. At the final indoor unit, a 120Ω resistor should be connected between the P and Q
terminals. After the final indoor unit, the communication wiring should NOT be continued back to the outdoor
unit – that is, do not attempt to form a closed loop.
 The P and Q communication wires should NOT be grounded.
 The shielding nets of the communication wires should be connected together and grounded. Grounding can be
achieved by connecting to the metal casing adjacent to the P Q E terminals of the outdoor unit electrical control
box.

109
Mini TVR Individual 60Hz

Notes for installers 


The communication wires should be connected to the outdoor unit terminals indicated in Figure 3-8.4 and Table
3-8.1.

Caution
 Communication wiring has polarity. Care should be taken to connect the poles correctly.

Figure 3-8.4: Outdoor unit communication terminals Table 3-8.1: Communication connections
Terminals Connection
K1 K2 E Connect to outdoor unit monitor
OAE Connect to digital energy meter
XYE Connect to indoor unit centralized controller
PQE Connect between indoor units and master outdoor unit
Mini TVR Individual Series Engineering Data Book

8.4 Wiring example


Figure 3-8.5: System power and communication wiring example

110
-I Mini TVR Individual 60Hz
9 Installation in Areas of High Salinity
9.1 Caution
Do not install outdoor units where they could be directly exposed to sea air. Corrosion, particularly on the condenser and
evaporator fins, could cause product malfunction or inefficient performance.

Outdoor units installed in seaside locations should be placed such as to avoid direct exposure to the sea air and additional
anticorrosion treatment options should be selected, otherwise the service life of the outdoor units will be seriously
affected.

Air conditioning installed in seaside locations should be run regularly as the running of the outdoor unit fans helps prevent
build-up of salt on the outdoor unit heat exchangers.

9.2 Placement and Installation


Outdoor units should be installed 300m or more from the sea. If possible, well-ventilated indoor locations should be
chosen. If it is necessary to install outdoor units outside, direct exposure to the sea air should be avoided. A canopy should
be added to shield the units from sea air and rain.

Part 3 - System Design and Installation


Ensure that base structures drain well so that outdoor unit footings do not become waterlogged. Check that outdoor unit
casing drainage holes are not blocked.

9.3 Inspection and maintenance


In addition to standard outdoor unit servicing and maintenance, the following additional inspections and maintenance
should be undertaken for outdoor units installed in seaside locations:
 A comprehensive post-installation inspection should check for any scratches or other damage to painted surfaces and
any damaged areas should be repainted/repaired immediately.
 The units should be regularly cleaned using (non-salty) water to remove any salt that has accumulated. Areas cleaned
should include the condenser, the refrigerant piping system, the outside surface of the unit casing and the outside
surface of the electric control box.
 Regular inspections should check for corrosion and if necessary corroded components should be replaced and/or
anti-corrosion treatments should be added.

111
Mini TVR Individual 60Hz
10 Commissioning
10.1 Outdoor Unit Capacity Settings
The capacity of each outdoor unit (on switch ENC2 on each outdoor unit’s main PCB) is factory-set and should not need
changing. Check that the capacity settings are correct. Refer to Table 3-10.1.

Table 3-10.1: Outdoor unit capacity settings


Switches Code Capacity
F 8HP
ENC2
0 9HP
4 14HP
5 16HP
Notes:7HP doesn’t have ENC2

10.2 Multi-system Projects


Mini TVR Individual Series Engineering Data Book

For projects with multiple refrigerant systems, each independent refrigeration system (i.e. each system of one outdoor
unit and its connected indoor units) should be given a test run independently, before the multiple systems that make up a
project are run simultaneously.

10.3 Pre-commissioning Checks


Before turning on the power to the indoor and outdoor units, ensure the following:
1. All indoor and outdoor refrigeration piping and communication wiring has been connected to the correct
refrigeration system and the system to which each indoor and outdoor unit belongs is clearly marked on each unit or
recorded in some other suitable place.
2. Pipe flushing, gas tightness testing and vacuum drying have been satisfactorily completed as per instructions.
3. All condensate drain piping is complete and a water tightness test has been satisfactorily completed.
4. All power and communication wiring is connected to the correct terminals on units and controllers. (Check that the
different phases of the 3-phase power supplies have been connected to the correct terminals).
5. No wiring has been connected in a short-circuit.
6. The power supplies to indoor and outdoor units have been checked and the power supply voltages are within ±10%
of the rated voltages for each product.
7. All control wiring is 0.75mm2 three-core shielded cable and the shielding has been grounded.
8. The outdoor unit’s capacity switch is set correctly (see Part 3, 10.1 “Outdoor Unit Capacity Settings”) and all other
indoor and outdoor unit field settings have been set as required.
9. The additional refrigerant charge has been added as per Part 3, 7 “Charging Refrigerant”. Note: In some
circumstances it may be necessary to run the system in cooling mode during the refrigerant charging procedure. In
such circumstances, points 1 to 8 above should be checked before running the system for the purpose of charging
refrigerant and the outdoor unit liquid and gas stop valves should be opened.

During commissioning, it is important that you:


 Keep a supply of R410A refrigerant at hand.
 Keep the system layout, system piping and control wiring diagrams at hand.

10.4 Commissioning Trial Runs


10.4.1 Commissioning test run of single refrigerant system
Once all the pre-commissioning checks in Part 3, 10.3 “Pre-commissioning Checks” have been completed, a test run should
be performed as described below and a Mini TVR Individual Series System Commissioning Report (see Part 3, 11
“Appendix to Part 3 – System Commissioning Report”) should be completed as a record of the operating status of the
system during commissioning.

112
-I Mini TVR Individual 60Hz
Note: When running the system for commissioning test runs, if the combination ratio is 100% or less, run all the indoor
units and if the combination ratio is more than 100%, run indoor units with total capacity equal to the capacity of the
outdoor unit.

The test run procedure is as follows:


1. Open the outdoor unit liquid and gas stop valves.
2. Turn on the power to the outdoor unit.
3. If manual addressing is being used, set the addresses of each indoor unit.
4. Leave the power on for a minimum of 12 hours prior to running the system to ensure that the crankcase heaters have
heated the compressor oil sufficiently.
5. Run the system:
a) Run the system in cooling mode with the following settings: temperature 17°C; fan speed high.
b) After one hour, complete Sheet A of the system commissioning report then check the system parameters using
the CHECK button on the outdoor unit’s main PCB and complete the cooling mode columns of one Sheet D and
one Sheet E of the system commissioning report for the outdoor unit.
c) Run the system in heating mode with the following settings: temperature 30°C; fan speed high.
d) After one hour, complete Sheet B of the system commissioning report then check the system parameters using

Part 3 - System Design and Installation


the CHECK button on the outdoor unit’s main PCB and complete the heating mode columns of one Sheet D and
one Sheet E of the system commissioning report for the outdoor unit.
6. Finally, complete Sheet C of the system commissioning report.

10.4.2 Commissioning test run of multiple refrigerant systems


Once the commissioning test run of each refrigerant system has been satisfactorily completed as per Part 3, 10.4.1
“Commissioning test run of single refrigerant system”, run the multiple systems that make up a project simultaneously and
check for any abnormalities.

113
Mini TVR Individual 60Hz
11 Appendix to Part 3 – System Commissioning Report
A total of up to 4 report sheets should be completed for each system:
 One Sheet A, one Sheet B and one Sheet C per system.
 One Sheet D per outdoor unit.
Mini TVR Individual Series Engineering Data Book

114
-I Mini TVR Individual 60Hz
Mini TVR Individual Series System Commissioning Report – Sheet A
SYSTEM INFORMATION

Project name and location Customer company

System name Installation company

Commissioning date Agent company

Outdoor ambient temp. Commissioning engineer


Model Serial no. Power supply (V)
Outdoor unit information

OUTDOOR UNIT
Compressor suction pipe
Current (A)
temperature
System pressure at check
Within normal range?
port
INDOOR UNITS
(Sample of over 20% of the indoor units including the unit farthest from the outdoor unit)

Part 3 - System Design and Installation


Room Set temp. Inlet temp. Outlet temp. Drainage Abnormal noise/
Model Address
no. (°C) (°C) (°C) OK? vibration?
(After running in cooling mode for one hour)
COOLING MODE PARAMETER RECORD

115
Mini TVR Individual 60Hz
Mini TVR Individual Series System Commissioning Report – Sheet B
SYSTEM INFORMATION

Project name and location Customer company

System name Installation company

Commissioning date Agent company

Outdoor ambient temp. Commissioning engineer


Model Serial no. Power supply (V)
Outdoor unit information

OUTDOOR UNIT
Compressor suction pipe
Current (A)
temperature
System pressure at check
Mini TVR Individual Series Engineering Data Book

Within normal range?


port
INDOOR UNITS
(Sample of over 20% of the indoor units including the unit farthest from the outdoor unit)

Room Set temp. Inlet temp. Outlet temp. Drainage Abnormal noise/
Model Address
no. (°C) (°C) (°C) OK? vibration?
(After running in heating mode for one hour)
COOLING MODE PARAMETER RECORD

116
-I Mini TVR Individual 60Hz
Mini TVR Individual Series System Commissioning Report – Sheet C
Project name and location System name

RECORD OF ISSUES SEEN DURING COMMISSIONING


Serial no. of
No. Description of observed issue Suspected cause Troubleshooting undertaken
relevant unit

Part 3 - System Design and Installation


3

OUTDOOR UNIT FINAL CHECKLIST

SW2 system check


performed?

Any abnormal noise?

Any abnormal vibration?

Fan rotation normal?

Commissioning engineer Dealer Trane representative

Name:

Signature:

Date:

117
Mini TVR Individual 60Hz
Mini TVR Individual Series System Commissioning Report – Sheet D
Project name and location System name

Observed values
DSP1 Cooling Heating
Parameters displayed on DSP2 Remarks
content mode mode
0.-- Unit capacity (Hp) Actual value = value displayed

1.-- Setting number of indoor units

2.-- Operating mode Refer to Note 1

3.-- Fan speed index Refer to Note 2

4.-- Total capacity of outdoor unit

5.-- Total capacity requirement of indoor units

6.-- Main heat exchanger pipe (T3) temperature (°C) Actual value = value displayed
Mini TVR Individual Series Engineering Data Book

7.-- Outdoor ambient (T4) temperature (°C) Actual value = value displayed

8.-- Inverter compressor discharge temperature (°C) Actual value = value displayed

9.-- Invert module (TF) temperature (°C) Actual value = value displayed

10.-- Refrigerant cooling pipe (TL) temperature (°C) Actual value = value displayed

11.-- Compressor discharge pressure (MPa) Actual value = value displayed × 0.1

12.-- Discharge superheat degree (°C) Actual value = value displayed

13.-- EXVA position Actual value = value displayed × 8

14.-- Actual current (A) Actual value = value displayed

15.-- Inverter compressor current (A) Actual value = value displayed

16.-- Actual voltage (V) Actual value = value displayed

17.-- DC bus voltage (V) Actual value = value displayed

18.-- Indoor heat exchanger pipe (T2/T2B) temperature (°C) Actual value = value displayed

19.-- Priority mode Refer to Note 3


Number of indoor units currently in communication with outdoor
20.-- Actual value = value displayed
unit
21.-- Number of indoor units currently operating Actual value = value displayed
“nn“ is displayed if no error or protection
22.-- Most recent error or protection code
events have occurred since start-up
23.-- Software version

-- -- -- End

Notes:
1. Operating mode:
 0: off; 2: cooling; 3: heating; 4: forced cooling.
2. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 9 (fastest).
3. Priority mode:
 0: heating priority; 1: cooling priority; 2: first ON priority; 3: heating only; 4: cooling only; 5: test mode 1; 6: test mode 2.

118